WARNING: Failure to follow these instructions could

result in death, personal injury, or property damage. • This circuit breaker is intended for use on single- phase grounded 120Vac 2-wire branch circuits. Shared neutral circuits where the neutral from separate branch circuits is combined to one neutral wire and returned to either

Push-to-test button will not trip

circuit breaker. 1. Circuit breaker is OFF. 2. Circuit breaker is tripped. 3. Load center is not energized. 4. The DFCI neutral (pigtail) is not connected to the neutral bus bar. 5. Circuit breaker is damaged. 1. Turn circuit breaker ON. 2. Reset the brea

Instrucciones para la instalación

ADVERTENCIA: El no seguir estas instrucciones puede resultar en la muerte, lesiones personales o daños a la propiedad. • Este cortacircuitos esta diseñado para usarse en circuitos ramales monofásicos de 2 cables, 120Vac con conexión a tierra. El uso de este cortacircuitos en circuitos con el neutral compartido está

Guías de solución de problemas

Condición Causa posible Solución/acción Al presionar el botón de prueba el cortacircuitos no interrumpe (TRIP). 1. El cortacircuitos está apagado (OFF). 2. El cortacircuitos está en la posición de interrupción (TRIP). 3. El panel eléctrico no está energizado. 4. El cable neutral embobinado del DFCI no está conec

Instructions pour l’installateur

AVERTISSEMENT : Le non-respect de ces instructions peut entraîner la mort, des blessures corporelles ou des dommages matériels. • Ce disjoncteur est conçu pour être utilisé sur des circuits de dérivation monophasés de 120 VCA à 2 fils. Les circuits partagés neutres où le fil neutre des circuits de dérivation