ABB EIB Delta Operation & User’s Manual

Brand: ABB
Category: Measuring Instruments
Model: EIB Delta (Operation & User’s Manual)
File Type: PDF
File Size: —
Pages: 34
Text of ABB EIB Delta Operation & User’s Manual

ABB EIB Delta ABB i-bus® EIB

Contents Page 1 General information 1.1 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.2 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.3 Important notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.4 Labelling of the EIB Delta-Meter . . . . . . . . . . . . . . . .

ABB EIB Delta The EIB Delta-Meters are a new generation of certified, electronic, electricity

meters with an integrated ABB i-bus® EIB communication interface. The new EIB Delta-Meters are compact, reliable, immune to interference impulses and suitable for use in single-phase and polyphase voltage networks. As the meters have no mechanical moving parts, they can easily be mounted in any position onto DIN rails according to EN 50022. The EIB communication interface allo

ABB EIB Delta 1.2 Technical Data

Accuracy class: Operating voltage: Nominal current Ib (limit current Imax): Starting current: Power consumption: Frequency: Electromagnetic compatibility (EMC): Overload capability: Circuit protection: Active energy meter: Class 1 or 2 according to IEC 1036 Reactive energy meter: Class 2 according to IEC 1268 Nominal voltage: See selection table Permitted deviation: – 20% ... +15% Transformer rated meter: 1(6) A for class 1, (/1 A or /
ABB i-bus® EIB Environmental conditions: Mechanical data: Display: EIB connection: Standards/norms: Ambient temperature: – 5° C ... + 45° C Storage temperature: – 40° C ... + 70° C Relative humidity: < 75% annual average, 95% max. 30 days/year Housing material: – Front window and housing Polycarbonate – Terminal area Glass-fibre-reinforced polycarbonate Dimensions (H x W x D): 96 x 122.5 x 64.8 mm Protectio

Labelling of the EIB Delta-

Meter (Example) EIB Delta-Meters are intended solely for the measurement of electrical energy. The installation and commissioning may only be carried out by authorised electrical specialists. The appropriate norms, guidelines, regulations and specifications should be observed when planning and setting up electrical installations. Advisory: – EIB Delta-Meters should be protected from damp, dirt and damage

The EIB Delta-Meters are suitable for installation in distribution boards

or small enclosures, for wall mounting or panel mounting. They can be snapped onto 35 mm mounting rails, according to DIN EN 50 022. Connection: The electrical connection is carried out via screw terminals. The terminal markings and insulation strip lengths are embossed in the terminal area of the meter. (Wiring diagrams can be found in section 5.3). The connecting screws should be t

Various measurement methods are used in the EIB Delta-Meters depending

on the type of meter. The following equations are vector equations. Measurement method with one measuring element This method only produces the correct result if the phase load is symmetrical. P = 3 · IL3 · UL3 This method is not suitable for carrying out accurate measurements in polyphase voltage networks as 100% symmetrical loading seldom occurs. Measurement method with two measurin

ABB Measuring Instruments Owners Instructions: