Endress+Hauser Levelflex FMP53 Brief Operating Instructions
Read Online
Read the Endress+Hauser Levelflex FMP53 Brief Operating Instructions online using the built-in PDF viewer.
Text of the manual
Brief Operating Instructions
Levelflex FMP53
Guided Level-Radar
These Instructions are Brief Operating Instructions; they do not replace the
Operating Instructions included in the scope of supply.
For detailed information, refer to the Operating Instructions and other
documentation on the CD-ROM provided or visit "www.endress.com/
deviceviewer".
KA01108F/00/EN/01.12
71163452
Table of contents
Levelflex FMP53
2
Endress+Hauser
Table of contents
1
Important document information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Document conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
2
Basic safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Requirements concerning the staff . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
2.2 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
2.3 Workplace safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
2.4 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
2.5 Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
3
Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Compact device Levelflex . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
3.2 Electronics housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
4
Incoming acceptance and product identification . . . . . . . . . . . . . . . . . . . . . 9
4.1 Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
4.2 Product identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
5
Storage, Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 Storage conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
5.2 Transport product to the measuring point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
6
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6.1 Suitable mounting position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
6.2 Special mounting conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
6.3 Mounting the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16
6.4 Post-installation check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
18
7
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7.1 Connection options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
7.2 Connection conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21
7.3 Connection data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
7.4 Connecting the measuring device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
7.5 Post-connection check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
8
Integration into a FOUNDATION Fieldbus network . . . . . . . . . . . . . . . . . . 25
8.1 Device Description (DD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
25
8.2 Integration into the FOUNDATION Fieldbus network . . . . . . . . . . . . . . . . . . . . . . . . . . . .
25
8.3 Device identification and addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
25
8.4 Block model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
8.5 Assignment of the measured values (CHANNEL) in an AI Block . . . . . . . . . . . . . . . . . . . . . . .
28
8.6 Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
9
Commissioning via operating menu (On-site display, FieldCare) . . . . . . . . . 30
9.1 Display and operating module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30
9.2 Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
9.3 Adjust the display contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
34
9.4 Unlock the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
34
9.5 Set the operating language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36
9.6 Configuration of a level measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
37
9.7 User-specific applications (operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
38
10 Commissioning with a FOUNDATION Fieldbus configuration program (block-
oriented operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.1 Block configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
38
Important document information
Endress+Hauser
3
10.2 Scaling of the measured value in an AI Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40
10.3 Language selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
10.4 Configuration of a level measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42
10.5 Configuration of the on-site display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
44
10.6 Configuration management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
44
10.7 Protection of the settings against unauthorized changes . . . . . . . . . . . . . . . . . . . . . . . . . . .
45
1
Important document information
1.1
Document conventions
1.1.1
Safety symbols
Symbol
Meaning
DANGER
A0011189-EN
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious
or fatal injury.
WARNING
A0011190-EN
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious
or fatal injury.
CAUTION
A0011191-EN
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor
or medium injury.
NOTICE
A0011192-EN
NOTICE!
This symbol contains information on procedures and other facts which do not result in personal
injury.
1.1.2
Electrical symbols
Symbol
Meaning
A0011197
Direct current
A terminal to which DC voltage is applied or through which direct current flows.
A0011198
Alternating current
A terminal to which alternating voltage (sine-wave) is applied or through which alternating current flows.
)
A0011200
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
*
A0011199
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
A0011201
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential equalization
line or a star grounding system depending on national or company codes of practice.
Important document information
Levelflex FMP53
4
Endress+Hauser
1.1.3
Tool symbols
A0011219
A0011220
A0013442
A0011221
A0011222
Phillips head
screwdriver
Flat blade
screwdriver
Torx screwdriver
Allen key
Hexagon wrench
1.1.4
Symbols for certain types of information
Symbol
Meaning
A0011182
Allowed
Indicates procedures, processes or actions that are allowed.
A0011183
Preferred
Indicates procedures, processes or actions that are preferred.
A0011184
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011193
Tip
Indicates additional information.
A0011194
Reference to documentation
Refers to the corresponding device documentation.
A0011195
Reference to page
Refers to the corresponding page number.
A0011196
Reference to graphic
Refers to the corresponding graphic number and page number.
,
…
,
Series of steps
Ã
Result of a sequence of actions
1.1.5
Symbols in graphics
Symbol
Meaning
1, 2, 3 ...
Item numbers
,
…
,
Series of steps
A, B, C, ...
Views
A-A, B-B, C-C, ...
Sections
Basic safety instructions
Endress+Hauser
5
Symbol
Meaning
-
A0011187
Hazardous area
Indicates a hazardous area.
.
A0011188
Safe area (non-hazardous area)
Indicates a non-hazardous location.
2
Basic safety instructions
2.1
Requirements concerning the staff
The staff must fulfill the following requirements for their tasks:
►Trained staff: Must have a qualification which corresponds to their function and tasks.
►Authorized by the plant operator.
►Familiar with the national regulations.
►Before starting their work: Must have read and understood all instructions in the operating
manual and supplementary documentation as well as the certificate (depending on the
application).
►Must comply with all instructions and the regulatory framework.
2.2
Designated use
Application and measured materials
The measuring device described in these Operating Instructions is intended only for level
measurement of liquids. Depending on the version ordered the device can also measure
potentially explosive, flammable, poisonous and oxidizing materials.
Observing the limit values specified in the "Technical data" and listed in the Operating
Instructions and supplementary documentation, the measuring device may be used for the
following measurements only:
►Measured process variables: level
►Calculated process variables: Volume or mass in arbitrarily shaped vessels (calculated from
the level by the linearization functionality)
To ensure that the measuring device remains in proper condition for the operation time:
►Use the measuring device only for measured materials against which the process-wetted
materials are adequately resistant.
►Observe the limit values in "Technical data".
Incorrect use
The manufacturer is not liable for damage caused by improper or non-designated use.
Verification for borderline cases:
►For special measured materials and cleaning agents, Endress+Hauser is glad to provide
assistance in verifying the corrosion resistance of wetted materials, but does not accept any
warranty or liability.
Basic safety instructions
Levelflex FMP53
6
Endress+Hauser
Residual risk
The electronics housing and its built-in components such as display module, main electronics
module and I/O electronics module may heat to 80 °C (176 °F) during operation through heat
transfer from the process as well as power dissipation within the electronics. During operation
the sensor may assume a temperature near the temperature of the measured material.
Danger of burns due to heated surfaces!
►For high process temperatures: Install protection against contact in order to prevent burns.
2.3
Workplace safety
For work on and with the device:
►Wear the required personal protective equipment according to federal/national regulations.
2.4
Operational safety
Risk of injury!
►Operate the device in proper technical condition and fail-safe condition only.
►The operator is responsible for interference-free operation of the device.
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to unforeseeable
dangers
►If, despite this, modifications are required, consult with Endress+Hauser.
Repair
To ensure continued operational safety and reliability,
►Carry out repairs on the device only if they are expressly permitted.
►Observe federal/national regulations pertaining to repair of an electrical device.
►Use original spare parts and accessories from Endress+Hauser only.
Hazardous area
To eliminate a danger for persons or for the facility when the device is used in the hazardous
area (e.g. explosion protection, pressure vessel safety):
►Based on the nameplate, check whether the ordered device is permitted for the intended use
in the hazardous area.
►Observe the specifications in the separate supplementary documentation that is an integral
part of these Instructions.
2.5
Product safety
This measuring device is designed in accordance with good engineering practice to meet state-
of-the- art safety requirements, has been tested, and left the factory in a condition in which they
are safe to operate.
It fulfills general safety requirements and legal requirements. It also conforms to the EC directives
listed in the device-specific EC declaration of conformity. Endress+Hauser confirms this fact by
applying the CE mark.
Compact device Levelflex
1
2
3
A0013421
å 1
Design of the Levelflex
1
Electronics housing
2
Process connection
3
Rod probe
Design of the electronics housing
1
Electronics compartment cover
2
Display module
3
Main electronics module
4
Cable glands (1 or 2, depending on instrument version)
5
Nameplate
6
I/O electronics module
7
Terminals (pluggable spring terminals)
8
Connection compartment cover
9
Grounding terminal
Incoming acceptance and product identification
Endress+Hauser
9
4
Incoming acceptance and product identification
4.1
Incoming acceptance
A0013696
DELIVERY NOTE
1 = 2
A0016870
A0013921
A0013696
A0013922
Incoming acceptance and product identification
Levelflex FMP53
10
Endress+Hauser
A0013696
DELIVERY NOTE
Made in Germany, 79689 Maulburg
A0014038
A0013696
A0014037
If one of the conditions does not comply, contact your Endress+Hauser distributor.
4.2
Product identification
The following options are available for identification of the measuring device:
• Nameplate specifications
• Order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
( www.endress.com/deviceviewer ): All information about the measuring device is displayed.
For an overview of the scope of the Technical Documentation provided, refer to the following:
enter serial numbers from nameplates in W@M Device Viewer
( www.endress.com/deviceviewer )
Ext. ord. cd.:
Ser. no.:
1
2
3
A0014103
å 3
Example of a nameplate
1
Order code
2
Serial number (Ser. no.)
3
Extended order code (Ext. ord. cd.)
Only 33 digits of the extended order code can be indicated on the nameplate. If the
extended order code exceeds 33 digits, the rest will not be shown. However, the complete
extended order code can be viewed in the operating menu of the device (Diagnostics ®
Device info ® Extended order code 1/2/3).
For detailed information about interpreting the nameplate specifications, refer to the
Operating Instructions for the device on the CD-ROM provided.
5
Storage, Transport
5.1
Storage conditions
• Permitted storage temperature: –40 to +80 °C (–40 to +176 °F)
• Use the original packaging.
5.2
Transport product to the measuring point
!WARNING
Risk of injury if the hosuing breaks away!
►Transport the measuring device to the measuring point in its original packaging or at the
process connection.
►Comply with the safety instructions, transport conditions for devices over 18kg (39.6lbs).
Suitable mounting position
A
1
2
C
B
3
A0014130
6.1.1
Mounting distances
• Distance (A) between wall and rod probe:
– for smooth metallic walls: > 50 mm (2")
– for plastic walls: > 300 mm (12") mm to metallic parts outside the vessel
• Distance (B) between rod probe and internal fittings (3) in the vessel: > 300 mm (12")
• Distance (C) from end of probe to bottom of the vessel: > 10 mm (0.4 in).
6.1.2
Additional conditions
• When mounting in the open, a weather protection cover (1) may be installed to protect the
device against extreme weather conditions.
• Do not mount the probe in the filling curtain (2).
When mounting the electronics housing into a recess (e.g. in a concrete ceiling), observe
a minimum distance of 100 mm (4 inch) between the cover of the terminal compartment /
electronics compartment and the wall. Otherwise the connection compartment /
electronics compartment is not accessible after installation.
6.2
Special mounting conditions
6.2.1
Non-metallic vessels
1
2
A0012527
1
Non-metallic vessel
2
Metal sheet or metal flange
To measure, Levelflex with a rod or rope probe needs a metallic surface at the process connection.
Therefore:
Mount a metal sheet with a diameter of at least 200 mm (8") to the probe at the process
connection. Its orientation must be perpendicular to the probe.
Plastic or glass tanks: Mounting the probe externally at the wall
1
2
a
3
A0014150
1
Plastic or glass tank
2
Metall sheet with threaded sleeve
3
No free space between tank wall and probe!
Requirements
• The dielectric constant of the medium must be at least DC > 7.
• The tank wall must be non-conductvie.
• Maximum wall thickness (a):
– Plastic: < 15 mm (0.6")
– Glass: < 10 mm (0.4")
• There may be no metallic reinforcements fixed to the tank.
Mounting conditions:
• The probe must be mounted directly to the tank wall (no open space)
• A plastic half pipe with a diameter of approx. 200 mm (8"), or some other protective unit,
must be affixed externally to the probe to prevent any influences on the measurement.
• If the tank diameter is less than 300 mm (12"):
A metallic grounding sheet must be installed at the opposite side of the tank. The sheet must
be conductively connected to the process connection and cover about the half of the vessel's
circumference.
• If the tank diameter exceeds 300 mm (12"):
A metal sheet with a diameter of at least 200 mm (8") must be mounted to the probe at the
process connection. Its orientation must be perpendicular to the probe (see above).
Calibration for external probe mounting
If the probe is mounted externally at the wall of the tank, the speed of signal propagation will
be reduced. There are two possibilities to compensate for this effect.
Compensation with the gas phase compensation factor
The effect of the dielectric wall can be compared to the effect of a dielectric gas phase. Thus it
can be compensated for in the same manner. The compensation factor if given by the quotient
of the actual probe length LN and the probe length meausred when the tank is empty.
The device looks for the end of probe signal in the subtracted curve. Thus, the value of the
measured probe length depends on the mapping. In order to obtain an exact value, it is
advisable to determine the probe length manually using the envelope curve display in
FieldCare.
Step
Parameter
Action
1
Expert ® Sensor ® Gas phase compensation ® GPC mode
Select Constant GPC factor option.
2
Expert ® Sensor ® Gas phase compensation ® Constant
GPC factor
Enter quotient: "(Actual probe length)/(Measured
probe length)".
Compensation via the calibration parameters
If an acutal gas phase has to be compensated for, the gas phase compensation functionality is no
longer available for a correction of the external mounting. In this case the calibration parameters
(Empty calibration and Full calibration) must be adjusted and a value longer than the actual
probe length has to be entered into the Present probe length parameter. The correction factor
for these three parameters is given by the quotient of the probe length measured when the tank
is empty and the acutal probe length LN.
The device looks for the end of probe signal in the subtracted curve. Thus, the value of the
measured probe length depends on the mapping. In order to obtain an exact value, it is
advisable to determine the probe length manually using the envelope curve display in
FieldCare.
Step
Parameter
Action
1
Setup ® Empty calibration
Increase parameter value by "(Measured probe length)/
(Actual probe length)".
2
Setup ® Full calibration
Increase parameter value by "(Measured probe length)/
(Actual probe length)".
3
Expert ® Sensor ® Sensor properties ® Probe length
correction ® Confirm probe length
Select Manual input option.
4
Expert ® Sensor ® Sensor properties ® Probe length
correction ® Present probe length
Enter measured probe length.
6.3
Mounting the device
6.3.1
Required mounting tools
• To shorten rod or coax probes: Saw
• For flanges and other process connections: appropriate mounting tools
• To turn the housing: Hexagonal wrench 8 mm
Preparing the device for mounting
When shortening the probe: Enter the new length of probe into the Quick Setup which
can be found in the electronics housing behind the display module.
A0014241
Shortening rod probes
Rod probes must be shortened if the distance to the container floor or outlet cone is less than
10 mm (0.4 in). The rods of a rod probe are shortened by sawing at the bottom end.
Rod probes of FMP52 can not be shortened as they are coated.
6.3.3
Turning the transmitter housing
To provide easier access to the connection compartment or display module, the transmitter
housing can be turned:
max. 350°
8 mm
8 mm
A0013713
1.
Unscrew the securing screw using an open-ended wrench.
2.
Rotate the housing in the desired direction.
Firmly tighten the securing screw. (1,5 Nm for plastics housing; 2,5 Nm for aluminium or
stainless steel housing).
6.3.4
Turning the display module
+
E
–
1
3 mm
A0013905
1.
Loosen the screw of the securing clamp of the electronics compartment cover using an
Allen key and turn the clamp 90° conterclockwise.
2.
Unscrew cover of the electronics compartment from the transmitter housing.
3.
Pull out the display module with a gentle rotation movement.
4.
Rotate the display module into the desired position: Max. 8 ´ 45 ° in each direction.
5.
Feed the spiral cable into the gap between the housing and main electronics module and
plug the display module into the electronics compartment until it engages.
6.
Screw the cover of the electronics compartment firmly back onto the transmitter housing.
7.
Tighten the securing clamp again using the Allen key.
6.4
Post-installation check
m
Is the device undamaged (visual inspection)?
m
Does the device conform to the measuring point specifications?
For example:
• Process temperature
• Process pressure (refer to the chapter on "Material load curves" of the "Technical Information"
document)
• Ambient temperature range
• Measuring range
m
Are the measuring point identification and labeling correct (visual inspection)?
m
Is the device adequately protected from precipitation and direct sunlight?
m
Are the securing screw and securing clamp tightened securely?
Terminal assignment FOUNDATION Fieldbus
1
Terminals FOUNDATION Fieldbus
2
Cable screen: Observe cable specifications (® ä 21)
3
Cable entry
4
Potential equalization
Terminals switching output (Open collector)
2
Connection cable switching output
3
Cable entry
Switching output
Function
Open collector switching output
Switching behavior
Binary (conductive or non-conductive), switches when the programmable switch
point is reached
Failure mode
non-conductive
Eectrical connection values
U = 10.4 to 35 VDC, I = 0 to 40 mA
Internal resistance
RI < 880 W
The voltage drop at this internal resistance has to be taken into account on planning
the configuration. For example, the resulting voltage at a connected relay must be
sufficient to switch the relay.
Insulation voltage
floating, Insulation voltage 1 350 VDC to power supply aund 500 VAC to ground
Switch point
freely programmable, separately for switch-on and switch-off point
Switching delay
freely programmable from 0 to 100 sec. , separately for switch-on and switch-off
point
Number of switching cycles
corresponds to the measuring cycle
Signal source
device variables
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Relative echo amplitude
Number of switching cycles
unlimited
Connection examples for the switch output
3+
+-
4-
A0015909
å 5
Connection of a relay
Suitable relays (examples):
• Solid-state relay: Phoenix Contact OV-24DC/480AC/5 with
mounting rail connector UMK-1 OM-R/AMS
• Electromechanical relay: Phoenix Contact PLC-RSC-12DC/21
3+
2
1
+
4-
A0015910
å 6
Connection of a digital input
1
Pull-up resistor
2
Digital input
7.2
Connection conditions
7.2.1
Cable specification
FOUNDATION Fieldbus
• Endress+Hauser recommends using twisted, shielded two-wire cables.
• Terminals for wire cross-sections: 0.5 to 2.5 mm2 (20 to 14 AWG)
• Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in)
For further information on the cable specifications, see Operating Instructions BA00013S
"FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC
61158-2 (MBP).
7.2.2
Cable diameter and cross-section of the strands
Type of protection
Cable gland
Admissible cable
diameter
Admissible cross-section of the
strands
• Standard
• Ex ia
• Ex ic
Plastics M20x1,5
5 to 10 mm (0.2 to 0.39
in)
0.5 to 2.5 mm2 (20 to 14 AWG)
• Ex tD
• Ex nA
• FM approval
• CSA approval
Metal M20x1.5
7 to 10 mm (0.28 to
0.39 in)
7.2.3
Overvoltage protection
If the measuring device is used for level measurement in flammable liquids which requires the
use of overvoltage protection according to DIN EN 60079-14, standard for test procedures
60060-1 (10 kA, pulse 8/20 ms), overvoltage protection has to be ensured by one of the following
measures:
• Integrated overvoltage protection (in preparation)
Product structure: Feature 610 "Accessory mounted", option NA "Overvoltage protection".
• External overvoltage protection, e.g. Endress+Hauser's HAW562 or HAW569.
For detailed information please refer to the following documents:
• HAW562: TI01012K
• HAW569: TI01013K
7.3
Connection data
7.3.1
FOUNDATION Fieldbus
"Power supply; Output" 1)
Terminal voltage
E: 2-wire; FOUNDATION Fieldbus, switch output
9 to 32 VDC
1)
Feature 020 of the product structure
7.4
Connecting the measuring device
!WARNING
Explosion hazard!
►Comply with the relevant national standards.
►Observe the specifications in the Safety Instructions (XA).
►Only use the specified cable glands.
►Check whether the supply voltage matches the specifications on the nameplate.
►Before connecting the device: Switch the supply voltage off.
►Before switching on the supply voltage: Connect the potential bonding line to the exterior
ground terminal.
Required tools and accessories:
• For instruments with safety pin for the lid: AF 3 Allen key
• Wire stripping pliers
• When using stranded wires: Wire end sleeves.
Loosen the screw of the securing clamp of the connection compartment cover and turn
the clamp 90° counterclockwise.
2.
Unscrew the connection compartment cover.
3.
Push the cable through the cable entry. To ensure tight sealing, do not remove the sealing
ring from the cable entry.
4.
Strip the cable.
5.
Strip the cable ends 10 mm (0.4 in). For stranded cables, also attach wire end ferrules.
6.
Firmly tighten the cable glands.
7.
2
1
4
3
A0013837
Connect the cable in accordance with the terminal assignment .
8.
When using screened cable: Connect the cable screen to the ground terminal.
Screw the cover onto the connection compartment.
10. For instruments with safety pin for the lid: Adjust the safety pin so that its edge is over the
edge of the display lid. Tighten the safety pin.
Pluggable spring-force terminals
Instruments without integrated overvoltage protection have pluggable spring-force
terminals. Rigid or flexible conductors with or without cable sleeve can directly be inserted
and are contacted automatically.
To remove cables from the terminal: Press on the groove between the terminals using a
flat-tip screwdriver £ 3 mm (0.12 inch) while pulling the cables out of the terminals.
mm (in)
≤3 (0.12)
A0013661
7.5
Post-connection check
m
Are cables or the device undamaged (visual inspection)?
m
Do the cables comply with the requirements?
m
Do the cables have adequate strain relief?
m
Are all cable glands installed, firmly tightened and correctly sealed?
m
Does the supply voltage match the specifications on the transmitter nameplate?
m
Is the terminal assignment correct ?
m
If required: Is the protective earth connected correctly ?
m
If supply voltage is present: Is the device ready for operation and do values appear on the display module?
m
Are all housing covers installed and firmly tightened?
m
Is the securing clamp tightened correctly?
Integration into a FOUNDATION Fieldbus network
Endress+Hauser
25
8
Integration into a FOUNDATION Fieldbus network
8.1
Device Description (DD)
You require the following to configure a device and integrate it into an FF network:
• An FF configuration program
• The Cff file (Common File Format: *.cff)
• The device description (DD) in one of the following formats
– Device Description format 4 : *sym, *ffo
– Device Description format 5 : *sy5, *ff5
Information on the device-specific DD
Manufacturer ID
452B48hex
Device Type
100Fhex
Device Revision
05hex
DD Revision
Information and files at:
• www.endress.com
• www.fieldbus.org
CFF Revision
8.2
Integration into the FOUNDATION Fieldbus network
• For more in-depth information on integrating the device into the FF system, see the
description for the configuration software used.
• When integrating the field devices into the FF system, make sure you are using the right
files. You can read out the required version by means of the Device Revision/DEV_REV
and DD Revision/ DD_REV parameters in the Resource Block.
The device is integrated into the FF network as follows:
1.
Start the FF configuration program.
2.
Download the Cff and device description files (*.ffo, *.sym (for format 4) *ff5, *sy5 (for
format 5) to the system.
3.
Configure the interface.
4.
Configure the device for the measuring task and for the FF system.
8.3
Device identification and addressing
FOUNDATION Fieldbus identifies the device using its ID code (Device ID) and automatically
assigns it a suitable field address. The identity code cannot be changed. The device appears in
the network display once you have started the FF configuration program and integrated the device
into the network. The blocks available are displayed under the device name.
If the device description has not yet been loaded, the blocks report "Unknown" or "(UNK)".
Integration into a FOUNDATION Fieldbus network
Levelflex FMP53
26
Endress+Hauser
–
–
RESOURCE_xxxxxxxxxxx (RB2)
EH_Levelflex_xxxxxxxxxx
SETUP_
(TRDSUP)
xxxxxxxxxxx
DISPLAY_
(TRDDISP)
xxxxxxxxxxx
DIAGNOSTIC_
(TRDDIAG)
xxxxxxxxxxx
EXPERT_CONFIG_
(TRDEXP)
xxxxxxxxxxx
EXPERT_INFO_
(TRDEXPIN)
xxxxxxxxxxx
SERVICE_INFO_
(TRDSRVIF)
xxxxxxxxxxx
DATA_TRANSFER_
(TRDHROM)
xxxxxxxxxxx
ANALOG_INPUT_1_
(AI)
xxxxxxxxxxx
ANALOG_INPUT_2_
(UNK)
xxxxxxxxxxx
DISCRETE_INPUT_
(DI)
xxxxxxxxxxx
ARITHMETIC_
(AR)
xxxxxxxxxxx
INPUT_SELECTOR_
(IS)
xxxxxxxxxxx
ANALOG_ALARM_
(AAL)
xxxxxxxxxxx
PID_
(PID)
xxxxxxxxxxx
SIGNAL_CHAR_
(SC)
xxxxxxxxxxx
INTEGRATOR_
(IT)
xxxxxxxxxxx
SERVICE_SENSOR_
(TRDSRVSB)
xxxxxxxxxxx
ADV_SETUP_
(TRDASUP)
xxxxxxxxxxx
1
2
A0017208
å 7
Typical display in a configuration program after the connection has been established
1
Device name
2
Serial number
Integration into a FOUNDATION Fieldbus network
Endress+Hauser
27
8.4
Block model
8.4.1
Blocks of the device software
The device has the following blocks:
• Resource Block (device block)
• Transducer Blocks
– Setup Transducer Block (TRDSUP)
– Advanced Setup Transducer Block (TRDASUP)
– Display Transducer Block (TRDDISP)
– Diagnostic Transducer Block (TRDDIAG)
– Expert Configuration Transducer Block (TRDEXP)
– Expert Information Transducer Block (TRDEXPIN)
– Service Sensor Transducer Block (TRDSRVSB)
– Service Information Transducer Block (TRDSRVIF)
– Data Transfer Transducer Block (TRDHROM)
• Function Blocks
– 2 Analog Input Blocks (AI)
– 1 Discrete Input Block (DI)
– 1 PID Block (PID)
– 1 Arithmetic Block (AR)
– 1 Signal Characterizer Block (SC)
– 1 Input Selector Block (IS)
– 1 Integrator Block (IT)
– 1 Analog Alarm Block (AAL)
In addition to the pre-instantiated blocks already mentioned, the following blocks can also be
instantiated:
• 5 Analog Input Blocks (AI)
• 2 Discrete Input Blocks (DI)
• 3 PID Blocks (PID)
• 3 Arithemetic Blocks (AR)
• 2 Signal Characterizer Blocks (SC)
• 5 Input Selector Blocks (IS)
• 3 Integrator Blocks (IT)
• 2 Analog Alarm Blocks (AAL)
Up to 20 blocks can be instantiated in the device altogether, including the blocks already
instantiated. For instantiating blocks, see the appropriate Operating Instructions of the
configuration program used.
Endress+Hauser Guideline BA00062S.
The guideline provides an overview of the standard function blocks that are described in
FOUNDATION Fieldbus Specifications FF 890 - 894. It is designed to help operators use
the blocks implemented in the Endress+Hauser field devices.
Integration into a FOUNDATION Fieldbus network
Levelflex FMP53
28
Endress+Hauser
8.4.2
Block configuration when device is delivered
DIAGNOSTIC
PID
ARITHMETIC
SIGNAL_CHAR
S
RESOURCE
ANALOG_INPUT_1
ANALOG_INPUT_2
DI
ADV_SETUP
DATA_TRANSFER
EXPERT_INFO
SERVICE_INFO
DISPLAY
INPUT_SELECTOR
INTEGRATOR
ANALOG_ALARM
EXPERT_CONFIG
SETUP
SERVICE_SENSOR
PV
SV
ESC
OPEN
OPEN
E
Device_01
F
mm
4841.000
A0017217
å 8
Block configuration when device is delivered
S
Sensor
PV
Primary value: Level linearized
SV
Secondary value: Distance
8.5
Assignment of the measured values (CHANNEL) in an AI
Block
The input value of an Analog Input Block is defined by the CHANNEL parameter.
Channel
Measured value
0
Uninitialized
89
Measured capacitance
144
EOP shift
145
Interface distance
172
Calculated DC value
211
Terminal voltage
212
Sensor debug
Integration into a FOUNDATION Fieldbus network
Endress+Hauser
29
Channel
Measured value
32785
Absolute EOP amplitude
32786
Absolute echo amplitude
32787
Absolute interface amplitude
32856
Distance
32885
Elektronic temperature
32938
Interface linearized
32949
Level linearized
33044
Relative echo amplitude
33045
Relative interface amplitude
33070
Noise of signal
33107
Upper interface thickness
8.6
Methods
The FOUNDATION Fieldbus Specification includes the use of methods to make device operation
easier. A method is a sequence of interactive steps to be carried out in the specified order so as
to configure certain device functions.
The following methods are available for the device:
• Restart
This method is located in the Resource Block and directly prompts the setting of the Device
reset parameter. This resets the device configuration to a defined state.
• ENP Restart
This method is located in the Resource Block and directly prompts the setting of the parameters
of the Electronic Name Plate (ENP).
• Setup
This method is located in the SETUP Transducer Block and allows to set the most important
parameters in this block for device configuration (measuring units, type of tank or vessel, type
of medium, empty and full calibration).
• Linearization
This method is located in the ADV_SETUP Transducer Block and allows to manage the
linearization table by which the measured value is converted into volume, mass or flow.
• Self Check
This method is located in the EXPERT_CONFIG Transducer Block and prompts the device
self check parameters.
Commissioning via operating menu (On-site display, FieldCare)
Levelflex FMP53
30
Endress+Hauser
9
Commissioning via operating menu (On-site display,
FieldCare)
9.1
Display and operating module
9.1.1
Display appearance
3.1
3.2
2.1
2.2
2.4
2.5
1.1
1.2
1.3
1.4
2.3
2.6
1
2
3
4
5
ESC
OPEN
OPEN
E
ABC_
DEFG
User
HIJK
LMNO
PQRS
TUVW
XYZ
Aa1
3
4
0
1
2
9
5
6
8
7
20
A0012635
å 9
Appearance of the display and operation module for on-site operation
1
Measured value display (1 value max. size)
1.1
Header containing tag and error symbol (if an error is active)
1.2
Measured value symbols
1.3
Measured value
1.4
Unit
2
Measured value display (2 values)
2.1
Bargraph for measured value 1
2.2
Measured value 1 (including unit)
2.3
Measured value symbols for measured value 1
2.4
Measured value 2
2.5
Unit for measured value 2
2.6
Measured value symbols for measured value 2
3
Representation of a parameter (here: a parameter with selection list)
3.1
Header containing parameter name and error symbol (if an error is active)
3.2
Selection list; Â marks the current parameter value.
4
Input matrix for numbers
5
Input matrix for alphanumeric and special characters
Commissioning via operating menu (On-site display, FieldCare)
Endress+Hauser
31
9.1.2
Navigation and selection from a list
Use the operating keys to navigate within the operating menu and to select options from a list.
Key
Meaning
A0011971
"Minus" key
Henceforth represented by S.
• In a selection list: Moves the selection bar upward.
• In an input matrix: Moves the selection bar backward.
A0011972
"Plus" key
Henceforth represented by O.
• In a selection list: Moves the selection bar downward.
• In an input matrix: Moves the selection bar forward.
E
A0011973
"Enter" key
Henceforth represented by F.
• Opens the marked submenu or parameter.
• Confirms a changed parameter value.
+
A0012661
"Escape" key combination (press keys simultaneously)
Henceforth represented by S + O.
• Closes a parameter without accepting the changes.
• Quits the current menu layer and returns to the next higher layer.
Commissioning via operating menu (On-site display, FieldCare)
Levelflex FMP53
32
Endress+Hauser
9.2
Operating concept
9.2.1
Structure
Language
Display/operation
Parameter 1
Parameter 2
Parameter N
Setup
Setup parameter 1
Setup parameter 2
Setup parameter N
Advanced setup
Enter access code
Parameter 1
Parameter N
Submenu 1
Submenu N
Diagnostics
Parameter 1
Parameter N
Submenu 1
Submenu N
Expert
Direct access
System
Sensor
Output
Communication
Application
Diagnostics
A0011407-EN
å 10
Basic structure of the operating menu; gray: submenus; white: parameters
Commissioning via operating menu (On-site display, FieldCare)
Endress+Hauser
33
9.2.2
Submenus and user roles
The submenus are designed for different user roles. A user role is defined by typical tasks within
the lifecycle of the device.
User role
Typical tasks
Submenu
Operator
Tasks in the ongoing process:
• Configuration of the display.
• Reading measuring values.
"Language"
Defines the operating language (® ä 36).
"Display/Operation"
Contains all parameters which are needed
during the ongoing process: configuration of the
display (display values, display format, display
contrast ...).
Maintenance
Commissioning:
• Configuration of the measurement.
• Configuration of the measured value processing
(scaling, linearization, limit detection etc.).
• Configuration of the measured value output (analog
and digital communication interface).
"Setup"
Contains all commissioning parameters
(® ä 37).
Error handling
"Diagnostics"
Contains all parameters needed to detect an
analyze operational errors.
Expert
Tasks which require detailed knowledge about the
instrument:
• Commissioning of measurements under demanding
conditions.
• Optimization of the measurement under demanding
conditions.
• Detailed configuration of the communication
interface.
• Error diagnosis in diffcult cases.
"Expert"
Commissioning via operating menu (On-site display, FieldCare)
Levelflex FMP53
34
Endress+Hauser
9.3
Adjust the display contrast
• O + F (pressed simultaneously): increases the contrast.
• S + F (pressed simultaneously): decreases the contrast.
9.4
Unlock the device
If the device has been locked, it must be unlocked before the measurement can be configured.
9.4.1
Revoke hardware locking
A0013649
å 11
Mesured value screen of a hardware-locked device
The padlock in the header of the measured value screen indicates that the device is hardware-
locked. In order to unlock the device, shift the locking switch (which is located below the display
module) into the "unlocked" position.
1
2
5
4
3
(B)
(A)
CDI
Spare part: FMP52X-AB
WP SIM
SW
ex works
SW update #1
SW update #2
02.01.03 Dev_R
DISPL
A0013132
Commissioning via operating menu (On-site display, FieldCare)
Endress+Hauser
35
1.
Unscrew the lid from the compartment for the display and operating module.
2.
Slightly turn the display and operating module to remove it from the compartment.
3.
Set the locking switch (WP: Write Protection) into the desired position. (A): unlocked; (B):
locked.
4.
Attach the display and operating module in the desired orientation until it closes with a
snap.
5.
Screw the lid onto the compartment.
9.4.2
Revoke software locking
E
A0013651
å 12
Input prompt for the access code to unlock software-locked parameters.
Parameters affected by the software lock are marked by a padlock in front of the parameter name.
After pressing F an input prompt appears. Enter the user defined locking code to unlock the
device.
Step
Parameter
Action
1
Setup ® Advanced setup ® Define access code
To lock the device:
Enter a user-defined access code.
2
Setup ® Advanced setup ® Enter access code
To unlock the device:
Enter the previously defined access code.
3
Setup ® Advanced setup ® Enter access code
To lock the device again:
Enter a number other than the previously defined access
code.
Commissioning via operating menu (On-site display, FieldCare)
Levelflex FMP53
36
Endress+Hauser
9.5
Set the operating language
E
E
E
+
1.
4.
2.
5.
3.
A0013637
Commissioning via operating menu (On-site display, FieldCare)
Endress+Hauser
37
9.6
Configuration of a level measurement
F
L
D
E
20mA
100%
4mA
0%
LN
R
A0011360
å 13
Configuration parameters for level measurements in liquids
LN = Length of probe
R = Reference point of the measurement
D = Distance
E = Empty calibration (= Zero point)
L = Level
F = Full calibration (= span)
Step
Parameter
Action
1
Setup ® Distance unit
Select distance unit.
2
Setup ® Tank type
Select tank type.
3
Setup ® Tube diameter 1)
Enter the diameter of the bypass or stilling well.
4
Setup ® Medium group
Select medium group ("water based": DC>4 or "other": DC>1.9)
5
Setup ® Empty calibration
Enter the distance E between the reference point R and the minimum level
(0%).
6
Setup ® Full calibration
Enter distance F between the minimum (0%) and maximum (100%) level.
7
Setup ® Level
Displays the measured level L.
8
Setup ® Distance
Displays the distance D between the reference point R and the level L.
Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation)
Levelflex FMP53
38
Endress+Hauser
Step
Parameter
Action
9
Setup ® Signal quality
Displays the signal quality of the level echo.
10
Setup ® Mapping ® Confirm
distance
Compare the displayed distance to the real distance in order to start the
recording of the mapping curve.
1)
only visible for coated probes and if "Tank type" = "Bypass/pipe"
9.7
User-specific applications (operation)
For details of setting the parameters of user-specific applications, see separate
documentation:
• Operator and Maintenance ® BA01053F/00/EN (Operating Instructions)
• Experte ® GP01015F/00/EN (Description of Device Parameters)
10
Commissioning with a FOUNDATION Fieldbus
configuration program (block-oriented operation)
10.1
Block configuration
10.1.1
Preparatory steps
1.
Switch on the device.
2.
Note the DEVICE_ID.
3.
Open the configuration program.
4.
Load Cff and device description files into the host system or the configuration program.
Make sure you are using the right system files.
5.
Identify the device using the DEVICE_ID (see Point 2). Assign the desired tag name to
the device by means of the Pd-tag/FF_PD_TAG parameter.
10.1.2
Configuring the Resource Block
1.
Open the Resource Block.
2.
If necessary, disable the lock for device operation.
3.
If necessary, change the block name. Factory setting: RS-xxxxxxxxxxx (RB2)
4.
If necessary, assign a description to the block by means of the Tag Description/
TAG_DESC parameter.
5.
If necessary, change other parameters as per the requirements.
10.1.3
Configuring the Transducer Blocks
The measurement and the display module are configured using the Transducer Blocks. The
general procedure is the same for all Transducer Blocks:
Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation)
Endress+Hauser
39
1.
If necessary, change the block name.
2.
Set the block mode to OOS by means of the Block Mode/MODE_BLK parameter,
TARGET element.
3.
Configure the device in accordance with the measuring task (® ä 42) .
4.
Set the block mode to Auto by means of the Block Mode/MODE_BLK parameter,
TARGET element.
The block mode must be set to Auto for the measuring device to function correctly.
10.1.4
Configuring the Analog Input Blocks
The device has 2 Analog Input Blocks that can be assigned as required to the various process
variables.
Default settings
Analog Input Block
CHANNEL
AI 1
32949: Level linearized
AI 2
32856: Distance
1.
If necessary, change the block name.
2.
Set the block mode to OOS by means of the Block Mode/MODE_BLK parameter,
TARGET element.
3.
Use the Channel/CHANNEL parameter to select the process variable which should be
used as the input value for the Analog Input Block (® ä 28).
4.
Use the Transducer Scale/XD_SCALE parameter to select the desired unit and the block
input range for the process variable (® ä 40). Make sure that the unit selected suits the
process variable selected. If the process variable does not suit the unit, the Block Error/
BLOCK_ERR parameter reports Block Configuration Error and the block mode cannot
be set to Auto.
5.
Use the Linearization Type/L_TYPE parameter to select the type of linearization for the
input variable (factory setting: Direct). Make sure that the settings for the Transducer
Scale/XD_SCALE and Output Scale/ OUT_SCALE parameters are the same for the
Direct linearization type. If the values and units do not match, the Block Error/
BLOCK_ERR parameter reports Block Configuration Error and the block mode cannot
be set to Auto.
6.
Enter the alarm and critical alarm messages by means of the High High Limit/
HI_HI_LIM, High Limit/HI_LIM, Low Low Limit/LO_LO_LIM and Low Limit/
LO_LIM parameters. The limit values entered must be within the value range specified
for the Output Scale/ OUT_SCALE parameter (® ä 40).
7.
Specify the alarm priorities by means of the High High Priority/HI_HI_PRI, High
Priority/ HI_PRI, Low Low Priority/LO_LO_PRI and Low Priority/LO_PRI
Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation)
Levelflex FMP53
40
Endress+Hauser
parameters. Reporting to the field host system only takes place with alarms with a priority
greater than 2.
8.
Set the block mode to Auto using the Block Mode/MODE_BLK parameter, TARGET
element. For this purpose, the Resource Block must also be set to the Auto block mode.
10.1.5
Additional configuration
1.
Link the function blocks and output blocks.
2.
After specifying the active LAS, download all the data and parameters to the field device.
10.2
Scaling of the measured value in an AI Block
If the type of linearisation L_TYPE = indirect has been selected in an AI block, the measured
value can be scaled within the block. The input range is defined by the XD_SCALE parameter
Through its EU_0 and EU_100 elements. This range is mapped linearly to the output ranged
defined by the OUT_SCALE parameter through its EU_0 and EU_100 elements.
0
1
0
1
EU_100
XD_SCALE
OUT_SCALE
EU_0
EU_0
EU_100
OUT_VALUE
A0017338
å 14
Scaling of the measured value in an AI Block
• If you have selected the Direct mode for the L_TYPE parameter, you cannot change
the values and units for XD_SCALE and OUT_SCALE.
• The L_TYPE, XD_SCALE and OUT_SCALE parameters can only be changed in the
OOS block mode.
Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation)
Endress+Hauser
41
10.3
Language selection
Step
Block
Parameter
Action
1
DISPLAY (TRDDISP)
Language (language)
Select language 1).
Selection:
• 32805: Arabian
• 32824: Chinese simplified
• 32842: Czech
• 32881: Dutch
• 32888: English
• 32917: French
• 32920: German
• 32945: Italian
• 32946: Japanese
• 32948: Korean
• 33026: Polish
• 33027: Portuguese
• 33062: Russian
• 33083: Spanish
• 33103: Thai
• 33120: Vietnamese
• 33155: Bahasa
• 33166: Turkish
1)
When ordering a device the set of available languages is defined. Refer to the product structure, feature 500
"Additional Operation Language".
Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation)
Levelflex FMP53
42
Endress+Hauser
10.4
Configuration of a level measurement
The Setup method can also be used to configure the measurement. It is called up via the
SETUP (TRDSUP) transducer block.
F
L
D
E
20mA
100%
4mA
0%
LN
R
A0011360
å 15
Configuration parameters for level measurements in liquids
LN = Length of probe
R = Reference point of the measurement
D = Distance
E = Empty calibration (= Zero point)
L = Level
F = Full calibration (= span)
If for rope probes the DC value is less than 7, then measurement is not possible in the area
of the straining weight. In these cases, the maximum allowed value for the empty
calibration E is LN - 250 mm (LN - 10 in).
Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation)
Endress+Hauser
43
Step
Block
Parameter
Action
1
SETUP (TRDSUP)
Distance unit (distance_unit)
Select distance unit.
Selection:
• 1010: m
• 1013: mm
• 1018: in
• 1019: ft
2
SETUP (TRDSUP)
Tank type (tank_type)
Select tank type.
Selection:
• 32816: Bypass / pipe
• 33288: Metallic
• 33302: Coaxial
• 33432: Twin rope
• 33433: Twin rod
• 33437: Rope centering disc metallic
• 33438: Rod centering disc metallic
• 33441: Non metallic
• 33444: Mounted outside
3
SETUP (TRDSUP)
Tube diameter
(tube_diameter) 1)
Enter the diameter of the bypass or stilling
well.
4
SETUP (TRDSUP)
Medium group
(medium_group)
Select medium group.
Selection:
• 316: water based (DC>4)
• 256: other (DC³ 1.9) 2)
5
SETUP (TRDSUP)
Empty calibration
(empty_calibration)
Enter the distance E between the reference
point R and the minimum level (0%).
6
SETUP (TRDSUP)
Full calibration
(full_calibration)
Enter distance F between the minimum (0%)
and maximum (100%) level.
7
SETUP (TRDSUP)
Level (level)
Displays the measured level L.
8
SETUP (TRDSUP)
Distance (filtered_dist_val)
Displays the distance D between the reference
point R and the level L.
9
SETUP (TRDSUP)
Signal quality (signal_quality)
Displays the signal quality of the level echo.
10
SETUP (TRDSUP)
Confirm distance
(confirm_distance)
Compare the displayed distance to the real
distance in order to start the recording of the
mapping curve.
Selection:
• 179: Manual map
• 32847: Delete all
• 32859: Distance ok
• 32860: Distance too big
• 32861: Distance too small
• 32862: Distance unknown
• 33100: Tank empty
1)
only available for coated probes and "Tank type" = "Bypass/pipe"
2)
If required, lower DCs can ben entered into the "DC value (dc_value)" parameter. However, for DC<1.6 the
measuring range may be reduced; for details please contact Endress+Hauser.
Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation)
Levelflex FMP53
44
Endress+Hauser
10.5
Configuration of the on-site display
10.5.1
Factory settings of the on-site display for level measurements
Parameter
Factory setting for devices with 1 current
output
Factory setting for devices with 2 current
outputs
Format display
1 value, max. size
1 value, max. size
Value 1 display
Levele linearized
Levele linearized
Value 2 display
Distance
Distance
Value 3 display
Current output 1
Current output 1
Value 4 display
None
Current output 21
The on-site display can be adjusted in the DISPLAY (TRDDISP) transducer block.
10.6
Configuration management
After commissioning, you can save the current device configuration, copy it to another measuring
point or restore the previous device configuration. You can do so using the Configuration
management parameter and its options.
Navigation path in the operating menu
Setup ® Advanced setup ® Conf.backup disp ® Config. managem.
Block operation
Block: DISPLAY (TRDDISP)
Parameter: Configuration management (configuration_management)
Functions of the parameter options
Options
Description
33097: Execute backup
A backup copy of the current device configuration in the HistoROM is saved to the display
module of the device. The backup copy comprises the transmitter data of the device.
33057: Restore
The last backup copy of the device configuration is copied from the display module to the
HistoROM of the device. The backup copy comprises the transmitter data of the device.
33838: Duplicate
The transmitter configuration from another device is duplicated to the device using the
display module.
265: Compare
The device configuration saved in the display module is compared to the current device
configuration of the HistoROM.
32848: Clear backup data
The backup copy of the device configuration is deleted from the display module of the
device.
HistoROM
A HistoROM is a "non-volatile" device memory in the form of an EEPROM.
Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation)
Endress+Hauser
45
While this action is in progress, the configuration cannot be edited via the local display and
a message on the processing status appears on the display.
For devices with FOUNDATION Fieldbus communication, the PD Tag parameter is also
transmitted when duplicating the parameter configuration. If required change PD Tag to
the required value after duplicating the set.
10.7
Protection of the settings against unauthorized changes
There are two ways to protect the settings against unauthorized changes:
• Via locking switch (hardware locking) (® ä 34)
• Via operating menu (software locking) (® ä 35)
• Via block operation:
– Block: DISPLAY (TRDDISP); parameter: Define access code (define_access_code)
– Block: EXPERT_CONFIG (TRDEXP); parameter: Enter access code
(enter_access_code)