ABB PQFS Installation, Operation And Maintenance Instructions
Read Online
Read the ABB PQFS Installation, Operation And Maintenance Instructions online using the built-in PDF viewer.
Text of the manual
Power Quality Filter PQFS
Installation, operation and maintenance
instructions
2 Table of contents Manual Power Quality Filter PQFS
—
Table of contents
1
Introduction to this manual .............................................................................................................. 6
1.1
What this chapter contains............................................................................................................................ 6
1.2
Intended audience ........................................................................................................................................... 6
1.3
Compatibility .................................................................................................................................................... 6
1.4
Contents ............................................................................................................................................................. 6
1.5
Related publications ........................................................................................................................................ 6
2
Safety Instructions ............................................................................................................................. 8
3
Upon Reception ................................................................................................................................ 10
3.1
What this chapter contains.......................................................................................................................... 10
3.2
Delivery inspection ........................................................................................................................................ 10
3.3
Unpacking instructions ................................................................................................................................ 10
3.4
Lifting and transportation guidelines ....................................................................................................... 10
3.5
Identification tag ........................................................................................................................................... 13
3.6
Storage ............................................................................................................................................................. 13
4
Hardware description ...................................................................................................................... 14
4.1
What this chapter contains.......................................................................................................................... 14
4.2
Typical PQFS filter panel layout .................................................................................................................. 14
4.3
The PQF current generator hardware ....................................................................................................... 16
4.4
The PQF main controller ............................................................................................................................... 17
4.5
The PQF-Manager user interface................................................................................................................ 18
4.6
Location of the main PQFS components ................................................................................................. 25
4.6.1 Active filter components ................................................................................................................... 25
4.6.2 Active filter door components and protective grid .................................................................... 29
5
Mechanical design and installation ................................................................................................ 30
5.1
What this chapter contains......................................................................................................................... 30
5.2
Installation location requirements ........................................................................................................... 30
5.3
Airflow and cooling requirements .............................................................................................................. 31
5.4
Standard cubicle dimensions, fixing holes and clearances ................................................................. 32
5.5
Instructions for mounting the filter .......................................................................................................... 33
5.6
Filter noise level ............................................................................................................................................. 34
5.7
Instructions for mounting the PQF-Manager in enclosures ................................................................ 35
6
Electrical design and installation ................................................................................................... 36
6.1
What this chapter contains..........................................................................................................................36
6.2
Instructions for connecting the PQF-Manager to a filter system ...................................................... 37
6.3
Checking the insulation of the assembly - earth resistance ................................................................ 37
6.4
EMC considerations.......................................................................................................................................38
6.5
Earthing guidelines ........................................................................................................................................38
6.6
Selection of the power cable size ...............................................................................................................39
6.7
Selection of the power cable protection/filter input protection scheme ........................................42
6.8
Connection of the PQFS to the network.................................................................................................. 44
6.8.1 Connection of the PQFS in 3-wire mode ...................................................................................... 45
6.8.2 Connection of the PQFS in 4-wire mode ....................................................................................... 47
6.9
Selection of the current transformers ..................................................................................................... 48
6.10 Current transformer installation ............................................................................................................... 50
6.10.1 Basic rules for correct CT installation ........................................................................................... 50
6.11
Electrical interconnection of PQFS enclosures ....................................................................................... 52
6.11.1 Mechanical interconnection of the enclosures ............................................................................ 53
6.11.2 Control board cable interconnection ............................................................................................. 53
6.11.3 CT cable interconnection ................................................................................................................. 54
6.11.4 Connection of the power stage to the supply .............................................................................55
6.12 Electrical connections to the PQF-Manager user interface ................................................................ 56
Manual Power Quality Filter PQFS Table of contents 3
6.12.1 Cabling of remote control functionality ........................................................................................ 57
6.12.2 Cabling of alarm functionality ........................................................................................................ 59
6.12.2.1 Alarm outputs .................................................................................................................... 59
6.12.2.2 Digital outputs.................................................................................................................... 62
6.12.3 Cabling of warning functionality .................................................................................................... 64
6.12.4 Cabling of the digital output contacts to monitor other filter operation modes than
warnings and alarms .................................................................................................................................... 65
6.12.5 Cabling of main/auxiliary control functionality ......................................................................... 66
6.12.6 Implementation of local start/stop buttons ............................................................................... 67
6.13 Electrical connections of filter options and accessories ......................................................................70
6.13.1 External communication with PQF .................................................................................................70
6.13.2 Connection of the Modbus adapter ............................................................................................... 71
7
The PQF-Manager user interface .....................................................................................................72
7.1
What this chapter contains.......................................................................................................................... 72
7.2
PQF-Manager user interface description ................................................................................................. 72
7.3
PQF-Manager overview and navigation .................................................................................................... 73
7.4
Icons and main screen .................................................................................................................................. 73
7.5
The PQF-Manager behavior during filter initialization ......................................................................... 80
7.6
The PQF-Manager locking facilities ........................................................................................................... 81
7.7
The PQF start, stop and fault acknowledgement menu ....................................................................... 82
7.8
The ‘Measurements’ menu .......................................................................................................................... 84
7.8.1 The ‘Overview’ menu ......................................................................................................................... 84
7.8.2 The ‘System values’ menu ................................................................................................................ 86
7.8.2.1
Voltages .............................................................................................................................. 86
7.8.2.2
Line currents ...................................................................................................................... 88
7.8.2.3
Filter currents .................................................................................................................... 89
7.8.2.4
Total filter currents........................................................................................................... 90
7.8.2.5
Powers .................................................................................................................................. 91
7.8.2.6
Temperatures ..................................................................................................................... 91
7.8.3 The ‘Min-Max logging’ menu ............................................................................................................ 92
7.9
The ‘Settings’ menu .......................................................................................................................................93
7.9.1 The ‘Customer settings’ menu ....................................................................................................... 94
7.9.1.1
Settings up harmonics, reactive power and filter mode ......................................... 95
7.9.1.2
Temp unit ........................................................................................................................... 101
7.9.1.3
Activate menu ................................................................................................................... 101
7.9.1.4
Setting up alarms, warnings and digital inputs and outputs (D I/O) ................. 102
7.9.2 The ‘Commissioning’ menu ........................................................................................................... 104
7.9.2.1
Setting up the network characteristics and the filter synchro mode ................ 105
7.9.2.2
Setting up the filter characteristics ........................................................................... 106
7.9.2.3
Setting up the current transformer ratios and position ....................................... 108
7.9.2.4
Setting up the filter rating parameter ........................................................................ 114
7.9.2.5
Setting up the user’s requirements ............................................................................. 115
7.9.2.6
Commissioning of temperature probes ..................................................................... 116
7.9.3 The ‘Installation settings’ menu .................................................................................................... 117
7.9.3.1
Setting up the ‘standby’ function ................................................................................ 118
7.9.3.2
Setting up the ‘auto restart’ function ......................................................................... 120
4 Table of contents Manual Power Quality Filter PQFS
7.9.3.3
Setting up the system clock .......................................................................................... 120
7.9.3.4
Setting Password ............................................................................................................. 121
7.9.3.5
Installation Locking ......................................................................................................... 121
7.9.4 Set Language ..................................................................................................................................... 122
7.10 The ‘PQF monitoring’ menu ....................................................................................................................... 122
7.10.1 The ‘Status of module’ menu ......................................................................................................... 123
7.10.2 The ‘Filter load’ menu ....................................................................................................................... 123
7.10.3 The ‘Event logging’ menu ................................................................................................................ 124
7.10.4 The ‘Active warnings’ menu ............................................................................................................ 128
7.10.5 The ‘Number of errors’ menu ......................................................................................................... 128
7.10.6 The ‘PQF operation’ .......................................................................................................................... 129
7.11
The ‘User Interface menu ........................................................................................................................... 130
7.11.1 Manufacturer setting ....................................................................................................................... 130
7.11.2 About PQF .......................................................................................................................................... 130
7.11.3 Screen configuration ....................................................................................................................... 131
7.11.4 Communication ................................................................................................................................. 132
7.11.4.1 Modbus RTU ...................................................................................................................... 133
7.11.4.2 MAC address ..................................................................................................................... 135
7.11.4.3 Ethernet settings ............................................................................................................. 135
7.11.4.4 IP address .......................................................................................................................... 139
8
Commissioning instructions .......................................................................................................... 141
8.1
What this chapter contains........................................................................................................................ 141
8.2
Step 1: Visual and installation check ........................................................................................................ 142
8.3
Step 2: Setting the address of each unit in a multi-unit filter and terminate the CAN bus ........ 142
8.4
Step 3: Voltage rating check/adaptation and phase rotation check .............................................. 145
8.5
Step 4: Basic commissioning parameters set up (using PQF-Manager) ....................................... 146
8.6
Step 5: Automatic and manual CT detection procedure ................................................................... 148
8.6.1 Automatic CT detection procedure ............................................................................................. 148
8.6.2 Manual CT detection procedure ................................................................................................... 149
8.6.2.1
PQF connection diagram .............................................................................................. 149
8.6.2.2
Material needed and hypotheses for correct measurements .............................. 150
8.6.2.3
Checking the correct connection of the CTs with a two-channel scopemeter 150
8.6.2.4
Checking the correct connection of the CTs with a Fluke 41B or similar
equipment .......................................................................................................................................... 154
8.7
Step 6: Before starting the filter .............................................................................................................. 154
8.8
Step 7: Start the filter .................................................................................................................................. 154
8.9
Step 8: Generate filter load ........................................................................................................................ 155
8.10 Step 9: Set up the user requirements...................................................................................................... 156
8.11
Commissioning report ................................................................................................................................ 159
8.11.1 Filter identification .......................................................................................................................... 160
8.11.2 Inspection on site – verification of the active filter after installation .................................. 161
8.11.3 Programming ..................................................................................................................................... 162
8.11.4 Testing (with load) ........................................................................................................................... 163
8.11.5 Programmed parameters .............................................................................................................. 164
8.11.6 Comments ..........................................................................................................................................166
9
Operating instructions ...................................................................................................................167
9.1
What this chapter contains........................................................................................................................ 167
9.2
Starting and stopping the filter ............................................................................................................... 167
9.2.1 Starting the filter with the PQF-Manager ...................................................................................168
Manual Power Quality Filter PQFS Table of contents 5
9.2.2 Stopping the filter with the PQF-Manager ................................................................................. 170
9.3
Modifying the user requirements............................................................................................................. 172
9.4
Changing the system temperature unit and PQF-Manager backlighting ...................................... 173
9.5
Consulting filter measurements............................................................................................................... 173
9.6
Consulting filter statistics and manufacturer data ............................................................................. 173
9.7
Filter behavior on fault – retrieving error information ........................................................................ 174
10
Maintenance instructions ...............................................................................................................176
10.1
What this chapter contains........................................................................................................................ 176
10.2 Maintenance intervals ................................................................................................................................. 176
10.3 Standard maintenance procedure ........................................................................................................... 177
10.3.1 Step 1: Check the ambient temperature conditions ................................................................ 177
10.3.2 Step 2: Record the filter operating status .................................................................................. 177
10.3.3 Step 3: Shut the filter down ............................................................................................................ 177
10.3.4 Step 4: Inspect and clean the filter ............................................................................................... 178
10.3.5 Step 5: Check the condition of the filter contactors and fuses ............................................. 178
10.3.6 Step 6: Check the tightness of the electrical and mechanical connections ....................... 178
10.3.7 Step 7: Correct any abnormal conditions found ....................................................................... 178
10.3.8 Step 8: Restart the filter .................................................................................................................. 178
10.4 Fan replacement ........................................................................................................................................... 179
10.5 DC capacitor change .................................................................................................................................. 180
10.6 DC capacitor reforming ............................................................................................................................. 180
10.7 Output filter board change ........................................................................................................................ 181
10.8 Servicing report ............................................................................................................................................ 181
10.8.1 Filter identification ........................................................................................................................... 182
10.8.2 Standard maintenance procedure ................................................................................................ 183
10.8.3 Special service actions .................................................................................................................... 185
10.8.4 Comments .......................................................................................................................................... 185
11
Troubleshooting guide .................................................................................................................. 186
11.1
What this chapter contains........................................................................................................................186
11.2
Fault treatment procedure ........................................................................................................................186
11.3
Spare part list for normal and dedicated filter servicing ...................................................................189
11.4
Troubleshooting guide .............................................................................................................................. 190
11.4.1 Verification of the PQF-Manager status and the system LEDs ............................................ 190
11.4.2 Fault tracing ....................................................................................................................................... 191
12
Technical specifications ................................................................................................................ 210
12.1
What this chapter contains........................................................................................................................ 210
12.2
Technical specifications ............................................................................................................................. 210
6 Introduction Manual Power Quality Filter PQFS
—
1 Introduction to this manual
1.1
What this chapter contains
This chapter gives basic information on this manual.
1.2
Intended audience
This manual is intended for all people that are involved in integrating, installing,
operating and/or maintaining the PQFS active filter range products. People involved in
the integration, installation and maintenance of the equipment are expected to know
the standard electrical wiring practices, electronic components and electrical schematic
symbols. End users should focus on the Operating instructions (Cf. Chapter 9) and
Maintenance instructions (Cf. Chapter 10) of this manual.
1.3
Compatibility
The manual is compatible with all filters of PQF range with PQF-Manager software
versions or higher.
−
V1 : V26 r3001
−
V2 : V11 r23
−
V3 : V2 r0
−
V4 : V0.1 r8
This product is not backward compatible with any other PQFx (x: A, B, L, T, I, M, K, S) filter
product.
1.4
Contents
−
Chapter 1: Introduction to this manual
−
Chapter 2: Safety instructions
−
Chapter 3: Upon reception
−
Chapter 4: Hardware description
−
Chapter 5: Mechanical design and installation
−
Chapter 6: Electrical design and installation
−
Chapter 7: The PQF-Manager user interface
−
Chapter 8: Commissioning instructions
−
Chapter 9: Operating instructions
−
Chapter 10: Maintenance instructions
−
Chapter 11: Troubleshooting guide
−
Chapter 12: Technical specifications
1.5
Related publications
−
Power Quality Filters PQFI-PQFM-PQFS Catalogue [English]
Manual Power Quality Filter PQFS Introduction 7
−
Power Quality Filter, Active Filtering Guide [English]
−
PQ-Link Installation and user’s guide [English]
−
PQF Modbus CD [English]
−
ABB PQF Active Filters - Raising system reliability to unprecedented levels
[English]
−
ABB quick start
8 Safety Instructions Manual Power Quality Filter PQFS
—
2 Safety Instructions
These safety instructions are intended for all work on the PQFS. Neglecting these
instructions can cause physical injury and death. All electrical installation and
maintenance work on the PQFS should be carried out by qualified electricians. Do not
attempt to work on a powered PQFS
After switching off the supply to the PQFS, always wait at least 25 minutes before
working on the unit in order to allow the discharge of DC capacitors through the
discharge resistors. Always verify by measurement that the capacitors have discharged.
DC capacitors may be charged to more than 800 Vdc.
Before manipulating current transformers, make sure that the secondary is short-
circuited. Never open the secondary of a loaded current transformer.
You must always wear isolating gloves and eye-protection when working on electrical
installations. Also make sure that all local safety regulations are fulfilled.
DANGER: To ensure safe access, supplies to each individual enclosure must be isolated
before entry / opening.
WARNING: This equipment contains capacitors that are connected between phase and
earth. A leakage current will flow during normal operation. Therefore, a good earth
connection is essential and must be connected before applying power to the filter.
WARNING: There are AC capacitors & DC capacitors connected inside this filter. Before
performing any maintenance work, please short and ground the three line terminals.
The DC capacitor needs 25 mins to discharge after disconnection. Please wait for this
duration before touching any live parts even after discharging the AC capacitors to
avoid electrical shock.
WARNING: Never discharge DC capacitors through short circuit. Always use a current
limiting resistor of minimum 100Ω.
WARNING: To avoid electrical shock due to residual voltage on the capacitors, the left
side cover of the filter should not be removed once the filter is commissioned.
WARNING: If the ground is not done properly, under certain fault conditions in the unit
or in the system to which it is connected it can result in full line voltage between
chassis and earth ground. Severe injury or death can result if the chassis and earth are
touched simultaneously.
Manual Power Quality Filter PQFS Safety Instructions 9
WARNING: The neutral current in a PQFS filter may be as high as 3 times the line current
hence do not use a 4 pole breaker to connect this type of filter as the rating of the
neutral pole may not be adequate.
10 Upon Reception Manual Power Quality Filter PQFS
—
3 Upon Reception
3.1
What this chapter contains
This chapter gives basic information on how to inspect, transport, identify and store the
PQFS active filter.
3.2
Delivery inspection
Each PQFS is delivered in a box designed to protect adequately the equipment during
shipment. Upon reception of the equipment, make sure that the packing is in good
condition. Verify the state of the shock and tilting indicators (if mounted on the
enclosure).
After removal of the packing, check visually the exterior and interior of your filter for
transportation damage.
3.3 Unpacking instructions
Figure 1: PQFS packing material opened
After removal of the top cover, check visually the exterior and interior of your filter for
transportation damage.
Your filter equipment comes with a package. Verify that all items are present, i.e.:
−
this manual
−
the electrical drawing
−
the rubber seal to cover a knock-out (to be used for multi-unit operation)
−
the communication cable needed for multi-unit operation
−
the two eyebolts
Any loss or damage should be notified immediately to your ABB representative.
3.4
Lifting and transportation guidelines
Please note that filter equipment weighs approximately 130 kilograms. Care should be
taken to ensure that correct handling facilities are used.
Manual Power Quality Filter PQFS Upon Reception 11
In order to transport the equipment use a forklift or similar equipment. PQFS enclosures
are best transported horizontally.
Table 1: Maximum allowed ambient conditions during transportation
Transportation (in the protected package)
Temperature
-25 to 70°C (-13 to 158°F)
Relative humidity
Max. 95%
Contamination levels (IEC 60721-3-3)
Chemical class 3C3(a)
Mechanical class 3S3(b)
Remarks:
(a) Locations with normal levels of contaminants, experienced in urban areas with industrial
activities scattered over the whole area, or with heavy traffic. Also applies to locations with
immediate neighborhood of industrial sources with chemical emissions.
(b) Locations without special precautions to minimize the presence of sand or dust. Also
applies to locations in close proximity to sand or dust sources.
In order to lift the equipment once it is at the installation location:
−
Remove the top cover of the protecting box (see Figure 1).
−
Remove the 4 panel securing screws at the bottom and the top of the enclosure
(see Figure 2).
Bottom side
Top side
Figure 2: Locating the 4 panel securing screws
−
Remove first the right side of the protective cover and put it aside (see Figure 3).
Figure 3: Lifting the right protective cover and putting it aside
12 Upon Reception Manual Power Quality Filter PQFS
−
Unplug the PQF-Manager from the main system (see Figure 4). Then the
protective cover can be safely put aside.
Figure 4: Unplugging the PQF-Manager from the main system
−
Remove the two screws fixing the filter unit to the wooden support (see Figure
5).
Right side Bottom
Figure 5: Position of the filter fixation screws that need to be removed
−
Fix the two eyebolts provided with the filter (see Figure 6).
Figure 6: Fix the eyebolts before lifting the PQFS
Manual Power Quality Filter PQFS Upon Reception 13
−
Fix an appropriate lifting device to the eyebolts to lift the filter from the wooden
support. It can then be positioned at the desired location (see Figure 7).
Figure 7: Lifting a PQFS unit by using the lifting lugs
3.5
Identification tag
Each PQFS is fitted with nameplates for identification purposes.
The filter nameplate is located at the top left of the master panel door, at the outside.
The nameplate information should always remain readable to ensure proper
identification during the whole life of the filter. The main filter nameplate includes the
filter type, the nominal voltage range and frequency as well as a serial number and an
ABB internal article code.
3.6
Storage
If your PQFS is not installed once unpacked, it should be stored in a clean indoor, dry,
dust free and non-corrosive environment. The storage temperature must be between -
25°C (-13°F) and 70°C (158°F) with a maximum relative humidity of 95%, non-condensing.
Table 2: Maximum allowed ambient conditions for storage
Storage (in the protected package)
Temperature
-25 to 70°C (-13 to 158°F)
Relative humidity
Max. 85%
Contamination levels (IEC 60721-3-
3)
Chemical class 3C3(a)
Mechanical class 3S3(b)
Remarks:
(a) Locations with normal levels of contaminants, experienced in urban areas with industrial
activities scattered over the whole area, or with heavy traffic.
(b) Locations without special precautions to minimize the presence of sand or dust. Also
applies to locations in close proximity to sand or dust sources.
14 Hardware description Manual Power Quality Filter PQFS
—
4 Hardware description
4.1
What this chapter contains
This chapter describes a typical PQFS-filter system and discusses its main components.
4.2 Typical PQFS filter panel layout
The PQFS active filter is basically composed of two parts (Figure 8):
−
A filter controller that determines the anti-harmonic current to be injected based
on the line current measurements and the user’s requirements. The line current
measurements are obtained from current transformers (CTs) provided by the
customer. The CTs must be connected upstream of the connection point of the
filter and the loads. The user enters his requirements by means of the PQF-
Manager user interface. This device also acts as the user’s connection point for
the alarm/warning contacts, the remote control functionality, the other digital
input functionality and the interface for external communication.
−
A current generator (power unit) that converts the control signals generated by
the filter controller into the filter compensation current. The current generator is
connected in parallel with the load(s). Up to eight power units may be connected
in parallel in one filter unit. The enclosure(s) containing the/a filter GUI controller
are referred to as master units. The other enclosures are referred to as the slave
units. In an active filter system more than one master unit can be present.
Compensation current
Current measurements
Non-linear load(s)
- Three-phase
- Single-phase
Supply
PQFS Filter panel
PQF main
controller
PQF current
generator 1
PQF Manager
1
2
3
5
4
6
Figure 8: PQFS schematic overview with user connections
The user connection description is given in Table 3.
Manual Power Quality Filter PQFS Hardware description 15
Table 3: User connections for PQFS
Item
User connections
Connection requirement
1
CT connections
Mandatory
2
Power cable connection to the supply (including
neutral connection if 4-wire operation is desired)
Mandatory
3
Programmable digital outputs (warnings…)
Not mandatory
4
Remote control contact connection or/and local
on/off buttons or/and main/auxiliary settings control
Not mandatory
5
PQ-link (USB-Ethernet) – Modbus RTU – Modbus TCP
communication connection
Not mandatory
6
Earth connections from the enclosure to installation
earth
Mandatory
Mandatory connections are connections that must be present to make the filter
operational. Connections that are not mandatory can be made to enhance the filter’s
basic functionality. For more information on cabling the user connections, please refer
to Chapter 6.
Figure 9 shows a typical PQFS master filter panel.
1
2
4
5
3
Figure 9: Example of a typical PQFS master filter panel
The input/output connections and protection description is given in Table 4.
Table 4: Input/Output connections
Item
Input/output connections
1
CT connection terminals
2
Main power connection
3
Auxiliary fuse protection
4
PQF-Manager user interface with connection terminals for user I/O (e.g. alarm
contact) and communication interfaces.
5
Neutral connection
16 Hardware description Manual Power Quality Filter PQFS
Up to 8 PQFS master panels can be connected in parallel providing full redundancy to the
customer. In addition to using master panels only, PQFS units can be connected in a
master-slave arrangement.
4.3
The PQF current generator hardware
The power circuit of a PQFS unit is represented hereafter.
N
Preload
resistor
Output filter
IGBT
Inverter
Master Unit
N
AC power supply
L
L
1
2
3
4
5
6
7
8
Figure 10: Power circuit diagram of a PQFS active filter
The description of the main components is given in Table 5.
Table 5: Main components of a PQFS active filter
Item
Main components
1
IGBT inverter
2
DC bus capacitors
3
PWM reactor
4
Output filter
5
Preload resistor
6
Main contactor
7
Auxiliary fuses
8
Neutral cable connection (not mandatory)
Manual Power Quality Filter PQFS Hardware description 17
The current generator is physically organized in power units. Each filter enclosure
contains one power unit. A PQFS filter can contain up to 4 power units. Power units can
be combined in a master-slave arrangement or in a master-master arrangement, the
latter giving full operational redundancy. The current rating of different units in a filter
must be the same. Please refer to Chapter 12 for more information on the possible unit
ratings.
In Figure 10 it may be seen that each current generator consists of an IGBT-inverter
bridge (1) that is controlled using PWM-switching technology. Information from the filter
controller is sent to the IGBTs through one flat cable. At the output of the inverter a
voltage waveform is generated which contains the desired spectral components
(imposed by the filter controller) as well as high frequency noise (due to the IGBT
switching technology). Coupling impedance consisting of a reactor (3) and a high
frequency rejection filter (4) ensures that the useful voltage components are converted
into a useful current while the high frequency noise is absorbed. The IGBT-inverter is
equipped with DC capacitors that act as energy storage reservoirs (2).
In active filters containing more than one power unit the control information between
different units passes through a CAN control cable.
If a master-master configuration of filter is chosen, all power units incorporate a PQF-
Manager display. If a master-slave configuration of filter is chosen, only the master
enclosure contains a PQF-Manager display. All units contain a DC capacitors preloading
resistor (5) which charges the DC capacitors of the filter unit once the auxiliary fuse box
of the unit(s) is closed. This approach ensures a smooth filter start-up without excessive
inrush currents.
4.4 The PQF main controller
The PQF main controller controls the complete active filter system. Its tasks include:
−
Accepting and executing customer requests to stop and start the equipment.
−
Calculating and generating IGBT-inverter control references based on the line
current measurements and the user requirements.
−
Interface to the IGBT-inverters.
−
Measurement of system voltages and currents for control, protection and
presentation purposes.
Figure 11 depicts the controller interface diagram of the PQFS active filter.
18 Hardware description Manual Power Quality Filter PQFS
PQF
Manager
PQF
Power
Stage
CAN
Bus
Direct Interface
Modbus & PQ-Link interface
Programmable Digital I/O
3∼ AC Out
First
unit
Second
unit
User interface
CT signals(a)
PQF
main
controller
CAN bus (1)
PQF
Power
Stage
3∼ AC Out
PQF
main
controller
PQF
Manager
(b)
(a) CT signals to different units (master or slave) must be routed through daisy chain principle with
return path.
(b) If second unit is a slave unit, it will not have a PQF-Manager. If second unit is a master unit, it will
CT’s
Figure 11: Controller interface diagram of the PQFS active filter
When the filter consists of a master unit only, the customer has to:
−
Wire the CT signals (on a designated terminal),
−
Connect the AC power lines (with or without neutral),
−
Set up the installation parameters and user’s requirements with the PQF-
Manager.
He may also want to wire the communication interface (Modbus or Ethernet) and the
programmable digital I/O (e.g. alarm contact, remote control).
When a second unit is added, it is connected to the first enclosure by means of a CAN
bus communication link (1). In addition, the CT measurements have to be supplied to
each unit, i.e. through a daisy chain link with return path.
All units have their own AC-connection and main contactor protection.
A PQFS active filter system consists of up to 8 units of equal rating. Additional units to
the first master unit may be master or slave units. Slave units do not have a PQF-
Manager.
4.5 The PQF-Manager user interface
All user interaction with the filter is channeled through the PQF-Manager.
In multi-unit filters consisting of only one master, only the master has a PQF-Manager.
In multi-unit filters consisting of more than one master, all the master units have a PQF-
Manager. However, only the PQF-Manager that is connected to the master unit which
Manual Power Quality Filter PQFS Hardware description 19
has the overall control will be active. The PQF-Manager installed on the unit’s operating
as "slaves" are capable of displaying the relevant information about that specific unit
only. Certain parameters which are specific to that unit (e.g. related to temperature
probes) can be set or changed locally using the PQF-Manager installed on that unit. The
PQF-Manager on the master unit has a "unit selection"
button which allows the user
to select the unit number which he wants to consult. The data then displayed on the
master PQF-Manager is specific to that particular unit number. This unit selection
button is "deactivated" on the slave Managers. Figure 12 shows the front side of the PQF-
Manager.
Figure 12: Front side of the PQF-Manager
Five main parts can be distinguished (see Table 6)
Table 6: Front side of the PQF-Manager
Item
Description
1
Menu display
By navigating through the menus with the
,
,
and
buttons, the filter can be set-up and controlled. On-line help is available by pressing
the
button.
2
Master/slaves units monitor
3
Locking status / Alarm and fan contact indicator / Digital output contact indicator
When the PQF-Manager closes one of its output relays, the corresponding symbol
lights up. The digital outputs of the PQF-Manager are discussed later in this section.
4
Filter selection
5
Start stop acknowledgment fault
20 Hardware description Manual Power Quality Filter PQFS
The PQF-Manager also acts as connection point for external user I/O communication.
Connections are made at the rear side of the PQF-Manager. Figure 13 depicts the
terminals that are present on the PQF-Manager rear side.
1
2
3
4
5
6
7
8
9
10
Figure 13: PQF-Manager rear side terminal designation
The terminal designation is given in Table 7.
Table 7: Terminal designation
Item
Customer terminals
1
Digital input 1 and 2
2
Digital outputs 1 to 6 with one common point
3
Alarm outputs (2 outputs with complementary signals) and fan outputs
4
Lock switch
5
Modbus adapter interface (optional) connection
6
CAN bus connection interface (routed to PQF-Manager connector)
7
Power supply terminals (routed to PQF-Manager connector)
8
Ethernet
9
USB
10
Temperature probes
The terminal explanation is given next:
1 Digital input 1 and 2
The digital inputs can be used for three different functions:
−
Implementation of remote control functionality;
−
Implementation of local on/off buttons (not provided);
Manual Power Quality Filter PQFS Hardware description 21
−
Selection of main filter settings or auxiliary filter settings (e.g. different filter
settings for the day and for the night)
The PQF-Manager is used to associate the required functionality with the chosen digital
input. The digital inputs can also be disabled.
WARNING: If a function is assigned to a digital input, the same function must never be
assigned to the other digital input. Otherwise the filter may behave erratically.
The external voltage source needed to drive the digital inputs has to comply with the
following characteristics:
−
Vlow: 0 Vdc
−
Vhigh: 15-24 Vdc
−
Driving current: 13 mA @ 24 Vdc (Rint = 1.88 kΩ)
The digital inputs have free of potential contacts (opto-isolated).
When implementing any of the functions described above, please note that according to
the setup done with the PQF-Manager for the input considered, the filter may behave
differently. Table 8 below gives an overview of the possible settings and the resulting
filter behavior.
Table 8: Overview of possible digital input settings and resulting filter behavior
Function
Vlow applied
to digital
input
Vhigh applied to digital
input
Remote control
PQF-Manager setup for digital input: Remote
ON(a)
Filter off
Filter on
Selection of main/auxiliary settings
PQF-Manager setup for digital input: Activ.
Main(a)
Auxiliary
settings are
used
Main settings are used
Selection of main/auxiliary settings
PQF-Manager setup for digital input: Activ.
Aux.(a)
Main settings
are used
Auxiliary settings are used
Local ON/OFF buttons
PQF-Manager setup for digital input: Edge
ON(a) (b)
No effect
Filter starts on rising edge
Local ON/OFF buttons
PQF-Manager setup for digital input: Edge
OFF(a) (b)
No effect
Filter stops on rising edge
22 Hardware description Manual Power Quality Filter PQFS
Local ON/OFF buttons
PQF-Manager setup for digital input: Edg
ON/OFF(a) (c)
No effect
Filter starts on first rising
edge, stops on second
rising edge etc.
Remarks:
(a): In order for this function to be activated, the PQF-Manager has to be set up accordingly.
To do this, navigate to [/Welcome/Settings/Customer set./Digital Inputs]
(b): When using the Edge ON function the filter can only be switched on by applying voltage to the digital
input considered. It is therefore recommended in that case to configure and cable the second digital
input as Edge OFF.
(c): When using this function, the filter stop and start can be controlled by one digital input leaving the
other one available for an additional remote control or switching between main and auxiliary settings.
Information on cabling the digital input contacts is given in Section 6.12.
Information on setting up the digital inputs with the PQF-Manager is given in Section
7.9.1.4.
By default, the digital inputs are disabled.
In a master-master filter arrangement, only the master that has the control over the
complete system will monitor its digital outputs. For full redundant functionality, it is
recommended to cable the digital inputs of all the units in the filter system.
2 Digital Outputs 1 to 6
With each digital output different filter conditions can be associated. The association
between the filter condition and the digital outputs is done with the PQF-Manager. Table
9 gives an overview of the possible PQF-Manager settings for a digital output and the
effect on the corresponding digital output relay.
Table 9: Filter conditions that can be related to the digital outputs
PQF-Manager setting for digital
output(a)
Output relay closes when…
Auxil. ON
The auxiliary power is present in the main filter
enclosure and the main controller is communicating
with the PQF-Manager
PQF running
The active filter is ‘on’ (IGBTs switching) or in
‘standby’ (main contactor closed but IGBTs not
switching)
Full load
The active filter is running under full load condition
Armed
The filter is ON or is in the startup procedure, or it is
stopped in fault condition but will restart as soon as
the fault has disappeared
T limit
The filter temperature limit has been reached and
the filter is derating itself to run at a safe
temperature
In standby
The filter is in standby(b)
Activ. Main
The main active filter settings are activated
Manual Power Quality Filter PQFS Hardware description 23
Activ. Aux
The auxiliary active filter settings are activated
Unit miss.
One of the filter units in a multi-unit arrangement is
not available (e.g. due to a permanent error), or has
not yet been commissioned.
Pg. alarm 1
The programmable alarm 1 is activated(c)
Pg. alarm 2
The programmable alarm 2 is activated(c)
Pg. alarm 3
The programmable alarm 3 is activated(c)
Warning 1
The programmable warning 1 is activated(c)
Warning 2
The programmable warning 2 is activated(c)
Warning 3
The programmable warning 3 is activated(c)
Remarks:
(a): In order to set up this function, navigate to [/Welcome/Settings/Customer set./Digital Outputs]
(b): More information on the standby function is given in Section 7.9.3.1
(c): Different programmable warnings and alarms can be defined. More information on this subject is given
in Section 7.9.1.4.1
Further it should be noted that:
−
Whenever a digital output is activated the corresponding icon on the PQF-
Manager display will change.
−
In a master-master filter arrangement, only the master that has the control over
the complete system will activate its digital outputs. For full redundant
functionality, it is recommended to monitor the digital outputs of all the units in
the filter system.
−
The default set-up for the digital contacts is given in Table 10.
Table 10: Default set-up for the digital output contacts
Digital output number
Default function
1
Auxil. ON
2
PQF running
3
Full Load
4
Armed
5
Unit miss.
6
T Limit
−
The customer can change the default output settings by means of the PQF-
Manager.
−
The digital outputs contacts have a common point and are of the NO-type (normal
open). The contact ratings are:
•
Maximum continuous ac rating: 440 Vac/1.5 A;
•
Maximum continuous dc rating: 110 Vdc/0.3 A;
•
The common is rated at 9A/terminal, giving a total of 18 A.
24 Hardware description Manual Power Quality Filter PQFS
Information on cabling the digital output contacts is given in Section 6.12.
Information on setting up the digital outputs with the PQF-Manager is given in Section
7.9.1.4
3 Alarm outputs and fan outputs
Apart from the digital outputs, one potential free relay with a NO and a NC alarm output
is available. This relay contact is activated if any error condition is present during a
preset time. The relay contact is deactivated if the error condition has disappeared for
another preset time. Information on changing the alarm activation/deactivation time is
given in Section 7.9.1.4.1.
In a master-master filter arrangement, only the master that has the control over the
complete system will activate its alarm contact. For full redundant functionality, it is
recommended to monitor the alarm contacts of all the units in the filter system.
The maximum continuous alarm contact ratings are: 250 Vac/1.5 A.
A fan relay can be activated if a temperature probe detects an overtemperature.
4 Lock switch
Allows locking the settings of the filter panel. This switch is documented in Section
7.9.3.5.
5 Modbus RTU adapter interface (optional) connection
The Modbus adapter interface is connected at this location. The output of the interface
is an RS-485 socket. The interface is described in the Modbus RTU interface manual.
6 CAN bus connection interface
The PQF-Manager communicates with the main controller through a CAN bus. This bus
consists of three terminals, i.e.:
−
Pin H: CAN High signal
−
Pin L: CAN Low signal
−
Pin Shield: shielding
The CAN bus wiring terminates into the PQF-Manager connection plug and is
subsequently routed to the main control (Cf. Section 4.6.1). It is used for PQF internal
communications only.
7 Power supply terminals
The PQF-Manager power supply is provided by the filter itself. The corresponding
terminals on the PQF-Manager labeled “Power supply” are connected to the PQF-
Manager connection plug.
Manual Power Quality Filter PQFS Hardware description 25
8 The PQF-Manager communicates with Modbus TCP and PQ-link thanks to the
Ethernet connection. For background information on the Modbus RTU and TCP
communication interface refer to the dedicated Modbus manual. For background
information on the PQ-link communication interface refer to the dedicated PQ-link
manual.
9 The PQF-Manager can communicate with PQ-link (PC software) also through USB. .
For background information on the PQ-link communication interface refer to the
dedicated PQ-link manual.
10 External temperature probes can be added. The PQF-manager can handle until 8
temperature probes connected in a daisy chain way. Please refer to the Temperature
probe User’s guide for more information.
For information on how to cable external systems (e.g. remote control, Modbus
interface) to the PQF-Manager, refer to Chapter 6. For information on how to use the
PQF-Manager, refer to Chapter 7. For background information on the Modbus RTU and
TCP communication interface refer to the dedicated Modbus manual. For background
information on the PQ-link communication interface refer to the dedicated PQ-link
manual.
4.6 Location of the main PQFS components
4.6.1
Active filter components
Figure 14 shows a picture of the PQFS without cover panel.
2
3
4
5
6
7
8
1
11
13
14
10
9
15
12
16
Figure 14: PQFS main components
The component identification is given in Table 11.
Table 11: PQFS main components description
Item
Description
Circuit diagram designation
1
Main contactor (MC) (underneath controller boards)
K01
2
Fuse holder auxiliaries circuit
Q02
26 Hardware description Manual Power Quality Filter PQFS
3
DC voltage power supply 24V
U002
4
CT connection terminal
X21
5
Preload circuit resistors
R1, R2
6
Main earth connection point
-
7
IGBT inverter with DC capacitors
U01
8
PQF main controller board
A005
9
IGBT heat extraction fans
M1, M2
10
PCB EMC neutral
A003
11
PCB EMC line
A002
12
PCB output filter preload
A001
13
Main power supply terminals (phases) (underneath
controller boards)
L1, L2, L3
14
Main power supply neutral connection (not
mandatory) (underneath controller boards)
N
15
Auxiliary transformer
T001
16
Fuse preload circuit
PF1, PF2
The PQFS filters are provided with the preload circuit and the output filter mounted on
a PCB. This design substantially reduces the time needed for replacement of the same.
It also gives a more robust design compared to the previous generation of filters. The
power supply to the exhaust fan at the top of the filter are connected to the terminal
block shown which make the replacement of the same easy during periodic
maintenance.
The fuse on the PCB is of very special characteristics and must be replaced only with the
same type. Please refer to our recommended list of spare parts.
The preload circuit is shown in Figure 15.
2
3
4
1
5
6
Figure 15 Preload circuit main components
Manual Power Quality Filter PQFS Hardware description 27
The component identification is given in Table 12.
Table 12: Preload circuit main components description
Item
Description
Circuit diagram designation
1
Fuse preload circuit
PF1
2
Fuse preload circuit
PF2
3
Preload circuit resistors
R1
4
Preload circuit resistors
R2
5
Capacitors
6
Terminal block for top fans
P3
The PQF Main controller board has connectors which are predominantly pre-wired for
use within the filter. However, it also contains a DIP-switch used to set the identification
address and CAN bus connectors for use in a multi-module filter arrangements.
The main controller board is shown in Figure 16.
10
2
6
7
8
9
15
3
12
11
4
13
14
5
16
17
18
21
22
19
20
1
Figure 16: PQF main controller board
The designation of the principal terminals is given in Table 13.
28 Hardware description Manual Power Quality Filter PQFS
Table 13: PQF main controller board description
Item
Description
Circuit
diagram
designation
1
System connector: 24 V power supply to control board
P2
2
CAN bus connection from previous filter unit
P20
3
CAN bus connection to next filter unit
P21
4
System connector: Power supply and CAN communication to PQF Manager
P4
5
System connector: 230 V power supply to control board
P3
6
System connector
P19
7
System connector: Main contactor control
P18
8
System connector
P17
9
System connector
P16
10
System connector
P25
11
System connector
P7
12
System connector: Coming from CT terminal X21 (internal)
P5
13
System connector: Supply and DC link voltage measurement
P6
14-
15-16
System connectors
P9, P10, P11
17
System connector: control of IGBT-module
P12
18
Voltage selector DIP-switch
19
System LED’s (top to bottom with ABB Logo at top left side)
LED 3: ON: Critical error in filter unit considered (red LED)
LED 3: OFF: No critical error in filter unit considered
LED 2: ON: PQF unit running or in startup process (Armed)
LED 2: OFF: PQF unit off and not in startup process
LED 1: Blinking at regular interval (1 s): Microcontroller running properly
LED 1: ON, OFF or blinking irregularly: Microcontroller not running properly
20
System LED’s (top to bottom with ABB Logo at top left side)
LED 5: ON: Filter unit is acting as the master of the complete system
LED 5: OFF: Filter unit is acting as a slave in the filter system
LED 4: Blinking at regular interval (1 s): DSP processor running properly
LED 4: ON, OFF or blinking irregularly: DSP processor not running properly
21
PQ-Link communication opto-isolated serial link connector
22
Filter unit address selector (3 Left most DIP switches with ABB Logo at top
left side) and CAN bus termination (Right hand DIP switch):
Symbols used: L: low – H: high
Address 1: Position of the 3 switches starting from left: L L L
Address 2: Position of the 3 switches starting from left: H L L
Address 3: Position of the 3 switches starting from left: L H L
Address 4: Position of the 3 switches starting from left: H H L
Address 5: Position of the 3 switches starting from left: L L H
Address 6: Position of the 3 switches starting from left: H L H
Address 7: Position of the 3 switches starting from left: L H H
Address 8: Position of the 3 switches starting from left: H H H
Note: In a multi-master arrangement, the master which is operational and
which has the lowest address controls the system.
The default address setting is L L L
CAN bus termination (Right hand DIP switch):
Manual Power Quality Filter PQFS Hardware description 29
Must be High (H) for the units that are at the extremity of the CAN bus
(maximum 2 units in a multi-unit filters, typically the first one and the last
one of the chain). This setting is also applicable to single-unit filters.
Must be Low (L) for units in the middle of a chain.
The default factory setting is H.
Remark:
(a) For physical locations of customer CT connection terminals, please refer to Figure 14, item 4.
4.6.2
Active filter door components and protective grid
The active filter master panel door contains the PQF-Manager and a protective grid
connected to the filter frame. At the bottom of the protective grid a cooling fan is
mounted.
30 Mechanical design and installation Manual Power Quality Filter PQFS
—
5 Mechanical design and installation
5.1
What this chapter contains
This chapter gives the information required for the mechanical design and installation
of the filter system.
In case you have a problem, please notify it to our service support mail box:
[email protected].
5.2
Installation location requirements
The PQFS is suitable for indoor wall-mount installation, in a well-ventilated area without
dust and excessive aggressive gases where the ambient operating conditions do not
exceed the following values:
Table 14: Ambient operating conditions for PQFS operation
Altitude
Nominal output at 0 to 1000m (3300ft) above sea level (a)
Minimum temperature
-10°C (23°F), non-condensing
Maximum temperature
40°C (104°F) (b)
Maximum average
temperature (over 24 h)
35°C (95°F)
Relative humidity
Max. 95% non-condensing
Contamination levels
(IEC 60721-3-3)
Chemical class 3C2 (c)
Mechanical class 3S2 (d)
Remarks:
(a) At sites over 1000m (3300ft) above sea level, the maximum output current must be derated
by 1% every additional 100m (330ft). The derating factor must be entered at commissioning.
(b) Above 40°C (104°F), the maximum output current must be derated by 2% every additional
1°C (1.8°F) up to 50°C (122°F) maximum limit. The derating factor must be entered at
commissioning.
(c) Locations with normal levels of contaminants, experienced in urban areas with industrial
activities scattered over the whole area, or with heavy traffic.
(d) Locations without special precautions to minimize the presence of sand or dust, but not
situated in proximity to sand or dust sources.
The filter installation must be indoor and it should be taken into account that the
standard protection class is IP30.
WARNING: Conductive dust may cause damage to this equipment. Ensure that the
filter is installed in a room where no conductive dust is present.
Manual Power Quality Filter PQFS Mechanical design and installation 31
5.3
Airflow and cooling requirements
The PQFS dissipates an amount of heat that has to be evacuated out of the room where
the filter is located. Otherwise, excessive temperature rise may be experienced. Please
note that life of the electrical equipment decreases drastically if the operating
temperature exceeds the allowable limit (divided by 2 every 10°C/23°F).
Each PQFS power unit has its own cooling fans. The air intakes are located at the bottom
of the unit. From the bottom, the air flows through the enclosure and is then routed to
the top of the enclosure. For proper cooling, a minimum airflow of cooling air has to be
supplied to each unit. Table 15 gives the airflow requirements for different unit ratings.
Table 15: Airflow requirement
Unit rating
Airflow requirement (m³/h)
30A - 60A
520 m³/h
70A - 100A
520 m³/h
120A
710m³/h
Please ensure that the air used for cooling is regularly renewed and does not contain
conductive particles, significant amounts of dust, or corrosive or otherwise harmful
gases. The cooling air intake temperature must not exceed 40°C under any operating
condition. The hot exhaust air also has to be properly ducted away. Figure 17 shows the
cooling air flow diagram for a single unit PQFS.
Bottom view
Top view
Figure 17: Cooling air flow for a single unit PQFS
When the natural cooling capacity at the location where the filter is installed is not
sufficient, air conditioning systems have to be installed to the room. In the design of the
air conditioning systems, the filter heat losses have to be taken into account. Table 16
gives an overview of the PQFS heat losses for the different power units. For multi-unit
filters, the values of Table 16 have to be multiplied by the number of filter units.
32 Mechanical design and installation Manual Power Quality Filter PQFS
Table 16: Filter unit heat losses (maximum values)
Unit rating (Arms)
Heat loss (kW)
30
1.5
45
1.8
60
2.1
70
2.6
80
2.9
90
3.2
100
3.5
120
4.3
5.4 Standard cubicle dimensions, fixing holes and clearances
Standard PQFS enclosures have dimensions of 588 x 326 x 795 mm (width x depth x
height). Each enclosure contains one power unit and is fitted with its own main
contactor. Power cables with protecting fuses can be connected to each PQFS from the
bottom.
A spacing of 30 mm between the filter sides and walls or other enclosures is
recommended. However the filter can rest on its back against a wall.
A spacing of 500 mm below the filter bottom and above the filter top is recommended.
Figure 18 shows a view of a typical PQFS with characteristic dimensions.
Manual Power Quality Filter PQFS Mechanical design and installation 33
Figure 18: View of a typical PQFS with characteristic dimensions
If a filter system consists of more than one filter unit, the units should be installed next
to each other. If it is not otherwise possible, additional units can be mounted above the
existing unit(s). However, care has to be taken that the hot air of the bottom unit cannot
be sucked in by the fans of the unit mounted above. An example of such an arrangement
is given in Figure 19.
Figure 19: Example of an installation where PQFS units are mounted above each other
5.5 Instructions for mounting the filter
The wall on which the filter unit is mounted must be able to support the weight of the
filter, which is about 130 kilograms. Please note that one enclosure contains always one
unit.
In order to mount a filter unit on to the wall, follow the steps outlined below:
−
Unpack the filter as per Section 3.3
−
Set the 2 eyebolts on the top of the filter cubicle. They will be used to lift the filter
properly.
−
Pull out the 2 fixation plates (Figure 20)
Figure 20: Top view of the PQFS filter with the fixation plates
−
2 bolts M8 are needed to install the filter on the wall (Figure 21). Use a spirit level
to ensure horizontal fixation.
34 Mechanical design and installation Manual Power Quality Filter PQFS
Figure 21: Eyebolts and fixation of PQFS
−
Carefully lift the enclosure and slide it down over the 2 fixation bolts until it is
supported by the 2 fixation plates. Screw the 2 bolts to ensure a good fixation of
the filter. Then the lifting tool can be disengaged.
−
By means of a lower end fixation screw (not provided) the enclosure can be pushed
against the rear support at the bottom also (see Figure 22).
Figure 22: Lower end fixation
For additional units, the same procedure has to be followed.
5.6 Filter noise level
Active filters produce a certain level of noise when they operate. The noise level depends
on the operating conditions of the unit and on the rating of the filter. These values
should be taken into account when choosing a location for the filter.
Table 17: Noise level
Unit rating
Noise (dBA) at one meter
30A - 60A
65.3 typically
70A - 100A
68.4 typically
120A
70.9 typically
Manual Power Quality Filter PQFS Mechanical design and installation 35
5.7 Instructions for mounting the PQF-Manager in enclosures
The PQF-Manager user interface is mounted on to the front panel. In case it needs to be
relocated to another enclosure, follow the guidelines presented next (Figure 23)
Step 2
Step 1
(a)
(b)
Step 3
Step 4
(c)
(e)
Step 5
Repeat steps 3 to 5
for the bottom
Mounting Bracket.
(d)
Figure 23: Mechanical installation of the PQF-Manager
Step 1: Slide the PQF-Manager (a) perpendicularly to the Capacitor Bank Cubicle (b).
Step 2: Rotate the PQF-Manager to insert it into the Capacitor Bank Cubicle.
Note: cut out dimensions are 138 x 138 mm.
Step 3: Insert the Mounting Bracket (c) in the corresponding Fixation Holes (d) of the
PQF-Manager.
Step 4: Pull the Mounting Bracket backwards.
Step 5: Turn the Screw (e) into the Mounting Bracket and tighten until the PQF-Manager
is secured in place.
Once the PQF-Manager has been installed, it has to be connected electrically (Cf. Section
6.2).
36 Electrical design and installation Manual Power Quality Filter PQFS
—
6 Electrical design and installation
6.1
What this chapter contains
This chapter gives the data required for integrating the PQFS active filter successfully in
an electrical installation. It also gives electrical connection examples for popular filter
options.
WARNING: The PQFS is able to operate on networks in a voltage range 208-240 V and
380-415 V with a tolerance range of +/- 10 % (inclusive of harmonics but not
transients). Since operation at the upper limits of voltage and temperature may
reduce its life expectancy, the PQFS should not be connected to systems for which it
is known that over voltages will be sustained indefinitely. Excessive voltage levels may
lead to filter damage.
WARNING: The PQFS is not designed to be connected to systems where one phase
serves as neutral. Connection of a PQFS to such a system is only authorized after
explicit approval by ABB.
The active filter must be connected to the network in parallel with the loads.
WARNING: The PQFS does not incorporate protective power line fuses or main
contactor. Hence the customer has to ensure that the feeding cables to each filter
panel are adequately protected taking into account the filter rating and the cable
section used. More information on this topic is presented in Section 6.7.
Basic filter functionality can be obtained after connection of:
−
Ground (PE) (per cubicle).
−
Four power cables including neutral. The neutral connection is not mandatory for
filtering three phase loads. The power lines must be protected by appropriately
sized fuses or a contactor.
−
3 CTs (one per phase, to be connected to each filter unit in a filter system through
a daisy chain method with return path).
More advanced filter features (e.g. external monitoring of the filter status) require some
more connections. The connections for these advanced features have to be made on the
PQF-Manager.
WARNING: Ensure that the filter supply is isolated upstream during filter installation.
If the system has been connected to the supply before, wait for 25 mins after
Manual Power Quality Filter PQFS Electrical design and installation 37
disconnecting the mains power in order to discharge the capacitors. Always verify by
measurement that the capacitors have discharged. DC capacitors may be charged to
more than 800 Vdc.
The DC capacitors of PQFS units are automatically charged once the auxiliary circuit is
energized, regardless of whether the filter is switched off or not. Do not touch the DC
capacitor link when the auxiliary fuse box is closed.
The active filter control board carries dangerous voltages and shall not be touched once
the the auxiliary circuit is energized, regardless of whether the filter is switched off or
on. Once the auxiliary circuit is opened, high voltage levels can still be present on the
control board. Respect a delay of 25 minutes after disconnecting the mains power
before touching the control board.
6.2 Instructions for connecting the PQF-Manager to a filter system
PQFS filter master units are by default equipped with the PQF-Manager user interface.
In some cases however it may be needed to remove and reconnect the PQF-Manager to
the filter.
In order to successfully connect the PQF-Manager to a PQFS filter unit, it suffices to plug
the male connector attached to the PQF-Manager into the corresponding female
connector attached to the filter hardware. This is illustrated in Figure 24.
Figure 24: Connection of the PQF-Manager user interface to the PQFS filter hardware
The female connector associated with the filter hardware is situated at the top right side
of the control board and becomes visible after removing/lifting slightly the filter
protective cover.
Note that the connector incorporates the following signals:
−
The 230 V power supply connection
−
The internal CAN bus connection
6.3
Checking the insulation of the assembly - earth resistance
WARNING: Follow the procedure outlined below to check the insulation of the filter
assembly. Applying other methods may damage the filter.
38 Electrical design and installation Manual Power Quality Filter PQFS
Every filter has been tested for insulation between the main circuit and the
chassis/frame at the factory. Therefore, do not make any voltage tolerance or insulation
resistance tests (e.g. hi-pot or megger) on the inverter units. Check the insulation of the
assembly by measuring the insulation resistance of the filter between the Protective
Earth (PE) and all 3 phases shorted together, with main contactor shorted. The auxiliary
fuse box may remain closed, but it is mandatory to disconnect P2 (24V supply), P3
(230Vac in), P4 (PQF-Manager if master), P12 (IGBT) and P20-P21 (to other units) from
the main control board (see Table 13).
WARNING: Making the test without disconnecting the abovementioned connectors
may damage the filter.
Use a measuring voltage of 500 Vdc. The insulation resistance must be higher than
500 kΩ per enclosure.
6.4 EMC considerations
The CE version of active filter complies in its standard version with the following EMC
guidelines:
−
EN/IEC 61000-6-2: Immunity standard for industrial environments, Industrial
level.
−
EN/IEC 61000-6-4: Emission standard for industrial environments, Class A.
6.5 Earthing guidelines
Each PQFS plate has one marked earth points (PE). The earth point is situated at the
bottom right side of the filter plate (Figure 25).
Earth point (PE)
Figure 25: Identification of the earth point on the PQFS hardware
For safety reasons and for proper operation of the filter the earth point of each
enclosure must be connected to the installation’s earth (PE). A copper (Cu) cable of
minimum size 16 mm² is recommended but local regulations should also be taken into
account.
Remark: in PEN systems, the earth connection of the filter must be connected to the
installation’s earth (PE) and not to the N-conductor.
Further, the following rules should be respected:
−
When the PQFS consists of only one enclosure, the enclosure’s PE-point must be
connected directly to the installation’s PE-point.
Manual Power Quality Filter PQFS Electrical design and installation 39
−
When the PQFs consists of more than one enclosure, each enclosure’s PE-points
must be connected directly to the installation’s PE-point.
6.6 Selection of the power cable size
Several types of power cable can be used to connect the filter to the network. Local
regulations and habits often determine the user’s choice. Note however that due to the
high frequency output filter of the PQF, there is no radiated emission through the
feeding cables.
The following steps have to be followed to determine the section of the power cables
feeding the filter:
1. Determine the RMS current rating of the enclosure for which the cable has to be rated
(Irms). The rating is marked on the enclosure label.
Each enclosure has to be individually connected to the supply and bottom cable entry
has to be used. If required an optional cable connection box can be added to allow for
multi-cable termination.
The minimum cable section to be used for the power conductors is 16 mm².
The RMS current for which the cable has to be rated equals the current rating of the
unit to be connected to the supply. Note that the neutral connection has to be able to
carry three times the unit current rating.
2. Determine the factor X and the cable section required taking into account the skin
effect.
The multiplication factor X is a factor that takes into account that the current that will
flow through the filter connection cables is predominantly a harmonic current, i.e. a
current of which the frequency of the most important components is higher than the
network base frequency. Due to the frequency being higher than the network base
frequency a physical phenomenon called ‘skin effect’ comes into play. This effect
implies that for higher frequencies the current will not flow through the complete
cross section of the cable but will have the tendency to flow at the cable surface. The
result is that although one may use a cable of A mm², the section through which the
current flows is only X*A mm² (with X < 1). In order to compensate for this “loss of
section”, the cable has to be oversized such that the total equivalent section through
which the current flows taking into account the skin effect is acceptable.
The multiplication factor X to be used depends on the cable material (e.g. copper [Cu],
aluminum [Al]) and on the base frequency of the network on which the filter will be
installed. For a given installation its value can be determined using the following
process:
Step 1: Determine in a conventional way (e.g. using cable manufacturer’s tables) the
cable section A (mm²) for the RMS current Irms obtained in 1 above.
Step 2: Using the cable section A, the cable material and the network frequency as
entry points in Table 18, determine the multiplication factor X.
40 Electrical design and installation Manual Power Quality Filter PQFS
Table 18: Multiplication factors X for different cable sections
Cable section
[mm²]
Network frequency 50Hz
Network frequency 60 Hz
Al-cable
Cu-cable
Al-cable
Cu-cable
16
1.00
1.00
1.00
1.00
25
1.00
1.01
1.00
1.01
35
1.01
1.01
1.01
1.02
50
1.01
1.03
1.02
1.04
70
1.02
1.05
1.03
1.06
95
1.04
1.08
1.05
1.10
120
1.05
1.11
1.07
1.14
Step 3: Determine in a conventional way the cable section A2 (mm²) for the current
rating found by multiplying Irms by X.
If the new cable section A2 is equal to the initially found cable section A, the right cable
section taking into account the skin effect has been found.
If the new cable section A2 is bigger than the initially found cable section A, steps
2 and 3 have to be repeated with the new values until the cable section A2 found is
equal to the cable section A.
Remark: During this process it may be found that more than one cable per phase is
needed. The process then has to be applied to each cable.
As an illustration of the cable sizing process consider the following example:
PQFS 60 A/50Hz, 3-wire connection, cable material: Cu (copper)
Step 1: IN = 60A cable section = 16 [mm2]
Step 2: multiplication factor for a 16 [mm2] copper cable at 50 Hz = 1.00
Step 3: I = IN x 1.00 = 60A x 1.00 = 60 A
Step 4: I = 60A cable section: 16 [mm2]
This section is equal to the section found in the previous step.
Conclusion: one copper cable of 16 [mm2] per phase is sufficient.
Remark: The cable sizing process discussed in point 2 above only takes into account
the skin effect. Any further derating due to local standards and/or installation
conditions (e.g. distance between cables, number of cables connected in parallel …)
have to be taken into account by the company responsible for the PQF cable
connection.
As an example of the cable sizing procedure, consider Table 19 and Table 20, which
show the allowed current for different parameters noting typical cable manufacturer
data.
Manual Power Quality Filter PQFS Electrical design and installation 41
WARNING: Consult your cable manufacturer for the applicable cable manufacturer
data.
Table 19: Allowed cable current for different cable sections noting the skin effect and typical
cable manufacturer data – Network frequency 50Hz
Copper
Aluminum
Cross section
Nr of
parallel
cables
Derating
due to
paralleling
Rated
current
[Arms]
Reduction
factor
Allowed
current
[Arms]
Rated
current
[Arms]
Reduction
factor
Allowed
current
[Arms]
[mm²]
[AWG]
16
6
1
1
100
0.997
100
75
0.999
75
25
4
1
1
130
0.993
125
100
0.997
100
35
2
1
1
160
0.987
158
120
0.994
119
50
1-1/0
1
1
190
0.975
185
145
0.989
142
70
2/0
1
1
230
0.955
220
180
0.98
176
95
3/0
1
1
285
0.93
265
220
0.965
210
120
4/0
1
1
325
0.904
290
250
0.95
238
150
300MCM
1
1
365
0.877
320
285
0.93
265
185
350MCM
1
1
415
0.844
350
325
0.908
295
240
500MCM
1
1
495
0.804
390
385
0.876
335
300
600MCM
1
1
550
0.768
420
425
0.843
358
16
6
2
0.8
160
0.997
159
120
0.999
120
25
4
2
0.8
208
0.993
205
160
0.997
160
35
2
2
0.8
256
0.987
250
192
0.994
190
50
1-1/0
2
0.8
304
0.975
290
232
0.989
229
70
2/0
2
0.8
368
0.955
350
288
0.98
282
95
3/0
2
0.8
456
0.93
420
352
0.965
340
120
4/0
2
0.8
520
0.904
470
400
0.95
380
150
300MCM
2
0.8
584
0.877
510
456
0.93
424
185
350MCM
2
0.8
664
0.844
560
520
0.908
472
240
500MCM
2
0.8
792
0.804
630
616
0.876
540
300
600MCM
2
0.8
880
0.768
675
680
0.843
573
Remark: The highlighted values in Table 19 refer to cable sizes that correspond to typical
filter ratings. Note that in 4-wire systems, the neutral may have to carry up to 3 times
the line current rating of the filter.
42 Electrical design and installation Manual Power Quality Filter PQFS
Table 20: Allowed cable current for different cable sections noting the skin effect and typical
cable manufacturer data – Network frequency 60Hz
Copper
Aluminum
Cross section
Nr of
parallel
cables
Derating
due to
paralleling
Rated
current
[Arms]
Reduction
factor
Allowed
current
[Arms]
Rated
current
[Arms]
Reduction
factor
Allowed
current
[Arms]
[mm²]
[AWG]
16
6
1
1
100
0.996
99
75
1
75
25
4
1
1
130
0.99
128
100
1
100
35
2
1
1
160
0.981
157
120
0.99
119
50
1-1/0
1
1
190
0.965
183
145
0.98
143
70
2/0
1
1
230
0.941
216
180
0.97
175
95
3/0
1
1
285
0.911
260
220
0.95
210
120
4/0
1
1
325
0.88
286
250
0.93
233
150
300MCM
1
1
365
0.85
310
285
0.91
260
185
350MCM
1
1
415
0.817
339
325
0.89
288
240
500MCM
1
1
495
0.775
383
385
0.85
326
300
600MCM
1
1
550
0.738
406
425
0.81
346
16
6
2
0.8
160
0.996
159
120
1
120
25
4
2
0.8
208
0.99
205
160
1
160
35
2
2
0.8
256
0.981
250
192
0.99
190
50
1-1/0
2
0.8
304
0.965
293
232
0.98
228
70
2/0
2
0.8
368
0.941
346
288
0.97
280
95
3/0
2
0.8
456
0.911
415
352
0.95
336
120
4/0
2
0.8
520
0.88
457
400
0.93
374
150
300MCM
2
0.8
584
0.85
496
456
0.91
416
185
350MCM
2
0.8
664
0.817
542
520
0.89
460
240
500MCM
2
0.8
792
0.775
613
616
0.85
522
300
600MCM
2
0.8
880
0.738
649
680
0.81
553
Remark: The highlighted values in Table 20 refer to cable sizes that correspond to typical
filter ratings. Note that in 4-wire systems, the neutral may have to carry up to 3 times
the line current rating of the filter.
6.7
Selection of the power cable protection/filter input protection
scheme
Once the power cables have been selected, a suitable cable and equipment protection
has to be selected. The protection only needs to protect the phases and not the neutral.
It is recommended to use fuses of type gG/gL with the RMS current ratings given in
Table 21.
Manual Power Quality Filter PQFS Electrical design and installation 43
Table 21: RMS current ratings for protection fuses
Filter nominal current rating
(Arms)
Minimum fuse protection
(Arms)
Maximum fuse protection
(Arms)
30
40
125
45
63
125
60
80
125
70
100
160
80
100
160
90
125
160
100
125
160
Voltage rating of the fuses should be in accordance with the network voltage.
As an alternative to fuse protection, MCCB protection of appropriate sizing can also be
used. When the customer protection is in place, the following PQFS input protection will
result.
L1
L2
L3
To PQFS
power stage
To PQFS control circuit and
DC bus loading circuit
2.5mm² reinforced
6A (10X38 for up to
415V)
N
Customer added protection
PQFS filter unit
Note: neutral connection only needed for 4-wire connection
Figure 26: Symbolic representation of the PQFS input protection
The active filter power circuit is internally connected to the network by means of a main
contactor of type ABB UA50 or UA95 (depending on the current rating).
The PQFS control circuit and DC bus preload system is protected by a fuse protection
scheme, the characteristics of which are given in the table below.
44 Electrical design and installation Manual Power Quality Filter PQFS
Table 22: Control circuit fuse characteristics for PQFS filters
Nominal
network
voltage (Vrms)
Control circuit
fuse type
Irms fuse
(Arms)
Isc(a) fuse
(kA) at rated
voltage
Rated Voltage (Vrms)
208 ≤ Ue ≤ 415
French Ferrule 10
X 38 gG/gl
6
~ 120
500
Remark:
(a) fuse short circuit current capability
WARNING: Once the auxiliary fuse box is closed, the DC bus is automatically charged
when the upstream network is live. Therefore, close the auxiliary circuit only when the
upstream power circuit is not live. Failure to adhere to this guideline may result in
injury or death.
6.8 Connection of the PQFS to the network
WARNING: The PQF has to be installed in parallel with the loads, preferably on a free
feeder. Local regulations and requirements prevail in determining how the equipment
has to be connected to the network. The feeding cables to the filter must be protected
by their own cable and equipment protection device (see Section 6.7).
WARNING: The PQF can operate on networks with nominal voltage in the range 208-
240 V and 380-415 V. The unit must be configured for the operation range it will be
used on. Follow the guidelines in this section to ensure that the hardware is configured
properly. Failure to do so may lead to filter damage.
For applications where predominantly 3 phase loads are present and where there is no
need for neutral current filtering nor line to neutral balancing, connect the active filter
in 3-Wire mode.
For applications where predominantly single-phase loads are present and where there
is a need for neutral current filtering and/or line to neutral balancing, connect the
active filter in 4-Wire mode.
NOTE: When installing an active filter in installations containing power factor
correction capacitor banks, it is recommended to use detuned capacitor banks and to
connect the capacitor banks upstream of the filter measurement CTs.
Manual Power Quality Filter PQFS Electrical design and installation 45
NOTE: The PQF active filter is not compatible with high impedance devices installed
upstream of the filter in the neutral. The PQF may refuse to start or may not function
correctly when such a device is present. For best PQF performance, these devices have
to be removed or bypassed.
6.8.1
Connection of the PQFS in 3-wire mode
Use the 3-wire connection mode for installations where there is no need for neutral
current filtering or line to neutral balancing. In this mode, the active filter can
compensate 20 individual harmonic components.
In order to connect the PQFS in 3-wire mode, follow the below guidelines:
1. Fix the filter mechanically to the wall (Cf. Section 5.7)
2. Ensure that an appropriately selected protecting device is connected upstream and
that the power supply cables are not live
3. Remove the protective cover present at the bottom right side of the filter (Cf. Figure
27)
Figure 27: Removing the Aluminum protective cover at the bottom side of the active filter
enclosure
4. Make holes in the protective cover of appropriate section corresponding to the
power cable section used. Also make holes for the earth cable, the CT wire and any
other control wires that may be needed, e.g. for implementing remote control
functionality. When finished, slide the cover over the feeding cables and the earth
cable.
5. Connect the earth cable (Cf. Section 6.5)
6. Connect the three power cables to the reactor terminals (Cf. Figure 28).
WARNING: The power cables are directly connected by the customer at the line reactor
terminals. In order to safeguard the terminals from mechanical stress, it is
recommended that the weight of the power cable is properly supported using a cable
tray or a suitable cable connection box.
46 Electrical design and installation Manual Power Quality Filter PQFS
Figure 28: Connecting the three power cables to the filter reactor terminals
Remarks:
−
The left reactor terminal corresponds to phase L1 (R, A)
−
The middle reactor terminal corresponds to phase L2 (Y, B)
−
The right reactor terminal corresponds to phase L3 (B, C)
The cable lugs of the feeding cables should comply with:
−
Maximum lug width: in accordance with terminal width
−
Minimum lug eye diameter: M8
Appropriate torque (20Nm) must be applied to ensure that cables are properly fixed.
7. Slide the bottom protective cover up and fix it with the screws to seal off the power
supply terminals
8. In addition to the power cables and the earth connection cable, the CT connection
cable and any other control cables used for enhanced functions can at this stage be
passed through the protective cover into the filter panel.
9. Preparation of the filter to match the networks voltages:
The active filter nominal voltage setting must be adapted to the actual network
voltage by adjusting the tap setting of the auxiliary transformer. If the tap setting
for your network voltage is not available, then choose a tap just above the network
voltage present (e.g. for 390V network choose 400V tap setting). The auxiliary
transformer is situated at the bottom right side of the filter (Cf. Figure 14, item 15).
Ensure that the filter panel is isolated before changing the transformer tap setting.
By default the tap setting of the auxiliary transformer is set at the highest voltage
position at the filter production stage.
WARNING: The tap setting of the auxiliary transformer’s primary must be adapted
according to the network voltage to avoid a too high or too low auxiliary voltage.
If the tap setting for your network voltage is not available, then choose a tap just
above the network voltage present (e.g. for 390V network choose 400V tap
setting). Excessive (auxiliary) voltage levels will lead to filter damage.
Manual Power Quality Filter PQFS Electrical design and installation 47
6.8.2
Connection of the PQFS in 4-wire mode
Use the 4-wire connecting mode for installations where there is a need for neutral
current filtering and/or line to neutral balancing. In this mode, the active filter can
compensate 15 individual harmonic components.
In order to connect the PQFS in 4-wire mode, follow the guidelines of Section 6.8.1 with
the exception that:
4. Make also a hole for the neutral cable in the protective cover noting the larger section
required for the neutral.
6. Connect the three power cables and the neutral cable. Whereas the three power cables
can be connected as describes in item 6 of Section 6.8.1, the neutral cable has to be
connected to the neutral connection point (Cf. Figure 29).
Figure 29: Connection of the neutral cable when using the PQFS in 4-wire mode
The cable lugs for the neutral cables should comply with:
−
Maximum lug width: in accordance with terminal width
−
Minimum lug eye diameter: M8
Appropriate torque must be applied to ensure that cables are properly fixed.
Other points in the connection procedure are as per previous Section.
Remarks:
In case of regenerative loads (e.g. loads that may inject active energy to the
network, usually called 4Q-loads), it is very important to connect the PQF
outside the protection of this load. Indeed, consider Figure 30 where a common
protection is installed for both the regenerative load and for the PQF. When the
load re-injects energy to the network and the mains protection trips, the whole
energy may be pushed into the PQF, which may damage it severely. Figure 31
shows the admitted protection scheme for regenerative loads. In this case, if
the breaker of the load trips, the PQF is isolated from the energy fed back by the
drive.
48 Electrical design and installation Manual Power Quality Filter PQFS
PQF
4Q
load
Figure 30: Incorrect connection in the case of
4Q-loads
PQF
4Q
load
Figure 31: Correct connection in the case of
4Q-loads
6.9 Selection of the current transformers
Each filter unit in a filter system has to monitor the line current in order to determine
the harmonic load and function correctly. This is done by three current transformers
(CTs). For proper operation of the PQFS standard accuracy CTs with the following
minimum specifications have to be used:
−
5 A secondary current rating.
−
15 VA burden for up to 30 meters of 2.5 mm² cable. For longer cables lengths refer
to the chart in Figure 32. In case the CTs are shared with other loads, the VA
burden shall be adapted accordingly. Note that the burden requirement for a
complete filter system (consisting of up to 8 filter units) is 5 VA, excluding
connecting cables.
−
Class 1 accuracy or better.
−
Primary side current rating sufficient to monitor the total line current (including
transient phenomena such as drive/motor starts …).
It is strongly recommended that the three CTs have the same characteristics.
WARNING: The connection of different filter units in a PQFS system, as well as other
loads, on the same CT must be in series.
In order to determine the suitable CTs for your application, please refer to the chart in
Figure 32.
Remark: In some applications two or more power supplies exist (e.g. a network
transformer supply and a generator supply). When the current into both supplies has to
be filtered, summing CTs have to be used. All summing CTs must have the same ratio.
More information on how to install the summing CTs is given in next section.
Manual Power Quality Filter PQFS Electrical design and installation 49
Maximum rms current of the
downstream loads (including starting
current of DC drives):
X1 = ….. Arms
Multiply X1 by
1.6:
X2 = …. Arms
CT cables > 30 meters ?
Select 3 identical CT’s such that:
- rating at primary ≥ X2
- rating at secondary: 5A
- Burden ≥ 15 VA
- Class 1 accuracy or better
NO
Section of CT cables:
2.5 mm²? (recommended)
Determine the length of
CT cables (meters)
L = … m
X3 = (L x 0.007 x 25) + 10
X3 = … VA
Select 3 identical CT’s such that:
- rating at primary ≥ X2
- rating at secondary: 5A
- Burden ≥ X3 VA
- Class 1 accuracy or better
Determine the length (m) and
resistance (Ω/m)of
CT cables (meters)
L = … m
R = … Ω/m
X4 = (L x R x 25) + 10
X4 = … VA
Select 3 identical CT’s such that:
- rating at primary ≥ X2
- rating at secondary: 5A
- Burden ≥ X4 VA
- Class 1 accuracy or better
NO
YES
YES
Figure 32: Flow chart for CT determination
50 Electrical design and installation Manual Power Quality Filter PQFS
6.10 Current transformer installation
6.10.1 Basic rules for correct CT installation
The location of the CTs is critical to ensure the proper operation of the active filter. The
CTs are the “eyes” of the filter and it will react in accordance with the information
supplied by them.
WARNING: Special care has to be taken for the connection and location of the CTs:
wrong CT installation is the most common source of problems found at the
commissioning stage.
WARNING: In a filter system consisting of more than one unit, the CT information has
to be supplied to all the units. This must be done through a daisy chain connection
with return path configuration.
By default, the PQFS active filter is provided with CT terminals that are not shorted. A
set of shorting plugs is provided with the filter. They should always be kept with the filter
and be accessible for service engineers.
WARNING: When connecting the CTs of a live system to the PQFS, the secondaries of
the CTs have to be shorted. Failure to do so may result in CT explosion and consequent
damage to the installation. Once the connections to the filter have been made, the
shorting links must be removed.
The basic rules for successful CT installation are given next (Cf. Figure 33):
−
The three filter CTs have to be positioned for closed loop control, i.e. the CT must
monitor the load current and the filter current. In some cases, summation CTs
may be needed to fulfil the closed loop requirement (Cf. examples further down
this section).
−
The CTs must be positioned in the correct direction around the power cable: the
K (P1) side should be in the direction of the supply and the L (P2) side should be
in the direction of the load.
−
Each CT must have its own guard circuit, i.e. one terminal of each CTs secondary
terminals (k (S1) or l (S2)) should be earthed. Once a terminal is chosen (e.g. k-
terminal), the same terminal should be earthed for all the CTs.
−
The CT monitoring a phase should be connected to the filter terminal dedicated
to the same phase. In practice this means that:
•
The k (S1) terminal of the line 1 CT (L1, Red, U) must be connected to
terminal X21-1 of the filter.
Manual Power Quality Filter PQFS Electrical design and installation 51
•
The l (S2) terminal of the line 1 CT (L1, Red, U) must be connected to
terminal X21-2 of the filter.
•
The k (S1) terminal of the line 2 CT (L2, Yellow, V) must be connected to
terminal X214 of the filter.
•
The l (S2) terminal of the line 2 CT (L2, Yellow, V) must be connected to
terminal X21-5 of the filter.
•
The k (S1) terminal of the line 3 CT (L3, Blue, W) must be connected to
terminal X21-7 of the filter.
•
The l (S2) terminal of the line 3 CT (L3, Blue, W) must be connected to
terminal X21-8 of the filter.
−
The CT connection terminal X21 is located at the middle of the top plate of the
filter (Cf. Figure 34).
L1
L2
L3
Load side
Supply side
K
L
k l
K
L
k l
K
L
k l
PQF
X21.1
X21.2
X21.3
X21.4
X21.5
X21.6
X21.7
X21.8
X21.9
L1
L2
L3
To X21.1/X21.2
To X21.4/X21.5
To X21.7/X21.8
K = P1, L = P2, k = S1, l = S2
N
N
Figure 33: Basic CT connection example for a single unit active filter
CT connection terminal X21
Figure 34: Location of the CT connection terminal X21 in the PQFS
The terminal block X21 can handle control cable wiring with sections from 2.5 mm² to
10 mm².
In addition to the 6-wire CT cabling approach shown in Figure 33 above, a 4-wire
approach may also be used. This approach is illustrated in Figure 35. In this case the CT
secondary terminal to which the guard circuit is connected is interconnected between
the CTs and also on the filter terminal X21. One common cable is used for this terminal.
52 Electrical design and installation Manual Power Quality Filter PQFS
Note that this cable must be able to withstand three times the secondary current rating
of the CTs. Note that this cable must be able to withstand three times the secondary
current rating of the CTs.
L1
L2
L3
Load side
Supply side
K
L
K
L
K
L
PQF
L1
L2
L3
To X21.2
To X21.5
To X21.8
K = P1, L = P2, k = S1, l = S2
N
N
X21.1
X21.2
X21.3
X21.4
X21.5
X21.6
X21.7
X21.8
X21.9
Figure 35: Four wires CT wiring approach that may be used with a single unit
PQFS active filter
In case a filter system consists of more than one unit, all units have to be supplied with
the CT measurement information. This is done by cabling the CTs in a daisy chain fashion
between the different units. This is illustrated in Section 6.11.3.
6.11 Electrical interconnection of PQFS enclosures
This section explains how to electrically interconnect different PQFS enclosures.
Figure 36 shows schematically which interconnections have to be made between two
filter enclosures.
Manual Power Quality Filter PQFS Electrical design and installation 53
N
Preload
resistor
Output filter
Unit 1
Unit 2
Output filter
Power Unit 1
Master Unit
Power Unit 2
Master or Slave Unit
N
AC power supply
L
L
…
(2)
(1)
Figure 36: Overview of the connections to be made between two filter enclosures
The interconnection description is given in Table 23.
Table 23: Interconnections between two filter cubicles
Item
Description
1
Control board intercommunication cable through CAN bus (RJ45 cable)
2
CT interconnection cable
Four steps have to be followed to electrically interconnect a new PQFS unit with an
existing filter. They are outlined in the next four paragraphs.
6.11.1 Mechanical interconnection of the enclosures
All cables to the PQFS unit such as power cable as well as interconnection cable between
modules must pass through the bottom cable entry hole provided in the PQFS box.
6.11.2 Control board cable interconnection
WARNING: Failure to interconnect the control boards in an appropriate way will result
in filter malfunctioning and possibly sever damage of the unit.
Interconnect the control boards of a following unit with a previous filter unit by an RJ45-
based communication cable. This cable is provided with each unit.
54 Electrical design and installation Manual Power Quality Filter PQFS
Figure 37: shows the way to interconnect the control boards.
Control board in the ‘previous’ unit
Control board in the ‘next’ unit
From previous unit (if present)
To next unit
(if present)
Figure 37: Control board interconnection cable connection method.
−
The RJ45 control cable coming from the preceding filter unit is plugged in the left
hand side RJ45-socket at the top of the filter control board.
−
The RJ45 control cable leaving for the next filter unit is plugged in the right hand
side RJ45-socket at the top of the filter control board.
−
Repeat the same procedure for any other filters to be connected.
Notes:
−
In the first unit of a filter system, the left hand RJ45-socket will always be empty.
−
In the last unit of a filter system, the right hand RJ45-socket will always be empty.
−
During the commissioning phase, a unique address has to be assigned to each
unit in a filter system through dip switch (see Chapter 8).
6.11.3 CT cable interconnection
WARNING: Failure to connect the CT’s to all units in a filter system in an appropriate
way will result in filter malfunctioning and possibly sever damage of the unit.
In a multi-unit PQFS-system, all units have to be supplied with the CT-measurement
results. In order to do this the CT’s have to be cabled to each unit in a daisy chain fashion.
The connection principle is shown in Figure 38 for the CT of phase which is fed to four
filter units. The same approach has to be implemented for the other phases too.
Manual Power Quality Filter PQFS Electrical design and installation 55
Figure 38: Principle of the CT interconnection circuit for multi-unit filters.
Note that the overall burden requirement for a complete filter system is 5 VA. To this
value has to be added the burden requirement of the interconnection cables to obtain
the total burden requirement of the CT’s to be used.
6.11.4 Connection of the power stage to the supply
As a final step in the interconnection process, the power stage of the new unit has to be
connected to the supply. The same connection approach as used for the other filter units
must be adopted. More information on how to connect a PQFS filter unit to the power
supply can be found in Section 6.8.
WARNING: Make sure that the phase rotation of the power cable connection is
clockwise at the filter terminals and that the L1, L2 and L3 terminal in each filter unit
is connected to the same phase for all units. Failure to do so may lead to the filter
being damaged upon startup.
WARNING: Once a new filter unit has been added to a filter system, this unit has to be
given a unique address (through DIP switch setting on its control board). In addition,
the filter unit has to be recommissioned.
If more than one unit is added, it is recommended to first finish the hardware
modifications and then set up the controller accordingly. More information on how to
change the filter controller unit settings can be found in Section 7.9.2.2 and Section 8.5.
After making and verification of all the electrical connections:
−
Set a unique address on each filter unit control board
−
Close the auxiliary fuse box of the filter units
56 Electrical design and installation Manual Power Quality Filter PQFS
− Restore the top cover(s) of the filter units
6.12 Electrical connections to the PQF-Manager user interface
The PQF-Manager is the user interface between the outside world and the filter
controller. It is mounted on the filter cover panel. Depending on the user requirements,
less or more electrical connections have to be made to it. Figure 39 shows the rear side
layout of the PQF-Manager. In order to get access to the rear side of the PQF-Manager,
remove the PQFS top cover (Cf. guidelines in Section 3.3.)
Figure 39: Rear side layout of the PQF-Manager user interface
When looking at the PQF-Manager from the rear, on the left side can be found a 15-pole
terminal block and on the right side an 8 pole terminal block (top-right) and a 45-pole
terminal block (bottom right). Intermediate contacts are not used. In order to make
control connections to any of these terminals, the following procedure has to be applied:
1. Push the lever of the connector backwards with a screwdriver.
2. Insert the control wires (from 0.75 mm² to 2.5 mm² single core without cable shoe or
max. 1.5 mm² for multi-strand wire) in the corresponding connection hole while keeping
the pressure on the lever.
3. Release the screwdriver.
4. The wire is then properly connected.
Manual Power Quality Filter PQFS Electrical design and installation 57
Figure 40: PQF-Manager lead connections
The remainder of this section gives examples of how to cable different functions, i.e.
Case 1: Cabling of remote control functionality.
Case 2: Cabling of alarm functionality.
Case 3: Cabling of warning functionality.
Case 4: Cabling of the digital output contacts to monitor other filter operation modes
than warnings and alarms.
Case 5: Cabling of main/auxiliary control functionality.
Case 6: Implementation of local start/stop buttons.
It is recommended that for additional functions that are cabled to the PQFS, a connector
approach is used such as is the case for the internal communication and PQF-Manager
power supply.
WARNING: Before cabling any of the circuits discussed below, switch off the power
supply to the filter. When the filter has already been installed on site, this is done by
opening the protection system located just upstream of the filter and opening the
auxiliary fuse box present in the filter. Wait at least 25 minutes to allow for the DC
capacitors to discharge when the filter has been connected to the network before.
Failure to do so may result in the lethal injury or death.
After making and verification of all the electrical connections
−
Close the auxiliary fuse box of the filter units starting from the last slave and
ending with the master unit.
−
Restore the top cover(s) of the filter units including the connection of the PQF-
Manager to the master unit
−
The power to the filter may then be restored.
6.12.1 Cabling of remote control functionality
The PQFS has the possibility to be controlled by remote control. An example of this
approach is a drive that is switched on at a location and which automatically gives a start
command to the filter. When the drive is then stopped, the drive sends automatically a
58 Electrical design and installation Manual Power Quality Filter PQFS
stop command to the filter too. This section gives an example of how the cabling has to
be done on the filter side.
Any of the two digital inputs on the PQF-Manager (Cf. Figure 39) can be used to cable
the remote control functionality. The electrical requirements of the digital inputs are
given in Table 63 (Filter characteristics section). Figure 41 gives an example of how to
implement the remote control functionality on Digital Input 1.
Switch controlled
by external process
24 Vdc
external
power
supply(b)
S
+
-
1 (a)
2 (a)
+
-
PQF-Manager
Digital input 1
(15-24Vdc)
Remarks:
(a) Left hand terminal block when looking from rear, counting from top to bottom
(b) Acceptable power supply range: 15Vdc-24 Vdc, driving current 13mA@24Vdc
Figure 41: Implementation of remote control functionality on Digital Input 1 of
the PQF-Manager
WARNING: If a function is assigned to a digital input, the same function must never be
assigned to the other digital input. Otherwise the filter may behave erratically.
Once the cabling has been finished:
−
The auxiliary fuse box may be closed
−
The filter top cover may be replaced including the connection of the
PQF-Manager to the master unit
−
The power to the filter may then be restored
Then, the PQF-Manager has to be used to associate the remote control functionality with
Digital Input 1. This is done by going to the digital input setup menu and selecting
‘Remote ON’ for digital input 1. When this is done the filter will switch on when the switch
S shown in Figure 41 is closed and the filter will switch off when the switch S is opened.
Refer to Section 7.9.1.4 for guidelines on how to navigate to the digital input setup menu.
In a multi-master arrangement, the master that has the control over the system (i.e. the
master which is operational and which has the lowest address) will monitor the digital
inputs. Therefore, in order to obtain full redundancy with filters consisting of more than
Manual Power Quality Filter PQFS Electrical design and installation 59
one master unit, the digital inputs of all the units in a multi-master arrangement have to
be set up and cabled in the same way.
Remarks:
−
When the remote control functionality has been activated this function has
priority over a local start/stop command. When the local command has to be
given, deactivate first the remote control functionality by navigating with the
PQF-Manager to the digital input setup menu and setting the digital input
considered to ‘Disabled’.
−
The remote control functionality can also be implemented on the Digital Input 2.
6.12.2 Cabling of alarm functionality
An alarm represents an error condition that makes the filter trip. Two types of error
conditions exist:
−
External error condition: These are conditions that are imposed on to the filter
from the outside world. Consider the example of the network voltage that
increases well above the filter safe operation level for a certain time. In that case
the filter will disconnect from the network reporting a network overvoltage. When
the network voltage returns to a normal level however, the filter will reconnect to
the network and continue filtering providing that the same problem does not
occur systematically.
−
Internal error conditions: These are error conditions that are reported by internal
controls of the filter itself. They may indicate an internal filter problem.
Two ways to cable the alarm functionality exist:
6.12.2.1 Alarm outputs
The PQF-Manager alarm outputs located at the bottom right side (when looking at the
PQF-Manager from the rear) are triggered (return to default position) whenever:
−
A permanent internal or external error condition is present. In order to avoid
transient switching of the contacts, the error has to be present for 3 minutes
before the alarm relays are activated.
−
No power is supplied to the filter.
Table 26 further down this section gives an overview of all the error conditions that lead
to the alarm contact being triggered. Two alarm contacts exist, one being of type
‘normally open’ (NO) and the other of type ‘normally closed’ (NC).
The alarm contacts are:
−
Free of potential.
−
Rated for a maximum of 250 Vac/1.5 A or 30 Vdc/5 A. When using a
24 Vdc power supply, a minimum current of 25 mA should be drawn by the circuit
connected to the alarm contact.
60 Electrical design and installation Manual Power Quality Filter PQFS
Table 24 shows the status of the alarm contacts for different operation modes of the
filter.
Table 24: Status of the alarm contacts for different filter operation modes
Filter state
Normally open alarm
contact state
Normally closed alarm contact state
Disconnected from the
supply
Open
Closed
Filter (auxiliaries)
connected to the supply,
no error present
Closed
Open
Filter (auxiliaries)
connected to the supply,
error appears
Opens when error
present for 3 minutes
Otherwise, remains
closed
Closes when error present for 3
minutes
Otherwise, remains open
Filter (auxiliaries)
connected to the supply,
error disappears
When open before,
closes when error
disappears
When closed before,
remains closed
When closed before, opens when error
disappears
When open before, remains open
Figure 42 shows an example of an alarm contact cabling scheme using the NC alarm
contact. Using this scheme the bulb B will be on when the power supply to the filter is
interrupted or the filter trips due to an error. Otherwise the bulb will be off.
15
16 (a)
17 (a)
PQF-Manager
Alarm
outputs
NO
NC
230 Vac
external
power
supply
External bulb
alarm indicator
B
Remark:
(a) Right hand terminal block when looking from rear, counting from top to
Figure 42: Alarm bulb cabling scheme using the NC alarm contact on
the PQF-Manager
When the filter system consists of multiple master-units and an alarm contact is needed
to signal when the complete system is off, then the NC alarm contacts of all the master
units have to be cabled in series. An example is given in Figure 43 for 2 master filters.
Manual Power Quality Filter PQFS Electrical design and installation 61
B
Note: Contacts drawn in non-alarm position
230 Vac
external
power
supply
NC Alarm
contact of
master 1
NC Alarm
contact of
master 2
Alarm bulb
Figure 43: Cabling of the alarm status of a multi-unit filter consisting of masters only, using the
NC alarm contact on each filter.
In the Figure 43, the alarm bulb will be activated when both master units are in alarm.
Figure 44 shows a cabling scheme using a 24 Vdc supply in conjunction with the NO
alarm contact. The scheme assumes that an external digital input monitors the alarm
contact of the filter. In this case the voltage applied to the digital input will be low when:
−
The filter is disconnected from the supply OR.
−
The filter trips due to an error OR.
−
The external 24 Vdc power supply fails.
The voltage applied to the external digital input is high when:
−
The filter is connected to the supply and is not in error AND
−
The external 24 Vdc power supply is in working order.
15 (a)
16 (a)
17
Alarm
outputs
NO
NC
24 Vdc
external
supply
Remark:
(a) Right hand terminal block when looking from rear, counting from top to
External
digital
input
+
-
+
-
PQF-Manager
Figure 44: Alarm cabling example using NO alarm contact and external digital input
When the filter system consists of multiple master-units and an alarm contact is needed
to signal when the complete system is off, then the NO alarm contacts of all the master
units have to be cabled in parallel. An example is given in Figure 45 for 2 master filters.
62 Electrical design and installation Manual Power Quality Filter PQFS
Note: Contacts drawn in non-alarm position
24 Vdc
external
supply
NO Alarm
contact of
master 1
NO Alarm
contact of
master 2
External
digital
input
+
-
Figure 45: Cabling of the alarm status of a multi-unit filter consisting of masters only, using the
NO alarm contact on each filter.
In the Figure 45 above, the external input will be low if:
−
Both master units are in alarm OR
−
The external 24 V power supply fails OR
−
Both filter units are disconnected from the supply.
6.12.2.2 Digital outputs
A second method to implement the alarm functionality is to use the PQF-Manager’s
programmable digital output contacts. Use this approach when the condition for alarm
is uniquely defined, e.g. an alarm has to be given only when the filter trips due to an
unacceptably high network voltage or when the filter trips due to a well-defined internal
error. This type of alarm has to be cabled on the 8 pin terminal block situated at the top
right corner when looking at the PQF-Manager from the rear (Cf. Figure 39).
The digital output contacts have a common point (cabled on contacts 1 and 2) and are
of the NO-type (normally open). The contact ratings are:
−
Maximum continuous ac rating: 440 Vac/1.5 A.
−
Maximum continuous dc rating: 110 Vdc/0.3A.
−
The common is rated at 9 A/terminal, giving a total of 18 A.
−
When using a power supply of 24Vdc, a minimum current of 10 mA should be
drawn by the circuit connected to the digital output contact.
Table 25 shows the status of a digital output contact configured as alarm contact for
different operation modes of the filter.
Table 25: Status of a digital output contact configured as alarm contact for different
filter operation modes
Filter state
Normally open digital contact state
Disconnected from the supply
Open
Filter (auxiliaries) connected to
the supply, no error present
Open
Manual Power Quality Filter PQFS Electrical design and installation 63
Filter (auxiliaries) connected to
the supply, predefined error
appears
Closes when error present for 3 minutes.
Otherwise, contact remains open.
Filter (auxiliaries) connected to
the supply, predefined error
disappears
When closed before, opens when error disappears.
When opened before, remains open.
The alarm conditions that can be assigned to a digital output are given in Table 26. The
assignment must be made with the PQF-Manager. Any of the six digital outputs can be
used to cable an alarm. A maximum of 3 alarms can be assigned to the digital outputs.
Note however that by default the digital outputs have been set up for monitoring other
functions than alarms (cf. Table 10) Refer to Section 7.9.1.4 for guidelines on how to
navigate to the digital output setup menu.
Table 26: List of possible alarm conditions that may trigger the alarm/digital outputs
Alarm condition
Criteria to be fulfilled before contact is activated
Supply voltage (RMS) unacceptably
high
Vrms_max > 110% Vnominal
Supply voltage (RMS) unacceptably
low
Vrms_min < 90% Vnominal
One of the phases of the supply is
missing
Vrms_min < 60% Vnominal
Network imbalance unacceptably high
Vimbalance > 2%
Frequency variation unacceptably
high
Frequency variation > 20%/s
PQFS DC bus voltage unacceptably
high
Vdc > 105% Vdc_max_allowed
PQFS internal preload error
DC capacitor voltage rise too low in preload phase or
the DC capacitors could not be preloaded in an
acceptable time.
PQFS overcurrent fault
Internal current higher than allowed
PQFS ground fault
Internal ground current higher than allowed
PQFS IGBT fault
IGBT hardware reports internal permanent error
PQFS IGBT overtemperature
IGBT hardware reports internal overtemperature
Control board temperature too high
Internal control board temperature probe reports
too high temperature
PQFS internal power supply fault
Internal control voltage too low or not present
PQFS control board fault
Internal control board reports an error
PQFS unit down (i.e. not operational
due to error)
Any of the units in a multi-unit arrangement is not
running although the start-command has been given.
Remark: the alarm trigger levels cannot be changed by the user.
For cabling the digital output contacts as alarm contact, the same approach as shown
in Figure 44 can be adopted. Note however that the following behavior will result:
−
The voltage applied to the external monitoring device will be low when:
64 Electrical design and installation Manual Power Quality Filter PQFS
o The filter is disconnected from the supply or when there is no error.
−
The voltage applied to the external monitoring device will be high when:
o The predefined error is present for the predefined time (minimum 180s)
AND
o The external 24 Vdc power supply is in working order.
The different electrical characteristics of the digital output contacts compared to the
alarm contact characteristics must be respected. Note also that all digital outputs have
the same common which is located at the pins 1 and 2 of the right hand terminal of the
PQF-Manager (rear view, counting from top to bottom). This is clearly indicated in
Figure 39 above.
A second use of the digital outputs is to monitor the status of individual master units in
a multi-filter system. This can be done by assigning the function ‘Unit missing’ (‘Unit
miss.) to a digital output. In that case the digital output of the master controlling the
complete system will activate the digital output considered when one of the units in a
filter system is not operational due to error.
In order to obtain full redundancy with filters consisting of more than one master unit,
the digital outputs of all the units in a multi-master arrangement have to set up and
cabled in the same way. The cabling scheme is given in Figure 45.
Once the cabling has been finished:
−
The auxiliary fuse box may be closed
−
The filter top cover may be replaced including the connection of the PQF-Manager
to the master unit
−
The power to the filter may then be restored
6.12.3 Cabling of warning functionality
A warning condition is a condition that can be set up by the user in such a way that if the
condition is met, a digital output contact of the PQF-Manager user interface (Cf. Figure
39) is closed. As an example consider a case where the user has set up an upper warning
level for the network voltage. If the level measured by the filter becomes higher than the
predefined warning level and this condition remains valid for a preset time, the
associated digital output will be closed. By monitoring the digital output, the customer
will then know when the network voltage becomes too high and subsequently he can
take appropriate action.
Note that the warning functionality is not associated with a filter trip. It only has a
monitoring function. Table 27 describes the behavior of the digital output contact
configured as warning contact for different filter operating modes.
Table 27: State of a digital output contact configured as warning contact for different filter
operation modes
Filter state
Normally open digital contact state
Disconnected from the supply
Open
Manual Power Quality Filter PQFS Electrical design and installation 65
Filter (auxiliaries) connected to the
supply, no warning present
Open
Filter (auxiliaries) connected to the
supply, predefined warning present
Closes when warning present for pre-defined time.
Otherwise, contact remains open.
Filter (auxiliaries) connected to the
supply, predefined warning disappears
When closed before and warning disappears for at
least the predefined time, contact opens.
When closed before and warning disappears for a
time smaller than predefined time, contact
remains closed.
Otherwise, contact remains open.
Table 28 gives a list of the warning conditions that can be assigned to a digital output.
Table 28: List of possible warning conditions that can be assigned to a digital output
Warning condition
Supply voltage (RMS) higher than preset value.
Supply voltage (RMS) lower than preset value.
Supply voltage imbalance higher than preset value.
Ground current level higher than preset value.
IGBT Temperature higher than preset value.
Control board temperature higher than preset value.
Remark: All warning levels can be changed by the user.
Any of the six digital outputs can be used to cable warning functionality. A maximum of
3 warnings can be assigned to the digital outputs. However, by default the digital
outputs of the PQF-Manager have been set up for monitoring other functions than
warnings (cf. Table 10). Refer to Section 7.9.1.4 for guidelines on how to set up warning
conditions and how to associate them with digital output contacts.
For cabling the digital output contacts as warning contact, the same approach as shown
in Figure 44 can be adopted. The electrical characteristics of the digital output contacts
and the points to pay attention to are discussed in Section 6.12.2.
In order to obtain full redundancy with filters consisting of more than one master unit,
the digital outputs of all the units in a multi-master arrangement have to be set up and
cabled in the same way. The wiring diagram given in Figure 45 can be used to implement
the monitoring of the warnings in multi-master units.
6.12.4 Cabling of the digital output contacts to monitor other filter operation
modes than warnings and alarms
Table 9 gives an overview of the other functions that can be monitored with the digital
outputs in addition to the already discussed warnings and alarms.
66 Electrical design and installation Manual Power Quality Filter PQFS
For cabling the digital output contacts to monitor other filter operation, the same
approach as shown in Figure 44 can be adopted. The electrical characteristics of the
digital output contacts and the points to pay attention to are discussed in Section 6.12.2.
In order to obtain full redundancy with filters consisting of more than one master unit,
the digital outputs of all the units in a multi-master arrangement have to be set up and
cabled in the same way. The wiring diagram given in Figure 45 can be used to implement
the monitoring of these functions in multi-master units.
6.12.5 Cabling of main/auxiliary control functionality
The active filter features main and auxiliary control setup modes. This implies that two
different compensation characteristics can be defined, e.g. one for the day and one for
the night or one for normal network operation and one for backup generator operation.
With the PQF-Manager a set up can be made to either use always the main or the auxiliary
settings. In addition, the possibility exists to switch between main and auxiliary settings
‘automatically’ according to a signal applied to a digital input of the PQF-Manager (Cf.
Figure 39). Any digital input can be configured to act as the deciding factor for switching
between the main and auxiliary settings. Moreover, both normal and inverse logic can be
used to drive the digital inputs.
Note that in a multi-unit filter system in which more than one master system is present,
the digital inputs of all masters have to be set up and cabled in the same way to obtain
full redundancy.
The electrical requirements of the digital inputs are as discussed in Chapter 12.
Figure 46 gives an example of how to implement the main/auxiliary control switching
functionality on Digital Input 2. It is assumed that normal control logic is used.
External switch for
switching between main
and auxiliary filter settings
24 Vdc
external
supply
+
-
3 (a)
4 (a)
PQF-Manager
Digital input 2
(15-24Vdc)
Remark:
(a) Left hand terminal block when looking from rear, counting from top to bottom
Figure 46: Example of how to cable the 2nd digital input of the PQF-Manager for main/auxiliary
control switching functionality
When implementing the function described above, please note that according to the
setup done with the PQF-Manager for the input considered, the filter may behave
differently. Table 29 shows the filter behavior as a function of the PQF-Manager settings.
Manual Power Quality Filter PQFS Electrical design and installation 67
WARNING: If a function is assigned to a digital input, the same function must never be
assigned to the other digital input. Otherwise the filter may behave erratically.
Table 29: Filter behavior as a function of the PQF-Manager settings for
main/auxiliary switching
PQF-Manager setup for
digital input
Vlow applied to digital
input
Vhigh applied to digital input
Activ. Main
Auxiliary settings are
used
Main settings are used
Activ. Aux.
Main settings are used
Auxiliary settings are used
Remark: Vlow = 0 Vdc, Vhigh = 15-24 Vdc
In order to obtain full redundancy with filters consisting of more than one master unit,
the digital inputs of all the units in a multi-master arrangement have to be set up and
cabled in the same way and the individual PQF-Managers have to be set up accordingly.
Once the cabling has been finished:
−
The auxiliary fuse box may be closed
−
The filter top cover may be replaced including the connection of the PQF-Manager
to the master unit
−
The power to the filter may be restored
Refer to Section 7.9.1.4 for guidelines on how to set up the digital inputs according to
the function required.
6.12.6 Implementation of local start/stop buttons
WARNING: If a function is assigned to a digital input, the same function must never be
assigned to the other digital input. Otherwise the filter may behave erratically.
The PQFS active filter is equipped with a start/stop function integrated in the PQF-
Manager user interface. If the customer desires this however, he can add extra
start/stop buttons (not provided) to the filter system. The start and stop button has to
be connected to the PQF-Manager’s digital inputs and the PQF-Manager has to be set
up accordingly.
68 Electrical design and installation Manual Power Quality Filter PQFS
Note that in a multi-unit filter system in which more than one master system is present,
the digital inputs of all masters have to be set up and cabled in the same way to obtain
full redundancy.
Two connection approaches exist:
−
The first approach is to use one digital input for the start function and the second
digital input for the stop function. Table 30 shows the PQF-Manager setup for the
input considered and the resulting effect when applying voltage to this input.
Table 30: Filter behavior as a function of the PQF-Manager settings for local start/stop and
using 2 digital inputs
PQF-Manager setup for
digital input
Vlow applied to digital
input
Vhigh applied to digital input
Edge ON
No effect
Filter starts on rising edge
Edge OFF
No effect
Filter stops on rising edge
Remark: Vlow = 0 Vdc, Vhigh = 15-24 Vdc
When using the Edge ON function the filter can only be switched on by applying
voltage to the digital input considered. It is therefore recommended in that case
to configure and cable the second digital input as Edge OFF. Refer to Section
7.9.1.4 for guidelines on how to set up the digital inputs according to the
function required.
The electrical requirements of the digital inputs are as discussed in Section 4.5.
Figure 47 shows a cabling diagram for implementing a start function on the first
digital input and a stop function on the second digital input.
External
stop
push
24 Vdc
external
supply
+
-
1 (a)
2 (a)
3 (a)
4 (a)
PQF-Manager
Digital input 1 (15-24Vdc)
Digital input 2 (15-24Vdc)
Remark:
(a) Left hand terminal block when looking from rear, counting from top to bottom
External
start
push
Figure 47: Cabling diagram for implementing start on digital input 1 and stop
on digital input 2
Manual Power Quality Filter PQFS Electrical design and installation 69
−
The second approach is to use one digital input for both the start function and
the stop function. This leaves the other digital input available for the
implementation of other functions.
Table 31 shows the PQF-Manager setup for the input considered and the resulting
effect when applying voltage to this input.
Table 31: Filter behavior as a function of the PQF-Manager settings for local start/stop and
using 1 digital input
PQF-Manager setup for
digital input
Vlow applied to digital
input
Vhigh applied to digital input
Edge ON/OFF
No effect
Filter starts on first rising edge, stops
on second rising edge, etc
Remark: Vlow = 0 Vdc, Vhigh = 15-24 Vdc
Refer to Section 7.9.1.4 for guidelines on how to set up the digital inputs
according to the function required.
The electrical requirements of the digital inputs are as discussed in Section 4.5.
Figure 48 shows a cabling diagram for implementing a start function and a stop
function on the first digital input.
External start/stop
push button
24 Vdc
external
supply
+
-
PQF-Manager
Digital input 1
(15-24Vdc)
Remark:
(a) Left hand terminal block when looking from rear, counting from top to bottom
1 (a)
2 (a)
3 (a)
4 (a)
Figure 48: Cabling diagram for implementing start and stop on digital input 1
Once the cabling has been finished:
−
The auxiliary fuse box may be closed
−
The filter top cover may be replaced including the connection of the PQF-Manager
to the master unit
−
The power to the filter may be restored
Remarks:
70 Electrical design and installation Manual Power Quality Filter PQFS
−
The implementation of local start/stop buttons does not inhibit the usage of the
start/stop function on the PQF-Manager.
−
When remote control functionality is implemented (cf. Section 6.12.1) at the same
time as local start/stop buttons, the remote control has priority over the local
start/stop buttons. When the local start/stop command has to be given,
deactivate first the remote control functionality by navigating with the
PQF-Manager to the digital input setup menu and setting the digital input
associated with the remote control to ‘Disabled’.
−
Note that in a multi-unit filter system in which more than one master system is
present, the digital inputs of all masters have to be set up and cabled in the same
way to obtain full redundancy.
6.13 Electrical connections of filter options and accessories
Filter options must be ordered in advance and are cabled in the factory. For these
options, refer to the wiring diagram provided with your filter to identify the electrical
connections if desired. For some accessories however, the customer may have to do the
cabling on site. These accessories include:
−
The connection of the USB or Ethernet cable used for PQ-Link software
communication (optional)
−
The connection of the Ethernet cable used for Modbus TCP communication
(optional)
−
The connection of the RS485 Modbus RTU adapter (optional)
The connections of the aforementioned accessories are discussed next.
WARNING: Before cabling any of the circuits discussed below, switch off the power
supply to the filter. When the filter has already been installed on site, this is preferably
done by opening the protection system located just upstream of the filter and opening
the auxiliary fuse box present in the filter. Wait at least 25 minutes to allow for the DC
capacitors to discharge when the filter has been connected to the network before.
Failure to do so may result in the lethal injury or death.
6.13.1 External communication with PQF
The PQF Filter communicates with a computer in three possible ways:
−
Using our in-house communication software called PQ-Link (TCP/IP-USB)
−
Using any communication system supporting the Modbus TCP protocol
−
Using any communication system supporting the Modbus RTU protocol
Manual Power Quality Filter PQFS Electrical design and installation 71
While using the PQ-Link software, the computer can be connected either through the
Ethernet port using standard cable (RJ45) or through the USB port using standard USB
cable.
Figure 49: Ethernet cable & USB cable for PC-filter interconnection
For communication over Modbus TCP, the computer can be connected through the
Ethernet port using standard cable (RJ45).
For communication over Modbus RTU, we need a RS485 Modbus adapter (as shown in
Figure 50). This adapter has to be connected to the rear side of the PQF-Manager. This
is done by inserting the adapter plug firmly in the dedicated socket. Figure 50 shows the
location at the rear of the PQF-Manager where the plug has to be inserted. The user can
use custom software where the standard Modbus RTU protocol is implemented or any
other standard software (OPC server, SCADA …).
Figure 50: Location at rear of PQF-Manager where the serial communication
cable has to be inserted
More information on the PQ-Link software or Modbus communication can be found in
the ‘PQ-Link installation and user’s guide’ and 2GCS214017A0070_PQF-Manager
communication with Modbus RTU, Modbus TCP and PQ-Link protocols.
6.13.2 Connection of the Modbus adapter
For the connection setup of the Modbus adapter, please refer to the document
“2GCS212013A0050-RS-485 Installation and Start-up guide”.
72 The PQF-Manager user interface Manual Power Quality Filter PQFS
—
7 The PQF-Manager user interface
7.1
What this chapter contains
This chapter presents the features and operating instructions for the PQF-Manager user
interface (Figure 51). Use the contents of this chapter as background information for the
next chapters, which explain how to commission, operate and troubleshoot the active
filter and how to set up various communication interfaces based on RS485 or Ethernet.
Some of the functions discussed in this chapter require cabling of external I/O to the
connection terminals at the rear of the PQF-Manager. Refer to Section 6.12 for guidelines
on how to do this.
Figure 51: Front view of the PQF-Manager user interface
7.2
PQF-Manager user interface description
The PQF-Manager is based on a touch screen user interface hence there are no hardware
buttons used. All user actions like moving from one to another menu or data entry are
done directly by touching the soft buttons or icons on the “touch sensitive” screen. The
screen is made of high quality scratch resistance glass. The screen is “resistive touch
screen” and hence the user may use any object such as finger or any blunt object like a
pen, screw driver etc. Care must be taken not to damage the screen by accidental hard
tapping by a sharp object.
The main screen of the PQF-Manager is given in Figure 52.
Manual Power Quality Filter PQFS The PQF-Manager user interface 73
Figure 52 Main screen of the PQF-Manager
7.3
PQF-Manager overview and navigation
All user inter-action with the filter is channeled through the PQF-Manager. It provides for
the following main functions (Cf. Figure 51):
−
Filter starting, filter stopping and acknowledgement of faults
−
Selection of power module for which the relevant data is displayed
−
Measuring, analyzing, logging
−
Setting up the filter
−
Monitoring the filter load, event logging and status of individual units
−
Providing filter identification information
Figure 53 outlines the principle menus that are accessible through the ‘Welcome’ screen.
In a multi master configuration (several master units in parallel in a single filter), the
PQF-Manager on the “Master” unit has all the menus and options active. The PQF-
Manager(s) on the “Slave” unit(s) have different screens in the sense that certain items
(menu, buttons etc.) are “non-active” and may appear “greyed”. In case the maser unit
fails and the next unit in the order takes over as new master (due to redundancy
feature of PQF), the menu of the new master automatically adapts to this new
situation.
7.4
Icons and main screen
Following icons and menu are present on the main screen:
Table 32 Filter status icons
Filter status
Menu display
Touching the button results in …
Filter stopped, no critical error
present (i.e. ‘normal’ stop
condition)
PQF START
Starting the filter unit
Filter running, no critical error
present (i.e. ‘normal’ running
condition)
PQF STOP
Stopping the filter unit
Filter stopped on critical fault
ACK. FAULT
Acknowledging the fault
74 The PQF-Manager user interface Manual Power Quality Filter PQFS
The module status indicator: there are 8 numbered icons present on the left bottom of
the screen, each representing a power module. The active modules are displayed in blue
color; the faulty ones in red and those modules which are not present are greyed.
Table 33 Module status icons
Icons
Status
Ready: the unit considered does not have a fault and can run normally
Fault: the unit considered has been stopped due to an error. By pressing Ack.
Fault, the reason for the fault will be displayed and an attempt will be made
to clear the fault. When doing this, the complete filter system will be shut
down. If the fault could be cleared, the unit status will become ‘ready’. If the
fault could not be cleared, the unit status will remain ‘Ack. Fault’. In the fault
clearing process, the complete filter system will be shut down. The filter can
be restarted after the fault clearing process has ended.
Not present: the unit considered has been excluded of the normal filter
operation due to either fault or the unit is not present
Master
An alarm icon showing when the PQF-Manager’s alarm contact has been activated (Cf.
Figure 51) changes its appearance when the alarm condition exists. When the alarm
condition has disappeared, the respective alarm icon takes back the normal appearance.
The status of protection (locked/unlocked) is also displayed by a dedicated icon.
Hardware lock and software locks have separate icons.
Table 34 Alarm/lock status icons
Icons
Status
Software lock
Software unlock
Hardware lock
Hardware unlock
Communication lock status
Communication unlock status
Alarm status
Fan status
Alarms
Manual Power Quality Filter PQFS The PQF-Manager user interface 75
Programmed alarm can:
−
activate any digital output relay 1-6 if selected
−
activate global alarm NO/NC relay
Tprobe alarm 1 to 8 can activate global alarm NO/NC relay.
Warnings
Programmed warning can activate any digital output relay 1-6 if selected.
Tprobe warning 1 to 8 can activate global fan NO relay.
Digital output contact icons are located at the bottom of the screen (Cf. Figure 52).These
icons are numbered 1 to 6 when they are disabled. If these output contacts are
programmed, the corresponding icon changes. When the PQF-Manager closes one of its
six digital output relays (Cf. Chapter 6) the corresponding symbol changes its
appearance as described in the Table 35. When the relay considered opens again, the
symbol takes back the original appearance.
If a digital output is ‘Disabled’ the default icon is shown.
Example:
Table 35 Digital outputs status icons
Icons
PQF-Manager
setting for digital
output
Output relay closes when…
Auxil. ON
Auxil. OFF
The auxiliary power is present in the main filter enclosure
and the main controller is communicating with the PQF-
Manager
PQF running
PQF not running
The active filter is ‘on’ (IGBTs switching) or in ‘standby’
(main contactor closed but IGBTs not switching)
Not full load
Full load
The active filter is running under full load condition
Armed
The filter is ON or is in the start-up procedure, or it is
stopped in fault condition but will restart as soon as the
fault has disappeared
76 The PQF-Manager user interface Manual Power Quality Filter PQFS
Not armed
Within T limit
T limit reached
The filter temperature limit has been reached and the filter
is derating itself to run at a safe temperature
In standby
The filter is in standby
Activ. Main
The main active filter settings are activated
Activ. Aux
The auxiliary active filter settings are activated
Unit miss.
One of the filter units in a multi-unit arrangement is not
available (e.g. due to a permanent error), or has not yet
been commissioned.
Pg. alarm 1
The programmable alarm 1 is activated
Pg. alarm 2
The programmable alarm 2 is activated
Pg. alarm 3
The programmable alarm 3 is activated
Warning 1
The programmable warning 1 is activated(c)
Warning 2
The programmable warning 2 is activated(c)
Warning 3
The programmable warning 3 is activated(c)
Following are the default functions set for the six digital output contacts:
Table 36 Main screen
Digital output number
Default function
1
Auxil. ON
2
PQF Running
3
Full Load
4
Armed
5
Unit miss.
6
T Limit
Manual Power Quality Filter PQFS The PQF-Manager user interface 77
Measurements
Overview
Vrms
THDV
V1
Frequency
Vdc
Irms
THDI
I1
PQF Irms
P
Q
S
PF
Cos ϕ
T Control
T Control max
T IGBT
T IGBT Max
System values
Voltages
Global Values
Waveforms
Spectrum
Harm. Table
Line currents
Global Values
Waveforms
Spectrum
Harm. Table
Filter currents
Waveforms
Spectrum
Harm. Table
Total filter curr.
Waveforms
Spectrum
Harm. Table
Powers
P
Q
S
PF
Cos ϕ
Temperatures
T Control
T Control Max
T IGBT
T IGBT Max
T PQF Manager
T Probe (1…8)
Min-Max logging
Voltages
Line currents
Power
Frequency
Temperatures
Settings
Customer set.
Main settings
Main Harmonics
Main PFC/Bal.
Deselect all
Filtering Mode
Aux settings
Aux Harmonics
Aux PFC/Bal.
Deselect all
Filtering Mode
Temp unit (C/F)
Activate (M/A)
Alarms
Prog. alarms
Temp. alarm levels
Warnings
Prog. warnings
Warnings levels
Digital inputs
Digital outputs
Commissioning
Network charact.
Vnom
fnom
Synchro mode
Filter Charac.
Unit current
3W or 4W
Auto CT detection
Manual CT settings
Derating
User
Main harmonics
Main PFC/Bal.
Filter mode
T Commissioning
Installation set.
Network charact.
Filter charact.
CT Installation
Derating
Start-Stop set.
Clock
Password
Installation lock
Set language
PQF monitoring
Status of module
Filter load
Event logging
Active warn.
Number of errors
PQF operation
User interface
Manufacturer set.
About PQF
Screen config.
Touchscreen calibration
Backlighting
Communication
Modbus
Ethernet settings
MAC address
IP address
Communication locking
PQF
Start
Stop
Ack fault
Welcome
Figure 53: Principle menus of the PQF-Manager
78 The PQF-Manager user interface Manual Power Quality Filter PQFS
In order to navigate through the menus of the PQF-Manager, the touch screen (Cf. Figure
51) has to be used. The starting point for the navigation after a power up is the ‘Welcome’
screen. The item selected is activated and its submenu appears on the screen (e.g. the
‘Measurements’ menu in Figure 51). The name of the parent menu is displayed at the top
of the screen.
Figure 54: Sub-menu Measurements
Please note that:
−
Sometimes the complete item list in a menu cannot be shown on the display. This
is indicated by a small
symbol that appear(s) at the bottom right (Cf. Figure
55). Pressing this button takes the menu to the next screen where more items are
available to choose from.
Figure 55: Illustration of arrow symbol on the PQF-Manager display
−
Sometimes, when the number of items or variables exceeds the limit of full screen
size, a sliding bar appears on the side of the screen. Sliding down (up) this bar
displays the remaining (previous) items as shown below:
Figure 56: Illustration of sliding bar on the PQF-Manager display
Manual Power Quality Filter PQFS Commissioning instructions 79
When any of these symbols is visible, the user can scroll down/up beyond the limit of the
screen. The item list will be adjusted accordingly.
To come back (up) in the menu ladder or to quit any screen, the
button available in
each screen (top right corner) should be used.
−
When a menu button is selected, any submenu under it appears in the screen.
−
The ‘Select Unit’-function
is accessible at different places in the menu
structure and allows selecting the measurements and data as reported by
different units in a multi-unit filter system.
Figure 57: Illustration of different menu item types
The next sections discuss the four main submenus of the ‘Welcome’ screen.
Remark:
This manual uses a directory structure convention to indicate a submenu.
The main ‘Welcome’ screen is referenced as [/Welcome].
Example: [/Welcome/Measurements/System values] indicates that the ‘System values’
menu can be accessed by:
−
Press
button (on the top right corner of any screen) successively until the
‘Welcome’ screen is reached
−
Press the ‘Measurements’ menu in the main ‘Welcome’ screen which opens the
‘Measurements’ menu.
−
Similarly, other submenus can be opened by pressing the respective button.
In all menus as well as sub menu, the help symbol
is present which offers a user
friendly contextual help. If this icon is touched, its color changes to yellow
and the
user is then expected to touch any button for which a help is required. A new window
pops-up with a brief explanation about that button which was touched by the user. For
example, is a help on the "Voltage" button is requested in the menu "System Values",
following help will appear:
80 The PQF-Manager user interface Manual Power Quality Filter PQFS
7.5
The PQF-Manager behavior during filter initialization
During powering up the filter or after a system reset, the filter is initialized. This includes
initialization of the PQF-Manager also. Depending on the type of reset, the initialization
process of the PQF-Manager results in following message displayed on the screen:
Case 1: If a filter is powered up first time or after a complete power shut down, following
screens with ABB logo appear:
−
Step 1
Figure 58: PQF-Manager display during communication initialization
−
Step 2
Figure 59: PQF-Manager display when the user interface is set up
Once the communication channel has been initialized, the user interface is set up. During
this process the PQF-Manager retrieves the data structure to be displayed from the PQF
main controller.
Manual Power Quality Filter PQFS Commissioning instructions 81
Case 2: If a system reset is done while the PQF-Manager is still powered (example the
power to the main controller is reset), the initialization process takes place without the
ABB logo appearing on the screen. During this process, following two messages appear
one after another:
−
“Initializing communication, please wait” followed by:
−
“Setting up user interface, please wait”.
Above messages can be observed when looking closely at the PQF-Manager.
Case 3: When the commissioning parameters are changed or a fault is acknowledged by
the user, the filter resets and the following messages are displayed on the screen
−
“Please wait….”
−
“Resetting system….”
Table 37 gives an overview of the initialization steps for common reset conditions.
Table 37: Overview of common reset conditions and corresponding PQF-Manager initialization
steps
Reset condition after…
PQF-Manager initialization steps
Applying power to the filter first time or after a
complete isolation of filter
Case 1
Resetting power only to the main controller
Case 2
Setting up commissioning parameters
Case 3
Acknowledging fault successfully
Case 3
7.6
The PQF-Manager locking facilities
In order to prevent unauthorized modification of any of the active filter settings,
switch on the hardware lock (Figure 13 item 4).
The hardware lock is switched on by pushing the blue button located at the bottom rear
side of the PQF-Manager with a pointed object (e.g. pencil). When the lock is set:
−
will appear bottom potion of the graphics display
−
Most setting values can be consulted
Once the PQF-Manager is locked, it can be unlocked by pushing the blue button again.
In order to prevent unauthorized modification of the core installation settings of the
active filter but still giving them access to typical user settings (e.g. harmonics
selection, programming digital outputs, …), switch on the software lock.
The communication lock is applied when the corresponding parameter is set through
the menu interface. When the lock is set:
−
will appear when the settings can be changed only through the communication
The software lock is applied when the corresponding parameter is set through the menu
interface. When the lock is set:
82 The PQF-Manager user interface Manual Power Quality Filter PQFS
−
will appear. No modification can be made to the settings
The software lock is switched on in the menu [/Welcome/Settings/Installation
set./Password].
In order to unlock the system go to the same menu. After giving the appropriate
password, the system will be unlocked. The password is a four-digit number, which is
set by default to:
1234
Entering the password is done by choosing the right value numeric keyboard which
appears
on
the
screen.
The
password
can
be
changed
in
the
menu
[/Welcome/Settings/Installation set/Change Password]. Entering the new password is
done the same way and confirming the password by re-entering the same.
If hardware and software lock are combined, the hardware lock has priority over the
software lock.
Note: In active filter systems consisting of more than one master, the PQF-Manager of
the master that has the control over the system has full functionality and the PQF-
Managers of the other master units have limited functionality. The hardware lock in the
master has no effect on access level of parameters in the slave modules like warning
(alarm …). To disable these settings the hardware lock of each PQF-Manager must be
engaged.
7.7
The PQF start, stop and fault acknowledgement menu
WARNING: The active filter should only be started when it has been installed and
commissioned according to the guidelines of this manual. Failure to adhere to this
guideline may damage the filter and void warranty.
Refer to Chapter 8 for more information on commissioning the filter.
‘The PQF start, stop and fault acknowledgement’ menu can only be accessed in the main
‘Welcome’ screen [/Welcome/PQF]
‘The start, stop and fault acknowledgement’ menu is the default menu for starting,
stopping and resetting the filter.
As can be seen in Table 38 the ‘start, stop and fault acknowledgement’ menu behaves
differently depending on the filter status.
Manual Power Quality Filter PQFS Commissioning instructions 83
Table 38: ‘Start, stop and fault acknowledgement’ menu functionality according to the filter
status
Filter status
Menu display
Pushing
results in…
Filter stopped, no critical error
present (i.e. ‘normal’ stop
condition)
PQF START
Starting the filter(a) (b)
Filter running, no critical error
present (i.e. ‘normal’ running
condition)
PQF STOP
Stopping the filter(a) (b)
Filter stopped on critical fault
ACK. FAULT
Acknowledging the fault(a) (b)
Filter controlled by remote
control
PQF START or
PQF STOP or
ACK. FAULT
No action on filter behavior
Display shows message that filter is
controlled by digital input
Remark:
(a) After pushing this button, there is always a validation phase.
(b) In multi-master filter units, this function is available on the master unit that has the control
over the system.
In a multi-unit system, the PQF start, stop and fault acknowledgement menu will only
switch to the ACK. FAULT message when the complete filter system is shut down.
If one of the units of a multi-unit system is shut down due to a fault, this fault can be
acknowledged
and
reset
in
the
PQF
Monitoring
menu
[/Welcome/PQF
Monitoring/Status of module]). Note that in the reset process the whole system will be
shut down. If the fault of the unit cannot be reset, the ACK. FAULT message will be
displayed again for the unit considered. The filter system can be restarted at any time
and the units that are available will operate normally.
Acknowledging of a fault which resulted in a complete filter system shut down has two
possible consequences:
−
If the fault is permanent (e.g. permanent network under voltage due to phase
loss), it cannot be cleared and the message ‘ACK. FAULT’ will remain on the
display. In this case the cause of the problem has to be identified and removed
before the filter can be restarted.
−
If the fault is not present anymore when the ‘ACK. FAULT’ command is given, the
menu will change into ‘PQF START’ to indicate that the filter can be restarted.
Fault analysis can be done by consulting the ‘PQF Monitoring’ menu [/Welcome/PQF
Monitoring]. For more information on the ‘PQF monitoring’ menu, refer to Section 7.10.
If the filter is set up for remote control operation, the local start/stop command has no
effect.
Disable
the
digital
inputs
to
override
the
remote
control
[/Welcome/Settings/Customer set./Digital inputs].
84 The PQF-Manager user interface Manual Power Quality Filter PQFS
7.8
The ‘Measurements’ menu
This menu allows monitoring a variety of variables (e.g. voltage, current …) in a variety
of formats (e.g. RMS-values, spectra, time domain waveforms). Its submenus are
discussed next.
In multi-unit filters, several parameters are measured by the individual units. In order to
consult measurements from a specific unit, select the unit with the ‘Select Unit’ option
(where available). The order of the unit is determined by the DIP switch unit
identification setting at the moment of commissioning.
7.8.1
The ‘Overview’ menu
The Overview menu summarizes the following characteristic parameters (Table 39).
These parameters are expressed as numerical values in a list.
Manual Power Quality Filter PQFS Commissioning instructions 85
Table 39: Summary of parameters displayed in the ‘Overview’ menu
Parameter name
Unit
Description
Vrms
V
4-wire mode: RMS value of all the line-to-neutral voltages
3-wire mode: RMS value of all the line-to-line voltages
THDV
%
4-wire mode: Total harmonic distortion of all the line-to-neutral
voltages
3-wire mode: Total harmonic distortion of all the line-to-line
voltages
V1
V
4-wire mode: RMS value of the fundamental component of all the
line-to-neutral voltages
3-wire mode: RMS value of the fundamental component of all the
line-to-line voltages
Frequency
Hz
Network frequency
V dc bus
V
Active filter DC capacitor voltage
Imbalance
%
Indicates the imbalance in supply voltage (%value)
Irms
A
4-wire mode: RMS value of all the line currents and the neutral
current
3-wire mode: RMS value of all the line currents
THDI
%
Total harmonic distortion of all the line currents.
I1
A
RMS value of the fundamental component of all the line currents
PQF Irms
A
RMS value of all the filter currents, including neutral current for 4-
wire configuration
P
W,
kW,
MW
Active power in the network at the location of the CTs
P > 0: Load absorbing active power
P < 0: Load generating active power
Q
var,
kvar
Mvar
Reactive power in the network at the location of the CTs
Q > 0: Inductive reactive power
Q < 0: Capacitive reactive power
S
VA,
kVA,
MVA
Apparent power in the network at the location of the CTs
PF
-
Power factor: calculation based on the fundamental and the
harmonic values of the measurements. Measurement only valid
for quasi-balanced loads.
cos ϕ
-
Displacement power factor: calculation based on the
fundamental values of the measurements.
: System has inductive behavior
: System has capacitive behavior
cos ϕ > 0: load absorbing active power
cos ϕ < 0: load generating active power
T Control
°C/°F
Main control board temperature of the selected module
T Control max
°C/°F
Main control board temperature of the hottest module in the
group
86 The PQF-Manager user interface Manual Power Quality Filter PQFS
T IGBT
°C/°F
IGBT module temperature of the selected module
T IGBT max
°C/°F
IGBT module temperature of the hottest module in the group
On the display, the parameters are organized in such a way that a maximum of
information is obtained without having to scroll down. The user may customize the
display to his particular needs. To do this, follow the steps given below:
−
Select the measured parameter that has to be moved. The selected parameter
gets highlighted in green color background.
−
Select a new location for this parameter by touching the preferred location on the
list of parameters.
−
The selected parameter relocates to the new place.
7.8.2
The ‘System values’ menu
The ‘System values’ menu gives detailed information on the following parameters.
7.8.2.1 Voltages
Refer to Table 39 for an explanation of the parameters.
Manual Power Quality Filter PQFS Commissioning instructions 87
7.8.2.1.1 Global values
Vrms, V1 and THDV in table format.
7.8.2.1.2 Waveforms
The network voltage waveforms for all phases (Figure 60). All waveforms are
synchronized with the rising edge zero crossing of the voltage V (L1-N) (4-W mode) or V
(L1-L2) (3-W mode).
Figure 60: Time domain waveform of line voltage displayed by the PQF-Manager (3-W mode
example)
7.8.2.1.3 Spectrum
The network voltage spectrum for all phases in chart format (Figure 61). The spectral
components up to the 49th order are expressed as a % of the fundamental component
with absolute values also shown in the top right corner. The two buttons with “+” and “-
“ mark help changing the voltage level resolution (i.e. Y-axis value in the chart).
Figure 61: Spectrum of the network voltage in chart format displayed by the PQF-Manager (4-W
mode example)
88 The PQF-Manager user interface Manual Power Quality Filter PQFS
7.8.2.1.4 Harmonic table
The network voltage spectrum for all phases in table format (Figure 62). Both the
absolute values and the % of the fundamental component values are shown for each
spectral component up to the 49th rank.
Figure 62: Spectrum of the network voltage in table format displayed by the PQF-Manager (4-W
mode example)
Following parameters are displayed in the sub-menu “Voltages” itself in a tabular form.
−
The network frequency
−
The network imbalance
−
The active filter DC bus voltage of the selected unit
−
The active filter DC bus voltage (max.)
7.8.2.2 Line currents
Refer to Table 39 for an explanation of the parameters.
Manual Power Quality Filter PQFS Commissioning instructions 89
7.8.2.2.1 Global values
Irms, I1 and THDI are displayed in table format.
7.8.2.2.2 Waveforms
The line current waveforms for all phases (3-W mode) and the neutral current waveform
(4-W mode). The graph layout is similar to the one of the voltages (Figure 60). All
waveforms are synchronized with the rising edge zero crossing of the voltage V (L1-N)
(4-W mode) or V (L1-L2) (3-W mode).
7.8.2.2.3 Spectrum
The line current spectrum for all phases (3-W mode) and the neutral current spectrum (4-
W mode) in chart format. The chart layout is similar to the one of the voltages (Figure
61).
7.8.2.2.4 Harmonic table
The line current spectrum for all phases (3-W mode) and the neutral current spectrum (4-
W mode) in table format. The table layout is similar to the one of the voltages (Figure
62).
7.8.2.3 Filter currents
Refer to Table 39 for an explanation of the parameters.
PQF Irms in table format for the unit selected with the ‘Select Unit’ option.
90 The PQF-Manager user interface Manual Power Quality Filter PQFS
7.8.2.3.1 Waveforms
The filter current waveforms for all phases for the unit selected with the ‘Select unit’
option. The graph layout is similar to the one of the voltages (Figure 60). All waveforms
are synchronized with the rising edge zero crossing of the voltage V (L1-N) (4-W mode)
or V (L1-L2) (3-W mode).
7.8.2.3.2 Spectrum
The filter current spectrum for all phases (3-W mode) and the neutral current spectrum
(4-W mode) in chart format for the unit selected with the ‘Select unit’ option. The chart
layout is similar to the one of the voltages (Figure 61) but the values are expressed in
absolute terms.
7.8.2.3.3 Harmonic table
The filter current spectrum for all phases (3-W mode) and the neutral current spectrum
(4-W mode) in table format for the unit selected with the ‘Select unit’ option. The table
layout is similar to the one of the voltages (Figure 46) but only absolute current values
are shown.
7.8.2.4 Total filter currents
Refer to Table 39 for an explanation of the parameters.
PQF Irms in table format for the complete filter system.
7.8.2.4.1 Waveforms
The filter current waveforms for all phases for the complete filter system. The graph
layout is similar to the one of the voltages (Figure 60). All waveforms are synchronized
with the rising edge zero crossing of the voltage V (L1-N) (4-W mode) or V (L1-L2) (3-W
mode).
7.8.2.4.2 Spectrum
The filter current spectrum for all phases (3-W mode) and the neutral current spectrum
(4-W mode) in chart format for the complete filter system. The chart layout is similar to
the one of the voltages (Figure 61) but the values are expressed in absolute terms.
7.8.2.4.3 Harmonic table
Manual Power Quality Filter PQFS Commissioning instructions 91
The filter current spectrum for all phases (3-W mode) and the neutral current spectrum
(4-W mode) in table format for the complete filter system. The table layout is similar to
the one of the voltages (Figure 46) but only absolute current values are shown.
Note: For a multi-unit filter system, the total filter current is an approximate value. More
detailed values for the individual units can be obtained in the ‘Filter currents’-menu.
7.8.2.5 Powers
The power in the system at the location of the CTs: (Refer Table 39 for an explanation
of the parameters).
−
Active power P
−
Reactive power Q
−
Apparent power S
−
Power factor PF
−
Displacement power factor cos ϕ
7.8.2.6 Temperatures
Refer to Table 39 for an explanation of the parameters.
−
Temperatures may be expressed in °C and in °F. For changing the temperature
unit, go to [/Welcome/Settings/Customer set. /Temp unit].
92 The PQF-Manager user interface Manual Power Quality Filter PQFS
−
Temperature of the hottest IGBT (‘T IGBT’) of the unit selected by the ‘Select unit’-
option. Temperature of the hottest IGBT (T IGBT max) in a multi-unit system
−
Temperature of the control board (‘T Control’) of the unit selected by the ‘Select
unit’-option
−
Temperature of the hottest control board (‘T control max’) in a multi-unit system
−
Temperature recorded by the optional temperature probes (up to 8 probes can
be connected on each PQF-Manager)
7.8.3
The ‘Min-Max logging’ menu
The ‘Min-Max logging’ function allows for the user to log for each significant measured
item and since the last reset:
−
The maximum (or minimum) value
−
The duration above (or below) the threshold
Once a threshold has been set the PQF-Manager starts recording the maximum (or
minimum) value automatically as well as the total duration until a reset is performed.
Figure 63 illustrates this.
Figure 63: Illustration of the threshold and the maximum recorded value used in the Min/Max
logging function
The parameters that can be used with the logging function are voltages (Vrms, THDV),
currents (Irms), Power (P, Q, S), frequency and temperature (T IGBT and Tcontrol) along
with temperatures recorded by the probes (max. 8 probes possible). All information
about temperature are specific to the probe connected to the PQF-Manager where the
probe is connected. Refer to Table 39 for an explanation of the parameters. For the
frequency, minimum values and duration below a threshold can also be recorded.
The recorded information may be cleared by selecting and validating the ‘Reset’ item.
Manual Power Quality Filter PQFS Commissioning instructions 93
If the hardware lock is engaged, the logging function cannot be started nor reset (Cf.
Section 7.6)
Figure 64 shows an example in which the network voltage between L1 and L2 is
monitored. The nominal network voltage is assumed to be 400 V. The threshold was
initially set at 1000 V and is changed to 420 V.
Figure 64: Example of the Min/Max logging function (4-W mode)
7.9
The ‘Settings’ menu
The ‘Settings’ menu [/Welcome/Settings] has four main levels:
−
The customer level which allows the user to set up the typical user requirements
such as harmonic filtration settings, the reactive power settings, sets up the
digital inputs and outputs and defines the programmable warnings and alarms.
At this level, the user can also change the temperature unit used by the system.
The customer level is accessed through [/Welcome/Settings/Customer set.]
−
The commissioning level which allows the commissioning engineer to set up the
equipment according to the customer’s installation. Typical parameters that
need to be entered are the network voltage and frequency, the CT parameters
and a derating factor that needs to be applied when the installation is at great
height above sea level or in conditions where excessive ambient temperatures are
present. At the commissioning level the possibility also exists to set up the user’s
requirements for harmonic filtration and reactive power compensation. The
commissioning level is accessed through [/Welcome/Settings/Commissioning].
94 The PQF-Manager user interface Manual Power Quality Filter PQFS
−
The installation settings level allows for the commissioning engineer to set up
advanced system functions such as the filter auto restart and standby functions,
the clock, the communication of Modbus and PQ-Link and the setting of a system
lock with password.
For information purposes the installation settings level also shows the settings
for the network voltage and frequency, the rating of the filter unit(s), the CT
parameters and the derating factor that has been set-up at the commissioning
level.
The
installation
settings
level
is
accessed
through
[/Welcome/Settings/Installation set.]
−
Apart from above three, the fourth button allows the language setting. The PQF-
Manager supports six languages: English, French, German, Spanish, Chinese
(simplified) and Korean.
Note: In active filter systems consisting of more than one master, the PQF-Manager of
the master that has the control over the system has full functionality and the PQF-
Managers of the other master units have limited functionality. In practice, the functions
that are not enabled on these units are locked and a
symbol will appear. These
functions are set up in the ‘real’ master and are automatically further dispatched to the
other units by the control system.
All functions and measurements (e.g. digital I/O, temperature) which are “hardwired” to
a PQF-Manager provide data/control only for that specific filter unit.
7.9.1
The ‘Customer settings’ menu
Manual Power Quality Filter PQFS Commissioning instructions 95
The customer settings menu is intended to be used by people that are authorized to
change the filter operation settings.
Refer to Section 7.6 for determining appropriate locking facilities for this menu.
7.9.1.1 Settings up harmonics, reactive power and filter mode
In multi-master units these functions need to be set up only in the master with the
lowest hardware ID (0001 in case of single module and 0000 in case of multiple units)
setting in the DIP switch.
Setting up harmonics, reactive power and filter mode can be done in a main window
[/Welcome/Settings/Customer set./Main settings]
and
in
an
auxiliary
window
[/Welcome/Settings/Customer set./Auxiliary settings]. By having two windows, the
customer can set two sets of different settings, e.g. one set for mains operation and one
set for generator operation, or one set for day settings and one set for night settings.
Both main and auxiliary settings windows have the same setup possibilities, i.e.
−
Definition of the filter mode
−
Selection of the harmonics with setting of curve levels
−
Selection of reactive power compensation with balancing functionality
−
Deselection of all harmonics
The filter has to be informed about whether the main window settings or the auxiliary
window
settings
must
be
used.
This
is
done
by
the
‘Activate’
flag
[/Welcome/Settings/Customer set/Activate]. Possible values for this flag are given in
Table 40. By default the filter uses the main filter settings.
Table 40: Possible settings for the activate field
‘Activate’ field value
Description
Main
Main window settings are always used
Auxiliary
Auxiliary window settings are always used
Ext. input
The filter switches between the main and the auxiliary settings
according to a signal applied to the PQF-Manager’s digital input(a).
Remark:
96 The PQF-Manager user interface Manual Power Quality Filter PQFS
(a) Refer to detailed manuals for cabling instructions for this feature. Refer to Section 7.9.1.4
configuring the digital input for this feature. The external input must be provided to the PQF-
Manager which acts like the “master” unit.
7.9.1.1.1 Setting up the filter mode
For setting up the filter’s main filter mode go to [/Welcome/Settings/Customer
set./Main settings/Filter mode].
For setting up the filter’s auxiliary filter mode go to [/Welcome/Settings/Customer
set./Auxiliary settings/Filter mode].
The filter can have three types of effect on the network:
−
Filter the selected harmonics until their magnitudes are close to zero (Maximum
Filtering)
−
Filter the selected harmonics until their magnitudes reach the residual level
permitted by the user (Filtering to Curve)
−
Produce or absorb reactive power including load balancing
The user can put the emphasis on one of the above effects by selecting the filtering
mode. Table 41 shows the three available modes:
Table 41: Available filter modes
Highest priority level
Lowest priority level
Mode 1
Filtering to curve
Maximum filtering
Reactive compensation
Mode 2
Filtering to curve
Reactive compensation
Maximum filtering
Mode 3
Filtering to curve
Reactive compensation
-
In Mode 1, the filter will first filter to the pre-programmed curve. Once the requirements
are fulfilled, the remaining resources will be allocated to reducing the selected
harmonics as close as possible to zero. If further resources are then available, reactive
power compensation and load balancing will be performed as required.
In Mode 2, the second priority after filtering to the curve is reactive power compensation
and load balancing. Maximum filtering comes in third place and will be done if both the
curve specification and the reactive power requirements including balancing are fulfilled.
In Mode 3, the filter will first ensure that the harmonic curve specification is fulfilled. If
then there are still resources available, the filter will do reactive power compensation
and load balancing if requested by the user.
Manual Power Quality Filter PQFS Commissioning instructions 97
Figure 65 illustrates the principle of filtering to curve for one particular harmonic order.
The flexibility of the PQF control is such that a specific curve level may be defined for
each selected harmonic.
Figure 65: Filtering to curve for harmonic order n
The default filter mode is Mode 3.
7.9.1.1.2 Selecting the harmonics with setting of curve levels
For setting up the filter’s main harmonics selection go to
[/Welcome/Settings/Customer set./Main settings/Main harmonics]
For setting up the filter’s auxiliary harmonics selection go to
[/Welcome/Settings/Customer set./Auxiliary settings/Aux. harmonics]
The harmonics that can be selected are presented in a table such as presented in Table
42.
When the PQF is operating in 4-W mode, 15 harmonics can be selected.
When the PQF is operating in 3-W mode, 20 harmonics can be selected.
98 The PQF-Manager user interface Manual Power Quality Filter PQFS
Table 42: Example of harmonic settings table displayed by PQF-Manager
Order
Select(a)
Curve(b)
3
Yes
0 A
5
Yes
10 A
7
Yes
0 A
9
No
0 A
Remarks:
(a) The ‘Select’ column may have three values:
No: Harmonic not selected by user
Yes: Harmonic selected by user and being filtered
S: Harmonic selected by user but put in ‘standby’ by the filter. Refer to Section 8.10 for more
information on the “harmonic standby” mode.
(b) Curve settings for allowed current into the network are expressed in Amps
In order to select the harmonics and set up a curve level (if desired)
−
Open the harmonic table by selecting the “Main harmonics”. The table has a
default factory setting.
−
Select any row by touching it, a new window opens up with two drop down menu
(one for harmonic order and another for select option) and a third one to enter
the “curve” value. In the harmonic order all harmonics from 2nd to 49th order are
listed but, only those harmonics which are not already chosen appears selectable
and those which are already in the pre-selected list appear “greyed”. Once a new
harmonic order is selected, the table automatically gets sorted in ascending
order. In order to remove any harmonic order from this list, one has to touch that
row and then from the dropdown menu, replace that harmonic order by any other
harmonic of choice.
−
Note: Above procedure is only to include (or exclude) any harmonic order in the
list. Further to that, the user must select specific harmonics by choosing Yes or
No from the other dropdown menu for the filter to consider them for filtering
−
To set the curve value, the “curve” data entry window needs to be selected. As
soon the window is touched, the numeric keypad appears allowing the user to set
a desired curve level (in terms of Amp). Fractional values are not accepted and are
rounded off to the nearest integer. Once all the harmonics are programmed, the
harmonic selection table can be exit by pressing. The
button at the top right
corner.
Manual Power Quality Filter PQFS Commissioning instructions 99
7.9.1.1.3 Deselect all harmonics
For deselecting all harmonics of the main window at once go to
[/Welcome/Settings/Customer set./Main settings/Deselect all]
For deselecting all harmonics of the auxiliary window at once go to
[/Welcome/Settings/Customer set./Auxiliary settings/Deselect all]
This function allows for the customer to quickly deselect all harmonics in the main or the
auxiliary window. This may be useful e.g. when the commissioning engineer realizes that
the CTs have been installed wrong and an intervention is required to correct the problem.
7.9.1.1.4 Selecting the reactive power compensation and balancing options
For setting up the filter’s main reactive power and balancing mode go to
[/Welcome/Settings/Customer set./Main settings/Main PFC/Bal.]
For setting up the filter’s auxiliary reactive power and balancing mode go to
[/Welcome/Settings/Customer set./Auxiliary settings/Aux. PFC/Bal.]
The active filter can perform different reactive power tasks including balancing, each of
which require the appropriate setup. Table 43 shows an overview of the possible tasks
and shows how the filter set up should be done to implement this task. The parameters
(italic print) referred to in Table 43 can be accessed in the ‘Main PFC/Bal.’ and ‘Aux.
PFC/Bal.’ windows of the PQF-Manager.
100 The PQF-Manager user interface Manual Power Quality Filter PQFS
Table 43: Reactive power tasks that the filter can perform
Reactive power task requirement
Description and filter set-up to be made
No requirements
PFC type: Disabled
Balance load: Disabled
The filter will not do any reactive power task,
regardless of the values set for cos ϕ or static reactive
power
Power factor compensation with
inductive power factor set point, no
load balancing required(a)
PFC type: Dyn. Ind.
Target cos ϕ: Desired power factor between 0.6 and
1.0
The filter will do power factor compensation up to the
cos ϕ set point, regardless of the value set for static
reactive power(b)
Power factor compensation with
capacitive power factor set point,
no load balancing required(a)
PFC type: Dyn. Cap.
Target cos ϕ: Desired power factor between 0.6 and
1.0
The filter will do power factor compensation up to the
cos ϕ set point, regardless of the value set for static
reactive power©
Fixed capacitive power step with a
rating of x kvar, no load balancing
required(a)
PFC type: Static cap.
Q static: x kvar
The filter will generate x kvar reactive capacitive
power, regardless of the value set for the target cos ϕ
Fixed inductive power step with a
rating of x kvar, no load balancing
required(a)
PFC type: Static ind.
Q static: x kvar
The filter will absorb x kvar reactive inductive power,
regardless of the value set for the target cos ϕ
Remarks:
(a) When load balancing is required, set the ‘Balance load’ flag to the desired mode. The
following modes are available depending on the way the filter is connected (3-W or 4-W)
-
‘Disabled’: No load balancing is done.
-
‘L-L’: Loads connected between phases only are balanced. Loads connected between
phases and neutral are not balanced.
-
‘L-N’: Loads connected between phase and neutral are balanced. Loads connected
between phases are not balanced. This mode is only available when the filter is connected
in 4-W mode.
-
‘L-L & L-N’: Both loads connected between phase and neutral as well as loads connected
between phases are balanced. This mode is only available when the filter is connected in
4-W mode.
Note: The modes ‘L-N’ and ‘L-L & L-N’ can be used to minimize the amount of fundamental
frequency current flowing in the neutral.
(b) If the measured cos ϕ is higher than the set point and is inductive (e.g. measured 0.97
inductive and set point 0.92 inductive, then the filter will not make any correction. If the
measured cos ϕ is capacitive, the filter will correct the power factor to 1.0
(c) If the measured cos ϕ is higher than the set point and is capacitive (e.g. measured 0.97
capacitive and set point 0.92 capacitive, then the filter will not make any correction. If the
measured cos ϕ is inductive, the filter will correct the power factor to 1.0