Made in Everson, WA USA rev-2014-08-05 QuickGuide DU200 DucTester Flex Duct DM-2 gauge (Batteries included) Umbilical Flange Low-Range Ring Mid-Range Ring DucTester Grill Mask QuickGuides Battery Charger Tubing Accessory Kit Unpack, connect DM-2 gauge Check boxes for each step. □ Remove everything from the case. □ Install 4 NiMH AA batteries.* □ Plug in the battery charger. □ Press [On], then [Exit], to display the battery indicator. □ Charge for 18 hrs. □ Connect yellow, green and blue tube to gauge. □ Slide gauge into the clear sleeve and velcro Umbilical to case. Gauge remains connected like this for all tests. * If changing to non-rechargeable batteries, disable charging in [Setup] menu. For steps see: Quick Guide DM-2 mark II Digital Gauge, page 1 www.retrotec.com Sales & Support: (855)738-7683 International: (604)732-0142

Step 1: Prepare ducts and house

□ Seal all supply and return grills/registers, including any exterior air inlets, with Grill Mask or tape. □ Open all interior doors leading to rooms containing a supply or return register, and open an exterior door or window. □ Shut off all HVAC (exhaust fans, dryers, A/C, furnaces). Page 2 of 8 Step 2: Connect to ducts □ Turn off air-handler and remove all filters. □ Tape Flange to main return or air handler cabinet using masking tape. □ Attach Flex Duct to Flange. □ Install Mid-Range Ring to start, as most systems can be tested on this Range Configuration. □ Press [Range Config] to select range on gauge to match fan, whenever Range Ring is changed. □ Press [Auto Zero] until “On” appears - to keep the gauge zeroed and ready to measure. □ Press [Time Avg] until “4s” appears. □ Press [Device] until “Retrotec DU200” appears. If desired Device does not appear, see: QuickGuide DM-2 mark II Digital Gauge, Add/Remove Devices section □ Press [Range Config] until “Mid” appears. □ Press [Mode] to cycle through results. Select based on “Get the results you need” on page 4. If you can’t find the required results, see: QuickGuide DM-2 mark II Digital Gauge Prepare the DM-2 gauge Next, prepare the ducts, house, and fan following Steps 1 through 3. Mid Low Open Remove Range Rings for leakier ducts, add Rings for tighter ducts.

□ Press [On] twice to get to main

screen. □ Adjust fan speed knob clockwise until “PrA” reaches test pressure. □ If not possible, go to Step 5 for advice on changing setup. □ Connect Speed Control Cable to fan. □ For a test pressure of 25 Pa *, press [Set Pressure] [25] [Enter]. * 50 Pa for Northwest ENERGY STAR. □ Press [@ Pressure] to display what the result would be at exactly 25 Pa. Page 3 of 8 Step 3: Connect DM-2 gauge & fan □ Insert blue tube into the supply register closest to the air handler. □ Read results directly from the gauge. Speed Control Cable □ Connect power cord. □ Switch to on: “ l “. Green light indicates that power is connected. □ Connect yellow and green tubes to matching color ports on fan. Ethernet style Speed Control Cable will disable the knob. It is connected later in Step 4. If Pressurizing, see tubing setup on page 7. □ Connect Flex Duct to fan inlet for depressurization. Ready to conduct the test by depressurizing the ducts: Depressurization is easiest and permitted in all States except CA & WA where it can still be used to evaluate, but not for a final result. Step 2: Connect to ducts cont’d Total Duct Leakage Test: Depressurize Step 4: Conduct test To pressurize, connect the Flex Duct to fan exhaust. All other connections remain the same pressurize Inlet airflow Exhaust Inlet with Range Rings inside Flex Duct Exhaust depressurize Solid green Status light indicates DM-2 is ready to control speed. airflow Depressurizing works best because the fan pulls the Grill Mask tight on the registers during the test.

Flow at the induced pressure is the

simplest result. Mode = “Flow” Units = “CFM” Flow per ft2 (sq ft) is required in some states, such as WA. Mode = “Flow/Area” Units = “CFM/ft2” (enter a value for Area) Flow per 100 ft2 is required for the following states: Mode = “Flow/Area” Units = “CFM/100 ft2” (enter a value for Area) Flow reads “TOO LOW” or “----” at test pressure? If the test pressure has been reached, but “TOO LOW” or “----” appears, the fan is running too slowly to measure flow. □ Add the next Low-Range Ring. □ Change [Range Config] on the DM-2 to match. □ Re-adjust speed. Cannot achieve test pressure at full speed? If fan reaches 100% speed before reaching the target pressure: □ Remove a Range Ring and try again. □ Change [Range Config] on the DM-2 to match. □ Check seals on all registers. Look for disconnected ducts or ducts open to outdoors. □ Press [@ Pressure] to get the gauge to calculate what the flow would be at exactly 25 Pa. Page 4 of 8 Get the results you need □ Press [Mode] until required results appear Show results as leakage area Equivalent Leakage Area (EqLA) describes the leakage area in terms of one large hole in a flat surface. □ Press [Mode] until “EqLA” appears. “PrA” displays the duct pressure and “EqLA” shows the combined size of all the holes in the ducts. Step 5: Desired results not achieved? 620 CFM is the flow rate that would occur at 25 Pa, even though only 22 Pa was achieved. CT DC DE GA ID IL IA ME MD MA NH NJ NY NC PA RI TX VT Use “Jog” to activate arrow keys [▲] [▼] then adjust target speed or pressure. Use “Hold” to freeze results display and hold fan speed. □ Press [Jog/Hold] until “Hold” appears in top center of display. □ Press [Jog/Hold] again to cancel “Hold”. □ Press [Jog/Hold] until “Jog” appears. □ The [▲] [▼] keys now adjust the speed just like a TV remote. With [Set Speed] the % speed changes. With [Set Pressure] the pressure changes. Hold display and Jog speed Leakage area is not a required result, but is a nice way to visualize the size of the hole in the ducts. □ Press [Enter] numbers [Enter] to input the floor area if CFM/ft2 or CFM/100 ft2 is used. *Floor area of 2000 square feet was entered in the above examples. [Enter] [2000] [Enter] “Jog” is only available when [Set Pressure] or [Set Speed] have a value entered. The display will be frozen with the current values. □ Press [Setup] for menu to change result units □ Press [▼] to find “Mode Setup”, then [Enter] □ Press [▼] until the Mode you want is highlighted □ Press [Enter] to change displayed result units □ Press [Exit] twice to return to main menu

Page 5 of 8

Free Training Videos We’re here to help! Check out Retrotec’s YouTube page, with all the videos you’ll need to help you setup, run, or trouble- shoot your equipment! ● Sign up for our monthly gauge setup webinars. ● Bookmark our blog! Everything from new testing techniques to industry updates. ● Our tech support is always ready to field phone-in troubleshoot and testing questions. Give us a call! ● Access all Retrotec training videos here: youtube.com/RetrotecTraining Duct Testing Watch universal training videos including: ● Set up ● Procedures ● Troubleshooting Leakage: Blower Door Watch video demonstrations including: ● Blower Door set up ● Common leak locations ● Software ● House preparation Pressure: Gauge Training Get help to successfully set up and use digital pressure gauges. ● Gauge set up ● Discover modes & devices ● Perform calibration checks retrotec.com/residential/SupportCenter/SetupWebinars.aspx retrotec.com/blog.aspx 1-855-738-7683 Retrotec’s playlist includes:

Page 6 of 8

To measure the air leakage from the duct system to outdoors requires both a DucTester and a Blower Door system. The Blower Door depressurizes the house and the DucTester depressurizes the ducts so leakage from the duct system back into the conditioned space of the home is neutralized. Method #1: Method #2: □ Connect the red T-connected tubes to red ports per diagram. □ Press [Set Pressure] [25] [Enter] on DucTester gauge then on Blower Door gauge. □ Press [@ Pressure] on DucTester gauge to display the results “@25Pa”. □ When “25 Pa” +/– 1 is achieved on both gauges, record duct leakage to outdoors from the DucTester gauge. □ Connect tubes to gauges per diagram. □ With DucTester off, set the Blower Door gauge to -25 Pa by pressing [Set Pressure] [25] [Enter]. □ Press [@ Pressure] on DucTester to remove “@25Pa” from the display. □ Set the DucTester to “0 Pa” by pressing [Set Pressure] [0] [Enter]. When “0 Pa” +/– 1 is achieved, record duct leakage to outdoors from the DucTester gauge. Method 1 uses the DucTester set up the same way as for the Total Duct Leakage test, and allows use of [@ Pressure] to increase accuracy. Results are easier to visualize since both the duct and house pressure can be seen. Method 2 does not require connecting a red tube to the DucTester gauge but results in large errors if [@ Pressure] is turned on. Set DucTester gauge to 0 Pa, Blower Door gauge to -25 Pa ** Set both gauges to -25 Pa ** Blower Door gauge DucTester gauge Optional Test Duct Leakage to Outdoors: Depressurize ** If 50 Pa test pressure required, use 50 in all instructions. Method# 1

□ Connect Flex Duct to fan exhaust.

□ Check that tubing is connected the same as for depressurize test (step 3). □ Conduct test (step 4). Duct Leakage to Outdoors: Pressurize Follow depressurize test method (page 6) except both fan directions are reversed. Page 7 of 8 Total Duct Leakage: Pressurize Pressurizing can blow the Grill Mask off the registers! Options pressurize Inlet airflow Exhaust □ Pass the Flange through the 10 inch hole in the Flow Hood and tape it inside. □ Attach the Flex Duct. □ Secure the Flow Hood over the register To measure Duct leakage: □ Connect the Flex Duct to the fan and test as usual. To measure HVAC System Flow: □ For measuring supply flows, attach the Flex Duct to the inlet (suction) side of the fan. □ For measuring return flows, attach the Flex Duct to the exhaust (discharge) side of the fan. □ Connect the umbilical to the DucTester. □ Attach the blue tube to the Flow Hood and gauge. □ Press [@ Pressure] until “@” is removed from display □ Press [Mode] to select “Flow” When a definite pressure appears on “PrA”: □ Adjust the speed until “PrA” reads a pressure of 0 Pa. Or □ Press [Set Pressure] [0] to have the DucTester automatically achieve a 0 pressure. □ Read the HVAC system flow result directly from the gauge Using the optional Flow Hood Connect it quickly to ceiling level returns to measure duct leakage or use it with your DucTester as a Pow- ered Flow Hood to accurately measure HVAC system flow rates. Flow Hood blue tube

Tubing Accessory Kit

35 ft (10 m) of blue, red, yellow and green 1/4 inch (12mm) outside diameter tubing. Static Pressure Probe, 4 inch (100 mm) x 1/8 inch (6 mm) outside diameter metal probe, 2 T and 2 male-to-male con- nectors. Red L for duct leakage to outdoors test. Part #: TU119 Flow Hood 24 x 24 inches (61 x 61 cm) Part #: PP105 Page 8 of 8 Optional accessories 12.5ft (3.8m) Flex Duct for DucTester Part #: DU161 Flange to connect Flex Duct to register Part #: DU157 Verification Plate Part #: DU159 Deluxe Cordura Toolbag with Shoulder Strap Part #: TL118 Grill Mask 12in x 216ft, 12in perfs, Hi-stick White, Single Roll Part #: GR116 Part #: GR117 (for case of 3) Umbilical for DucTester fans, 7ft (2 m) Part #: DM240 Optional DU159 Verification Plate shown. □ Tape the optional flow Verification Plate to the Flange and attach the red tube. □ Attach the Flex Duct to the exhaust side of the fan to pressurize the Flex Duct. □ Stretch the Flex Duct to it’s full length. □ Set the DM-2 to measure “Flow” in “CFM @25 Pa”. □ Adjust the speed until “PrA” reads close to 25 Pa. □ Read the Verification Plate to determine the acceptable range for flow. Typically, 100 to 110 CFM is a pass. Check gauge operation and check for blocked, leaking or pinched tubes weekly, and anytime results are in question. To perform the gauge check, you will need the gauge and Umbilical. □ Press [Exit] [Time Average] until “4s” appears. □ Press [Mode] repeatedly to display “PrB”. □ Connect the yellow tube between the red and yellow ports. □ Repeat between different ports with each of the tubes you use for testing. Field check gauge weekly If readings on “PrA” and “PrB” are within 2% and don’t drop rapidly, the tube is not blocked or leaking and the gauge is correct. Checking your gauge and tubes regularly will eliminate a common source of error in readings. Mid-Range Ring & Low-Range Ring (Mid) Part #: DU154 (Low) Part #: DU155 Check the DucTester system monthly with a known setup―if flow is outside the acceptable range then system needs full calibration. Field check system monthly