Ampac FIREVIEW Quick Start Manual
Text of the manual
PORTABLE FIRE DETECTOR
TESTER
World’s first all in one unified tester for heat and
smoke detector.
MAN 3141
FireView Portable Fire Detector Test Kit
1
Components
2
Ampac Product Item Numbers
Item Number
Description
4112-1012
Ampac FireView Portable Fire Detector Tester
4112-1007
Smoke Oil (100ML)
4112-1008
FireView 6M Extension Pole
4112-1009
FireView 10M Extension Pole
4112-1010
FireView Smoke Detector Removal Tool
4112-1011
FireView Heat Detector Removal Tool
4112-1013
FireView Replacement Head Unit
FireView Detector Test Kit
3
Specifications
Items
Specifications
Testable Detector
Heat: Rate of Rise Heat Detector, Fixed Temperature Heat Detector
Smoke: Ionization Smoke Detector, Photoelectric Smoke Detector
Option: Analog Type Detector, Unexploded Type (Heat)
Head Size
150mm (Detector Insertion)
Inspection Pole Length
Minimum Approx. 127cm / Maximum approx. 250cm
If longer pole is needed 6m and 10m poles are available upon request.
Weight
2.3kg
Material
Aluminum
Input
AC100 ~ 240V 50~60Hz 2A
Output
DC12V 2A
Operating Temperature Range
Approx. 0°C to 40°C
Keeping Temperature Range
Approx. -10°C to 40°C
Operating Humidity Range
Approx. 0% to 85%, No Frost
Smoke Generator Ability
Approx. 50 testable based on 1.00ml smoke detector
Battery
14.8V Li-ION
Charging Time
Full charge consumes approx. 5 hours
Charger
Input: AC 100-240V, 50-60Hz, 0.5A / Output: DC 12V2A
Running Time
Up to 5 hours
Duration may vary due to operating conditions; battery has limited
recharge cycles and may eventually need to be replaced.
Tester Ability (One Time of
Charge)
Approximately 200 Heat Detectors and 300 Smoke Detectors
FireView Detector Test Kit
4
Controller – Indication & Controls
5
Test Pole Components
6
Battery Charging
1. If the controller does not operate when the LOW LED is lit or the controller’s button is pressed, the
battery is discharged. Charge the battery by inserting it into the charging jack with the dedicated
charger (DC 12V2A).
2. The CHARGE LED lights up while charging.
3. The charging time is approximately 5 hours. When the charging is complete, the red FULL LED will
turn on and the charging will stop. The instrument will not have any problems even if the charging
jack is plugged in for a long time.
4. If a different charger (voltage higher than 12V) is used, it may cause a breakdown or fire. Therefore,
you must use the dedicated charger (DC 12V2A) supplied with the device.
FireView Detector Test Kit
7
Smoke Oil Fill
1. Remove the wing nut from the smoke oil fill point.
2. Inject 10ml to 20ml of smoke oil, do not over fill as this will produce excessive smoke and lead to
extended test times and fan usage.
3. Replace the wing nut ensuring that it is tight.
8
User Instructions
8.1
Paring Instructions
1. To activate pairing mode, press the ‘C’ button on the controller twice to activate the pairing mode
blinking Smoke, Heat and Fan LED’s with a beep sound.
2. To cancel the pairing mode, press the ‘C’ button.
3. To complete the pairing mode, press the ‘C’ button on the remote control or the ‘C’ icon on the
FireView Smartphone Application.
4. If pairing is successful, LED lights will blink 3 times and make a beep sound.
8.2
Controller Instructions
1. Power up the controller using the ‘Power On’ switch.
2. Locate detector tester rubber gaiter over the detector located on the ceiling, adjust the length of the
pole where required.
3. Press either the Heat or Smoke switch according to the detector type under test.
4. Heat and smoke are created in 5 and 3 seconds after the heating element is fully warmed up,
respectively.
5. The unit has a built-in fan which can be used to expel smoke from the smoke detector following the
activation test. To start the fan, press the ‘D’ button.
6. When heat generation times needs to be extended for fixed temperature detector testing, press the
‘C’ button to extend for approximately 2 minutes.
7. A Smartphone application is also available for Android devices. Please contact your local Ampac
Customer Service Office for more information.
FireView Detector Test Kit
WWW.AMPAC.NET