ABB EIB Delta Operation & User’s Manual
| Brand: | ABB |
| Category: | Measuring Instruments |
| Model: | EIB Delta (Operation & User’s Manual) |
| File Type: | |
| File Size: | — |
| Pages: | 34 |
Text of ABB EIB Delta Operation & User’s Manual
ABB EIB Delta ABB i-bus® EIB
Contents
Page
1
General information
1.1
General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
1.2
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
1.3
Important notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
1.4
Labelling of the EIB Delta-Meter . . . . . . . . . . . . . . . .
ABB EIB Delta The EIB Delta-Meters are a new generation of certified, electronic, electricity
meters with an integrated ABB i-bus® EIB communication interface.
The new EIB Delta-Meters are compact, reliable, immune to interference
impulses and suitable for use in single-phase and polyphase voltage
networks. As the meters have no mechanical moving parts, they can easily
be mounted in any position onto DIN rails according to EN 50022. The EIB
communication interface allo
ABB EIB Delta 1.2 Technical Data
Accuracy class:
Operating voltage:
Nominal current Ib
(limit current Imax):
Starting current:
Power consumption:
Frequency:
Electromagnetic
compatibility (EMC):
Overload capability:
Circuit protection:
Active energy meter:
Class 1 or 2 according to IEC 1036
Reactive energy meter:
Class 2 according to IEC 1268
Nominal voltage:
See selection table
Permitted deviation:
– 20% ... +15%
Transformer rated meter:
1(6) A for class 1,
(/1 A or /
ABB i-bus® EIB Environmental conditions:
Mechanical data:
Display:
EIB connection:
Standards/norms:
Ambient temperature:
– 5° C ... + 45° C
Storage temperature:
– 40° C ... + 70° C
Relative humidity:
< 75% annual average,
95% max. 30 days/year
Housing material:
– Front window and housing
Polycarbonate
– Terminal area
Glass-fibre-reinforced polycarbonate
Dimensions (H x W x D):
96 x 122.5 x 64.8 mm
Protectio
Labelling of the EIB Delta-
Meter (Example)
EIB Delta-Meters are intended solely for the measurement of electrical
energy. The installation and commissioning may only be carried out by
authorised electrical specialists. The appropriate norms, guidelines,
regulations and specifications should be observed when planning and setting
up electrical installations.
Advisory:
– EIB Delta-Meters should be protected from damp, dirt and damage
The EIB Delta-Meters are suitable for installation in distribution boards
or small enclosures, for wall mounting or panel mounting. They can be
snapped onto 35 mm mounting rails, according to DIN EN 50 022.
Connection: The electrical connection is carried out via screw terminals.
The terminal markings and insulation strip lengths are embossed in the
terminal area of the meter. (Wiring diagrams can be found in section 5.3).
The connecting screws should be t
Various measurement methods are used in the EIB Delta-Meters depending
on the type of meter. The following equations are vector equations.
Measurement method with one measuring element
This method only produces the correct result if the phase load is symmetrical.
P = 3 · IL3 · UL3
This method is not suitable for carrying out
accurate measurements in polyphase
voltage networks as 100% symmetrical
loading seldom occurs.
Measurement method with two measurin