Brief Operating Instructions

Levelflex FMP55 PROFIBUS PA Guided wave radar These Instructions are Brief Operating Instructions; they are not a substitute for the Operating Instructions pertaining to the device. Detailed information about the device can be found in the Operating Instructions and the other documentation: Available for all device versions via: – Internet: www.endress.com/deviceviewer – Smart phone/tablet: Endress+Hauser Operations App KA01072F/00/EN/16.18 71396577 2018-04-12

Levelflex FMP55 PROFIBUS PA

2 Endress+Hauser Order code: Ext. ord. cd.: Ser. no.: www.endress.com/deviceviewer Endress+Hauser Operations App XXXXXXXXXXXX XXXXX-XXXXXX XXX.XXXX.XX Serial number 1. 3. 2. A0023555

Levelflex FMP55 PROFIBUS PA

Table of contents Endress+Hauser 3 Table of contents 1 Important document information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.1 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 Terms and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.3 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2 Basic safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.1 Requirements for the personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.2 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.3 Workplace safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2.4 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 2.5 Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 3 Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.1 Product design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 4 Incoming acceptance and product identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 4.1 Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 4.2 Product identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 5 Storage, Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 5.1 Storage conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 5.2 Transport product to the measuring point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 6 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 6.1 Mounting requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 6.2 Mounting the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 6.3 Post-installation check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 7 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 7.1 Connection conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 7.2 Connecting the measuring device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 7.3 Post-connection check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 8 Integration into a PROFIBUS network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 8.1 Overview of the device database files (GSD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 8.2 Set device address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 9 Commissioning via wizard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 10 Commissioning (via operating menu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 10.1 Display and operating module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 10.2 Operating menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 10.3 Unlock the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 10.4 Setting the operating language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 10.5 Configuration of an interface measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 10.6 User-specific applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Important document information

Levelflex FMP55 PROFIBUS PA 4 Endress+Hauser 1 Important document information 1.1 Symbols 1.1.1 Safety symbols Symbol Meaning DANGER DANGER! This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury. CAUTION CAUTION! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor or medium injury. NOTICE NOTE! This symbol contains information on procedures and other facts which do not result in personal injury. 1.1.2 Electrical symbols Symbol Meaning Symbol Meaning Direct current Alternating current Direct current and alternating current Ground connection A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system. Symbol Meaning Protective Earth (PE) A terminal which must be connected to ground prior to establishing any other connections. The ground terminals are situated inside and outside the device: • Inner ground terminal: Connects the protectiv earth to the mains supply. • Outer ground terminal: Connects the device to the plant grounding system. 1.1.3 Tool symbols A0011219 A0011220 A0013442 A0011221 A0011222 Cross-head screwdriver Flat blade screwdriver Torx screwdriver Allen key Hexagon wrench

Levelflex FMP55 PROFIBUS PA

Important document information Endress+Hauser 5 1.1.4 Symbols for certain types of information Symbol Meaning Symbol Meaning Permitted Procedures, processes or actions that are permitted. Preferred Procedures, processes or actions that are preferred. Forbidden Procedures, processes or actions that are forbidden. Tip Indicates additional information. Reference to documentation. A Reference to page. Reference to graphic. 1., 2. , 3.… Series of steps. Result of a step. Visual inspection. 1.1.5 Symbols in graphics Symbol Meaning 1, 2, 3 ... Item numbers 1., 2. , 3.… Series of steps A, B, C, ... Views A-A, B-B, C-C, ... Sections - Hazardous area Indicates a hazardous area. . Safe area (non-hazardous area) Indicates the non-hazardous area. 1.1.6 Symbols at the device Symbol Meaning Safety instructions Observe the safety instructions contained in the associated Operating Instructions. Temperature resistance of the connection cables Specifies the minimum value of the temperature resistance of the connection cables.

Important document information

Levelflex FMP55 PROFIBUS PA 6 Endress+Hauser 1.2 Terms and abbreviations Term/abbreviation Explanation BA Document type "Operating Instructions" KA Document type "Brief Operating Instructions" TI Document type "Technical Information" SD Document type "Special Documentation" XA Document type "Safety Instructions" PN Nominal pressure MWP Maximum Working Pressure The MWP can also be found on the nameplate. ToF Time of Flight FieldCare Scalable software tool for device configuration and integrated plant asset management solutions DeviceCare Universal configuration software for Endress+Hauser HART, PROFIBUS, FOUNDATION Fieldbus and Ethernet field devices DTM Device Type Manager DD Device Description for HART communication protocol εr (DC value) Relative dielectric constant Operating tool The term "operating tool" is used in place of the following operating software: • FieldCare / DeviceCare, for operation via HART communication and PC • SmartBlue (app), for operation using an Android or iOS smartphone or tablet. BD Blocking Distance; no signals are analyzed within the BD. PLC Programmable Logic Controller CDI Common Data Interface PFS Pulse Frequence Status (Switching output)

Levelflex FMP55 PROFIBUS PA

Important document information Endress+Hauser 7 1.3 Registered trademarks PROFIBUS® Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany Bluetooth® The Bluetooth® word mark and logos are registered trademarks owned by the Bluetooth SIG, Inc. and any use of such marks by Endress+Hauser is under license. Other trademarks and trade names are those of their respective owners. Apple® Apple, the Apple logo, iPhone, and iPod touch are trademarks of Apple Inc., registered in the U.S.and other countries. App Store is a service mark of Apple Inc. Android® Android, Google Play and the Google Play logo are trademarks of Google Inc. KALREZ®, VITON® Registered trademark of DuPont Performance Elastomers L.L.C., Wilmington, USA TEFLON® Registered trademark of E.I. DuPont de Nemours & Co., Wilmington, USA TRI CLAMP® Registered trademark of Alfa Laval Inc., Kenosha, USA

Basic safety instructions

Levelflex FMP55 PROFIBUS PA 8 Endress+Hauser 2 Basic safety instructions 2.1 Requirements for the personnel The personnel must fulfill the following requirements for its tasks: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task. ‣ Are authorized by the plant owner/operator. ‣ Are familiar with federal/national regulations. ‣ Before starting work, read and understand the instructions in the manual and supplementary documentation as well as the certificates (depending on the application). ‣ Follow instructions and comply with basic conditions. 2.2 Designated use Application and measured materials The measuring device described in these Operating Instructions is intended only for level and interface measurement of liquids. Depending on the version ordered the device can also measure potentially explosive, flammable, poisonous and oxidizing materials. Observing the limit values specified in the "Technical data" and listed in the Operating Instructions and supplementary documentation, the measuring device may be used for the following measurements only: ‣ Measured process variable: Level and/or interface ‣ Calculated process variable: Volume oder mass in arbitrarily shaped vessels (calculated from the level by the linearization functionality) To ensure that the measuring device remains in proper condition for the operation time: ‣ Use the measuring device only for measured materials against which the process-wetted materials are adequately resistant. ‣ Observe the limit values in "Technical data". Incorrect use The manufacturer is not liable for damage caused by improper or non-designated use. Verification for borderline cases: ‣ For special measured materials and cleaning agents, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of wetted materials, but does not accept any warranty or liability. Residual risk The electronics housing and its built-in components such as display module, main electronics module and I/O electronics module may heat to 80 °C (176 °F) during operation through heat transfer from the process as well as power dissipation within the electronics. During operation the sensor may assume a temperature near the temperature of the measured material. Danger of burns due to heated surfaces! ‣ For high process temperatures: Install protection against contact in order to prevent burns.

Levelflex FMP55 PROFIBUS PA

Basic safety instructions Endress+Hauser 9 2.3 Workplace safety For work on and with the device: ‣ Wear the required personal protective equipment according to federal/national regulations. 2.4 Operational safety Risk of injury. ‣ Operate the device in proper technical condition and fail-safe condition only. ‣ The operator is responsible for interference-free operation of the device. Conversions to the device Unauthorized modifications to the device are not permitted and can lead to unforeseeable dangers. ‣ If, despite this, modifications are required, consult with the manufacturer. Repair To ensure continued operational safety and reliability, ‣ Carry out repairs on the device only if they are expressly permitted. ‣ Observe federal/national regulations pertaining to repair of an electrical device. ‣ Use original spare parts and accessories from the manufacturer only. Hazardous area To eliminate a danger for persons or for the facility when the device is used in the hazardous area (e.g. explosion protection, pressure vessel safety): ‣ Based on the nameplate, check whether the ordered device is permitted for the intended use in the hazardous area. ‣ Observe the specifications in the separate supplementary documentation that is an integral part of these Instructions. 2.5 Product safety This measuring device is designed in accordance with good engineering practice to meet state- of-the-art safety requirements, has been tested, and left the factory in a condition in which it is safe to operate. It meets general safety standards and legal requirements. NOTICE Loss of degree of protection by opening of the device in humid environments ‣ If the device is opened in a humid environment, the degree of protection indicated on the nameplate is no longer valid. This may also impair the safe operation of the device. 2.5.1 CE mark The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in the corresponding EC Declaration of Conformity together with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.

Levelflex FMP55 PROFIBUS PA

10 Endress+Hauser 2.5.2 EAC conformity The measuring system meets the legal requirements of the applicable EAC guidelines. These are listed in the corresponding EAC Declaration of Conformity together with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the EAC mark. 3 Product description 3.1 Product design 3.1.1 Levelflex FMP51/FMP52/FMP54/FMP55 1 2 5 3 4 6 A0012399  1 Design of the Levelflex 1 Electronics housing 2 Process connection (here as an example: flange) 3 Rope probe 4 End-of-probe weight 5 Rod probe 6 Coax probe

Levelflex FMP55 PROFIBUS PA

Incoming acceptance and product identification Endress+Hauser 11 4 Incoming acceptance and product identification 4.1 Incoming acceptance Upon receipt of the goods check the following: • Are the order codes on the delivery note and the product sticker identical? • Are the goods undamaged? • Do the nameplate data match the ordering information on the delivery note? • If required (see nameplate): Are the Safety Instructions (XA) present? If one of these conditions is not satisfied, contact your Endress+Hauser Sales Center. 4.2 Product identification The following options are available for identification of the measuring device: • Nameplate specifications • Order code with breakdown of the device features on the delivery note • Enter serial numbers from nameplates in W@M Device Viewer ( www.endress.com/deviceviewer ): All information about the measuring device is displayed. • Enter the serial number from the nameplates into the Endress+Hauser Operations App or scan the 2-D matrix code (QR code) on the nameplate with the Endress+Hauser Operations App: all the information for the measuring device is displayed. 4.2.1 Nameplate Order code: Ext. ord. cd.: Ser. no.: Order code: Ext. ord. cd.: Ser. no.: 1 2 3 4 A0030196  2 Example of a nameplate 1 Order code 2 Serial number (Ser. no.) 3 Extended order code (Ext. ord. cd.) 4 2-D matrix code (QR code) For detailed information about interpreting the nameplate specifications, refer to the Operating Instructions for the device. Only 33 digits of the extended order code can be indicated on the nameplate. If the extended order code exceeds 33 digits, the rest will not be shown. However, the complete extended order code can be viewed in the operating menu of the device in the Extended order code 1 to 3 parameter.

Levelflex FMP55 PROFIBUS PA

12 Endress+Hauser 5 Storage, Transport 5.1 Storage conditions • Permitted storage temperature: –40 to +80 °C (–40 to +176 °F) • Use the original packaging. 5.2 Transport product to the measuring point LWARNING Housing or probe may be damaged or break away. Risk of injury! ‣ Transport the measuring device to the measuring point in its original packaging or at the process connection. ‣ Do not fasten lifting devices (hoisting slings, lifting eyes etc.) at the housing or the probe but at the process connection. Take into account the mass center of the device in order to avoid unintended tilting. ‣ Comply with the safety instructions, transport conditions for devices over 18kg (39.6lbs) (IEC61010). A0013920 NOTICE Shipping lock for FMP5x with coax probe ‣ For FMP5x with coax probe the coax tube is not fixed permanently to the electronics housing. For shipping and transport it is secured with two cable ties. In order to prevent the spacer at the probe rod from moving along the probe, these cable ties must not be loosened when transporting and mounting the device. They may only be undone directly before screwing the device flange to the process connection.

Levelflex FMP55 PROFIBUS PA

14 Endress+Hauser 6 Mounting 6.1 Mounting requirements 6.1.1 Suitable mounting position A0011281  3 Mounting position of Levelflex FMP55 • Rod probes / rope probes: must be mounted in a stilling well or bypass. • Coax probes: can be mounted at an arbitrary distance from the wall of the vessel. • When mounting in the open, a weather protection cover may be installed to protect the device against extreme weather conditions. • Minimum distance from the end of probe to the bottom of the vessel: 10 mm (0.4 in)

Levelflex FMP55 PROFIBUS PA

Mounting Endress+Hauser 15 6.1.2 Securing the probe Securing coax probes For WHG approvals: For probe lengths ≥ 3 m (10 ft) a support is required. A0012608 Coax probes can be supported at any point of the outer tube.

Levelflex FMP55 PROFIBUS PA

16 Endress+Hauser 6.2 Mounting the device 6.2.1 Required mounting tools • For flanges and other process connections: appropriate mounting tools • To turn the housing: Hexagonal wrench 8 mm 6.2.2 Mounting the device Flange mounting If a seal is used, be sure to use unpainted metal bolts to ensure good electrical contact between probe flange and process flange. Mounting rope probes NOTICE Electrostatic discharges may damage the electronics. ‣ Earth the housing before lowering the rope into the vessel. * A0012852 When lowering the rope probe into the vessel, observe the following: • Uncoil rope and lower it slowly and carefully into the vessel. • Do not kink the rope. • Avoid any backlash, since this might damage the probe or the vessel fittings. 6.2.3 Mounting the "Sensor remote" version This section is only valid for devices of the version "Probe Design" = "Sensor remote" (feature 600, option MB/MC/MD). For the version "Probe design" = "Sensor remote" the following is supplied:

Levelflex FMP55 PROFIBUS PA

Mounting Endress+Hauser 17 • The probe with the process connection • The electronics housing • The mounting bracket for wall or pipe mounting of the electronics housing • The connection cable (length as ordered). The cable has got one straight and one angled plug (90°). Depending on the local conditions the angled plug can be connected at the probe or at the electronics housing. LCAUTION The plugs of the connection cable may be damaged by mechanical stress. ‣ Mount the probe and the electronics housing tightly before connecting the cable. ‣ Lay the cable such that it is not exposed to mechanical stress. Minimum bending radius: 100 mm (4"). ‣ When connecting the cable: Connect the straight plug before the angled one. Torque for both coupling nuts: 6 Nm. Probe, electronics and connection cable are adjusted to match each other. They are marked by a common serial number. Only components with the same serial number shall be connected to each other. If the measuring point is exposed to strong vibrations, an additional locking compound (e.g. Loctite 243) can be applied at the plug connectors.

Levelflex FMP55 PROFIBUS PA

18 Endress+Hauser Mounting the electronics housing 122 (4.8) 52 (2) 86 (3.4) 70 (2.8) 127...140 (5...5.51) 161 (6.34) 162...175 (6.38...6.89) A B ø42...60 (1.65...2.36) A0014793  4 Mounting the electronics housing using the mounting bracket; dimensions: mm (in) A Wall mounting B Pipe mounting Connecting the cable Required tools: Open-end wrench 18AF

Levelflex FMP55 PROFIBUS PA

Mounting Endress+Hauser 19 A B C C r = 100 (4) min r = 100 (4) min 6 Nm (4.42 lbf ft) 6 Nm (4.42 lbf ft) 6 Nm (4.42 lbf ft) 6 Nm (4.42 lbf ft) A0014794  5 Connecting the cable. There are the following possibilities: A Angled plug at the probe B Angled plug at the electronics housing C Length of the remote cable as ordered 6.2.4 Turning the transmitter housing To provide easier access to the connection compartment or display module, the transmitter housing can be turned: max. 350° 8 mm 8 mm 1. 2. 3. A0032242

Levelflex FMP55 PROFIBUS PA

20 Endress+Hauser 1. Unscrew the securing screw using an open-ended wrench. 2. Rotate the housing in the desired direction. 3. Tighten the securing screw (1.5 Nm for plastic housing; 2.5 Nm for aluminum or stainless steel housing). 6.2.5 Turning the display Opening cover 2. 1. 3 mm A0021430 1. Loosen the screw of the securing clamp of the electronics compartment cover using an Allen key (3 mm) and turn the clamp 90 ° counterclockwise. 2. Unscrew cover and check lid gasket, replace if necessary. Turning the display module 1. 2. A0036401 1. Pull out the display module with a gentle rotational movement. 2. Rotate the display module to the desired position: max. 8 × 45 ° in each direction.

Levelflex FMP55 PROFIBUS PA

Mounting Endress+Hauser 21 3. Feed the coiled cable into the gap between the housing and main electronics module and plug the display module into the electronics compartment until it engages. Closing electronics compartment cover 2. 2,5 Nm 3 mm 1. A0021451 1. Screw back firmly electronics compartment cover. 2. Turning securing clamp 90 ° clockwise and tighten the clamp with 2.5 Nm using the Allen key (3 mm).

Levelflex FMP55 PROFIBUS PA

22 Endress+Hauser 6.3 Post-installation check m Is the device undamaged (visual inspection)? m Does the device conform to the measuring point specifications? For example: • Process temperature • Process pressure (refer to the chapter on "Material load curves" of the "Technical Information" document) • Ambient temperature range • Measuring range m Are the measuring point identification and labeling correct (visual inspection)? m Is the device adequately protected from precipitation and direct sunlight? m Are the securing screw and securing clamp tightened securely?

Levelflex FMP55 PROFIBUS PA

Electrical connection Endress+Hauser 23 7 Electrical connection 7.1 Connection conditions 7.1.1 Terminal assignment Terminal assignment 4-wire: 4-20 mA HART (90 to 253 VAC) 3 1 + L 4 2 - N 1 3 2 A0036519  6 Terminal assignment 4-wire: 4-20 mA HART (90 to 253 VAC) 1 Connection 4-20 mA HART (active): terminals 3 and 4 2 Connection supply voltage: terminals 1 and 2 3 Terminal for cable screen

Levelflex FMP55 PROFIBUS PA

24 Endress+Hauser LCAUTION To ensure electrical safety: ‣ Do not disconnect the protective connection. ‣ Disconnect the supply voltage before disconnecting the protective earth. Connect protective earth to the internal ground terminal (3) before connecting the supply voltage. If necessary, connect the potential matching line to the external ground terminal. In order to ensure electromagnetic compatibility (EMC): Do not only ground the device via the protective earth conductor of the supply cable. Instead, the functional grounding must also be connected to the process connection (flange or threaded connection) or to the external ground terminal. An easily accessible power switch must be installed in the proximity of the device. The power switch must be marked as a disconnector for the device (IEC/EN61010).

Levelflex FMP55 PROFIBUS PA

Electrical connection Endress+Hauser 25 Terminal assignment PROFIBUS PA / FOUNDATION Fieldbus 1 3 + + 2 4 - - A 1 3 + + 2 4 - - B 1 4 5 2 3 A0036500  7 Terminal assignment PROFIBUS PA / FOUNDATION Fieldbus A Without integrated overvoltage protection B With integrated overvoltage protection 1 Connection PROFIBUS PA / FOUNDATION Fieldbus: terminals 1 and 2, without integrated overvoltage protection 2 Connection switch output (Open Collector): terminals 3 and 4, without integrated overvoltage protection 3 Connection switch output (Open Collector): terminals 3 and 4, with integrated overvoltage protection 4 Connection PROFIBUS PA / FOUNDATION Fieldbus: terminals 1 and 2, with integrated overvoltage protection 5 Terminal for cable screen

Levelflex FMP55 PROFIBUS PA

26 Endress+Hauser Block diagram PROFIBUS PA / FOUNDATION Fieldbus + + - - Y I 2 3 1 2 3 4 1 4 A0036530  8 Block diagram PROFIBUS PA / FOUNDATION Fieldbus 1 Cable screen; observe cable specifications 2 Connection PROFIBUS PA / FOUNDATION Fieldbus 3 Measuring device 4 Switch output (open collector)

Levelflex FMP55 PROFIBUS PA

Electrical connection Endress+Hauser 27 7.1.2 Device plug connectors For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be connected without opening the housing. Pin assignment of the M12 plug connector 2 1 3 4 A0011175 Pin Meaning 1 Signal + 2 not connected 3 Signal - 4 Ground Pin assignment of the 7/8" plug connector 4 2 3 1 A0011176 Pin Meaning 1 Signal - 2 Signal + 3 Not connected 4 Screen

Levelflex FMP55 PROFIBUS PA

28 Endress+Hauser 7.1.3 Power supply PROFIBUS PA, FOUNDATION Fieldbus "Power supply; Output" 1) "Approval" 2) Terminal voltage E: 2-wire; FOUNDATION Fieldbus, switch output G: 2-wire; PROFIBUS PA, switch output • Non-Ex • Ex nA • Ex nA[ia] • Ex ic • Ex ic[ia] • Ex d[ia] / XP • Ex ta / DIP • CSA GP 9 to 32 V 3) • Ex ia / IS • Ex ia + Ex d[ia] / IS + XP 9 to 30 V 3) 1) Feature 020 of the product structure 2) Feature 010 of the product structure 3) Input voltages up to 35 V will not spoil the device. Polarity sensitive No FISCO/FNICO compliant according to IEC 60079-27 Yes 7.1.4 Overvoltage protection If the measuring device is used for level measurement in flammable liquids which requires the use of overvoltage protection according to DIN EN 60079-14, standard for test procedures 60060-1 (10 kA, pulse 8/20 μs), an overvoltage protection module has to be installed. Integrated overvoltage protection module An integrated overvoltage protection module is available for 2-wire HART as well as PROFIBUS PA and FOUNDATION Fieldbus devices. Product structure: Feature 610 "Accessory mounted", option NA "Overvoltage protection". Technical data Resistance per channel 2 × 0.5 Ω max. Threshold DC voltage 400 to 700 V Threshold impulse voltage < 800 V Capacitance at 1 MHz < 1.5 pF Nominal arrest impulse voltage (8/20 μs) 10 kA

Levelflex FMP55 PROFIBUS PA

Electrical connection Endress+Hauser 29 External overvoltage protection module HAW562 or HAW569 from Endress+Hauser are suited as external overvoltage protection. For detailed information please refer to the following documents: • HAW562: TI01012K • HAW569: TI01013K 7.2 Connecting the measuring device LWARNING Risk of explosion! ‣ Observe applicable national standards. ‣ Comply with the specifications in the Safety Instructions (XA). ‣ Use specified cable glands only. ‣ Check to ensure that the power supply matches the information on the nameplate. ‣ Switch off the power supply before connecting the device. ‣ Connect the potential matching line to the outer ground terminal before applying the power supply. Required tools/accessories: • For devices with a cover lock: Allen key AF3 • Wire stripper • When using stranded cables: One ferrule for every wire to be connected. 7.2.1 Opening connection compartment cover 2. 1. 3 mm A0021490 1. Loosen the screw of the securing clamp of the connection compartment cover using an Allen key (3 mm) and turn the clamp 90 ° clockwise. 2. Afterwards unscrew connection compartment cover and check lid gasket, replace if necessary.

Levelflex FMP55 PROFIBUS PA

30 Endress+Hauser 7.2.2 Connecting 10 (0.4) 10 (0.4) 2. 3. 3. 1. A0036418  9 Dimensions: mm (in) 1. Push the cable through the cable entry . To ensure tight sealing, do not remove the sealing ring from the cable entry. 2. Remove the cable sheath. 3. Strip the cable ends over a length of 10 mm (0.4 in). In the case of stranded cables, also fit ferrules. 4. Firmly tighten the cable glands. 5. Connect the cable in accordance with the terminal assignment.  2 1 4 3 2 1 4 3 A0034682 6. If using shielded cables: Connect the cable shield to the ground terminal.

Levelflex FMP55 PROFIBUS PA

Electrical connection Endress+Hauser 31 7.2.3 Plug-in spring-force terminals In the case of devices without integrated overvoltage protection, electrical connection is via plug-in spring-force terminals. Rigid conductors or flexible conductors with ferrules can be inserted directly into the terminal without using the lever, and create a contact automatically. ≤3 (0.12) 1. 2. A0013661  10 Dimensions: mm (in) To remove cables from the terminal: 1. Using a flat-blade screwdriver ≤ 3 mm, press down on the slot between the two terminal holes 2. while simultaneously pulling the cable end out of the terminal. 7.2.4 Closing connection compartment cover 1. 2. 2,5 Nm 3 mm A0021491 1. Screw back firmly connection compartment cover.

Integration into a PROFIBUS network

Levelflex FMP55 PROFIBUS PA 32 Endress+Hauser 2. Turning securing clamp 90 ° counterclockwise and tighten the clamp with 2.5 Nm (1.84 lbf ft) again using the Allen key (3 mm). 7.3 Post-connection check  Is the device or cable undamaged (visual check)?  Do the cables comply with the requirements ?  Do the cables have adequate strain relief?  Are all cable glands installed, securely tightened and leak-tight?  Does the supply voltage match the specifications on the nameplate?  Is the terminal assignment correct?  If required: Has protective ground connection been established ?  If supply voltage is present, is the device ready for operation and do values appear on the display module?  Are all housing covers installed and securely tightened?  Is the securing clamp tightened correctly? 8 Integration into a PROFIBUS network 8.1 Overview of the device database files (GSD) Manufacturer ID 17 (0x11) Ident number 0x1558 Profile version 3.02 GSD file Information and files under: • www.endress.com • www.profibus.org GSD file version

Levelflex FMP55 PROFIBUS PA

Integration into a PROFIBUS network Endress+Hauser 33 8.2 Set device address 2 98 3 4 5 6 7 8 1 DIP ON A0015686  11 Address switches in terminal compartment 8.2.1 Hardware adressing 1. Set switch 8 to "OFF". 2. Define the address with switches 1 to 7 according to the table below. The address change becomes effective after 10 seconds. The device restarts automatically. Switch 1 2 3 4 5 6 7 Value in position "ON" 1 2 4 8 16 32 64 Value in position "OFF" 0 0 0 0 0 0 0 2 98 3 4 5 6 7 8 1 DIP ON 2 + 8 = 10 A0015902  12 Example of hardware addressing: switch 8 is in position "OFF"; switches 1 to 7 define the address. 8.2.2 Software addressing 1. Set switch 8 to "ON". 2. The device restarts automatically. The address remains the same as before (factory setting: 126). 3. Set the required address via the operating menu: Setup → Device address

Integration into a PROFIBUS network

Levelflex FMP55 PROFIBUS PA 34 Endress+Hauser 2 98 3 4 5 6 7 8 1 DIP ON A0015903  13 Example of software addressing; switch 8 is in position "ON"; the address is defined in the operating menu (Setup → Device address)

Levelflex FMP55 PROFIBUS PA

Commissioning via wizard Endress+Hauser 35 9 Commissioning via wizard A wizard guiding the user through the initial setup is available in FieldCare and DeviceCare 1). 1. Connect the device to FieldCare or DeviceCare (for details refer to the "Operating options" chapter of the Operating Instructions). 2. Open the device in FieldCare or DeviceCare.  The dashboard (home page) of the device appears: 1 A0025866 1 "Commissioning" button calls up the wizard. 3. Click on "Commissioning" to call up the wizard. 4. Enter or select the appropriate value for each parameter. These values are immediately written to the device. 5. Click "Next" to switch to the next page. 6. After finishing the last page, click "End of sequence" to close the wizard. If the wizard is cancelled before all necessary parameters have been set, the device may be in an undefined state. A reset to the default settings is recommended in this case. 1) DeviceCare is available for download at www.software-products.endress.com. The download requires a registration in the Endress+Hauser software portal.

Commissioning (via operating menu)

Levelflex FMP55 PROFIBUS PA 36 Endress+Hauser 10 Commissioning (via operating menu) 10.1 Display and operating module 10.1.1 Display appearance 3.1 3.2 2.1 2.2 2.4 2.5 1.1 1.2 1.3 1.4 2.3 2.6 1 2 3 4 5 ESC OPEN OPEN E ABC_ DEFG User HIJK LMNO PQRS TUVW XYZ Aa1 3 4 0 1 2 9 5 6 8 7 20 A0012635  14 Appearance of the display and operation module for on-site operation 1 Measured value display (1 value max. size) 1.1 Header containing tag and error symbol (if an error is active) 1.2 Measured value symbols 1.3 Measured value 1.4 Unit 2 Measured value display (1 bargraph + 1 value) 2.1 Bargraph for measured value 1 2.2 Measured value 1 (including unit) 2.3 Measured value symbols for measured value 1 2.4 Measured value 2 2.5 Unit for measured value 2 2.6 Measured value symbols for measured value 2 3 Representation of a parameter (here: a parameter with selection list) 3.1 Header containing parameter name and error symbol (if an error is active) 3.2 Selection list;  marks the current parameter value. 4 Input matrix for numbers 5 Input matrix for alphanumeric and special characters

Levelflex FMP55 PROFIBUS PA

Commissioning (via operating menu) Endress+Hauser 37 10.1.2 Operating elements Key Meaning A0018330 Minus key For menu, submenu Moves the selection bar upwards in a picklist. For text and numeric editor In the input mask, moves the selection bar to the left (backwards). A0018329 Plus key For menu, submenu Moves the selection bar downwards in a picklist. For text and numeric editor In the input mask, moves the selection bar to the right (forwards). A0018328 Enter key For measured value display • Pressing the key briefly opens the operating menu. • Pressing the key for 2 s opens the context menu. For menu, submenu • Pressing the key briefly Opens the selected menu, submenu or parameter. • Pressing the key for 2 s for parameter: If present, opens the help text for the function of the parameter. For text and numeric editor • Pressing the key briefly – Opens the selected group. – Carries out the selected action. • Pressing the key for 2 s confirms the edited parameter value. + A0032909 Escape key combination (press keys simultaneously) For menu, submenu • Pressing the key briefly – Exits the current menu level and takes you to the next higher level. – If help text is open, closes the help text of the parameter. • Pressing the key for 2 s returns you to the measured value display ("home position"). For text and numeric editor Closes the text or numeric editor without applying changes. + A0032910 Minus/Enter key combination (press and hold down the keys simultaneously) Reduces the contrast (brighter setting). + A0032911 Plus/Enter key combination (press and hold down the keys simultaneously) Increases the contrast (darker setting).

Commissioning (via operating menu)

Levelflex FMP55 PROFIBUS PA 38 Endress+Hauser 10.1.3 Opening the context menu Using the context menu, the user can call up the following menus quickly and directly from the operational display: • Setup • Conf. backup disp. • Env.curve • Keylock on Opening and closing the context menu The user is in the operational display. 1. Press  for 2 s.  The context menu opens. XXXXXXXXXX kg/h 50 Setup Conf.backup disp Env. curve Keylock on A0033110-EN 2. Press  +  simultaneously.  The context menu is closed and the operational display appears. Calling up the menu via the context menu 1. Open the context menu. 2. Press  to navigate to the desired menu. 3. Press  to confirm the selection.  The selected menu opens.

Levelflex FMP55 PROFIBUS PA

Commissioning (via operating menu) Endress+Hauser 39 10.2 Operating menu Parameter/Submenu Meaning Description Language 1) Defines the operating language of the on-site display. BA01008F (Operating Instructions FMP55, PROFIBUS PA) Setup When appropriate values have been assigned toall setup parameters, the measured should be completely configured in a standard application. Setup→Mapping Interference echo suppression Setup→Advanced setup Contains further submenus and parameters: • to adapt the device to special measuring conditions. • to process the measured value (scaling, linearization). • to configure the signal output. Diagnostics Contains the most important parameters needed to detect and analyze operational errors. Expert 2) Contains all parameters of the device (including those which are already contained in one of the above submenus). This menu is organized according to the function blocks of the device. GP01001F (Description of Device Parameters FMP5x, PROFIBUS PA) 1) In case of operation via operating tools (e.g. FieldCare), the "Language" parameter is located at "Setup→Advanced setup→Display" 2) On entering the "Expert" menu, an access code is always requested. If a customer specific access code has not been defined, "0000" has to be entered.

Commissioning (via operating menu)

Levelflex FMP55 PROFIBUS PA 40 Endress+Hauser 10.3 Unlock the device If the device has been locked, it must be unlocked before the measurement can be configured. For details refer to the Operating Instructions of the device: BA01008F (FMP55, PROFIBUS PA) 10.4 Setting the operating language Factory setting: English or ordered local language XXXX XXX X X 20.50 Operation Setup Main menu 0104-1 Display language English Español Français Display language English Deutsch à 0104-1 à Español Français Display language English Deutsch 0104-1 Betrieb Setup Hauptmenü Sprache Deutsch 0104-1 XX XX 1. 2. 3. 4. A0029420  15 Using the example of the local display

Levelflex FMP55 PROFIBUS PA

Commissioning (via operating menu) Endress+Hauser 41 10.5 Configuration of an interface measurement DL LL F LI UP DI LN E R 0% 100% DK (DC ) 2 2 DK DC 1 1 ( ) A0011177  16 Configuration parameters for interface measurements R = Reference pioint of the measurement DI = Interface distance (Distance from reference point to lower medium) E = Empty calibration (= zero point) LI = Interface F = Full calibration (= span) DL = Distance LN = Length of probe LL = Level UP = Measured thickness upper layer 1. Setup → Tag description  Enter tag for measuring point. 2. Setup → Device address  Enter bus address of the device (only in case of software addressing). 3. Setup  →  Operating mode  Select the Interface with capacitance option 4. Setup  →  Distance unit  Select distance unit. 5. Setup  →  Tank type  Select tank type. 6. Setup  →  Tube diameter (only if "Tank type" = "Bypass / pipe")  Enter the diameter of the bypass or stilling well.

Commissioning (via operating menu)

Levelflex FMP55 PROFIBUS PA 42 Endress+Hauser 7. Setup  →  DC value  Enter dielectric constant of the upper medium. 8. Setup  →  Empty calibration  Enter the distance E between the reference point R and the minimum level (0%). 9. Setup  →  Full calibration  Enter distance F between the minimum (0%) and maximum (100%) level. 10. Setup  →  Level  Displays the measured level LL. 11. Setup  →  Interface  Displays the interface height LI. 12. Setup  →  Distance  Displays the distance DL between the reference point R and the level LL. 13. Setup  →  Interface distance  Displays the distance DI between the reference point R and the interface LI. 14. Setup  →  Signal quality  Displays the signal quality of the level echo. 15. Setup  →  Mapping  →  Confirm distance  Make sure the vessel is completely empty. Then select the Tank empty option. NOTICE Wrong dielectric constant of the lower medium may cause a measuring error. ‣ If in the case of Operating mode = Interface with capacitance the lower medium is no water, it is necessary to specify its dielectric constant (DC value): Setup → Advanced setup → Interface  →  DC value lower medium NOTICE Wrong empty capacity may cause a measuring error. ‣ For rod and rope probes with Operating mode = Interface with capacitance, a correct measurement is only possible after the empty capacity has been determined. To do so, make sure that the vessel is completely empty. Then select Confirm distance = Tank empty (Step 13 in the table above). For coax probes the correct empty capacitance is always set on delivery. 10.6 User-specific applications For details of setting the parameters of user-specific applications, see separate documentation: BA01008F (Operating Instructions FMP55, PROFIBUS PA) For the Expert submenu refer to: GP01001F (Description of Device Parameters FMP5x, PROFIBUS PA)