Intrinsic Safety Certification
3.1
ATEX gas certification
3.2
Zones, gas groups & T rating
3.3
Special conditions for safe use
3.4
Power supply
3.5
Pulse input terminals
3.5.1
sensors that do not require
energising.
3.5.2
sensors that do require
energising.
3.6
Remote reset terminals
3.7
Certification label information
4.
System Design for Hazardous Areas
4.1
Use with Zener barriers
4.1.1
Power supply
4.1.2
Pulse input
4.1.3
Switch contact input
4.1.4
2-wire proximity detector input
4.1.5
Open collector
4.1.6
Magnetic pick-off input
4.1.7
Voltage pulse input
4.1.8
Remote reset
4.2
Use with galvanic isolators
4.2.1
Power supply
4.2.2
Pulse input
4.2.3
Switch contact input
4.2.4
2-wire proximity detector input
4.2.5
Open collector
4.2.6
Magnetic pick-off input
4.2.7
Voltage pulse input
4.2.8
Remote reset
5.
Installation
5.1
Location
5.2
EMC
5.3
Installation procedure
5.4
Scale card
6.
Configuration and Calibration
6.1
Calibration structure
6.2
Accessing configuration functions
6.3
Summary of configuration functions
6.4
Input A
6.5
Input A type
6.6
Input A debounce
6.7
Input b
6.8
Input b type
6.9
Input b debounce
6.10 Input A pulse counting edge
6.11 Input b pulse counting edge
6.12 Display update interval
6.13 Counting function
6.14 Upper display
6.15 Lower display
6.16 Position of decimal points
6.17 Total scale factor
6.18 Rate scale factor
6.19 Timebase
6.20 Display filter
6.21 Direction of count
6.22 Reset value
6.23 Local reset
6.24 Local total reset
6.25 Local grand total reset
6.26 Reset grand total from configuration
menu.
6.27 Security code
6.28 Reset configuration to factory defaults
6.29 Display overflow
7.
Pulse Output
7.1
Intrinsic safety
7.2
System design
7.3
Configuration
7.4
Access pulse output sub-menu
7.5
Enable pulse output
7.6
Source of output pulse
7.7
Divide output pulse frequency
7.8
Output pulse width
8.
Configuration example
2
CONTENTS
The BA368E is CE marked to show compliance with the European Explosive Atmospheres Directive
2014/34/EU and the European EMC Directive 2014/30/EU
Fault finding during commissioning
9.2
Fault finding after commissioning
9.3
Servicing
9.4
Routine maintenance
9.5
Guarantee
9.6
Customer comments
10.
Accessories
10.1 Scale card
10.2 Tag information
10.3 Alarms
10.3.1
Solid state output
10.3.2
Intrinsic safety
10.3.3
Summary of configuration
functions.
10.3.4
Alarm enable
10.3.5
Type of alarm
10.3.6
Setpoint adjustment
10.3.7
Alarm function
10.3.8
Alarm output status
10.3.9
Hysteresis
10.3.10 Alarm delay
10.3.11 Alarm silence time
10.3.12 Flash display when alarm
occurs.
10.3.13 Access setpoint
10.3.14 Adjusting alarm setpoints
from display mode.
10.4 Display backlight
10.5 4/20mA output
10.5.1
Intrinsic safety
10,5.2
System design
10.5.3
Configuration and calibration
10.5.4
Access 4/20mA output sub-menu
10.5.5
Enable 4/20mA output
10.5.6
Select rate or total source
10.5.7
Define display for 4mA output
10.5.8
Define display for 20mA output
Appendix 1
IECEx certification
Appendix 2
ETL & cETL certification
3
This intrinsically safe, two input pulse counter will
accept pulses on one or both inputs and may be
configured to show one of the following in
engineering units on an eight digit display:
Input A
+
Input b
Input A
-
Input b
Input A direction controlled by Input b
Quadrature input
(Input A and Input b electrically 90o apart)
A smaller six digit display may be activated to show
the composite pulse rate in engineering units per
second, minute or per hour.
In addition to simple counting applications, the
quadrature input allows direction of movement and
position to be displayed.
The optically-isolated pulse output may be
configured to synchronously retransmit either of the
two inputs or a scaled composite output.
This instruction manual supplements the abbreviated
instruction sheet supplied with each instrument.
The BA368E has been certified intrinsically safe for
use in gas hazardous areas by Notified Body
Intertek Testing and Certification Ltd and complies
with the European ATEX Directive 2014/34/EU.
For international applications the BA368E also has
IECEx certification which is described in
Appendix 1.
For applications in the USA and Canada the BA368E
has ETL and cETL certification which is described in
Appendix 2.
2. OPERATION
Fig 1 shows a simplified block diagram of the
BA368E Counter. The instrument has two inputs, A
and b, which can be configured to accept pulses
from most types of sensor and display the total
number of pulses received and their combined rate
on separate displays.
Each input can be individually configured to accept
pulses from a wide variety of sensors. When the
sensor requires energising, such as a switch
contact, open collector or a two wire proximity
detector, an external link supplies power to the input
terminals.
The BA368E may be supplied with any of the
following factory fitted accessories:
Internally powered display backlight
Dual isolated alarms
Isolated 4/20mA output
Fig 1 BA368E block diagram
2.1 Initialisation
Each time power is applied to a BA368E Counter
initialisation is performed. After a short delay the
following display sequence occurs:
All segments of the display are activated
Counter starts functioning, using the
configuration information stored in the
instrument’s permanent memory. Unless total
and grand total displays have been reset to
zero, new pulses will be added to the existing
totals.
4
The BA368E Counter is controlled and configured
via four front panel push buttons. In the display
mode i.e. when the instrument is counting the push
button functions are:
Push Button Functions
) + &
Grand total - shows Lo followed by least
significant 8 digits of the 16 digit grand
total.
) + * Grand total - shows Hi followed by the
most significant 8 digits of the 16 digit
grand total.
If Local Grand Total Reset CLr Gtot in
the instrument configuration menu has
been activated, operating the ) and
* buttons simultaneously for ten
seconds will result in Clr . no being
displayed with the
no
flashing.
Operating the * or & button will
change the display to Clr . YE5, the )
button will then reset the grand total to
zero which will be confirmed by a brief
display of Gt Clrd. See 6.25
& + *
If Local Total Reset CLr tot in the
instrument configuration menu has
been activated, operating the & and
* buttons simultaneously for three
seconds will reset the total display to
zero and clear any pulses stored in the
pulse output.
See 6.24
( + &
Shows firmware version
( + )
Access to configuration menu
Note: When optional alarms are fitted, the BA368E
Counter may be configured to provide direct access
to the alarm setpoints from the display mode when
the ( and * buttons are operated simultaneously.
See 10.3.13 and 10.3.14
2.3 Displays
The BA368E Counter has two digital displays and
associated annunciators, plus a pulse input indicator
as shown on the front cover of this manual.
Total
Shows the total pulse count on the
display
upper eight digit display. May be
reset to zero via front panel push
buttons or by a remote reset switch.
Rate
Shows the pulse rate on the lower six
Display
digit display. Total and rate displays
may be reversed.
Pulse input
This disc in the lower left hand corner
indicator
of the display 'rotates' for two
seconds each time an input pulse is
received on either input. Appears to
rotate continuously when combined
input frequency on both inputs
exceeds 0.5Hz.
Reset
Activated while the total display
annunciator is being reset via the front panel
push buttons, or the external reset
terminals.
Rate
Identifies rate display
annunciator
Total
Identifies total display
annunciator
RTx
Retransmitted pulse
annunciator annunciator.
Depends upon the setting of 5ource
in the pulse output configuration
menu.
5caled:
Annunciator activated each time
pulse output open collector is on,
i.e. Ron is less than 60Ω + 3V.
direct:
Annunciator continuously
activated.
5
3. INTRINSIC SAFETY CERTIFICATION
The BA368E Counter has ATEX and IECEx gas
certification. This section of the instruction manual
describes ATEX gas certification. IECEx and other
approvals are each described in separate
appendixes to this manual.
3.1 ATEX gas certification
Notified Body Intertek Testing and Certification Ltd
have issued the BA368E with an EC-Type
Examination Certificate number ITS16ATEX28408X.
This confirms compliance with harmonised
European standards and it has been used to confirm
compliance with the European ATEX Directive for
Group II, Category 1G equipment. The Counter
carries the community mark and subject to local
codes of practice may be installed in any of the
European Economic Area (EEA) member countries.
ATEX certificates are also acceptable for
installations in Switzerland.
This section of the instruction manual describes
ATEX installations in explosive gas atmospheres
conforming with EN60079-14 Electrical Installations
in Hazardous Areas. When designing systems for
installation outside the UK the local Code of Practice
should be consulted.
3.2 Zones, gas groups and T rating
The BA368E Counter has been certified
Ex ia IIC T5 Ga
-40ºC ≤ Ta ≤ +70ºC.
When
connected to a suitable system it may be installed in:
Zone 0
explosive gas air mixture
continuously present.
Zone 1
explosive gas air mixture likely
to occur in normal operation.
Zone 2
explosive gas air mixture not
likely to occur, and if it does will
only exist for a short time.
Be used with gases in groups:
Group
A
propane
Group
B
ethylene
Group
C
hydrogen
Having a temperature classification of:
T1
450°C
T2
300°C
T3
200°C
T4
135°C
T5
100°C
At ambient temperatures between -40 and +70°C.
The specified operating temperature of the BA368E
Counter is -40 to +70°C. At temperatures below -
20°C the instrument will continue to count, but the
display digits will change increasingly slowly and the
contrast will be reduced.
This allows the BA368E Counter to be installed in all
gas Zones and to be used with most common
industrial gases except carbon disulphide and ethyl
nitrite which have an ignition temperature of 95°C.
3.3 Special conditions for safe use
The ATEX certificate has an ‘X’ suffix indicating that
special conditions apply to prevent an electrostatic
charge developing on the outside of the instrument
enclosure.
WARNING
To avoid an electrostatic charge being
generated instrument enclosure should
only be cleaned with a damp cloth.
3.4 Power supply
When installed in a hazardous area the BA368E
Counter should be powered via a certified Zener
barrier or galvanic isolator from a dc supply located
in the safe area, or from associated apparatus with
an intrinsically safe output.
The input safety parameters of terminals 1 and 2
are:
Ui
=
28V dc
Ii
=
200mA dc
Pi
=
0.84W
Any certified Zener barrier or galvanic isolator with
output safety parameters equal to or less than these
limits may be used.
The maximum equivalent capacitance and
inductance between terminals 1 and 2 is:
Ci
=
2nF
Li
=
4µH
To determine the maximum permissible cable
parameters the above figures, which are small and
may be ignored in many applications, should be
subtracted from the maximum permitted cable
parameters specified for the Zener barrier or
galvanic isolator powering the BA368E Counter.
6
3.5 Pulse input terminals
The BA368E Counter has two pulse inputs, A and b,
that may be individually configured for use with most
types of sensor. Each input is a separate
intrinsically safe circuit, although the negative side of
each input is internally connected to the negative
side of the power supply and reset terminal RS2.
See Fig 1. The two inputs should not be connected
in parallel.
Some types of sensor that may be connected to the
BA368E inputs, such as a switch contact or a 2-wire
proximity detector, require energising to determine
their state. For sensors requiring energising fitting
an external link between terminals 3 & 4 of the
BA368E for input A and between terminals 7 & 8 for
input b, connects an internal 7V, 6mA supply to the
respective input. Energising is not required when a
BA368E input is connected to a voltage source.
Fitting an energising link changes the output safety
parameters of each BA368E input as shown in the
following table which also shows the types of sensor
requiring energising (link fitting).
Output safety
parameters of each
input.
Type of input
Link*
Uo
Io
Po
Switch contact
Yes
10.5V
9.2mA
24mW
Proximity detector
Yes
10.5V
9.2mA
24mW
Open collector
Yes
10.5V
9.2mA
24mW
Magnetic pick-off
No
1.1V
0.5mA
0.2mW
Voltage input (low)
No
1.1V
0.5mA
0.2mW
Voltage input (high)
No
1.1V
0.5mA
0.2mW
*For input A link terminals 3 and 4
*For input b link terminals 7 and 8
3.5.1 sensors that do not require energising
Magnetic pick-offs and voltage pulse inputs do not
require energising, see section 3.5. For intrinsic
safety purposes, sources of energy with output
parameters less than 1.5V; 100mA and 25mW are
considered to be simple apparatus (Clause 5.7 of
EN60079-11), which allows them to be ignored and
not documented when assessing an intrinsic safe
system.
When terminals 3 & 4 and terminals 7 & 8 are not
linked, the associated BA368E Counter input
complies with the requirements for
simple
apparatus. This allows the output parameters of the
pulse input to be ignored when assessing the safety
of the sensor connected to a Counter.
This allows almost any certified intrinsically safe
voltage pulse or certified magnetic pick-off to be
directly connected to one of the BA368E Counter
inputs.
The BA368E EC-Type Examination Certificate
specifies that the equivalent capacitance and
inductance of each BA368E Counter input are:
Ci
=
2nF
Li
=
4H
To determine the maximum permissible cable
parameters these figures should be subtracted from
the maximum permitted cable parameters specified
for the sensor connected to the input terminals of the
Counter. However, the Counter input parameters
are very small and they are unlikely to make any
significant difference to the allowable cable
parameters.
3.5.2 sensors that require energising
Switch contacts, proximity detectors and open
collector inputs require energising as described in
section 3.5. When energised, the output parameters
of each BA368E Counter input are:
Uo = 10.5V
Io = 9.2mA
Po = 24mW
These parameters do not comply with the
requirements for simple apparatus and should be
included when assessing the safety of the circuits
connected to the inputs of the BA368E Counter.
Any certified intrinsically safe sensor or simple
apparatus may be connected to an energised
BA368E Counter input providing that the sensor's
input parameters are equal to, or greater than, the
output safety parameters of the BA368E Counter
input which are shown above. This is not restrictive
and most sensors will comply.
This allows most mechanically operated switch
contacts, open collector transistors and certified
intrinsically safe NAMUR proximity detectors to be
directly connected to a BA368E Counter input
providing the sensor and associated wiring can
withstand a 500V rms insulation test to earth and
both are located within the same hazardous area as
the Counter.
The maximum capacitance and inductance that may
be safely connected to each Counter input when
energised (link connected) is:
Co
=
2.4µF
Lo
=
200mH
Again this is not restrictive and most sensors will
comply.
7
3.6 Remote reset terminals
The BA368E Counter may be reset to zero by
connecting the reset terminals RS1 and RS2
together for more than one second. These two
terminals have the following input and output safety
parameters:
Uo
=
3.8V
Io
=
1mA
Po
=
1mW
Ui
=
28V dc
Ii
=
200mA dc
Pi
=
0.84W
The equivalent capacitance and inductance between
them is:
Ci
=
0nF
Li
=
0H
The maximum capacitance and inductance that may
be safely connected between the reset terminals
RS1 and RS2 is:
Co
=
40µF
Lo
=
1H
The total Counter display may be reset to zero from
within the hazardous area by any mechanically
operated switch contact connected directly to
terminals RS1 and RS2. To reset the total display
from the safe area a Zener barrier or intrinsically
safe relay is required to transfer the contact closure
into the hazardous area. Almost any intrinsically
safe relay with certification permitting the contacts to
be connected to equipment in the hazardous area
may be used. A positive polarity Zener barrier may
also be used as shown in Fig 2.
Alternatively, the BA368E Counter may be
configured so that the total display is reset to zero
when the & and * push buttons are operated
simultaneously for more than three seconds.
See 6.24.
3.7 Certification label information
The certification information label is fitted in a recess
on the top outer surface of the enclosure. It shows
the ATEX and IECEx certification information, plus
BEKA associates name and location and the
instrument serial number.
Non European
certification information may also be included.
BA368E Certification information label
8
4. SYSTEM DESIGN FOR HAZARDOUS AREAS
4.1 Use with Zener barriers
Zener barriers are the least expensive intrinsically
safe interface between a safe and hazardous area.
However they require a high integrity earth
connection that may be expensive to install and they
do not provide isolation. When a high integrity earth
connection is not already available, it may be less
expensive and complicated to use galvanic isolators
for the installation of a single BA368E Counter.
Terminals 2, 6, 10 and RS2 of the BA368E Counter
are internally connected together. If any of these
terminals are earthed, as shown in Figs 2 & 3, the
other terminals should only be connected to the
same earth, i.e. the barrier busbar, or to circuits that
have 500V insulation to earth.
Any certified Zener barriers may be used with the
BA368E Counter providing their output parameters
do not exceed the input parameters of the terminals
to which they are connected. Only one polarity of
Zener barrier i.e. positive or negative, may be used
in each Counter system.
Fig 2 illustrates the basic circuit that is used for all
BA368E Counter installations protected by Zener
barriers. For simplicity, connections for the pulse
output and the optional alarms and 4/20mA output
are shown separately in sections 7 and 10 of this
manual.
Fig 2 BA368E used with Zener barriers
Alternatively the pulse source may be located in the
safe area. Fig 3 shows how an additional Zener
barrier is used to transfer the signal to the Counter in
the hazardous area. When more than one Zener
barrier is used in a system all must have the same
polarity. i.e. all positive or all negative barriers.
When designing a system it is important to
remember that terminals 2, 6, 10 and RS2 are
interconnected within the BA368E See Fig 1.
Fig 3 BA368E used with Zener barriers
pulse source in safe area.
4.1.1 Power supply
The BA368E Counter requires a minimum of 10V
between terminal 1 & 2 and consumes:
10mA
without optional backlight
plus
16mA
for optional backlight
plus
6mA
when terminals 3 & 4 are linked
plus
6mA
when terminals 7 & 8 are linked
Any certified Zener barrier may be used to power a
BA368E Counter providing the output safety
parameters of the barrier are equal to or less than
the input safety parameters of terminals 1 & 2 of the
BA368E Counter.
Although this allows a wide variety of barriers to be
used, a positive polarity 28V; 93mA; 300 Zener
barrier, which has an end-to-end resistance of about
340, is an industry standard device which is
frequently used. With this barrier the supply voltage
in the safe area, with both counter inputs energised,
must be between 17.5V and the maximum working
voltage of the Zener barrier which, depending upon
manufacturer, will be approximately 26V. The
minimum voltage increases to 23V if a display
backlight is fitted.
9
4.1.2 Pulse input
As shown in Fig 2 the BA368E can count pulses
from a wide variety of sensors in the hazardous
area, or from the safe area as shown in Fig 3.
No Zener barrier is required in series with each input
if the intrinsically safe pulse source is located within
the same hazardous area as the BA368E Counter.
The following table shows the switching thresholds
for the various types of sensor. For reliable
counting the pulse input must fall below the lower
threshold and rise above the upper threshold.
Input sensor
Switching thresholds
Lower
Upper
Switch
100
1000
Proximity detector
1.2mA
2.1mA
Open collector
2k
10k
Magnetic pick-off
0mV
40mV peak
Voltage pulse low
1.0V
3.0V
Voltage pulse high
3.0V
10.0V
4.1.3 Switch contact input
Any mechanically activated switch contact located in
the same hazardous area as the BA368E Counter
may be directly connected to the pulse input
terminals 5 & 6 and 9 & 10 providing the switch and
associated wiring can withstand a 500V rms
insulation test to earth. Most magnetically activated
reed relays comply with these requirements. The
BA368E contains a configurable debounce circuit to
prevent contact bounce being counted.
See section 6.6 for details of the maximum counting
frequency.
4.1.4 2-wire proximity detector input
Most certified intrinsically safe 2-wire proximity
detectors complying with NAMUR switching
thresholds may be connected to the BA368E
Counter inputs, providing the input safety
parameters of the proximity detector are equal to or
greater than the output safety parameters of the
Counter inputs i.e.
Ui
≥
10.5V dc
Ii
≥
9.2mA dc
Pi
≥
24mW
and the minimum operating voltage of the proximity
detector is less than 7.5V.
See section 6.6 for details of the maximum counting
frequency.
4.1.5 Open collector input
Most open collector sensors located in the same
hazardous area as the BA368E Counter may be
directly connected to pulse input terminals 5 & 6 and
9 & 10 providing the sensor and associated wiring
can withstand a 500V rms insulation test to earth.
The open collector device must comply with the
requirements for simple apparatus or have input
safety parameters equal to or greater than:
Ui
≥
10.5V dc
Ii
≥
9.2mA dc
Pi
≥
24mW
See section 6.6 for details of the maximum counting
frequency.
4.1.6 Magnetic pick-off input
CoiL in the input configuration menu is a low level
voltage pulse input intended for use with magnetic
pick-off sensors producing an ac output. For a CoiL
input the pulse input terminals 5 & 6 and 9 & 10 of
the BA368E Counter comply with the requirements
of simple apparatus allowing connection to any
certified intrinsically safe magnetic pick-off within the
hazardous area having output parameters equal to
or less than:
Uo
≤
28V dc
Io
≤
200mA dc
Po
≤
0.84W
The maximum permitted cable parameters will be
defined by the magnetic pick-off’s intrinsic safety
certificate less the Counters input parameters Ci & Li
which are small and can often be ignored,
See section 6.6 for details of the maximum counting
frequency.
4.1.7 Voltage pulse input
Two voltage pulse input ranges are selectable in the
configuration menu, VoLt5 L and VoLt5 H. When
configured for either of the voltage pulse ranges, the
pulse input terminals 5 & 6 and 9 & 10 of the
BA368E Counter comply with the requirements of
simple apparatus allowing connection to any
intrinsically safe voltage source within the hazardous
area having output parameters equal to or less than:
Uo
≤
28V dc
Io
≤
200mA dc
Po
≤
0.84W
The maximum permitted cable parameters will be
defined by the voltage source intrinsic safety
certificate less the
BA368E Counter
input
parameters which are small and can often be
ignored.
See section 6.6 for details of the maximum counting
frequency.
10
4.1.8 Remote reset
The BA368E Counter total display may be remotely
reset to zero by connecting terminals RS1 & RS2
together for more than one second. Permanent
interconnection inhibits counting. Remote resetting
may be accomplished by any mechanically operated
switch located in the same hazardous area as the
Counter providing it and the associated wiring can
withstand a 500V rms insulation test to earth. No
Zener barrier is required.
A BA368E may also be remotely reset to zero from
the safe area. Any switch may be used but a Zener
barrier is required to transfer the contact closure into
the hazardous area which may be combined with the
supply barrier so that only one package is required.
A diode return barrier is not suitable for this
application. Fig 2 illustrates how the BA368E total
display may be reset from both the safe and the
hazardous area.
Note: The BA368E can be configured to reset the
total display to zero when the & and * push
buttons are operated simultaneously for more than
three seconds - see 6.24.
4.2 Use with Galvanic Isolators
Galvanic isolators are probably the simplest
intrinsically safe interface to install as they provide
isolation and do not require a high integrity earth
connection.
Any certified galvanic isolator with output parameters
less than the input parameters of the BA368E having
the correct function may be used.
Fig 4 BA368E protected by galvanic isolators.
Fig 4 illustrates the basic circuit that is used for all
BA368E Counter installations protected by galvanic
isolators. For simplicity, connections for the pulse
output and the optional factory fitted alarms and
4/20mA output are shown separately in section 7
and 10 of this manual.
Alternatively the pulse source may be located in the
safe area. Fig 5 shows how an additional galvanic
isolator is used to transfer the signal to the BA368E
Counter in the hazardous area, although it may be
difficult to find isolators for some sensors.
11
Fig 5 Pulse source in safe area
4.2.1 Power supply
The BA368E Counter requires a minimum of 10V
between terminal 1 & 2 and consumes 10mA plus
6mA for each input that is energised, a maximum
total of 22mA if both inputs are energised. Any
certified galvanic isolator may be used to power a
BA368E Counter providing the output safety
parameters of the isolator are equal to or less than
the input safety parameters of terminals 1 & 2 of the
BA368E Counter. These requirements are not
restrictive and allow a wide range of galvanic
isolators, such as solenoid drivers, to be used.
4.2.2 Pulse input
As shown in Fig 4 the BA368E can count pulses
from a wide variety of sensors in the hazardous
area, or from the safe area as shown in Fig 5.
No galvanic isolator is required in series with the
input if the intrinsically safe pulse source is located
within the same hazardous area as the BA368E
Counter.
The following table shows the switching thresholds
for the various types of sensor. For reliable
counting the pulse input must fall below the lower
threshold and rise above the upper threshold.
Input sensor
Switching thresholds
Lower
Upper
Switch
100
1000
Proximity detector
1.2mA
2.1mA
Open collector
2k
10k
Magnetic pick-off
0mV
40mV peak
Voltage pulse low
1.0V
3.0V
Voltage pulse high
3.0V
10.0V
4.2.3 Switch contact input
Any mechanically activated switch contact located in
the same hazardous area as the BA368E Counter
may be directly connected to pulse input terminals 5
& 6 and 9 & 10 providing the switch and associated
wiring can withstand a 500V rms insulation test to
earth. Most magnetically activated reed relays
comply with these requirements. The BA368E
contains a configurable debounce circuit to prevent
contact bounce being counted.
See section 6.6 for details of the maximum counting
frequency.
4.2.4 2-wire proximity detector input
Most certified intrinsically safe 2-wire proximity
detectors complying with NAMUR switching
thresholds may be connected to the BA368E
Counter inputs, providing the input safety
parameters of the proximity detector are equal to or
greater than the output safety parameters of the
Counter inputs i.e.
Ui
≥
10.5V dc
Ii
≥
9.2mA dc
Pi
≥
24mW
and the minimum operating voltage of the proximity
detector is less than 7.5V.
See section 6.6 for details of the maximum counting
frequency.
12
4.2.5 Open collector input
Most open collector sensors located in the same
hazardous area as the BA368E Counter may be
directly connected to pulse input terminals 5 & 6 and
9 & 10 providing the sensor and associated wiring
can withstand a 500V rms insulation test to earth.
The open collector device must comply with the
requirements for simple apparatus or have input
safety parameters equal to or greater than:
Ui
>
10.5V dc
Ii
>
9.2mA dc
Pi
>
24mW
See section 6.6 for details of the maximum counting
frequency.
4.2.6 Magnetic pick-off input
CoiL in the input configuration menu is a low level
voltage pulse input intended for use with magnetic
pick-off sensors producing an ac output. For a CoiL
input the pulse input terminals 5 & 6 and 9 & 10 of
the BA368E Counter comply with the requirements
of simple apparatus allowing connection to any
certified intrinsically safe magnetic pick-off within the
hazardous area having output parameters equal to
or less than:
Uo
≤
28V dc
Io
≤
200mA dc
Po
≤
0.84W
The maximum permitted cable parameters will be
defined by the magnetic pick-off’s intrinsic safety
certificate less the Counters input parameters Ci & Li
which are small and can often be ignored.
See section 6.6 for details of the maximum counting
frequency.
4.2.7 Voltage pulse input
Two voltage pulse input ranges are selectable in the
configuration menu, VoLt5 L and VoLt5 H. When
configured for either of the voltage pulse ranges, the
pulse input terminals 5 & 6 and 9 & 10 of the
BA368E Counter comply with the requirements of
simple apparatus allowing connection to any
intrinsically safe voltage source within the hazardous
area having output parameters equal to or less than:
Uo
≤
28V dc
Io
≤
200mA dc
Po
≤
0.84W
The maximum permitted cable parameters will be
defined by the voltage source intrinsic safety
certificate less the
BA368E Counter
input
parameters which are small and can usually be
ignored.
See section 6.6 for details of the maximum counting
frequency.
4.2.8 Remote reset
The BA368E Counter total display may be remotely
reset to zero by connecting terminals RS1 & RS2
together for more than one second. Permanent
interconnection inhibits totalisation.
Remote
resetting may be accomplished by any mechanically
operated switch located in the same hazardous area
as the Counter providing it and the associated wiring
can withstand a 500V rms insulation test to earth.
No galvanic isolator is required.
A BA368E Counter may also be remotely reset to
zero from the safe area. Any switch may be used
but a galvanic isolator or IS relay is required to
transfer the contact closure into the hazardous area.
Almost any device with a contact that may be
connected to equipment in the hazardous area may
be used for this application. Fig 4 illustrates how a
BA368E Counter may be reset from both the safe
and the hazardous area.
Note: The BA368E can be configured to reset the
total display to zero when the & and * push
buttons are operated simultaneously for more than
three seconds - see 6.24.
13
The BA368E Counter has a robust glass reinforced
Noryl enclosure with a toughened glass window.
The front of the instrument has IP66 ingress
protection and a gasket seals the joint between the
instrument enclosure and the panel. The rear of the
instrument has IP20 ingress protection.
The BA368E may be installed in any panel providing
that the operating temperature is between -40°C and
+70°C and the intrinsic safety requirements are
complied with. At temperatures below -20°C the
instrument will continue to count but the display will
become increasingly slow and the contrast will be
reduced.
Figs 6 shows the overall dimensions together with
the recommended panel cut-out dimensions. To
achieve an IP66 seal between the instrument
enclosure and the instrument panel, the smaller cut-
out dimensions should be used and the instrument
should be secured with four panel mounting clamps.
5.2 EMC
The BA368E Counter complies with the
requirements of the European EMC Directive
2014/30/EU. For specified immunity all wiring
should be in screened twisted pairs, with the screens
earthed at one point within the safe area.
Recommended panel cut-out
dimensions for all installations
Mandatory to achieve an IP66 seal
between instrument and panel
136 +0.5/-0.0 x 66.2 +0.5/-0.0
DIN 43700
138.0 +1.0/ -0.0 x 68 +0.7 -0.0
Note: Optional backlight is internally powered
Fig 6 BA368E dimensions & terminals
14
5.3 Installation Procedure
a.
Cut the specified aperture in the panel. To
achieve an IP66 seal between the instrument
enclosure and the instrument panel the
aperture must have the tighter tolerances
specified in Fig 6.
b.
Slide the gasket over the body of the BA368E
Counter before inserting the instrument into
the panel aperture.
c.
Firstly ensure that all the panel mounting
clamps are closed by turning the knurled
screws fully anti clockwise until the two pips in
the clamp foot align with holes in the clamp
body.
d.
Place a clamp in the recess on each side of
the Counter, pulling gently to slide it onto the
dovetail as shown in Fig 7. Push the knurled
screw slightly forward to engage the thread
and tighten by turning clockwise until it is just
finger tight. When all clamps are fitted ensure
that the gasket behind the front panel bezel is
correctly positioned before fully tightening the
clamps to secure the instrument. The
maximum recommended clamp tightening
torque is 22cNm (1.95 lbf in) which is
approximately equivalent to finger-tight plus
one half turn. Do not over tighten.
e.
Four panel mounting clamps are required to
achieve an IP66 seal between a BA368E
Counter and the instrument panel.
f.
Connect the panel wiring to the rear terminal
block(s) as shown in Fig 6. To simplify
installation, the terminals are removable so
that the panel wiring can be completed before
the instrument is installed. To prevent vibration
damage ensure panel wiring is supported.
Fig 7 Fitting panel mounting clamps
5.4 Scale card
The Counter’s units of measurement may be shown
on a printed scale card in a window at the right hand
side of the display. The scale card is mounted on a
flexible strip that is inserted into a slot at the rear of
the instrument as shown in Fig 8. Thus the scale
card can easily be changed without removing the
Counter from the panel or opening the instrument
enclosure.
New BA368E Counters are supplied with a printed
scale card showing the requested units of
measurement, if this information is not supplied
when the instrument is ordered a blank card will be
fitted.
A pack of self-adhesive scale cards printed with
common units is available as an accessory from
BEKA associates. Custom printed scale cards can
also be supplied.
To change a scale card, unclip the tapered end of
the flexible strip at the rear of the instrument by
gently pushing it upwards and pulling it out of the
enclosure. Peel the existing scale card from the
flexible strip and replace it with a new printed card,
which should be aligned as shown below. Do not fit
a new scale card on top of an existing card.
Install the new scale card by gently pushing the
flexible strip into the slot at the rear of the Counter,
when it reaches the internal end-stop secure it by
pushing the end of the flexible strip downwards so
that the tapered section is held by the rear panel.
Align the self-adhesive printed
scale card onto the flexible strip
and insert the strip into the
Counter as shown below.
Fig 8 Inserting the flexible strip carrying the scale
card into slot at the rear of the BA368E Counter.
15
6.0 CONFIGURATION & CALIBRATION
The BA368E Counter is configured and calibrated
via four front panel push buttons. All the
configuration functions are contained in an easy to
use intuitive menu that is shown diagrammatically in
Fig 10.
Each menu function is summarised in section 6.3 of
this manual and each summary includes a reference
to more detailed information.
The isolated pulse output, including configuration, is
described in section 7 of this manual. When factory
fitted optional alarms and the optional 4/20mA output
are included, additional functions appear in the
configuration menu which are described in section
10 of this manual.
All new BA368E Counters are supplied calibrated as
requested at the time of ordering. If calibration is not
requested, Counters will have default configuration
as shown in the following table, but can easily be re-
configured on-site.
Function
Display Default
Input A
inP . tYPE
oP . CoL
Debounce
dEbounCE
dEFAuLt
Input b
inP . tYPE
oP . CoL
Debounce
dEbounCE
dEFAuLt
Counting edge A
CntEdG-A
EdGE 1
Counting edge b
CntEdG-b
EdGE 1
Update
uPdAtE
0.5
Count
Count
A:b
Upper display
di5p-1
totAL
Lower display
di5P-2
on
Decimal point
dP
Rate
00000 . 0
Total 00000000
Total scale factor
5CALE . t
001 . 00
Rate scale factor
5CALE . r
001 . 00
Timebase
t-bA5E
tb-01
Filter
FiLter
24
Counter direction
uP or dn
uP
Clear value
clr val
00000000
Local clear
loc clr
Local total reset
Clr tot
oFF
Local grand total reset Clr Gtot
oFF
Security code
CodE
0000
Note: While the instrument is being configured
counting continues so that any input pulses
occurring during this time are recorded.
6.1 Calibration structure
Fig 9 shows the calibration structure of the BA368E
Counter. The two pulse inputs are processed by the
count function to produce a single output having the
selected arithmetic function, such as the sum of
pulse input A and pulse input b. This output is
passed to the 5cALE . r and 5CALE . T functions
allowing the rate and total displays to have different
engineering units.
5CALE . t is a dividing factor that converts the output
from the Counter function into the required total
display in engineering units. e.g. if the output from
the Counter function is two pulses per pump stroke
and a total display of thousands of pump strokes is
required, 5CALE . t should be set to 2000.
5CALE . r is a dividing factor that converts the output
from the Counter function into a rate display with the
required engineering units. e.g. if the output from
the Counter function is two pulses per pump stroke
and it is required to display the pump stroke rate,
5CALE . r should be set to 2.
The timebase t-bA5E is a multiplying factor that
determines if the instrument displays rate per
second, per minute or per hour.
The BA368E uses ‘real’ decimal points. Moving the
position of a decimal point in a scale factor will affect
the instrument calibration.
Fig 9 Calibration structure
16
6.2 Accessing configuration functions
Throughout this manual the instrument front panel
push buttons are shown as &, *, ( and ) and
legends displayed by the instrument are shown in a
seven segment font as displayed by the Counter
e.g. FiLtEr and 5CALE . r.
Access to the configuration menu is obtained by
operating the
(
and
)
push buttons
simultaneously. If the instrument is not protected by
a security code the first parameter inPut-A will be
displayed. If a security code other than the default
code 0000 has already been entered, the instrument
will display CodE. Press ( to clear this prompt and
enter the security code for the instrument using the
& or * push button to adjust the flashing digit,
and the ( push button to transfer control to the
next digit. If the correct code has been entered
pressing ) will cause the first parameter inPut-A
to be displayed. If an incorrect code is entered, or a
push button is not operated within ten seconds, the
instrument will automatically return to the display
mode.
All configuration functions and prompts are shown
on the upper eight digit display.
Once within the configuration menu the required
function can be selected by scrolling through the
menu using the & and * push buttons. The
configuration menu is shown diagrammatically in
Fig 10.
When returning to the display mode following
reconfiguration, the BA368E Counter will display
dAtA followed by 5AVE while the new information is
stored in permanent memory.
If after accessing the configuration menu the interval
between operating any front panel push button
exceeds one minute, the BA368E will automatically
return to the display mode and any configuration
changes will not be stored in permanent memory.
When making changes to multiple configuration
functions, it is therefore sensible to occasionally
return to the display mode to save the changes that
have already been made.
6.3 Summary of configuration functions
This section summarises all the configuration
functions. When read in conjunction with Fig 10 it
provides a quick aid for configuring the Counter. If
more detail is required, each summary contains a
reference to a full description of the function.
Display Summary of function
inPut-A
Contains sub-menu with two
functions:
inP . tYPE
Select Input type
dEbounCE
Set debounce
See section 6.4
inP . tYPE [for Input-A]
Configures input-A to accept one of
six types of input:
oP . CoL
Open collector *
VoLt5 L
Voltage pulse <1 >3V
VoLt5 H
Voltage pulse <3 >10V
CoiL
Magnetic pick-off
Pr . dEt
Proximity detector *
ContACt
Switch contact *
* Link terminals 3 & 4
See section 6.5
dEbounCE [[[for Input-A]
Defines level of input debounce
applied to the pulse input A to
prevent false counting:
dEFAuLt
HEAVY
LiGHt
See section 6.6
inPut-b
Contains sub-menu with two
functions:
inP . tYPE
Select Input type
dEbounCE
Set debounce
See section 6.7
inP . tYPE [for Input-b]
Configures input-b to accept one of
six types of input:
oP . CoL
Open collector *
VoLt5 L
Voltage pulse <1 >3V
VoLt5 H
Voltage pulse <3 >10V
CoiL
Magnetic pick-off
Pr . dEt
Proximity detector *
ContACt
Switch contact *
* Link terminals 7 & 8
See section 6.8
17
Summary of function
dEbounCE [for Input-b]
Defines level of input debounce
applied to the pulse input b to
prevent false counting:
dEFAuLt
HEAVY
LiGHt
See section 6.9
CntEdG-A
Input A pulse counting edge
Defines whether the Counter is
incremented/decremented on the
leading or trailing edge of a pulse on
input A.
See section 6.10
CntEdG-b
Input b pulse counting edge
Defines whether the Counter is
incremented/decremented on the
leading or trailing edge of a pulse on
input b.
See section 6.11
updAtE
Display update interval
Defines the interval between display
updates between 0.5 and 5
seconds.
See section 6.12
Count
Counting function
Defines the arithmetic relationship of
the two pulse inputs. The total
display can be derived from:
A:b
Input A + Input b
A:-b
Input A - Input b
A con b
Input A controlled by
Input b.
a rel b
Quadrature input
(for position display)
See section 6.13
di5P-1
Upper display
Defines whether rAtE or totAL is
shown on the upper display. The
other variable will be shown on the
lower display, providing the lower
display is on in function dI5P-2.
See section 6.14
Display
Summary of function
di5P-2
Lower display
Turns the lower display, which
normally shows rate, on or oFF.
See section 6.15
dP
Position of decimal points
Defines the position of the decimal
point in both the total and rate
displays.
See section 6.16
5CALE . t
Total Scale Factor
5CALE . t is a dividing factor that
converts the pulse output from
arithmetic Count function into the
required total display in engineering
units. 5CALE . t may be adjusted
between. 0.0001 and 99999. e.g. if
one pulse represents 1 centimetre of
dispensed cable and the total
display is required in metres,
5CALE . t should be set to 100.0
which is the number of centimetres
in a metre.
The total display is independent of
the rate display.
See section 6.17
5CALE . r
Rate scale factor
5CALE . r is a dividing factor that
converts the pulse output from the
arithmetic Count function into the
required rate display in engineering
units. 5CALE . r may be adjusted
between 0.0001 and 99999. e.g. if
one pulse represents 2 pump
strokes and the rate display is
required in pump strokes, 5CALE . r
should be set to 0.5.
The rate display is independent of
the total display.
See section 6.18
t-bA5E
Timebase
Selectable multiplier allowing rate to
be displayed in units per second, per
minute or per hour.
Select:
tb-01
for rate / second
tb-60
for rate / minute
tb-3600
for rate / hour
See section 6.19
18
Summary of function
FiLtEr
Display filter
Is an adjustable digital filter to
reduce the noise on the rate display.
The filter has two parameters each
represented by a digit adjustable
between 0 and 9. The first digit
defines the amount of filtering
applied to the display, the second
digit the deviation from the displayed
rate at which the filter will be
overridden and the rate display will
move rapidly to the new value.
See section 6.20
& or *
Direction of count
Determines whether pulses at inputs
A and b increment or decrement the
total display.
See section 6.21
CLr VAL
Reset value
Defines a preset number to which
the total display will be set when the
BA368E Counter is locally or
remotely reset.
Enables the
instrument to count down from a
preset number.
See section 6.22
LoC CLr
Local clear
Contains sub-menu with two
functions enabling the total and the
grand total to be reset via the front
panel push buttons while the
Counter is in the display mode.
See section 6.23
Clr tot
When on is selected total display is
reset when & and * buttons are
operated simultaneously for more
than 3 seconds in the display mode.
See section 6.24
Clr Gtot
When on is selected the grand total
may be reset when ) and *
buttons are operated simultaneously
for more than 10 seconds in the
display mode - see section 2.2 for
details.
Note: Once reset, the grand total
can not be restored.
See section 6.25
Display
Summary of function
Clr Gtot
Resets grand total to zero from
within configuration menu.
This function resets the grand total
to zero from within the configuration
menu when CLr YE5 is selected.
Note: Once reset, the grand total
can not be recovered.
See section 6.26
CodE
Access code
Defines a four digit alphanumeric
code that must be entered to gain
access to the configuration menu.
Default code 0000 disables the
security function and allows
unrestricted
access
to
all
configuration functions.
See section 6.27
r5Et dEF
Reset to factory defaults
Returns the BA368E Counter to the
factory defaults shown in section 6.0
To prevent accidental use the
request must be confirmed by
entering 5urE before the reset will
be executed.
See section 6.28
19
6.4 Input A: inPut-A
The Input A function contains two sub-functions
inP . tYPE and dEbounCE that define the type of input
and the amount of input noise rejection.
6.5 Input A type: inP. tYPE
inP . tYPE is a sub-menu in the inPut-A function
which defines the type of input sensor or input pulse
that the instrument will count at Input-A. To check or
change the type of input, select inPut-A in the
configuration menu and press ( which will reveal
the inP. tYPE prompt, pressing ( again will show
the existing Input-A setting. If set as required press
) twice to return to the configuration menu, or
repeatedly press the & or * button until the
required type of input is displayed and then press
) twice to return to the configuration menu.
One of following six types of input may be selected:
Switching
thresholds
Low High
oP . CoL
Open collector 2
2
10kΩ
VoLt5L
Voltage pulse low 1
1
3V
VoLt5H
Voltage pulse high1
3
10V
CoiL
Magnetic pick-off
0
40mV
Pr . dEt
Proximity detector 2
1.2
2.1mA
ContACt
Switch contact 2
100
1000Ω
Notes:
1. Maximum voltage input +28V.
2. For sensors connected to Input-A that require
energising i.e. proximity detectors, switch
contacts or open collector sensors, terminals
3 & 4 of the BA368E should be linked
together.
3. To count correctly, the input pulse must fall
below the lower switching threshold and rise
above the higher switching threshold.
4. See section 6.6 for maximum counting
frequency.
6.6 Input A debounce: dEbouncE
dEbouncE is an adjustable sub-menu in both the
inPut-A and inPut-b functions which prevents the
input miscounting when the input pulse has noisy
edges, such as those resulting from a mechanical
contact closing and bouncing. The debounce
function only applies to the input in which the
function is located.
Three levels of protection may be independently
selected for each input. The amount of debounce
applied depends upon the type of Counter input that
has been selected for the input in the associated
inP . tYPE function.
Select inPut-A or inPut-b in the configuration menu
and press ( which will reveal the inP . tYPE prompt,
press the & or * button to select dEbouncE
followed by ( to reveal the existing setting.
Pressing the & or * button will scroll through the
three levels. When the required level has been
selected, pressing ) twice will enter the selection
and return the display to the configuration menu.
The following table shows the minimum time that the
input pulse must be continuously above the upper
input switching threshold and continuously below the
lower switching threshold to ensure that the Counter
processes the input pulse. Input switching
thresholds are shown in section 4.1.2.
debounce
level
Min input pulse width
Type of Input
Contact
All others
Default
1600µs
40µs
Heavy
3200µs
350µs
Light
400µs
5µs
The maximum counting frequency of the BA368E
depends upon the debounce level selected, the
shape of the input pulse and its amplitude. The
following table assumes a square wave input and is
included for guidance. The maximum counting
frequency will be lower if the input pulses have
sloping edges and the pulse amplitude only slightly
exceeds the input switching thresholds.
ONLY FOR GUIDANCE
debounce
level
Max counting frequency
Type of input
Contact
All others
Default
250Hz
12kHz
Heavy
120Hz
2kHz
Light
1000Hz
100kHz
The minimum input frequency is 0.01Hz. Below this
frequency the rate display will be forced to zero.
22
6.7 Input b: inPut-b
The Input b function contains two sub-functions
inP . tYPE and dEbounCE that define the type of input
and the amount of input noise rejection.
6.8 Input b type: inP. tYPE
inP. tYPE is a sub-menu in the inPut-b function
which defines the type of input sensor or input pulse
that the instrument will count at Input-b. To check or
change the type of input, select inPut-b in the
configuration menu and press ( which will reveal
the inP. tYPE prompt, pressing ( again will show
the existing Input-b setting. If set as required press
) twice to return to the configuration menu, or
repeatedly press the & or * button until the
required type of input is displayed and then press
) twice to return to the configuration menu.
One of following six types of input may be selected:
Switching
thresholds
Low High
oP . CoL
Open collector 2
2
10kΩ
VoLt5L
Voltage pulse low 1
1
3V
VoLt5H
Voltage pulse high1
3
10V
CoiL
Magnetic pick-off
0
40mV
Pr . dEt
Proximity detector 2
1.2
2.1mA
ContACt
Switch contact 2
100
1000Ω
Notes:
1.
Maximum voltage input +28V.
2.
For sensors connected to Input-b that require
energising i.e. proximity detectors, switch
contacts or open collector sensors, terminals
7 & 8 of the BA368E should be linked
together.
3.
To count correctly, the input pulse must fall
below the lower switching threshold and rise
above the higher switching threshold.
4.
See section 6.6 for the maximum counting
frequency.
6.9 Input b debounce: dEbouncE
Exactly as input A, please see section 6.6
6.10 Input A pulse counting edge: CntEdg-A
This function allows the edge on which a count
occurs to be selected. It applies to input A for all
counting modes except quadrature (A rEL b).
To check or change the input A pulse edge on which
the count occurs select CntEdG-A from the
configuration menu and press ( which will reveal
EdGE 1 or EdGE 2. If required press the & or *
button to change the setting, followed by the )
button to return to the configuration menu.
EdGE 1
Type of input Counting edge
Voltage
Low to high
Switch contact
Closed to open
Open collector
Closed to open
Proximity detector
High to low current
EdGE 2
Type of input Counting edge
Voltage
High to low
Switch contact
Open to closed
Open collector
Open to closed
Proximity detector
Low to high current
Note:
The counting edge function CntEdg-A is not
included in the configuration menu when the
BA368E Counter has a quadrature input A rEL b.
In quadrature mode the instrument will count up
when the rising edge of input-b leads the rising
edge of input-A.
See section 6.13.
6.11 Input b pulse counting edge: CntEdg-b
This function allows the edge on which a count
occurs to be selected. It applies to input b for all
counting modes except quadrature A rEL b and input
A controlled by input b A Con b.
To check or change the input b pulse edge on which
the count occurs select CntEdG-b from the
configuration menu and press ( which will reveal
EdGE 1 or EdGE 2. If required press the & or *
button to change the setting, followed by the )
button to return to the configuration menu.
EdGE 1
Type of input Counting edge
Voltage
Low to high
Switch contact
Closed to open
Open collector
Closed to open
Proximity detector
High to low current
EdGE 2
Type of input Counting edge
Voltage
High to low
Switch contact
Open to closed
Open collector
Open to closed
Proximity detector
Low to high current
23
The counting edge function CntEdg-b is not
included in the configuration menu when the
BA368E Counter has a quadrature input A rEL b
or when input A is controlled by input b A Con b.
In quadrature mode the instrument will count up
when the rising edge of input-b leads the rising
edge of input-A.
See section 6.13.
6.12 Display update interval: uPdAtE
If either the rate or the total display is likely to
change rapidly, a longer interval between display
updates may simplify reading. This function allows
one of six different display intervals between 0.5 and
5 seconds to be selected. The selected display
update interval does not affect the update time of
any other instrument function.
To adjust the update interval select uPdAtE from the
configuration menu and press ( to reveal the
current update interval. Pressing the & or *
button will scroll through the six times. When the
required interval has been selected press ) to
enter the selection and return to the configuration
menu.
6.13 Counting function: Count
This function defines the arithmetic relationship
between Inputs A and Input b. The following four
modes may be selected:
Display Input count mode
A : b
Pulses at input A added to
pulses at input b.
A : -b
Pulses at input b
subtracted from pulses at
input A. *
A Con b
Input b controls count
direction of input A. *
Input b Input A
Low
Up counter
High
Down counter
A rEL b
Quadrature input with
sensors electrically 90o
apart. *
* The pulse output is not available with these
count modes.
Fig 11 shows the voltage waveforms at the two
inputs and the resulting total display when the
BA368E is configured to count up on a rising edge.
Fig 11 Counting waveforms
Note:
For a quadrature input the two signals do not
require equal marks and spaces to achieve
reliable counting.
6.14 Upper display: di5P-1
Usually the total count is shown on the larger upper
eight digit display, but this function reverses the
display locations allowing rate to be shown on the
larger upper display and total on the smaller lower
display.
To check the setting for the display, select dI5P-1
from the configuration menu and press ( which will
reveal if the display is showing rAtE or totAL. The
setting can be changed by pressing the & or *
button followed by the ) button to enter the
selection and return to the configuration menu.
24
6.15 Lower display: di5P-2
This function turns the lower display on or off. When
turned off, the BA368E will only have one eight digit
display which may be configured in the di5P-1
function to show the total count or rate.
To check the setting for the lower display, select
di5P-2 from the configuration menu and press
( that will reveal if the lower display is on or oFF.
The setting may be changed by pressing the & or
* button followed by the ) button to enter the
selection and return to the configuration menu.
6.16 Position of the decimal points: dP
The upper and lower displays have eight and six
digits respectively. This function enables the
position of the decimal point in both displays to be
independently positioned as shown below.
Upper display
Total 0 0 0 . 0 . 0 . 0 . 0 . 0
1 of 5 positions or absent
Rate
0 0 . 0 . 0 . 0 . 0
1 of 4 positions or absent
Lower display
Total 0 . 0 . 0 . 0 . 0 . 0
1 of 5 positions or absent
Rate 0 0 . 0 . 0 . 0 . 0
1 of 4 positions or absent
To adjust the position of the decimal points select dP
from the configuration menu and press (. The
upper display defined as the rate or total display by
function di5P-1 (section 6.14) will be activated and
identified by the display annunciator as Rate or
Total. The decimal point, which may be positioned
as shown in the table above, is moved by operating
the & or * push button. The & button moves
the position of the decimal point to the left and the
* button moves the decimal point position to the
right.
When the decimal point in the upper display has
been positioned pressing the ( button will transfer
control to the lower display variable, but it will be
shown and annunciated on the larger upper display.
The position of the decimal point may be positioned
in the same way by operating the & and * push
buttons. When both decimal points are positioned
as required, enter the settings and return to the
configuration menu by operating the ) button.
Note:
Adjustment of a decimal point position will
disable the following outputs which must be
re-enabled after the adjustment is complete:
Pulse output
Optional Alarm outputs
Optional 4/20mA output
6.17 Total scale factor: 5CALE . t
5CALE . t is a dividing factor adjustable between
0.0001 and 99999 that enables the total to be
displayed in engineering units. e.g. if one pulse from
the arithmetic count function represents 1 centimetre
of dispensed cable and the total display is required
in metres, 5CALE . t should be set to 100.0 which is
the number of centimetres in a metre. If just the
total number of input pulses is required, 5CALE . t
should be set to 1.0.
The total display is
independent of the rate display.
To check or change the total scale factor select
5CALE . t from the configuration menu and press (
which will reveal the existing value with one digit
flashing. The value of the flashing digit may be
changed by pressing the & or * button. When
this digit has been adjusted as required, pressing (
will transfer control to the next digit. When all the
digits have been adjusted pressing ( will transfer
control to the decimal point that may be positioned
between any of the digits, or may be omitted by
moving it to the right of the least significant digit.
When the total scale factor has been entered, press
( to return to the 5CALE . t prompt in the
configuration menu.
Note:
Adjustment of 5cale . t will disable the
following ouputs which must be re-enabled
after the adjustment is complete:
Pulse output
Optional Alarm outputs
Optional 4/20mA output
6.18 Rate scale factor: 5CALE . r
5CALE . r is a dividing factor adjustable between
0.0001 and 99999 that enables the rate display to be
shown in engineering units. e.g. if one pulse from
the arithmetic count function represents 2 pump
strokes and the rate display is required in pump
strokes, 5CALE . r should be set to 0.5. If just the rate
of input pulses is required, 5CALE . r should be set to
1.0. The rate display is independent of the total
display.
The units of the rate display are counts per unit of
time. The unit of time is the timebase of the
instrument which is determined by
t-bA5E
described in section 6.19.
To check or change the rate scale factor select
5CALE . r from the configuration menu and press (
which will reveal the existing value with one digit
flashing. The value of the flashing digit may be
adjusted by pressing the & or * button.
25
When this digit has been adjusted as required,
pressing ( will transfer control to the next digit.
When all the digits have been adjusted pressing
( will transfer control to the decimal point that may
be positioned between any of the digits, or may be
omitted by moving it to the right of the least
significant digit. When the required rate scale factor
has been entered, press ) to return to the 5CALE . r
prompt in the configuration menu.
Note:
Adjustment of 5cale . r will disable the
following ouputs which must be re-enabled
after the adjustment is complete:
Pulse output
Optional Alarm outputs
Optional 4/20mA output
6.19 Timebase: t-bA5E
The timebase multiplies the rate display by 1, 60 or
3,600 depending upon whether the BA368E Counter
is required to display rate per second, per minute or
per hour. See Fig 9.
To check or change the timebase, select t-bA5E
from the configuration menu and press ( which will
reveal the current setting. Pressing the & or *
button will scroll through the three options:
tb-1
for pulses / second
tb-60
for pulses / minute
tb-3600
for pulses / hour
When the required multiplier is displayed press )
to return to the t-bA5E prompt in the configuration
menu.
6.20 Display filter: FiLtEr
The digital display filter has two independent
adjustable parameters enabling the rate display
response to be tailored for optimum performance.
The filter parameters are controlled by a two digit
number. The first digit defines the amount of filtering
applied to the display as shown below.
First digit
Filter time constant
Seconds
0X
0
1X
1.3
2X
4.3
3X
6.5
4X
8.7
5X
11.3
6X
15.7
7X
20.9
8X
25.2
9X
31.5
The second digit defines the deviation from the
displayed rate at which the filter will be overridden
and the rate display will move rapidly to the new
value.
Second
digit
Magnitude of step
change which will
produce a rapid
response
X0
Off
X1
1%
X2
2%
X3
4%
X4
8%
X5
12%
X6
16%
X7
24%
X8
32%
X9
64%
By careful adjustment of the two parameters a stable
display with an acceptable input step response can
be obtained for most applications.
During commissioning it is recommend that initially
the second digit is set to 0 (off) and the first digit is
adjusted to provide acceptable rate display stability.
The second digit should then be increased until the
selected step size is greater than the noise on the
display signal, at which setting the rate display will
become stable. These will be the optimum filter
parameters for acceptable rate display stability and a
fast response to a large rate signal change.
To check or change the filter select FiLtEr in the
configuration menu and press ( which will reveal
the current settings with the first digit flashing.
Pressing the & or * button will adjust the flashing
digit and ( will transfer control to the second digit.
While making adjustments the filtered rate display is
shown on the lower display so that stability can be
assessed while adjustments are being made. When
set as required, press the ) button to enter the
revised parameters and return to the FiLtEr prompt
in the configuration menu.
26
6.21 Direction of count: uP or dn
This function defines whether input pulses increment
or decrement the total display. i.e. whether Input A
is an up-counter or a down counter.
When configured as a down-counter with a non-zero
number entered for the reset value CLr VAL, the
BA368E will count down from the re-set value to
zero.
To check or change the count direction select
uP or dn from the configuration menu and press
( which will reveal the present setting. uP
indicates that the instrument is an up-counter and dn
that it is a down counter. Pressing the & or *
buttons will toggle the instrument between the two
settings. When set as required, press the ) button
to enter the setting and return to the configuration
menu.
Note:
The Count function described in section 6.13
also affects the direction in which the BA368E
counts.
6.22 Reset value: CLr VAL
This function defines the value to which the total
display is reset when the local or remote reset are
operated. This allows the BA368E to be used as a
pre-set down counter.
When the instrument is used as an up-counter, CLr
VAL is normally set to zero.
To check or change the reset value select CLr VAL
from the configuration menu and press ( which will
reveal the current setting with one digit flashing. The
flashing digit may be adjusted by pressing the & or
* button. When this digit is correct, pressing
( will transfer control to the next digit.
When all the digits have been adjusted press the )
button to enter the revised number and return to the
configuration menu.
6.23 Local reset: LoC CLr
The Local reset function contains two sub-functions
Clr tot and Clr Gtot which when enabled allow the
total display and grand total to be reset via the
instrument front panel push buttons while the
BA368E Counter is in the display mode.
6.24 Local total reset: Clr tot
Clr tot is a sub-menu in the LoC CLr function. When
activated it allows an operator to reset the total
display to the reset value [see section 6.22] while
the BA368E Counter is in the display mode by
operating the
&
and
*
push buttons
simultaneously for more than three seconds.
To check or change the setting select LoC CLr in the
configuration menu and press ( which will reveal
the Clr tot prompt, operating ( again will show if
the local total reset is on or oFF. If set as required
operate the ) button twice to return to the
configuration menu, or the & or * button to
change the setting followed by the ) button twice
to enter the change and return to the LoC CLr prompt
in the configuration menu.
Note:
The total display may also be remotely reset
to the reset value by connecting terminals
RS1 and RS2 together for more than one
second. See sections 3.6; 4.1.8 and 4.2.8 of
this manual.
6.25 Local grand total reset: Clr Gtot
The grand total is a separate sixteen digit counter
which is incremented or decremented in parallel with
the total display, but is not reset when the total
display is reset. The grand total may be viewed in
the display mode in two eight digit sections as
described in section 2.2 of this manual.
Clr Gtot is a sub-menu in the LoC CLr function
which when activated allows the operator to reset
the grand total display to zero from the display mode
by operating the ) and * push buttons
simultaneously for more than ten seconds.
To check or change the setting select LoC CLr in the
configuration menu and press ( which will reveal
Clr tot. Using the & or * button to select
Clr Gtot and press ( which will show if local grand
total reset is on or oFF. If set as required operate
the ) button twice to return to the configuration
menu, or the & or * button to change the setting
followed by the ) button twice to enter the change
and return to the LoC CLr prompt in the configuration
menu.
Note:
Once reset, the grand total can not be
recovered.
6.26 Reset grand total from configuration menu:
Clr Gtot
The grand total is a separate sixteen digit counter
which is incremented or decremented in parallel with
the total display, but is not reset when the total
display is reset. The grand total may be viewed in
the display mode in two eight digit sections as
described in section 2.2 of this manual.
To zero the grand total from within the configuration
menu select CLr Gtot and press ( which will cause
the instrument to display Clr . no with no flashing.
27
Using the & or * push button change Clr no to
clr ye5, pressing ( will result in the instrument
displaying 0000 with the first digit flashing. This is a
request to confirm the reset instruction by entering
5urE. Using the & or * button set the first
flashing digit to 5 and press ( to transfer control to
the second digit which should be set to u. When
5urE has been entered pressing the ) button will
reset the grand total which will be confirmed by a
brief display of Gt Clrd, the instrument will
automatically return to the Clr Gt prompt in the
configuration menu.
Note:
Once reset, the grand total can not be
recovered.
6.27 Security code: ‘CodE’
Access to the instrument configuration menu may be
protected by a four digit security code which must be
entered to gain access. New instruments are
configured with the default security code 0000 which
allows unrestricted access to all configuration
functions.
To enter a new security code select CodE from the
configuration menu and press ( which will cause
the BA368E Counter to display 0000 with one digit
flashing. The flashing digit may be adjusted using
the & and * push buttons, when set as required
operating the ( button will transfer control to the
next digit. When all the digits have been adjusted
press ) to return to the CodE prompt. The revised
security code will be activated when the BA368E
Counter is returned to the display mode.
Please contact BEKA associates sales department if
the security code is lost.
6.28 Reset configuration to factory defaults
r5Et dEF
This function returns the BA368E Counter to the
factory defaults shown in section 6.0. To prevent
accidental use the request must be confirmed by
entering 5urE before the configuration change will be
executed.
Select r5Et dEF from the configuration menu and
press (. the instrument will display 0000 with the
first digit flashing. To confirm the instruction to reset
all the configuration functions to factory defaults
5urE must be entered. Using the & or * button
set the first flashing digit to 5 and press ( to
transfer control to the second digit which should be
set to u. When 5urE has been entered pressing the
) button will reset all the configuration functions to
the factory default settings and zero both the total
display and the grand total. While resetting the
BA368E Counter will display - - - - - - - - before
automatically returning to the display mode when the
operation is complete.
6.29 Display overflow
The BA368E Counter total has a maximum display
range of -9999999 to 99999999 when shown on the
eight digit upper display. If this range is exceeded
the display will be as shown below with all of the
decimal points flashing:
Overrange 9.9.9.9.9.9.9.9
Underrange -9.9.9.9.9.9.9
When the total is shown on the lower six digit display
the maximum display range is -99999 to 999999.
When a total overflow occurs the actual total may be
obtained from the instrument's grand total display
which has sixteen digits - see 2.2.
To prevent future total display overflows occurring
the total scale factor 5CALE . t and the position of the
decimal point in the total display dP should be
reviewed.
28
7. Pulse output
The BA368E Counter has an opto-isolated solid
state pulse output. The output is an open collector
having the following electrical parameters:
Ron
=
60 + 3V
Roff
=
1M
Imax
=
10mA
The output pulse may be a duplicate of Input A or
Input b for re-transmission applications, or it may be
derived from the total display. When derived from
the total display the output pulse frequency may be
divided and the output pulse width defined.
The retransmitted RTx annunciator on the
instrument display shows the status of the
retransmitted pulse output. Annunciator activation
depends upon the setting of 5ource in the pulse
output configuration menu.
5caled:
Annunciator activated each time pulse output
open collector is on, i.e. Ron is less than
60Ω + 3V.
direct:
Annunciator continuously activated
7.1 Intrinsic safety
The pulse output is an optically isolated separate
intrinsically safe circuit that has zero output safety
parameters. The output therefore complies with the
requirements for simple apparatus. This allows
pulse output terminals P1 and P2 to be directly
connected to any intrinsically safe circuit protected
by a certified Zener barrier or galvanic isolator
providing the output parameters do not exceed:
Uo
=
28V dc
Io
=
200mA
Po
=
0.84W
The equivalent capacitance and inductance of the
pulse output are both zero which allows the
maximum permissible cable parameters specified by
the certificate for the Zener barrier or galvanic
isolator powering the pulse output circuit to be used.
7.2 System design
The BA368E Counter pulse output is a passive
circuit i.e. not powered, but it is totally isolated from
all other Counter circuits. Subject to complying with
intrinsic safety interconnection requirements, the
terminals P1 and P2 may be connected to another
instrument with an open collector input. The pulse
output may also be transferred to the safe area via a
galvanic isolator or a Zener barrier.
Fig 12 shows how a 2-channel Zener barrier may be
used to produce a voltage pulse in the safe area that
could be used to drive a safe area counter. The
positive terminal of the pulse output circuit P1 is
connected to the BA368E Counter’s positive supply
terminal 1 at the instrument. When an output pulse
occurs and the open collector output 'closes', P2 is
connected to P1 and a pulse current flows through
the diode return barrier to resistor R1 in the safe
area. The current flowing in the circuit is determined
by R1 which should be chosen to limit the pulse
output current to less than 10mA. For a 24V supply
R1 should be greater than 2,200Ω.
29
Fig 12 Generating voltage pulse in safe area
using Zener barriers.
7.3 Configuration
The pulse output is configured via a PuL5E oP
sub-menu located between the LoC CLr and the
Clr Gtot functions in the configuration menu as
shown in Fig 13.
This sub-menu allows the source of the output pulse
to be selected. For re-transmission applications the
output pulse may be a synchronous duplicate of the
pulse at Input A or at Input b by selecting dirECt A or
dirECt b in the 5ourCE sub-function.
Selecting 5CALEd derives the output pulse from the
total display and introduces two additional functions,
diVidE and durAtion to the sub-menu allowing the
output pulse frequency to be divided and the output
pulse width (duration) to be defined.
If the diVidE and durAtion functions are configured
such that the output pulse frequency with the
specified pulse width can not be output in real time,
the number of pulses will be stored and transmitted
at the maximum possible speed.
When the total display is reset to zero or the power
supply to the BA368E Counter is disconnected or
turned off, any stored pulses will not be retained.
7.4 Access Pulse output sub-menu: PuL5E oP
Using the & or * push button scroll through the
Counters configuration menu until PuL5E . oP is
displayed, pressing ( will then access the pulse
output sub-menu which is shown in Fig 13.
Fig 13 Pulse output configuration sub-menu
7.5 Enable pulse output: EnbL
This function allows the pulse output to be disabled
or enabled without altering any of the pulse output
parameters. Using the & or * push button select
EnbL in the pulse output sub-menu and press (. to
reveal the existing setting on or oFF. The function
can be changed by pressing the & or * push
button followed by the ) button to return to EnbL
prompt.
30
7.6 Source of output pulse: 5ourCE
The output pulse may be derived from:
dirECt A
Output is duplicate of input A
pulse.
dirECt b
Output is duplicate of input b
pulse.
5CALEd
Output is derived from the total
display and is only functional
when the Count function is
configured for
A+b.
When
5CALEd is selected two additional
functions, diVidE and durArion,
appear in the pulse output sub-
menu.
Using the & or * push button select 5ourCE in the
pulse output sub-menu and press (. to reveal the
existing pulse source. The function can be changed
by pressing the & or * push button followed by
the ) button to return to 5ourCE prompt.
7.7 Divide output pulse frequency: diVidE
When the output pulse is derived from the total
display the output pulse frequency may be divided
by:
1
10
100
1000
10000
Using the & or * push button select diVidE in the
pulse output sub-menu and press ( to reveal the
existing divisor. The value can be changed by
pressing the & or * push button to select the
required value followed by the ) button to return to
diVidE prompt.
Note:
This function only appears in the sub-menu
when the output pulse is derived from the
total display.
7.8 Output pulse width: durAtion
When the output pulse is derived from the total
display, the pulse width is defined by this function.
One of 11 pulse widths in milliseconds may be
selected:
0 . 1
0 . 5
1
2 . 5
5
10
25
50
100
250
500
Using the & or * push button select durAtion in
the pulse output sub-menu and press ( to reveal
the existing pulse duration. The value can be
changed by pressing the & or * push button to
select the required value followed by the ) button
to return to durAtion prompt.
Note:
This function only appears in the pulse
output sub-menu when the output pulse is
derived from the total display.
31
8. CONFIGURATION EXAMPLE
A BA368E Counter is required to display the position
and speed, including direction, of a cable which is
sensed by two proximity detectors mounted on a
wheel with a circumference of 1m over which the
cable runs. The sensors, which produce fifteen
pulses per revolution, are positioned so their outputs
are electrically 90° apart. The BA368E is required
to display the position of the cable relative to a
starting point in metres with a resolution of 0.1m,
and to show speed of the cable in metres per
second with a resolution of 1m. The total display
(position) is to be resettable by an external contact,
not from the BA368E Counter front panel. Similarly
the grand total is not to be resettable from the
BA368E Counter front panel. To prevent tampering
the instrument configuration menu is to be protected
by security code 1209.
The BA368E may be configured on-site without
disconnection from the power supply or from the two
proximity detectors.
If after accessing the configuration menu the interval
between operating any front panel push button
exceeds one minute the BA368E will automatically
return to the display mode and any configuration
changes will not be stored in permanent memory.
When making multiple changes it is therefore
sensible to occasionally return to the display mode
to save the changes that have already been made.
Step 1
Enter the configuration menu
Put the BA368E Counter in the
configuration mode by simultaneously
pressing ( and ) push buttons.
Assuming a security code has not
already been entered the instrument will
respond by displaying inPut-A which is
the first parameter in the configuration
menu.
See Fig 10
Step 2
Select the type of inputs
With InPut-A displayed; press ( to
reveal the existing setting. Using the
& or * button select Pr . dEt, the input
for a 2-wire proximity detector, and then
return to the inPut-A prompt in the
configuration menu by pressing ).
Repeat for the second input inPut-b
Step 3
Select input count mode
The two proximity detectors are
positioned so their outputs are electrically
90° apart. From this information, in the
quadrature input mode the BA368E
Counter can sense the direction and
angular movement of the wheel to which
the proximity detectors are attached.
Hence, the relative position of the cable
can be displayed by the counter.
Select Count from the configuration
menu and press (. Using the & or *
button select A rEL b the quadrature
function and press ) to return to the
‘Count’ prompt in the configuration menu.
Step 4
Define function of upper display
In the example the cable position (total
display) is required on the eight digit
upper display.
Select dI5P-1 from the configuration
menu and press ( which will reveal if
the upper display is showing rAtE or
totAL. Using the & or * button select
totAL followed by the ) button to enter
the selection and return to the
configuration menu.
Step 5
Activate lower rate display
A rate display is required so the lower
display must be activated.
Select di5PLAY . 2 from the main menu
and press ( to show the existing
setting. Using the & or * button
select on followed by ) to enter the
selection and return to the configuration
menu.
Step 6
Position of decimal point
In this example the BA368E is required
to display total (position) with a resolution
of one decimal place and rate (speed)
with no decimal point.
Select d . P. from the configuration menu
and press (. The BA368E will show
and identify the total display with all the
digits activated. Using the & or *
button position the decimal point between
the first and second least significant
digits.
Operating the ( button will show and
identify the rate display with all the digits
activated, Using the & or * button
position the decimal point to the right of
the least significant digit i.e. not visible.
Finally press ) to return to the
configuration menu.
32
Enter the total scale factor
In this example the proximity detectors
produce fifteen pulses per one metre
movement of the cable. The position
display is required in metres so the total
(position) scale factor 5CALE . t should be
set to 15.0.
Select 5CALE . t from the configuration
menu and press ( to view the current
value with one digit flashing. Use the &
and * buttons to adjust each digit in
turn and the ( button to transfer control
to the next digit and to the decimal point.
Enter 15.0 and return to the 5CALE . t
prompt in the configuration menu by
pressing ).
Step 8
Enter the rate scale factor
In this example the proximity detectors
produce fifteen pulses per one metre
movement of the cable. The rate display
is required in metres per second so the
rate (speed) scale factor 5CALE . r should
be set to 15.0.
Select 5CALE . r from the configuration
menu and press ( to view the current
value with one digit flashing. Use the &
and * buttons to adjust each digit in
turn and the ( button to transfer control
to the next digit and to the decimal point.
Enter 15.0 and return to the 5CALE . r
prompt in the configuration menu by
pressing ).
Step 9
Set the display timebase
In this example the rate display (speed)
is required in metres per second.
Select t-bA5E from the configuration
menu and press ( to reveal the current
setting. Using the & or * button scroll
through the three options and select
tb-1. Return to the t-bA5E prompt in the
configuration menu by pressing ).
Step 10 Adjust the rate display filter
The rate display filter parameters should
be adjusted experimentally after
installation to provide a stable rate
display with an acceptable step
response.
During commissioning it is recommended
that initially the second digit of the rate
parameters is set to 0 (step response off)
and the first digit (amount of filtering) is
adjusted to provide acceptable rate
display stability. The second digit should
then be increased until acceptable rate
display stability is once again achieved.
To adjust the filter parameters select
FiLtEr from the main menu and press
( to reveal the current setting. The first
digit will be flashing and may be adjusted
using the & or * button. The
( button will transfer control to the
second digit. When both are set as
required, return to the FiLtEr prompt in
the main menu by pressing ).
Note: While adjusting the filter, the rate is
shown on the lower display so that
stability can be assessed.
Step 11
Direction of count
In this application the direction of count
will determine whether a cable
movement is shown as a positive or
negative position and rate. If input A
occurs before input b, a positive display
will result when the BA368E is configured
to count up.
Select uP or dn from the main menu and
press ( to reveal the existing setting.
Using the & or * button select uP
followed by ) to enter the selection and
return to the configuration menu.
33
Step 12 Turn local clear off
In this example the operator must not be
able to zero the total (cable position)
display or the grand total from the
instrument front panel. Both local clear
functions should therefore be turned off.
Select LoC CLr from the main menu and
press ( which will result in Clr tot
being displayed, press ( again to show
if the function is turned on or oFF. Using
the & or * button toggle the display to
oFF and press ) to return to the Clr tot
prompt from which Clr Gtot can be
selected by pressing the & or *
button. Turn this function off in exactly
the same way before returning to the
configuration menu by pressing the )
button twice.
Step 13 Define the security code
Defining an access security code
prevents unauthorised access to the
configuration menu. Select CodE in the
configuration menu and press ( which
will reveal the existing security code with
the first digit flashing. Using the & and
* buttons enter the new code 1209 digit
by digit. The ( button transfers control
between digits. When the new code has
been entered, press ) to return to the
configuration menu.
Step 14 Return to the display mode
Following completion of configuration,
return the BA368E to the display mode
by pressing ). The instrument will
display dAtA followed by 5AVE while the
configuration changes are stored in
permanent memory.
34
9.1 Fault finding during commissioning
If a BA368E Counter fails to function during
commissioning the following procedure should be
followed:
Symptom
Cause
Check:
No display
No power supply,
or incorrect
wiring.
Note: Terminals 2,
6, 10 & RS2 are
interconnected
within the
instrument.
That there is
between 10 and
28V on terminals
1 & 2 with
terminal 1
positive.
Counter is
receiving power
but pulse input
indicator not
rotating.
No input pulses,
incorrect input
configuration,
incorrect linking of
terminals 3 & 4
and
terminals 7 & 8.
Input
configuration.
Linking of
terminals 3 & 4.
and
terminals 7 & 8.
That input signal
polarity is correct.
Pulse input
indicator rotating
but incorrect rate
display.
Incorrect rate
display calibration
5CALE . r
t-bA5E
Pulse input
indicator rotating
but incorrect total
display.
Incorrect total
display
calibration.
Remote reset
switch contacts
closed.
5CALE . t
That RESET
annunciator on
display is not
activated. If it is,
check reset wiring
and switch.
Pulse input
indicator rotating
but total display
showing
9.9.9.9.9.9.9.9
or
-9.9.9.9.9.9.9
Or if shown on
the lower display
9.9.9.9.9.9
or
-9.9.9.9.9
Total display has
overflowed.
Reposition
decimal point in
total display or
enter a different
5CALE . t
to reduce total
display
magnitude.
Unstable rate
display
Noisy pulse input
signal
Eliminate source
of electrical noise.
Increase
debounce and/or
display filter.
Unable to enter
configuration
menu.
Incorrect security
code
That the correct
security code is
being used.
Contact BEKA if
code is lost.
Alarms do not
function
Alarms have been
disabled following
calibration
change.
Re-enable both
alarms.
9.2 Fault finding after commissioning
ENSURE PLANT SAFETY BEFORE
STARTING MAINTENANCE
Live maintenance is permitted on
intrinsically safe equipment installed in a
hazardous area, but only certified test
equipment should be used unless a gas
clearance certificate is available.
If a BA368E Counter fails after it has been
functioning correctly, the following table may help to
identify the cause of the failure.
Symptom
Cause
Check:
No display
No power supply.
That there is
between 10 and
28V on terminals
1 & 2
Pulse input
indicator not
rotating.
No input pulses
Output from
sensor.
Wiring between
sensor and
BA368E Counter.
Unstable rate
display
Noisy pulse input
signal
Locate source of
electrical noise, or
increase
debounce and
rate display filter.
If this procedure does not reveal the cause of the
fault, it is recommended that the instrument is
replaced.
9.3 Servicing
We recommend that faulty BA368E Counters are
returned to BEKA associates or to our local agent for
repair.
9.4 Routine maintenance
The mechanical and electrical condition of the
instrument should be regularly checked. Initially
annual inspections are recommended, but the
inspection frequency should be adjusted to suit the
environmental conditions.
9.5 Guarantee
Instruments which fail within the guarantee period
should be returned to BEKA associates or our local
agent. It is helpful if a brief description of the fault
symptoms is provided.
9.6 Customer comments
BEKA associates is always pleased to receive
comments from customers about our products and
services. All communications are acknowledged and
whenever possible, suggestions are implemented.
35
10.1 Scale card
The BA368E Counter has a window on the right
hand side of the display through which a scale card
showing the units of measurement such as metres is
visible. New Counters are fitted with a scale card
showing the units of measurement specified when
the instrument was ordered, if the units are not
specified a blank scale card will be fitted. A pack of
scale cards pre-printed with common units of
measurement is available as an accessory. These
can easily be fitted on-site to the Counter without
opening the instrument enclosure or removing it from
the panel, See section 5.4 of this instruction
manual.
Custom scale cards for applications requiring less
common units of measurement are also available.
10.2 Tag information
New Counters can be supplied with a tag number or
application information thermally printed onto the
rear panel adjacent to the terminals. This
information is not visible from the front of the
instrument after installation.
10.3 Alarms
The BA368E Counter can be supplied with factory
fitted dual alarms. Each may be independently
configured as a rate display or total display, high or
low alarm. with a normally open, or a normally
closed solid state output.
Configurable functions for each alarm include
adjustable setpoint, alarm delay time and alarm
silence time. Hysteresis may be applied to rate
alarms.
WARNING
These alarm outputs should not be used
for critical safety applications such as a
shut down system.
When the BA368E power supply is turned off or
disconnected, alarm outputs will open irrespective of
whether normally open or normally closed outputs
have been selected. When designing a system an
open output should therefore be chosen for the
alarm condition.
Alarm annunciators on the instrument display
indicate the status of each alarm. If an alarm delay
or silence time has been selected the annunciator
will flash during the delay or silence period.
The BA368E internal counters are up-dated and
compared with the alarm setpoint twice per second,
irrespective of the display update time selected.
This may result in an alarm being delayed for up to
half a second after the rate or total has exceeded the
setpoint.
10.3.1 Solid state output
Each alarm has a galvanically isolated single pole
solid state switch output as shown in Fig 14. The
outputs are polarised and current will only flow in
one direction. Terminals A1 and A3 should be
connected to the positive side of the supply.
Ron
=
less than 5 + 0.7V
Roff
=
greater than 1M
Note: Because of the series protection diode some
test meters may not detect a closed alarm
output
Fig 14 Equivalent circuit of each alarm output
10.3.2 Intrinsic safety
Each alarm output is a separate galvanically isolated
intrinsically safe circuit with output safety parameters
complying with the requirements for
simple
apparatus. This allows the alarm output terminals
A1 & A2 and A3 & A4 to be connected to almost any
intrinsically safe circuit protected by a Zener barrier
or galvanic isolator providing the output parameters
of the circuit do not exceed:
Uo
28V dc
Io
200mA
Po
0.84W
The maximum equivalent capacitance and
inductance between each set of alarm terminals is:
Ci
=
22nF
Li
=
4µH (Effectively 0)
36
To determine the maximum permissible cable
parameters Ci should be subtracted from the
maximum permitted external capacitance Co
specified by the certificate for the intrinsically safe
interface powering the alarm circuit, such as the
solenoid driver and switch transfer galvanic isolators
shown in Fig 15
Fig 15 Typical alarm application
10.3.3 Summary of configuration functions
When a BA368E Counter is supplied with alarms the
configuration menu is extended as shown in Fig 16.
The alarm functions appear after LoC clr, each
alarm may be configured to operate on the rate or
total display.
For simplicity Fig 16 only shows the configurable
functions on the rate option of alarm AL1, the total
option is identical except that the total alarms can
not have hysteresis. Configuration of alarm AL2 is
identical to alarm AL1.
The following table summarises each of the alarm
configuration functions and includes a cross
reference to more detailed information. Again only
the functions on alarm AL1 are listed.
Display Summary of function
EnbL
Alarm enable
Enables or disables the alarm without
changing the alarm parameters.
See section 10.3.4
tYPE
Type of alarm
Defines whether the alarm operates on
the rate or total display.
See section 10.3.5
5P1r
Alarm setpoint 1
or
Adjusts the alarm setpoint. The
5P1t
alarm is activated when the rate or
total display equals the setpoint.
Note: 5P1r is displayed for a rate alarm
and 5P1t for a total alarm.
See section 10.3.6
HI. LO
Alarm function
Defines whether the alarm has a high or
low function.
See section 10.3.7
no . nc
Normally open or normally closed
output.
Determines whether the single pole
alarm output is open or closed in the
non-alarm condition.
See section 10.3.8
H5tr
Hysteresis
Adjusts the alarm hysteresis. Only
available on a rate alarm.
See section 10.3.9
dELA
Alarm delay time
Adjusts the delay between the display
equaling the setpoint and the alarm
output being activated.
See section 10.3.10
5IL
Alarm silence time
Defines the time that the alarm output
remains in the non-alarm condition
following acceptance of an alarm.
See section 10.3.11
FL5H
Flash display when alarm occurs
When enabled, alternates the rate or
total display between process value and
alarm reference AL1 or AL2 when an
alarm output is activated.
See section 10.3.12
AC5P
Access setpoint
Sub-menu that enables direct access to
the alarm setpoints from the display
mode and defines a separate security
code.
See section 10.3.13
37
10.3.4 Alarm enable: EnbL
This function allows the alarm to be enabled or
disabled without altering any of the alarm
parameters. Using the & or * push button select
AL1 or AL2 from the configuration menu and press
( to reach EnbL in the alarm sub-menu. Pressing
( will then reveal the existing setting. The function
can be changed by pressing the & or * push
button followed by the ) button to return to the
alarm sub-menu.
10.3.5 Type of alarm: tYPE
Alarm 1 and Alarm 2 are totally independent, both
may be rate or total alarms, or one may be
conditioned for rate and the other for total.
Using the & or * push button select tYPE from the
selected alarm sub-menu and press ( to check or
change the function. The & or * push button will
toggle the selection between rAtE and totAL, when
set as required press the ) button to return to the
alarm sub-menu.
Note:
When
tYPE
is changed, the alarm
configuration is automatically reset to the
default values and the alarm is disabled. It
must therefore be reconfigured before use.
38
10.3.6 Setpoint adjustment: 5P1x & 5P2x
The rate alarm setpoints SP1r and SP2r may be
positioned anywhere between 000000 and 999999,
and the total alarm setpoint SP1t and SP2t
anywhere between 00000000 and 99999999.
All the setpoints are adjusted in the same way, for
example, to adjust the setpoint of Alarm 1 which has
been configured to operate on the rate display.
Using the & or * push button select 5P1r in the
AL1 sub-menu and press ( which will reveal the
existing setpoint with one digit flashing. The
required setpoint can be entered using the & or *
push button to adjust the flashing digit and the
( button to transfer control to the next digit. When
set as required press ) to enter the value and
return to the 5P1r prompt in the alarm 1 sub-menu.
10.3.7 Alarm function: Hi. Lo
Alarm 1 and Alarm 2 are totally independent, both
may be Hi or Lo, or one may be conditioned as a Hi
alarm and the other as a Lo alarm.
Using the & or * push button select Hi. Lo from
the selected alarm sub-menu and press ( to check
or change the function. The & or * push button
will toggle the alarm function between Hi and Lo,
when set as required, press the ) button to return
to the Hi. Lo prompt in the alarm sub-menu.
10.3.8 Alarm output status: no . nC
Each single pole alarm output may be open or
closed in the non-alarm condition. When the
BA368E power supply is turned off or disconnected,
the alarm output(s) will open irrespective of whether
normally open or normally closed outputs have been
selected. Therefore, when designing an alarm
system normally closed nc should be selected so
that the output opens when an alarm occurs or if the
power supply fails.
Using the & or * push button select no . nC from
the selected alarm sub-menu and press ( to check
or change the function. The & or * push button
will toggle the contact status between no and nC,
when set as required, press the ) button to return
to the no . nC prompt in the alarm sub-menu
10.3.9 Hysteresis: H5tr
Hysteresis is only available on rate alarms so the
H5tr function only appears in the configuration sub-
menu when alarm tYPE has been set to rAtE. During
configuration hysteresis is shown in the units of rate
previously configured for the rate display.
Using the & or * push button select H5tr in the
selected alarm sub-menu and press ( which will
reveal the existing hysteresis with one digit flashing.
The required hysteresis can be entered using the &
or * push button to adjust the flashing digit and the
( button to transfer control to the next digit. When
set as required press ) to enter the value and
return to the H5tr prompt in the alarm sub-menu.
e.g. A BA368E Counter configured to display a rate
of 0 to 5000, with a high alarm set at 4000 and
hysteresis of 100 will perform as follows:
High alarm will be activated when rate
equals or exceeds 4000, but will not reset
until the rate falls below 3900.
10.3.10 Alarm delay: dELA
This function enables activation of the alarm output
to be delayed for a fixed time following the alarm
condition occurring. The delay can be set in 1
second increments up to 3600 seconds. If a delay is
not required zero should be entered.
To adjust the delay select dELA using the & or *
push button in the selected alarm sub-menu and
press ( which will reveal the existing delay time in
seconds with one digit flashing. The required delay
time can be entered using the & or * push button
to adjust the flashing digit and the ( button to
transfer control to the next digit. When set as
required press ) to enter the value and return to
the dELA prompt in the alarm sub-menu.
The alarm annunciator will start flashing immediately
an alarm condition occurs and will continue for the
delay time, after which the alarm output will be
activated and the alarm annunciator will be
permanently activated.
10.3.11 Alarm silence time: 5IL
The alarm silence function is primarily intended for
use in small installations where the alarm output
directly operates an annunciator such as a sounder.
When the alarm silence time is set to any figure
other than zero, the ( push button becomes an
alarm accept button.
After an alarm has occurred, operating the
( button will cause the alarm output to revert to the
non-alarm condition for the alarm silence time.
When an alarm is silenced the alarm annunciator will
flash until the silence time expires.
To adjust the alarm silence time select 5iL using the
& or * push button in the selected alarm sub-
menu and press ( which will reveal the existing
alarm silence time in seconds with one digit flashing.
The required silence time can be entered using the
& or * push button to adjust the flashing digit and
the ( button to transfer control to the next digit.
When set as required press ) to enter the value
and return to the 5iL prompt in the alarm sub-menu.
39
10.3.12 Flash display when alarm occurs:
FL5H
In addition to the two alarm annunciators on the left
hand side of the BA368E Counter display which
show the status of both alarms, this function
provides an even more conspicuous indication that
an alarm has occurred.
When enabled, this function alternates the rate or
total display between the numerical value and the
alarm identification AL1 or AL2 when an alarm
occurs.
Using the & or * push button select FL5H from the
selected alarm sub-menu and press ( to check or
change the function. The & or * push button will
toggle the function between oFF and on, when set as
required, press the ) button to return to the FL5H
prompt in the alarm sub-menu.
10.3.13 Access Setpoint: AC5P
This function activates a separate menu that
provides direct access to the alarm setpoints from
the display mode by simultaneously operating the
( and * buttons. An operator can therefore
adjust the alarm setpoints without having access to
the configuration and alarm sub-menus. Protection
against unauthorised or accidental adjustment is
provided by a separate security access code.
Using the & or * push button select AC5P from the
configuration menu and press ( to reach the
enable function EnbL. Pressing ( will reveal the
existing setting which can be toggled between on
and oFF by pressing the & or * push button.
When set as required, press the ) button to return
to the EnbL prompt from which a separate security
access code can be entered using the ACCd function
which can be selected using the & or * push
button.
To enter a new security code select ACCd from the
sub-menu and press ( which will cause the
BA368E Counter to display 0000 with one digit
flashing. The flashing digit may be adjusted using
the & or * push button, when set as required
operating the ( button will transfer control to the
next digit. When all the digits have been adjusted
press ) to return to the ACCd prompt. The revised
security code will be activated when the BA368E
Counter is returned to the display mode. Default
security access code 0000 will disable the security
code allowing direct access to the setpoints in the
display mode by pressing the ( and * buttons
simultaneously.
Please contact BEKA associates sales department if
the security code is lost.
10.3.14 Adjusting alarm setpoints from the
display mode
Access to the two alarm setpoints from the BA368E
Counter’s display mode is obtained by operating the
( and * push buttons simultaneously as shown in
Fig 17. If the setpoints are not protected by a
security code the alarm setpoint prompt 5P1r or
5P1t will be displayed depending upon whether a
rate or total alarm has been configured. If the
setpoints are protected by a security code, CodE will
be displayed first. Pressing ( again will allow the
alarm setpoint security code to be entered digit by
digit using the & and * buttons to adjust the
flashing digit and the ( push button to move
control to the next digit. If the correct code is
entered pressing ) will then cause alarm setpoint
prompt 5P1x to be displayed. If an incorrect security
code is entered, or a button is not pressed within ten
seconds, the instrument will automatically return to
the display mode.
Once within the menu pressing the & or * buttons
will toggle the display between the two alarm
setpoint prompts 5P1x and 5P2x.
Fig 17 Setpoint adjustment from the display mode
40
To adjust an alarm setpoint select 5P1x or 5P2x and
press ( which will reveal the current setting. The
flashing digit of the setpoint may be adjusted using
the & or * push button and the ( button to
move control to the next digit. When the required
setpoint has been entered, pressing ) will return
the display to the 5P1x or 5P2x2 prompt from which
the other setpoint may be selected, or the instrument
may be returned to the display mode by pressing )
again.
Note: Direct access to the alarm setpoints from the
display mode is only available when the
AC5P menu is enabled - see section 10.3.13
10.4 Display backlight
The BA368E Counter can be supplied with a factory
fitted backlight that produce green illumination
enhancing display contrast and enabling it to be read
at night or in poor lighting conditions. The backlight
is internally powered from the instrument power
supply so that no additional wiring or intrinsically
safe interface is required, but the supply current
increases as shown below.
BA368E
Maximum
current
consumption
Without backlight
10mA
Additional for backlight
16mA
Addition with terminals 3 & 4 linked
6mA
Addition with terminals 7 & 8 linked
6mA
----------
Total current
38mA max
10.5 4/20mA output
The BA368E Counter can be supplied with an
optional factory fitted galvanically isolated 4/20mA
output which may be configured to represent the rate
or total display.
10.5.1 Intrinsic safety
The 4/20mA output has been certified as a separate
galvanically isolated intrinsically safe circuit
complying with the requirements for
simple
apparatus. This allows terminals C1 and C3 to be
connected to any intrinsically safe circuit protected
by a certified Zener barrier or galvanic isolator
providing the output parameters do not exceed:
Uo
=
28V dc
Io
=
200mA
Po
=
0.84W
The maximum equivalent internal capacitance and
inductance of the 4/20mA output is:
Ci
=
2.2nF
Li
=
4µH
To determine the maximum permissible cable
parameters, these figures should be subtracted from
the maximum cable capacitance and inductance
specified by the certificate for the Zener barrier or
galvanic isolator powering the 4/20mA output circuit.
10.5.2 System design
The BA368E Counter 4/20mA output is a passive
current sink i.e. not powered, but it is totally isolated
from all other Counter circuits. It is effectively a
2-wire 4/20mA transmitter requiring a minimum
supply of 10V with its current being controlled by the
BA368E Counter. Subject to complying with intrinsic
safety interconnection requirements, the terminals
C1 and C3 may be directly connected to another
instrument located in the same hazardous area
which will accept a 4/20mA transmitter input. The
4/20mA current output may also be transferred to the
safe area via a galvanic isolator or Zener barriers.
Fig 18 shows how a 2-channel Zener barrier may be
used to transfer the 4/20mA current output into the
safe area, alternatively a galvanic isolator may be
used.
41
Fig 18 Application of 4/20mA output
10.5.3 Configuration and calibration
When a BA368E Counter is supplied with an
optional 4/20mA output the configuration menu is
extended as shown in Fig 19. The 4/20mA output
sub-menu is accessed via the 4-20 oP function.
The 4/20mA output sub-menu allows the 4/20mA
output to be controlled by the rate or the total
display.
Fig 19 4/20mA output configuration sub-menu
10.5.4 Access 4/20mA output sub-menu: 4-20 oP
Access the BA368E Counter configuration menu as
described in section 6.2. Using the & and * push
buttons scroll though the menu until 4-20 oP is
displayed, pressing ( will then access the 4/20mA
output sub-menu which is shown in Fig 19.
10.5.5 Enable 4/20mA output: EnbL
This function allows the 4/20mA output to be
disabled or enabled without altering any of the
4/20mA output parameters. Using the & or *
push button select EnbL in the 4-20 oP sub-menu
and press ( to reveal the existing setting on or oFF.
The function can be changed by pressing the & or
* push button followed by the ) button to return
to EnbL prompt.
Note:
When the 4/20mA output is disabled by
selecting oFF, the output is a constant
3.5mA irrespective of the instrument
display.
10.5.6 Select rate or total source: 4-20tYPE
The 4/20mA output current can represent the
BA368E Counter’s rate or total display and this must
be defined before any other 4/20mA current output
functions are configured.
Using the & or * push button select 4-20tYPE in
the 4/20mA output sub-menu and press ( to reveal
the existing setting totAL or rAtE. The function can
be changed by pressing the & or * push button
followed by the ) button to return to 4-20tYPE
prompt.
Note:
If the controlling source of the 4/20mA
output is changed i.e. from rate to total, the
4/20mA output will be disabled and the
output will be a constant 3.5mA
irrespective of the instrument display.
The 4/20mA output must always be re-
enabled and reconfigured following the
controlling source being changed.
10.5.7 Display which corresponds to 4mA
output: 4 . 000
The BA368E Counter display which corresponds to
a 4.000mA output current is defined by this function.
Using the & or * push button select 4 . 000 in the
4/20mA output sub-menu and press ( to reveal the
existing rate or total display with one digit flashing.
The required display can be entered using the
& or * push button to adjust the flashing digit and
the ( button to transfer control to the next digit.
When set as required press ) to enter the value
and return to the 4 . 000 prompt in the 4/20mA output
sub-menu.
42
10.5.8 Display which corresponds to 20mA
output: 20.000
The BA368E Counter display which corresponds to
20.000mA output current is defined by this function.
Using the & or * push button select 20 . 000 in the
4/20mA output sub-menu and press (. to reveal
the existing rate or total display with one digit
flashing. The required display can be entered using
the & or * push button to adjust the flashing digit
and the ( button to transfer control to the next
digit. When set as required press ) to enter the
value and return to the 20 . 000 prompt in the 4/20mA
output sub-menu.
Note:
If the BA368E Counter and the 4/20mA
current sink output are powered from
separate supplies, the 4/20mA output
current will continue to flow when the
BA368E Counter supply fails or is turned
off. Powering both from a common supply
eliminates this effect.
43
Appendix 1 IECEx Certification
A1.1 IECEx Certificate of Conformity
The BA368E Counter has been issued with an
IECEx Certificate of Conformity number
IECEx ITS 16.0004X which specifies the following
certification code:
Ex ia IIC T5 Ga
-40ºC ≤ Ta ≤ +70ºC
The IECEx certificate may be downloaded from
www.beka.co.uk, www.iecex.com or requested from
the BEKA sales office.
A1.2 Installation
The IECEx intrinsic safety parameters are identical
to the ATEX safety parameters described in the main
section of this manual and both refer to the same
standards.
Therefore the ATEX installation
requirements specified in section 5 of this manual
may be used for IECEx installations, but the local
code of practice should also be consulted.
A1.3
Special conditions for safe use
The IECEx Certificate of Conformity number has an
'X' suffix indicating that special conditions apply to
prevent an electrostatic charge developing on the
outside of the instrument enclosure.
WARNING
To avoid an electrostatic charge being
generated instrument enclosure should
only be cleaned with a damp cloth.
44
Appendix 2 ETL & cETL certification for
installations in USA and Canada
A2.0 cETL Mark
For installations in the USA and Canada, the
BA368E Two Input Counter has ETL and cETL
intrinsic safety and nonincendive approval, Control
Number 4008610. Copies of the Authorisation to
Mark are available from the BEKA associates sales
office and www.beka.co.uk
A2.1 Intrinsic safety approval
The US and Canadian standards used for
assessment and certification of the BA368E Two
Input Counter are listed on the cETL Authorisation to
Mark.
Installations must comply with BEKA associates
Control Drawing CI330-52, which is attached to this
appendix.
The ETL safety parameters are the same as the
ATEX and IECEx parameters, the systems shown in
sections 3 and 4 of this manual may therefore also
be used for US and Canadian installations subject to
compliance with the local codes of practice.
ETL and cETL intrinsic safety codes
CL I Div 1 Groups A, B, C, D T5 (US IS gas, Div cert)
CL II Div 1 Groups E, F, G. CL III (US IS dust, Div cert)
CL I Zone 0 AEx ia IIC T5 Ga (US IS gas, Zone cert)
Ex ia IIC T5 Ga (Canadian IS gas, Zone cert)
-40ºC Ta 70ºC
A2.2 Nonincendive approval
The BA367E Counter also has ETL nonincendive
approval allowing installation in Division 2 hazardous
(classified) locations without the need for Zener
barriers or galvanic isolators.
Installations must comply with BEKA associates
Control Drawing CI330-53, which is attached to this
appendix, and with the local codes of practice.
ETL and cETL nonincendive codes US & Canada
CL I Div 2 Groups A, B, C, D T5
CL II Div 2 Groups F, G CL III Div 2
-40ºC Ta 70ºC
45