IDS 860-06-0005 Manual
Text of the manual
IDS Two Channel Remote Receiver
IDS Two Channel Remote Receiver
IDS Two Channel Remote Receiver
•
The Normally Open (NO), Normally Closed (NC)
IDS Two Channel
Receiver (Digital)
P/N 860-06-0005
Specifications
Power Supply
12V - 16V DC
Max. Power Consumption
175mA
Weight
145g
Dimensions (H x W x L)
33 x 66 x 104
2. Features
•
Two channel receiver
•
High noise immunity
•
238 Users + 64 supervised RF devices may be
learned
•
Signal Jamming Detection and Ambient Noise
Level indication
•
Advanced RF anti-collision software
•
Individual relay pulse periods selectable up to 10
minutes
•
Dedicated panic remotes may be learned
•
Selectable retrigger protection on any relay
•
Panel arming / disarming / stay arming and panic
through keypad bus
•
Expansion of panel zones with RF devices such
as RF passives.
3. Introduction
The IDS Digital Wireless Receiver is an extremely versatile
receiver unit that may be used either as a standalone
product or in conjunction with any DIGITAL IDS alarm panel
such as the IDS 816, 1224 or 1632. When used with a
DIGITAL IDS alarm panel, the receiver connects onto the
same communication and power bus as the keypad and
no other connections are needed to make use of any of
the advanced receiver functions.
4. Installation and Wiring
•
The IDS Digital Wireless receiver may be used in
either a standalone mode or connected to an IDS
and Common (COM) outputs of both relays are
available to be connected to external devices such
as gate operators or other alarm panels.
•
Relay 4ís NO contact is only available with jumper
6 in position 2. When Jumper 6 is in position 1
Relay 4ís NO contact is connected to ground via
the tamper switch on the receiver.
•
For ease of programming Jumper 5 may be used
to remove power to the unit after installation.
5. Switches, Jumpers, and Relays
•
The IDS Digital Wireless Receiver has 8 DIP
switches, 1 Tamper switch and 2 Jumpers
•
The 8 DIP switches are used to program the
receiver and adjust its available features. When
connected to an IDS DIGITAL alarm panel the
programming of users and RF devices such as
RF Passives are done through the panel keypad.
The programming of any of the other features does
however still need to be done using the DIP
switches.
•
Jumper 5 is the power jumper that may be used to
remove power from the unit when required to do
so during programming.
•
Jumper 6 selects between Relay 4ís NO contact
or the Tamper Switch Contact. The tamper switch
is internally connected to ground.
•
Any of the relay outputs may be used to switch a
maximum of 3A at a maximum of 24V DC. The
relays are not intended for switching high voltage
Colour
White
Channels
2
Users
238
Passives (Supervised)
64
•
•
DIGITAL alarm panel.
When used in standalone mode, the receiver
needs a supply of between 12V and 16V DC. The
Data lines D+ and D- do not need to be connected.
When connected to a DIGITAL IDS alarm panel,
the D+ and D- data lines must be connected to
the panelís D+ and D- data lines. (Connection of
relays to arm and disarm the panel via zones is
NOT needed. Arming and disarming of the panel
is done through the data bus.)
signals directly such as lights or motors.
IDS
IDS 700-284-5 AUG 2005 VER 1.40
IDS
IDS
1
2
3
IDS Two Channel Remote Receiver
IDS Two Channel Remote Receiver
IDS Two Channel Remote Receiver
6. Programming the Unit in Stand-Alone
Mode. (Power Up Settings)
N.B. to change any settings on the receiver unit, the
receiver needs to be powered down, the settings
changed and then powered up again.
Restoring the Factory Default Settings:
1. Remove power from the unit by removing jumper
J5 and switch all DIP switches OFF.
2. Switch DIP switches 1, 5, 6, 7 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. Switch DIP Switch 8 OFF.
5. Wait for the LEDís to start flashing alternately.
6. Switch ALL Dip switches OFF.
7. When the LEDís stop flashing the unit is in the
normal operating mode.
The factory default settings with all Dip switches
OFF and all jumpers ON are as follow:
Three Minute Retrigger Protect
Off
Remote Learn
Off
Panic Remote Learn
Off
RF Device Learn
Off
Ambient Noise Level Test
Off
Device Failure Relay
Disabled
Panic Relay
Enabled
3 Sec Remote Panic
Enabled
Relays
Pulse
Relay 4 Output
Selected
Power Jumper
On
Relay Pulse Period
3 Sec
Relays Safe / Secure
Secure
Panic Relay
Relay 4
RF Device Output Relay
None
Remote Button Outputs
Button 1
Relay 1
3 Sec Hold for Panic Button
All
Relay 3 Min Retrigger Protect
None
Signal Jamming Detect Period
30s
Device Not Reporting
1hr max
Deleting ALL the User Remotes:
1. Remove power from the unit by removing jumper
J5 and switch all DIP switches OFF.
2. Switch DIP switches 2, 5, 6, 7 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. Switch DIP Switch 8 OFF.
5. Wait for the LEDís to start alternating.
6. Switch ALL DIP switches OFF.
7. When the LEDís stop flashing the unit is in the
normal operating mode.
Deleting ALL Supervised RF Devices
(e.g. RF Passive IR’s):
1. Remove power from the unit by removing jumper
J5 and switch all DIP switches OFF.
2. Switch DIP switches 3, 5, 6, 7 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. Switch DIP Switch 8 OFF.
5. Wait for the LEDís to start flashing alternately.
6. Switch ALL DIP switches OFF.
7. When the LEDís stop flashing the unit is in the
normal operating mode.
Adjusting the Relay Pulse Periods:
1. Remove power from the unit by removing jumper
J5 and switch all DIP switches OFF.
2. Switch DIP switches 7 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. To adjust relay 1ís pulse period, switch DIP switch
1 ON.*
5. Wait for as long as the pulse needs to be (Up to
10 minutes).
6. Switch DIP switch 1 OFF (For relay 1ís pulse
period).
7. Switch DIP switch 8 OFF.
8. Wait for the LEDís to start flashing alternately.
9. Switch ALL DIP switches OFF.
10. When the LEDís stop flashing the unit is in the
normal operating mode.
Changing Between Relay Safe and Secure Modes:
1. Remove power from the unit by removing jumper
J5 and switch all DIP switches OFF.
2. Switch DIP switches 6 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. To make Relay 1 and 4 Fail Safe, switch DIP
switches 1 and 4 ON.* (Any relay not selected will
be Fail Secure.)
5. Switch DIP switch 8 OFF.
6. Wait for the LEDís to start flashing alternately.
7. Switch ALL DIP switches OFF.
8. When the LEDís stop flashing the unit is in the
normal operating mode.
Selecting the Panic Relay Output:
1. Remove power from the unit by removing jumper
J5 and switch all DIP switches OFF.
2. Switch DIP switches 6, 7 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. Select the relay to be the Panic Relay.* (If no relay
is selected, the panic relay will be disabled.)
5. Switch DIP switch 8 OFF.
6. Wait for the LEDís to start flashing alternately.
7. Switch ALL DIP switches OFF.
8. When the LEDís stop flashing the unit is in the
normal operating mode.
* *
Where indicated DIP switch 1 represents Relay 1,
DIP switch 4 represents Relay 4.
IDS
IDS 700-284-5 AUG 2005 VER 1.40
IDS
IDS
4
5
6
IDS Two Channel Remote Receiver
IDS Two Channel Remote Receiver
IDS Two Channel Remote Receiver
Selecting the Relay to Activate When a Remote
Button is Pressed:
1. Remove power from the unit by removing jumper
J5 and switch all DIP switches OFF.
2. Switch DIP switches 5 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. Select the relay to be the new Output Relay.* (If
no relay is selected, no relay will be activated when
the remote button is pressed.)
5. Press the button on a learned remote that must
activate the selected relay output.
6. Switch DIP switch 8 OFF.
7. Wait for the LEDís to start flashing alternately.
8. Switch ALL DIP switches OFF.
9. When the LEDís stop flashing the unit is in the
normal operating mode.
Protecting Relays from retriggering within 3
minutes after a previous trigger:
1. Remove power from the unit by removing jumper
J5 and switch all DIP switches OFF.
2. Switch DIP switches 5, 7 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. Select the relay(s) to be retrigger protected.*
5. Switch DIP switch 8 OFF.
6. Wait for the LEDís to start flashing alternately.
7. Switch ALL DIP switches OFF.
8. When the LEDís stop flashing the unit is in the
normal operating mode.
Assigning a Relay to be Activated when a RF
Device is Triggered:
1. Remove power from the unit by removing jumper
J5 and switch all DIP switches OFF.
2. Switch DIP switches 5, 6 and 8 ON.
3. Restore Power to the Unit by replacing J5
4. Select the relay to be activated.* (If no relay is
selected, no relay will be activated when the
remote button is pressed.)
5. Trigger the device that must activate the selected
Relay Output.
6. Switch Dip switch 8 OFF.
7. Wait for the LEDís to start flashing alternately.
8. Switch ALL Dip switches OFF.
9. When the LEDís stop flashing the unit is in the
normal operating mode.
Assigning a Dedicated Panic Button to a Remote:
N.B. This Function will affect ALL remotes.
1. Remove power from the unit by removing jumper
J5 and switch all Dip switches OFF.
2. Switch Dip switches 4 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. Press the button on a known remote that will
become an instant panic button.
5. Switch Dip switch 8 OFF.
6. Wait for the LEDís to start flashing alternately.
7. Switch ALL Dip switches OFF.
8. When the LEDís stop flashing the unit is in the
normal operating mode.
Assigning an Arm / Disarm Button on a Remote:
N.B. This Function will affect ALL remotes.
1. Remove power from the unit by removing jumper
J5 and switch all Dip switches OFF.
2. Switch Dip switches 3 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. Press the button on a known remote that will
become the Arm / Disarm button.
5. Switch Dip switch 8 OFF.
6. Wait for the LEDís to start flashing alternately.
7. Switch ALL Dip switches OFF.
8. When the LEDís stop flashing the unit is in the
normal operating mode.
Assigning a Stay Arm Button on a Remote:
N.B. This Function will affect ALL remotes.
1. Remove power from the unit by removing jumper
J5 and switch all Dip switches OFF.
2. Switch Dip switches 2 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. Press the button on a known remote that will
become the Stay Arm button.
5. Switch Dip switch 8 OFF.
6. Wait for the LEDís to start flashing alternately.
7. Switch ALL Dip switches OFF.
8. When the LEDís stop flashing the unit is in the
normal operating mode.
Assigning the Device Failure Output Relay:
1. Remove power from the unit by removing jumper
J5 and switch all Dip switches OFF.
2. Switch Dip switches 4, 7 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. Switch Dip switch 4 OFF.
5. Select the relay to be the Device Failure Relay.*
(If no relay is selected, the device failure relay will
be disabled.)
6. Switch Dip switch 8 OFF.
7. Wait for the LEDís to start flashing alternately.
8. Switch ALL Dip switches OFF.
9. When the LEDís stop flashing the unit is in the
normal operating mode.
Learning a New RF Device such as a RF Passive
IR:
1. Remove power from the unit by removing jumper
J5 and switch all Dip switches OFF.
2. Switch Dip switches 3, 7 and 8 ON.
3. Restore Power to the Unit by replacing J5.
4. Press the TAMPER switch on the Device to be
Learned.
5. Switch Dip switch 8 OFF.
6. Remove power from the unit and adjust Dip switch
setting as needed.
7. Restore power to the unit. When the LEDís stop
flashing the unit will be in normal operating mode.
* *
Where indicated DIP switch 1 represents Relay 1,
DIP switch 4 represents Relay 4.
IDS
IDS 700-284-5 AUG 2005 VER 1.40
IDS
IDS
7
8
9
IDS Two Channel Remote Receiver
IDS Two Channel Remote Receiver
IDS Two Channel Remote Receiver
7. Programming the Unit in Stand-Alone
Mode. (Normal Settings)
These settings may be adjusted during normal
operation and it is not necessary to power the unit
down for the settings to take effect.
Remote Arm or Disarm 3 Minute Retrigger Protecting:
1. Switch Dip switch 2 ON to enable retrigger
protecting.
Learning New Remotes:
1. Switch DIP switch 3 ON to enable learning of new
remotes.
2. Press any button on the remotes to be learned.
3. Switch DIP switch 3 OFF to exit the learn mode.
To indicate the Ambient Noise Level:
N.B. This function must be disabled during normal
operation
This function allows the testing of ambient noise in
2. Press any button on the remotes to be learned.
3. Switch DIP switch 6 OFF to exit the learn mode.
Disable the 3 second Hold for Panic Feature:
1. To disable the 3 second hold for panic feature on
ALL remotes switch DIP switch 7 ON.
Changing the Relays from Pulsing to Toggling:
1. Remove power from the unit by removing jumper
J5 and switch all DIP switches OFF.
2. Switch DIP switches 5, 6, 7 & 8 on.
3. Restore the power to the Unit by replacing J5.
4. To select toggling relays, use DIP switches 1 & 4
for Relays 1 & 4.
5. Switch DIP switch 8 off.
6. Wait for the LEDís to start alternating.
7. Switch all DIP switches off and set DIP switches
9. Connector, Switch and Jumper Positions
10. Program Summary and LED Indications:
the environment surrounding the receiver during
to the desired setting.
Switch Settings
1 2 3 4 5 6 7 8
R G
Function
installation.
1. Switch DIP switch 4 ON to enable noise level
testing.
2. ONLY install the receiver in an environment with
normal or better noise Levels.
During noise testing the LEDís indicate the following:
8. Programming a Unit Connected to a
DIGITAL IDS alarm panel.
When connected to a DIGITAL IDS alarm panel,
programming of the unit is as for the Stand-Alone
mode with the following exceptions.
~ ~ ~ ~ ~ ~ 1 0
1 0 PANIC DISABLE
~ ~
~ ~ ~ 1 ~ 0
1 2 LEARN PANIC
~ ~
~ ~ 1 ~ ~ 0 2 0 ERROR RELAY
~ ~
~ 1 ~ ~ ~ 0
1 0 TEST NOISE
~ ~
1 ~ ~ ~ ~ 0
1 4 LEARN
~ 1 ~ ~ ~ ~ ~ 0
1 0 RETRIG PROTECT
1 ~ ~ ~ ~ ~ ~ 0
1 0
0 0 0 0 0 0 1 1 3 0 PULSE PERIOD
RED
LED
GREEN
LED
NOISE
LEVEL
Learning and Deleting Individual User Remotes:
1. To learn a new user remote, leave DIP switch 3
0 0 0 0 0 1 0 1 4 3 SAFE/SECURE
0 0 0 0 0 1 1 1 4 0 PANIC RELAY
0 0 0 0 1 0 0 1 4
1 RELAY FOR
OFF
OFF
VERY LOW
ON (it need not be switched OFF for normal
operation when connected to an IDS DIGITAL
0 0 0 0 1 0 1 1 3 1 RELAY RETRIGGER
0 0 0 0 1 1 0 1 0 4 RELAY FOR DEVICE
OFF
SLOW
LOW
alarm panel).
0 0 0 1 0 0 0 1 0 3 PANIC BUTTON
OFF
FAST
NORMAL
2. Follow the user manual of the DIGITAL IDS alarm
0 0 1 0 0 0 0 1 0 3 ARM BUTTON
0 1 0 0 0 0 0 1 0 3 STAY BUTTON
SLOW
ONHIGH
panel for learning new users.
0 0 0 1 0 0 1 1 2 1 ERROR RELAY
FAST
ONVERY HIGH
Learning New Supervised RF Devices and deleting
0 0 1 0 0 0 1 1 1 3 LEARN DEVICE
0 1 0 0 0 0 1 1 3 2 RECEIVER ID
ON
ON POSSIBLE JAMMING
Devices by Zone allocation:
1. Follow the user manual of the DIGITAL IDS alarm
0 0 0 0 1 1 1 1 1 2 ELAY PULSE /
TOGGLE
0 0 1 0 1 1 1 1 4 4 DELETE DEVICES
Enabling the Device Failure Relay Output:
1. Switch DIP switch 5 ON
panel for learning new RF devices and deleting
RF devices by zone.
0 1 0 0 1 1 1 1 4 4 DELETE REMOTES
1 0 0 0 1 1 1 1 3 3 FACTORY RESETS
Learn New Panic Remotes:
1. Switch DIP Switch 6 ON
IDS
IDS 700-284-5 AUG 2005 VER 1.40
IDS
0 = OFF
1 = ON
2 = BLINK
3 = FAST
4 = SLOW
5 = ALT
R = RED LED
G = GREEN LED
3 4 MEMORY FULL
1 1 BUSY SIGNAL
0 0 INVALID SIGNAL
5 5 LOW BATT