ABB Relion REB500 Communication Protocol Manual

Specifications

Brand: ABB
Category: Protection Device
Model: Relion REB500 (Communication Protocol Manual)
File Type: PDF
File Size: —
Pages: 36

Read Online

Read the ABB Relion REB500 Communication Protocol Manual online using the built-in PDF viewer.

Text of the manual

Distributed busbar protection REB500

Version 8.3 IEC Communication protocol manual IEC60870-5-103 /t1ainm1:nu Events Measurements Disturbance records Settings 2013-03-3010:53:.10 j$superUser joi,jectname a /Mainmenu = I ; D D i!9? J;;:::et�,� SettirlgS confi�ation rua,gr,ostics rests O•� L¥19"39f� - I D I; = D =

I ; D

D i!9? J;;:::et�,� SettirlgS confi�ation rua,gr,ostics rests O•� L¥19"39f� - I D I; = D = Document ID: 1MRK 511 451-UEN Issued: May 2019 Revision: B Product version: 8.3 © Copyright 2019 ABB. All rights reserved

This document and parts thereof must not be reproduced or copied without written

permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license. This product includes software developed by the OpenSSL Project for use in theOpenSSL Toolkit. (http://www.openssl.org/) This product includes cryptographicsoftware written/ developed by: Eric Young ([email protected]) and Tim Hudson([email protected]). Trademarks ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. Warranty Please inquire about the terms of warranty from your nearest ABB representative.

The data, examples and diagrams in this manual are included solely for the concept or product

description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and /or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.

This product complies with the directive of the Council of the European Communities on the

approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is designed in accordance with the international standards of the IEC 60255 series.

Table of contents

Section 1 Introduction.................................................................................................... 3 1.1 This manual....................................................................................................................................3 1.2 Intended audience........................................................................................................................3 1.3 Product documentation..............................................................................................................3 1.4 Symbols and conventions...........................................................................................................3 1.4.1 Symbols........................................................................................................................................ 3 1.4.2 Document conventions.............................................................................................................4 Section 2 Safety information.........................................................................................5 Section 3 Interbay bus functions...................................................................................7 3.1 Introduction...................................................................................................................................7 3.2 Basic configuration...................................................................................................................... 7 3.3 Configuring IEC 60870-5-103 IBB............................................................................................ 10 3.4 Transfer of differential current values....................................................................................11 3.4.1 The delta/dead band algorithm.............................................................................................11 3.4.2 Configuring the SCS differential current parameter.........................................................12 Section 4 IEC60870-5-103.............................................................................................15 4.1 Introduction.................................................................................................................................15 4.2 General functions........................................................................................................................15 4.3 Disturbance recorder................................................................................................................. 17 4.4 ACC actual channel.....................................................................................................................18 4.5 Generic REB500 functions........................................................................................................ 19 4.5.1 Diagnostic information...........................................................................................................19 4.5.2 Status information................................................................................................................... 21 4.5.3 Entries for single-point indications......................................................................................22 4.5.4 Entries for double-point indications ................................................................................... 23 4.5.5 Display of busbar differential currents................................................................................24 4.6 Special information and instructions for configuring the control system.....................26 Table of contents Distributed busbar protection REB500 1 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

The communication protocol manual describes a communication protocol supported by the

IED. The manual concentrates on vendor-specific implementations. 1.2 Intended audience GUID-ACC7A898-5907-41E1-8DDD-DD8591298668 v1 This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a substation from an IED perspective. The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowledge of the specific communication protocol. 1.3 Product documentation GUID-91F0A03F-D1AF-4695-A239-1FC87E7459EE v2 REB500 manuals Document numbers Product guide 1MRK 505 402-BEN Application manual 1MRK 505 399-UEN Technical manual 1MRK 505 400-UEN Operation manual 1MRK 500 132-UEN Engineering manual 1MRK 511 452-UEN Commissioning manual 1MRK 505 401-UEN Application manual for bay protection functions 1MRK 505 403-UEN Technical manual for bay protection functions 1MRK 505 406-UEN Cyber security deployment guideline 1MRK 511 453-UEN Communication protocol manual IEC61850 1MRK 511 450-UEN Communication protocol manual IEC60870-5-103 1MRK 511 451-UEN Getting started guide 1MRK 505 404-UEN 1.4 Symbols and conventions 1.4.1 Symbols GUID-4F7DD10A-DEE5-4297-8697-B8AAB5E3262F v2 The electrical warning icon indicates the presence of a hazard which could result in electrical shock. 1MRK 511 451-UEN B Section 1 Introduction Distributed busbar protection REB500 3 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

The warning icon indicates the presence of a hazard which could result in

personal injury. The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property. The information icon alerts the reader of important facts and conditions. The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices. 1.4.2 Document conventions GUID-37C3ACF4-BD79-43C6-B37E-24B38EE69301 v2 A particular convention may not be used in this manual. • Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. • Push button navigation in the LHMI menu structure is presented by using the push button icons. For example, to navigate the options, use and . • HMI menu paths are presented in bold. For example, select Main menu/Settings. • Signal names are presented in bold. The signal 21120_EXT_TEST_TRIP can be set and reset via the LHMI Test Trip menu. • Parameter names and parameter values are presented in italics. For example, the default value of the Operation setting is Not inverted. • Section references are presented with the respective section numbers. For example, see Section 1.4.2 for more details about document conventions. Section 1 1MRK 511 451-UEN B Introduction 4 Distributed busbar protection REB500 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Dangerous voltages can occur on the connectors, even though the auxiliary

voltage has been disconnected. Non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation. National and local electrical safety regulations must always be followed. The frame of the IEDs has to be carefully earthed. Whenever changes are made in the IEDs, measures should be taken to avoid inadvertent tripping. The IEDs contain components which are sensitive to electrostatic discharge. Unnecessary touching of electronic components must therefore be avoided. 1MRK 511 451-UEN B Section 2 Safety information Distributed busbar protection REB500 5 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Interbay bus functions

GUID-FC8C1289-F943-4E92-A50E-BDA7281A5337 v1 3.1 Introduction GUID-7A41F2A2-F366-4D30-9D76-BB6279380110 v2 An interface is available for connecting the numerical busbar protection to a station automation system or station monitoring system (SCS/SMS). For an overview of REB500’s communication interfaces, see the Operation manual. In contrast to feeder control and protection bay units, REB500 is equipped with only a single interbay bus interface via which all the REB500 bay units in the entire station communicate. This has to be taken into account by the various bus protocols. This document applies for IEC60870-5-103. However, Section 3 of this document also contains information of a second IBB using IEC61850-8-1 if configured. 3.2 Basic configuration GUID-A112B99B-E8BF-4750-8E26-D9C9BD9F6048 v2 The fourth octet in the Data Unit Identification field of an ASDU determines the common address of ASDU. It normally has to be the same as the station address on the link layer. Exceptions are permitted where additional common ASDU addresses are needed because of multiple instances of functions. In case of REB500, this exception allowed in the IEC recommendation is used to be able to address the Central Unit and the Bay Units via a single physical connection. Common Address of ASDU – CAA Basic setting: 0 Central Unit 1-60 Bay Units 255 Global address The dialog for configuring the communication is accessed by selecting HMI500 Configuration/Communication/SCS Configuration. 1MRK 511 451-UEN B Section 3 Interbay bus functions Distributed busbar protection REB500 7 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

IEC18000623 V1 EN-US

Figure 1: Dialog box for configuring the communication If Common Link Layer Address of the SCS Configuration is selected: The link address can be setup in this dialog box. The Common Address of ASDU (CAA) for all units is setup in the CAA Setting dialog box by pressing the Addr. Setting button. Table 1: Configuration of IEC60870-5-103 Setting Description Default setting Common Link layer address Link layer address used for all Units in common 1 Baud Rate Baud rate 9600 Addr. Setting Individual Common Address of ASDU for each Bay Unit 0 Central Unit 1-60 Bay Units Section 3 1MRK 511 451-UEN B Interbay bus functions 8 Distributed busbar protection REB500 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

IEC18000624 V1 EN-US

Figure 2: Dialog box for configuring CAA Table 2: Configuration of IEC60870-5-103 Setting Description Default setting CAA Individual Common Address of ASDU for each Bay Unit 0 Central Unit 1-60 Bay Units If Common Link Layer Address of the SCS Configuration is not selected: The link address and the Common Address of ASDU (CAA) for all units is setup in the CAA Setting dialog box by pressing the Addr. Setting button. 1MRK 511 451-UEN B Section 3 Interbay bus functions Distributed busbar protection REB500 9 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

IEC18000625 V1 EN-US

Figure 3: Dialog box for configuring CAA and LLA Table 3: Configuration of IEC 870-5-103 Setting Description Default setting CAA Individual Common Address of ASDU for each Bay Unit 0 Central Unit 1-60 Bay Units LLA Individual Link Address for each Bay Unit 0 Central Unit 1-60 Bay Units 3.3 Configuring IEC 60870-5-103 IBB GUID-605B1ACD-79EB-4C0A-8839-331FD573E41B v1 For changes in status generated by REB500 to be transferred as events to an SCS/SMS, the corresponding signals must be configured by selecting them in HMI500 Configuration/Binary module and making the settings in the Event configuration section of the Details dialog box. To which IBB an event is sent is determined by selecting the appropriate check box IBB 1 or IBB 2 when configuring the signal. As the 61850 model is implemented as defined by the standard, no custom assignments can be made for the IBB associated with 61850. Section 3 1MRK 511 451-UEN B Interbay bus functions 10 Distributed busbar protection REB500 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

IEC18000608 V1 EN-US

Figure 4: Configuring signals as events Diagnostic and system events are always available for transfer whichever protocol is in use and cannot be configured. The IEC 60870-5-103 section only appears when the protocol is configured. 3.4 Transfer of differential current values 3.4.1 The delta/dead band algorithm GUID-85BE2C1A-DD67-4564-99E1-CF504CBD06D7 v1 To keep the load on the IBB as low as possible, the bus zone differential currents are checked cyclically, but only actually transferred via the bus if the value has changed. Diff. Current Values transferred to the SCS Zero limit 0 100 200 12000189-IEC18000308-1-en.vsd IEC18000308 V1 EN-US Figure 5: Transmitted values and the zero limit To stabilize the display during normal operation, differential currents below the zero limit (dead band) count as zero and are transferred as such. 1MRK 511 451-UEN B Section 3 Interbay bus functions Distributed busbar protection REB500 11 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Providing the condition for transmitting a current value is fulfilled, all the differential currents

belonging to the respective zone are sent to the SCS/SMS. sum = sum + |current – last| if sum > delta then sum = 0 if current < deadband then current = 0 endif send current endif last = current The system continuously performs the above algorithm: It adds up the absolute difference between the last two measurements (current and last) since the last status update was sent (sum). As soon as sum is greater than the threshold delta a new event will be sent with the current value. If this value is below the deadband threshold, the value 0 will be sent instead. 3.4.2 Configuring the SCS differential current parameter GUID-DF29CA42-6DDD-459D-A610-175B597D83C9 v2 The precise conditions for sending differential currents to the SCS can be set by selecting HMI500 Settings/Communication/SCS Diff. Current Parameters. 12000190-IEC18000536-1-en.vsdx IEC18000536 V1 EN-US Figure 6: Settings/Communication/SCS Diff. Current Parameters Settings in this dialog box are made for each busbar section (bus zone) and can be changed after activating the respective field. The differential current parameters are as follows: Table 4: SCS differential current parameters Item Description Min. Max. Default Step Unit Update period Determines how often the differential current measurement has to be updated. 0 1000 60 100 s Enabled Enables polling of the bus zone differential currents. yes no Yes Delta L1_L2_L3 Applies to all bus zones. Delta per bus zone for phases L1, L2 and L3. 0 65535 10 1 A Table continues on next page Section 3 1MRK 511 451-UEN B Interbay bus functions 12 Distributed busbar protection REB500 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Dead band per bus zone for phases

L1, L2 and L3. 0 65535 5 1 A Delta L0 Delta per bus zone for the neutral current L0. 0 65535 10 1 A Dead band L0 Dead Band per bus zone for the neutral current L0 0 65535 5 1 A Delta and Dead band settings that are too low, result in a high data load on the bus. For this reason, care should be taken to set reasonable values. 1MRK 511 451-UEN B Section 3 Interbay bus functions Distributed busbar protection REB500 13 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Busbar protection is not one of the types of protection defined in IEC 60870-5-103.

Nevertheless, the commands and signals of the REB500 system are modeled as far as possible on functions defined in the IEC recommendation. The functional scope of the station protocol is therefore reduced. The backup protection functions breaker failure, time-overcurrent and end fault that are optionally available with REB500 are also supported. According to the IEC recommendation, usage of the private range is only permitted with regard to the compatibility of existing devices. For this reason, additional REB500 functions that are not defined in the recommendation were implemented according to the future- oriented generic part of IEC 60870-5-103. REB500 also optionally provides a private range. Refer to IEC 60870-5-103 for an explanation of the various abbreviations. 4.2 General functions GUID-B95181CD-4E96-4569-BA0A-5D1EF56CA1D1 v2 The tables below define the functional scope of REB500 according IEC60870-5-103. The details are to be found in the recommendation itself. Table 5: System functions in monitoring direction INF Description GI. TYPE. COT <0> End of general interrogation (polling) – 8 10 <0> Time synchronization – 6 8 <2> Reset frame control bit (FCB) – 5 3 <3> Reset CU – 5 4 <4> Start/restart – 5 5 <5> Power on – 5 6 The information number 0 refers to the global function type and is the same for all system functions. The information numbers 2 to 5 are used with FUN in relation to the main function of a protection system. Table 6: Status signals in monitoring direction INF Description GI. TYPE COT REB500 signal configuration <18> Protection active x 1 1,9 41810_In service (CU output)21805_In service (BU output) <19> LED reset – 1 11 31810_External reset (CU input)11610_external reset (BU input) <20> Blocks the supervisory equipment x 1 9,11 31215_Block.IEC master_direction (CU input) 1MRK 511 451-UEN B Section 4 IEC60870-5-103 Distributed busbar protection REB500 15 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Supervisory signals in monitoring direction

INF Description GI. TYPE COT REB500 signal configuration <47> General alarm x 1 1,9 41805_Alarm (CU output) Table 8: Disturbance signals in monitoring direction INF Description GI. TYPE COT FUN REB500 signal configuration <68> General trip – 2 1 254 42305_BBP trip (CU output) 21110_TRIP (BU output) 21305_TRIP (BU output) <69> Trip L1 – 2 1 254 42315_BBP trip L1 (CU output) 23315_BFP TRIP L1 (BU output) <70> Trip L2 – 2 1 254 42320_BBP trip L2 (CU output) 23320_BFP TRIP L2 (BU output) <71> Trip L3 – 2 1 254 42325_BBP trip L3 (CU output) 23325_BFP TRIP L3 (BU output) <72> Trip L0 – 2 1 254 23340_BFP TRIP L0 (BU output) <85> Breaker failure – 2 1 254 43305_BFP trip t1 (CU output) 43310_BFP trip t2 (CU output) 23305_BFP trip t1 (BU output) 23310_BFP trip t2 (BU output) <90> Trip I> – 2 1 254 45305_OCDT trip (CU output) 25105_OCDT TRIP (BU output) 25305_OCDT trip (BU output) <92> Trip IN> – 2 1 254 42310_BBP trip L0 (CU output) Table 9: Types of function FUN Description <254> Generic Table 10: Generic functions in monitoring direction INF Description GI TYPE COT <240> Read headings of all defined groups – 10 42,43 <241> Read values or attributes of all entries of one group – 10 42,43 <242> Not used – – – <243> Read the directory of a single entry – 11 42,43 <244> Read the value or attribute of a single entry (x) 10 1,2,9,11,12,42,43 Table 11: Generic functions in control direction INF Description TYPE COT <240> Read headings of all defined groups 21 42 <241> Read values or attributes of all entries of one group 21 42 <242> Not used – – <243> Read the directory of a single entry 21 42 <244> Read the value or attribute of a single entry 21 42 Section 4 1MRK 511 451-UEN B IEC60870-5-103 16 Distributed busbar protection REB500 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Commands in control direction

INF Description TYPE COT FUN CAA <19> LED reset 20 20 254 Central Unit 4.3 Disturbance recorder GUID-442CE5CB-AD4B-428F-9921-15E145294B02 v2 Disturbance data are uploaded and displayed in accordance with the IEC recommendation with the following exceptions: • REB500 supports a maximum of 15 records per Bay Unit, but only the first (oldest) eight in the queue can be displayed in accordance with the recommendation. • Of the records that are displayed, only the oldest can be deleted or uploaded. This is determined by the REB500 principle. The time stamp invalid bit (IV) in a disturbance record is always set, because the CIM module is unaware of the synchronization status at the instant of the record. The upload of disturbance data from the central unit is not possible via IEC60870-5-103. Creating an export file HMI500 provides facility for exporting the IEC 60870-5-103 communication data contained in the system database in the form of a text file (export file). To do this, select Tools/Export SCS data and IEC 60870-5-103 IBB and then click on the Export button. The application creates a text file (export file) iec103exp.lst, which contains all the information required. The file has the following structure: 1. Disturbance recorder signal configuration 2. IEC60870-5-103 events The columns are separated by a semicolon (;). The following is an example of an export file generated by HMI500: -------------------------------------------------------------------------------------------------- IEC 60870-5-103 Disturbance Recorder signals -------------------------------------------------------------------------------------------------- CAA;ABB ref.; Feeder; Station number; Signal ID; Signal text 0;CU;-;Null;Null;Null 2;BU2;BU2;2;1;Trip 2;BU2;BU2;2;2;In service -------------------------------------------------------------------------------------------------- IEC 60870-5-103 events and private Information Object Identifier settings -------------------------------------------------------------------------------------------------- CAA;ABB ref.; Feeder; Signal text; IEC FUN;IEC INF 0;CU;BU2;41810_In service;254;18 2;BU1;BU1;23310_BFP trip t2;254;85 2;BU1;BU1;221105_I0INV Trip Si;160;67 2;BU1;BU1;211880_DIST Com Send.2;128;76 1MRK 511 451-UEN B Section 4 IEC60870-5-103 Distributed busbar protection REB500 17 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Description of the columns in the export file

Column Description CAA Common Address ASDU: Sub-address for identifying a Bay Unit at the application level ABB ref.: ABB’s designation for the Bay Unit Feeder: User’s designation for the respective bay Station Number: Disturbance recorder number Signal ID: Consecutive signal number Signal Text: User’s signal description IEC FUN: Assigned IEC function type IEC INF: Assigned IEC information number The above Signal ID and Signal Text assignment for a specific Bay Unit can also be made via HMI500 providing a COMTRADE file for the Bay Unit disturbance recorder is uploaded. The file filename.cfg generated by the PC contains the same information as the list generated by the export tool. The assignment can change when the disturbance recorder configuration changes, for example, by deleting or adding signals. The above list then has to be recreated and possibly corrected by the control system. The configured length of disturbance records shall not exceed one second (1 s) to avoid conflicts with the maximum number of 65535 events foreseen in IEC60870-5-103. 4.4 ACC actual channel GUID-1AC25D43-EFDB-4521-9ACB-FE818FB9CAF8 v2 The REB500 Bay Unit 500BU04 supports five voltage channels. Since, however, the compatible range of the standard only lists four voltage channels, the fifth channel is transferred to the private domain. Assignment of REB500 channels to IEC 60870-5-103 channel numbers: Table 14: IEC 60870-5-103 analogue channel assignment REB500 channel designation REB500 application IEC 60870-5-103 channel designation ACC (actual channel) I1 I L1 1 = I L1 I2 I L2 2 = I L2 I3 I L3 3 = I L3 I4 I L0 4 = V L1 U1 U L1 5 = V L1E U2 U L2 6 = V L3 U3 U L3 7 = V 0E U4 U L0 8 = U L1 U5 U 5 64 = private Section 4 1MRK 511 451-UEN B IEC60870-5-103 18 Distributed busbar protection REB500 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Generic REB500 functions

4.5.1 Diagnostic information GUID-9430347F-A35F-4AB3-A63A-9FF711FEBCB5 v2 Status and diagnostic information is generated by the various REB500 application software modules and transferred spontaneously as events every time the status changes. A separate group exists for diagnostic information with an entry for every subsystem of the REB500 system software REBSYS. Diagnostic event group: Table 15: Diagnostic event ENTRY No. Group 64 (0x40) 0 (Heading) Diagnostic information 1 BBP (Busbar protection) 2 ITT (Intertripping) 3 BCF (Binary input and output configuration facility) 4 DIA (Diagnostic) 5 TGR (Test generator) 6 EMI (External man/machine interface) 7 LMI (Local man/machine interface) 8 DAC (Data access) 9 TIM (Time management) 10 DBS (Database system) 11 SIG (Signal processor) 12 EVR (Event recording) 13 RFS (Remote file system) 14 SPR (Signal pre-processing and recording) 15 MBA (Multi-function bus administrator) 16 OCP (Overcurrent protection) 17 BFP (Breaker failure protection) 18 DRR (Disturbance recorder) 19 MPL (Multi functional process bus library) 20 EFP (End-fault protection) 21 PDF (Pole discrepancy function) 22 BOC (Binary input/output control) 23 BPP (Binary pre-processing) 24 DIE (Diagnostic extensions) 25 DRD (Disturbance recorder dispatcher) 26 EVA (Event and alarm handling) 27 GPI (General purpose interface) 28 LAC (LON application converter) 29 IAC (IAC application converter) 30 CMD (Command processor) Table continues on next page 1MRK 511 451-UEN B Section 4 IEC60870-5-103 Distributed busbar protection REB500 19 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Group 64 (0x40)

31 LPL (LON protocol layer) 32 TRC (Traceability) 33 BP (Bay protection) Table 16: Used attributes of ASDU 10 for diagnostic events COT CAA FUN 1 Spontaneous 0 for REB500 CU 254 Generic 1 to 60 for REB500 BU With the exception of the header (entry 0), the current values of the entries are not available on request. The response to the corresponding generic read command is therefore COT 43 ‘invalid data response to generic read command’. The current value of the group header (entry 0) corresponds to the number of subsystems in the REB500 system software. Table 17: Directory entry for GIN 0x4000 (header) COD Data type Length Number Value / Significance <10> Description <1> OS8ASCII 21 1 “Diagnostic information” <1> Current value <3> UI 1 1 Number of SW subsystems All the other entries in this group consist of the following attributes that are needed to describe a diagnostic event generated by one of the software subsystems. The status of a diagnostic event is indicated by an ASCII string, which can have one of the following values: • Initializing • Major error • Minor error • Not ready • Ready • Last wish • Shutdown • No status The error code is assigned by the application when the status changes and precisely describes the cause of the error. Table 18: Directory entry for GIN 0x40 (xx) COD Data type Length Number Value / Significance <10> Description <1> OS8ASCII 3 1 BBP (example) <1> Current value <23> DATASTRUCTU RE 29 1 (Includes the following three definitions) <1> OS8ASCII 12 1 Status <3> UI 1 1 Error code <14> BINARY TIME 7 1 Time stamp (CP56Time2a) Section 4 1MRK 511 451-UEN B IEC60870-5-103 20 Distributed busbar protection REB500 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

The following table gives an example of the ASDU 10 Generic Data that is transferred

spontaneously for a diagnostic event. Table 19: TYPE IDENTIFICATION: Generic data 0 0 0 0 1 0 1 0 Type Identification 10 DATA UNIT IDENTIFIER 1 0 0 0 0 0 0 1 Variable Structure Qualifier SQ=1, SQ_No.= 1 Spontaneous <1> Cause Of Transmission COT REB500 CU/BU No. Common Address of ASDU <0 .. 60> GEN <254> Function type FUN INFORMATION OBJECT Read value of single entry <244> Information number INF <0> Return information identifier RII {1, 0, 0} Number of generic data sets NGD {NO, COUNT, CONT} 40 H 01 H Generic identification number GIN Example Current value <1> Kind of description KOD DATA STRUCTURE <23> 29 1,0 DATA TYPE DATA SIZE NUMBER, CONT GDD <1> OS8ASCII 12 1,0 DATA TYPE DATA SIZE NUMBER, CONT GDD 1 Major Error GID 1 (example) <3> UI 1 1,0 DATA TYPE DATA SIZE NUMBER, CONT GDD 2 Error code (UI1) GID 2 <14> BINARY TIME 7 1,0 DATA TYPE DATA SIZE NUMBER, CONT GDD 3 Time stamp (CP56Time2a) GID 3 4.5.2 Status information GUID-49587D6A-D1F8-43AD-ACBD-AEB285A3C396 v1 All the status information relating to binary input and output signals, internal signals (single- point indications - SPI) and switchgear positions (double-point indications - DPI) that are configured in REB500 for transfer via IEC60870-5-103, but are not covered by the compatible part of the IEC recommendation, are transferred as generic data. An entry is made in the table for every event configured using HMI500 or REBCON for transfer via IEC 60870-5-103. Since there can be more events per type (SPI or DPI) than the maximum number of entries a group can have (255), the system reserves additional groups as necessary. By this means, up to 1020 events per event type can be defined in the generic part. 1MRK 511 451-UEN B Section 4 IEC60870-5-103 Distributed busbar protection REB500 21 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Group for displaying status information

Entry No. Group No. 66 (0x42) to Group No. 69 (0x45) Group No. 70 (0x46) to Group No. 73 (0x49) 0 (Heading) Single-point indications Double-point indications 1 Indication #1 Indication #1 2 Indication #2 Indication #2 … … … 255 Indication #255 Indication #255 Table 21: Used attributes of ASDU 10 for status information COT CAA FUN 1 Spontaneous 0 / 1..60 REB500 CU / REB500 BU 254 Generic With the exception of the header (entry 0), the current values of the entries are not available on request. The response to the corresponding generic read command is therefore COT 43 “invalid data response to generic read command”. 4.5.3 Entries for single-point indications GUID-AD226E53-FF68-4ADB-BA19-CB654D580D49 v2 Table 22: Directory entry for GIN 0x4200 (header) COD Data type Length Number Value / Significance <10> Description <1> os8ascii 24 1 Single-point indications <1> Current value <3> UI 1 1 Number of SPI defined in this group Table 23: Directory entry for GIN 0x42 (xx) COD Data type Length Number Value / Significance <10> Description <1> os8ascii 20 1 Event text defined by user <1> Current value <23> data structure 14 1 (Includes the following two definitions) <9> Double Point Information 1 1 OFF (1) / ON (2) <14> binary time 7 1 Time stamp (CP56Time2a) The following table gives an example of the ASDU 10 Generic Data that is transferred spontaneously for a single-point indication. Table 24: TYPE IDENTIFICATION: Generic data 0 0 0 0 1 0 1 0 Type Identification 10 DATA UNIT IDENTIFIER 1 0 0 0 0 0 0 1 Variable Structure Qualifier SQ=1, SQ_No.= 1 Spontaneous <1> Cause Of Transmission COT REB500 CU/BU No. Common Address of ASDU <0 .. 60> Table continues on next page Section 4 1MRK 511 451-UEN B IEC60870-5-103 22 Distributed busbar protection REB500 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Read value of single entry <244>

Information number INF OBJECT <0> Return information identifier RII {1, 0, 0} Number of generic data sets NGD {NO, COUNT, CONT} 43 H Generic identification number Group <41H .. 45H> 01 H Entry <1 .. 255> Current value <1> Kind of description KOD DATA STRUCTURE <23> 14 1,0 DATA TYPE DATA SIZE NUMBER, CONT GDD <9> DOUBLE-POINT INFORMATION 1 1,0 DATA TYPE DATA SIZE NUMBER, CONT GDD 1 0 0 0 0 0 0 <0 .. 3> GID 1 <14> BINARY TIME 7 1,0 DATA TYPE DATA SIZE NUMBER, CONT GDD 2 Time stamp (CP56Time2a) GID 2 4.5.4 Entries for double-point indications GUID-F19F8A2D-F20A-4393-AEB3-66F5D3292526 v2 Table 25: Directory entry for GIN 0x4600 (header) COD Data type Length Number Value / Significance <10> Description <1> os8ascii 24 1 Double-point Indications <1>Current value <3> UI 1 1 Number of DPI defined in this group. Table 26: Directory entry for GIN 0x46 (xx) COD Data type Length Number Value / Significance <10> Description <1> os8ascii 20 1 Event text defined by user <1> Current value <23> data structure 14 1 (Includes the following two definitions) <9> Double Point INFORMATIO N WITH TRANSIENT AND ERROR 1 1 TRANSIENT (0) /OFF (1) / ON (2) / ERROR (3) <14> binary time 7 1 Time stamp (CP56Time2a) The following table gives an example of the ASDU 10 Generic Data that is transferred spontaneously for a double-point indication. 1MRK 511 451-UEN B Section 4 IEC60870-5-103 Distributed busbar protection REB500 23 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

TYPE IDENTIFICATION: Generic data

0 0 0 0 1 0 1 0 Type Identification 10 DATA UNIT IDENTIFIER 1 0 0 0 0 0 0 1 Variable Structure Qualifier SQ=1, SQ_No.= 1 Spontaneous <1> Cause Of Transmission COT GEN <254> Function type FUN INFORMATION Read value of single entry <244> Information number INF OBJECT <0> Return information identifier RII {1, 0, 0} Number of generic data sets NGD {NO, COUNT, CONT} 46 H Generic identification number Group <46H .. 49H> 01 H Entry <1 .. 255> Current value <1> Kind of description KOD DATA STRUCTURE <23> 14 1,0 DATA TYPE DATA SIZE NUMBER, CONT GDD <9> DOUBLE-POINT INFORMATION WITH TRANSIENT AND ERROR 1 1,0 DATA TYPE DATA SIZE NUMBER, CONT GDD 1 0 0 0 0 0 0 <0 .. 3> GID 1 <14> BINARY TIME 7 1,0 DATA TYPE DATA SIZE NUMBER, CONT GDD 2 Time stamp (CP56Time2a) GID 2 4.5.5 Display of busbar differential currents GUID-A271FDFD-8D47-4A1F-B45E-51DB2BD31164 v2 The differential currents are displayed for each corresponding busbar zone (1..32) (see transfer of differential currents). Table 28: Used attributes of ASDU 10 for differential current COT CAA FUN 1 Spontaneous 0 REB500 CU 254 Generic The group number 75 (0x4B) is used to display busbar differential currents and is therefore only assigned to the Central Unit (CAA = 0). Table 29: Directory entry for GIN 0x4B00 (header) COD Data type Length Number Value / Significance <10> Description <1> os8ascii 21 1 Differential currents <1> Current value <3> UI 1 1 Number of valid entries The number of valid entries corresponds to the number of bus-bar zones and thus limited to the range [1…32]. Each of the entries 1…32 in the group relates to a given busbar zone. Section 4 1MRK 511 451-UEN B IEC60870-5-103 24 Distributed busbar protection REB500 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Directory entry for GIN 0x4B (xx)

COD Data type Length Number Value / Significance <10> Description <1> os8ascii 3 1 BBI, example <1> Current value <23> data structure 2 1 (Includes the following two definitions) <12> Measured variable with quality descriptor 2 3,4 Field with 3 / 4 measurements CP16 {OV,ER,RES,MVAL} <14> binary time 7 1 Time stamp (CP56Time2a) <9> Unit <1> os8ascii 1 1 A <6> Factor <6> I 4 1 32 Bit integer The description has a maximum length of 16 characters. The current value is a field with three (L1, L2, L3) or four (L1, L2, L3, L0) measurements and the associated time stamp. The effective number of measurements is determined by how the REB500 is configured. Table 31: COD Current Value Attribute Description OV Overflow This Bit is set to <1> whenever an overflow occurs or the measurement is not assigned. It is normally therefore set to <0>. ER Error flag BBP (Busbar protection) This Bit indicates whether a measurement is valid or not (measurement valid <0>, measurement invalid <1>). RES Reserved Spare for future use. MVAL Contains the actual measurement in fixed decimal point format. The Factor is a 32 Bit integer for scaling to the original value. The following table gives an example of the ASDU 10 ‘Generic Data’ that is transferred spontaneously for displaying the differential currents of a given bus zone. Table 32: TYPE IDENTIFICATION: Generic data 0 0 0 0 1 0 1 0 Type Identification 10 DATA UNIT IDENTIFIER 1 0 0 0 0 0 0 1 Variable Structure Qualifier SQ=1, SQ_No.= 1 Spontaneous <1> Cause Of Transmission COT REB500 CU Common Address of ASDU <0> GEN <254> Function type FUN INFORMATION Read value of single entry <244> Information number INF OBJECT <0> Return information identifier RII {1, 0, 0} Number of generic data sets NGD {NO, COUNT, CONT} 4B H Generic identification number Group Table continues on next page 1MRK 511 451-UEN B Section 4 IEC60870-5-103 Distributed busbar protection REB500 25 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Entry <1 .. 32>

Current value <1> Kind of description KOD DATA STRUCTURE <23> 21 1,0 DATA TYPE DATA SIZE NUMBER, CONT GDD <12> MEASUREMENT WITH QUALITY DESCRIPTOR 2 3,0 DATA TYPE DATA SIZE NUMBER, CONT GDD 1 3 or 4 (including measurement L0) OV ER RES MVAL (4 .. 8) GID 1a MVAL (9 .. 16) OV ER RES MVAL (4 .. 8) GID 1b MVAL (9 .. 16) OV ER RES MVAL (4 .. 8) GID 1 c MVAL (9 .. 16) <14> BINARY TIME7 1,0 DATA TYPE DATA SIZE NUMBER, CONT GDD 2 Time stamp (CP56Time2a) GID 2 4.6 Special information and instructions for configuring the control system GUID-A8AF440A-22B6-4443-B341-64B408B162ED v2 Private range Provision is made in the event configuration (see Section 3.3) for the user to enter his own private IEC60870-5-103 definition for each REB500 signal. The input fields for REB500 signals covered by the public part of the standard (see Section 4.2) have a bright yellow background their default setting 0 for both IEC function type and information number. All other signals receive the presetting 0 for the IEC function type and the information number. A signal defined for protocol 60870-5-103 that is not in the public range and has 0 set for function type and information number is transmitted via the generic part of the protocol. A private IEC60870-5-103 definition can be entered for every REB500 signal in this dialog. The Set Default button is enabled for a signal in the public range of the protocol so that the ABB default setting can be restored at any time. The limitations specified in the standard must be observed when assigning information numbers. The latter must be within the following ranges: 16-52; 73; 128-130; 64-72; 74-93 Section 4 1MRK 511 451-UEN B IEC60870-5-103 26 Distributed busbar protection REB500 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

IEC18000627 V1 EN-US

Figure 7: Private IEC 60870-5-103 definition Disturbance recorder, binary signal transfer Binary signals transmitted in disturbance records only have numbers and no designation. The assignment of numbers to signal names is given in the COMTRADE file filename.cfg, which can be uploaded, for example, from aBay Unit using HMI500. Signal configuration instructions Should the same logical signal be configured on two different BIO modules in a Bay Unit, only one of them should be relayed to the IEC 60870-5-103 bus. A configuration that is duplicated produces two indistinguishable events, which can cause some confusion. The response is reflected by HMI500, which also generates two events. Cause of transmission With the exception of 42 (generic writing command), all the possible causes of transmission are supported in the command direction. In the supervisory direction, they are all supported with the exception of 7 (test mode), 12 (local HMI) and 44 (return confirmation of a generic write command). Type identification The type identification defines the type of ASDU that has been transferred. Table 33: Information in the supervisory direction TYPE Description <1> time-tagged message <2> time-tagged message with relative time <5> Identification <6> Time synchronization <8> General interrogation termination <10> Generic data <11> Generic identification <23> List of recorded disturbances <26> Ready for transmission of disturbance data <27> Ready for transmission of a channel <28> Ready for transmission of tags <29> Transmission of tags <30> Transmission of disturbance values <31> End of Transmission 1MRK 511 451-UEN B Section 4 IEC60870-5-103 Distributed busbar protection REB500 27 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved

Information in the command direction

TYPE Description <6> Time synchronization <7> General interrogation (polling) <10> Generic data <20> General command <21> Generic command <24> Order for disturbance data transmission <25> Acknowledgement for disturbance data transmission Timeouts • Protocol time-out <50 ms as defined in the IEC recommendation applies for the protocol. • When a command to upload the disturbance recorder data is issued, the data has to be transferred from the Bay Unit to the Central Unit first before they are transferred via the IEC bus. The timeout from the instant the upload command is issued to the receipt of the data varies in relation to the length of the disturbance record. The following applies: STP timeout <2.5 minutes per 1 second of disturbance record data (4I+4U, 2400 Hz). • Once the transfer of disturbance recorder data has started, the timeout changes to: Transfer timeout <1 Minute Section 4 1MRK 511 451-UEN B IEC60870-5-103 28 Distributed busbar protection REB500 Communication protocol manual IEC60870-5-103 © Copyright 2019 ABB. All rights reserved