UltraLink® Monitor
FTMU
lindab | technical information
Introduction
UltraLink® FTMU is a highly accurate flow monitor without any obstacles in the airstream that creates pressure drop. It mea-
sures the flow with an angled ultrasonic beam which can be calculated and compensated to a very high accuracy over the
whole flow range. The method is very stable over time due to that it is not sensitive to dirt and the design minimizes the dust
accumulation on the flow sensors.
An increased focus on energy saving has led to ventilation systems requiring low minimum flows. The low flows are a pro-
blem since they are very difficult to measure, which makes it difficult to control the ventilation system.
The new technology of UltraLink® makes it possible to measure lower air flows compared to today’s products while maintai-
ning measurement accuracy. This offers great advantages for the user in terms of comfort and savings in energy consump-
tion, which is of great interest.
Content
Introduction ....................................................................................................2
Overview (Application, Design, Display unit) .................................................3
Mounting ........................................................................................................4
Electrical installation ......................................................................................7
Commissioning ............................................................................................ 11
Mobile app .............................................................................................. 11
Ultra BT™ Room Control System (Installation of wireless sensors) ...... 11
Display .................................................................................................... 12
Parameter structure ................................................................................ 12
Status light .............................................................................................. 12
Connecting flow measurement for installation close to disturbance ..... 13
ID-numbers ............................................................................................. 13
PIN code ................................................................................................. 13
Maintenance ........................................................................................... 13
Configuration menu structure ................................................................. 13
Digital communication settings .................................................................... 14
Analog communication settings .................................................................. 14
Troubleshooting ........................................................................................... 15
Technical data .............................................................................................. 16
Appendix A – Modbus register .................................................................... 17
© 11.2021 Lindab Ventilation. All forms of reproduction without written permission are forbidden.
is the registered trademark of Lindab AB.
Lindab's products, systems, product and product group designations are protected by intellectual property rights (IPR).
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Overview
Application
The FTMU is suitable for measuring air flow and tempe-
rature. Communication is established via analog or digital
signal using Modbus.
Design
The FTMU consists of a sensor body with Lindab Safe
gaskets.
Two flow sensors are mounted on the sensor body and
connected to a display unit. The display unit is mounted
on top of a shelf on the sensor body.
Note! The flow sensors are placed at a fixed distance
to each other and they shall never be removed and
not used as handles when turning the sensor body.
Display unit
QR code
Status light
Bluetooth®
Display parameters
Air flow direction
Mode button
CE-mark
IP classification
Display unit
Transducer
Sensor body
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Mounting
Please note:
•
The transducers must never be removed!
•
Do not use the transducers as handles when you mount the
FTMU since this may cause damage!
Transducers
•
Make sure the airflow arrow is pointing in the direction of the
airflow.
Airflow direction arrow
•
Rotate the senor body to the correct position according to
the chapter “Planning” on the next page.
•
Position the display so it is visible from a suitable direction.
By loosening the screw of the steel strip, the display unit can
be rotated.
•
Mount the FTMU into the air duct system according to the
mounting instructions for Lindab Safe.
•
Never use a FTMU on the outlet side of a duct fan. (Place it
on the inlet side or in worst case use a flow conditioner if it
must be placed on the outlet side.)
Duct fan
•
Note the ID-number of the FTMU. The ID is the three last
numbers of the serial number and can be found:
- on the label of the box it was delivered in
- on the label on the FTMU itself
- in the display after pressing the “MODE” button
- in the App when the product is turned on
Controller FTCU Ø125
Serial no. 132600052
UltraLink
Lindab®
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Planning
The longer distance to disturbance, i.e. the longer straight duct before the FTMU, the higher the measurement accuracy
will be. However this is not the only factor which affects the accuracy of the measurement. The rotation of the FTMU
and hence the positioning of the first flow sensor has an impact on the uncertainty of the measurement. It is not
recommended to mount the FTMU so that the first flow sensor (*) is placed on an outer radius of a fitting.
For example: in the case of the bend in the table below, by rotating the FTMU to position the first flow sensor according
to the first picture (with the first flow sensor on the inner radius of the bend), the FTMU can be placed at the distance
of two duct diameters from the disturbance to achieve 5 % uncertainty. Positioning the FTMU according to the second
picture (with the first sensor on the outer radius of the bend), the FTMU must be mounted five duct diameters from the
disturbance to achieve the same level of uncertainty.
Other obstructions in the duct system such as axial fans, silencer baffels or cleaning hatches etc. are not allowed before
the UltraLink (in the direction of the flow). If a cleaning hatch is required, it must be placed after the UltraLink (in the direc-
tion of the flow). The reason is that these cause turbulences, which can result in errors in flow measurements.
Disturbance
* Placement of first flow sensor
Measurement uncertainty
± % or X l/s depending wich
is the greatest of percentage
or the absolute value for the
specific product size, see
table on page 16.
a
2-4·Ød
>4-5·Ød
>5·Ød
Bend
a
Ød
*
Inner radius
(Best position)
5
5
5
Bend
a
Ød
*
Outer radius
(Not recommended)
20
10
5
Bend
a
Ød
*
a
Ød
*
Side
10
5
5
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Disturbance
* Placement of first flow sensor
Measurement uncertainty
± % or X l/s depending wich
is the greatest of percentage
or the absolute value for the
specific product size, see
table on page 16.
a
2-4·Ød
>4-5·Ød
>5·Ød
Reducer
a
Ød
*
Duct diameter
decrease
5
5
5
Reducer
a
Ød
*
Duct diameter increase
10
5
5
T-piece
a
Ød
*
Inner radius
(Best position)
10
5
5
T-piece
a
Ød
*
Outer radius
(Not recommended)
20
10
5
T-piece
a
Ød
*
Side
10
5
5
a
Ød
*
8 9 10 11 12
SCL
SDA
GND
3V3
14 15 16
13
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Electrical installation
Please note:
•
You must under no circumstances make any holes or connect anything with screws to
the body of the FTMU.
•
In case electrical installation equipment such as a junction box is needed for installation,
the FTES is a Lindab accessory which can be mounted on the FTMU without causing
damage to the FTMU.
•
Never remove the blue electronics box.
•
Never remove the transducers.
Use the premounted cable >>
•
Connect power and communication cables to the
premounted cable.
•
Check the label on cable for reference to cable
colours.
•
It is important that the cable is as short as pos-
sible for optimal Modbus communication.
For cable connections there is two options, use the
premounted cable or connect directly in the
PCB (option A and B):
Connect directly on PCB >>
•
To access the terminals on the circuit board,
remove the lid by pushing the two heels on the
side of the blue box.
•
To be able to connect cords to the terminal board
the rubber cable grommet on the backside of the
display unit must be punctured, preferably using
an awl or something pointy to ensure tightness to
the environment. Do not remove the blue box to
do this!
•
When the cables have been connected they must
be strain relieved. The cables can be attached
to the shelf by using cable ties that are attached
around cut outs in the shelf.
Option A
Option B
8 9 10 11 12
SCL
SDA
GND
3V3
14 15 16
13
24V AC/DC {
G+
G-
Modbus
+B
-A
GND
Analog
signals {
AO1
AO2
AIN
{
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Option B: Circuit board screw terminals
Connections are made in the terminal board which can be accessed when the lid of the display unit is removed. In the
back of the lid there is a picture with a list of the terminals.
1.
24V, power supply (AC G, DC +) *
2.
GND, power supply (AC G0, DC -) *
3.
+B, connection for Modbus via RS485
4.
-A, connection for Modbus via RS485
5.
SH, shield
6.
GND, ground (system neutral)
7.
AO1, analog output
8.
AO2, analog output
9.
AIN, (not used in this version)
10. MO1, (not used in this version)
11. MO2, (not used in this version)
12. GND, ground (system neutral)
13. SCL, not used
14. SDA, not used
15. GND, ground (system neutral)
16. 3V3, not used (in case of biasing)
*) When using AC terminal 1 (G) should have system potential and terminal 2 (G0) should be system neutral.
Recommendations for wiring
Function
Cable type
24 V Supply
2-wire, thickness depending on length and load, max. 1,5 mm²
RS485 Modbus communication
2-wire shielded twisted pair, min. 0,1 mm² (LIYCY cable)
Using other cables for Modbus signals may result in communication problems.
Analog connection
When connecting the FTMU
using analog signals, it is impor-
tant to connect the analog out
signals on the FTMU (AO1, AO2)
to the analog in terminals on the
RTU and the analog in signal
(AIN) is connected to the analog
out terminal on the RTU. Also
make sure to connect the cables
to the same analog ground.
Option A: Connect to premounted cable
Connect the premounted cable in a junction box near the FTMU. Con-
nect power and signal cables in the junction box according to the color
scheme on the lable on the premounted cable, see picture to the right.
When connecting Modbus signal wires, the length of the premounted
cable needs to be as short as possible, since these have a negative
effect on signal quality.
In this case, place junction box as close to the FTMU as possible, then
cut the premounted where it is as short as possible for installation.
Connection of
UltraLink
Note! All cables that are
not connected must be
insulated.
24V
Red
GND
White
+B
Yellow
-A
Brown
GND
Grey
AO1
Green
AO2
Blue
AIN
Pink
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Digital connection (Modbus)
Connect A on the RTU to -A on the display unit and B to +B. When connecting more than one FTMU in series it is
important to keep connecting -A to -A and +B to +B since crossing them will stop Modbus from working. It is recom-
mended to use RS485 cables with twisted pairs and shield, do not supply power in the same cable unless the cable
is produced for that purpose. When connecting signal ground, attach it to “GND” on the terminal to the right of the
terminal for shield (SH) on the PCB. Then attach it to the corresponding terminal in the RTU.
Connecting shield
The shield in the RS485 cable should be connected to ground at the transformer and then continuously connect to
”SH” on all the UltraLinks that are powered from that transformer. If more than one transformer is used on the bus, the
shield is broken at each transformer so ”SH” on every product only has connection to ground at the transformer from
which its power is supplied.
BA
+B -A
+B -A
+B -A
+B -A
GND
GND
GND
GND
Signal ground
Shield ground
Biasing
The master on the bus must have biasing on
-A and +B. This is more or less standard on
BMS-controllers, but if communication should
be established with a conventional compu-
ter using a RS485-USB converter, then it is
important to make sure that the converter has
a bias circuit. If communication fails and you
are uncertain about existance of biasing,
you can add biasing resistors in the screw terminal on one of the UltraLinks to see if this is the cause of the com-
munication failure. Use 500 - 1000 Ω resistors and connect one resistor from -A to GND and one from +B to the 3V3
terminal. It is also recommendedto add a 120 Ω termination resistor between -A and +B on the last UltraLink on the
bus to avoid signal reflections.
Repeater
If the bus is longer than 300 meters or if there
are more than 30 devices, the system might
need an RS485 repeater (FDS-R, see picture
to the right) to be able to communicate in an
efficient way.
Wire cross section Area [ mm2 ]
0
0,1
0,2
0,3
0,4
0,5
0,20
0,15
0,10
0,05
0
Copper Resistance [ Ω/m ]
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Power supply
Transformer sizing
The needed size of 24 V AC transformer(s) can be defined by adding up the dimensioning power consumption [VA] of all
the components. The transformer power must exceed this. Use only safety isolating transformers. Calculation of the cur-
rent demand I:
I = (P1+P2+…+Pn) / U [A] where: Pn is the dimensioned power consumption for each component [VA] U is the voltage
(24) [V].
If the current demand I exceeds 6 A ( which corresponds to approximately 150 VA for a 24 V AC transformer ), it is neces-
sary to use more transformers to prevent overheating.
Supply cable sizing
The wire size of the supply cable can be determined by calculating the resistance per meter R. The calculation presuppo-
ses that a voltage drop of e.g. 2 V is accepted in the supply cable:
R(per m) = Udrop / (I * L) [Ω/m] where: Udrop is the accepted voltage drop (2 V) in the cable [V] I is the current [A]
L is the longest distance of supply cables from transformer to a component [m]
Wire cross section area as a function of resistance per m for copper wire
Example:
Udrop = 2 V, I = 4 A, L = 20 m
R (per m) = 2V / (4A × 20 m) = 0,025 Ω/m
In the diagram a Wire cross section Area of 0,7 mm² can be read.
Power consumption
The power consumption for dimensioning supply cables for an UltraLink® FTMU is 0,5 VA.
It is not recommended to use a transformer with a higher capacity than 150 VA.
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Commissioning
Mobile app
Using a smartphone with the Lindab OneLink app, nearby UltraLinks will be identified.
Now you can connect to all the different UltraLink units, change settings and view
information regarding each unit. You can find the OneLink app in both Google Play and
AppStore, free of charge. The settings of all the different UltraLink units can then easy
be changed directly through the app. This means you can have individually settings
chosen for a specific building.
It is therefore necessary to change the PIN code in the UltraLink, for a discription on
how this is done, see page 13.
Download app
Lindab Ultra BT™ User Manual
You can find the specific user manual for the Ultra BT™
Room Control System by clicking or scaning the QR code.
Lindab Ultra BT™ Room Control System
(Installation of wireless sensors)
Ultra BT is based on few components and introduces a revolutionized way of
controlling and optimizing your Demand Controlled Ventilation system at room
level.
It is a 360-degree system upgrade with a fully integrated Bluetooth Technology,
making both costs, installation complexity, and daily operations much more
efficient and indoor climate optimal at all times.
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Display
The display can show
useful information both
with the diode flashing in
green (status light) and
with parameters in the
LCD. If the product is
equipped with Bluetooth,
then the diode will also
flash in blue every three seconds. If a device has been
connected to the UltraLink via Bluetooth, then the diode
will flash in blue every other second.
By short pressing the mode button you can change the
displayed parameter. If the button is pressed for more than
5 seconds (long press) then the configuration menu will be
visible. The arrow at the bottom of the display indicates the
current parameter type and unit.
For a detailed description on configurating the UltraLink
using the mode button on the display, see page 13.
Parameter structure
The information menu is visible in the display as soon as
the device is powered and by default the air flow in m³/h is
shown. You can toggle between the different parameters in
the menu by short pressing the Mode button. The arrows
at the bottom of the menu indicates the air flow reading,
temperature and also what unit the current value has (if
any). The following list of parameters are available;
• Air flow (m³/h)
• Air flow (l/s)
• Air velocity (m/s)
• Temperature (°C)
• FTMU ID number
Status light
The green status light indicates:
Mode
Function
No light
FTMU is turned off
Flashing light every 1 second
A problem has occurred, error code will be visible in display
Constant light
FTMU is turned on and functioning as normal
The Blue status light indicates:
Mode
Function
No light
Bluetooth is turned off or the FTMU is not equipped with it.
Flashing light every 3 second
Bluetooth is on stand by and is ready to connect to mobile device.
Flashing light every 1 second
A mobile device has been connected to the FTMU.
Controller FTCU Ø125
Serial no. 132600052
UltraLink
Lindab®
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Correcting flow measurement for
installation close to disturbance
Later UltraLinks have a function to compensate for
mounting the product closer to a disturbance, and still
have 5% measurement uncertainty, than what is specified
in the chapter “Mounting”. If it is required to install an
UltraLink close to a disturbance, the correction is done via
a function in the OneLink app. Connect a mobile device to
the UltraLink and tap the “Device” tab, there is a function
ID-numbers
The FTMU is given an
ID-number between 1 to 239
during production. The given
ID-number can be seen on
the label on the outside of the box the FTMU is delivered
in, the ID-number is the same as the three last digits in the
serial number.
If two or more Modbus devices have the same ID-number
it is necessary to apply changes so that each of them get
an unique ID-number to allow communication.
To change the Modbus ID register of an UltraLink® all other
devices with the same ID must be disconnected. It is more
efficient to change the ID in the display under “Con.Set”
(see table below) or with the OneLink app. The register for
Modbus ID is a holding register with address 4x001.
PIN code
UltraLink with Bluetooth must be protected againt
unauthorized access by PIN-code, which has to be
stated before changes to the settings can be made. It is
important to choose and change the code that the product
is delivered with (1111), to ensure that no unauthorized
changes are made. The Bluetooth radio can be disabled by
setting register 4×007 to 0.
The code can be changed in three ways:
• using the configuration menu in the display,
see below table.
• connecting a PC via Modbus and using the
“Configuration Tool” software.
• connect a Bluetooth device and use the OneLink
application.
Maintenance
The FTMU does not normally require any maintenance.
The visible parts of the device can be wiped with a damp
cloth.
Configuration menu structure
The configuration menu is activated by long pressing the button (5 sec). After long pressing the button a new menu will
appear with three different options;
• Con.Set
(Connection settings)
• Cancel
(Cancel and return to information menu)
Under Con.Set (connection settings) you can find the following options (toggle with short press, select with long press);
which is activated by choosing “Type of disturbance” and
then “Distance to dirsturbance”. After these two inputs
have been made, the function is active and corrects the
flow according to the inputs made.
Menu tag
Description
Options
Description
• Pr.
Protocol
Pr.PAS
Pr.Mod
Pascal protocol
Modbus
• b.
Baud rate
b.9600
b.19200
b.38400
b.76800
Baud rate 9600
Baud rate 19200
Baud rate 38400
Baud rate 76800
• bit.
Stop bits
bit.1
bit.2
1 stop bits
2 stop bits
• P.
Parity
P.odd
P.even
P.none
Odd parity
Even parity
Parity none
• Id.
Modbus Id
Id.x
Modbus id (x = value) *)
• PLA.
PLA address for Pascal
PLA.x
PLA address (x = value) *)
• ELA.
ELA address for Pascal
ELA.x
ELA address (x = value) *)
• Pi.
Pin-code
Pi.xxxx
Default: xxxx = 1111
• Store
Store changes
Strores changes on long press
• Cancel
Cancel
Cancel and ignore changes on long press
*) To change the value you need to long press until a blinking cursor appears under the first single number in the current value. After that
you short press to toggle to the desired number, then you long press to move the blinking cursor to the next single number in the current
value. Proceed until the new value has been set and long press to continue.
Lindab reserves the right to make changes without prior notice
2021-11-02
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Size Ø
[mm]
4x400
Level
Conf.
4x401
Unit
Conf.
4x402
Temp Min
[°C]
4x403
Temp Max
[°C]
4x404
Flow Min
[l/s]
4x406
Flow Max
[l/s]
100
2 (2-10V)
0 (Flow)
0
50
0
55
125
0
50
0
86
160
0
50
0
141
200
0
50
0
220
250
0
50
0
344
315
0
50
0
546
400
0
50
0
880
500
0
50
0
1374
630
0
50
0
2182
Default values for the relevant registers related to “Analog Out 2” are according to the table below (Default values for flow
max corresponds to 7 m/s).
Size Ø
[mm]
4x430
Level
Conf.
4x431
Unit
Conf.
4x432
Temp Min
[°C]
4x433
Temp max
[°C]
4x434
Flow Min
l/s]
4x436
Flow Max
[l/s]
100
2 (2-10V)
1 (Temperature)
0
50
0
55
125
0
50
0
86
160
0
50
0
141
200
0
50
0
220
250
0
50
0
344
315
0
50
0
546
400
0
50
0
880
500
0
50
0
1374
630
0
50
0
2182
Digital communication settings
Registers 4x001-4x009 are used to configure communica-
tion settings. When initializing contact for the first time the
default settings will be active;
Modbus id: Last three digits in the serial number (also
visible in the display if the product has power)
Baud rate: 19200
Parity:
Odd
Stop bits:
1
After updating any of the communication parameters the
product needs to be power cycled for the changes to take
effect.
PLEASE LOOK IN THE APPENDED MODBUS REGIS-
TER FOR INSTRUCTIONS ON HOW TO CHANGE
REGISTER VALUES. SOME VALUES HAS SCALE
FACTORS AND SOME VALUES OCCUPY TWO REGIS-
TERS!
All available settings are presented in the appendix.
The settings can be changed via the RS485 bus and
can be done from any device and configuration that
can communicate using Modbus, but it can also be
done via the OneLink app. For more register details
see appendix.
Analog communication settings
Analog out settings via Modbus
Analog out is always active but you need to specify what
kind of data you want to read on the two ports Analog Out
1 (AO1) and Analog Out 2 (AO2);
1.
Configure registers 4×401(AO1) and 4×431 (AO2) for the
variables you want to read on the analog out terminals (0
= Flow, 1 = Temperature).
2.
Configure registers 4×400 (AO1) and 4×430 (AO2) for
analog out level configuration ( (0) 0-10V, (1) 10-0V, (2)
2-10V, (3) 10-2V)
3.
Configure registers 4×401–406 (AO1) and 4×431–436
(AO2) with relevant data for max and min levels for
the voltage range selected in step 2. You only need to
configure the max and min values corresponding to the
variable selected in step 1.
Default values for the relevant registers related to “Analog
Out 1” are according to the table below (Default values for
flow max corresponds to 7 m/s).
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Error code
Problem
Comment
Err004
Problems with flow measurement
Might be caused by:
• something blocking the flow sensors
• an electronic fault
• the flow sensors are not connected properly into the display
unit
• the sensor body is flawed
Err05
External sensor low battery
Err06
External sensor not reporting
Err032
Factory data is corrupted
Reset to factory defaults using UltraLink® configuration tool
If digital communication fails, please verify the fol-
lowing before contacting support:
•
Check settings for Baud rate, parity and stop bit and
make sure the master uses the same settings as the
UltraLinks. This can be done with a mobile phone and
the OneLink app.
•
-A and +B are continuously connected between all the
products without any mixups of -A and +B.
•
Bus layout is not allowed to be “star connection”.
•
The cables for power supply are connected identical
on all products and transformers connecting G to G
(24V) and G0 to G0 (GND).
•
The shield is continuous along the bus and grounded
only at the transformer and the last UltraLink on the
bus.
•
There are not more than 30 devices on the bus. (Install
a repeater if you have more than 30 devices.)
•
The total length of the bus is maximum 300 m. (Install
with a repeater if you have more than 300 m bus
cable.)
•
Try to establish communication with a PC using Confi-
guration Tool and a biased RS485-USB converter.
•
Keep the total length of stubbs (such as the premoun-
ted cable) of a buss with 30 devices, no more than 20
meters.
Error codes
If a problem occurs the status light will start to flash and an
error code will be displayed. Listed in the table below are
their problem and possible solution.
If analog signals fails, make sure to doublecheck the
following:
•
Measure voltage on the screw terminal, the voltage
should be the same as that on the BMS controller.
•
If the voltage is not correct, check that the wire is
firmly attach to the terminal of the UltraLink. If it is
not, then the UltraLink might not be able to pick up
the signal.
Problems accessing UltraLink via Bluetooth:
•
The UltraLink must have the Bluetooth logotype on
the lid of the display unit in order to have a Bluetooth
function.
•
To access the UltraLink via Bluetooth, the correct PIN
code must be input before being able to connect.
Verify with administrator that the PIN code is correct
if you cannot connect.
Troubleshooting
We recommend you to in first hand
use our Product Assistant inside the
commissioning app OneLink.
1. Open Lindab OneLink app
2. Go to
3. Click on Product Assistant
4. Choose product
2
3
4
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Power supply
AC/DC
24 (18-32)
V
Cable
Max outer diameter
7
mm
Power consumption
0,4
W
Power consumption
For wiring
0,5
VA
Degree of protection
EN 60529
IP44
Tightness class to the environment
EN 12237
D
Storage temperature range
-30 to +50
°C
Maximum ambient moisture
95
% RH
Connection
RS485 standard or analog
Cable
RS485 standard cable, 2-wire shielded twisted
pair, min. 0,1 mm² (LIYCY cable)
Protocol
Modbus
Output
Flow
Flow
Velocity
Temperature
m³/h
l/s
m/s
°C
Velocity range
For guaranteed measurement uncertainty
0,2 - 15,0
m/s
Measurement uncertainty flow
(assuming correct installation)
Depending on which is the greatest of the per-
centage or the absolute number for the specific
products size.
±5
Dim. 100 = ±1,00
Dim. 125 = ±1,25
Dim. 160 = ±1,60
Dim. 200 = ±2,00
Dim. 250 = ±2,50
Dim. 315 = ±3,15
Dim. 400 = ±4,00
Dim. 500 = ±5,00
Dim. 630 = ±6,00
% or
l/s
l/s
l/s
l/s
l/s
l/s
l/s
l/s
l/s
Temperature range
-10 to +50
°C
Measurement uncertainty temperature
±1
°C
Bluetooth radio
Frequency
2402 — 2480
MHz
Output
-40 to +9
dB
Airflows
Ø [mm]
0,2 m/s
7,0 m/s
15,0 m/s
m³/h
l/s
m³/h
l/s
m³/h
l/s
100
6
2
198
55
425
118
125
9
3
309
86
662
184
160
14
4
507
141
1087
302
200
23
6
792
220
1696
471
250
35
10
1237
344
2650
736
315
56
16
1964
546
4208
1169
400
90
25
3167
880
6786
1885
500
141
39
4948
1374
10603
2945
630
224
62
7855
2182
16833
4676
Technical data
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Address :
Modbus register address (3x indicates Input & 4x indicates Holding)
UltraLink® :
Type of UltraLink® where the register is available (Indicated by “x”)
Name:
Name of register
Description:
Short description of register.
Data type:
Data type for register (16bit contained in one register, 32bit and float in two consecutive registers) .
Unit:
Unit for register value (if any).
Div:
Scale factor for stored value (divide register value with “div” to get correct value).
Default:
Default setting.
Min:
Minimum value allowed for the register.
Max:
Maximum value allowed for the register.
Access:
RO for read only (Input registers) and RW for read and write (Holding registers).
* = the value depends on the dimension of the product.
Appendix A – Modbus register
Address
UltraLink®
Name
Description
Data type
Unit
Div
Default
Min
Max
Access
FTCU
FTMU
INPUT REGISTERS
3x008
X
X
Product Nominal Size
Nominal diameter of duct
16bit
mm
RO
3x013
X
X
Unit Status
Current unit status:
0 = Normal mode;
1 = Locating flow;
2 = Override control;
3 = Error;
4 = Control loop regulating;
5 = Angle sensor calibrating
16bit
RO
Flow info
3x150
X
X
Velocity in m/s
Velocity in m/s
Float
m/s
RO
3x152
X
X
Air flow in m³/h
Air flow in m³/h
Float
m³/h
RO
3x154
X
X
Air flow in l/s
Air flow in l/s
Float
l/s
RO
Temperature info
3x200
X
X
Current temperature in ºC
Temperature in degree celcius.
16bit
ºC
10
RO
Alarms
3x400
X
X
Alarm Register 1
Alarms 1-32 - bitwise:
1 = Motor not working.
2 = Angle sensor not working correctly.
3 = Flow setpoint not reached.
4 = Flow measure problems.
5 = External sensor low battery.
6 = External sensor not responding.
7 - 31 = Reserved for future use.
32 = Factory data is corrupted.
32bit
RO
Other
3×500
X
X
Signal amplification
Current signal amplification
16bit
0
3
20
RO
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
* = the value depends on the dimension of the product.
Address
UltraLink®
Name
Description
Data type
Unit
Div
Default
Min
Max
Access
FTCU
FTMU
Sensor
3x2001
X
X
Sensor Global Set Point
Factor
Multiplication factor for flow set point
16bit
100
100
RO
3x2002
X
X
Sensor Global Factored
Set Point
Holding register FLOW_SET_POINT (314)
multiplied with SENSOR_GLOBAL_SET_
POINT_FACTOR
16bit
l/s
0
RO
3x2007
X
X
Sensor Global State for
Control
Current state of control:
0 = Off
1 = Unoccupird
2 = Normal
3 = Forced
4 = Delayed presence
5 = Temperature increase
6 = Temperature decrease
7 = CO2 decrease
8 = Humidity increase
9 = Humidity decrease
10 = VOC decrease
11 = Particles decrease
50 = Flow slave
100 = Clearing error
101 = Error C1
102 = Error C2
103 = Error C3
104 = Error C4
105 = Error C5
106 = Error C6
3x2012
X
X
Sensor Com Current Pre-
sence Sum
Current Presence based on sum from all
sensors
16bit
0
RO
3x2014
X
X
Sensor Com Presence
State
0 = Disabled
1 = Unoccupied
2 = Normal
3 = Forced
4 = Delayed presence
5 = Error
16bit
RO
3x2021
X
X
Sensor Com Min. Temp
Minimum Temperature
16bit
degC
10
RO
3x2022
X
X
Sensor Com Max. Temp
Maximum Temperature
16bit
degC
10
RO
3x2023
X
X
Sensor Com Average Temp
Average Temperature
16bit
degC
10
RO
3x2025
X
X
Sensor Com Temp State
0 = Disabled,
1 = Within deadband,
2 = Outside deadband,
3 = Error
16bit
RO
3x2034
X
X
Sensor Com Summed
Flow
Summed Flow
16bit
l/s
10
RO
3x2036
X
X
Sensor Com Flow State
0 = Disabled,
1 = Within deadband,
2 = Outside deadband,
3 = Error
16bit
RO
3x2041
X
X
Sensor Com Min. Humidity
Minimum Humidity
16bit
% RH
10
RO
3x2042
X
X
Sensor Com Max. Hu-
midity
Maximum Humidity
16bit
% RH
10
RO
3x2043
X
X
Sensor Com Average
Humidity
Average Humidity
16bit
% RH
10
RO
3x2045
X
X
Sensor Com Humidity
State
0 = Disabled,
1 = Within deadband,
2 = Otside deadband,
3 = Error
16bit
RO
3x2051
X
X
Sensor Com Minimum CO2
Minimum CO2
16bit
ppm
0
RO
3x2052
X
X
Sensor Com Maximum
CO2
Maximum CO2
16bit
ppm
0
RO
3x2053
X
X
Sensor Com Average CO2
Average CO2
16bit
ppm
0
RO
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
* = the value depends on the dimension of the product.
Address
UltraLink®
Name
Description
Data type
Unit
Div
Default
Min
Max
Access
FTCU
FTMU
3x2055
X
X
Sensor Com CO2 State
0 = Disabled,
1 = Within deadband,
2 = Otside deadband,
3 = Error
16bit
RO
3x2103
X
X
Sensor 1 Battery Level
Sensor 1 battery level
16bit
%
0
RO
3x2104
X
X
Sensor 1 RSSI
Sensor 1 RSSI
16bit
%
0
RO
3x2107
X
X
Sensor 1 Current Presence
Sensor 1 Current Presence
16bit
0
RO
3x2108
X
X
Sensor 1 Temperature
Sensor 1 Temperature
16bit
degC
10
0
RO
3x2109
X
X
Sensor 1 Flow
Sensor 1 Flow
16bit
l/s
10
0
RO
3x2110
X
X
Sensor 1 Humidity
Sensor 1 Humidity
16bit
% RH
10
0
RO
3x2111
X
X
Sensor 1 CO2
Sensor 1 CO2
16bit
ppm
0
RO
3x2123
X
X
Sensor 2 Battery Level
Sensor 2 battery level
16bit
%
0
RO
3x2124
X
X
Sensor 2 RSSI
Sensor 2 RSSI
16bit
%
0
RO
3x2127
X
X
Sensor 2 Current Presence
Sensor 2 Current Presence
16bit
0
RO
3x2128
X
X
Sensor 2 Temperature
Sensor 2 Temperature
16bit
degC
10
0
RO
3x2129
X
X
Sensor 2 Flow
Sensor 2 Flow
16bit
l/s
10
0
RO
3x2130
X
X
Sensor 2 Humidity
Sensor 2 Humidity
16bit
% RH
10
0
RO
3x2131
X
X
Sensor 2 CO2
Sensor 2 CO2
16bit
ppm
0
RO
3x2143
X
X
Sensor 3 Battery Level
Sensor 3 battery level
16bit
%
0
RO
3x2144
X
X
Sensor 3 RSSI
Sensor 3 RSSI
16bit
%
0
RO
3x2148
X
X
Sensor 3 Temperature
Sensor 3 Temperature
16bit
degC
10
0
RO
3x2149
X
X
Sensor 3 Flow
Sensor 3 Flow
16bit
l/s
10
0
RO
3x2150
X
X
Sensor 3 Humidity
Sensor 3 Humidity
16bit
% RH
10
0
RO
3x2151
X
X
Sensor 3 CO2
Sensor 3 CO2
16bit
ppm
0
RO
3x2163
X
X
Sensor 4 Battery Level
Sensor 4 battery level
16bit
%
0
RO
3x2164
X
X
Sensor 4 RSSI
Sensor 4 RSSI
16bit
%
0
RO
3x2167
X
X
Sensor 4 Current Presence
Sensor 4 Current Presence
16bit
0
RO
3x2168
X
X
Sensor 4 Temperature
Sensor 4 Temperature
16bit
degC
10
0
RO
3x2169
X
X
Sensor 4 Flow
Sensor 4 Flow
16bit
l/s
10
0
RO
3x2170
X
X
Sensor 4 Humidity
Sensor 4 Humidity
16bit
% RH
10
0
RO
3x2171
X
X
Sensor 4 CO2
Sensor 4 CO2
16bit
ppm
0
RO
3x2183
X
X
Sensor 5 Battery Level
Sensor 5 battery level
16bit
%
0
RO
3x2184
X
X
Sensor 5 RSSI
Sensor 5 RSSI
16bit
%
0
RO
3x2187
X
X
Sensor 5 Current Presence
Sensor 5 Current Presence
16bit
0
RO
3x2188
X
X
Sensor 5 Temperature
Sensor 5 Temperature
16bit
degC
10
0
RO
3x2189
X
X
Sensor 5 Flow
Sensor 5 Flow
16bit
l/s
10
0
RO
3x2190
X
X
Sensor 5 Humidity
Sensor 5 Humidity
16bit
% RH
10
0
RO
3x2191
X
X
Sensor 5 CO2
Sensor 5 CO2
16bit
ppm
0
RO
HOLDING REGISTERS
Communication settings
4x001
X
X
Communication id
Modbus address
16bit
1
239
RW
4x002
X
X
RS485 Baud Rate Conf.
Baudrate:
0 = 9600
1 = 19200
2 = 38400
3 = 76800
16bit
1
0
3
RW
4x003
X
X
RS485 Parity Conf.
Parity:
0 = Odd;
1 = Even;
2 = None
16bit
0
0
2
RW
4x004
X
X
RS485 Stop Bit Conf.
Number of stopbits: 1 or 2.
16bit
1
1
2
RW
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
* = the value depends on the dimension of the product.
Address
UltraLink®
Name
Description
Data type
Unit
Div
Default
Min
Max
Access
FTCU
FTMU
4x005
X
X
RS485 Protocol Conf.
Protocol:
0 = Modbus;
1 = Not used;
2 = Pascal;
16bit
0
0
2
RW
4×006
X
X
Bluetooth Password
Password which must be provided to pair
Bluetooth devices. This password can always
be changed from wired connection. From wi-
reless it can only be changed when connec-
tion is established using current password.
16bit
1111
0000
9999
RW
4×007
X
X
Bluetooth Enable
Enable Bluetooth Communication
0 = Bluetooth turned off;
1 = Bluetooth turned on;
16bit
1
0
2
RW
4x008
X
X
PLA
ID used for Pascal
16bit
1
239
RW
4x009
X
X
ELA
ID used for Pascal
16bit
1
239
RW
4×010
X
X
Bluetooth TX Power Level
Configure TX Power Level dBm. Accepted
values:
-40, -20, -16, -12, -8, -4, 0, 2, 3, 4, 5, 6, 7,
8, 9
16bit
0
-40
9
RW
System configuration
4x072
X
X
Installation as Extract or
Supply
Specifies if device is in supply or extract:
0 = Undefined
1 = Supply
2 = Extract
16bit
0
0
2
RW
4x073
X
X
Installation Zone Number
Specifies in which zone the product is
installed in
16 bit
0
0
65535
RW
4x074
X
X
Installation Floor Number
Specifies on which floor the product is
installed in
16bit
0
0
65535
RW
4x082
X
X
Execute Factory Reset
Factory reset of all parameters. Unit will
restart
0 = Do nothing;
1 = Factory Reset
16bit
0
0
1
RW
4x083
X
X
Execute Reboot
Reboot the unit
0 = Do nothing;
1 = Reboot the unit;
16bit
0
0
1
RW
Analog output
4x400
X
X
Analog Output 1 Level
Conf.
Analog output config:
0 = 0-10 V,
1 = 10-0 V,
2 = 2-10 V,
3 = 10-2 V.
16bit
2
0
3
RW
4x401
X
X
Analog Output 1 Unit Conf.
Show:
0 = Flow;
1 = Temperature;
2 = Angle;
16bit
0
0
2
RW
4x402
X
X
Analog Output 1 Temp.
Min.
Min temperature shown = Min output voltage
(Only relevant when 4x401 is set to 1 )
16bit
ºC
0
-40
50
RW
4x403
X
X
Analog Output 1 Temp.
Max.
Max temperature shown = Max output volta-
ge (Only relevant when 4x401 is set to 1 )
16bit
ºC
50
-40
50
RW
4x404
X
X
Analog Output 1 Flow Min.
Min flow shown = Min output voltage (Only
relevant when 4x401 is set to 0 )
16bit
l/s
0
-4700
4700
RW
4x406
X
X
Analog Output 1 Flow Max.
Max flow shown = Max output voltage (Only
relevant when 4x401 is set to 0 )
16bit
l/s
*
-4700
4700
RW
4x430
X
X
Analog Output 2 Level
Conf.
Analog output config:
0 = 0-10 V,
1 = 10-0 V,
2 = 2-10 V,
3 = 10-2 V.
16bit
2
0
3
RW
4x431
X
X
Analog Output 2 Unit Conf.
Show:
0 = Flow
1 = Temperature
2 = Angle
16bit
2
0
2
RW
Lindab reserves the right to make changes without prior notice
2021-11-02
UltraLink® Monitor
FTMU
lindab | technical information
Address
UltraLink®
Name
Description
Data type
Unit
Div
Default
Min
Max
Access
FTCU
FTMU
4x432
X
X
Analog Output 2 Temp.
Min.
Min temperature shown = Min output voltage
(Only relevat when 4x431 is set to 1 )
16bit
ºC
0
-40
50
RW
4x433
X
X
Analog Output 2 Temp.
Max.
Max temperature shown = Max output volta-
ge (Only relevant when 4x431 is set to 1 )
16bit
ºC
50
-40
50
RW
4x434
X
X
Analog Output 2 Flow Min.
Min flow shown = Min output voltage (Only
relevant when 4x431 is set to 0 )
16bit
l/s
0
-4700
4700
RW
4x436
X
X
Analog Output 2 Flow Max.
Max flow shown = Max output voltage (Only
relevant when 4x431 is set to 0 )
16bit
l/s
*
-4700
4700
RW
Sensor
4x2100
X
X
Sensor Presence Enable
Control
0 = Disable
1 = Enable
16bit
0
0
1
RW
4x2101
X
X
Sensor Presence Trigger
Time
Temporary trigger time for presence
16bit
min
1
0
60
RW
4x2102
X
X
Sensor Presence Trigger
Factor
Factor related to toggle 0 -> 1
16bit
%
100
150
49
501
RW
4x2103
X
X
Sensor Unoccupied Mul-
tiplication Factor
Multiplication factor for Unoccupied
16bit
%
100
50
-1
101
RW
4x2110
X
X
Sensor Temperature Ena-
ble Control
0 = Disable
1 = max
2 = min
3 = avg
16bit
0
0
3
RW
4x2111
X
X
Sensor Temperature
Baseline
Baseline for temperature
16bit
C
22
-50
50
RW
4x2112
X
X
Sensor Temperature
Deviation
Allowed deviation before full factor effect
16bit
C
2
0
50
RW
4x2113
X
X
Sensor Temperature Dead
Band
Dead band for sensor type Temperature
16bit
%
100
50
-1
101
RW
4x2114
X
X
Sensor Temperature Mul-
tiplication Factor
Multiplication factor for Temperature
16bit
%
100
150
49
501
RW
4x2120
X
X
Sensor Flow Enable
Control
0 = Disable
1 = Sum
16bit
0
0
1
RW
4x2121
X
X
Sensor Flow Dead Band
Dead band for sensor type Flow
16bit
%
100
2
0
100
RW
4x2122
X
X
Sensor Flow Multiplication
Factor
Multiplication factor for Flow
16bit
%
100
100
0
500
RW
4x2130
X
X
Sensor Humidity Enable
Control
0 = Disable
1 = max
2 = min
3 =avg
16bit
0
0
3
RW
4x2131
X
X
Sensor Humidity Baseline
Baseline for humidity
16bit
%
50
0
100
RW
4x2132
X
X
Sensor Humidity Deviation
Allowed deviation before full factor effect
16bit
%
20
0
100
RW
4x2133
X
X
Sensor Humidity Dead
Band
Dead band for sensor type Humidity
16bit
%
100
50
-1
101
RW
4x2134
X
X
Sensor Humidity Multipli-
cation Factor
Multiplication factor for Humidity
16bit
%
100
150
49
501
RW
4x2135
X
X
Sensor Humidity Supplied
Estimated value of supply air humidity
16bit
%
50
0
100
RW
4x2140
X
X
Sensor CO2 Enable Control
0 = Disable
1 = max
2 = min
3 =avg
16bit
0
0
3
RW
4x2141
X
X
Sensor CO2 Baseline
Baseline for CO2
16bit
ppm
600
400
2000
RW
4x2142
X
X
Sensor CO2 Deviation
Allowed deviation before full factor effect
16bit
ppm
400
0
1000
RW
4x2143
X
X
Sensor CO2 Dead Band
Dead band for sensor type CO2
16bit
%
100
50
-1
101
RW
4x2144
X
X
Sensor CO2 Multiplication
Factor
Multiplication factor for CO2
16bit
%
100
150
49
501
RW
4x2145
X
X
Sensor CO2 Supplied
Estimated value of supply air CO2
16bit
ppm
400
300
2000
RW
* = the value depends on the dimension of the product.
Most of us spend the majority of our time indoors.
Indoor climate is crucial to how we feel, how productive
we are and if we stay healthy.
We at Lindab have therefore made it our most important
objective to contribute to an indoor climate that improves