Key Pages of Document

Sub channel 1

Sub channel 2 Factory setting Change to Description Page ARR 1 3 System 45 ROSA 0000 6 ROSA number 66 LOAD1 > Loading 1 DT1O 6.0 K [12.0 °Ra] Switch-on temperature difference 1 46 DT1F 4.0 K [8.0 °Ra] Switch-off temperature difference 1 46 DT1S 10.0 K [20.0 °Ra] Set temperature difference 1 46 RIS1 2 K [4 °Ra] Rise 1 46 S1MAX 60 °C [140 °F] Tank maximum limitation 1 46 SMXS1 2 Sensor tank max 1 46 LOAD2 > Loading 2 DT2O 6.0 K [12.0 °Ra] Switch-on temperature difference 2 46 DT2F 4.0 K [8.0 °Ra] Switch-off temperature difference 2 46 DT2S ...

Temperature tank 1 base

S3 TST1T Temperature tank 1 top S4 TST2B Temperature tank 2 base S5 TST2T Temperature tank 2 top V40 optional: flowmeter Relay Description R1 Solar pump R2 Heat exchange pump R3 3-port valve tank 1/2 R4 optional: Thermal disinfection Parallel relay Heat dump The controller compares the temperature at sensor S1 to the temperatures at sensors S2 and S4. If the measured temperature differences are higher than the adjusted switch-on temperature differences, the pump (R1) will be activated a ...

If a malfunction occurs, a message will appear on the display of the controller.

The display is permanently off. Press button ➄. Display illuminated? no yes Controller has been in standby, everything o.k. Check the supply line and recon- nect it. The fuse of the controller could be blown. The fuse holder (which holds the spare fuse) becomes ac- cessible when the cover is removed. The fuse can then be replaced. Check the power supply of the controller. Is it disconnected? no yes Disconnected temperature sensors can be checked with an ohmmeter. Please check if the resis ...

2-tank system with valve logic, 1 pump, 3 sensors and 3-port valve

The controller calculates the temperature difference between collector sensor S1 and tank sensor S2. If the difference is larger than or identical to the adjusted switch-on temperature difference, the pump (R1) will be switched on and the tank will be loaded until the switch-off temperature difference or the maximum tank temperature is reached. Sensors S1 Temperature collector 1 / GND S2 Temperature tank base 2 / GND S3 Free 3 / GND S4 Free 4 / GND S5 Free 5 / GND Relay R1 Solar pump R1 / N / PE R2 F ...

If a malfunction occurs, a message will appear on the display of the controller.

The display is permanently off. Press button ➄. Display illuminated? no yes Controller has been in standby, everything o.k. Check the supply line and recon- nect it. The fuse of the controller could be blown. The fuse holder (which holds the spare fuse) becomes ac- cessible when the cover is removed. The fuse can then be replaced. Check the power supply of the controller. Is it disconnected? no yes Disconnected temperature sensors can be checked with an ohmmeter. Please check if the resis ...

Lower tank sensor

Sensor Sensor Sensor Valve Tank Tank heat exchanger Tank 3 Tank 2 or backup heating Upper tank sensor System screen in the system monitoring display The system selected is indicated in the system monitoring display. It consists of several system component symbols which are – depending on the current status of the system – either flashing, permanently shown or “hidden”. Collectors with collector sensor 3-port valves Only the flow direction or current switching position are indicated. Tanks 1, 2 and 3 with he ...

Î Adjust the desired menu language.

3. Time: Î Adjust the clock time. First of all adjust the hours, then the minutes. 2. Unit: Î Adjust the desired unit. 4. Date: Î Adjust the date. First of all adjust the year, then the month and then the day. 5. System: Î Adjust the desired system. Note If the desired system layout has been selected in the ARR channel, the ROSA channel can be skipped. 6. ROSA: Î Enter the 4-digit number given by the RESOL Online Service Assistant. 5 Initial commissioning When the hydronic system is fi lled and ready for operation, connect the cont ...

2-tank system with valve logic, 1 pump, 3 sensors and 3-port valve

The controller calculates the temperature difference between collector sensor S1 and tank sensor S2. If the difference is larger than or identical to the adjusted switch-on temperature difference, the pump (R1) will be switched on and the tank will be loaded until the switch-off temperature difference or the maximum tank temperature is reached. Sensors S1 Temperature collector 1 / GND S2 Temperature tank base 2 / GND S3 Free 3 / GND S4 Free 4 / GND S5 Free 5 / GND Relay R1 Solar pump R1 / N / PE R2 F ...

Resol DeltaSol BX L user guide recommended for: WMZ, DeltaSol SLT, VA32, DeltaSol BX, DeltaSol MX.

⚠️ Download Safety

The Controller Manual  (80 pages) is completely safe to download (last scan date: 28/01/2026).

Related PDF Instructions for Resol DeltaSol BX L:

Controller Equipment: Frequently Requested

Have some Questions about Resol DeltaSol BX L Device?

Get valuable and actionable advices from other Resol DeltaSol BX L device users. Describe your problem or question, regarding the using of DeltaSol BX L, in as much detail as possible, and other users will be able to answer you.