FUZRR FR3010 Operation & User’s Manual
Read Online
Read the FUZRR FR3010 Operation & User’s Manual online using the built-in PDF viewer.
Text of the manual
I. Safety Precautions and Procedures................................................. 1
II. Introduction ......................................................................................... 3
III.Measuring Range and Accuracy ................................................... 4
IV.Technical Specifications ................................................................. 5
V.Tester Structure ................................................................................ 7
VI.Measuring Principle ........................................................................ 8
VII. Operation Methods ......................................................................... 9
1.Switch On/Off ............................................................................. 9
2.Battery Voltage Check ................................................................. 9
3. Ground voltage measurement ..................................................... 10
4.Wire Resistance Verification ..................................................... 10
7.Two-wire easy Test Grounding Resistance ............................... 14
8.Soil Resistivity Test ................................................................... 15
9.Backlight Control .................................................................... 177
10.Alarm Settings ..................................................................... 177
11.Data Lock/Storage ................................................................. 177
12.Data Review/Deletion ........................................................... 177
VIII. Battery Replacement ................................................................. 188
IX.Accessories ................................................................................. 188
I. Safety Rules and Precautions
Thanks for your purchase of Ground Resistance Soil
Resistivity Tester of our company. Before you use the instrument
for the first time, in order to avoid possible electric shock or
personal injury, please be sure to: read and strictly observe the
safety rules and precautions listed in this manual.
Under any circumstance, it shall pay special attention on
safety in use of this tester
u The tester is conforming to IEC61010 on design, production
and test.
u Under any circumstance, it shall pay special attention on
safety in use of this tester.
u Please don’t use high-frequency signal generators like mobile
phone and etc. to avoid error during measuring.
u Pay attention to words and symbols stick on the Tester.
u It shall make sure that tester and accessories are in good
condition before use; it can be used only when there is no
damaged, naked or broken part in testing wires or insulation
layer.
u During measurement, it is forbidden to touch bare conductors
and circuit under measurement.
u Confirm that connector plug of lead has been inserted in the
tester interface closely.
u Please don’t impose over 600V A.C. or D.C. voltage on the
part between testing end and interface. Otherwise, it may have
damage on the tester.
u Please don’t measure in an inflammable place. The flame
sparkle maybe cause explosion.
u During usage of tester, please stop using it when exposed
metal is caused by broken enclosure or testing wires.
u Please don’t keep or store the tester in the spot with
high-temperature and moisture, or condensation, and under
direct daylight radiation for a long time.
u For replacing battery, please confirm testing wire has moved
apart the meter, and FUNCTION SWITCH rotary switch is in
“OFF” position.
u Please put the used batteries in appointed collection place.
u When replacing the battery with the meter, make sure that the
test line has been removed from the meter and the meter is
turned off.
u When the meter displays battery low voltage symbol“ ”,
and need to replace the battery in time.
u Pay attention to measuring range and usage environment
stipulated for the Tester.
u This measuring device is only to be used, disassembled,
adjusted and repaired by qualified personnel with authorization.
u When it may cause hazard by continuous use for the reason
of the Tester itself, it shall immediately stop using it and deposit it
at once, leaving it for disposal by authorized agency.
u For risk of danger icon in manual
, users must perform
safety operations strictly in compliance with the manual content.
II. Introduction
Ground Resistance • Soil Resistivity Tester also known
as Four-Wire Ground Tester, Precision Ground Resistance
Tester, etc., is a commonly used meter for measuring grounding
resistance. It adopts a large LCD gray-white screen backlight
display and microprocessor technology to meet the requirements
of two-wire, three-wire and four-wire test resistance and soil
resistivity test. Suitable for telecommunications, electricity,
meteorology, computer rooms, oil fields, power distribution
lines, iron tower transmission lines, gas stations, factory
grounding networks, lightning rods and so on. Instrument
testing is precise, fast, simple, stable and reliable.
The Ground Resistance • Soil Resistivity Tester is
controlled by the microprocessor and can automatically detect the
connection status of each interface and the interference voltage
and interference frequency of the ground network, and has the
function of testing the auxiliary grounding resistance value. At the
same time store 500 sets of data, resistance measurement
range: 0.01Ω ~ 30.00kΩ, grounding voltage range: 0.01 ~
600.0V
III.Measuring Range and Accuracy
Remark:1. Reference conditions: Accuracy when Rh Rs < 100Ω.
Operating conditions: Rh max = 3kΩ + 100R <50kΩ; Rs max =
3kΩ + 100R <50kΩ
Category
Measurement Range
Intrinsic Error
Resolution
Earth
Resistance
(R)
0.00Ω-30.00Ω
±2%rdg±5dgt
0.01Ω
30.0Ω-300.0Ω
±2%rdg±3dgt
0.1Ω
300Ω-3000Ω
±2%rdg±3dgt
1Ω
3.00kΩ-30.00kΩ
±4%rdg±3dgt
10Ω
Soil Resistivity
(ρ)
0.00Ωm-99.99Ωm
ρ=2πaR
(remark 2)
0.01Ωm
100.0Ωm-999.9Ωm
0.1Ωm
1000Ωm-9999Ωm
1Ωm
10.00kΩm-99.99kΩm
10Ωm
100.0kΩm-999.9kΩm
100Ωm
1000kΩm-9999kΩm
1kΩm
Earth Voltage
AC 0.00-600V
±2%rdg±3dgt
0.01V
2. Depending on the measurement accuracy of R, π = 3.14, a: 1 m
~ 100m;
IV.Technical Specifications
Function
Two, three, four-wire measure grounding resistance,
soil resistivity; Ground voltage, AC voltage
Ambient
temperature
and humidity
23℃±5℃,below 75%rh
Power Supply
DC 9V 6-section LR14 Dry Battery Standby for more
than 100 hours
Interference
current
<2A (should be avoided)
Measure R
electrode
spacing
a>5d
Measured
electrode
spacing
a>20h
Auxiliary Earth
Resistance
Reference Conditions <100Ω, Operating Conditions
<5kΩ
Range
Grounding resistance: 0.00Ω to 30.00kΩ
Soil resistivity: 0.00Ωm~9999kΩm
Ground voltage: 0.00V to 600.0V
Measurement
Method
Precision 4-wire, 3-wire measurement, simple 2-wire
grounding resistance
Measuring
Methods
Grounding resistance: rated current change method
Soil resistivity: four-pole method
Ground voltage: average rectification (S-FR interface)
Test Frequency
128Hz
Short-circuit
Test Current
AC >20mA (sine wave)
Open Circuit
Test Voltage
AC 28V max
Electrode
Spacing Range can be set from 1m to 100m
Change Gear
Grounding resistance: fully automatic shifting from
0.00Ω to 30.00kΩ
Soil resistivity: 0.00 Ω m ~ 9000k Ω m automatic
Gray screen backlight, suitable for dim places
Display Mode
4-digital super-large LCD display, blue screen
backlight
Measuring
Indicator
During measurement, LED flash
LCD Frame
Dimension
111mm×65mm
LCD display
area
108mm×65mm
Dimension
L×W×H: 240mm×188mm×85mm
Standard Test
Wire
4 wires: each for red 20m, black 20m, yellow 10m,
and green 10m
Simple Test
Wire
2 wires: each for yellow 1.5m and green 1.5m
Auxiliary
Earthing Rod
4 PCS
Measuring Rate
Voltage to ground: about 3 times/second
Earth resistance, soil resistivity: about 7 seconds/time
Circuit Voltage
below AC 600V
Data Storage
500 sets, “MEM” icon storage indicator, flash display
“FULL” icon to indicate storage is full
Data Read
Data read function: “MR” icon display
Overflow
Display
Exceeding measuring range overflow function: “OL”
icon display
Alarm Function
Alarm when the measured value exceeds the alarm
setting value
Battery Voltage
Low battery voltage symbol display
Power
Consumption
Standby: About 40mA (backlight off)
Turn on and backlight on: about 43mA
Measurement: about 75mA (backlight off)
Weight
Tester:1230g (including battery)
Testing Wires:1300g
Auxiliary earthing rod:720g(4 PCS)
Working
Temperature &
Humidity
-10℃~40℃;below 80%rh
Measuring earth ground resistance: between each
interfaces of H-E、S-FR, AC 280V/3 seconds
Insulation
Resistance
Over 20MΩ(between circuit and enclosure it is 500V)
Withstanding
Voltage
AC 3700V/rms (Between circuit and enclosure)
Electromagnetic
Features
IEC61326(EMC)
Protection Type
IEC61010-1 (CAT III 300V, CAT IV 150V, Pollution
Degree 2);
IEC61010-031;
IEC61557-1 (grounding resistance);
IEC61557-5 (soil resistivity);
JJG 366-2004
V.Tester Structure
1. LCD 2. C(H) interface: Current electrode
3. P(S) interface: Voltage electrode
4. ES interface: Auxiliary earth electrode
5. E interface:Earth electrode 6. Button area
7. Rotary switch for selecting function 8. Test button
9. Safety alligator clip 10. Standard test wires
11. Auxiliary earthing rods 12. Simple test wires
13. Interface of testing wires
VI.Measuring Principle
1. Ground voltage measurement uses average rectification.
2. The grounding resistance measurement adopts the rated current change
pole method, that is, the alternating current rated current I flowing between the
measuring object E ground electrode and the H current electrode, to obtain
the potential difference V of the E ground electrode and S voltage electrode,
and according to the formula R=V/ I Calculate the ground resistance value R.
In order to ensure the accuracy of the test, a four-wire method was designed
to increase the FR auxiliary ground. During actual testing, FR and E were
clamped at the same point of the grounding body. The four-wire test can
eliminate the influence of the contact resistance (usually dirt or rust) on the
measured grounding body, auxiliary grounding rod, test clip, and the input
interface of the instrument to the measurement, and can eliminate the
influence of the wire resistance on the measurement, more precision.
3.It’s operating error(B) is an error obtained within the rated operating
conditions, and calculated with the intrinsic error(A) and the error(E) due to
variations.
A: Intrinsic error
E2:Variation due to power supply voltage
E3:Variation due to temperature change
E4:Variation due to interference voltage change
E5:Variation due to contact electrode resistance
4. The soil resistivity (ρ) is measured using the 4-pole method (Winner
method): the alternating current I flows between the E ground electrode and
the H current electrode, and the potential difference V between the S voltage
electrode and the FR auxiliary ground electrode is calculated. The potential
difference V is divided by the alternating current I obtains the grounding
resistance value R, the electrode spacing distance is a(m), and the soil
resistivity value is obtained according to the formula ρ=2πaR(Ωm), and the
distance between the HS pitch and the S-FR is equal (both a), that is Wenner
method. For ease of calculation, please make the electrode spacing a much
larger than the buried depth h, generally should meet a> 20h, see the figure
below.
VII. Operation Methods
1.Switch On/Off
Turn the function key to the corresponding test position and turn it on.
Turn the function key to the OFF position to turn off the instrument. After
power on, there is "APO" displayed in the lower corner. If it is not operated, it
will be automatically turned off after 15 minutes.
2.Battery Voltage Check
After switch on, if LCD displays low battery voltage icon “ “ ,which
indicates that battery voltage is low, and please replace the battery in time.
3. Ground voltage measurement
One auxiliary grounding rod is required for the ground voltage test.
As long as the instrument is connected to the ground through the test
wire and the auxiliary grounding rod, the other test wires of the
instrument interface cannot be connected to the L and N wires of the
commercial power supply. Otherwise, the leakage may occur, and the
circuit breaker may start up and be dangerous.
Ground voltage test cannot exceed 600V.
Grounding voltage: when the ground fault of the electrical equipment
occurs, the potential difference between the grounding device casing, the
grounding wire, the grounding body and the zero potential point, the
grounding voltage is the reference point of the ground, the potential difference
from the earth, and the earth is zero potential point.
An auxiliary grounding rod is required for the ground voltage test. Note
the difference from the commercial AC voltage test. See the following figure:
After the meter, auxiliary grounding rod, and test line are all connected, after
turning on the power, turn the function selection key to U. The LCD shows the
test result.
4.Wire Resistance Verification
In order to improve precision and stability of field measurement of earth
ground resistance, avoid error due to wire resistance change due to prolonged
usage of testing wires; avoid error due to testing wire that is failed to be fully
inserted into tester interface or by poor contact; avoid error due to users’
replacing or lengthening testing wires and etc., wire resistance verification is
specially designed, which is more accurate on low value resistance
measurement.
As shown in the figure below, press the function button R button to switch
to the corresponding ground resistance measurement position, press
button to start verification. During verification, During the calibration, the
LED indicator flashes. The LCD counts down. After the calibration is
completed, the LCD displays the line resistance and stores the value. The
checked line resistance value is automatically deducted from this start-up
ground resistance measurement.
Shutdown does not save the calibration line resistance. The next time you
turn on the power, you need to verify again..
5.Grounding Resistance Precision Measurement
When testing the grounding resistance, first confirm the grounding
voltage of the grounding wire, that is, the voltages of H and E or S and
FR must be less than 20V. If the grounding voltage is more than 5V, the
measured value of the grounding resistance may be inaccurate. At this
time, the measured grounding device should be powered off first, so that
the grounding voltage is reduced and then the grounding resistance test
is performed.
Four-wire test: The four-wire test eliminates the influence of the contact
resistance (usually dirt or rust) on the measured grounding body, auxiliary
grounding bar, test clip, and the input interface of the instrument to the
measurement, eliminating the effect of the wire resistance to the
measurement. It is better than the three-line test.
See the following figure: Beginning with the measured object, generally
spaced 5m ~ 20m, respectively, the S, H auxiliary grounding rod is buried
deep into the ground in a straight line, the ground test line (black, green,
yellow, red) from the instrument E, FR, S, and H interfaces are initially
connected to the ground electrode E under test, the auxiliary voltage electrode
S, and the auxiliary current electrode H.
The distance between the measured grounding body E and the current pole
H should be at least 5 times the buried ground depth (h) of the measured
grounding body, or 5 times the buried ground electrode length (d).
Measure the total grounding resistance of a complex grounding system. The
distance d is the distance of the largest diagonal of the grounding system.
During the test, the test leads cannot be intertwined with each other.
Otherwise, the test accuracy may be affected.
For a multi-point independent grounding system or a geodetic grounding
system, the user can choose a longer test line, and the electrode spacing is
greater than 5 times the maximum diagonal length of the tested network. As
shown below:
R=r1∥r2∥r3∥r4∥r5∥r6∥...∥rn (r1...rn are all independent earth points)
R——meter readings, total grounding resistance of the entire grounding
system;
R1...rn - are all independent grounding points, and grounding bodies are not
connected together under the ground;
RH—ground resistance of auxiliary current pole H;
RS - ground resistance of auxiliary voltage pole S;
n - the number of independent grounding points, the more points, the smaller
the R value.
6.Three-wire Test Grounding Resistance
Three-wire test: As shown in the figure below, short-circuit the FR
and E interfaces of the instrument, that is, the three-wire test, and the
instrument operation is the same as the four-wire test. The three-wire test
can not eliminate the influence of the wire resistance on the measurement,
nor can it eliminate the influence of the change of the contact resistance
between the instrument and the test wire and between the test wire and
the auxiliary grounding rod, and the oxide layer on the surface of the
ground body to be measured needs to be removed.
7.Two-wire easy Test Grounding Resistance
Second-line test: This method is a simple measurement method that does
not use the auxiliary grounding rod. It uses the existing grounding electrode
with the smallest value of the grounding resistance as the auxiliary grounding
electrode, and uses two simple test lines to connect the HS interface and the
E-FR interface. ). The auxiliary ground rods H and S may be replaced with
metallic ground pipes such as metal water pipes and fire hydrants, common
grounding of commercial power systems, or lightning protection grounds of
buildings, etc., and the oxide layer of the connection points of the selected
metal auxiliary grounding body should be removed during measurement. Floor.
Wiring as shown below, the instrument operation with the four-wire test.
When using the commercial power system grounding as an auxiliary
grounding pole measurement, it must be confirmed that it is the
grounding pole of a commercial power system. Otherwise, the circuit
breaker may start up and be in danger.
Use a simple two-wire method to measure the grounding resistance, and
try to select the grounding body with a small re value as the auxiliary
grounding electrode so that the meter reading is closer to the true value.
When measuring, please select the metal water pipe and metal fire
hydrant as the auxiliary grounding electrode.
Two-wire easy Test Grounding Resistance its reading on Tester is the
total value of earth ground resistance value of measured earthing object and
that of commercial earthing object, namely:
RE=RX+re
In which: RE is the Tester reading value;
RX is the earth ground resistance value of measured earthing
object;
re is the earth ground resistance value of common earthing
object like commercial use power system.
Then, the earth ground resistance value of measured earthing object is:
RX=RE-re
8.Soil Resistivity Test
The soil resistivity ρ is an important factor that determines the
grounding resistance of the grounding body. Different types of soil, of
course, have different soil resistivities, that is, even the same kind of soil,
because of different temperature and moisture content, the soil resistivity
will also change significantly. Therefore, in order to have a correct basis
in the design of the grounding device, so that the designed grounding
device can more meet the actual needs of the work, the soil resistivity
must be measured.
The soil resistivity was measured by the four-pole method (Winner
method).
The soil resistivity ρ is calculated according to the formula ρ=2πaR
(Ωm), and the unit is Ωm, and:
a - electrode spacing
R——Soil resistance between S-FR electrodes
Four-pole method (Winner method): Connect the test wire as shown
below. Pay attention to the space between the auxiliary grounding rods
and the depth of burial. H, S, FR, and E auxiliary ground rods are buried
in the ground and buried deep into the earth. The ground test lines (red,
yellow, green, and black) are connected from the H, S, FR, and E ports of
the meter to the H, S, FR, and E auxiliary ground bars under test.
Auxiliary grounding rod spacing setting: After connecting the test line,
press the function button ρ to enter the soil resistivity test mode, press
and hold the SET button (more than 3 seconds) to enter the spacing
setting of the auxiliary grounding rod, press the “ ” key shortly to
move the cursor, press " " or " " key to change the current number
size (a value range: 1m ~ 100m), and then press the SET key (more than
3 seconds) to save the set a value, and return to the soil resistivity test
mode
After the value of a is set, in the soil resistivity test mode, press the
“TFRT” key to start the test and count down to display the test
progress. After the test is completed, a stable soil resistivity value is
displayed.
After startup, press “ “ button to turn on or off backlight. The backlight
function is suitable to dark spot. It will default backlight turn-off for each
startup.
10.Alarm Settings
After power on, short press “ ” to turn on and off the alarm function.
Short press "SET" key to set the resistance alarm value, press " " key to
move the cursor, press " " or " " key to change the current size, and then
press "SET" key to save and exit. When the measured value is greater than
the alarm critical setting value and the alarm function is turned on, the meter
displays the “ ” symbol and issues a “beep-beep-beep--” alarm sound.The
maximum value of the ground voltage alarm setting is 100V, the maximum
value of the ground resistance alarm setting is 3000Ω, and the maximum
value of the soil resistivity alarm setting is 9999Ωm. As shown below:
11.Data Lock/Storage
Startup or after measurement, press
button to lock current
displayed data, showing
icon and automatically store with serial
numbers. If storage is full, the Tester will display
icon. to remove lock.
As shown in figure below: the lock measurement data is1032Ω,press
button save as the 3th group of data .
12.Data Review/Deletion
Startup or after measurement, press
button for a longer time (over
3 seconds) to enter data reading, the interface corresponding to the stored
data interface and the stored data group number flash alternately. Press
or button to select reading data group number by step value 1, press
or button constantly to select reading data group number by step value 5,
and then press
button to exit from reading.
In the figure below, the number 3 is the current group number, and 6 is
the total group number, LCD will display“NULL”, see the above figure.
Under data reading status, press SET button to enter data deletion, press
or to select “no” or “YES”, selecting “no” and then pressing SET button
for not deleting and return data reading status, selecting “YES” and then
pressing SET button for deleting stored data and it will show as above right
figure after deletion.
IX. Battery Replacement
The instrument uses 9V 6-section LR14 dry cell battery, when the
battery power is reduced, the power indicator bar is reduced. When the
voltage drops to 5V, the battery symbol “ ” is displayed.Please
replace the battery in time. Low voltage affects the measurement
accuracy.
X.Accessories
Tester
1 PC
Tester Box
1 PC
Auxiliary Earthing Rod
4 PCS
Testing Wire
4 PCS
Simple testing wire
2 PCS
1.5V battery
6 PCS
Manual , Qualification Certificate
1 SET
GuangZhou ZhengNeng Electronics Technology Co.
Address: 2F, No.15 Baoshu Road, Taihe, Baiyun District, Guangzhou,
Guangdong, China
Toll-free call:4000-1515-38
Tel:86-20-36544172
Fax:86-20-37319075
Post:510540
WebSite:www.znele.com