ABB Relion REB500 Engineering Manual
Read Online
Read the ABB Relion REB500 Engineering Manual online using the built-in PDF viewer.
Text of the manual
Distributed busbar protection REB500
Version 8.3 ANSI
Engineering manual
/t1ainm1:nu
Events
Measurements
Disturbance records
Settings
2013-03-3010:53:.10
j$superUser
joi,jectname
a
/Mainmenu =
I ; D
D
i!9?
J;;:::et
,
SettirlgS
confiation
rua,gr,ostics
rests
O•
L¥19"39f -
I D I; =
D =
I ; D
D
i!9?
J;;:::et
,
SettirlgS
confiation
rua,gr,ostics
rests
O•
L¥19"39f -
I D I; =
D =
Document ID: 1MRK 511 452-UUS
Issued: October 2020
Revision: A
Product version: 8.3
© 2020 Hitachi Power Grids. All rights reserved
This document and parts thereof must not be reproduced or copied without written permission
from Hitachi Power Grids, and the contents thereof must not be imparted to a third party, nor
used for any unauthorized purpose.
The software and hardware described in this document is furnished under a license and may be
used or disclosed only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit
(http://www.openssl.org/). This product includes cryptographic software written/developed by:
Eric Young ([email protected]) and Tim Hudson([email protected]).
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their respective
holders.
Warranty
Please inquire about the terms of warranty from your nearest Hitachi Power Grids representative.
The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guaranteed properties. All persons
responsible for applying the equipment addressed in this manual must satisfy themselves that
each intended application is suitable and acceptable, including that any applicable safety or other
operational requirements are complied with. In particular, any risks in applications where a system
failure and /or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the person or entity
applying the equipment, and those so responsible are hereby requested to ensure that all
measures are taken to exclude or mitigate such risks.
This document has been carefully checked by Hitachi Power Grids but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to notify the
manufacturer. Other than under explicit contractual commitments, in no event shall Hitachi Power
Grids be responsible or liable for any loss or damage resulting from the use of this manual or the
application of the equipment.
ABB is a registered trademark of ABB Asea Brown Boveri Ltd. Manufactured by/for a Hitachi Power
Grids company.
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility (EMC
Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage
limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB
Power Grids in accordance with the product standard EN 60255-26 for the EMC directive, and with
the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is
designed in accordance with the international standards of the IEC 60255 series.
Table of contents
Section 1
Introduction......................................................................................................... 5
1.1
This manual.......................................................................................................................................... 5
1.2
Intended audience.............................................................................................................................. 5
1.3
Revision history................................................................................................................................... 5
1.4
Product documentation.....................................................................................................................5
1.5
Symbols and conventions................................................................................................................. 6
1.5.1
Symbols...............................................................................................................................................6
1.5.2
Document conventions....................................................................................................................6
Section 2
Safety information.............................................................................................. 9
Section 3
HMI500 modes....................................................................................................11
Section 4
Setfile (REB500 Configuration File)................................................................ 13
4.1
File - New.............................................................................................................................................13
4.1.1
File name...........................................................................................................................................13
4.1.2
Project directory structure............................................................................................................14
4.1.3
Initial windows (default system settings)................................................................................. 15
4.2
File - Open…....................................................................................................................................... 15
4.3
File - Save as…................................................................................................................................... 15
4.4
File - Compare…................................................................................................................................ 15
4.5
File - Exit..............................................................................................................................................15
Section 5
Configuration..................................................................................................... 17
5.1
System installation............................................................................................................................17
5.1.1
System data..................................................................................................................................... 18
5.1.2
File version management system................................................................................................18
5.2
Plant data............................................................................................................................................19
5.3
BP Licences.........................................................................................................................................19
5.4
Communication................................................................................................................................. 19
5.5
Single-line diagram...........................................................................................................................20
5.5.1
Process feeders mode................................................................................................................... 20
5.5.2
Process bus zones mode...............................................................................................................22
5.5.3
Select Bay model.............................................................................................................................24
5.5.4
Import options................................................................................................................................ 25
5.6
Device structure................................................................................................................................ 26
5.7
CU device creator.............................................................................................................................. 27
5.8
Network...............................................................................................................................................29
5.9
Binary inputs/outputs..................................................................................................................... 30
1MRK 511 452-UUS Rev. A
Table of contents
Distributed busbar protection REB500
1
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Event text configuration................................................................................................................. 30
5.11
LMI LED............................................................................................................................................... 30
5.12
Disturbance recorder....................................................................................................................... 30
Section 6
Settings...............................................................................................................31
6.1
Breaker failure protection................................................................................................................31
6.2
Time overcurrent protection...........................................................................................................31
6.3
End fault protection..........................................................................................................................31
6.4
CB pole discrepancy..........................................................................................................................31
6.5
Overcurrent release...........................................................................................................................31
6.6
Voltage release...................................................................................................................................31
6.7
Bay protection....................................................................................................................................31
6.8
Circuit breakers................................................................................................................................. 32
6.9
Disconnectors....................................................................................................................................32
6.10
Current transformers....................................................................................................................... 32
6.11
Voltage transformers....................................................................................................................... 32
6.12
Voltage/ external release................................................................................................................ 32
6.13
System response...............................................................................................................................34
6.14
Activate/ deactivate device............................................................................................................34
6.15
CB inspection.....................................................................................................................................34
6.16
Event memory....................................................................................................................................34
6.17
Time..................................................................................................................................................... 35
Section 7
Tools....................................................................................................................37
7.1
File verification.................................................................................................................................. 37
7.2
Reports................................................................................................................................................37
7.3
Export SCS data................................................................................................................................ 38
7.4
Export Bay Model catalogues.........................................................................................................38
7.5
Default values.................................................................................................................................... 38
7.6
Bay model viewer.............................................................................................................................. 39
7.7
Operator mode..................................................................................................................................40
7.8
Settings...............................................................................................................................................41
Section 8
Annex A | Configurator mode - Definitions....................................................43
8.1
Setfile.................................................................................................................................................. 44
8.2
Configuration models (1)................................................................................................................ 45
8.3
Configuration models (2)................................................................................................................46
8.4
Configuration models (3)................................................................................................................ 47
8.5
Bay Figure (BF).................................................................................................................................. 48
8.6
Bus interconnections (1)..................................................................................................................49
8.7
Bus interconnections (2)................................................................................................................. 50
Section 9
Annex B | Configurator mode - System configuration..................................51
9.1
Preparations (1)................................................................................................................................. 51
Table of contents
1MRK 511 452-UUS Rev. A
2
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Sequence of configuration............................................................................................................. 54
9.5
Start configuration - File-New (1).................................................................................................. 55
9.6
Start configuration - File-New (2)..................................................................................................56
9.7
Initial (default) settings (1)..............................................................................................................57
9.8
Initial (default) settings (2).............................................................................................................58
9.9
Initial (default) settings (3).............................................................................................................59
9.10
Initial (default) settings (4).............................................................................................................60
9.11
Communication (1)............................................................................................................................61
9.12
Communication (2)........................................................................................................................... 62
9.13
SLD-CONF - Start.............................................................................................................................. 63
9.14
SLD-CONF Select BM (1).................................................................................................................. 64
9.15
SLD-CONF — Select BM (2)............................................................................................................. 65
9.16
SLD-CONF — Select BM (3)............................................................................................................. 66
9.17
SLD-CONF — Select BM (4)............................................................................................................. 67
9.18
SLD-CONF — adjust BM (1).............................................................................................................68
9.19
SLD-CONF — adjust BM (2).............................................................................................................69
9.20
SLD-CONF — export BM (1).............................................................................................................70
9.21
SLD-CONF — export BM (2).............................................................................................................71
9.22
SLD-CONF — export BM (3).............................................................................................................72
9.23
SLD-CONF — typical bays (1).......................................................................................................... 73
9.24
SLD-CONF — typical bays (2)..........................................................................................................74
9.25
SLD-CONF — completion of single-line diagram....................................................................... 75
9.26
SLD-CONF — Positioning of bay figures......................................................................................75
9.27
SLD-CONF — Bus labels (1)............................................................................................................. 76
9.28
SLD-CONF — Bus labels (2)............................................................................................................. 77
9.29
SLD-CONF — Labels (1)....................................................................................................................78
9.30
SLD-CONF — Labels (2)....................................................................................................................79
9.31
SLD-CONF — Bus zone assignment (1)........................................................................................ 80
9.32
SLD-CONF - Bus zone assignment (2)........................................................................................... 81
9.33
SLD-CONF — Bus zone assignment (3)........................................................................................ 82
9.34
CU device creator (1)........................................................................................................................ 83
9.35
CU device creator (2)........................................................................................................................84
9.36
CU device creator (3)........................................................................................................................85
9.37
Device structure................................................................................................................................86
9.38
File verification.................................................................................................................................. 87
9.39
Final settings..................................................................................................................................... 88
9.40
Completed setfile............................................................................................................................. 89
1MRK 511 452-UUS Rev. A
Table of contents
Distributed busbar protection REB500
3
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
This document contains the description of the REB500 Configurator Tool (HMI500 started under
Configurator Mode) and the setfile engineering process. In addition to the theoretical part, the
Engineering Manual provides an application example (see Section 8 and Section 9). This part of the
documentation can be used for training purposes.
1.2
Intended audience
GUID-38C46E80-F5F2-4880-BD0E-A7EF458601ED v1
The engineering manual addresses system and project engineers involved in the engineering
process of a project, and installation and commissioning personnel, who change configuration
data during engineering, installation and commissioning.
In the Configurator mode, a system configuration can be modified. This mode
should be used by selected (trained) users only.
1.3
Revision history
GUID-C876BDE2-918C-4B31-BA00-4D4A4190BFDC v1
1.4
Product documentation
GUID-AE1A560D-7F68-4E95-807B-ECB7C6DFE706 v2
For an introduction into REB500, it is recommended to study the Product guide and/or the
Application manual.
REB500 manuals
Document numbers
Product guide
1MRK 505 402-BEN
Application manual
1MRK 505 399-UUS
Technical manual
1MRK 505 400-UUS
Operation manual
1MRK 500 132-UUS
Engineering manual
1MRK 511 452-UUS
Commissioning manual
1MRK 505 401-UUS
Application manual for bay protection functions
1MRK 505 403-UUS
Technical manual for bay protection functions
1MRK 505 406-UUS
Cyber security deployment guideline
1MRK 511 453-UEN
Table continues on next page
1MRK 511 452-UUS Rev. A
Section 1
Introduction
Distributed busbar protection REB500
5
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Document
revision
Date
Product revision
History
A
2020-10
8.3.1
First release
Communication protocol manual IEC 61850
1MRK 511 450-UEN
Communication protocol manual IEC 60870-5-103
1MRK 511 451-UEN
Getting started guide
1MRK 505 404-UEN
1.5
Symbols and conventions
1.5.1
Symbols
GUID-FBABB9D6-60F3-4BFB-B9C9-9B2F65B5F7CE v3
The electrical warning icon indicates the presence of a hazard which could result in
electrical shock.
The warning icon indicates the presence of a hazard which could result in personal
injury.
The caution icon indicates important information or warning related to the
concept discussed in the text. It might indicate the presence of a hazard which
could result in corruption of software or damage to equipment or property.
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project or how to
use a certain function.
Although warning hazards are related to personal injury, it is necessary to understand that under
certain operational conditions, operation of damaged equipment may result in degraded process
performance leading to personal injury or death. Therefore, comply fully with all warning and
caution notices.
The tutor icon points to the tutorial of the REB500 configuration process and vice
versa (see Annex A and Annex B).
1.5.2
Document conventions
GUID-37C3ACF4-BD79-43C6-B37E-24B38EE69301 v3
A particular convention may not be used in this manual.
•
Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also
contains definitions of important terms.
•
Push button navigation in the LHMI menu structure is presented by using the push button
icons.
For example, to navigate the options, use
and
.
•
HMI menu paths are presented in bold.
For example, select Main menu/Settings .
•
Signal names are presented in bold.
Section 1
1MRK 511 452-UUS Rev. A
Introduction
6
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
The signal 21120_EXT_TEST_TRIP can be set and reset via the LHMI Test Trip menu.
•
Parameter names and parameter values are presented in italics.
For example, the default value of the Operation setting is Not inverted.
•
Section references are presented with the respective section numbers.
For example, see Section 1.5.2 for more details about document conventions.
•
The phase names L1, L2, L3, and L0 should be read as phase A,B,C, and N respectively.
•
The term Disturbance recorder should be read as Digital Fault Recorder in the document.
•
The term Single-line diagram should be read as One-line diagram in the document.
•
OFF is used for Disabled and On is used for Enabled in Settings.
•
The term Isolator is used in the the HMI500 menus and the LHMI menus, and should be read
as Disconnector.
1MRK 511 452-UUS Rev. A
Section 1
Introduction
Distributed busbar protection REB500
7
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
The busbar protection system REB500 corresponds to the latest practices and guidelines and
complies with the recognized safety rules. Nevertheless, care must always be taken to avoid
danger.
Use the busbar protection system only when it is in perfect working order and in strict accordance
with the operating instructions.
Dangerous situations can arise if the equipment is used improperly, especially if the user changes
the configuration.
Live electrical equipment is in the immediate vicinity of the REB500 system. Before
working on the system, always ensure that it is impossible to come into contact
with, or even close to live parts.
The IEDs of the REB500 system can initiate operation of items of electrical plant
(circuit breakers and disconnectors). Before working on the equipment, always
ensure that unwanted operation is disabled or has no effect on persons or plant.
Strictly observe all safety precautions (interlocks, locks and blocking devices),
especially those issued for the specific station.
Only properly authorized, professionally qualified and correspondingly trained
personnel, who have also read and understood the operating instructions, may
work on the system.
Dangerous voltages can occur on the connectors, even though the auxiliary voltage
has been disconnected.
Non-observance can result in death, personal injury or substantial property
damage.
Only a competent electrician is allowed to carry out the electrical installation.
National and local electrical safety regulations must always be followed.
The frame of the IEDs has to be carefully grounded.
1MRK 511 452-UUS Rev. A
Section 2
Safety information
Distributed busbar protection REB500
9
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Whenever changes are made in the IEDs, measures should be taken to avoid
inadvertent tripping.
The IEDs contain components which are sensitive to electrostatic discharge.
Unnecessary touch of electronic components must therefore be avoided.
Take care never to open the secondary circuits of CTs conducting current.
There is a danger of contact with live parts when opening REB500 cubicle doors.
Electrostatic discharge can destroy components in the equipment.
Other safety instructions pertaining to particular operations are contained in the
respective chapters of the operating instructions.
Section 2
1MRK 511 452-UUS Rev. A
Safety information
10
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
See Section 9.3.
HMI500 software is primarily used as a human-machine interface (HMI) for the protection system
REB500 (Operator mode). Furthermore, the program can be used for the configuration of the
system file (Configurator mode), if a licence key file has been saved under the HMI500-REBWIN
installation directory (see HMI500 Licence request description).
Specific software and descriptions in connection with the Configurator mode are
located on the Product media HMI Configurator, section English-Software-HMI500
Configurator Mode.
The first screen to appear after starting the program is the System log-on dialog box.
15000002-IEC18000371-1-en.vsdx
IEC18000371 V1 EN-US
Figure 1:
System login dialog box
Operator mode (for information only)
The Operator mode can be run in a read only mode by appropriately activating the Read only
check box, that is, the data can be viewed but not changed. Users that want to run the Operator
mode in a read/write mode must deactivate Read only.
When the HMI500 software establishes communication with a REB500 system
(only possible in Operator mode) initially user must enter a password.
For further information about HMI500-modes, see REB500 Operation Manual, section Starting
HMI500.
1MRK 511 452-UUS Rev. A
Section 3
HMI500 modes
Distributed busbar protection REB500
11
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
The following Engineering Manual covers the Configurator mode and the REB500
setfile engineering process only.
Section 3
1MRK 511 452-UUS Rev. A
HMI500 modes
12
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Setfile (REB500 Configuration File)
GUID-9D30690A-48AE-4B1E-8285-F23775FB61F9 v2
See Section 8.1.
4.1
File - New...
GUID-B0D82583-74A2-4957-91A5-8C32328642DA v2
See Section 9.5.
The configuration of a new protection system (new setfile) is started with NEW. First input is the
name of the project.
IEC18000564-IEC18000564-1-en.vsdx
IEC18000564 V1 EN-US
Figure 2:
New configuration file
4.1.1
File name
GUID-AED0EBCC-2E9C-4A89-BA95-4F71A522F9F4 v2
ABB recommends the following guidelines for the naming of a setfile (example):
1MRK 511 452-UUS Rev. A
Section 4
Setfile (REB500 Configuration File)
Distributed busbar protection REB500
13
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
provided by ABB
10
File version index
This index is defined by the user, for example:
01 = 0.1 → preliminary setfile
10 = 1.0 → setfile version for commissioning
_A
Revision index
The file revision index (A, B, up to AY, AZ) should be defined
by the client engineer on site by using the HMI500 program.
.mdb
File extension
The extension .mdb, which is mandatory, is added
automatically
Remark: File version index and revision index are automatically added to the file name (see Section
5.1.2).
4.1.2
Project directory structure
GUID-B616CBFE-40B7-4F81-8A2A-2986DBE85087 v1
A REB500 set file configured with the HMI500 Configurator mode has to be saved in a REB500
project structure. For ABB in-house configured systems, the following projects structure is used:
IEC18000565-IEC18000565-1-en.vsdx
IEC18000565 V1 EN-US
Figure 3:
Directory structure REB500 setfiles
1-File-configuration (draft version)
In this directory, the setfile is temporarily stored during the configuration phase. It has to be
moved to 2-File-Testing, after setfile configuration has finished.
2-File-testing (test version)
While testing/commissioning the system, the setfile is saved under this directory. After the
system tests/ commissioning have finished, the file has to be moved to 3-File definitive.
3-File-definitive
This is the place for a setfile of a REB500 in service. The directories 1-File-configuration and 2-File-
Testing should be empty now.
4-File-old-versions
If a system (setfile) is modified (re-configured), it is recommended to store the old version(s) of
the setfile under this directory. This folder contains the history of all versions, which had been
applied during the lifetime of a REB500/REB500sys system.
Section 4
1MRK 511 452-UUS Rev. A
Setfile (REB500 Configuration File)
14
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
This directory structure, used for ABB in house configured projects, ensures the
transparency about setfile versions used in a REB500 system throughout the
engineering process. It is recommended to implement this structure also for client
configured systems.
4.1.3
Initial windows (default system settings)
GUID-0F7BBE93-F4F9-4C77-94ED-0603FE411280 v2
See Section 9.6.
After pressing the button Save (see Figure 2), three windows containing the basic (default) system
settings will appear:
•
System Installation (see Section 5.1)
•
Plant Data (see Section 5.2)
•
Default Values (see Section 7.5)
It is recommended to fill in the system data into these initial menus.
4.2
File - Open…
GUID-50EB72FB-0CBA-481B-8526-ACCC076A8E76 v1
If the HMI500 software is started, the program will load the last used project by default. However,
any another configured project can be opened via Open.
4.3
File - Save as…
GUID-8A1A95A0-3D08-4779-95B3-98D4E30C4DAC v1
An existing project (setfile) can be overwritten with a currently opened project, or a currently
opened project can be saved as a new project under a different name with Save as.
4.4
File - Compare…
GUID-5D16BDBC-512C-40EA-ABA1-EC07CC8373EB v1
This menu item provides facility for comparing the PC database loaded by HMI500 and the
database stored in the protection system or a second database file in the PC.
For detailed information about setting and configuration, see REB500 Operation
Manual, section Compare.
4.5
File - Exit
GUID-9B6E6601-77E9-4437-80E5-7DD1AB0E420F v1
To quit HMI500, choose Exit.
1MRK 511 452-UUS Rev. A
Section 4
Setfile (REB500 Configuration File)
Distributed busbar protection REB500
15
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
See Section 9.7.
Under this dialog box, the general system data, the licensed protection functions and the version/
revision control shall be entered.
IEC18000566-IEC18000566-1-en.vsdx
IEC18000566 V1 EN-US
Figure 4:
System installation
1MRK 511 452-UUS Rev. A
Section 5
Configuration
Distributed busbar protection REB500
17
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Function of selections
Selection
Function
S1
File version of setfile:
•
preliminary versions → for example, 0.10, 0.20 ….
•
commissioned versions → for example, 1.00, 2.00 ….
S2
Revision index of setfile:
•
setting changes on site → A, B,.. up to AY, AZ
5.1.1
System data
GUID-4B93572D-E320-4624-BA37-213534C3B52C v1
Specified data
General system information as well as the type of installation is entered on the left hand side
under Specified data.
Licensed data
On the right hand side, the Licensed components (that is, the licensed protection functions) have
to be entered. This selection of licensed function in the setfile has to match with the licensed
function scope of the ordered Bay Units.
5.1.2
File version management system
GUID-B1FCC2E2-F1BB-40D8-A43E-12F90D079A97 v2
The HMI500 tool contains a file version management system which is active under the
Configurator mode only. The file version (see Figure 4, selection S1) will be added to the file name
by default. During configuration/testing/commissioning phase, it is recommended to use
preliminary versions such as 0.1, 0.2. The commissioned file version shall be incremented to 1.0.
For major configuration updates, the first digit shall be incremented (for eample, 1.0 to 2.0). For
minor updates the second digit of the file version index has to be incremented (for example, 1.0 to
1.1).
Definition major update
•
New configuration of primary system (which was not pre-configured)
•
Additional Bay Unit (which was not pre-configured)
•
Additional functionality as BFP, UMZ etc.
•
Setfile migration (software upgrade)
Definition minor update
•
New binary I/O configuration (implemented by the setfile engineer)
•
New protection settings (implemented by the setfile engineer)
The file revision index A, B, up to AY, AZ (see Figure 4, selection S2) shall be used for setting
changes on site (not for configuration changes done under the Configurator mode). This index
shall be changed in the HMI500 Operator mode.
Section 5
1MRK 511 452-UUS Rev. A
Configuration
18
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
See Section 9.8.
IEC18000567-IEC18000567-1-en.vsdx
IEC18000567 V1 EN-US
Figure 5:
Plant data
Under this menu, Rated voltage, Rated frequency, busbar Grounding and the type of Busbar shall
be selected. The Rated frequency, can be either 50 Hz or 60 Hz, whereas the range of the Rated
voltage, can be from 6 kV to 1000 kV. Pressing Default values button reactivates the default
values.
To save the entries, activate the buttons OK or Apply; with Restore and Cancel the entries will be
rejected.
5.3
BP Licences...
GUID-401C043B-556F-4EC9-B89B-595ECA42B6BC v1
The menu Configuration /BP Licences… provides an overview of licensed and configured
protection function groups for each bay unit.
5.4
Communication
GUID-A0D4041C-FBF9-4AFE-9344-48169727DF45 v1
For detailed information about setting and configuration, see REB500 Operation Manual, section
Communication.
1MRK 511 452-UUS Rev. A
Section 5
Configuration
Distributed busbar protection REB500
19
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
The single-line diagram editor is the core menu of the HMI500 Configurator tool. Its basic function
is the configuration of the bus image (single-line diagram) used for the protection system. For this
part of the configuration, tailor-made Bay Models (BM) are copied from a data base to a selected
position of the single-line diagram. The Bay Model is not only a graphical layout of a bay, it also
contains an image of the hardware, the logical objects and assignments.
Before starting the configuration of the single-line diagram, it is recommended to study the
Section 8.
See Section 8.
The Section 9 shows an example for the complete setfile configuration process. The single-line
diagram editor is explained in detail.
See Section 9.
5.5.1
Process feeders mode
GUID-6FE67B26-7064-4B38-AA97-0DB56ACC7F0B v2
See Section 9.13.
IEC18000568-IEC18000568-1-en.vsdx
IEC18000568 V1 EN-US
Figure 6:
Single-line diagram editor
Section 5
1MRK 511 452-UUS Rev. A
Configuration
20
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Function of selections
Selection
Function
S1
The basic single-line editor mode is the ‘Process feeder’ mode.
Under this mode, the configuration of the single-line diagram
is defined. After the single-line (bus configuration) of the
complete station is finished, the (logical) bus zone
assignment has to be checked under the ‘Process bus zone’
mode.
S2
A Bay Model (BM) or a Bay Figure (BF) can be selected by a left
mouse click in the bay area. The selected BM or BF appears
marked with a red line rectangle (the BM is marked with a bold
rectangle)
The single-line editor provides two selection modes:
•
Figure: In this mode, a single Bay Figure (BF) can be
selected and moved to left, or the right side.
•
Model: In this mode, a complete Bay Model (BM) can be
selected and copied to the User model database, or
removed from the single-line diagram, or a BM can be
copied (imported) from the User model database, the
selected position in the single-line diagram.
For deleting BM(s) from the single-line diagram, or for the
import to the User model database, press SHIFT+left mouse
button on the BM. The view of the BM changes to bold framed
now.
Table 3:
Function of buttons
Button
Functions
B1
The (physical) position of the CB and the CT in the single-line diagram
can be mutually exchanged (swapped). This button is only active, if a CT
object is selected.
1.
Select (exactly) the center of the CT object with a left mouse click.
The CT object appears filled with red color.
2.
Press button B1.
3.
The positions of CB and CT are exchanged now.
The single-line diagram including the CB/CT positions
configured with the HMI500 tool has to reflect the
substation’s bus configuration exactly.
There are bays where an exchange of the CB/CT
position is not possible (for example, coupler bays with
two CT’s). The swapping function for such bays is
blocked by the configurator tool.
B2
Copy a selected Bay Model under a new name into the User Model
Database. This button is active only, if the Model Mode (see S2) is
selected.
B3
Move the selected Bay Model or Bay Figure one position to the left. This
button is active only, if the Figure Mode (see S2) is selected.
B4
Move the selected Bay Model or Bay Figure one position to the right. This
button is active only, if the Figure Mode (see S2) is selected.
Table continues on next page
1MRK 511 452-UUS Rev. A
Section 5
Configuration
Distributed busbar protection REB500
21
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Import a Bay Model from the Bay Model database to the left side of the
selected bay. This button is active only, if the Model Mode (see S2) is
selected.
B6
Import a Bay Model from the Bay Model database to the right side of the
selected bay. This button is active only if the Model Mode (see S2) is
selected.
B7
Import a Bay Model from the Bay Model database to the right end side of
the busbar. This button is active only if the Model Mode (see S2) is
selected.
B8
Remove the selected Bay Model or Bay Figure from the single-line
diagram. This button is active only if the Model Mode (see S2) is selected.
B9
Interconnect two selected adjacent busbar-connectors.
(for special applications only)
B10
Interconnect two selected distant busbar-connectors with →← reference.
(for special applications only, for example, ring busbars)
B11
Interconnect two selected distant busbar-connectors with ←→ reference.
(for special applications only, for example, ring busbars)
B12
Remove interconnection between two selected busbar-connectors.
(for special applications only)
B13
Make the invisible caption of one or several selected busbar-connectors
visible.
B14
Make the visible caption of one or several selected busbar-connectors
invisible
5.5.2
Process bus zones mode
GUID-C405A422-0A43-4B82-8EC8-405520BB4886 v3
See Section 9.31 and Section 9.32.
Section 5
1MRK 511 452-UUS Rev. A
Configuration
22
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
ANSI18000569 V1 EN-US
Figure 7:
Single-line diagram editor/ Process bus zones mode
Table 4:
Function of buttons
Button
Functions
B15
After pressing the button B15, the system checks whether all busbar
connectors are assigned to a bus zone. At the end of the test, a
message box indicates the test result.
In most cases, the bus zones are automatically assigned at the
moment the Bay Model is inserted into the single-line diagram. For
complex bus-configurations or after modifications on an existing
Setfile (re-configuration), a reassignment of the bus zones could be
necessary.
If not all busbar connectors are assigned to a bus
zones, the correct function of the REB500 system
cannot be guaranteed.
B16
By pressing the button B16 the complete bus zone arrangement is
reassigned. The reassignment might be necessary if an existing setfile
has to be extended with new bay models and new bus zones are
generated.
If the bus zone reassignment process is started
with button B16, the configurator tool also
performs the reassignment of the bus zone related
signals (I/Os) in the background automatically. Re-
configuration of a complex system (setfile) can
induce a changed signal configuration in
comparison to the original setfile. If necessary,
these bus-zone related signals have to be worked
over under the binary module configuration of the
Central Unit (CU).
1MRK 511 452-UUS Rev. A
Section 5
Configuration
Distributed busbar protection REB500
23
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Select Bay model
GUID-03705FA1-3C45-4695-B43B-922C2CA52C22 v3
See Section 9.14.
This menu appears if one of the buttons Import bay Model (Figure 6 B5-B7) is pressed.
Under the Select Bay Model window, a Bay Model (BM) can either be selected from the Base Bay
Models database (models created by ABB) or from the User Bay Models database (models created
by the user).
S4
S1
S3
V1
V2
S2
S4
S1
S3
V1
V2
S2
ANSI18000570 V1 EN-US
Figure 8:
Select Bay Model
Section 5
1MRK 511 452-UUS Rev. A
Configuration
24
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Function of selections
Selection
Function
S1
Activates the Base Model Database. The table of Bay Models (S4) containing the
BM’s created by ABB can be selected.
S2
Activates the User Model Database. The table of Bay Models (S4) containing the
BM’s created by the user (client) can be selected.
S3
If the option Filter Selection by Bay Model type is selected, the table of Bay
Models (S4) is filtered according the BM type. The filter criteria (number of
busbars) is automatically derived from the Plant data settings (see Figure 5).
If this option is not selected, all models of the respective database are visible.
S4
Table of bay models à The content of this table is controlled by the buttons S1-S3.
By selecting one of the table lines with a left mouse click, a BM is selected
(highlighted in blue colour) for import to the single-line diagram.
After pressing the button OK or Apply, the menu Import options appears for the
selected BM (see Section 5.5.4).
Table 6:
Indications
Selection
Function
V1
Single-line diagram of the selected BM → Selection made under S4
V2
Description of the selected BM → Selection made under S4
Example:
2SSF5A1
BBP,BFP
2 x single Pole
double busbar, F5A1→ BM identifier
Station protection functions contained in the BM
Tripping outputs configured in the BM → two sets of
single pole trip-ping contacts (2 x 3)
5.5.4
Import options
GUID-27683D70-F7C5-482C-8808-52E05B7522AF v2
See Section 9.16.
This menu appears, if under the menu Select bay Model (see Section 5.5.3), the button OK or Apply
is pressed. Now, the import-options of the BM can be selected by the user.
15000008-IEC18000615-1-en.vsdx
IEC18000615 V1 EN-US
Figure 9:
BM import options
1MRK 511 452-UUS Rev. A
Section 5
Configuration
Distributed busbar protection REB500
25
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
If the Voltage transformer option is selected, after pressing the button OK, the
imported BM includes the voltage transform configuration (VT is visible under
the single-line diagram).
If the BM selected under Select Bay Model (see Section 5.5.3) does not contain a
voltage transformer, this option is inactive (grey colored).
If the Voltage transformer option is not selected, the BM will in any case be
imported without voltage transformer. Resulting from this, no voltage
protection function and no disturbance recording for voltage channels is
available for this bay.
S2/ S5
For details about the import options of bay protection and the corresponding
Variant (L-V2), see Application Manual for bay protection functions REB500,
section Configuring bay protection using HMI500/ Integration of bay protection
S3
If the LMI LED configuration option is selected, after pressing the button OK,
the imported BM includes a pre-defined LMI-LED configuration.
If the LMI LED configuration option is not selected, the BM will be imported
without LMI-LED configuration and configuration table of LED’s on the LMI will
be empty. This table can be manually edited later (see Section 5.11).
S4
If the BU with PIO’s option is selected, additional 12 inputs and 6 precision
outputs are available as a Bay Unit variant. The precision outputs are based on
MOSFET technology and offer an improved tripping time performance.
5.6
Device structure
GUID-B354F1CC-B669-4091-8C5D-AF11E4AE67C9 v2
See Section 9.37.
Under the menu item Device structure, the system generated hardware device labels of the CU
and the BUs (so called ABB-References) can be edited with client specific labels.
IEC18000579-IEC18000579-1-en.vsdx
IEC18000579 V1 EN-US
Figure 10:
Device structure
Section 5
1MRK 511 452-UUS Rev. A
Configuration
26
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Function of selections
Selection
Function
S1
One of the hardware devices can be selected from the device table
Table 8:
Function of buttons
Button
Function
B1
After all Bay Models are placed in the single-line diagram and the CU device creator
process is completed, the device labels and the associated network in the
background is automatically sorted from BU01 to BUxx → Bay Unit on the left end
side to Bay Unit on the right end side of the single-line diagram in the correct
order.
After modifications (extensions) to an existing setfile, this sequence (label) of
devices might be unsorted. By pressing the button B1, the reassignment of the
ABB-References is started from left to right side of the single-line diagram (ABB-
Reference = logical device containing label, node Id, device Id of a Bay Unit).
If the reassignment of the ABB-References is started, the node-Id
and device-Id of the Bay Units and the Central Unit may change
compared to the original setfile.
B2
The button B2 opens the Edit device menu for the selected device.
IEC18000580-IEC18000580-1-en.vsdx
The user can fill in a device label which is
in accordance with the client system
labeling conventions. If one label is
changed, the labelling shall be worked
over for all devices.
If necessary, the hardware type of the
Bay Units can also be exchanged under
this menu item.
5.7
CU device creator
GUID-71CD124E-234C-4BE9-912F-AF38E2222576 v2
See Section 9.34.
After completion of the basic setfile configuration, the single-line diagram and the bay
configuration, the design wizard of the Central Unit shall be started by the button Next.
17000043-IEC18000614-1-en.vsdx
IEC18000614 V3 EN-US
Figure 11:
CU Hardware wizard
1MRK 511 452-UUS Rev. A
Section 5
Configuration
Distributed busbar protection REB500
27
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
After pressing the button Next, a windows containing the settings of the hardware options on the
Central Unit will appear:
S1
S2
S3
15000011-IEC18000363-1-en.vsd
IEC18000363 V1 EN-US
Figure 12:
CU Hardware wizard/ Options
Table 9:
Function of selections
Selection
Function
S1
Redundant Power Supply on CU
If this option is selected, the CU rack contains a second DC/DC converter for
redundant power supply.
S2
Power supply (voltage) type
Type 1 : 48-125VDC
Type 2 : 125-250VDC
S3
Set the number of BIO boards
1 BIO Board → 9 Inputs, 19 outputs
2 BIO Boards → 18 Inputs, 29 outputs
After pressing the buttons Next and Finish, the Hardware Wizard starts the build-process and
creates a hardware device for the Central Unit.
Section 5
1MRK 511 452-UUS Rev. A
Configuration
28
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
IEC18000581 V1 EN-US
Figure 13:
CU Hardware wizard/ finish HW build process
Once the build process of the CU device creator is completed, it can be repeated
again (for example, to reflect subsequent corrections resulting from system
configuration changes).
5.8
Network
GUID-C6C951BA-AC72-425D-A1AF-1554B0BB6955 v2
See Section 9.36.
This menu contains an overview of the BU device Id’s. Since the CU device creator process (see
Section 5.7) performs the complete network assignment (physically and logically), manual changes
are usually not necessary. If required (for example, for reordering the bays after initial
engineering), the ID can be adjusted manually, taking care that IDs have to be unique and can only
be used once.
1MRK 511 452-UUS Rev. A
Section 5
Configuration
Distributed busbar protection REB500
29
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
IEC18000582 V1 EN-US
Figure 14:
Network
5.9
Binary inputs/outputs
GUID-592398BD-6787-4AAE-8C52-DD6819B6E3C4 v1
For detailed information about setting and configuration, see REB500 Operating Manual, section
Binary inputs/outputs.
5.10
Event text configuration
GUID-8B10823C-8C93-47FE-B5C5-05A6CDE513D6 v1
For detailed information about setting and configuration, see REB500 Operating Manual, section
Event text configuration.
5.11
LMI LED...
GUID-B7842074-BCF2-4074-8EF9-0F6F11B83FAB v1
For detailed information about setting and configuration, see REB500 Operating Manual, section
HMI LEDs.
5.12
Disturbance recorder
GUID-33A13563-6556-4C5B-BD4F-D25CD987EF3E v1
For detailed information about setting and configuration, see REB500 Operating Manual, section
Disturbance recorder.
Section 5
1MRK 511 452-UUS Rev. A
Configuration
30
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Breaker failure protection
GUID-39AA7F6F-529C-4865-AC15-82BC2B921004 v1
For detailed information about setting and configuration, see REB500 Technical Manual, section
Breaker failure protection.
6.2
Time overcurrent protection
GUID-CC0F4526-743A-4DFC-A51E-4A1BA137D385 v1
For detailed information about setting and configuration, see REB500 Technical Manual, section
Time overcurrent protection.
6.3
End fault protection
GUID-771F4032-C12D-4521-B59A-AA36DCCBAD0F v1
For detailed information about setting and configuration, see REB500 Technical Manual, section
End fault protection.
6.4
CB pole discrepancy
GUID-3696D654-9319-4D17-BEC0-DA95191B0C71 v1
For detailed information about setting and configuration, see REB500 Technical Manual, section
CB pole discrepancy.
6.5
Overcurrent release
GUID-98246423-FB18-41BC-9E44-334BC03FC1BB v1
For detailed information about setting and configuration, see REB500 Technical Manual, section
Overcurrent release.
6.6
Voltage release
GUID-F5245633-5774-46E4-B2A7-11F24D92DF62 v1
For detailed information about setting and configuration, see REB500 Technical Manual, section
Voltage release.
6.7
Bay protection
GUID-E5A5C7C1-C916-4458-89B3-CCAA9656B4B6 v1
For detailed information about bay protection functions, configuration and technical data see,
REB500 Application Manual for Bay protection functions.
1MRK 511 452-UUS Rev. A
Section 6
Settings
Distributed busbar protection REB500
31
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
For detailed information about setting and configuration, see REB500 Technical Manual, section
Circuit breakers.
6.9
Disconnectors
GUID-2FE5781F-5572-44E0-A613-AFFB193F4F79 v2
For detailed information about setting and configuration, see REB500 Technical Manual, section
Disconnectors.
6.10
Current transformers
GUID-F024399D-3EA5-466F-8970-8E3237F8299A v1
For detailed information about setting and configuration, see REB500 Technical Manual, section
Current transformers.
6.11
Voltage transformers
GUID-30DABA81-43A8-4222-A46B-E9F26D72D257 v1
For detailed information about setting and configuration, see REB500 Technical Manual, section
Voltage transformers.
6.12
Voltage/ external release
GUID-5658FD39-6699-4B3F-AB1F-9B14053746F1 v2
For detailed information about setting and configuration, see REB500 Technical Manual, section
Voltage/ external release.
Supplementary information necessary for configuration
The under voltage release criteria is performed with the normalized voltage amplitudes. The
voltage limit UL is in relation to the defined nominal voltage UN of the corresponding voltage
transformer.
Abbreviations
•
UL Voltage limit
•
UN Nominal voltage (phase-phase)
The scaling of 1/√3 in case of phase to ground configuration (3-phase wye, 1-phase to ground) is
done internally by the algorithm.
For more information about settings and calculations, refer to the document Ground fault
protection for high voltage busbars, 1KHL 020319-Aen.
The number of activated measurements depends on the setting of the Bay Unit input voltage
scaling and on the setting of the network grounding:
Input scaling: 3-Phase Delta (independent of network grounding):
Section 6
1MRK 511 452-UUS Rev. A
Settings
32
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Input scaling: 3-Phase wye (solidly grounded or impedance grounded):
Ungrounded or Petersen coil:
Input scaling: 1-Phase to Phase (independent of network grounding):
, only one voltage measured
Input scaling: 1-Phase to Ground (independent of network grounding):
, only one voltage measured
Voltage transformer connections for U< measurement
ANSI18000583=ANSI18000583=1=en-us=Original.vsdx
ANSI18000583 V1 EN-US
Figure 15:
3-phase VT connections
1MRK 511 452-UUS Rev. A
Section 6
Settings
Distributed busbar protection REB500
33
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
ANSI18000584 V1 EN-US
Figure 16:
1-phase VT connections
6.13
System response
GUID-75759610-00B1-44EE-A8D5-DC31969CC915 v1
For detailed information about setting and configuration, see REB500 Technical Manual, section
System response.
6.14
Activate/ deactivate device
GUID-8EC20800-53B2-4754-AC2F-587628EBB38A v1
For detailed information about setting and configuration, see REB500 Commissioning Manual.
6.15
CB inspection
GUID-8DC1F221-26A4-4D4E-86EE-58D0F108A0F6 v1
For detailed information about setting and configuration, see REB500 Commissioning Manual.
6.16
Event memory
GUID-626D28D4-160D-4BC9-886E-6822342FD567 v1
For detailed information about setting and configuration, see REB500 Technical Manual, section
Event memory.
Section 6
1MRK 511 452-UUS Rev. A
Settings
34
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
For detailed information about setting and configuration, see REB500 Technical Manual, section
Time synchronization and the specific subsection Additional settings.
1MRK 511 452-UUS Rev. A
Section 6
Settings
Distributed busbar protection REB500
35
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
After starting the File verification tool, the content, structure and completeness of the REB500
setfile is checked.
This test routine shall be started after the setfile configuration has been completed. Once the test
run is finished, the HMI500 menu shows the test result. For a successful test run, the system
provides the information Number of errors: 0, Number of warnings: 0.
IEC18000585-IEC18000585-1-en.vsdx
IEC18000585 V1 EN-US
Figure 17:
File verification — no errors
If the test procedure locates a setfile inconsistency, then an error level and a short description of
the problem is given:
•
Error level 1 (minor error)
Such errors are caused by incomplete settings and configurations in the setfile (for example,
CU device creator not started). An error level1 is mostly accompanied by errors level 2 and 3.
These error messages (side effect) should be cleared, after the errors level 1 are fixed. The
repetition of the file verification shall prove the setfile again.
•
Error level > 1 (major error)
If errors level >1 should remain after the errors level 1 are fixed, the setfile has an important
inconsistency, which cannot be solved by the user (engineer) of the HMI500 Tool, please
contact your HMI500 supplier for clarification.
It is mandatory, to start the test run after the setfile configuration has been
finished.
7.2
Reports
GUID-2842D78B-C0D7-408A-A262-F618DB28EAFB v1
For detailed information about setting and configuration, see REB500 Operation Manual, section
Reports.
1MRK 511 452-UUS Rev. A
Section 7
Tools
Distributed busbar protection REB500
37
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Export SCS data
GUID-12267C3B-0001-4923-9A7F-C7F490ECDE23 v1
For detailed information about setting and configuration, see REB500 Operation Manual, section
Export SCS data.
7.4
Export Bay Model catalogues
GUID-D48C80C1-58D0-43A8-9DB0-F595A3C9F146 v1
The setfile engineer can save (export) a Bay Model catalogue in the PDF file format at any time.
Depending on a selection, this catalogue contains Bay Models from the Base model database, or
the User model database. The catalogue comprises the selected models filter criteria: busbar
type(s) or all models.
IEC18000586-IEC18000586-1-en.vsdx
IEC18000586 V1 EN-US
Figure 18:
Export bay models
7.5
Default values
GUID-2F6D2B8F-8CC4-43D6-8978-09A6255AF2B2 v2
See Section 9.9.
Section 7
1MRK 511 452-UUS Rev. A
Tools
38
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
IEC18000587 V1 EN-US
Figure 19:
Default values
In this window, the default values common for all bays can be adjusted (the adjustment has a
system global validity). If the entries are made during the initial setfile configuration phase (prior
to the Bay Model engineering under the window single-line diagram), they are active for the
further configuration process.
If the entries are made at a later stage (after the Bay Model engineering phase), the settings have
to be confirmed with Change value of all (group individually).
Of course, these values can also be locally adjusted (individually) for each bay.
7.6
Bay model viewer
GUID-AA831828-522B-4723-A99B-144E75DD01E5 v3
During the configuration phase of the single-line diagram, the user can select pre-configured Bay
Models (see Section 5.5.3). The menu item BM Mode viewer, provides a preview of the available
Bay Models (library).
1MRK 511 452-UUS Rev. A
Section 7
Tools
Distributed busbar protection REB500
39
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
ANSI18000588 V1 EN-US
Figure 20:
Bay model viewer
Table 10:
Function of selections
Selection
Function
S1
Preview of Base bay models(created by ABB)
S2
Preview of User bay models (created by users)
S3
Table of bay models: The content of this table depends on the selection S1/S2.
By selecting one table row (one Bay Model) with a left mouse click, the Bay Model
viewer provides a preview of the single-line diagram as well as a short
description.
Table 11:
Indications
Selection
Function
V1
Single-line diagram of the selected BM → Selection made under S3
V2
Description of the selected BM → Selection made under S3
Example:
2SSF5A1
BBP,BFP
2 x single Pole
double busbar, F5A1 → BM identifier
Station protection functions contained in the BM
Tripping outputs configured in the BM → two sets of
single pole trip-ping contacts (2 x 3)
7.7
Operator mode
GUID-F2E37B70-AB2E-4638-93A1-B811142498EB v3
If the HMI500 software is started under the Configurator Mode, the user can change over to the
Operator Mode at any time. The login process is described under Section 3.
Section 7
1MRK 511 452-UUS Rev. A
Tools
40
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
ANSI18000288 V1 EN-US
Figure 21:
Change over from Configurator mode to Operator mode
7.8
Settings
GUID-BAC41B41-8392-49C3-86F5-A23684D5137C v1
For detailed information about setting and configuration, see REB500 Operation Manual, section
Settings.
1MRK 511 452-UUS Rev. A
Section 7
Tools
Distributed busbar protection REB500
41
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Annex A | Configurator mode - Definitions
GUID-A7A2496D-6635-4F72-9217-F1AF44852B8B v2
1MRK 511 452-UUS Rev. A
Section 8
Annex A | Configurator mode - Definitions
Distributed busbar protection REB500
43
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
IEC18000341 V1 EN-US
See Section 4.
Section 8
1MRK 511 452-UUS Rev. A
Setfile
44
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Configuration models (1)
GUID-817BCAF9-EB57-4626-B854-D963FA2D098B v3
Bay Model → (BM)
The Bay Model is a logical image representing the complete configuration of a bay in a
REB500 setfile. It contains the Bay Figure and the Bay Unit Model.
Bay Figure → (BF)
The Bay Figure contains the bus image of a bay (including the switchgear objects,
connections and the busbar connectors)
Bay Unit Model → (UM)
The Bay Unit Model contains:
•
the device type of the Bay Unit
•
the image of the switchgear objects (derived from the Bay Figure)
•
the licensed functions (pre-configured with basic settings → to be worked over)
•
the basic I/O configuration settings → to be worked over
Bay unit
model
FUNCT.
I/O
Objects
Bay Unit
Bay unit
model
FUNCT.
I/O
Objects
Bay Unit
Bay unit
model
FUNCT.
I/O
Objects
Bay Unit
ANSI18000616 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 8
Annex A | Configurator mode - Definitions
Distributed busbar protection REB500
45
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Configuration models (2)
GUID-FF31106B-B069-4A67-A0A4-DA6D0298D52A v3
FUNCT.
I/O
Objects
A B
B
ES
C
RE
B 50
0
Read
y
Star
t
Trip
Clea
rHel
p
Men
u
LR
ABB
32
1
I
A B
B
ES
C
RE
B 50
0
Read
y
Star
t
Trip
Clea
rHel
p
Men
u
LR
ABB
32
1
I
Bay Unit
Bay Model containing more than one Bay Figure
A Bay Model can contain more than one Bay Figure (for example, a feeder bay +
bus section disconnectors), while only one Bay Unit Model (one Bay Unit) is used.
This under the condition, that the following limitations are not exceeded.
Maximum per bay unit:
•
1 CB object
•
1 CT object (represents 4I-inputs → for example, I3ph + Iground)
•
1 VT object (represents 5U-inputs → for example, U3ph + UBB1 + UBB2)
From the Bay Model side, the number of disconnectors is not limited, if the
number of binary inputs is sufficient.
ANSI18000617 V1 EN-US
Section 8
1MRK 511 452-UUS Rev. A
Annex A | Configurator mode - Definitions
46
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Configuration models (3)
GUID-0898CF32-0B9D-4519-9DB1-9E05EF2B64C9 v3
FUNCT.
I/O
Objects
FUNCT.
I/O
FUNCT.
I/O
Objects
Objects
Bay Unit 2
Bay Unit 3
Bay Unit 1
FUNCT.
I/O
Objects
FUNCT.
I/O
FUNCT.
I/O
Objects
Objects
Bay Unit 2
Bay Unit 3
Bay Unit 1
Bay Model containing more than one Bay Figure AND more than one Bay Unit
Model
This type of Bay Model, is called Multiple Bay Model (MBM).
➢ For example, a Multiple Bay Model for a complete 1 ½ - breaker bay
Multiple Bay Models are allowed, if following limitations are not exceeded:
•
Number of CB objects number of bay units
•
Number of CT objects number of bay units
•
Number of VT objects number of bay units
•
From the Bay Model side, the number of disconnectors is not limited, if the number of
binary inputs is sufficient.
ANSI18000618 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 8
Annex A | Configurator mode - Definitions
Distributed busbar protection REB500
47
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Bay Figure (BF)
GUID-67242FB2-62F0-4757-AF7C-0E579ABECD15 v3
Bay Figure BF
The bay figure is a part of the
single-line diagram. It contains
the Bay Objects (BO) as well as
the Bay Topology (BT).
Bay internal
connect
Topological
connections in a BF
Bay Node
Place holder for the (logical)
bay label
QB1
QB2
BI1
BU1
=Trafo 05
QB1
QB2
BI1
BU1
=Trafo 05
Bay Topology BT
Busbar Connectors
Connection points between
the Bay Fiures
Circuit Breaker (CB)
two state objects → Open/ Closed
(inclusive CB close command)
Voltage Transformer (VT)
analogue object → UL1, UL2, UL3, UL0
Bay Objects BO
Disconnectors
two state objects → Open/ Closed
Current Transformer (CT)
analogue object → IL1, IL2, IL3, IL0
ANSI18000619 V1 EN-US
Section 8
1MRK 511 452-UUS Rev. A
Annex A | Configurator mode - Definitions
48
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Bus interconnections (1)
GUID-74BAF243-DBED-4E7A-ADA5-104E131B70EF v3
QB1
QB2
BI1
BU1
=Line 01
QB1
QB2
BI1
BU1
=Trafo 02
The (logical) connections between
adjacent Bay Models (adjacent Busbar
Connectors.
If the number of bus connectors of
adjacent Bay Models is identical, these
interconnects are automatically added
by the tool
Bus Interconnections
QA1
ANSI18000620 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 8
Annex A | Configurator mode - Definitions
Distributed busbar protection REB500
49
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Bus interconnections (2)
GUID-C24C8E53-7F36-4090-92AB-D0CEAB145EAD v3
If the number of Bus Connectors of adjacent
Bay Models is not identical (for example,
single bus and double bus Bay Models within
the same single-line diagram), Bus
Interconnections have to be added manually.
For manual insertion of a Bus Interconnection,
select two Busbar Connectors and use the
Connect button.
ANSI18000621 V1 EN-US
Section 8
1MRK 511 452-UUS Rev. A
Annex A | Configurator mode - Definitions
50
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Annex B | Configurator mode - System configuration
GUID-86AFE642-693E-4673-AEEB-583AAB379836 v2
9.1
Preparations (1)
GUID-68BFB64E-1F1E-4671-B50D-0D7ADB67D904 v2
Ordering code for Central Unit
Ordering code for Bay Unit
Ordering code for Central Unit
Ordering code for Bay Unit
Data acquisition
Before starting the setfile configuration, the relevant
system data shall be collected and the Bay Unit /
Central Unit hardware as well as their functional scope
shall be defined (evaluation of the order codes).
For the evaluation of the order codes, the tables
attached to the REB500 Product Guide shall be used.
Ordering code for Central Unit
Ordering code for Bay Units
IEC18000622 V2 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
51
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
It is mandatory for the configuration of a setfile to have a binding single-line diagram of the
substation (latest version).
The bus image implemented in the REB500 system will be based on this diagram.
ANSI18000828 V1 EN-US
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
52
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Starting HMI500 Configurator mode
For the setfile configuration, the HMI500 has to be
started under the Configurator mode.
HMI500 Setfile Editor
Under the setfile editor, the complete system
configuration (setfile) can be configured.
IEC18000829 V1 EN-US
See Section 3.
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
53
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Sequence of configuration
GUID-06B24AFF-D8CE-4B68-A959-CA4E5E67E604 v2
(1) System configuration
The system configuration includes the global system
data. The related inputs have to be made once per
system (× 1).
(2) Bay configuration
The bay configuration includes the bay (Bay Model) individual
data. The related inputs have to be made 'n' times per system (x n).
n = number of different Bay Models per system
Sequence of configuration
As a guideline for the sequence of work items, the
setfile engineer can follow the sequence of menu
items.
IEC18000830 V1 EN-US
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
54
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Start configuration - File-New (1)
GUID-991B7F63-BDD5-425E-AEC8-82AA43F88365 v2
(2) File name
Save the new setfile under a new file name. The ABB
System Number shall be used for the file name (5221
in this example).
(1) File New…
Create a new setfile
IEC18000831 V1 EN-US
See Section 4.1 and Section 4.1.1.
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
55
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Start configuration - File-New (2)
GUID-55AD2BD9-43E3-46F2-AC5E-DAC9505ED01F v2
Default system settings
After pressing the Save button, three
windows containing the basic
(default) system settings will appear:
1. System Installation
2. Plant Data
3. Default Values
The default system data shall be
worked over before starting any
further detail configuration.
IEC18000832 V1 EN-US
See Section 4.1.3.
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
56
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Initial (default) settings (1)
GUID-E9DE260C-C724-4CB3-92D9-0D0A9D65B506 v2
Revision information
The revision index information is not used
during the configuration phase. It has to be
filled in for changes during the service phase of
the system (for example, setting changes in
the protection).
Version information
The first version of the setfile shall get a preliminary index, for example, 0.10.
To confirm a new index, press OK, or Apply button. Now, the HMI500 tool saves a
new version of the setfile under a new name. The original file name (for example,
5221.mdb) is extended by the version part (for example, 01 522101.mdb).
Licensed components
The licensed components (protection
functions) shall be activated under this
section.
After the OK, or Apply button is pressed, the
sub-menu items of the selected (licensed)
protection functions become visible under the
main menu Settings.
IEC18000833 V1 EN-US
See Section 5.1.
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
57
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Initial (default) settings (2)
GUID-2B389032-7C6C-4E6A-ACBA-259E7B78F7C4 v2
Plant data/ Busbar data
The busbar specific data shall be entered
under this window:
(1) Rate voltage ' Busbar voltage ph-ph
(2) Rated frequency
(3) Grounding ' Network grounding
(4) Busbar ' Busbar configuration
- single up to quadruple busbar
- optional transfer bus
- 1 ½ breaker system
IEC18000834 V1 EN-US
See Section 5.2.
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
58
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Initial (default) settings (3)
GUID-F223C83F-65A7-4B21-ACB2-2B947AFA8005 v2
Recovery time
For detailed information, see REB500
Application Manual section Breaker reclaim
time.
Battery voltage
This setting is valid for:
Aux. DC voltage of BU/CU voltage supply
Aux. DC voltage of BU/CU binary inputs
General
The default values are valid for the complete protection system.
If the entries are made during the initial setfile configuration phase
(prior to the Bay Model engineering under the window Single-line
diagram), they are valid for the further configuration process.
If the entries are made at a later stage, they have to be confirmed
with Change value of all (group individually) to get a system-wide
validity.
CT (VT) ratio
Secondary values of current and voltage
transformers (If VTs are used for protection
system)
IEC18000835 V1 EN-US
See Section 7.5.
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
59
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Initial (default) settings (4)
GUID-AB11128F-B14D-435A-86C1-463AF48F2BB2 v2
Max. recording time
This disturbance recorder provides two
options for the setting of the recording
time standard and extended.
For detailed information, see REB500
Product Guide, table Disturbance
recorder.
Disturbance recorder licence
The default values are valid for the
complete protection system.
Voltage channels
As an option, the voltage channels can be
implemented to disturbance recording
(for bay units only).
IEC18000836 V2 EN-US
See Section 7.5.
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
60
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
The default setting is no interface. Under th
setting, no protocol specific settings are
visible.
If an inter-bay bus (IBB) is selected, the
particular protocol specific settings are
visible.
Max. two IBB configurations (connections) c
be realized per system.
IBB1/ IBB2
For detailed information about IBB
settings, see REB500 Communication
Protocol manuals.
IEC18000837 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
61
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SCS Diff Current Parameters
The settings shall be worked over only
after the configuration of single-line
diagram has finished.
For detailed information about SCS Diff
Current Parameters setting, see REB500
Communication Protocol Manual, IEC 61850.
IEC18000838 V1 EN-US
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
62
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF - Start
GUID-5BBDF823-4C12-44BC-8BB2-93F0E0A3CAED v2
(2) Import model from database (DB)
First model to be inserted into the single-line
diagram (SLD) with the button Copy Bay Model.
(1) Model Mode
Before starting SLD-CONF, select Model
mode.
Configuration of the single-line diagram
SLD-CONF
IEC18000839 V1 EN-US
See Section 5.5.1.
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
63
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF Select BM (1)
GUID-DB7EAD24-5A59-44FF-ACBF-870009C593A5 v3
Now, the Select Bay Model window appears.
ANSI18000840 V1 EN-US
See Section 5.5.3.
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
64
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — Select BM (2)
GUID-031EADBA-D56A-4496-833A-D8E0BDCE4467 v3
(1) Bay Model DB
Use Base Bay Models
(Models created by ABB) for
the BM selection.
(2) Filter selection...
This selection filters the Base Bay
Models according to the number of
busbars (see settings made under
Plant data → Busbar data).
(3) Select BM from table
Select the BM, suitable for the
first bay of the single-line
diagram.
(4) Press OK.
ANSI18000841 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
65
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — Select BM (3)
GUID-64DD32F2-7DCE-47ED-BFA4-957F86F875D8 v3
(1) Select BM from table
The 'Bay model import options' menu
appears now, providing the following
selection items:
→ BM to be imported with or without
voltage transformer
(If a disturbance recorder with voltage
option, or any voltage function is used,
this item must be selected)
→ BM to be imported with or without
PIO's
(6 precision outputs per BU)
→ BM to be imported with a set of bay
protection functions (Variant available '
"L-V2")
→ BM to be imported with or without
LMI LED configuration
(If the default LED configuration shall be
applied for the local HMI, this item has to
be selected)
(2) Press OK.
ANSI18000842 V1 EN-US
See Section 5.5.4.
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
66
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — Select BM (4)
GUID-6E2978E7-11F2-45E7-A252-97F4C09C0045 v3
Now, the first Bay Figure is imported into the
single-line diagram.
ANSI18000843 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
67
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — adjust BM (1)
GUID-D92282C9-E7D9-478D-9191-342D7ED33C47 v3
Menu Configuration-Device structure (hardware object)
Menu Configuration-Binary module (I/O signals/ configuration)
Menu Configuration-LMI LED configuration
Menu Configuration-Disturbance recorder
Setting menus of the protection
functions and switchgear objects.
Note: While inserting the Bay Figure into the
single-line diagram, the HMI500 tool has
implemented the complete Bay Model under the
related Menus automatically.
ANSI18000844 V1 EN-US
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
68
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — adjust BM (2)
GUID-2FBBC426-D6AD-4A04-BF81-7204ADDE3532 v3
Menu Configuration-Device structure (hardware object)
Menu Configuration-Binary module (I/O signals/ configuration)
Menu Configuration-LMI LED configuration
Menu Configuration-Disturbance recorder
Setting menus
Note: Before duplicating the (first) Bay Model, it is
recommended to work over the bay specific configuration
and settings (menus) with the user (client) setting values
(if different from ABB default setting).
IEC18000845 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
69
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — export BM (1)
GUID-101BAFAB-B6F3-4CB9-B93C-3FDA543B1537 v3
(2) Press the Copy selected BM to user
model database button .
(1) Select the rectangular box of
the Bay Figure with a left mouse
click.
Now, the BM, which is custom made for
a line bay can be copied to the user
model database (template database).
ANSI18000846 V1 EN-US
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
70
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — export BM (2)
GUID-DD8E11A1-7F07-4318-8B92-7A5EA6398258 v3
(1) Define a BM name.
(3) Press OK to write the BM to the
user model database.
(2) Provide a BM description.
ANSI18000847 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
71
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — export BM (3)
GUID-06E59B02-4BE0-4A93-9318-83098F1E2F70 v3
Now, the typical Bay Model My Line 380kV, which is saved under the user model database is finished.
Note: The user model database and consequentially the Bay Model My Line 380kV can also be used for other stations.
ANSI18000848 V1 EN-US
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
72
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — typical bays (1)
GUID-5E5C0425-6D0F-4B68-9131-D7C59100A6FE v3
Configuration steps from
8.14 SLD-CONF → Select BM (1)
to
8.22 SLD-CONF → Export BM (3)
are ready
Repeat the configuration
steps done for the typical line
feeder My line 380kV for each
typical bay of the station.
Typical bays of this station
are:
•
Line 380 kV
•
Trafo 380 kV
•
Buscoupler 380kV
•
Line 380 kV including
section Disconnector
Configuration steps from
8.14 SLD-CONF → Select BM (1)
to
8.22 SLD-CONF → Export BM (3)
are ready
Repeat the configuration
steps done for the typical line
feeder My line 380kV for each
typical bay of the station.
Typical bays of this station
are:
•
Line 380 kV
•
Trafo 380 kV
•
Buscoupler 380kV
•
Line 380 kV including
section Disconnector
ANSI18000849 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
73
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — typical bays (2)
GUID-6B80FE3B-0CCB-4665-BA44-3B2D3BD95913 v2
The User Bay Model database
contains each typical bay of the
station now.
IEC18000850 V1 EN-US
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
74
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — completion of single-line diagram
GUID-7D58F271-2EB4-4A9E-A9AD-4C91611AEEE5 v3
Now, the single-line diagram shall be completed
step by step by importing the typical Bay Models
from the User Bay Model database.
Import buttons to be used.
ANSI18000851 V1 EN-US
9.26
SLD-CONF — Positioning of bay figures
GUID-3FE8F16D-6293-4CB6-8FBD-97BF8CBFB112 v3
In case of Multiple Bay Models, change over to
Figure mode, select the relevant Bay Figure (for
example, bus section disconnector figure) and
move it to the appropriate position of the
single-line diagram.
Figure mode
Moved Bay Model
Bay Figure to be moved.
Multiple Bay Model
Move buttons
ANSI18000852 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
75
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — Bus labels (1)
GUID-DF3E5306-8B79-4EAF-961D-1AA1A873B56C v3
(1) Select a Busbar Connector
After a left mouse click the
connector point is highlighted in
red colour.
(2) Make labels visible
Now, the button Bus label visible
shall be pressed.
After all Bay models have been imported to
the SLD, the busbar labels shall be made
visible.
ANSI18000853 V1 EN-US
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
76
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — Bus labels (2)
GUID-3896871F-1800-4693-A547-8F400A37D261 v3
Now, the Bus Label is visible.
It is recommended to make all necessary Bus Labels
visible now.
Note: At least one Bus Label should be visible at the end of each zone.
ANSI18000854 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
77
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — Labels (1)
GUID-E013E5AA-1B61-45E3-AEC6-4A60631874DA v3
(2) Change label
Now, the Change label dialog box
appears.
(1) Select a label
With a right mouse click, the
button Change label appears.
Press Change label, now.
Each text (caption) of the single-line
diagram can be worked over by the user.
(3) New label
Write a new label (client
label) and press OK.
ANSI18000855 V1 EN-US
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
78
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — Labels (2)
GUID-E14D2549-22BD-47FB-B6FF-08056C0C90C1 v3
Note: The single-line diagram configured in the
REB500 setfile should now reflect the single-line
diagram of the station.
Note: The single-line diagram configured in the
REB500 setfile should now reflect the single-line
diagram of the station.
ANSI18000856 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
79
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — Bus zone assignment (1)
GUID-94ACBEC7-7838-4AF5-838D-82390F51F8A0 v3
(1) Process bus zones mode
After the configuration of the
single-line diagram is finished,
switch over to the process
Process bus zones mode.
(2) Bus zone assignment
Under this mode, the user can check
whether the system has (automatically)
assigned each busbar connector to a
bus zone.
ANSI18000857 V1 EN-US
See Section 5.5.2.
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
80
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF - Bus zone assignment (2)
GUID-48883315-F0A3-40F6-9B8E-B2BEC1BD7D0B v3
Check Bus zone assignment
After pressing this button, the
software checks whether the bus
zone assignment is completed or
not.
→ The result of the check is
indicated in a separate window.
Note: For the initial configuration of a standard bus (single-line diagram), the bus zone
assignment is performed completely by the configurator tool.
For complex bus configurations, or for reconfiguration (extension) of existing setfiles,
it might be necessary to Reassign Buszones.
ANSI18000858 V1 EN-US
See Section 5.5.2.
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
81
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
SLD-CONF — Bus zone assignment (3)
GUID-84006325-F3A6-4ACB-8AF6-13E84E6702AD v3
Reassign Buszones
Press button Reassign Buszone only
if the assignment made by the
system is incomplete.
Warning: If the bus zones reassignment process is started with the button "Reassign Buszones", the configurator
tool also performs the reassignment of the bus zone related signals (I/Os) in the background. The reconfiguration
of a complex system (setfile) can induce a changed signal configuration compared to the original setfile. These (bus
zone related) signals have to be worked over under the binary module configuration of the central unit (CU) now.
ANSI18000859 V1 EN-US
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
82
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
CU device creator (1)
GUID-2B881384-B924-4FAE-A98E-0C398157C0E7 v2
The hardware design wizard starts the configuration process
of a Central Unit suited for the bays (Bay Units) configured
under the single-line diagram.
In addition the CU specific hardware (settings) shall be
defined:
Redundant power supply on CU (or not)
Power supply type (voltage range)
Set the number of BIO boards (number of I/O's)
Press Next.
CU device creator
After the basic setfile configuration, the single-line diagram and the
bay configuration are completed, the design wizard for the Central
Unit (CU) shall be started.
Press Next.
IEC18000860 V1 EN-US
See Section 5.7.
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
83
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
CU device creator (2)
GUID-B427F50D-C0B0-414F-80C5-A7B19E713AE9 v2
The Build Process completes now the configuration of the CU.
The Build Process creates a new CU including the specified
hardware options:
Redundant power supply on CU (or not)
Power supply type (voltage range)
Set the number of BIO boards (number of I/O's)
Press Finish.
After the build process of the CU device creator was started once,
it can be repeated again (for example, to reflect subsequent
corrections resulting from system configuration changes).
IEC18000861 V1 EN-US
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
84
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
CU device creator (3)
GUID-8A0D092A-3025-447E-B997-90C429711DB5 v2
Network
Additionally to the CU device, the Build Process defines the
device allocation of the REB500 process bus (network)
including the Device IDs of the Bay Units.
IEC18000862 V1 EN-US
See Section 5.8.
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
85
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
(2) Edit device
Fill in a device label which is in accordance
with the client system labelling
conventions.
Work over devices line by line and press
OK.
Device structure
Under the menu item Device Structure, the system
generated device labels of the CU and the Bus can
be worked over with client specific labels.
(1) Select device line
and press Edit.
IEC18000863 V1 EN-US
See Section 5.6.
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
86
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
(2) Check test result
The test result must be:
Number of errors: 0
Number of warnings: 0
File verification
After the configuration of the setfile has been completed,
it must be verified. The File verification tool checks the
plausibility and completeness of the bus configuration,
hardware-configuration and the assignments.
(1) Start verification
Press Start.
Warning: Of course, the file verification tool can check the setfile internal configuration only. It is the responsibility of
the user to check that the REB500 configuration is in accordance with the configuration of the protected station.
IEC18000864 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
87
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
Final adjustment of the setting menus
The settings shall be changed, if the default values generated by the
configurator tool are not in accordance with the station parameters.
IEC18000865 V1 EN-US
See Section 6.
Section 9
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
88
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
The setfile is now ready for a download to the protection system
REB500 (target).
A download can be realized under the HMI500 Operator mode only.
Setfile
xxxxxx.mdb
IEC18000866 V1 EN-US
1MRK 511 452-UUS Rev. A
Section 9
Annex B | Configurator mode - System configuration
Distributed busbar protection REB500
89
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
1MRK 511 452-UUS Rev. A
Annex B | Configurator mode - System configuration
90
Distributed busbar protection REB500
Engineering manual
© 2020 Hitachi Power Grids. All rights reserved
ABB Power Grids Sweden AB
Grid Automation Products
SE-721 59 Västerås, Sweden
Phone +46 (0) 10 738 00 00
https://www.abb.com/protection-control
© 2020 Hitachi Power Grids.
All rights reserved.
Scan this QR code to visit our website
1MRK 511 452-UUS