Specified Controls SC-T32-TS Installation Manual
Text of the manual
TABLE OF CONTENTS
1
Introduction ............................................................................................................................................4
Getting Started .......................................................................................................................................5
Installing the Thermostat .....................................................................................................................6-8
Disassembly ..........................................................................................................................6
Thermostat Location ..............................................................................................................6
Mounting the Subbase ........................................................................................................6-7
Terminal Designations ............................................................................................................8
Setting the System Switches ..................................................................................................................9
System Switch Functions .....................................................................................................................10
Installing the Batteries ..........................................................................................................................11
Typical System Wiring Diagrams .....................................................................................................12-20
Heat only (Gas) ....................................................................................................................12
Heat only (Electric)................................................................................................................13
Cool only (Single or Multi-stage) ...........................................................................................14
1 Heat / 1 Cool (Gas) .............................................................................................................15
2 Heat / 2 Cool (Gas) .............................................................................................................16
2 Heat / 1 Cool (Heat Pump) ..................................................................................................17
3 Heat / 2 Cool (Heat Pump) ..................................................................................................18
TABLE OF CONTENTS
2
TABLE OF CONTENTS
2 Heat / 1 Cool (Dual Fuel) ....................................................................................................19
3 Heat / 2 Cool (Dual Fuel) ....................................................................................................20
Installer Setup Menu .......................................................................................................................21-43
Entering the Setup Menu ......................................................................................................21
Selecting the Programmable or Non-programmable Operation ............................................22
Selecting Number of Program Events ...................................................................................23
Selecting Mode ....................................................................................................................24
Selecting Programmable Fan ...............................................................................................25
Assigning Auxiliary Contacts ................................................................................................26
Selecting Touchscreen Lock Options ....................................................................................27
Selecting the Cooling Setpoint Limit .....................................................................................28
Selecting the Heating Setpoint Limit .....................................................................................29
Selecting Back Light Option ..................................................................................................30
Selecting Adaptive Recovery Option ....................................................................................31
Selecting First Stage Heating and Cooling Differential Option ...............................................32
Selecting Second Stage Heating and Cooling Differential Option ..........................................33
Selecting Third Stage Heating Differential Option .................................................................34
Selecting Demand Staging or Locked Staging Option ...........................................................35
Sensor Calibration ...............................................................................................................36
Selecting Low Balance Point Option .....................................................................................37
Selecting High Balance Point Option ....................................................................................38
Selecting Fahrenheit or Celsius ............................................................................................39
Selecting Audible ON/OFF ...................................................................................................40
TABLE OF CONTENTS
3
Timed Ventilation Duration ...................................................................................................41
Timed Ventilation Low Temp Limit .........................................................................................42
Timed Ventilation High Temp Limit ........................................................................................43
Daylight Saving Time ............................................................................................................44
Remote Sensor Installation .............................................................................................................45-47
Remote Sensor Types ..........................................................................................................45
SC-T-S1 Indoor Sensor Installation .................................................................................45-46
SC-T-OTS Outdoor Sensor Installation ................................................................................46
Temperature/Resistance Chart ............................................................................................47
Display Functions .................................................................................................................................48
Testing ............................................................................................................................................49-53
Fan Operation ......................................................................................................................49
Conventional Heating ...........................................................................................................49
Conventional Cooling .....................................................................................................49-50
Conventional Heat Pump .....................................................................................................50
Dual Fuel ..............................................................................................................................51
Low Balance Point ..........................................................................................................51-52
High Balance Point ...............................................................................................................52
Adaptive Recovery .........................................................................................................52-53
Programmable Fan ..............................................................................................................53
Auxiliary Contacts ................................................................................................................53
Timed Ventilation Setup ..................................................................................................................54-55
Basic Troubleshooting .....................................................................................................................56-57
Specifications .......................................................................................................................................58
The SC-T32-TS is a feature-rich touchscreen thermostat that can be battery powered or hardwired to
the HVAC equipment. Using a common sense approach to the installation will ensure this product is
installed properly and to the customer’s satisfaction. Please take time to read and understand this
manual so that installation and testing is performed in an efficient manner.
This manual is to be used in conjunction with the supplied User Manual.
Although great care has been taken in the preparation of this manual, Specified Controls takes
no responsibility for errors or omissions contained herein. It is the responsibility of the
installer to ensure that this thermostat and the equipment connected to it operate in a safe and
efficient manner.
Due to ongoing product improvements, Specified Controls reserves the right to change the
specifications of the SC-T32-TS thermostat or its components without notice.
All rights reserved.
©Specified Controls 2019.
Intellectual rights apply.
4
As with any HVAC project, careful installation is the key to a successful outcome.
Time taken during the installation process will be rewarded with fewer call-backs.
The steps required to install the SC-T32-TS thermostat are as follows.
1. Read and understand this Installation Manual and User Manual.
2. Mount and wire the subbase.
3. Install the batteries.
4. Set the 4 system switches to match the equipment application.
5. Wire optional remote temperature sensor(s).
6. Power the thermostat.
7. Set the Advanced Installer settings.
8. Test the thermostat.
5
INSTALLING THE THERMOSTAT
DISASSEMBLY
There are two release slots located on the bottom of the thermostat. Gently push
the flat blade of a small screwdriver into one slot at a time and pry upward until
the catch disengages. Carefully swing the thermostat upward and away from the
subbase. (Figure 1)
THERMOSTAT LOCATION
The thermostat should be installed in a location that
represents the ambient space temperature. Do not install
the thermostat in an area where drafts are present, near
the floor, behind doors or on an external wall. Avoid
placing the thermostat in areas where the air movement
is limited, affected by direct sunlight or other areas not
typical of the temperature in the space.
MOUNTING THE SUBBASE
When mounting the thermostat subbase, be aware that drafts
may travel down wall cavities and enter the back of the
thermostat through the control wire hole in the wall. It is
important to seal the hole to prevent any drafts that might affect
the internal temperature sensor.
FIGURE 1
6
INSTALLING THE THERMOSTAT
Pull the control wires through the large opening in the thermostat subbase. Next,
level and mount the subbase on the wall using the supplied anchors and screws.
(Figure 2)
Do not over tighten the mounting screws as the subbase may warp causing
the improper seating of the thermostat connecting pins to the terminal
blocks.
Use a properly sized
screwdriver and back each
screw terminal out (counter
clockwise) before landing each
wire to its dedicated terminal.
Do not over tighten the terminal
screws. Check to ensure that all
wires are landed correctly and
dressed properly to prevent any
shorts. Refer to Typical System
Wiring Diagrams in this manual
for proper wiring.
FIGURE 2
7
S2 SC S1
O/B
AUX AUX
Y1 Y2 W1 G R C
WIRE
ACCESS
HOLE
BATTERY
COMPARTMENT
MOUNTING HOLES
MOUNTING HOLES
W2
MOUNTING
HOLE
INSTALLING THE THERMOSTAT
TERMINAL DESIGNATIONS
TERMINAL
DESIGNATION
S2
Outdoor Sensor
SC
Sensor Common
S1
Indoor Sensor
AUX
Auxiliary Contacts
W2/OB
Second Stage Heat or Reversing Valve
Y1
First Stage Cool or First Stage Compressor
Y2
Second Stage Cool or Second Stage Compressor
W1
First Stage Heat/Auxiliary/Emergency Heat
G
Fan
R
24 VAC Hot
C
24 VAC Common
8
SETTING THE SYSTEM SWITCHES
The thermostat contains a set of four system switches located on the thermostat
printed circuit board. (Figure 3) The switches are used to match the thermostat
operation and relay outputs with the HVAC system requirements. Refer to the
system switch functions on the next page to properly configure the thermostat.
FIGURE 3
9
1 2 3 4
ON DIP
SYSTEM SWITCHES
. . . . .
.
. . . . .
.
SYSTEM SWITCH FUNCTIONS
Switch 1 - Equipment Type
Switch 1 sets the equipment type. For conventional
heat/cool equipment, set the switch to the OFF
position (factory default). For heat pump equipment set
the switch to the ON position.
Switch 2 - Fan or
When Switch 1 is OFF
Reversing Valve
For gas heat, set the switch to the OFF position
(factory default). For electric heat, set the switch to the
ON position.
When Switch 1 is ON
For ‘O’ reversing valve, set the switch to the OFF
position. (factory default) For ‘B’ reversing valve, set
the switch to the ON position.
Switch 3 - Equipment Stages
Switch 3 sets the number of equipment stages.
OFF = 1 heat / 1 cool gas / electric or 2 heat / 1 cool
heat pump or dual fuel.
ON = 2 heat / 2 cool gas / electric or 3 heat / 2 cool
heat pump or dual fuel.
Switch 4 - Dual Fuel Mode
For conventional heat pump equipment, leave
switch 4 in the OFF position (factory default). For
dual fuel equipment, set switch 4 to the ON position.
10
INSTALLING THE BATTERIES
The thermostat comes with two AA batteries. Even if the thermostat is hardwired,
battery backup is recommended to maintain the real-time clock in the event of a
power failure. All other memory is non-volatile in the event of battery or primary
power loss. Press in on the battery access compartment and slide the drawer
out. Install the two AA batteries matching the + and - orientation. Push the battery
compartment in until it clicks shut. When the batteries are properly installed, the
touchscreen display will light up. (Figure 4)
FIGURE 4
+-
11
TYPICAL SYSTEM WIRING DIAGRAMS
HEAT ONLY (GAS)
Switch Settings
OFF
Switch 1 =
Heat/Cool
Switch 2 =
Equipment controls fan on call for heat
OFF
Switch 3 =
Single Stage
OFF
Switch 4 =
Leave OFF
OFF
12
SC
S1
Y1 Y2 W1 G R C
FAN
RELAY
LINE
24 V
W2
O/B
S2
OPTIONAL
REMOTE SENSOR
TERMINALS
THERMOSTAT
EQUIPMENT
OUTDOOR
SENSOR
INDOOR
SENSOR
HEAT 1
RELAY
AUX AUX
TYPICAL SYSTEM WIRING DIAGRAMS
HEAT ONLY (ELECTRIC)
Switch Settings
OFF
Switch 1 =
Heat/Cool
Switch 2 =
Thermostat controls fan on call for heat
ON
Switch 3 =
Single Stage
OFF
Switch 4 =
Leave OFF
OFF
13
SC
S1
Y1 Y2 W1 G R C
FAN
RELAY
LINE
24 V
W2
O/B
S2
OPTIONAL
REMOTE SENSOR
TERMINALS
THERMOSTAT
EQUIPMENT
OUTDOOR
SENSOR
INDOOR
SENSOR
HEAT 1
RELAY
AUX AUX
TYPICAL SYSTEM WIRING DIAGRAMS
COOL ONLY (SINGLE OR MULI-STAGE)
Switch Settings
OFF
Switch 1 =
Heat/Cool
Switch 2 =
Fan energized on call for cooling
OFF
Switch 3 =
= Single Stage
= Multi-stage
OFF/ON
OFF
ON
Switch 4 =
Leave OFF
OFF
14
SC
S1
Y1 Y2 W1 G R C
FAN
RELAY
LINE
24 V
W2
O/B
S2
OPTIONAL
REMOTE SENSOR
TERMINALS
THERMOSTAT
EQUIPMENT
OUTDOOR
SENSOR
INDOOR
SENSOR
COOL 1
RELAY
COOL 2
RELAY
AUX AUX
TYPICAL SYSTEM WIRING DIAGRAMS
1 HEAT/1 COOL (GAS)
Switch Settings
OFF
Switch 1 =
Heat/Cool
Switch 2 =
Fan energized on call for cooling
OFF
Switch 3 =
Single Stage
OFF
Switch 4 =
Leave OFF
OFF
15
SC
S1
Y1 Y2 W1 G R C
FAN
RELAY
LINE
24 V
W2
O/B
S2
OPTIONAL
REMOTE SENSOR
TERMINALS
THERMOSTAT
EQUIPMENT
OUTDOOR
SENSOR
INDOOR
SENSOR
COOL 1
RELAY
HEAT 1
RELAY
AUX AUX
TYPICAL SYSTEM WIRING DIAGRAMS
2 HEAT/2 COOL (GAS)
Switch Settings
OFF
Switch 1 =
Heat/Cool
Switch 2 =
Fan energized on call for cooling
OFF
Switch 3 =
Multi-stage
ON
Switch 4 =
Leave OFF
OFF
16
SC
S1
Y1 Y2 W1 G R C
FAN
RELAY
LINE
24 V
W2
O/B
S2
OPTIONAL
REMOTE SENSOR
TERMINALS
THERMOSTAT
EQUIPMENT
OUTDOOR
SENSOR
INDOOR
SENSOR
COOL 1
RELAY
HEAT 1
RELAY
HEAT 2
RELAY
COOL 2
RELAY
AUX AUX
TYPICAL SYSTEM WIRING DIAGRAMS
2 HEAT/1 COOL (HEAT PUMP)
Switch Settings
ON
Switch 1 =
Heat Pump
Switch 2 =
= ‘O’
= ‘B’
OFF/ON
OFF
ON
Switch 3 =
2 Heat / 1 Cool HP
OFF
Switch 4 =
Leave OFF
OFF
17
SC
S1
Y1 Y2 W1 G R C
FAN
RELAY
LINE
24 V
W2
O/B
S2
OPTIONAL
REMOTE SENSOR
TERMINALS
THERMOSTAT
EQUIPMENT
OUTDOOR
SENSOR
INDOOR
SENSOR
COMP 1
RELAY
AUX
RELAY
REV
VALVE
AUX AUX
TYPICAL SYSTEM WIRING DIAGRAMS
3 HEAT/2 COOL (HEAT PUMP)
Switch Settings
ON
Switch 1 =
Heat Pump
Switch 2 =
= ‘O’
= ‘B’
OFF/ON
OFF
ON
Switch 3 =
3 Heat / 2 Cool HP
ON
Switch 4 =
Leave OFF
OFF
18
SC
S1
Y1 Y2 W1 G R C
FAN
RELAY
LINE
24 V
W2
O/B
S2
OPTIONAL
REMOTE SENSOR
TERMINALS
THERMOSTAT
EQUIPMENT
OUTDOOR
SENSOR
INDOOR
SENSOR
COMP 1
RELAY
AUX
RELAY
REV
VALVE
COMP 2
RELAY
AUX AUX
TYPICAL SYSTEM WIRING DIAGRAMS
2 HEAT/1 COOL (DUAL FUEL)
Switch Settings
ON
Switch 1 =
Heat Pump
Switch 2 =
= ‘O’
= ‘B’ Reversing Valve
OFF/ON
OFF
ON
Switch 3 =
2 Heat / 1Cool dual fuel
OFF
Switch 4 =
Locks out heat pump when furnace is energized
ON
19
SC
S1
Y1 Y2 W1 G R C
FAN
RELAY
LINE
24 V
W2
O/B
S2
OPTIONAL
REMOTE SENSOR
TERMINALS
THERMOSTAT
EQUIPMENT
OUTDOOR
SENSOR
INDOOR
SENSOR
COMP 1
RELAY
AUX
RELAY
REV
VALVE
AUX AUX
TYPICAL SYSTEM WIRING DIAGRAMS
3 HEAT / 2 COOL (DUAL FUEL)
20
SC
S1
Y1 Y2 W1 G R C
FAN
RELAY
LINE
24 V
W2
O/B
S2
OPTIONAL
REMOTE SENSOR
TERMINALS
THERMOSTAT
EQUIPMENT
OUTDOOR
SENSOR
INDOOR
SENSOR
COMP 1
RELAY
AUX
RELAY
REV
VALVE
COMP 2
RELAY
Switch Settings
ON
Switch 1 =
Heat Pump
Switch 2 =
= ‘O’
= ‘B’ Reversing Valve
OFF/ON
OFF
ON
Switch 3 =
3 heat / 2 cool dual fuel
ON
Switch 4 =
Locks out heat pump when furnace is energized
ON
AUX AUX
INSTALLER SETUP MENU
ENTERING THE SETUP MENU
Tap the display to bring the back light on then press and hold both the
and
Clock
Mode
section for 5 seconds to enter the Installer Menu.
To advance through the menu, touch Next.
To back up in the menu, touch Back.
To exit the menu at any time and save changes, press and hold Next for 4
seconds.
NOTE: Depending on thermostat configuration, some menu items may not
appear.
21
AM
DST
01/01/2012
INSTALLER SETUP MENU
SELECTING THE PROGRAMMABLE OR NON-PROGRAMMABLE
OPERATION
The first menu 01 selects programmable or non-programmable operation. Press the
or
UP
DOWN
7
arrows to change the selection. The factory default is .
Program
Morning Day
Evening Night
7 = 7-Day Programmable (Factory Default)
0 = Manual Mode (Non-programmable)
Back
Next
22
o1
INSTALLER SETUP MENU
SELECTING NUMBER OF PROGRAM SCHEDULES
(
)
ONLY DISPLAYED WHEN 01 = 7
If menu 01 is set to 7, the thermostat can be configured for 4 or 2 schedules per day. The
factory default is .
4
4 = 4 schedules per day (Factory Default)
2 = 2 schedules per day
Back
Next
23
o2
INSTALLER SETUP MENU
SELECTING MODE
Menu 03 selects the mode of operation. The factory default is .
0
0 = Auto-changeover (Heat/Cool/Auto/Off for Heat/Cool)
(Heat/Cool/Auto/EHeat/Off for Heat Pump (Factory
Default)
1 = Manual Changeover (Heat/Cool/Off) or (Heat/Cool/E.Heat/Off)
2 = Heating Only (Heat/Off) or (Heat/E.Heat/Off)
3 = Cooling Only (Cool/Off)
Program
Back
Next
24
o3
INSTALLER SETUP MENU
SELECTING PROGRAMMABLE FAN
Menu 04 selects the Programmable Fan option which allows selecting continuous or auto
fan operation for each program event when programmable mode is selected. The factory
default is .
0
0 = No Programmable Fan (Factory Default)
1 = Programmable Fan
Program
Refer to the User Manual for selecting continuous or auto fan for each
scheduled event when the Programmable Fan option is ON.
Back
Next
25
o4
INSTALLER SETUP MENU
ASSIGNING AUXILIARY CONTACTS
Menu 05 assigns the auxiliary dry relay contacts (AUX) as Normally Open or Normally
closed when the Programmable Fan Option 04 is ON. Whenever Programmable Fan is in
the
mode (constant ventilation) for a selected program period, the relay
Always On
contact will go open or closed based on the auxiliary relay option selection. The auxiliary
contacts are also used to open an outside air damper when Timed Ventilation is selected.
(See details on page 55 and 56)
1 = Relay contacts closed when Programmable Fan is ON (Factory Default)
2 = Relay contacts open when Programmable Fan is ON
3 = Relay contacts used for Timed Ventilation
Back
Next
26
o5
INSTALLER SETUP MENU
SELECTING TOUCHSCREEN LOCK OPTIONS
Menu 06 allows you to prevent changes to all or part of the touchscreen functions. The
factory default is . Touch the
or
arrows to change the selection.
0
UP
DOWN
0 = All functions unlocked (Factory Default)
1 = All functions locked except setpoint adjustment
2 = All functions locked
Back
Next
27
o6
INSTALLER SETUP MENU
SELECTING THE COOLING SETPOINT LIMIT
Menu 07 selects the minimum cooling setpoint. The factory default is
. Touch the
or
50
UP
DOWN arrows to adjust the limit from 43° - 122°F.
Set
Back
Next
28
o7
INSTALLER SETUP MENU
SELECTING THE HEATING SETPOINT LIMIT
Menu 08 selects the maximum heating setpoint limit. The factory default is
. Touch the
90
UP
DOWN
or
arrows to adjust the limit from 41° - 120°F.
Set
Heat
Back
Next
29
o8
INSTALLER SETUP MENU
SELECTING BACK LIGHT OPTION
Menu 09 allows you to select the back light option. The factory default is . Touch the
0
UP
or
arrows to change the display option.
DOWN
0 = Back Light on for 10 seconds when screen is touched
1 = Back Light on high for 10 seconds when screen is touched and then
low continuously. (Thermostat must be hardwired to 24VAC for
this option)
Back
Next
30
o9
INSTALLER SETUP MENU
SELECTING ADAPTIVE RECOVERY OPTION
Menu 10 allows you to select the Adaptive Recovery option. Only displayed when 01 is
set to 7. Adaptive Recovery compares the space temperature deviation from setpoint and
rate of recovery history to bring the equipment on and reach the setpoint at the scheduled
start time. The factory default is . Touch the
or
arrows to select this option.
0
UP
DOWN
0 = No Adaptive Recovery (Factory Default)
1 = Adaptive Recovery On (For programmable mode only)
Back
Next
31
1o
INSTALLER SETUP MENU
SELECTING FIRST STAGE HEATING AND COOLING DIFFERENTIAL
OPTION
Menu 11 is used to adjust the heating and cooling differential. The factory default is (1°F).
This represents the temperature above the cooling setpoint or below the heating setpoint
when the equipment is energized. Touch the
or
arrows to change the
UP
DOWN
differential.
1 = 1°F Differential
2 = 2°F Differential
3 = 3°F Differential
Back
Next
32
11
INSTALLER SETUP MENU
SELECTING SECOND STAGE HEATING AND COOLING DIFFERENTIAL
OPTION
Menu 12 is used to adjust the second stage heating and cooling differential. The factory
default is (2°F). This represents the temperature above the first stage cooling
2
differential or below the first stage heating differential when second stage is energized.
Touch the
or
arrows to change the differential.
UP
DOWN
Adjustable from 1 - 10°F in 1° increments
Back
Next
33
12
INSTALLER SETUP MENU
SELECTING THIRD STAGE HEATING DIFFERENTIAL OPTION
Menu 13 is used to adjust the third stage heating differential. Only displayed when SW1
and SW 3 are ON. The factory default is
(2°F). This represents the temperature below
2
the second stage heating differential when third stage heat is energized. Touch the
or
UP
DOWN arrows to change the differential.
Adjustable from 1 - 10°F in 1° increments
Back
Next
34
13
INSTALLER SETUP MENU
SELECTING DEMAND STAGING OR LOCKED STAGING OPTION
Menu 14 is used to select how the thermostat will stage the equipment. The factory
default is
which =
. Demand Staging allows the thermostat to upstage
0
Demand Staging
or downstage the equipment based on the stage differential settings. In dual fuel setup,
the thermostat will not downstage to compressor if fossil fuel is energized. =
1
Locked
Staging. Locked Staging allows the thermostat to upstage the equipment based on the
stage differential settings but locks in each stage until the setpoint is reached. (No down-
staging)
0 = Demand Staging (Factory Default)
1 = Locked Staging
Back
Next
35
14
INSTALLER SETUP MENU
SENSOR CALIBRATION
Menu 15 allows you to re-calibrate the internal or a single indoor remote sensor. When a
remote sensor is wired to the SC and S1 terminals, the internal sensor is automatically
disabled. The factory default is
(0°F). Touch the
or
arrows to adjust the
0
UP
DOWN
calibration from -9° to +9°F.
Back
Next
36
15
INSTALLER SETUP MENU
SELECTING LOW BALANCE POINT OPTION
Menu 16 allows you to select a low balance point setting when the thermostat is
configured for Heat Pump or Dual Fuel and an outdoor sensor is used. When the outdoor
temperature falls below the balance point setting, the compressor is locked out and only
auxiliary electric heat or dual fuel furnace is used for heating. The factory default is
.
OFF
Touch the
or
arrows to select a low balance point setting.
UP
DOWN
Adjustable from OFF, 1° to 77°F
Remote outdoor sensor must be used
Back
Next
37
16
INSTALLER SETUP MENU
SELECTING HIGH BALANCE POINT OPTION
Menu 17 allows you to select a high balance point setting when the thermostat is
configured for Heat Pump or Dual Fuel. When the outdoor temperature rises above the
balance point setting, the auxiliary electric heat or dual fuel furnace is locked out and only
the heat pump is used for heating. The factory default is
. Touch the
or
OFF
UP
DOWN
arrows to select a high balance point setting.
Adjustable from OFF, 32° to 122°F
Remote outdoor sensor must be used
Back
Next
38
17
INSTALLER SETUP MENU
SELECTING FAHRENHEIT OR CELSIUS
Menu 18 allows you to select temperature readings and temperature setpoints in
Fahrenheit or Celsius. The factory default is (Fahrenheit). Touch the
or
F
UP
DOWN
arrows to select (Celsius).
C
Back
Next
39
18
INSTALLER SETUP MENU
SELECTING AUDIBLE ON/OFF
Menu 26 allows you to select an audible beep whenever the screen is touched or to
silence the beep. The factory default is audible beep
. Touch the
or
arrows
ON
UP
DOWN
to change the selection.
ON = Audible Beep
OFF = Audible Beep Silenced
Back
Next
40
26
INSTALLER SETUP MENU
TIMED VENTILATION DURATION
Menu 27 is used to select Timed Ventilation when Menu 05 is set to 3. Timed Ventilation is
used to bring outside air into the home at a controlled CFM rate based on ASHRAE 62.2 -
2013 Ventilation and Indoor Air Quality Standard. See Ventilation Reference Chart on
page 54 to calculate ventilation minutes per hour.
Range = 0-60 minutes in 1 minute increments.
Factory Default = 15 minutes.
Back
Next
41
27
INSTALLER SETUP MENU
TIMED VENTILATION LOW TEMPERATURE LIMIT
Menu 28 is used to select a low outdoor temperature when a remote outdoor sensor is
installed. If the temperature is lower than or equal to the selected value, Timed Ventilation
is suspended. Menu 28 is only displayed if thermostat is fitted with an outdoor sensor.
Range = OFF - 0-50 degrees in 1 degree increments.
Factory Default = OFF.
Back
Next
42
28
INSTALLER SETUP MENU
TIMED VENTILATION HIGH TEMPERATURE LIMIT
Menu 29 is used to select a high outdoor temperature limit when a remote outdoor sensor
is installed. If the temperature is higher than or equal to the selected value, Timed
Ventilation is suspended. Menu 29 is only displayed if thermostat is fitted with an outdoor
sensor.
Range = OFF - 60-90 degrees in 1 degree
increments.
Factory Default = OFF.
Back
Next
43
29
INSTALLER SETUP MENU
DAYLIGHT SAVING TIME
Menu 30 is used to enable or disable Daylight Saving Time (DST). In areas of the country
where DST is not observed, the feature can be disabled. Touch the
or
arrows
UP
DOWN
to change the selection.
1 = DST (Factory Default)
0 = DST Disabled
Back
Next
44
30
REMOTE SENSOR INSTALLATION
45
REMOTE SENSOR TYPES
The thermostat can accommodate both an indoor and outdoor remote sensor.
For indoor applications, the SC-T-S1 remote sensor can be wired to the
thermostat
and
terminals. Each sensor contains two thermistors wired in
SC
S1
series with a switch to select one or both sensors. This reduces the total number
of sensors required for series/parallel temperature averaging. Whenever an
indoor remote sensor is used, the thermostats internal sensor is automatically
disabled.
The SC-T-OTS outdoor remote sensor is wired to the
and
terminals. The
SC
S2
outdoor sensor thermistor is housed in a waterproof encapsulation and is ideally
suited for ambient conditions ranging from -40 to 140°F and humidity levels of 5
to 95% RH (non-condensing).
SC-T-S1 INDOOR SENSOR INSTALLATION
Locate the sensor in the same manner as the thermostat. Mount the sensor 18”
away from any outside wall. Do not install the sensor behind doors, in corners or
other dead air spaces. Keep the sensor away from direct air flow, supply
registers or near sources of heat such as lamps and appliances.
REMOTE SENSOR INSTALLATION
46
Use a separate 18-2 shielded cable for sensor wiring. Prior to wiring the sensor
to the thermostat, use an ohm-meter or multi-meter to measure the resistance of
the sensor. Measure at the end of the wires that will connect to the thermostat.
Confirm the resistance value (within 5%) to the temperature where the sensor is
mounted. Refer to the Temperature/Resistance Chart on page 41 of this manual.
Use a high quality, digital electronic thermometer to read the temperature at the
sensor. Remove the sensor cover and place the thermometer probe next to the
thermistor to verify an accurate reading. Disconnect power to the thermostat
when wiring the sensor to the proper sensor terminals. Strip only as much
insulation off of the wires as necessary to provide a good contact with the
terminals. The sensor is not polarity specific so either sensor lead may be
connected to either designated terminal on the thermostat. Refer to the SC-T-S1
installation guide for additional information.
SC-T-OTS OUTDOOR SENSOR INSTALLATION
When the SC-T-OTS is wired to the SC-T32-TS, it will display the outside air
temperature as well as control high and low balance points for heat pump or dual
fuel systems. Refer to the SC-T-OTS installation guide for additional information.
REMOTE SENSOR INSTALLATION
47
TEMPERATURE/RESISTANCE CHART
Temperature Resistance
Temperature Resistance
(°F) (K
) ( F) (K )
Ω
Ω
º
30 34.6 70 11.9
40 26.1 80 9.4
50 19.9 90 7.4
60 15.3 100 5.9
NTC type 2 sensor - 10K @ 77° F
Ω
Heat 2 3 Cool 2
Auto E. heat
Mon Tue Wed Thu Fri Sat Sun Outside Air Temperature
Automatic
Always On
OFF
Morning Day
Evening Night
Clean
Screen
88/88/2088
Cool
Heat Set
Back
Next
Hold
DAYS OF THE WEEK
TIME OF DAY
12 HOUR ONLY
WITH AM/PM
INDICATION
MONTH, DAY, YEAR
DAYLIGHT SAVINGS TIME
DISPLAYED WHEN DST IS ACTIVE
(DST CAN BE DISABLED)
DISPLAYED WITH OUTSIDE
AIR TEMPERATURE AND
FLASHES WHEN ANY OUTDOOR
LIMIT IS EXCEEDED
(OPTIONAL OUTDOOR SENSOR REQUIRED)
SET TEMPERATURE
OR OUTDOOR TEMPERATURE
DISPLAY
FAHRENHEIT ONLY
CLEAN SCREEN
WHEN TOUCHED, ALLOWS
30 SECONDS TO
CLEAN SCREEN
WHILE THERMOSTAT
FUNCTIONS ARE
LOCKED
LOCK ICON
DISPLAYED WHEN A
FUNCTION CAN NOT
BE ACCESSED OR
EXCEEDING A SET LIMIT
FLASHING LOW BATTERY
INDICATOR WITH
AUDIBLE WARNING BEEP
UP AND DOWN ARROWS
USED TO SET TEMPERATURE,
TIME, DAY, MONTH, YEAR
AND OTHER VALUES
SPACE TEMPERATURE
FAHRENHEIT ONLY
MODE
USED TO SELECT
HEAT, COOL, AUTO,
OFF OR E. HEAT
ALSO DISPLAYS
HEATING AND COOLING STAGES
MODE BLINKS WHEN COMPRESSOR
TIME DELAY IS ACTIVE
FAN
USED TO SELECT
AUTOMATIC OR
ALWAYS ON
OPERATION
PROGRAM
USED TO PROGRAM EVENTS
IN PROGRAMMABLE
MODE
ERROR
NO
FUNCTION
FAN FLASHES WHEN
TIMED VENTILATION IS
IN USE
until the word
is displayed. Touch FAN until the words
Mode
OFF
Always
On appear. After a brief moment, the internal fan relay ‘G’ will energize and the
system fan should operate. Touch
again until the word
appears.
FAN
Automatic
After a brief moment, the internal fan relay will de-energize and the system fan
will shut off.
CONVENTIONAL HEATING
Touch
until the word
appears. Touch the
arrow and raise the
Mode
Heat
UP
setpoint above the space temperature and the first stage differential. After a brief
moment, the internal heating relay ‘W1’ will energize and the heating system
should operate. The word
will flash continuously. If the thermostat has been
Heat
configured for two stage heating, raise the setpoint above the second stage
differential and
will flash indicating the ‘W2’ heating relay is energized.
Heat 2
Touch
until the word
is displayed.
Mode
OFF
CONVENTIONAL COOLING
Touch
until
appears. Touch the
arrow and lower the setpoint
Mode
Cool
DOWN
below the space temperature and the first stage differential.
Note: On a call for cooling, the thermostat activates a 3 minute time delay before
the cooling relay ‘Y1’ is energized.
will flash to indicate the thermostat is in
Mode
time delay. After the time delay, the internal fan ‘G’ and cooling relay ‘Y1’ will
energize. The word
will flash. If the thermostat has been configured for two
Cool
stage cooling, lower the setpoint below the second stage differential and
Cool 2
will flash indicating the ‘Y2’ cooling relay is energized. Touch
until the word
Mode
OFF is displayed.
CONVENTIONAL HEAT PUMP
When the thermostat is configured for conventional heat pump operation, testing
is the same as a heating and cooling system with the exception that a 3 minute
time delay is activated before the ‘Y1’ compressor relay will energize on a call for
heating or cooling.
will flash to indicate the thermostat is in time delay.
Mode
Depending on the mode of operation and equipment configuration,
or
Heat
Cool
will flash when the ‘Y1’ compressor relay is energized.
or
will flash
Heat 2
Cool 2
when the ‘Y2’ compressor relay is energized.
will flash when the
Heat 2 3
auxiliary ‘W1’ relay is energized.
will flash when the mode is set to
E.Heat
emergency heat. After testing, touch
until the word
is displayed.
Mode
OFF
When the thermostat is configured for dual fuel operation, testing is the same as
a heating and cooling system with the exception that a 3 minute time delay is
activated before the ‘Y1’ compressor relay will energize on a call for heating or
cooling.
will flash to indicate the thermostat is in time delay. Depending on
Mode
the mode of operation and equipment configuration,
or
will flash when
Heat
Cool
the ‘Y1’ compressor relay is energized.
or
will flash when the ‘Y2’
Heat 2
Cool 2
compressor relay is energized.
will flash when the auxiliary ‘W1’ relay is
Heat 3
energized.
will flash when the mode is set to emergency heat. Whenever
E.Heat
the thermostat calls for auxiliary heat, the heat pump compressor or compressors
will be de-energized and the auxiliary heat will remain on until the call is satisfied.
LOW BALANCE POINT (Heat Pump or Dual Fuel)
When an outdoor sensor is used with the thermostat, Installer Option 16 allows
you to select a low balance point temperature. When the outdoor temperature
falls below the low balance point setting, a call for heat from the thermostat
automatically energizes the ‘W1’ relay and bypasses the ‘Y1’ compressor relay.
To test the low balance point setting, set Option 16 above the displayed outdoor
temperature and force a call for heating. Only the auxiliary heat relay ‘W1’ should
energize. After testing, reset the low balance point setting to a normal operating
range.
HIGH BALANCE POINT (Heat Pump or Dual Fuel)
High balance point is designed to prevent the auxiliary heat ‘W1’ relay from
energizing when the outdoor temperature is above the balance point setting. To
test the high balance point setting, set Option 17 below the displayed outdoor
temperature and force a call for auxiliary heat. Only the compressor ‘Y1’ and/or
‘Y1’ and ‘Y2’ should energize. If the thermostat is placed in the E.Heat
(emergency heat) mode, the ‘W1’ relay will energize. After testing, reset the high
balance point setting to a normal operating range.
ADAPTIVE RECOVERY
Adaptive Recovery is only available in programmable mode (Installer Option 01 =
7) The Adaptive Recovery function of the thermostat permits the user to program
a time that a desired set temperature is required. The thermostat then calculates
the most energy efficient time to bring on the equipment to reach the setpoint at
the designated time.
PROGRAMMABLE FAN
Programmable Fan (Installer Option 04 = 0) is used to program the fan operation
along with the thermostat schedule. This is a very convenient feature that allows
selecting continuous (Always ON) or Automatic fan operation for each scheduled
event. When Programmable Fan is used, the fan operation can still be overridden
at the thermostat and will remain in the override mode until the next scheduled
event.
AUXILIARY CONTACTS
The Auxiliary Contacts (Installer Option 05) provide a selectable normally open
(1) or normally closed (2) dry contact output that works in conjunction with the
Programmable Fan feature when the thermostat is configured for programmable
mode. When the fan is in continuous (Always ON) mode, the auxiliary relay coil is
energized and de-energizes in Automatic mode. The Auxiliary Contacts may also
be used for Timed Ventilation when Installer Option 05 is set to 3.
The auxiliary dry contacts can be used with the Programmable Fan feature when
the Programmable Fan Option 04 is ON. They can also be used for Timed
Ventilation when Option 05 is set to 3. Timed Ventilation is designed to improve
residential indoor air quality by introducing fresh, outside air through a 2-wire,
power open / spring closed motorized intake damper controlled by the
thermostat. The thermostat controls the amount of fresh air required each hour
based on ASHRAE 62.2 - 2013 Ventilation and Indoor Air Quality Standard. The
reference chart on the next page provides the ventilation timer setting based on
using an 8” outside air damper ducted to the return air plenum on the HVAC
system. A separate 24 volt transformer should be used to power the damper.
54
THERMOSTAT
AUX AUX
LINE
24V
PO/SC
DAMPER
SEPARATE
24V TRANSFORMER
TIMED VENTILATION SETUP
<500
501-1000
1001-1500
1501-2000
2001-2500
2501-3000
3001-3500
3501-4000
4001-4500
4501-5000
NUMBER OF BEDROOMS
ONE
TWO
THREE
FOUR
FIVE
VENTILATION TIMER SETTING (MINUTES PER HOUR)
8 10 12 15 16
12 15 16 19 21
16 19 21 23 25
21 23 25 27 29
25 27 29 31 33
29 31 33 35 37
33 35 37 39 41
37 39 41 43 45
41 43 45 47 49
45 47 49 51 53
55
The reference chart below provides the ventilation timer setting (Installer Option
27) based on using 8” rigid straight duct with friction loss of 0.1” w.g. per 100 ft.
This chart can be used for most applications.
SYMPTOM POSSIBLE FAULT AND REMEDY
No LCD display
If the thermostat is battery powered only, remove the battery
compartment and check to see that the positive (+) and negative (-)
ends of each battery are oriented properly. Also make sure that the
thermostat is securely attached to the subbase with no exposed
gaps.
Thermostat can not
Installer Option 03 needs to be set to 0 to provide Heat/Auto/Cool/Off
be set for auto changeover operation or Heat/Auto/Cool/Emergency Heat/Off for heat pumps.
03 = 1 Manual Changeover (Heat/Cool/Off)
03 = 2 Heat Only (Heat/Off)
03 = 3 Cool Only (Cool/Off)
Temperature display
Air from wall cavity may be leaking into the rear of the thermostat.
inaccurate
Seal hole where wiring enters subbase to prevent air infiltration.
External influence from appliances, lighting or drafts may be affecting
temperature accuracy. Move lamps or other sources of heat away
from thermostat.
Thermostat not displaying
Check wiring at outdoor sensor and sensor terminals on subbase.
outdoor temperature
Outdoor sensor wires to terminals S2 and SC.
SYMPTOM POSSIBLE FAULT AND REMEDY
Heat or Cool is flashing
This is not a fault but indicates that the thermostat heating or cooling
relay is energized. Depending upon the equipment configuration,
Heat 2 or Cool 2 will also be displayed if a second stage is energized.
Heat 3 is also displayed for heat pumps having three heating stages.
Lock icon is displayed
This is not a fault. The thermostat heating and cooling limits are
when trying to set a higher
preventing setting a temperature above or below the limit values.
or lower temperature
These values can be changes in the Installer Menu.
07 = Cooling Limit. Factory default is 50° F. Adjustable from 43° F
to 122° F.
08 = Heating Limit. Factory default is 90° F. Adjustable from 41° F
to 120° F.
The fan continues to run
The thermostat fan mode may be set to Always On. Touch the fan icon
after a heating or cooling
and change it to Automatic. When the thermostat is configured as a
call is satisfied
programmable thermostat, the fan operation can be programmed for
Automatic or Always On with each event. If the Programmable Fan
feature is not required, set Option 04 = 1.
Some functions cannot be
Lock values have been set. Refer to Installer Option menu 06. To
changed and a padlock
remove all lock values, set 06 = 0.
Input Voltage (Hardwired)
20-30 VAC 50/60 Hz
Relay Rating
24 VAC @ 1 Amp maximum per relay
Battery Power
(2) AA 1.5 V
Operating Temperature
32° F to 150° F
Operating Relative Humidity
0-95% RH (non-condensing)
Storage Temperature
32° F to 150° F
Overall Size
5.5” W x 3.75” H x 1.312” D
LCD Display Size
4.125” W x 2.375” H
Back Light
Blue LED
Short-cycle Delay
4 minutes
Displayed Temperature Resolution
1° F
Setpoint Range
Heating
41° F - 120° F
Cooling
43° F - 122° F
Heating and Cooling Limits
Fully adjustable
Onboard and Remote Sensors
NTC type 2
Resistance
10KΩ @ 77 F
°
Tolerance
+ / - 3% @ 77 F
°
Warranty
5 years
SC-06-1324-101320
www.specifiedcontrols.com
888.359.0365