Basler BE1-81 Instruction Manual
Read Online
Read the Basler BE1-81 Instruction Manual online using the built-in PDF viewer.
Text of the manual
������������������
���
����������������������������
������������
������������
�������������
���������
�
�����
W A R N I N G !
To avoid personal injury or equipment damage, only
qualified personnel should perform the procedures
presented in this manual.
������������
This Instruction Manual provides information concerning the
operation and installation of the BE1-81 Digital Underfrequency Relay.
To accomplish this, the following is provided.
� Specifications
� Functional Characteristics
� Mounting Information
� Connections
� Testing
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. IT IS LOANED FOR
CONFIDENTIAL USE, SUBJECT TO RETURN ON REQUEST, AND WITH THE
MUTUAL UNDERSTANDING THAT IT WILL NOT BE USED IN ANY MANNER
DETRIMENTAL TO THE INTEREST OF BASLER ELECTRIC COMPANY.
First Printing: October 1979
Printed in USA
© 1995, Basler Electric Co., Highland, IL 62249
May 1996
It is not the intention of this manual to cover all details and variations
in equipment, nor does this manual provide data for every possible
contingency regarding installation or operation. The availability and
design of all features and options are subject to modification without
notice. Should further information be required, contact Basler
Electric Company, Highland, Illinois.
BASLER ELECTRIC, BOX 269 HIGHLAND, IL 62249 USA
PHONE 618-654-2341
FAX 618-654-2351
SECTION 1 GENERAL INFORMATION
1-1
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Definite Time Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Inverse Time Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Relay Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Model and Style Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Sample Style Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Style Number Identification Chart
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
SECTION 2 CONTROLS AND INDICATORS
2-1
SECTION 3 FUNCTIONAL DESCRIPTION
3-1
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Power Supply Status Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Voltage Inhibit Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Input Conditioning Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Crystal Reference Oscillator
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Synchronizer Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Reference Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Period Difference Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Period Difference To Frequency Difference Circuit . . . . . . . . . . . . . . . . . . 3-3
Threshold Setting Comparator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Definite Time Delay Circuit (Timing Option E1) . . . . . . . . . . . . . . . . . . . . . 3-3
Inverse Time Delay Circuit (Timing Option D1) . . . . . . . . . . . . . . . . . . . . . 3-3
Relay Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Internally Operated Target Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Current Operated Target Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Target Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
SECTION 4 INSTALLATION
4-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Relay Operating Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Dielectric Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Relay Mounting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
S1 Case, Panel Drilling Diagram, Semi-Flush Mounting . . . . . . . . . . . . . . 4-2
S1 Case, Outline Dimensions, Front View . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
S1 Case, Single-Ended, Semi-Flush Mounting, Side View . . . . . . . . . . . . 4-3
S1 Case, Single-Ended, Semi-Flush Mounting, Outline Dimensions . . . . . 4-4
S1 Case, Single-Ended, Projection Mounting, Panel Drilling Diagram . . . . 4-5
S1 Case, Single-Ended, Projection Mounting, Rear View . . . . . . . . . . . . . 4-6
S1 Case, Single-Ended, Projection Mounting, Side View
. . . . . . . . . . . . . 4-7
S1 Case, Double-Ended, Semi-Flush Mounting, Side View . . . . . . . . . . . . 4-8
S1 Case, Double-Ended, Semi-Flush Mounting, Outline Dimensions . . . . 4-9
SECTION 4 INSTALLATION - Continued
Relay Mounting - Continued
S1 Case, Double-Ended, Projection Mounting, Panel Drilling Diagram . . . 4-10
S1 Case, Double-Ended, Projection Mounting, Rear View . . . . . . . . . . . . . 4-11
S1 Case, Double-Ended, Projection Mounting, Side View . . . . . . . . . . . . . 4-12
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
AC Sensing Input Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
DC Control Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Internal Connections, Style Number T?E ?1? A0S5? . . . . . . . . . . . . . . . . . 4-15
Internal Connections, Style Number T?E ?1C A2S5?
. . . . . . . . . . . . . . . . 4-16
SECTION 5 TESTING
5-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Test Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Definite Time Delay (Option E1) Test Procedure . . . . . . . . . . . . . . . . . . . . . . . 5-2
Inverse Time Delay (Option D1) Test Procedure
. . . . . . . . . . . . . . . . . . . . . . . 5-3
SECTION 6 MAINTENANCE
6-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
In-House Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Test Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
SECTION 7 Manual Change Information
7-1
BE1-81 Digital Underfrequency Relays are single-phase, solid-state, protective devices designed to
detect an underfrequency condition and provide an output to actuate external control circuits and/or
alarms. Both 50 hertz and 60 hertz styles are available with either definite time delay or inverse time
delay characteristics.
DESCRIPTION
BE1-81 relays compare the frequency of the applied voltage with a crystal oscillator reference frequency.
When the measured frequency is less than a preset level for a predetermined period of time, external
control circuits and/or alarms are actuated by the relay.
Definite Time Option
Definite time option trip frequency settings are set by three front panel thumbwheel switches. Setting
ranges are between 0.05 and 5.00 hertz in 0.05 hertz increments below nominal system frequency. The
delay time (measured in cycles of the underfrequency waveform) is set by two front panel thumbwheel
switches. Delay ranges are from 01 to 99 cycles. The actual trip time is the delay time setting, plus one
cycle.
Inverse Time Option
Inverse time option trip frequency settings are also set by three front panel thumbwheel switches and the
ranges are from 0.05 to 5.00 hertz in 0.05 hertz increments below nominal system frequency. The
inverse time delay characteristic is inversely proportional to the magnitude of the frequency difference
between the measured waveform and the trip frequency setting. This time may be adjusted to
correspond to a particular characteristic curve by a continuously adjustable front panel time dial. (Refer
to Figures 1-1 and 1-2.)
Relay Assembly
The relay assembly is mounted in a drawout cradle and enclosed in a standard, utility style, semi-flush
case. Individual circuit components are accessible by removal of the individual printed circuit boards
from the relay cradle and using an extender card (Basler part number 9 1655 00 100) to test or
troubleshoot. A front panel, electrically operated, manually reset target may be selected to indicate that a
fault has occurred and the relay has operated. A wide range of options permits the relay to be
specifically tailored to a variety of applications.
MODEL AND STYLE NUMBER DESCRIPTION
BE1-81 Digital Underfrequency Relays electrical characteristics and optional features are defined by a
combination of letters and numbers that make up its style number. The model number, together with the
style number, describe the options included in a specific device, and appear on the front panel, drawout
cradle, and inside the case assembly. Upon receipt of a relay, be sure to check its style number against
the requisition and packing list, to see that they agree.
BE1-81 General Information
1-4
Sample Style Number
Style number identification chart (Figure 1-3) defines the electrical characteristics and operational
features included in BE1-81 relays. For example, if the style number were T1E-E1C-A0N0F, the device
would have the following:
(T)
Single phase sensing input type
(1)
120 Vac, 60 hertz nominal sensing input range
(E)
One normally open relay output
(E1) Definite time delay
(C)
Internal operating power obtained from 125 Vdc or 100/120 Vac - external source
(A)
One internally operated target
(0)
Internal relay operating power independent of sensed voltage
(N)
No Option 2 available
(0)
No auxiliary output
(F)
Semi-flush mounting
Figure 1-3. Style Number Identification Chart
BE1-81 General Information
1-5
SPECIFICATIONS
Power Input
One of the six types of power supplies listed in Table 1-1 may be optionally
selected to provide internal relay operating power.
Table 1-1. Power Supply Options
Frequency Sensing Input
Input sensing circuits are nominally rated 120 Vac at the selected
frequency. Relay trip points may be manually set for a single-phase
underfrequency trip point from 45 to 50 hertz for the 50 hertz styles, or 55
to 60 hertz for the 60 hertz styles. Both styles are adjustable in 0.05 hertz
increments.
Sensing Burden
Burden of the frequency sensing input is 2 VA for 50 hertz styles, and 1 VA
for 60 hertz styles.
Target Indicators
Function targets may be specified as either internally operated, or current
operated by a minimum of 0.2 ampere through the output trip circuit. When
current operated, the output circuit must be limited to 30 amperes for 0.2
seconds, 7 amperes for 2 minutes, and 3 amperes continuously. Internally
operated targets must be specified if the breaker control (trip) circuit is ac
powered.
Reset Time
Reset is automatic and instantaneous when frequency increases above
selected pickup setting. (Target must be manually reset.)
Pickup Setting
Pickup setting is adjusted in Hertz-below-nominal-frequency in 0.05 hertz
steps, using three front panel thumbwheel switches.
Pickup Accuracy
The relay will pickup and check timing within 0.030 hertz of the trip point in
a 60 hertz system, and within 0.035 hertz in a 50 hertz system.
BE1-81 General Information
1-6
Dropout Ratio
99 percent of pickup value (frequency difference).
Temperature Stability
Pickup point variation will not exceed 0.03 hertz over the operating
temperature range.
Undervoltage Inhibit
The relay is factory adjusted for an 80 Vac undervoltage inhibit level that
prevents nuisance tripping during protected equipment start-up. This level
may be internally adjusted by the user for inhibit levels between 40 and
120 Vac except for relays using option 1-2, Sensing Input Power Supply.
Output Circuits
Output contacts are rated as follows:
Resistive:
120/240 Vac
Make 30 amperes for 0.2 seconds, carry 7 amperes continuously, and
break 7 amperes.
250 Vdc
Make and carry 30 amperes for 0.2 seconds, carry 7 amperes
continuously, and break 0.3 amperes.
500 Vdc
Make and carry 15 amperes for 0.2 seconds, carry 7 amperes
continuously, and break 0.1 amperes.
Inductive:
120/240 Vac,
Make and carry 30 amperes for 0.2 seconds, carry 7 amperes continuously,
125/250 Vdc
and break 0.3 amperes. (L/R = 0.04).
Isolation
1500 Vac at 60 hertz for one minute in accordance with IEC 255-5 and
ANSI/IEEE C37.90-1989 (Dielectric Test).
Radio Frequency
Maintains proper operation when tested for interference in accordance with
Interference (RFI)
ANSI/IEEE C37.90-1989, Trial-Use Standard Withstand Capability of Relay
Systems to Radiated Electromagnetic Interference from Transceivers.
UL Recognized
UL Recognized per Standard 508, UL File No. E97033. Note: Output
contacts are not UL Recognized for voltages greater than 250 volts.
Surge Withstand Capability
Qualified to ANSI/IEEE C37.90.1-1989 Standard Surge Withstand Capabil-
ity (SWC) Tests for Protective Relays and Relay Systems.
Operating Temperature
-20�C (-4�F) to +65�C (+149�F).
Storage Temperature
-50�C (-58�F) to +90�C (+194�F).
Shock
In standard tests, the relay has withstood 15 g in each of three mutually
perpendicular planes without structural damage or degradation of perfor-
mance.
Vibration
In standard tests, the relay has withstood 2 g in each of three mutually per-
pendicular planes, swept over the range of 10 to 500 Hz for a total of six
sweeps, 15 minutes each sweep, without structural damage or degradation
of performance.
Weight
10.5 pounds net.
Case Size
S1. Dimensions shown in Section 4, Installation.
CONTROLS AND INDICATORS
GENERAL
Table 2-1 lists and describes the controls and indicators of BE1-81 Digital Underfrequency Relays.
Table 2-1. Controls and Indicators (Refer to Figures 2-1 and 2-2)
Letter
Control or Indicator
Function or Indicator
A
DELAY CYCLES switches
(Option E1 only)
Two thumbwheel switches set the time delay (measured
in cycles of the underfrequency waveform. The time
delay range is from 01 to 99 cycles. False tripping may
occur if the delay is set below 3 cycles. Also, the relay will
not function if these switches are set at 00.
B
POWER LED
LED lights to indicate that the relay power supply is
functioning.
C
TRIP FREQUENCY HZ
BELOW 60 HZ switches
Three thumbwheel switches set the trip frequency in
increments of 0.05 hertz, between 45 and 50 hertz
(50 hertz styles) or 55 and 60 hertz (60 hertz styles). The
switch settings then display the frequency (in hertz) below
the nominal system frequency at which the relay trip
threshold is set.
D
Target Reset Lever
Linkage extending through bottom of front cover that
resets magnetically latching target indicators.
E
Target Indicator
Magnetically latching target that indicates that trip current in
excess of 0.2 amperes was present and that the associated
output relay has been energized.
F
TRIP TIME ADJUST Control
(Option D1 only)
Control selects the desired inverse characteristic trip
curve.
Functional circuit descriptions provided in this section apply to both the 50 hertz and 60 hertz
underfrequency relays. Refer to Figure 3-1 for a typical functional block diagram.
Sensing
When single-phase 120 Vac is applied to the sensing input, the input transformer provides the proper
signal levels to the voltage inhibit and input conditioning circuits.
Figure 3-1. Functional Block Diagram
BE1-81 Functional Description
3-2
Power Supply
A variety of power supply options allow a wide range of external voltage inputs for relay operation.
Relay operating power is developed by the low burden, flyback switching design, solid-state power
supply. A nominal plus or minus twelve volts dc is delivered to the internal circuitry. Power supply
inputs are not polarity sensitive. A red LED lights to indicate that the power supply is functioning
properly. The LED circuit is not provided on styles receiving operating power from the sensing input.
Type W power supplies use a field adjustable link (J4) to select the appropriate input voltage (either 48
Vdc or 125 Vdc). Selection is accomplished by placing the link into the desired position (refer to Figure
3-2). This link is factory pre-set for 125 Vdc.
Figure 3-2. J4 Link Positioning
Power Supply Status Contacts
Power supply voltages are monitored on the mother board. Normal supply voltage causes the power
supply status relay to be continually energized. However, if at any time the voltage falls below
requirements, the relay drops out, and closes the normally closed contacts.
Voltage Inhibit Circuit
This circuit prevents the relay from tripping because of transient underfrequency conditions associated
with equipment startup. It inhibits sensing of underfrequency conditions by the synchronizer circuit and
output circuitry until the input sensing voltage is greater than 80 Vac.
Input Conditioning Circuit
The input conditioning circuit converts the sensing voltage to a squarewave whose transitions
correspond to the zero crossings of the input waveform. The resulting squarewave (after further
shaping) is applied to the synchronizer circuit.
Crystal Reference Oscillator
This four megahertz, crystal-controlled oscillator provides an accurate reference for the synchronizer
circuit and the frequency reference circuit.
BE1-81 Functional Description
3-3
Synchronizer Circuit
This circuit synchronizes the squarewave (representative of the input waveform) with the crystal
reference oscillator to generate a synchronized zero crossing pulse. The zero crossing pulse resets the
system timing. Each time this zero crossing pulse occurs, a new frequency comparison is initiated.
Reference Circuit
This circuit generates a reference signal each 16.667 millisecond (60 hertz nominal system frequency)
or 20.000 ms (50 hertz nominal system frequency) after a synchronized zero crossing pulse. This signal
is generated by counting pulses from the reference oscillator. When the proper count is reached, an
output signal is applied to the period difference circuit.
Period Difference Circuit
This circuit initiates a train of pulses beginning with the occurrence of the reference signal and ending
when the synchronized zero crossing pulse occurs. The time span between these two signals is the
difference in period between the sensing input waveform and the nominal system frequency. Each pulse
in the pulse train represents a one microsecond difference in period.
Period Difference To Frequency Difference Circuit
This circuit converts the pulses received from the period difference circuit to one pulse for each 0.05
hertz difference from the nominal frequency. This is accomplished by a variable scale divider which
compensates for the inverse relationship between period and frequency.
Threshold Setting Comparator
This circuit counts the number of pulses coming from the frequency difference circuit and compares it
with the front panel control setting. When the frequency decreases beyond the difference established by
the front control, an output pulse is applied to the appropriate timing circuit.
Definite Time Delay Circuit (Timing Option E1)
The definite time delay circuit counts the number of consecutive cycles of the underfrequency waveform
after the threshold setting comparator output pulse occurs. When the number of underfrequency cycles
equals the front panel time delay setting, a pulse is generated to the output trip circuit. It is
recommended that the time delay control be set for a minimum of three cycles delay to reduce the
possibility of a trip signal caused by transient-generated underfrequency conditions.
Inverse Time Delay Circuit (Timing Option D1)
The inverse time delay circuit uses the magnitude of the underfrequency condition to determine the time
delay. A set of pulses, representative of the magnitude of the underfrequency condition, is applied to an
RC network to generate an inverse time delay. A front panel dial permits adjustment of the time curve
over the applicable 60 hertz or 50 hertz system range. An LED on the front panel indicates that the relay
pickup setting has been exceeded.
Relay Output
Either normally closed or normally open relay output contacts may be selected. An optional set of
auxiliary relay contacts may be specified when the relay auxiliary output option is selected. The relay
contacts remain in the energized condition as long as the sensed input is below pickup.
BE1-81 Functional Description
3-4
Internally Operated Target Driver
Output from the time delay circuit is applied to this circuit to drive the target indicator. The indicator is
tripped regardless of the current level in the trip circuit.
Current Operated Target Driver
This circuit will operate when a minimum dc current of 0.2 amperes flow in the output trip circuit. A
special reed relay in series with the output contact provides the signal to the target indicator.
Target Indicator
The target trip indicator is visible at the front panel. The target is magnetically latched and must be reset
manually after the fault condition has been cleared.
When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to
prevent damage during transit. Immediately upon receipt of a relay, check the model and style number
against the requisition and packing list to see that they agree. Visually inspect the relay for damage that
may have occurred during shipment. If there is evidence of damage, immediately file a claim with the
carrier and notify the Regional Sales Office, or contact the Sales Representative at Basler Electric,
Highland, Illinois.
In the event the relay is not to be installed immediately, store the relay in its original shipping carton in a
moisture and dust-free environment. When relay is to be placed in service, it is recommended that the
operational test procedure (Section 5) be performed prior to installation.
RELAY OPERATING PRECAUTIONS
Before installation or operation of the relay, note the following precautions:
1.
A minimum of 0.2 A in the output circuit is required to ensure operation of current operated
targets.
2.
Do not touch target indicator vanes. Always reset targets by use of the target reset lever.
3.
The relay is a solid-state device. If a wiring insulation test is required, remove the connecting
plugs and withdraw the cradle from its case.
4.
When the connecting plugs are removed, the relay is disconnected from the operating circuit and
will not provide system protection. Always be sure that external operating (monitored) conditions
are stable before removing a relay for inspection, test, or service.
5.
Be sure the relay case is hard wired to earth ground using the ground terminal on the rear of the
unit. It is recommended to use a separate ground lead to the ground bus for each relay.
DIELECTRIC TEST
In accordance with IEC 255-5 and ANSI/IEEE C37.90-1978, one-minute dielectric (high potential) tests
up to 1500 Vac (45-65 hertz) may be performed. This device employs decoupling capacitors to ground
from terminals 3 and 4. Accordingly, a leakage current is to be expected at these terminals.
RELAY MOUNTING
Because the relay is of solid state design, it does not have to be mounted vertically. Any convenient
mounting angle may be chosen. Figures 4-1 through 4-12 provide relay outline dimensions and panel
drilling diagrams.
Figure 4-1. S1 Case, Panel Drilling Diagram, Semi-Flush Mounting
Figure 4-2. S1 Case, Outline Dimensions, Front View
Figure 4-4. S1 Case, Single-Ended, Semi-Flush Mounting, Outline Dimensions, Rear View
Figure 4-5. S1 Case, Single-Ended, Projection Mounting, Panel Drilling Diagram, Rear View
Figure 4-9. S1 Case, Double-Ended, Semi-Flush Mounting, Outline Dimensions, Rear View
Figure 4-10. S1 Case, Double-Ended, Projection Mounting, Panel Drilling Diagram, Rear View
Be sure the relay case is hard-wired to earth ground with no smaller than 12 AWG
copper wire attached to the ground terminal on the rear of the relay case. When the
relay is configured in a system with other protective devices, it is recommended to use
a separate lead to the ground bus from each relay.
CONNECTIONS
Incorrect wiring may result in damage to the relay. Except as noted previously, connections should be
made with minimum wire size of 14 AWG. Typical AC circuit connections are shown in Figure 4-13, and
typical control circuit connections in Figure 4-14. Internal connections are shown in Figures 4-15 and 4-
16.
Terminals 3 and 4 are external relay power supply voltage inputs and are not polarity sensitive. When
the sensing input power supply (Option 1-2) is specified, the power supply is wired directly from the
sensing input terminals by the factory. Terminals 6 and 7 are the frequency sensing inputs.
Figure 4-13. AC Sensing Input Connections
The test setups and procedures contained in this section are suggested for use in verifying or setting the
desired pickup frequency threshold, as well as the time delay parameters, for both the definite and
inverse time delay style of relay. Accuracy of the measurements in these procedures is dependent upon
the stability of the test frequency sources, and the resolution of the frequency and time measuring test
equipment. Functional tests performed with test equipment with an overall accuracy of less than the
accuracy of the relay may be useful to the extent that they verify relay operation and approximate relay
characteristics. However, tests performed under these conditions will not verify or produce calibrations
any better than the test equipment accuracy; as a result, tolerances may be outside of those specified.
TEST SETUP
Figure 5-1 illustrates a test setup using a commercially available frequency test set having frequency
and time generating accuracies exceeding those of the underfrequency relay.
Figure 5-1. Test Setup
With the trip frequency set at the desired pickup threshold, and with the test variable
frequency source output adjusted to the trip frequency, verify/set the desired definite
delay timing of the relay as outlined in the steps below.
Delay time (seconds) � DELAY CYCLES Thumbwheel Setting � 1 Cycle
Applied Trip Frequency
DEFINITE TIME DELAY (OPTION E1) TEST PROCEDURE
To verify/set underfrequency 50 hertz (Style T2) or 60 hertz (Style T1) relays equipped with definite time
delay, perform the following steps.
Step 1.
Connect the relay as shown in Figure 5-1.
Step 2.
Apply appropriate ac or dc voltage to terminals 3 and 4 for relay styles equipped with external
power supply. Apply 120 Vac, 50 hertz or 60 hertz as applicable, at terminals 6 and 7 for
relay styles equipped with sensing input power supply (option 1-2).
Step 3.
Set test frequency select switch to the 50/60 hertz position as applicable.
Step 4.
Set relay front panel TRIP FREQUENCY Hz BELOW (50 or 60) thumbwheel switches for the
desired underfrequency pickup point.
Step 5.
Set front panel DELAY CYCLES thumbwheel switches for a 03 cycle delay.
Step 6.
Adjust variable test frequency source to a frequency above the threshold frequency set in
Step 4.
Step 7.
Set test frequency select switch to the variable position and slowly adjust variable test
frequency source output down toward the pickup threshold until the relay operates. Check
that target indicator, if applicable, has tripped. (Current operated targets require a minimum
of 0.2 amperes dc in the trip circuit for proper operation.)
Step 8.
Read the trip frequency as indicated by the frequency source, or by an external frequency
measuring device. The pickup point should be within 0.035 hertz of the selected pickup
frequency set in Step 4 for the 50 hertz (T2) relays, or 0.030 hertz for the 60 hertz (T1) relays,
or within the accuracy of the test set, whichever is greater. Return test frequency select
switch to the 50/60 hertz position. Reset the target indicator (if supplied).
Step 9.
Repeat Steps 6 through 8 several times to verify threshold settings.
Step 10.
Set test frequency select switch to the 50/60 hertz position as applicable.
Step 11.
Set front panel DELAY CYCLES thumbwheel switches for the desired delay in cycles.
Step 12.
Switch the test frequency select switch to the variable position. Verify that the relay trips and
that the target indicator operates.
Step 13.
Read the delay time as indicated by the counter. The desired delay time in seconds,
resulting from a sudden decrease in frequency below any pickup threshold frequency setting,
should be within a 0.020 second tolerance for the 60 hertz (T1) relay or 0.030 second
tolerance for the 50 hertz (T2) relay. Using the 60 hertz (T1) relay as an example, any cycles
delay time setting may be calculated as follows:
TD � 39 � 1
57
TD � 40
57
TD � 0.701 second, ±0.020 second of calculated delay time.
NOTE
The delay time accuracy should be as specified above or within the accuracy of the
test equipment, whichever is greater.
NOTE
The timing required between lighting of the TIMING LED and contact closure will be
long. As the frequency is decreased below the threshold setting, the time required for
the output to change states is reduced.
For example:
DELAY CYCLES setting
= 39
TRIP FREQUENCY hertz below setting
= 3.00
Applied Trip Frequency
= 57 hertz:
Step 14.
Repeat Steps 10 through 13 several times to verify relay time delay setting.
INVERSE TIME DELAY (OPTION D1 TEST PROCEDURE
To verify/set underfrequency 50 hertz (Style T2) or 60 hertz (Style T1) relays equipped with inverse time
delay, perform the following steps.
Step 1.
Connect the relay as shown in Figure 5-1.
Step 2.
Apply appropriate ac or dc voltage to terminals 3 and 4 for relay styles equipped with external
power supply. Apply 120 Vac, 50 hertz or 60 hertz as applicable, at terminals 6 and 7 for
relay styles equipped with sensing input power supply (option 1-2).
Step 3.
Set test frequency select switch to 50 or 60 hertz position.
Step 4.
Set relay front panel TRIP FREQUENCY Hz BELOW (50 or 60) thumbwheel switches for the
desired underfrequency pickup point.
Step 5.
Set front panel TRIP TIME ADJUST control at 0 position.
Step 6.
Adjust the variable test frequency source to a frequency above the threshold frequency set in
Step 4.
Step 7.
Set the test frequency select switch to the variable position and slowly adjust the test variable
frequency down toward pickup threshold until the front panel TIMING LED lights, indicating
that the relay pickup point has been exceeded.
The front panel TRIP TIME ADJUST control is continuously variable and the time dial
settings are therefore approximations. To set the time dial for the desired delay
characteristics on or between the plotted curves for the inverse time delay, perform the
following procedures.
Step 8.
Read the trip frequency as indicated by the frequency source, or by an external frequency
measuring device. The pickup point should be within 0.035 hertz of the selected pickup
frequency set in Step 4 for the 50 hertz (T2) relays or 0.030 hertz for the 60 hertz (T1) relays,
or within the test set accuracy, whichever is greater. Be sure the target indicator has tripped.
Return the test frequency select switch to the 50 or 60 hertz position. Reset target (if
supplied).
Step 9.
Repeat Steps 6 through 8 several times to verify the relay threshold setting.
Step 10.
The steps below may be used to verify/set the inverse time delay.
Step 11.
Set test frequency select switch to the 50 or 60 hertz position, as applicable.
Step 12.
Set front panel TRIP TIME ADJUST control to the desired position.
Step 13.
Set front panel TRIP FREQUENCY thumbwheel switches at 1.00.
Step 14.
Adjust the variable frequency source for either 48.0 hertz (T2) or 58.0 hertz (T1 ) output.
Step 15.
Switch test frequency select switch to the variable position.
Step 16.
Read the trip delay time indicated by the counter. Record the delay time and compare it to
the applicable delay curve shown in Section 1 to determine if the delay time is within the
specified 15 percent tolerance.
Step 17.
Using the 60 hertz 0 TIME curve in Section 1 as an example, the time delay recorded in Step
16 for a 60 hertz relay should be 0.230 seconds ±15 percent. To read this time on the curve,
first subtract the input test frequency of 58.0 hertz from the nominal 60 hertz, which gives 2.0
hertz below pickup. Then subtract the front panel TRIP FREQUENCY thumbwheel setting (in
this case 1.00) from the 2.0 hertz, leaving a normalized 1.0 hertz below pickup. Look along
the 0 TIME curve (lower curve) until curve intersects the vertical 1.0 HERTZ BELOW PICKUP
grid line. At the intersection read 0.230 seconds (±15 percent) delay time on the TRIP TIME
(SECONDS) scale.
Step 18.
Adjust TRIP TIME ADJUST control as necessary for the above tolerance.
Step 19.
Set the test frequency select switch to the 50 hertz or 60 hertz position, as applicable.
Step 20.
Adjust the variable frequency source for either a 47.0 hertz (T2) or 57.0 hertz (T1) output.
Step 21.
Switch the test frequency select switch to the variable position.
Step 22.
Read the trip time delay indicated by the counter. Record the delay time and compare it to
the applicable delay curve to determine if the delay time is within the specified ±15 percent
tolerance.
Again using the 60 hertz 0 TIME curve as an example, the time delay recorded in Step 22
should be 0.135 seconds ±15 percent. Here again, subtract test frequency (57 hertz) from
nominal (60 hertz) to arrive at hertz below pickup (3.0 hertz). Subtract front panel TRIP
FREQUENCY setting (1.00) from hertz below pickup (3.0) to get normalized (2.0) hertz below
pickup point. Move to the left along the 0 TIME curve until the vertical HERTZ BELOW
PICKUP (2 hertz) and curve intersect. Read the corresponding delay on the TRIP TIME
(SECONDS) axis.
Step 24.
Progressively decrease test variable oscillator frequency in 1 hertz steps to 46 hertz for the
50 hertz (T2), or to 56 hertz for the 60 hertz (T1). Record the resultant time delays as
provided in the previous steps.
Step 25.
Using the delay times recorded in Steps 16, 22, and 24, plot these points on the appropriate
time curve (50 or 60 hertz) for future reference. Connection of these points should be a curve
of the same shape as the desired curve within ±15 percent.
Substitution of printed circuit boards or individual components does not necessarily mean
the relay will operate properly. Always test the relay before placing it in operation.
���������
MAINTENANCE
GENERAL
BE1-81 Digital Underfrequency Relays require no preventive maintenance other than a periodic
operational test (refer to Section 5 for operational test procedure). If the relay fails to function properly,
and in-house repair is contemplated, consult the Service Manual (publication number 9 1064 00 620). If
factory repair is desired, contact the Customer Service Department of the Power Systems Group, Basler
Electric, for a return authorization number prior to shipping.
IN-HOUSE REPAIR
In-house replacement of individual components may be difficult and should not be attempted unless
appropriate equipment and qualified personnel are available.
If in-house repair is to be attempted, component values may be obtained from the schematics or the
parts list of the Service Manual. Replacement parts may be purchased locally. The quality of
replacement parts must be at least equal to that of the original components.
Where special components are involved, Basler Electric part numbers may be obtained from the number
stamped on the component or assembly, the schematic, or parts list. These parts may be ordered
directly from Basler Electric. When complete boards or assemblies are needed, the following
information is required.
1.
Relay model and style number
2.
Relay serial number or date code
3.
Board or assembly
a)
Part number
b)
Serial number
c)
Revision letter
4.
The name of the board or assembly
STORAGE
This protective relay contains aluminum electrolytic capacitors which generally have a life expectancy in
excess of 10 years at storage temperatures less than 40�C. Typically, the life expectancy of the
capacitor is cut in half for every 10�C rise in temperature. Storage life can be extended if, at one-year
intervals, power is applied to the relay for a period of thirty minutes.
Test plugs (Basler part number 10095 or G.E. part number XLA12A1) provide a quick, easy method of
testing relays without removing them from their case. Test plugs are simply substituted for the
connection plugs. This provides access to the external stud connections as well as to the internal
circuitry.
Test plugs consist of black and red phenolic moldings with twenty electrically separated contact fingers
connected to ten coaxial binding posts. Fingers on the black side are connected to the inner binding
posts (black thumb nuts) and tap into the relay internal circuitry. Fingers on the red side of the test plug
are connected to the outer binding posts (red thumb nuts) and also connect to the relay case terminals.
When testing circuits connected to the bottom set of case terminals, the test plug is inserted with the
numbers 1 through 10 facing up. Similarly, when using the test plug in the upper part of the relay, the
numbers 11 through 20 are faceup. It is impossible, due to the construction of the test plug, to insert it
with the wrong orientation.
This section contains information concerning the previous editions of the manual. The substantive
changes to date are summarized in the Table 7-1.
Table 7-1. Changes
Revision
Change
ECA/Date
A
Revised the entire manual to conform with the current instructional
manual style and relay configuration.
14138/04-18-96
B
Added Case Size to Section 1, Specifications. Corrected
Table 2-1, Callout letters A and F. Changed mounting illustrations
in Section 4, Installation, to make all illustrations more uniform in
symbol size. Added ground connection to Figure 4-13, and
changed the title to AC Sensing Input Connections. Changed
Figure 4-14 title to DC Control Connections.