eta External ETAtouch Installation Manual

Text of the manual

A-4716 Hofkirchen an der Trattnach

Tel: +43 (0) 7734 / 22 88 -0 Fax: +43 (0) 7734 / 22 88 -22 [email protected] www.eta.co.at

General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.1 Control panel with concealed housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.2 Control panel with surface-mounted housing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.3 CAN bus installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.3.1 Setting node numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 3 Concluding activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.1 Software version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.2 ETAtouch software update. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.2.1 Download software update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.2.2 Up to software version X.35.X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 3.2.3 Software version X.36.0 and later . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 3.3 meinETA remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 3.3.1 Up to software version X.35.X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 3.3.2 Software version X.36.0 and later . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

All contents of this document are property of ETA

Heiztechnik GmbH and are protected by copyright. Any reproduction, transfer to third parties or use for other purposes is prohibited without written permission from the owner. Software Description The software version described in this documentation corresponds to the version valid at the time of publica- tion. The software version installed on your product may differ from that described in this documentation. A software update to a more recent version can always be performed. With the appropriate au- thorisation, the required files can be found at "www.eta.co.at". Subject to technical changes We reserve the right to make technical modifications without notice. Printing and typesetting errors or changes of any kind made in the interim are not cause for claims. Individual configurations depicted or described here are only available optionally. In the event of contradictions between individual documents regarding delivery scope, the information in our current price list applies. Properly dispose of parts which are no longer required. All parts which are no longer required must be disposed of properly and not sent back to ETA. Only parts which are still subject to warranty or guarantee claims are to be returned to ETA. Explanation of symbols Instructions and information Layout of safety instructions SIGNAL WORD! Type and source of danger Possible effects • Measures for avoiding the danger Types of safety instruction CAUTION! On non-compliance with this safety instruction, there is a risk of material damage. WARNING! On non-compliance with this safety instruction, there is a risk of physical injury. DANGER! On non-compliance with this safety instruction, there is a risk of major physical injury.

Control panel with concealed housing

5 2 Installation Assembly and installation only by qualified specialist personnel The assembly and installation may be performed by specialist personnel with the corresponding qualifications only. DANGER! Electric shock There are live parts on the circuit boards. If touched, they can cause injury and property damage.  Before beginning any work, isolate the system completely from all power sources, ensure that it cannot be switched back on, and verify that it is safely isolated from supply. 2.1 Control panel with concealed housing Mounting the control panel The control panel is delivered pre-assembled. Remove the control panel. The unit is held by a magnet. Unscrew the screw and remove the control panel to prevent it from being damaged during assembly. Make an opening in the wall for the housing. Fig. 2-1: Concealed housing

Control panel with concealed housing

Installation Fit the concealed housing into the wall flush with the outer edge. Mount the control panel only after the concealed housing has been mounted and the paint work, if any, is finished. Cover the concealed housing properly prior to any plastering or filling work. Insert the control panel and tighten the screw again. The distance between the control panel and the housing can be adjusted with the magnet holder. Run the CAN bus wire and the network cable (if available) down to the control panel.

Control panel with surface-mounted housing

7 2.2 Control panel with surface- mounted housing Mounting the control panel on the flush-mounted junction box It is possible to mount the control panel on a flush- mounted junction box (not included in delivery scope). To do so, you will need to use the four inner attachment points on the rear side of the surface- mounted housing. Should this not be possible, other attachment points are available for mounting on the wall. Run the CAN bus wire and the network cable (if available) down to the control panel.

CAN bus installation

Installation 2.3 CAN bus installation Establishing a CAN bus connection Two terminals and the associated line for establishing the CAN-bus connection to the ETAtouch control panel are included in the delivery scope. Allocation of CAN-Bus terminal Only clamp the "Sch" shield on one side. Example: connection to [EM-C] circuit board A terminal resistor (yellow jumper) must be set at the end of the CAN-Bus . If both CAN-Bus terminals are allocated, the terminal resistor must be removed on this circuit board. In the example listed above, the terminal resistor must be placed on the [EM-C] circuit board at [X1] as well as the ETAtouch control panel. Connections at the control panel "BE-P3" 1 LAN connection for network cable (e.g. for remote control "meinETA") 2 Socket for data line 3 Socket for CAN bus line 4 Terminal for yellow jumper 5 USB connections (e.g. for software update) 2.3.1 Setting node numbers Serveral control panels in the system If further control units (BE-P) are in the system, all of them must have different node numbers. The setted node number for each control panel is displayed in the ETAtouch control system. Depending on the software version installed (up to X.35.X or from X.36.0), the set node numbers are displayed different- ly. • Up to software version X.35.X On the control panel, press the button and then the [Software Version] button. The node number set is displayed in the overview. Fig. 2-2: Overview (up to X.35.X)

CAN bus installation

9 • Software version X.36.0 and later On the control panel, open the system settings and press the [Version overview] button. The node number set is displayed in the overview. Fig. 2-3: Overview (from X.36.0) Setting the node number is described in chapter 2.3.1.1 "Setting node numbers". Increasing the node number of the control panel The node number is set to "1" by default. If a control panel is already available with node number "1", this must be increased for the new control panel. 1. Switch off the entire heating system. 2. Detach the CAN-Low (CL) wire. 3. Switch on the entire heating system. 4. Set the node number (see chapter 2.3.1.1 "Setting node numbers") 5. Switch off the entire heating system once again. 6. Reattach the CAN-Low (CL) wire. 7. Restart the entire heating system. The change will only take effect after restarting. 2.3.1.1 Setting node numbers Up to software version X.35.X Set node number on ETAtouch control panel 1) Switch on the entire heating system. 2) On the ETAtouch control panel, press . 3) Press [Change authorisation]. 4) Raise the access level to [Service]. 5) Press [System configuration]. A window with the system settings appears. 6) Press the [Change] button next to [CAN node switch]. A window appears where you can enter the desired node number. The values 0 to 7 are permitted for the node numbers. 7) Press [Accept]. 8) Restart the entire heating system. The change will only take effect after the restart. Software version X.36.0 and later Set node number on ETAtouch control panel 1. Switch on the entire heating system. 2. On the ETAtouch control panel, increase the au- thorization level to [Service].

CAN bus installation

Installation 3. Press the [CAN network] button. A window appears where you can enter the desired node number. The values 0 to 7 are permitted for the node numbers. 4. Restart the entire heating system. The change will only take effect after the restart.

Check your installed software version

Software version 3.35.X is already installed on the "BE-P3" control panel. Whether a software update is required after the instal- lation also depends on whether or not other control panels are located within the system. Because for faultless communication between the control panels, the same software version must be installed on all units. The following table shows which software update is required after the installation. Version 1.XX.X is required for the "BE-P1" control panel software, 2.XX.X for "BE-P2" , and 3.XX.X for "BE-P3". As a precaution, you can also download all software versions for the user interface up to X.35.X (1.35.X, 2.35.X and 3.35.X) and the versions from X.36.0 (e.g.: 2.39.0 and 3.39.0). You can find information about downloading the software in chapter 3.2 "ETAtouch software update". You can find the description for the software update in chapter 3.2.2 "Up to software version X.35.X" and 3.2.3 "Software version X.36.0 and later". 3.2 ETAtouch software update 3.2.1 Download software update Download software update files Version 1.XX.X is required for the "BE-P1" control panel software, 2.XX.X for "BE-P2" , and 3.XX.X for "BE-P3". You can find the files required for the software update in the login area of the www.ETA.co.at website, and also on www.meinETA.at. 1. Download the software update: a) Login to the website with your username and password. In the login area, select the menu item [System Update], and download the appropriate software update. b) Or login to the website with your username and password. Press the [System settings] button in the navigation bar, and then select [Installation & software]. Download the relevant software update: 2. Copy the file to the root directory of a USB-memory stick (FAT32 or FAT16 formatting). The file may not be located in any folder and may not be renamed, otherwise the ETAtouch control system cannot find the file. Only one control panel exists installed version is lower than X.35.X => download latest version 3.35.X installed version is higher than X.36.0 => download latest version 3.XX.X (e.g. 3.39.X) installed version cannot be determined => download latest versions of 3.35.X and 3.XX.X (e.g. 3.39.X) Several control panels exist installed version is lower than X.35.X => download latest versions of 1.35.X as well as 2.35.X and 3.35.X installed version is higher than X.36.0 => download latest versions of 2.XX.X (e.g. 2.39.0) and 3.XX.X (e.g. 3.39.0) installed version cannot be determined => download latest versions of 1.35.X, 2.35.X, 3.35.X as well as 2.XX.X and 3.XX.X (e.g. 3.39.0)

ETAtouch software update

Concluding activities Implement updates one after another The installation of software versions X.36.0 and higher first requires an update to version X.35.X If a software version older than X.35.X is installed, first update to this version (see chapter 3.2.2 "Up to software version X.35.X"). Only then can the software be updated to later versions (X.36.0 or later) (see chapter 3.3.2 "Software version X.36.0 and later"). A corresponding message is displayed on the screen if your hardware does not support the new software version. 3.2.2 Up to software version X.35.X Update software A software update must always be carried out separately and in succession on the ETAtouch control panel of the boiler itself and on all further ETAtouch control panels. 1. Plug the USB-memory stick (with the files for the software update) into the ETAtouch control panel. 2. Press the button on the ETAtouch control panel. Then press the [Change authorisation] button. A window opens. Enter the password "135" and press [Log in] to confirm. 3. Press the [Update software] button. The software version already installed will be compared with the one on the USB-memory stick. 4. Select the desired software update in the [Versions at USB flash drive] window. 5. Press the [Start] button. The software update will be copied to the ETAtouch control system. If no USB- memory stick is detected, remove the USB-memory stick, plug it in again and press the [Refresh] button. 6. Press the [OK] button. The ETAtouch control panel will be restarted auto- matically. After the restart the software update will be configured and installed on the ETAtouch control panel. 7. After installation, a request appears to remove the USB -memory stick. After removing the USB memory stick, the ETAtouch control panel will restart automatically. The software update was successfully installed and completed when the (up to X.35.X) or symbol (X.36.0 or later) is displayed at the bottom of the screen. Install the software update on all further ETAtouch control panels in the same way.

meinETA remote control

13 3.2.3 Software version X.36.0 and later Update software A software update must always be carried out separately and in succession on the ETAtouch control panel of the boiler itself and on all further ETAtouch control panels. 1. Plug the USB-memory stick (with the files for the software update) into the ETAtouch control panel. 2. On the ETAtouch control panel, increase the au- thorization level to [Service]. For this, open the system settings and tap the [Authorisation] symbol. A settings window appears. Enter the password "135" and press [Accept the authorisa- tion] to confirm. 3. The software update menu opens by pressing the [Software update] button. If an update is available, it will appear on the screen. Fig. 3-1: Software update menu If the USB-memory stick is not detected, remove it, plug it in again and press the [Reload] button. 4. To install, press the symbol during the update. A safety notice appears to confirm this. The software update is then installed. 5. After installation, a request appears to remove the USB -memory stick. After removing the USB memory stick, the ETAtouch control panel will restart automatically. The software update was successfully installed and completed when the symbol is displayed at the bottom of the screen. Install the software update on all further ETAtouch control panels in the same way. 3.3 meinETA remote control register on "meinETA" If the "meinETA" remote control is used, you can also use this with the new control panel. To do so, simply register the new control panel with your access data. 3.3.1 Up to software version X.35.X Registering the ETAtouch controller 1. On the ETAtouch control panel, press . 2. Press the [meinETA access] button. 3. Press [Register]. 4. Enter the user name and the password from the meinETA access data. 5. Enter the boiler number. 6. Press [Register]. The data are transferred to ETA and the ETAtouch controller is registered for this user. 3.3.2 Software version X.36.0 and later Registering the ETAtouch controller 1. On the local ETAtouch control panel, press the button. 2. Press the [meinETA access] button. 3. Enter the access data [User name], [Password] and [Type plate]: a) Press the button. An on-screen keyboard appears for input. 4. Press the [Register now] button. The data is transferred to ETA and the ETAtouch control system is registered.

Other Control Panel Manuals