M-system R3-AR4 Instruction Manual
Read Online
Read the M-system R3-AR4 Instruction Manual online using the built-in PDF viewer.
Text of the manual
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8433 Rev.3 P. 1 / 4
INSTRUCTION MANUAL
RTD INPUT ALARM MODULE
(4 points, isolated)
MODEL
R3-AR4
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
RTD input alarm module ....................................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
■ HOT SWAPPABLE MODULES
• Replacing the module does not affect other modules on
the same base. Thus, the module can be replaced while
the power is ON. However, replacing multiple modules
at once may greatly change live voltage levels. We highly
recommend to replace them one by one.
■ GENERAL PRECAUTIONS
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
Use the Installation Base (model: R3-BSx).
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8433 Rev.3 P. 2 / 4
COMPONENT IDENTIFICATION
1
11
12
13
14
15
16
17
18
19
20
2
3
4
5
6
7
8
9
10
ON
8
7
6
5
4
3
2
1
SW1
SW2
ON
8
7
6
5
4
3
2
1
SW3
ON
4
3
2
1
■ FRONT VIEW
■ SIDE VIEW
ERR LED
RUN LED
Conv.
Rate
Temp.
Unit
Input 2 (SW1)
or
Input 4 (SW2)
RTD
Input 1 (SW1)
or
Input 3 (SW2)
Burnout
Functions
■ STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with burnout;
Green in normal operating conditions.
■ SIDE DIP SW
(*) Factory setting
• RTD Type: SW1, SW2
INPUT 1 (SW1)
INPUT 2 (SW1)
RTD
INPUT 3 (SW2)
INPUT 4 (SW2)
1
2
3
4
5
6
7
8
OFF OFF OFF OFF OFF OFF OFF OFF Pt 100 (*)
(JIS ’97, IEC)
ON OFF OFF OFF ON OFF OFF OFF Pt 100 (JIS ’89)
OFF ON OFF OFF OFF ON OFF OFF JPt 100 (JIS ’89)
ON
ON OFF OFF ON
ON OFF OFF Pt 50 Ω (JIS ’81)
OFF OFF ON OFF OFF OFF ON OFF Ni 100
ON OFF ON OFF ON OFF ON OFF Cu 10 @ 25°C
OFF ON
ON OFF OFF ON
ON OFF Pt 1000
ON
ON
ON OFF ON
ON
ON OFF Ni 508.4 Ω
OFF OFF OFF ON OFF OFF OFF ON
Cu 50
• Burnout: SW3-1
SW3-1
BURNOUT
OFF
Upscale (*)
ON
Downscale
• Temperature Unit: SW3-2, 3-3
SW3-2
SW3-3
TEMP. UNIT
OFF
OFF
°C (*)
ON
OFF
°F
OFF
ON
(Absolute Temp)
• Conversion Rate: SW3-4
SW3-4
CONV. RATE
OFF
250 msec. (*)
ON
1 sec.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8433 Rev.3 P. 3 / 4
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■ EXTERNAL DIMENSIONS unit: mm (inch)
1
11
12
13
14
15
16
17
18
19
20
2
3
4
5
6
7
8
9
10
130 (5.12)
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
TERMINAL
COVER
20–M3
SCREW
6.2
(.24)
■ CONNECTION DIAGRAM
1
2
INPUT 1
3
4
INPUT 2
6
7
INPUT 3
8
9
INPUT 4
100Ω
11
13
16
18
• Unused Input Channels
Close across the unused input terminals with a resistor as
shown below and set the DIP switch for Pt 100 input.
Unused channels left open are equal to the burnout,
which turns the red ERR LED on and sets a burnout flag at
the PLC or the host device.
Connecting the resistor means approx. 0°C. An alarm
setpoint must be set to a value that does not trip an
unwanted alarm.
Unused channels can be specified and set so on the PC
Configurator Software (model: R3CON) without needing to
connect resistors at the field terminals.
A
B
B
RTD
1
2
11
3
4
13
6
7
16
8
9
18
*For dual redundant communication.
INPUT 1
A
B
B
A
B
B
A
B
B
RTD
INPUT 2
RTD
INPUT 3
RTD
INPUT 4
BUS CONNECTOR
INTERNAL POWER
INTERNAL BUS A
INTERNAL BUS B*
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-8433 Rev.3 P. 4 / 4
ALARM SETTING
The following parameters are programmable using the PC
Configurator Software (model: R3CON).
■ ALARM TRIP POINT
(-200.0 to +850.0°C or -328 to +1562°F; factory set to A1:
400.0°C, A2: 300.0°C, A3: 200.0°C, A4: 100.0°C)
Four alarm setpoints are selectable per each input.
■ ALARM TYPE (High or Low; factory set to A1: High, A2:
High, A3: Low, A4: Low)
High or Low alarm is selectable for each alarm trip point.
High alarm: An alarm is set when the input signal goes
above the setpoint.
Low alarm: An alarm is set when the input signal goes be-
low the setpoint.
■ DEADBAND (HYSTERESIS)
(0.00 to 100.0°C or 0 to 1800°F; factory set to 10.0°C or 100°F)
Deadband (deviation between the points where the alarm is
set and reset) is selectable for each alarm trip point.
■ POWER ON DELAY TIME
(0.0 to 99.0 seconds; factory set to 5.0)
The alarm output start functioning in the preset time after
the power has been turned on.
This setting is common to all four points.
■ ALARM ON DELAY TIME
(0.0 to 99.0 seconds; factory set to 1.0)
The alarm output is set when the preset time elapses after
the input has entered in the alarm range.
This setting is common to all four points.
■ ALARM HOLD TIME
(0.0 to 99.0 seconds; factory set to 1.0)
The alarm output is held for the preset time even if it is
reset in shorter time.
This setting is common to all four points.
OUTPUT DATA DESCRIPTIONS
Four alarm setpoints are selectable per each input. One
(1) word (16 bit) data is transmitted to the PLC or the host
device via the R3 network module.
0
15
Alarm 1
Alarm 2
Input 1
Alarm 3
Alarm 4
Alarm 1
Alarm 2
Input 2
Alarm 3
Alarm 4
Alarm 1
Alarm 2
Input 3
Alarm 3
Alarm 4
Alarm 1
Alarm 2
Input 4
Alarm 3
Alarm 4
WIRING INSTRUCTIONS
■ SCREW TERMINAL
Torque: 0.5 N·m
■ SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Applicable wire size: 0.3 – 0.75 mm2
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd., Nichifu Co., Ltd.
12max
6max
3max
4min
3.2 dia.
(mm)