Clevertronics CLP LIFELIGHT PRO Installation And Maintenance Instruction
Read Online
Read the Clevertronics CLP LIFELIGHT PRO Installation And Maintenance Instruction online using the built-in PDF viewer.
Text of the manual
8 June 2021
UK Instruction Sheet Template – V1.1 – Updated: 20/11/2020
Zoneworks, HIVE and DATA Monitored Options
Fittings with part numbers -ZW, -HVG, -DATA are fitted with Zoneworks communications modules
(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power
cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated
data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also
be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor,
coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a
single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides
a multifunction indication of the status of the fitting during testing and normal operation:
Option
State
LED Operation
ZW, HVG, DATA
Commissioned
LED on Solid (Green)
ZW, DATA
Un-commissioned
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
HVG
Un-commissioned
With network connectivity
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
HVG
Un-commissioned
Without network connectivity
Batt plugged-in: yellow 250mS, green
250mS, yellow 250mS, green 250mS,
green 1s
Batt unplugged: red 250mS, off
250mS, red 250mS,off 250mS, off 1s
ZW, DATA
Emergency Light Test In Progress
LED flashes at yellow 5s , 0ff 1s
HVG
Emergency Light Test In Progress
LED flashes at yellow 1s , 0ff 1s
In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)
DALI EM Option
Luminaires with part numbers having -DALI are fitted with DALI modules (nodes) that facilitate connection
and integration to 3rd Party Lighting Control Systems. Before installing the -DALI fitting please confirm
that the Lighting Control System has the capability to monitor DALI Emergency Luminaires. The -DALI
fitting will be addressed and configured into the control system by the Lighting Control System
Commissioning Technicians and not Clevertronics
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
“IDENTIFY COMMAND”
Fitting goes into emergency mode for 10 seconds
A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 5/6way
“structured wiring system” lead and plug facilitating the power and DALI connection. DALI connections
are marked as Da Da.
Clevertest and Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red
flashing for a period up to 2 minutes.
Maintained fittings (CLIFEM-PRO-xx) cannot be scanned with a camera using the Clevertest Plus App
as the maintained light source interferes with the camera scanning function. To register the fitting
manually enter the serial number from the QR code and visually read the test result and enter manually
into Clevertest Plus App.
CLP™ LIFELIGHT PRO Surface Mount
Emergency Luminaire
Installation & Maintenance Instruction Leaflet
NOTE: Standard product codes with this symbol
are enabled with Clevertest Plus capability. Please refer to the
operation guide supplied with the product for details.
Australia (Head Office)
Website: www.clevertronics.com.au
Email: [email protected]
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
IP20
UK OFFICE
Website: www.clevertronics.co.uk
362 Stockley Close
West Drayton UB7 9BL
Phone: 01895 430 255
Models:
CLIFEz-PRO-aa-SMC-bb-xx-yy
Testing :
Options:
Manual Test
xx = Blank
Maintained
z = M
Zoneworks
xx = ZW
Non-Maintained
z = Blank
Z/W DATA
xx = DATA
Colour, Black
yy = BLK
Zoneworks Hive
xx = HVG
Warm White
aa = WW
DALI Registered xx = DALI
Switched Live(Active) bb = SA
Spare Parts:
1550230
BATT:LP 3.2V 6400mAh.200mm lead.Brkt.
1100811
Lifelight Pro,Head Assem,Ld:280mm,Round,Gen2,LT (Daylight White)
1100809
Lifelight Pro Head Ass,Ld:280mm,Rnd,Gen2,Blk,LT (Daylight White, Black)
1100821
Lifelight Pro,Head Assem, Ld:280mm,Rnd,WW,Gen 2 (Warm White)
1100808
LifelightPro,HeadAss, Ld:280mm,Rnd,WW,Gen 2,Blk (Warm White, Black)
UKM02370030002
CLIFE-PRO-SMS-CKIT-IC2-475, Lifelight Pro, Control Only, 475mA, LP, CTP, OWC
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant British Standards.
8 June 2021
UK Instruction Sheet Template – V1.1 – Updated: 20/11/2020
Installation:
This CLIFE-PRO-SMC Surface Mount Emergency Luminaire can be installed on solid or T-BAR ceilings
or used to replace an existing unit.
•
Locate the installation position.
•
Refer Images and Dimensions below for the mounting hole dimensions.
•
Pre-drill mounting holes.
•
Mount ceiling mounting bracket and use suitable fixings to secure the bracket into the pilot holes.
•
Bring in supply cables via the top entry hole (surface mount conduit entry).
•
Terminate the supply cables to the L, N & E terminals (for -SA, terminate the Switched Live(Active)
to Lsw, for –DALI or –DATA fittings terminate the DALI or DATA cable to the terminals marked Da
Da or DATA).
•
Install Cylinder containing the control gear, ensuring to connect the supply cable to the connector
from the supply terminal block.
•
Locate and fit securing screws on sides.
•
If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four
Segment Marking on the product will include an ‘’F’’ in third segment block.
•
For -HVG fittings, screw in the supplied antenna to the antenna connector accessible on the
external surface.
•
Wall mounting bracket optional, comes with additional instructions.
•
The luminaire should be positioned so that prolonged staring into the luminaire at a distance closer
than 350mm is not expected.
Images and Dimensions:
Ceiling Mounting Bracket
Optional Wall Mounting Bracket
Luminaire Dimensions
245mm (L) x 128mm (D)
Mounting Hole Dimensions
35mm x 90mm
Mounting Hole Dimensions
70mm x 70mm
Weight
0.7kg
Weight
1.9kg
Part Number White
2740045
Part Number Black
2740048
Note:
This luminaire (with reinforced insulation between control/LED terminal and AC supply) contains non-
user replaceable light source and battery - to be replaced (if required, refer installation instructions for
battery replacement) by Clevertronics service personnel/agents or a registered electrician.
Battery Replacement:
1.
Prior to any work, isolate the power to the luminaire that requires battery replacement.
2.
Open the fitting by removing the securing screws on sides, support cylinder while removing screws.
3.
Disconnect the Supply Connector. The Luminaire is now isolated from the Mounting Bracket.
4.
Remove screws from Top Bar and the Gear Tray assembly can be removed.
5.
Remove the Battery Connector from the Emergency Driver.
6.
Remove the battery from the gear tray by removing mounting screws.
7.
Replace battery, re-install screws and connecter to Emergency Driver.
8.
Reinstall the Gear Tray, ensure the Top Bar is aligned at 90 degrees (1/4 turn) to the side securing
screw holes.
9.
Reconnect the Supply Connector and fit the securing screws on sides to secure the luminaire into
the Mounting Bracket.
Testing Procedure:
When the luminaire is connected to the un-switched Live, it must be allowed to charge the battery for at
least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the following tests:
•
The emergency lamp must illuminate for at least 180 min after disconnection from the mains. The
results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all
times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the
situation and once completed, the unit must pass a subsequent test.
•
Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On.
•
Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-
maintained operation).
Below are a list of common problems and their possible causes:
Fault:
The Green LED indicator is not illuminated.
Check:
A.C. is connected and is turned on.
Battery is connected.
Test Switch for damage.
Fault:
Lamp does not illuminate in emergency mode.
Check:
A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode, but only stays on for a short period.
Check:
Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The Li-ion battery in the Exit & Emergency Unit has been selected to give
excellent long life performance in a controlled IEC 60598-2-22 testing environment. Excessive battery
cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty
claims, as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
https://clevertronics.co.uk/product-warranty-statement/