Multi-tone Open-area Alarm Devices
Installation Guide
General
This guide describes the installation of the following products:
Part No
Product Name
Type
Colour
55000-278
Multi-tone Open-area Sounder
Indoor (Type A)
Red
55000-279
Multi-tone Open-area Sounder
Indoor (Type A)
White
55000-274
Multi-tone Weatherproof Open-area Sounder
Outdoor (Type B)
Red
55000-275
Multi-tone Weatherproof Open-area Sounder
Outdoor (Type B)
White
55000-293
Multi-tone Open-area Sounder with Visual Indicator and Isolator*
Indoor (Type A)
Red
55000-294
Multi-tone Open-area Sounder with Visual Indicator and Isolator*
Indoor (Type A)
White
55000-291
Multi-tone Open-area Sounder with Visual Indicator*
Indoor (Type A)
Red
55000-292
Multi-tone Open-area Sounder with Visual Indicator*
Indoor (Type A)
White
55000-298
Multi-tone Weatherproof Open-area Sounder with Visual Indicator
and Isolator*
Outdoor (Type B)
Red
55000-299
Multi-tone Weatherproof Open-area Sounder with Visual Indicator
and Isolator*
Outdoor (Type B)
White
55000-296
Multi-tone Weatherproof Open-area Sounder with Visual Indicator *
Outdoor (Type B)
Red
55000-297
Multi-tone Weatherproof Open-area Sounder with Visual Indicator *
Outdoor (Type B)
White
* This is a supplementary indicator and is not to be used where a VAD is speci� ed. This product in not
EN54-23 compliant.
The Multi-tone Open-area Alarm Devices are connected to control panels which use the
Discovery or XP95 protocol. It complies with the requirements of EN54–3: 2001. Versions with isolator also
comply with EN54–17: 2005.
Tones incorporated in the product are:
Apollo Standard Tone, Slow Whoop Tone to NEN2575 and DIN 33404 Tone. There are 2 volume settings in
each variant.
The versions which incorporate a short-circuit isolator have a yellow indicator LED, which illuminates
through the lens if a short circuit is detected on the loop wiring.
Mounting the Backbox
The backbox is removed by using either an unlocking key (Type A versions) to press in one of the retain-
ing lugs, or a hex driver (Type B versions).
The Type A product has 6 slotted knockouts on the backbox and is installed directly to the mounting
surface. For the Type B product, � t the backbox to the mounting surface with four screws using the holes
in each corner (see Fig 1). Do not drill through the backbox.
To ensure that there is a good seal between the back box and the unit, the mounting surface should be
as � at as possible and the mounting screws not over tightened.
Wiring Details
Note: This product is polarity sensitive (supply reversal protected) and will not function if wired incor-
rectly.
Drill holes for cable entry as appropriate for the installation. Drill guides are marked on the backbox. To
maintain the integrity of the Type B product it is essential that suitable cable glands be used.
Connect the loop cables to the terminal block, observing polarity and functional earth/screen if appli-
cable. The wiring terminals accept solid or stranded cables up to 2.5mm².
The maximum number of Multi-tone Open-area Alarm Devices permitted between standard XP95
isolators (part no. 55000-720) or isolating bases (part no. 45681-321/284) is 20, depending on the loop
loading. Apollo's Loop Calculator is a program available as a free download from www.apollo-� re.
co.uk and can be used to check the loading of any proposed loop design.
PP2248/Issue 11
©Apollo Fire Detectors Ltd 2003–2018
Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, UK
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo-� re.co.uk Website: www.apollo-� re.co.uk
Group Address Setting
In group mode the Multi-tone Open-area Alarm Devices responds to an additional address referred to
as the group address, which is used to activate groups of sounders simultaneously. Individual units con-
tinue to respond to their own addresses and report their status in the normal way. A group address is set
on a four-segment DIL switch which is factory set to 0000. A group address may be any spare address
within–and only within–the range 112 to 126 inclusive. The required group address is set in accordance
with the following table.
DIL switch
DIL switch
DIL switch
setting
setting
setting
addr
1234
addr
1234
addr
1234
112
1111
117
0101
122
1010
113
0111
118
1001
123
0010
114
1011
119
0001
124
1100
115
0011
120
1110
125
0100
116
1101
121
0110
126
1000
Note: group mode is disabled if the group address DIL switch is set to 0000, irrespective of the protocol
message.
Commissioning
It is important that the Multi-tone Open-area Alarm Devices be fully tested after installation. An XP95
Test Set, part no. 55000-870, may be used to carry out func tion al testing of individual units. The test set
can also perform data integrity tests of an entire system.
Troubleshooting
Before investigating individual units for faults, it is important to check the system wiring is fault-free. Earth
faults on data loops may cause communication errors.
Fault Finding
Problem
Possible Cause
No response or missing
Incorrect address setting
Incorrect loop wiring (polarity reversed)
Too many Sounders with Visual Indicator between isolators
Analogue value 2
Visual Indicator failed (Sounder with Visual Indicator version only)
Analogue value 4
Incorrect group or individual address setting
Device fault
Incorrect group address setting
Device fails to operate
Control panel has incorrect cause and effect programming
Incorrect group address setting
Locking Mechanism
To meet the requirements of EN54 Part 3 and the Construction Products Directive, the devices have
been designed to lock to its base. To release the Type A device from its base, a release key (supplied)
must be used to release the latch in the side of the base. To unlock the Type B (Weatherproof) versions,
a hex driver (supplied) is required.
Maximum Loop Current Consumption at 24V
Switch-on Surge
1.2mA for <1 sec
Quiescent
330µA
Sounder Operated
4mA Max
Sounder Beacon Operated: 92/100dB(A)
9mA Max
Sound Output
100dB(A)
IP Rating - Type A
21C
IP Rating - Type B
IP33C (IP66C**)
** Non EN 54 certi� ed
For sound pressure levels measured to EN54–3 see document PP2203 and for isolator operation informa-
tion see document PP2090, both available on request.
IP Rating
To maintain the integrity of the enclosure it is essential that suitable IP rated cable glands be used.
Individual Address Setting
The address of the Multi-tone Open-area Alarm Devices is set using seven segments of the eight-seg-
ment DIL switch. The eighth seg ment is used to adjust the volume output. Segments 1-7 of the switch are
set to “0” (ON) or “1”, using a small screwdriver or similar tool. A complete list of address settings is shown
below.
DIL switch
DIL switch
DIL switch
DIL switch
DIL switch
setting
setting
setting
setting
setting
addr
1234567
addr
1234567
addr
1234567
addr
1234567
addr
1234567
1
1000000
11
1101000
21
1010100
31
1111100
41
1001010
2
0100000
12
0011000
22
0110100
32
0000010
42
0101010
3
1100000
13
1011000
23
1110100
33
1000010
43
1101010
4
0010000
14
0111000
24
0001100
34
0100010
44
0011010
5
1010000
15
1111000
25
1001100
35
1100010
45
1011010
6
0110000
16
0000100
26
0101100
36
0010010
46
0111010
7
1110000
17
1000100
27
1101100
37
1010010
47
1111010
8
0001000
18
0100100
28
0011100
38
0110010
48
0000110
9
1001000
19
1100100
29
1011100
39
1110010
49
1000110
10
0101000
20
0010100
30
0111100
40
0001010
50
0100110
51
1100110
61
1011110
71
1110001
81
1000101
91
1101101
52
0010110
62
0111110
72
0001001
82
0100101
92
0011101
53
1010110
63
1111110
73
1001001
83
1100101
93
1011101
54
0110110
64
0000001
74
0101001
84
0010101
94
0111101
55
1110110
65
1000001
75
1101001
85
1010101
95
1111101
56
0001110
66
0100001
76
0011001
86
0110101
96
0000011
57
1001110
67
1100001
77
1011001
87
1110101
97
1000011
58
0101110
68
0010001
78
0111001
88
0001101
98
0100011
59
1101110
69
1010001
79
1111001
89
1001101
99
1100011
60
0011110
70
0110001
80
0000101
90
0101101
100
0010011
101
1010011
106
0101011
111
1111011
116
0010111
121
1001111
102
0110011
107
1101011
112
0000111
117
1010111
122
0101111
103
1110011
108
0011011
113
1000111
118
0110111
123
1101111
104
0001011
109
1011011
114
0100111
119
1110111
124
0011111
105
1001011
110
0111011
115
1100111
120
0001111
125
1011111
126
0111111
Fig 3. Example of address and tone setting
Tone Setting
5
6
Tone
0
0
Standard
1
0
Slow Whoop
0
1
DIN
1
1
Standard
The alert or evacuate mode is selected
using the appropriate settings on the
CIE (Control & Indicating Equipment
Fig 2. Wiring
Fig 1. Mounting Type B weatherproof products