ABB Relion REB500 Communication Protocol Manual
Read Online
Read the ABB Relion REB500 Communication Protocol Manual online using the built-in PDF viewer.
Text of the manual
Distributed busbar protection REB500
Version 8.3 IEC
Communication protocol manual
IEC60870-5-103
/t1ainm1:nu
Events
Measurements
Disturbance records
Settings
2013-03-3010:53:.10
j$superUser
joi,jectname
a
/Mainmenu =
I ; D
D
i!9?
J;;:::et�,�
SettirlgS
confi�ation
rua,gr,ostics
rests
O•�
L¥19"39f� -
I D I; =
D =
I ; D
D
i!9?
J;;:::et�,�
SettirlgS
confi�ation
rua,gr,ostics
rests
O•�
L¥19"39f� -
I D I; =
D =
Document ID: 1MRK 511 451-UEN
Issued: May 2019
Revision: B
Product version: 8.3
© Copyright 2019 ABB. All rights reserved
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party, nor
used for any unauthorized purpose.
The software and hardware described in this document is furnished under a license and may
be used or disclosed only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in theOpenSSL
Toolkit. (http://www.openssl.org/) This product includes cryptographicsoftware written/
developed by: Eric Young ([email protected]) and Tim Hudson([email protected]).
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their respective
holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guaranteed properties. All persons
responsible for applying the equipment addressed in this manual must satisfy themselves that
each intended application is suitable and acceptable, including that any applicable safety or
other operational requirements are complied with. In particular, any risks in applications where
a system failure and /or product failure would create a risk for harm to property or persons
(including but not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby requested to
ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be completely ruled
out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
Other than under explicit contractual commitments, in no event shall ABB be responsible or
liable for any loss or damage resulting from the use of this manual or the application of the
equipment.
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified
voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests
conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for
the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international standards of
the IEC 60255 series.
Table of contents
Section 1
Introduction.................................................................................................... 3
1.1
This manual....................................................................................................................................3
1.2
Intended audience........................................................................................................................3
1.3
Product documentation..............................................................................................................3
1.4
Symbols and conventions...........................................................................................................3
1.4.1
Symbols........................................................................................................................................ 3
1.4.2
Document conventions.............................................................................................................4
Section 2
Safety information.........................................................................................5
Section 3
Interbay bus functions...................................................................................7
3.1
Introduction...................................................................................................................................7
3.2
Basic configuration...................................................................................................................... 7
3.3
Configuring IEC 60870-5-103 IBB............................................................................................ 10
3.4
Transfer of differential current values....................................................................................11
3.4.1
The delta/dead band algorithm.............................................................................................11
3.4.2
Configuring the SCS differential current parameter.........................................................12
Section 4
IEC60870-5-103.............................................................................................15
4.1
Introduction.................................................................................................................................15
4.2
General functions........................................................................................................................15
4.3
Disturbance recorder................................................................................................................. 17
4.4
ACC actual channel.....................................................................................................................18
4.5
Generic REB500 functions........................................................................................................ 19
4.5.1
Diagnostic information...........................................................................................................19
4.5.2
Status information................................................................................................................... 21
4.5.3
Entries for single-point indications......................................................................................22
4.5.4
Entries for double-point indications ................................................................................... 23
4.5.5
Display of busbar differential currents................................................................................24
4.6
Special information and instructions for configuring the control system.....................26
Table of contents
Distributed busbar protection REB500
1
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
The communication protocol manual describes a communication protocol supported by the
IED. The manual concentrates on vendor-specific implementations.
1.2
Intended audience
GUID-ACC7A898-5907-41E1-8DDD-DD8591298668 v1
This manual addresses the communication system engineer or system integrator responsible
for pre-engineering and engineering for communication setup in a substation from an IED
perspective.
The system engineer or system integrator must have a basic knowledge of communication in
protection and control systems and thorough knowledge of the specific communication
protocol.
1.3
Product documentation
GUID-91F0A03F-D1AF-4695-A239-1FC87E7459EE v2
REB500 manuals
Document numbers
Product guide
1MRK 505 402-BEN
Application manual
1MRK 505 399-UEN
Technical manual
1MRK 505 400-UEN
Operation manual
1MRK 500 132-UEN
Engineering manual
1MRK 511 452-UEN
Commissioning manual
1MRK 505 401-UEN
Application manual for bay protection functions
1MRK 505 403-UEN
Technical manual for bay protection functions
1MRK 505 406-UEN
Cyber security deployment guideline
1MRK 511 453-UEN
Communication protocol manual IEC61850
1MRK 511 450-UEN
Communication protocol manual IEC60870-5-103
1MRK 511 451-UEN
Getting started guide
1MRK 505 404-UEN
1.4
Symbols and conventions
1.4.1
Symbols
GUID-4F7DD10A-DEE5-4297-8697-B8AAB5E3262F v2
The electrical warning icon indicates the presence of a hazard which could
result in electrical shock.
1MRK 511 451-UEN B
Section 1
Introduction
Distributed busbar protection REB500
3
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
The warning icon indicates the presence of a hazard which could result in
personal injury.
The caution icon indicates important information or warning related to the
concept discussed in the text. It might indicate the presence of a hazard which
could result in corruption of software or damage to equipment or property.
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project or
how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to understand that
under certain operational conditions, operation of damaged equipment may result in
degraded process performance leading to personal injury or death. Therefore, comply fully
with all warning and caution notices.
1.4.2
Document conventions
GUID-37C3ACF4-BD79-43C6-B37E-24B38EE69301 v2
A particular convention may not be used in this manual.
•
Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary
also contains definitions of important terms.
•
Push button navigation in the LHMI menu structure is presented by using the push button
icons.
For example, to navigate the options, use
and
.
•
HMI menu paths are presented in bold.
For example, select Main menu/Settings.
•
Signal names are presented in bold.
The signal 21120_EXT_TEST_TRIP can be set and reset via the LHMI Test Trip menu.
•
Parameter names and parameter values are presented in italics.
For example, the default value of the Operation setting is Not inverted.
•
Section references are presented with the respective section numbers.
For example, see Section 1.4.2 for more details about document conventions.
Section 1
1MRK 511 451-UEN B
Introduction
4
Distributed busbar protection REB500
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Dangerous voltages can occur on the connectors, even though the auxiliary
voltage has been disconnected.
Non-observance can result in death, personal injury or substantial property
damage.
Only a competent electrician is allowed to carry out the electrical installation.
National and local electrical safety regulations must always be followed.
The frame of the IEDs has to be carefully earthed.
Whenever changes are made in the IEDs, measures should be taken to avoid
inadvertent tripping.
The IEDs contain components which are sensitive to electrostatic discharge.
Unnecessary touching of electronic components must therefore be avoided.
1MRK 511 451-UEN B
Section 2
Safety information
Distributed busbar protection REB500
5
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Interbay bus functions
GUID-FC8C1289-F943-4E92-A50E-BDA7281A5337 v1
3.1
Introduction
GUID-7A41F2A2-F366-4D30-9D76-BB6279380110 v2
An interface is available for connecting the numerical busbar protection to a station
automation system or station monitoring system (SCS/SMS).
For an overview of REB500’s communication interfaces, see the Operation manual.
In contrast to feeder control and protection bay units, REB500 is equipped with only a single
interbay bus interface via which all the REB500 bay units in the entire station communicate.
This has to be taken into account by the various bus protocols.
This document applies for IEC60870-5-103. However, Section 3 of this
document also contains information of a second IBB using IEC61850-8-1 if
configured.
3.2
Basic configuration
GUID-A112B99B-E8BF-4750-8E26-D9C9BD9F6048 v2
The fourth octet in the Data Unit Identification field of an ASDU determines the common
address of ASDU. It normally has to be the same as the station address on the link layer.
Exceptions are permitted where additional common ASDU addresses are needed because of
multiple instances of functions.
In case of REB500, this exception allowed in the IEC recommendation is used to be able to
address the Central Unit and the Bay Units via a single physical connection.
Common Address of ASDU – CAA
Basic setting:
0
Central Unit
1-60
Bay Units
255
Global address
The dialog for configuring the communication is accessed by selecting HMI500
Configuration/Communication/SCS Configuration.
1MRK 511 451-UEN B
Section 3
Interbay bus functions
Distributed busbar protection REB500
7
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
IEC18000623 V1 EN-US
Figure 1:
Dialog box for configuring the communication
If Common Link Layer Address of the SCS Configuration is selected:
The link address can be setup in this dialog box. The Common Address of ASDU (CAA) for all
units is setup in the CAA Setting dialog box by pressing the Addr. Setting button.
Table 1:
Configuration of IEC60870-5-103
Setting
Description
Default setting
Common Link layer
address
Link layer address used for all Units in
common
1
Baud Rate
Baud rate
9600
Addr. Setting
Individual Common Address of ASDU for
each Bay Unit
0
Central Unit
1-60
Bay Units
Section 3
1MRK 511 451-UEN B
Interbay bus functions
8
Distributed busbar protection REB500
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
IEC18000624 V1 EN-US
Figure 2:
Dialog box for configuring CAA
Table 2:
Configuration of IEC60870-5-103
Setting
Description
Default setting
CAA
Individual Common Address of ASDU for
each Bay Unit
0
Central Unit
1-60
Bay Units
If Common Link Layer Address of the SCS Configuration is not selected:
The link address and the Common Address of ASDU (CAA) for all units is setup in the CAA
Setting dialog box by pressing the Addr. Setting button.
1MRK 511 451-UEN B
Section 3
Interbay bus functions
Distributed busbar protection REB500
9
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
IEC18000625 V1 EN-US
Figure 3:
Dialog box for configuring CAA and LLA
Table 3:
Configuration of IEC 870-5-103
Setting
Description
Default setting
CAA
Individual Common Address of ASDU for
each Bay Unit
0
Central Unit
1-60
Bay Units
LLA
Individual Link Address for each Bay Unit
0
Central Unit
1-60
Bay Units
3.3
Configuring IEC 60870-5-103 IBB
GUID-605B1ACD-79EB-4C0A-8839-331FD573E41B v1
For changes in status generated by REB500 to be transferred as events to an SCS/SMS, the
corresponding signals must be configured by selecting them in HMI500 Configuration/Binary
module and making the settings in the Event configuration section of the Details dialog box.
To which IBB an event is sent is determined by selecting the appropriate check box IBB 1 or IBB
2 when configuring the signal.
As the 61850 model is implemented as defined by the standard, no custom assignments can
be made for the IBB associated with 61850.
Section 3
1MRK 511 451-UEN B
Interbay bus functions
10
Distributed busbar protection REB500
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
IEC18000608 V1 EN-US
Figure 4:
Configuring signals as events
Diagnostic and system events are always available for transfer whichever protocol is in use
and cannot be configured.
The IEC 60870-5-103 section only appears when the protocol is configured.
3.4
Transfer of differential current values
3.4.1
The delta/dead band algorithm
GUID-85BE2C1A-DD67-4564-99E1-CF504CBD06D7 v1
To keep the load on the IBB as low as possible, the bus zone differential currents are checked
cyclically, but only actually transferred via the bus if the value has changed.
Diff.
Current
Values transferred
to the SCS
Zero limit
0
100
200
12000189-IEC18000308-1-en.vsd
IEC18000308 V1 EN-US
Figure 5:
Transmitted values and the zero limit
To stabilize the display during normal operation, differential currents below the zero limit
(dead band) count as zero and are transferred as such.
1MRK 511 451-UEN B
Section 3
Interbay bus functions
Distributed busbar protection REB500
11
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Providing the condition for transmitting a current value is fulfilled, all the differential currents
belonging to the respective zone are sent to the SCS/SMS.
sum = sum + |current – last|
if sum > delta then
sum = 0
if current < deadband then
current = 0
endif
send current
endif
last = current
The system continuously performs the above algorithm: It adds up the absolute difference
between the last two measurements (current and last) since the last status update was sent
(sum).
As soon as sum is greater than the threshold delta a new event will be sent with the current
value. If this value is below the deadband threshold, the value 0 will be sent instead.
3.4.2
Configuring the SCS differential current parameter
GUID-DF29CA42-6DDD-459D-A610-175B597D83C9 v2
The precise conditions for sending differential currents to the SCS can be set by selecting
HMI500 Settings/Communication/SCS Diff. Current Parameters.
12000190-IEC18000536-1-en.vsdx
IEC18000536 V1 EN-US
Figure 6:
Settings/Communication/SCS Diff. Current Parameters
Settings in this dialog box are made for each busbar section (bus zone) and can be changed
after activating the respective field. The differential current parameters are as follows:
Table 4:
SCS differential current parameters
Item
Description
Min.
Max.
Default
Step
Unit
Update
period
Determines how often the differential
current measurement has to be
updated.
0
1000
60
100
s
Enabled
Enables polling of the bus zone
differential currents.
yes
no
Yes
Delta
L1_L2_L3
Applies to all bus zones. Delta per bus
zone for phases L1, L2 and L3.
0
65535
10
1
A
Table continues on next page
Section 3
1MRK 511 451-UEN B
Interbay bus functions
12
Distributed busbar protection REB500
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Dead band per bus zone for phases
L1, L2 and L3.
0
65535
5
1
A
Delta L0
Delta per bus zone for the neutral
current L0.
0
65535
10
1
A
Dead band L0
Dead Band per bus zone for the
neutral current L0
0
65535
5
1
A
Delta and Dead band settings that are too low, result in a high data load on the
bus. For this reason, care should be taken to set reasonable values.
1MRK 511 451-UEN B
Section 3
Interbay bus functions
Distributed busbar protection REB500
13
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Busbar protection is not one of the types of protection defined in IEC 60870-5-103.
Nevertheless, the commands and signals of the REB500 system are modeled as far as possible
on functions defined in the IEC recommendation. The functional scope of the station protocol
is therefore reduced. The backup protection functions breaker failure, time-overcurrent and
end fault that are optionally available with REB500 are also supported.
According to the IEC recommendation, usage of the private range is only permitted with
regard to the compatibility of existing devices. For this reason, additional REB500 functions
that are not defined in the recommendation were implemented according to the future-
oriented generic part of IEC 60870-5-103.
REB500 also optionally provides a private range.
Refer to IEC 60870-5-103 for an explanation of the various abbreviations.
4.2
General functions
GUID-B95181CD-4E96-4569-BA0A-5D1EF56CA1D1 v2
The tables below define the functional scope of REB500 according IEC60870-5-103. The details
are to be found in the recommendation itself.
Table 5:
System functions in monitoring direction
INF
Description
GI.
TYPE.
COT
<0>
End of general interrogation (polling)
–
8
10
<0>
Time synchronization
–
6
8
<2>
Reset frame control bit (FCB)
–
5
3
<3>
Reset CU
–
5
4
<4>
Start/restart
–
5
5
<5>
Power on
–
5
6
The information number 0 refers to the global function type and is the same for
all system functions. The information numbers 2 to 5 are used with FUN in
relation to the main function of a protection system.
Table 6:
Status signals in monitoring direction
INF
Description
GI.
TYPE
COT
REB500 signal configuration
<18>
Protection active
x
1
1,9
41810_In service (CU
output)21805_In service (BU
output)
<19>
LED reset
–
1
11
31810_External reset (CU
input)11610_external reset (BU
input)
<20>
Blocks the supervisory
equipment
x
1
9,11
31215_Block.IEC
master_direction (CU input)
1MRK 511 451-UEN B
Section 4
IEC60870-5-103
Distributed busbar protection REB500
15
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Supervisory signals in monitoring direction
INF
Description
GI.
TYPE
COT
REB500 signal configuration
<47>
General alarm
x
1
1,9
41805_Alarm (CU output)
Table 8:
Disturbance signals in monitoring direction
INF
Description
GI.
TYPE
COT
FUN
REB500 signal configuration
<68>
General trip
–
2
1
254
42305_BBP trip (CU output)
21110_TRIP (BU output)
21305_TRIP (BU output)
<69>
Trip L1
–
2
1
254
42315_BBP trip L1 (CU output)
23315_BFP TRIP L1 (BU output)
<70>
Trip L2
–
2
1
254
42320_BBP trip L2 (CU output)
23320_BFP TRIP L2 (BU output)
<71>
Trip L3
–
2
1
254
42325_BBP trip L3 (CU output)
23325_BFP TRIP L3 (BU output)
<72>
Trip L0
–
2
1
254
23340_BFP TRIP L0 (BU
output)
<85>
Breaker failure
–
2
1
254
43305_BFP trip t1 (CU output)
43310_BFP trip t2 (CU output)
23305_BFP trip t1 (BU output)
23310_BFP trip t2 (BU output)
<90>
Trip I>
–
2
1
254
45305_OCDT trip (CU output)
25105_OCDT TRIP (BU output)
25305_OCDT trip (BU output)
<92>
Trip IN>
–
2
1
254
42310_BBP trip L0 (CU output)
Table 9:
Types of function
FUN
Description
<254>
Generic
Table 10:
Generic functions in monitoring direction
INF
Description
GI
TYPE
COT
<240>
Read headings of all defined groups
–
10
42,43
<241>
Read values or attributes of all entries of one
group
–
10
42,43
<242>
Not used
–
–
–
<243>
Read the directory of a single entry
–
11
42,43
<244>
Read the value or attribute of a single entry
(x)
10
1,2,9,11,12,42,43
Table 11:
Generic functions in control direction
INF
Description
TYPE
COT
<240>
Read headings of all defined groups
21
42
<241>
Read values or attributes of all entries of one group
21
42
<242>
Not used
–
–
<243>
Read the directory of a single entry
21
42
<244>
Read the value or attribute of a single entry
21
42
Section 4
1MRK 511 451-UEN B
IEC60870-5-103
16
Distributed busbar protection REB500
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Commands in control direction
INF
Description
TYPE
COT
FUN
CAA
<19>
LED reset
20
20
254
Central Unit
4.3
Disturbance recorder
GUID-442CE5CB-AD4B-428F-9921-15E145294B02 v2
Disturbance data are uploaded and displayed in accordance with the IEC recommendation
with the following exceptions:
•
REB500 supports a maximum of 15 records per Bay Unit, but only the first (oldest) eight in
the queue can be displayed in accordance with the recommendation.
•
Of the records that are displayed, only the oldest can be deleted or uploaded. This is
determined by the REB500 principle.
The time stamp invalid bit (IV) in a disturbance record is always set, because the CIM
module is unaware of the synchronization status at the instant of the record.
The upload of disturbance data from the central unit is not possible via
IEC60870-5-103.
Creating an export file
HMI500 provides facility for exporting the IEC 60870-5-103 communication data contained in
the system database in the form of a text file (export file). To do this, select Tools/Export SCS
data and IEC 60870-5-103 IBB and then click on the Export button.
The application creates a text file (export file) iec103exp.lst, which contains all the information
required.
The file has the following structure:
1.
Disturbance recorder signal configuration
2.
IEC60870-5-103 events
The columns are separated by a semicolon (;). The following is an example of an export file
generated by HMI500:
--------------------------------------------------------------------------------------------------
IEC 60870-5-103 Disturbance Recorder signals
--------------------------------------------------------------------------------------------------
CAA;ABB ref.; Feeder; Station number; Signal ID; Signal text
0;CU;-;Null;Null;Null
2;BU2;BU2;2;1;Trip
2;BU2;BU2;2;2;In service
--------------------------------------------------------------------------------------------------
IEC 60870-5-103 events and private Information Object Identifier settings
--------------------------------------------------------------------------------------------------
CAA;ABB ref.; Feeder; Signal text; IEC FUN;IEC INF
0;CU;BU2;41810_In service;254;18
2;BU1;BU1;23310_BFP trip t2;254;85
2;BU1;BU1;221105_I0INV Trip Si;160;67
2;BU1;BU1;211880_DIST Com Send.2;128;76
1MRK 511 451-UEN B
Section 4
IEC60870-5-103
Distributed busbar protection REB500
17
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Description of the columns in the export file
Column
Description
CAA
Common Address ASDU: Sub-address for identifying a Bay Unit
at the application level
ABB ref.:
ABB’s designation for the Bay Unit
Feeder:
User’s designation for the respective bay
Station Number:
Disturbance recorder number
Signal ID:
Consecutive signal number
Signal Text:
User’s signal description
IEC FUN:
Assigned IEC function type
IEC INF:
Assigned IEC information number
The above Signal ID and Signal Text assignment for a specific Bay Unit can also be made via
HMI500 providing a COMTRADE file for the Bay Unit disturbance recorder is uploaded. The file
filename.cfg generated by the PC contains the same information as the list generated by the
export tool.
The assignment can change when the disturbance recorder configuration changes, for
example, by deleting or adding signals. The above list then has to be recreated and possibly
corrected by the control system.
The configured length of disturbance records shall not exceed one second (1 s)
to avoid conflicts with the maximum number of 65535 events foreseen in
IEC60870-5-103.
4.4
ACC actual channel
GUID-1AC25D43-EFDB-4521-9ACB-FE818FB9CAF8 v2
The REB500 Bay Unit 500BU04 supports five voltage channels. Since, however, the compatible
range of the standard only lists four voltage channels, the fifth channel is transferred to the
private domain.
Assignment of REB500 channels to IEC 60870-5-103 channel numbers:
Table 14:
IEC 60870-5-103 analogue channel assignment
REB500 channel
designation
REB500 application
IEC 60870-5-103 channel designation ACC
(actual channel)
I1
I L1
1 = I L1
I2
I L2
2 = I L2
I3
I L3
3 = I L3
I4
I L0
4 = V L1
U1
U L1
5 = V L1E
U2
U L2
6 = V L3
U3
U L3
7 = V 0E
U4
U L0
8 = U L1
U5
U 5
64 = private
Section 4
1MRK 511 451-UEN B
IEC60870-5-103
18
Distributed busbar protection REB500
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Generic REB500 functions
4.5.1
Diagnostic information
GUID-9430347F-A35F-4AB3-A63A-9FF711FEBCB5 v2
Status and diagnostic information is generated by the various REB500 application software
modules and transferred spontaneously as events every time the status changes. A separate
group exists for diagnostic information with an entry for every subsystem of the REB500
system software REBSYS.
Diagnostic event group:
Table 15:
Diagnostic event
ENTRY No.
Group 64 (0x40)
0 (Heading)
Diagnostic information
1
BBP (Busbar protection)
2
ITT (Intertripping)
3
BCF (Binary input and output configuration facility)
4
DIA (Diagnostic)
5
TGR (Test generator)
6
EMI (External man/machine interface)
7
LMI (Local man/machine interface)
8
DAC (Data access)
9
TIM (Time management)
10
DBS (Database system)
11
SIG (Signal processor)
12
EVR (Event recording)
13
RFS (Remote file system)
14
SPR (Signal pre-processing and recording)
15
MBA (Multi-function bus administrator)
16
OCP (Overcurrent protection)
17
BFP (Breaker failure protection)
18
DRR (Disturbance recorder)
19
MPL (Multi functional process bus library)
20
EFP (End-fault protection)
21
PDF (Pole discrepancy function)
22
BOC (Binary input/output control)
23
BPP (Binary pre-processing)
24
DIE (Diagnostic extensions)
25
DRD (Disturbance recorder dispatcher)
26
EVA (Event and alarm handling)
27
GPI (General purpose interface)
28
LAC (LON application converter)
29
IAC (IAC application converter)
30
CMD (Command processor)
Table continues on next page
1MRK 511 451-UEN B
Section 4
IEC60870-5-103
Distributed busbar protection REB500
19
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Group 64 (0x40)
31
LPL (LON protocol layer)
32
TRC (Traceability)
33
BP (Bay protection)
Table 16:
Used attributes of ASDU 10 for diagnostic events
COT
CAA
FUN
1 Spontaneous
0
for REB500 CU
254 Generic
1 to 60
for REB500 BU
With the exception of the header (entry 0), the current values of the entries are not available on
request. The response to the corresponding generic read command is therefore COT 43
‘invalid data response to generic read command’.
The current value of the group header (entry 0) corresponds to the number of subsystems in
the REB500 system software.
Table 17:
Directory entry for GIN 0x4000 (header)
COD
Data type
Length
Number
Value / Significance
<10> Description
<1> OS8ASCII
21
1
“Diagnostic information”
<1> Current value
<3> UI
1
1
Number of SW subsystems
All the other entries in this group consist of the following attributes that are needed to
describe a diagnostic event generated by one of the software subsystems.
The status of a diagnostic event is indicated by an ASCII string, which can have one of the
following values:
•
Initializing
•
Major error
•
Minor error
•
Not ready
•
Ready
•
Last wish
•
Shutdown
•
No status
The error code is assigned by the application when the status changes and precisely describes
the cause of the error.
Table 18:
Directory entry for GIN 0x40 (xx)
COD
Data type
Length
Number
Value / Significance
<10> Description
<1> OS8ASCII
3
1
BBP (example)
<1> Current value
<23>
DATASTRUCTU
RE
29
1
(Includes the following three
definitions)
<1> OS8ASCII
12
1
Status
<3> UI
1
1
Error code
<14> BINARY
TIME
7
1
Time stamp (CP56Time2a)
Section 4
1MRK 511 451-UEN B
IEC60870-5-103
20
Distributed busbar protection REB500
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
The following table gives an example of the ASDU 10 Generic Data that is transferred
spontaneously for a diagnostic event.
Table 19:
TYPE IDENTIFICATION: Generic data
0
0
0
0
1
0
1
0
Type Identification
10
DATA UNIT IDENTIFIER
1
0
0
0
0
0
0
1
Variable Structure
Qualifier
SQ=1,
SQ_No.= 1
Spontaneous <1>
Cause Of Transmission
COT
REB500 CU/BU No.
Common Address of
ASDU
<0 .. 60>
GEN <254>
Function type
FUN
INFORMATION
OBJECT
Read value of single entry <244>
Information number
INF
<0>
Return information
identifier
RII
{1, 0, 0}
Number of generic data
sets
NGD {NO, COUNT, CONT}
40 H
01 H
Generic identification
number
GIN
Example
Current value <1>
Kind of description
KOD
DATA STRUCTURE <23>
29
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD
<1> OS8ASCII
12
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD 1
Major Error
GID 1 (example)
<3> UI
1
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD 2
Error code (UI1)
GID 2
<14> BINARY TIME
7
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD 3
Time stamp (CP56Time2a)
GID 3
4.5.2
Status information
GUID-49587D6A-D1F8-43AD-ACBD-AEB285A3C396 v1
All the status information relating to binary input and output signals, internal signals (single-
point indications - SPI) and switchgear positions (double-point indications - DPI) that are
configured in REB500 for transfer via IEC60870-5-103, but are not covered by the compatible
part of the IEC recommendation, are transferred as generic data. An entry is made in the table
for every event configured using HMI500 or REBCON for transfer via IEC 60870-5-103. Since
there can be more events per type (SPI or DPI) than the maximum number of entries a group
can have (255), the system reserves additional groups as necessary. By this means, up to 1020
events per event type can be defined in the generic part.
1MRK 511 451-UEN B
Section 4
IEC60870-5-103
Distributed busbar protection REB500
21
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Group for displaying status information
Entry No.
Group No. 66 (0x42) to Group No. 69
(0x45)
Group No. 70 (0x46) to Group No. 73
(0x49)
0 (Heading)
Single-point indications
Double-point indications
1
Indication #1
Indication #1
2
Indication #2
Indication #2
…
…
…
255
Indication #255
Indication #255
Table 21:
Used attributes of ASDU 10 for status information
COT
CAA
FUN
1 Spontaneous
0 / 1..60 REB500 CU / REB500 BU
254 Generic
With the exception of the header (entry 0), the current values of the entries are not available on
request. The response to the corresponding generic read command is therefore COT 43
“invalid data response to generic read command”.
4.5.3
Entries for single-point indications
GUID-AD226E53-FF68-4ADB-BA19-CB654D580D49 v2
Table 22:
Directory entry for GIN 0x4200 (header)
COD
Data type
Length
Number
Value / Significance
<10> Description
<1> os8ascii
24
1
Single-point indications
<1> Current value
<3> UI
1
1
Number of SPI defined in this group
Table 23:
Directory entry for GIN 0x42 (xx)
COD
Data type
Length
Number
Value / Significance
<10> Description
<1> os8ascii
20
1
Event text defined by user
<1> Current value
<23> data
structure
14
1
(Includes the following two
definitions)
<9> Double
Point
Information
1
1
OFF (1) / ON (2)
<14> binary
time
7
1
Time stamp (CP56Time2a)
The following table gives an example of the ASDU 10 Generic Data that is transferred
spontaneously for a single-point indication.
Table 24:
TYPE IDENTIFICATION: Generic data
0
0
0
0
1
0
1
0
Type Identification
10
DATA UNIT IDENTIFIER
1
0
0
0
0
0
0
1
Variable Structure
Qualifier
SQ=1,
SQ_No.= 1
Spontaneous <1>
Cause Of Transmission
COT
REB500 CU/BU No.
Common Address of
ASDU
<0 .. 60>
Table continues on next page
Section 4
1MRK 511 451-UEN B
IEC60870-5-103
22
Distributed busbar protection REB500
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Read value of single entry <244>
Information number
INF
OBJECT
<0>
Return information
identifier
RII
{1, 0, 0}
Number of generic data
sets
NGD {NO, COUNT, CONT}
43 H
Generic identification
number
Group <41H .. 45H>
01 H
Entry <1 .. 255>
Current value <1>
Kind of description
KOD
DATA STRUCTURE <23>
14
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD
<9> DOUBLE-POINT INFORMATION
1
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD 1
0
0
0
0
0
0
<0 .. 3>
GID 1
<14> BINARY TIME
7
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD 2
Time stamp (CP56Time2a)
GID 2
4.5.4
Entries for double-point indications
GUID-F19F8A2D-F20A-4393-AEB3-66F5D3292526 v2
Table 25:
Directory entry for GIN 0x4600 (header)
COD
Data type
Length
Number
Value / Significance
<10> Description
<1> os8ascii
24
1
Double-point Indications
<1>Current value
<3> UI
1
1
Number of DPI defined in this group.
Table 26:
Directory entry for GIN 0x46 (xx)
COD
Data type
Length
Number
Value / Significance
<10> Description
<1> os8ascii
20
1
Event text defined by user
<1> Current value
<23> data
structure
14
1
(Includes the following two
definitions)
<9> Double
Point
INFORMATIO
N WITH
TRANSIENT
AND ERROR
1
1
TRANSIENT (0) /OFF (1) / ON (2) /
ERROR (3)
<14> binary
time
7
1
Time stamp (CP56Time2a)
The following table gives an example of the ASDU 10 Generic Data that is transferred
spontaneously for a double-point indication.
1MRK 511 451-UEN B
Section 4
IEC60870-5-103
Distributed busbar protection REB500
23
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
TYPE IDENTIFICATION: Generic data
0
0
0
0
1
0
1
0
Type Identification
10
DATA UNIT IDENTIFIER
1
0
0
0
0
0
0
1
Variable Structure
Qualifier
SQ=1,
SQ_No.= 1
Spontaneous <1>
Cause Of Transmission
COT
GEN <254>
Function type
FUN
INFORMATION
Read value of single entry <244>
Information number
INF
OBJECT
<0>
Return information
identifier
RII
{1, 0, 0}
Number of generic data
sets
NGD {NO, COUNT, CONT}
46 H
Generic identification
number
Group <46H .. 49H>
01 H
Entry <1 .. 255>
Current value <1>
Kind of description
KOD
DATA STRUCTURE <23>
14
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD
<9> DOUBLE-POINT INFORMATION
WITH TRANSIENT AND ERROR
1
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD 1
0
0
0
0
0
0
<0 .. 3>
GID 1
<14> BINARY TIME
7
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD 2
Time stamp (CP56Time2a)
GID 2
4.5.5
Display of busbar differential currents
GUID-A271FDFD-8D47-4A1F-B45E-51DB2BD31164 v2
The differential currents are displayed for each corresponding busbar zone (1..32) (see transfer
of differential currents).
Table 28:
Used attributes of ASDU 10 for differential current
COT
CAA
FUN
1 Spontaneous
0 REB500 CU
254 Generic
The group number 75 (0x4B) is used to display busbar differential currents and is therefore
only assigned to the Central Unit (CAA = 0).
Table 29:
Directory entry for GIN 0x4B00 (header)
COD
Data type
Length
Number
Value / Significance
<10> Description
<1> os8ascii
21
1
Differential currents
<1> Current value
<3> UI
1
1
Number of valid entries
The number of valid entries corresponds to the number of bus-bar zones and thus limited to
the range [1…32].
Each of the entries 1…32 in the group relates to a given busbar zone.
Section 4
1MRK 511 451-UEN B
IEC60870-5-103
24
Distributed busbar protection REB500
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Directory entry for GIN 0x4B (xx)
COD
Data type
Length
Number
Value / Significance
<10> Description
<1> os8ascii
3
1
BBI, example
<1> Current value
<23> data
structure
2
1
(Includes the following two
definitions)
<12>
Measured
variable with
quality
descriptor
2
3,4
Field with 3 / 4 measurements CP16
{OV,ER,RES,MVAL}
<14> binary
time
7
1
Time stamp (CP56Time2a)
<9> Unit
<1> os8ascii
1
1
A
<6> Factor
<6> I
4
1
32 Bit integer
The description has a maximum length of 16 characters.
The current value is a field with three (L1, L2, L3) or four (L1, L2, L3, L0) measurements and the
associated time stamp. The effective number of measurements is determined by how the
REB500 is configured.
Table 31:
COD Current Value
Attribute
Description
OV Overflow
This Bit is set to <1> whenever an overflow occurs or the
measurement is not assigned. It is normally therefore set to <0>.
ER Error flag
BBP (Busbar protection) This Bit indicates whether a measurement is
valid or not (measurement valid <0>, measurement invalid <1>).
RES Reserved
Spare for future use.
MVAL
Contains the actual measurement in fixed decimal point format.
The Factor is a 32 Bit integer for scaling to the original value.
The following table gives an example of the ASDU 10 ‘Generic Data’ that is transferred
spontaneously for displaying the differential currents of a given bus zone.
Table 32:
TYPE IDENTIFICATION: Generic data
0
0
0
0
1
0
1
0
Type Identification
10
DATA UNIT
IDENTIFIER
1
0
0
0
0
0
0
1
Variable Structure
Qualifier
SQ=1,
SQ_No.= 1
Spontaneous <1>
Cause Of Transmission
COT
REB500 CU
Common Address of
ASDU
<0>
GEN <254>
Function type
FUN
INFORMATION
Read value of single entry <244>
Information number
INF
OBJECT
<0>
Return information
identifier
RII
{1, 0, 0}
Number of generic data
sets
NGD {NO, COUNT, CONT}
4B H
Generic identification
number
Group
Table continues on next page
1MRK 511 451-UEN B
Section 4
IEC60870-5-103
Distributed busbar protection REB500
25
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Entry <1 .. 32>
Current value <1>
Kind of description
KOD
DATA STRUCTURE <23>
21
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD
<12> MEASUREMENT WITH QUALITY
DESCRIPTOR
2
3,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD 1
3 or 4 (including measurement
L0)
OV
ER
RES
MVAL (4 .. 8)
GID 1a
MVAL (9 .. 16)
OV
ER
RES
MVAL (4 .. 8)
GID 1b
MVAL (9 .. 16)
OV
ER
RES
MVAL (4 .. 8)
GID 1 c
MVAL (9 .. 16)
<14> BINARY TIME7
1,0
DATA TYPE
DATA SIZE
NUMBER, CONT
GDD 2
Time stamp (CP56Time2a)
GID 2
4.6
Special information and instructions for configuring
the control system
GUID-A8AF440A-22B6-4443-B341-64B408B162ED v2
Private range
Provision is made in the event configuration (see Section 3.3) for the user to enter his own
private IEC60870-5-103 definition for each REB500 signal.
The input fields for REB500 signals covered by the public part of the standard (see Section 4.2)
have a bright yellow background their default setting 0 for both IEC function type and
information number. All other signals receive the presetting 0 for the IEC function type and the
information number. A signal defined for protocol 60870-5-103 that is not in the public range
and has 0 set for function type and information number is transmitted via the generic part of
the protocol.
A private IEC60870-5-103 definition can be entered for every REB500 signal in this dialog. The
Set Default button is enabled for a signal in the public range of the protocol so that the ABB
default setting can be restored at any time.
The limitations specified in the standard must be observed when assigning information
numbers. The latter must be within the following ranges:
16-52; 73; 128-130; 64-72; 74-93
Section 4
1MRK 511 451-UEN B
IEC60870-5-103
26
Distributed busbar protection REB500
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
IEC18000627 V1 EN-US
Figure 7:
Private IEC 60870-5-103 definition
Disturbance recorder, binary signal transfer
Binary signals transmitted in disturbance records only have numbers and no designation. The
assignment of numbers to signal names is given in the COMTRADE file filename.cfg, which can
be uploaded, for example, from aBay Unit using HMI500.
Signal configuration instructions
Should the same logical signal be configured on two different BIO modules in a Bay Unit, only
one of them should be relayed to the IEC 60870-5-103 bus. A configuration that is duplicated
produces two indistinguishable events, which can cause some confusion. The response is
reflected by HMI500, which also generates two events.
Cause of transmission
With the exception of 42 (generic writing command), all the possible causes of transmission
are supported in the command direction.
In the supervisory direction, they are all supported with the exception of 7 (test mode), 12
(local HMI) and 44 (return confirmation of a generic write command).
Type identification
The type identification defines the type of ASDU that has been transferred.
Table 33:
Information in the supervisory direction
TYPE
Description
<1>
time-tagged message
<2>
time-tagged message with relative time
<5>
Identification
<6>
Time synchronization
<8>
General interrogation termination
<10>
Generic data
<11>
Generic identification
<23>
List of recorded disturbances
<26>
Ready for transmission of disturbance data
<27>
Ready for transmission of a channel
<28>
Ready for transmission of tags
<29>
Transmission of tags
<30>
Transmission of disturbance values
<31>
End of Transmission
1MRK 511 451-UEN B
Section 4
IEC60870-5-103
Distributed busbar protection REB500
27
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Information in the command direction
TYPE
Description
<6>
Time synchronization
<7>
General interrogation (polling)
<10>
Generic data
<20>
General command
<21>
Generic command
<24>
Order for disturbance data transmission
<25>
Acknowledgement for disturbance data transmission
Timeouts
•
Protocol time-out <50 ms as defined in the IEC recommendation applies for the protocol.
•
When a command to upload the disturbance recorder data is issued, the data has to be
transferred from the Bay Unit to the Central Unit first before they are transferred via the
IEC bus. The timeout from the instant the upload command is issued to the receipt of the
data varies in relation to the length of the disturbance record. The following applies:
STP timeout <2.5 minutes per 1 second of disturbance record data (4I+4U, 2400 Hz).
•
Once the transfer of disturbance recorder data has started, the timeout changes to:
Transfer timeout <1 Minute
Section 4
1MRK 511 451-UEN B
IEC60870-5-103
28
Distributed busbar protection REB500
Communication protocol manual IEC60870-5-103
© Copyright 2019 ABB. All rights reserved
Grid Automation Products
SE-721 59 Västerås, Sweden
Phone +46 (0) 21 32 50 00
www.abb.com/protection-control
© Copyright 2019 ABB.
All rights reserved.
Scan this QR code to visit our website
1MRK 511 451-UEN