GE S2500 INSTRUCTIONS - Field Replacement
CONTACT ARMS, ARC CHUTES, LINE and LOAD STRAPS, HANDLE ASSEMBLY
Type 52500 Molded Case Circuit Breaker
Part Name
CONTACT ARM ASSEMBLY- All Poles
ARC CHUTE ASSEMBlY- All Poles
LINE STRAP ASSEMBlY - All Poles
LOAD STRAP ASSEMBlY - All Poles
HANDLE
GASKET, Handle
PLATE, Handle Fastening
SCREW, Handle Fastening
CONTACT ARM
ASSEMBLY
Cat. No.
5678161
5678163
794A641
794A690
456C143
794A723
794A668
N646P16008C
ARC CHUTE
REPLACING CONTACT ARM ASSEMBLY
For Outside Poles
REMOVE BREAKER COVER
1)
Manually trip breaker
2)
Remove escutcheon plate from breaker covP-r by
unscrewing 4 screws.
3)
Remove breaker cover by unscrewing 4 cover
screws. Note: Lower screws concealed by escutch
eon plate.
For detailed instructions, see GEH-3371-A
REMOVE TRIP UNIT
4)
Unscrew hex head bolts but leave in position in
line-conductor holes of trip unit coils.
5)
Unscrew socket head bolts from lo
REPLACING ARC CHUTE ASSEMBLY- All Poles
REMOVE BREAKER COVER - Steps 1 to 3
18)
Remove Round Head Screws (J) Figure I, and
retaining plates. Arc chute may now be lifted
out.
19)
Replace arc
chute by
reversing
procedure.
NOTE: Make certain each retaining plate is
seated flat in side recess of arc chute before
tightening screws.