Siemens SIMATIC OP 77B Operating Instructions Manual
Read Online
Read the Siemens SIMATIC OP 77B Operating Instructions Manual online using the built-in PDF viewer.
Text of the manual
Order No.: 6AV6691-1EA01-0AB0
This manual contains notices intended to ensure
personal safety, as well as to protect the products and
connected equipment against damage. These notices
are graded according to severity by the following texts:
Danger
indicates that death or severe personal injury will result
if proper precautions are not taken.
Warning
indicates that death or severe personal injury can result
if proper precautions are not taken.
Caution
used with the safety alert symbol indicates a potentially
hazardous situation which, if not avoided, may result in
minor or moderate injury.
Caution
used without the safety alert symbol indicates a
potentially hazardous situation which, if not avoided,
may result in property damage.
Notice
indicates that unwanted events or status can occur if
the relevant information is not observed.
Operating safety and safety regulations
Detailed information on operating safety and the
applicable safety regulations is provided in the
"OP 77B" operating instructions.
Voltage supply
Warning
The OP 77B complies to Protection Class I in
accordance with EN 61131-2 and EN 50178.
Ensure safe electrical insulation of the power supply.
Only use mains power supply units which fulfill the
standards for SELV and PELV.
When dimensioning the power supply, take a voltage
drop in the connection cable into account!
Operating Instructions (Compact) – for
professionals
Important information on the OP 77B is summarized in these
Operating Instructions (Compact).
Operating Instructions
Detailed information on the OP 77B is provided in the "OP 77B"
operating instructions.
Migration
Information on migration of existing OP7 and C7-633 projects to
WinCC flexible is provided in the "WinCC flexible Migration"
operating instructions.
PDF files on this topic are also available in Internet under
http://www.ad.siemens.de/simatic/index_76.htm.
Editor and Publisher
A&D AS SM ID 5
Printer
A&D AS EWK
Copyright Siemens AG 2004 All rights reserved
The reproduction, transmission or use of this document or its
contents is not permitted without express written authority.
Offenders will be liable for damages. All rights, including rights
created by patent grant or registration of a utility model or
design, are reserved.
Disclaimer of Liability
We have checked the contents of this manual for agreement
with the hardware and software described. Since deviations
cannot be precluded entirely, we cannot guarantee full
agreement. However, the data in this manual are reviewed
regularly and any necessary corrections included in subsequent
editions. Suggestions for improvement are welcomed.
Siemens AG
Automation & Drives
SIMATIC Human Machine Interface
Postfach 4848, D-90327 Nürnberg
Siemens AG 2004
Technical data subject to change.
Order No.: 6AV6691-1EA01-0AB0
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
v
Contents
0
Contents
1
Overview
1.1
HMI Device Design............................................ 1–1
1.2
Options.............................................................. 1–3
1.3
Miscellaneous ................................................... 1–4
1.4
Scaled Drawings ............................................... 1–4
1.5
Description of Interfaces.................................... 1–5
2
Technical Data
3
Installing the OP 77B
3.1
EMC Guidelines ................................................ 3–1
3.2
Installation Position and Fixation ....................... 3–2
3.3
Producing the Installation Cut-Out..................... 3–3
4
Connecting the OP 77B
4.1
Connecting the Potential Equalization ............... 4–2
4.2
Connecting the PLC .......................................... 4–3
4.3
Connecting the Configuration Computer............ 4–6
4.4
Connecting Peripheral Equipment ..................... 4–7
4.5
Connecting the Power Supply ........................... 4–8
Operating Instructions (Compact) OP 77B
vi
6AV6691-1EA01-0AB0
5
Operating the OP 77B
5.1
Front Side Operating Elements and Indicators ...5–1
5.2
Further Operating Elements ...............................5–2
5.3
Operating the Project .........................................5–7
5.4
Input Within a Project.......................................5–10
5.4.1
Numeric values .............................................5–10
5.4.2
Alphanumeric values.....................................5–11
5.4.3
Entering numeric and
alphanumeric characters...............................5–12
5.4.4
Correcting input ............................................5–14
5.4.5
Entering symbolic values ..............................5–16
5.4.6
Entering date and time..................................5–17
5.5
Calling Help on a Project..................................5–17
5.6
Logging On and Off..........................................5–18
5.7
User Administration in a Project .......................5–19
5.7.1
Log on user...................................................5–21
5.7.2
Setting up a user...........................................5–22
5.7.3
Changing passwords ....................................5–24
5.7.4
Deleting a user name....................................5–24
6
Recipes and Alarms
6.1
Operating Recipes .............................................6–1
6.2
Operating Alarms ...............................................6–8
7
Index
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
1–1
Overview
1
Overview
1.1 HMI Device Design
1
3
2
1
Display
2
LED display
3
Membrane keyboard
Figure 1–1
Front view
1
Operating Instructions (Compact) OP 77B
1–2
6AV6691-1EA01-0AB0
2
5
4
1
3
3
1
Memory card holder
2
Memory card slot for an MMC
3
Slot for wrench
4
Guides for the labeling strips
5
Rubber seal
Figure 1–2
Side view
1
2
4
5
3
1
Connection for the power supply
2
RS 422/RS 485 interface
(MPI/PROFIBUS DP-interface)
3
Ground connection
4
RS 232 interface (serial interface)
5
USB interface
Figure 1–3
Bottom view
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
1–3
Overview
1.2 Options
Memory card
An MMC (Multi Media Card), tested and approved by
Siemens AG can be used as an external storage
medium. The memory card is an option and can be
ordered separately.
Notice
The MMC of the SIMATIC S7 controller cannot be
used.
Accessory kit
Plug for the power supply
(terminal block)
1 piece
Spring terminals for installing the HMI
device
4 pieces
Supplement
The Supplement is only applicable for the
HMI device with the following identification
on the rear:
1 piece
Operating Instructions (Compact) OP 77B
1–4
6AV6691-1EA01-0AB0
1.3 Miscellaneous
Labeling strips
Labeling strips are not supplied as accessories. If
necessary, these can be produced using the template
supplied. The template can be found on the installation
computer after installing WinCC flexible and on the
"WinCC flexible" installations CD under
...\Documents\slide77b.doc.
1.4 Scaled Drawings
134
6,2
38,5
170
150
186
Figure 1–4
Main dimensions of the OP 77B
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
1–5
Overview
1.5 Description of Interfaces
Power supply
2
1
Plug connector, 2-pin
Pin
Assignment
1
+24 V DC
2
GND
Figure 1–5
Pin assignment for power supply
RS 422/RS 485 (IF 1B)
1
5
9
6
Sub-D socket, 9-pin,
secured by screws
Pin
Assignment with
RS 422
Assignment with
RS 485
1
N. c.
N. c.
2
M
M
3
TxD+
LTG-B
4
RxD+
RTS-AS
5
GND, potential-free
GND, potential-free
6
DC +5 V, potential-free
DC +5 V, potential-free
7
DC 24 V in
DC 24 V in
8
TxD-
LTG-A
9
RxD-
RTS-AS
Figure 1–6
RS 422 and RS 485 interface pin assignments
Operating Instructions (Compact) OP 77B
1–6
6AV6691-1EA01-0AB0
RS 232 (IF 1A)
1
5
9
6
Sub-D plug, 9-pin,
secured by screws
Pin
Assignment
1
DCD
2
RxD
3
TxD
4
DTR
5
GND
6
DSR
7
RTS
8
CTS
9
N. c.
Figure 1–7
RS 232 interface pin assignment
1
2
3
4
5
6
7
8
9
Figure 1–8
Pin switching
USB
1
4
USB standard connector
Pin
Assignment
1
DC +5 V, max. 100 mA
2
USB-DN
3
USB-DP
4
GND
Figure 1–9
USB standard connector pin assignment
Release 03/2004
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
2–1
Technical Data
2
Technical Data
Housing
Degree of protection
•
Front panel
•
Rear panel
IP65,
NEMA 4X/NEMA 12 indoor use only
IP20
Weigh – without packing
Approx. 500 g
Display
Type
STN
Screen area, active
102.38 x 40.94 mm
Resolution
160 x 64 pixels
Pixel size
0.62 x 0.62 mm
Colors, possible
Monochrome, yellow-green
Contrast control
Yes
Brightness, typical
20 cd/m2
Back-lighting –
Half Brightness Life, typical
100,000 h
Keyboard
Type
Membrane keyboard
System keys with dedicated functions 23
Softkeys
Configurable as softkeys
8
8
Labeling strips
2 for keys:
F1 to F4 and K1 to K4
Keys with LED
4, keys K1 to K4
2
Operating Instructions (Compact) OP 77B
2–2
6AV6691-1EA01-0AB0
Memory
Working memory
1 MByte
Memory card
MMC, optional
Power supply
Rated voltage
Range, permissible
24 V DC
+18 V to +30 V
Transients, maximum permissible
35 V (500 msec)
Time between two transients,
minimum
50 s
Power consumption
•
Typical
•
Constant current, maximum
•
Power on current surge I2t
•
USB interface
Approx. 200 mA
Approx. 300 mA
Approx. 0.5 A2s
Approx. 100 mA
Fuse, internal
Electronic
Release 03/2004
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
3–1
Installing the OP 77B
3
Installing the OP 77B
3.1 EMC Guidelines
Electromagnetic compatibility
The HMI device fulfills the requirements stipulated in
the law on EMC in Germany as well as the EMC
guidelines of the European Union.
Installing HMI devices conform to EMC
requirements
Preconditions for errorfree operation are a PLC design
compliant with EMC requirements and the use of
interferenceproof cables. The "guidelines for
interference-free construction of PLCs" and the
"PROFIBUS network" manual apply for the installation
of the HMI device.
Note
The term "switching cabinet" subsequently used also
relates to the installation cabinets, front panels and
consoles.
3
Operating Instructions (Compact) OP 77B
3–2
6AV6691-1EA01-0AB0
3.2 Installation Position and Fixation
Installation positions
2
1
Installation
position
Max. permissible ambient
temperature
1
vertical
50 °C
2
horizontal
40 °C
Figure 3–1
Permissible ambient temperatures without
external ventilation
If the unit is installed horizontally and the permissible
ambient temperature is exceeded, external ventilation is
necessary. In general, ambient temperatures exceeding
50 °C are impermissible.
Caution
If the HMI device is used at a temperature exceeding
the maximum permissible temperature without any
external ventilation, the terms of warranty complying to
UL 508 are annulled!
Release 03/2004
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
3–3
Installing the OP 77B
Type of fixation
Spring terminals are provided for installation in a
switching cabinet. Install them in the slots as illustrated
in the figure below.
Figure 3–2
Installing the spring terminals
3.3 Producing the Installation Cut-Out
Warning
Danger, high voltage
After opening the switching cabinet, parts become
exposed which conduct voltage levels that could prove
fatal on contact.
Switch off the power supply to the switching cabinet
before opening it.
When selecting the installation cut-out, ensure that the
installation surface around the installation cut-out is
stable. If necessary, install reinforcements.
Operating Instructions (Compact) OP 77B
3–4
6AV6691-1EA01-0AB0
Caution
The degree of protection against water and dust can
only be guaranteed when the following is maintained:
• Material thickness for the installation cut-out
2 mm to 6 mm
• Deviation of the installation cut-out to the horizontal
plane in respect of the overall dimensions of the HMI
device:
≤ 0.5 mm
• Permissible surface roughness in the area of the
installation seal:
≤ 120 µm (Rz 120)
An installation cut-out complying to the figure below is
required:
135 +1
171 +1
Figure 3–3
Installation cut-out
Ensure that the switching cabinet has enough space to
allow a sufficient circulation of air.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
4–1
Connecting the OP 77B
4
Connecting the OP 77B
Conditions
• Installation of the HMI device in accordance with the
specifications in the operating instructions
Electrical connections
Connect the HMI device in the following sequence:
Potential equalization line
PLC
Configuration computer, if necessary
Peripheral equipment, if necessary
Power supply
Notice
Connection sequence
Please observe the sequence of HMI device
connections. Failure to do so may result in damage to
the HMI device.
When disconnecting the connections, ensure it is done
in the reverse sequence.
Connecting the cables
When connecting the cables, ensure that the contact
pins are not bent. Secure the cable plug, if possible,
with screws.
4
Operating Instructions (Compact) OP 77B
4–2
6AV6691-1EA01-0AB0
4.1 Connecting the Potential
Equalization
Connection configuration
1
2
4
5
3
3
1
Grounding connection on the HMI device
2
Grounding cable
3
Switching cabinet
4
Grounding connection
5
Potential equalization line
Figure 4–1
Potential equalization line connection
Notice
Potential equalization line
Line shields are not suitable for potential equalization.
Only use the potential equalization lines recommended
– refer to Figure 4–1. Potential equalization lines, for
example, must have a minimum cross-section of
16 mm2. When setting up MPI and PROFIBUS DP
networks, ensure cables with a sufficient cross-section
are used otherwise the interface modules may be
damaged or even destroyed.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
4–3
Connecting the OP 77B
4.2 Connecting the PLC
Connection configuration
RS 232
Use only the approved cables for connections to the SIMATIC S7.
1
SIMATIC S5
Converter
TTY
AS 511
SIMATIC S7/M7
SIMATIC 500/505
PLC of other
manufacturers
RS 485
RS 422
RS 422/RS 485
1)
SIMATIC 500/505
PLC of other
manufacturers
Figure 4–2
Connecting the PLC
• Interfaces: Serial
• Interface description – refer to Chapter 1.5.
• Standard cables are available for the connection –
refer to SIMATIC HMI Catalog ST 80
Operating Instructions (Compact) OP 77B
4–4
6AV6691-1EA01-0AB0
Configuring the interface
The RS 422/RS 485 interface can be configured by
changing the switch settings on the DIL switch. In this
case, the RS 422 receive data and RTS signal are
interchanged.
Normally, the RTS signal is not required by the PLC.
2
1
3
3
1
Rear panel cover
2
DIL switch
3
Illustration of the switch setting
Figure 4–3
Position of the DIL switch
Note
Pay attention to the DIL switch settings on the rear of
the HMI device depicted in the diagrams – also refer to
Table 4-1.
The following table describes the DIL switch settings
according to the communication to be selected. The
switch settings relate to Figure 4–3.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
4–5
Connecting the OP 77B
Table 4-1
DIL switch setting positions
Communication
Switch settings
PLC
MPI/PPI
Standard cable
4
3
2
1
ON
No RTS on connector
PLC
RS 422
4
3
2
1
ON
PLC
PROFIBUS-DP/MPI
4
3
2
1
ON
No RTS on connector
4
3
2
1
ON
RTS on Pin 9
(as programming unit)
4
3
2
1
ON
RTS on Pin 4
ON
Switch
4
3
2
1
ON
State on delivery
Operating Instructions (Compact) OP 77B
4–6
6AV6691-1EA01-0AB0
4.3 Connecting the Configuration
Computer
Connection configuration
PC
MPI card
PG 7xx
MPI card
PROFIBUS DP/MPI
PROFIBUS DP/MPI
PC
PG 7xx
USB
USB
PC
COM 1
COM 2
PG 7xx
COM 2
RS 232
RS 232
Figure 4–4
Connecting the configuration computer
• Interfaces: serial or USB
• Interface description – refer to Chapter 1.5.
Applies for the USB interface:
HMI device and programming unit are master.
Therefore, a host-to-host cable is required for the USB
interface.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
4–7
Connecting the OP 77B
4.4 Connecting Peripheral Equipment
Connection configuration
USB
Figure 4–5
Connecting peripheral equipment
• Interfaces: USB
• Interface description – refer to Chapter 1.5.
Notice
Nominal load of the interface
The load capacity of the USB connection is limited to
100 mA. Avoid applying higher loads. Otherwise,
functional faults can occur on the peripheral equipment
connected.
The following peripheral equipment can be connected:
• Printer
Note
Documentation on peripheral equipment
Also observe the documentation supplied with the
printer when connecting it.
Operating Instructions (Compact) OP 77B
4–8
6AV6691-1EA01-0AB0
4.5 Connecting the Power Supply
Connection configuration
Figure 4–6
Connecting the power supply
The associated terminal block is contained in the
accessories kit and designed for cables with a
maximum cross-section of 1.5 mm2.
Connecting the terminal block
2
1
DC +24 V
GND
Figure 4–7 Connecting the terminal block
Connect the terminal lock to the power supply lines as
illustrated in Figure 4–7. Ensure that the lines are
connected properly and not to the wrong terminals.
Reverse battery protection
The HMI device is equipped with reverse battery
protection.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
4–9
Connecting the OP 77B
Power supply
Caution
Ensure safe electrical insulation of the power supply.
Use only power supply units complying with
IEC 364-4-41 or HD 384.04.41 (VDE 0100, Part 410).
Only use mains apparatus which complies to SELV
(Safety Extra Low Voltage) and PELV (Protective Extra
Low Voltage) standards.
The supply voltage must be within the specified voltage
range. Voltages outside this range can cause HMI
device malfunctions.
The requirements of the voltage supply are set out in
Chapter 1.5.
Switching on the HMI device
Proceed as follows:
Connecting the terminal block to the HMI device.
Switch on the power supply to the HMI device.
The following window appears:
Bootloader
Date: xx.xx.xxxx
B 7.0.0.xx
Version x.xx
Figure 4–8
Bootloader
If the HMI device does not run-up, it is possible that
the lines on the terminal block have been swapped
over. Swap the connected lines back.
Operating Instructions (Compact) OP 77B
4–10
6AV6691-1EA01-0AB0
After loading the operating system, the HMI device
automatically switches to Transfer mode and the
Transfer dialog opens:
Figure 4–9
Transfer dialog
Note
When the HMI device is restarted, it is possible that a
project already exists on the HMI device; in which case
Transfer mode is not called in but the project is started.
Exit from the project. The Loader then reappears.
Press
ESC
After canceling, the Loader appears:
Loader
Transfer
Start
Infos/Settings
B 7.0.0.xx
Figure 4–10 Loader
Switching off the power supply to the HMI device.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
4–11
Connecting the OP 77B
Keys for navigation in the Loader
Table 4-2
Overview of keys available for use
Key
Effect of pressing
or
Move to the next menu item.
or
Move to the previous menu item.
ENTER
The menu item or associated submenu is called in.
ESC
Cancel the entry and return to the menu item one
level above.
Note
Entries in the dialog boxes are possible using the
cursor keys – numeric values, too, using the numeric
keypad.
Other keys without functions are available in the
Loader.
Operating Instructions (Compact) OP 77B
4–12
6AV6691-1EA01-0AB0
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
5–1
Operating the OP 77B
5
Operating the OP 77B
5.1 Front Side Operating Elements and
Indicators
1
5
3
2
4
1
Softkeys without LED
2
Softkeys with LED
3
System keys – digit keypad
4
LED display
5
System keys – control keys
Figure 5–1
Front side operating elements and indicators
5
Operating Instructions (Compact) OP 77B
5–2
6AV6691-1EA01-0AB0
The standard input unit for the OP 77B is the keyboard.
This is basically composed of two key groups:
• Softkeys
F1 to F4 and K1 to K4
The function executed by each softkey is defined
specifically for a project during the configuration
phase; the softkey have no function in the Loader.
• System keys
Digit keypad and control keys
Notice
Keyboard damage
Heavy-handed operation of the keys with a hard,
pointed or sharp object leads to a considerable
reduction in their service life and even to their complete
failure.
Only use your fingers to operate the HMI device keys.
5.2 Further Operating Elements
When an HMI device is installed, further operating
elements can be accessed by opening the switching
cabinet.
Danger
Danger, high voltage
After opening the switching cabinet, parts become
exposed which conduct voltage levels that could prove
fatal on contact.
Switch off the power supply to the switching cabinet
before opening it.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
5–3
Operating the OP 77B
Other operating elements include:
• Ejection button on memory card holder; refer to
Figure 5–2
• Guides for the labeling strips; refer to Figure 1–2
• DIL switches for the RS 422/RS 485 switch; refer to
Figure 4–3
Using memory cards
Notice
Data loss
If a prompt for formatting appears when using a
memory card for the first time on the HMI device, make
a backup copy of the data on the memory card on a PC
beforehand.
Proceed as follows to prevent loss of data:
Cancel the formatting process by pressing ESC
Data which must not be lost should be saved on a
PC
Format the memory card on the HMI device
Transfer the data saved on the PC to the memory
card
Then transfer the backed up data from the memory
card to the HMI device.
Operating Instructions (Compact) OP 77B
5–4
6AV6691-1EA01-0AB0
Ejecting the memory card
When the memory card is installed correctly in the
memory card slot, the memory card holder is latched in
behind the memory card.
Do not plug the memory card in or unplug it during data
access when making a data backup or transferring a
recipe. Otherwise, the memory card can be inserted
and removed during operation.
2
1
1
Eject knob
2
MMC
Figure 5–2
Ejecting the memory card
On pressing the Eject knob, the memory card is
released from the memory card slot.
Notice
Do not press the knob abruptly. This could damage the
ejection mechanism.
Store the memory for safekeeping well protected.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
5–5
Operating the OP 77B
Labeling the softkey
1
1
Guides for the labeling strips
Figure 5–3
Labeling of the softkey
The labeling strips can also be inserted when the HMI
device has been installed.
Softkeys which are not screen dependent can be
provided with labeling strips (also refer to Figure 5–6).
Printing the labeling strips
The template can be found on the installation computer
after installing WinCC flexible and on the "WinCC
flexible" installation CD under
...\Documents\slide77b.doc.
The file can be edited using the MS Office programs
MS Word or Wordpad.
160
15,3
15
25,6
8,25
–1
16
25,6
25,6
2 x 45°
Figure 5–4
Labeling strip dimensions
Operating Instructions (Compact) OP 77B
5–6
6AV6691-1EA01-0AB0
Where possible, print the labeling strips on transparent
foil. This means that the LEDs on the softkeys remain
visible.
Edit and print templates
Cut out labeling strips
Ensure that the corners are cut according to Figure
5–4. This simplifies sliding it into the guide.
Danger
Danger, high voltage
After opening the switching cabinet, parts become
exposed which conduct voltage levels that could prove
fatal on contact.
Switch off the power supply to the switching cabinet
before opening it.
Remove the existing labeling strips
Slide the labeling strips in the guide
1
2
1
Labeling strips
2
MMC
Figure 5–5
Insert the labeling strips
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
5–7
Operating the OP 77B
5.3 Operating the Project
Softkeys with global function assignment
A softkey with global function assignment always
triggers the same action on the HMI device or PLC
regardless of the screen currently open. These actions
include:
• Calling in a screen
• Printing the screen displayed
Within a screen, a softkey can only have one function
assigned – either global or local. In the case of local
and global functions, the local function has priority.
Softkeys with local function assignment
A softkey with a local function assignment relates to a
specific screen and, thus, is only effective in the active
screen.
The function of a softkey can vary from screen to
screen.
The two-row softkeys are particularly suitable for
implementing binary states and machine functions, as
illustrated in the following screen.
OFF
ON
STOP
START
–
+
Figure 5–6
Example of two row, labeled keys
Operating Instructions (Compact) OP 77B
5–8
6AV6691-1EA01-0AB0
System keys
Table 5-1
Overview of control keys
Key
Effect of pressing
,
The cursor keys have a repeat function.
In the case of I/O fields, selects the next field in
horizontal direction.
,
In the case of I/O fields, selects the next field in
vertical direction.
TAB
The following field is selected in the sequence
defined in the project (Tab Order).
SHIFT
The second function of another key is released for
use.
SHIFT
+
SHIFT
+
When used with the cursor keys, scroll in the
selection fields; refer to Chapter 5.4.3 and 5.4.5.
SHIFT
+
TAB
The Tab Order is reversed
INS
DEL
In character "String" input fields, the character at the
current cursor position is deleted.
All the following characters move one position to the
left.
HELP
Calls in a window containing operator notes on the
selected object. Condition:
Operator notes are only available on the selected
object when the
HELP
LED lights up.
Pressing
ENTER
enables toggling between operator
notes for a screen and an object; toggling for an I/O
field for example.
ESC
•
Undo
An entry can be undone by pressing this key
before the
ENTER
key is pressed to confirm the input.
•
Close the System Event window, if configured
•
Cancel the display of an operator note to return to
the previous display.
ACK
Acknowledges the alarm current displayed or marked,
or all alarms in an acknowledgment group, depending
on the configuration; refer to Chapter 6.2
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
5–9
Operating the OP 77B
Key
Effect of pressing
ENTER
•
The input is confirmed and applied.
•
Initiates input via
and
Navigation in lists
Table 5-2
Keys for navigation in lists
Key
Effect of pressing
or
Selects the previous or next list item.
SHIFT
+
9
SHIFT
+
3
Scrolls one page forward or back to other list entries
SHIFT
+
.
HOME
SHIFT
+
0
END
Marks the first or last entry in a list
Operating Instructions (Compact) OP 77B
5–10
6AV6691-1EA01-0AB0
5.4 Input Within a Project
General procedure
Values are entered in the project input fields. They are
transferred from there to the PLC.
Proceed as follows:
Open the required screen.
Select the required input field from the screen.
Enter values of the following type in the input field
according to the configuration:
–
Numeric
–
Alphanumeric
–
Symbolic
–
Date/Time
Enter value
Incorrect input can be canceled by pressing
ESC
.
The original value is then automatically restored.
Confirm input with
ENTER
5.4.1 Numeric values
Entering numeric values
Numeric values are entered character by character
using the system keyboard. If a field already contains a
value, it is fully deleted from the field after entering the
first character of the new value using the numeric
keypad. The value can also be modified character by
character by pressing ENTER.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
5–11
Operating the OP 77B
Display formats
Values can be entered in numeric input fields using the
following display formats:
• Decimal
• Hexadecimal
• Binary
The input can be aligned to the left or right, depending
on the configuration.
Limit value test
Limit values can be configured for tags. If the value
entered exceeds a configured limit value (e.g. 55 with a
limit value of 50), a system event is automatically
displayed in cases where an alarm window has been
configured. The value entered is not accepted and the
original value reappears.
Decimal places
If a numeric input field is configured with a specific
number of decimal places, additional decimal places
are ignored after confirmation or too few decimal places
are filed with "0".
5.4.2 Alphanumeric values
Alphanumeric values – digits and letters – are entered
character by character using the system keyboard. If a
field already contains a value, it is fully deleted from the
field after entering the first character of the new value
using the numeric keypad. The value can also be
modified character by character by pressing ENTER.
If characters are required which are not available on the
keypad, select them using the character set on the
extended keyboard. The extended character set is
available in "String" format fields.
Operating Instructions (Compact) OP 77B
5–12
6AV6691-1EA01-0AB0
5.4.3 Entering numeric and alphanumeric
characters
Table 5-3
Overview of keys for use for entering characters
Key
Effect of pressing
0
END
to
9
Enter the digits 0 to 9.
,
+/–
,
.
HOME
Enter a comma or stop.
SHIFT
+
,
+/–
The sign of a numeric value is changed
Press
,
+/–
to toggle between the two signs.
SHIFT
+
1
A
to
SHIFT
+
8
F
Letters A to F can be entered
The characters in an extended character set are
called in successively
All 255 character are displayed in succession.
ENTER
The input is valid.
ESC
The input is deleted.
The original value becomes valid again.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
5–13
Operating the OP 77B
Example of alphanumeric input using cursor keys
and numeric keypad
To enter "OP 77B", activate the selection field. If the
cursor keys are used for input, press them until the
required character appears. The following keyboard
input is necessary:
2
B
SHIFT
INS
DEL
ENTER
+
SHIFT +
ENTER
7
E
7
E
A
O
1
1
2
2
2
O
A
O P
O P
O P
A
O P
7
O P
A
7
O P
7
7
O P
A
7 7
O P
B
7 7
B
7
7
P
O
1
Input via the cursor keys
2
Input via the numeric keypad
Figure 5–7
Example of alphanumeric input using cursor keys
and numeric keypad
Operating Instructions (Compact) OP 77B
5–14
6AV6691-1EA01-0AB0
5.4.4 Correcting input
Correcting input using the cursor keys
Replacing an incorrect character
Proceed as follows:
Press
ENTER
Position the cursor at the character to be changed.
Press
or
until the required character
appears.
Press
ENTER
Deleting a character
Proceed as follows:
Press
ENTER
Position the cursor at the character to be deleted.
Press
INS
DEL
The marked character is deleted. The remaining
characters to the right of the cursor shift one
position to the left.
Valid for writing aligned to the right:
The marked character is deleted. The remaining
characters to the left of the cursor shift one position
to the right.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
5–15
Operating the OP 77B
Entering a space
Proceed as follows:
Press
ENTER
Move the cursor to the position where a character is
to be entered.
Press
SHIFT
+
INS
DEL – a space is entered.
The remaining characters to the right of the cursor
shift one position to the right.
Valid for writing aligned to the right:
The remaining characters from the cursor shift one
position to the left.
Correcting input using the numeric keypad
Replacing an incorrect character
Press
ENTER
Position the cursor at the character to be changed.
Enter the correct character via the numeric keypad
One character too many or too few
Corrections are made as described in Section
"Correcting input using the cursor keys".
Operating Instructions (Compact) OP 77B
5–16
6AV6691-1EA01-0AB0
5.4.5 Entering symbolic values
The work involves accepting text from a symbolic I/O
field. Proceed as follows:
Select a symbolic I/O field
Activate the selection field.
Key
Effect of pressing
ENTER
or
SHIFT
+
SHIFT
+
The selection field is activated containing the
symbolic input configured for it.
Select text.
Key
Effect of pressing
,
Text is scrolled in a single line list until the text
searched for is found.
Accept or cancel the input
Key
Effect of pressing
ENTER
The text selected becomes valid.
The symbolic I/O field is deactivated.
ESC
The original text becomes valid again.
The symbolic I/O field is deactivated.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
5–17
Operating the OP 77B
5.4.6 Entering date and time
To enter the date and time, use the keys according to
the section "Entering numeric and alphanumeric
characters".
Note
When entering the date and time, please note that the
format is dependent on the language set.
Use the keys as described in Chapter 5.4.3 to enter the
date and time.
5.5 Calling Help on a Project
Operator notes can be created for the following objects
during configurations with WinCC flexible ES:
• Alarms
• Screens
• I/O field
• Recipes and recipe elements
Operator notes can be configured in several languages.
The availability of an operator note is indicated by the
HELP
LED when lit up. The configured operator notes
can be displayed on the HMI device by pressing
HELP .
Operating Instructions (Compact) OP 77B
5–18
6AV6691-1EA01-0AB0
5.6 Logging On and Off
General information
Standard groups in the security system are:
• Administrator
• User
Other groups can be configured. Each group is
assigned certain user rights. Each user is assigned to
one of these groups, i.e. users within a group have the
same operating rights. Each user is assigned a
password.
Login dialog
When a user calls a function which is protected and has
not been assigned the necessary user rights, the
Logon dialog appears.
User:
OK
Password:
Cancel
Figure 5–8
Example of a Logon dialog
Enter the user name and password – refer to
Chapter 5.4.3 for the keys.
Note
Characters entered for the password are always
represented by "∗". Characters entered via the cursor
keys remain visible until another character is entered or
the input is confirmed with the ENTER.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
5–19
Operating the OP 77B
Select OK
Press
ENTER
to confirm
If the user has the necessary user rights for a
selected operating element, it can be operated.
Otherwise, an alarm appears indicating the user
does not have the necessary rights.
Note
In the case of an operating element assigned operating
rights, a log on is necessary. This is obsoleted,
however, on exceeding the logoff time – refer to
Figure 5-13.
5.7 User Administration in a Project
There are three groups which can manage the users
and their assigned entries:
• the administrator
During configuration, the administrator is assigned
unlimited user rights.
• the operator (user)
• the user with unrestricted user rights.
These groups of people result from the assignment of
user rights during configuration.
Administrator
Operator
Runtime User 1
Figure 5–9
Example of a user display
Operating Instructions (Compact) OP 77B
5–20
6AV6691-1EA01-0AB0
In this case, as indicated in the example in
Figure 5–9, the administrator and two users are
shown. The administrator may change his own
entries and those of the other users:
– User name
– Password
– Group assignment
– Log off time
In addition, further users can be set up. The empty
bottom line is available for the setup.
• If a user cannot log on as "Administrator" but only as
a user, only that entry is displayed, e.g. "Operator".
In this case, no unrestricted user rights have been
assigned.
Only the following entries can then be changed for
that user
– Password and
– Logoff time.
• However, it is possible for a user to modify the entry
of another user. A condition for this is that the user
rights include the user rights of the other users.
Entries which can be modified include:
– User name
– Password
– Group assignment
– Log off time
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
5–21
Operating the OP 77B
Table 5-4
Keys for navigation in lists
Key
Effect of pressing
,
Selects the previous or next user.
SHIFT
+
9
SHIFT
+
3
Scrolls one page up or down to other users.
SHIFT
+
.
HOME
SHIFT
+
0
END
Selects the first or last user.
Limit values for user, password and user displays
Characters
Length of user name, maximum
40
Length of password, minimum
3
Length of password, maximum
24
Entry in the user display, maximum
50
5.7.1 Log on user
Proceed as follows:
Select the empty line in the dialog – refer to
Figure 5–9
Press ENTER
Note
The following Logon dialog only appears when the user
has still not been logged on as a user. The dialog also
appears when the user logs on as Administrator without
the necessary user rights in order to create a new user.
The Logon dialog opens.
Operating Instructions (Compact) OP 77B
5–22
6AV6691-1EA01-0AB0
Enter the user and password.
Confirm with OK
The dialogs necessary to set up a user then
appear.
After having logged on, you ca carry out the following
according to your user rights:
• Change the password
• Create a user
5.7.2 Setting up a user
The following dialogs appear after entering the user and
password:
User:
OK
Cancel
|
Figure 5-10 Example of a User dialog
Proceed as follows:
Enter a user
Confirm with OK
The following dialog appears:
Password:
OK
Cancel
|
Figure 5-11 Example of a Password dialog
Note
The password is only legible once in plain text – when it
is assigned in the Password dialog.
On entering a password at a later date, the characters
entered are represented by
.
Enter the password
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
5–23
Operating the OP 77B
Confirm with OK
The following dialog appears:
Group:
OK
Cancel
Operators
Figure 5-12 Example of a Group dialog
From the list of available groups, select the one
containing the user rights to be assigned to the new
user.
Make the selection using
SHIFT
+
or
or
using
ENTER
and then
or
.
Logoff time:
OK
Cancel
5
Figure 5-13 Example of a Logoff Time dialog
The logoff time is defined in minutes. 5 minutes are
entered as the default value.
Select the value depending on the respective
operating situation.
Confirm with OK
The user display appears containing the new user,
refer to Figure 5–9.
Operating Instructions (Compact) OP 77B
5–24
6AV6691-1EA01-0AB0
5.7.3 Changing passwords
The following dialogs appear after entering the user and
password:
User:
OK
Cancel
User 1
Figure 5-14 Example of a Password dialog
Proceed as follows:
Enter a user
Confirm with OK
The following dialog appears:
Password:
OK
Cancel
Password
Figure 5-15 Example of a Password dialog
Enter the password
Confirm with OK
Confirm the two subsequent dialogs. The new
password becomes valid.
5.7.4 Deleting a user name
When a user is deleted, the password is deleted from
the User display. A condition for deleting users is the
assignment of administrator rights.
There are two methods of deleting a user:
• Select the user name in the User display and press
INS
DEL .
• Delete all the characters in the user name input
dialog and confirm by clicking OK.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
6–1
Recipes and Alarms
6
Recipes and Alarms
6.1 Operating Recipes
Terminology
Recipe
A recipe is comprised of several tags which define the
data structure of as data record.
Data record
A data record contains the values of a recipe.
Recipe entry
A recipe element consists of an entry name and a
value. The names, assigned to the tags, are referred to
an element names.
Single recipe views
The Recipe view is a configurable object in the recipes,
data records and recipe elements displayed in lists.
These are described below.
6
Operating Instructions (Compact) OP 77B
6–2
6AV6691-1EA01-0AB0
Recipe list
The recipes configured are displayed as a recipe list. A
recipe list can appear as follows, for example:
1 Grapefruit
2 Lemon
3 Orange
4 Apple
Figure 6–1
Example of a recipe list
Table 6-1
Overview of keys available
Key
Effect of pressing
SHIFT
+
INS
DEL
Creates a new data record.
ENTER
Opens the data record list of the selected recipe.
HELP
Calls in a window containing operator notes on the
selected object – refer to Table 5-1.
Opens the menu
Further keys used for navigation are explained in
Section "Navigation in lists". This also applies to
operating in recipes.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
6–3
Recipes and Alarms
Data record list – Data records of a recipe
1 Juice
2 Drink
3 Nectar
Figure 6–2
Example of a data record list
Table 6-2
Overview of keys used in data record lists
Key
Effect of pressing
SHIFT
+
INS
DEL
Creates a new data record.
ENTER
Opens the entry list of the selected data record.
ESC
The recipe list is displayed again.
Note
When the first data record has been selected and
is pressed, the associated recipe name is displayed.
Operating Instructions (Compact) OP 77B
6–4
6AV6691-1EA01-0AB0
Element list – data record values
The element list can be used to edit data record values.
l Orange
l Water
kg Sugar
g Aroma
90
10
1.5
200
1
3
2
1
Data record
2
Menu
3
Element name
Figure 6–3 Example of an element list
The sequence of columns for element names and
values can be configured.
Table 6-3
Overview of keys available for use
Key
Effect of pressing
ESC
The data record list is displayed again.
HELP
Calls in a window containing operator notes on the
selected object – refer to Table 5-1.
Note
When the first element has been selected and
is
pressed, the associated data record and recipe name is
displayed.
Proceed as follows to edit a value:
Select element name
The entries possible are dependent on the tag type.
If a text list has been configured in a recipe
element, symbolic values can also be entered.
Enter value
Apply the entry or cancel it
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
6–5
Recipes and Alarms
Menu
A menu is available for quick access to the permitted
operating procedures in recipes, data records and
element lists.
Menu button
Effect of pressing
Call in the menu
Alternatively to using
, the menu can be called in with
.
The menu items which can be configured can be
determined from Table 6-4.
Configurable menu items in the Recipe view
The following table indicates which menu items are
available in the three lists. Some menu items in the
following table can also be called in via the system
keys.
Operating Instructions (Compact) OP 77B
6–6
6AV6691-1EA01-0AB0
Table 6-4
Overview of configurable menu items
Menu item
System key
Recipe list
Data record list
Entry list
Add data record
SHIFT
+
INS
DEL
Yes
Yes
–
Save data record
–
–
Yes
Delete data record
INS
DEL
–
Yes
–
Write data record in PLC
–
–
Yes
Read data record from PLC
–
–
Yes
Data record, save as
–
Yes
Yes
Data record, rename
–
Yes
Yes
Display operator notes
HELP
Yes
Yes
Yes
Open list
ENTER
Yes
Yes
–
Open previous list
ESC
–
Yes
Yes
The menu can appear as follows, for example:
2 Save
4 to PLC
5 from PLC
6 Save as
Figure 6–4
Example of a menu with menu items configured
for entry lists
Each of these menu items can also be called in by
entering the assigned number or by marking it with the
cursor and pressing ENTER.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
6–7
Recipes and Alarms
Table 6-5
Overview of keys for use in a menu for a
Recipe view
Key
Effect of pressing
1
A
to
9
Calls in the assigned menu item.
ENTER
Triggers the menu item selected with the cursor.
ESC
Displays the previously selected list.
Example
Using the Save Data Record menu item – refer to
Figure 6–4.
Proceed as follows:
With cursor key input
Select Save Data Record with the cursor key.
Confirm the selection with ENTER.
The data record is saved and the entry list
reappears.
With numeric input
Enter "2".
The data record is saved and the entry list
reappears.
Operating Instructions (Compact) OP 77B
6–8
6AV6691-1EA01-0AB0
6.2 Operating Alarms
Alarm classes
The alarm classes can exist in a project:
• User-defined alarms
A user-defined alarm can be assigned to one of the
following alarm classes:
– Fault
Alarms in this category must always be
acknowledged.
– Operation
– User-defined alarm classes
The properties of this alarm class are defined
during configuration.
• System events
A system event is assigned to the "System" event
category.
The related alarms consist of static text. They can also
contain tags. It is possible to configure an alarm text to
flash.
A maximum of 80 characters per alarm are possible.
"Fault" alarm class
The occurrence of an alarm of the alarm class "Fault" is
indicated by the flashing "alarm indicator" LED:
Figure 6–5
"Alarm indicator" LED
The "alarm indicator" LED
• is off when no alarms of the "Fault" alarm class are
queued,
• flashes when an alarm of the "Fault" alarm class has
been received but not acknowledged and
• only lights up if acknowledged alarms of the "Fault"
alarm class are present.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
6–9
Recipes and Alarms
Alarm view
156 12:05:49 Alarm
Engine 23 to hot
Figure 6–6
Alarm view for "Fault" alarm class
It is possible to configure:
• The number of lines per alarm.
• Number of visible lines
Table 6-6
Overview of keys used in Alarm views
Key
Effect of pressing
ACK
Acknowledges the alarms which have arrived.
HELP
Calls in the operator notes on the selected alarm.
Further keys for navigation purposes are explained in
Table 5-1.
The keys displayed in the table are valid for all alarm
classes.
Edit alarm
Pressing
ENTER
triggers the function assigned to the
"Edit" event in respect of a selected alarm.
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
7–1
Index
7
Index
A
Accessory kit 1–3
Alarm class
Fault 6–8
Alarm classes 6–8
User-defined 6–8
Alarm view 6–9
Alarms 6–1
User-defined 6–8
Alphanumeric input
Via the cursor keys 5–14
Via the numeric keypad
5–14
B
Bottom view 1–2
C
Cable cross-section 4–8
Configuring
Interface 4–4
Configuring the interface
4–4
Connecting
Configuration computer
4–6
OP 77B 4–1
Periphery 4–7
PLC 4–3
Potential equalization
line 4–2
Power supply 4–8
Terminal block 4–8
Connecting peripheral
equipment 4–7
Connecting the configuration
computer 4–6
Connecting the PLC 4–3
Connecting the potential
equalization 4–2
Connecting the terminal
block 4–8
Connection configuration
Configuration computer
4–6
Periphery 4–7
PLC 4–3
Potential equalization
line 4–2
Power supply 4–8
Connection sequence 4–1
Connections, electrical 4–1
Control keys 5–9
Correcting
Input 5–15
Cross-section
connection cables 4–8
D
Data record list 6–3
Date 5–18
Decimal places 5–12
Deleting a user name 5–25
DIL switch 4–5
Display 2–1
Display formats 5–12
7
Operating Instructions (Compact) OP 77B
7–2
6AV6691-1EA01-0AB0
E
Edit
Alarm 6–9
Edit alarm 6–9
Element list 6–4
EMC Guidelines 3–1
Entering
Alphanumeric characters
5–13
Date and time 5–18
Numeric characters
5–13
Numeric values 5–11
Symbolic values 5–17
Example
Alphanumeric input via
the cursor keys 5–14
Alphanumeric input via
the numeric keypad
5–14
F
Front view 1–1
G
Guidelines
EMC 3–1
H
Help on a project 5–18
Housing 2–1
I
IF 1A 1–6
IF 1B 1–5
Indicators 5–1
Input
Correcting 5–15
Input in a project 5–11
Installation
OP 77B 3–1
Installation cut-out 3–3
Installation positions 3–2
Interfaces 1–5
K
Keyboard 2–1
L
Labeling 5–6
Labeling strips 1–4, 5–6
Limit value test 5–12
Limit values
For users, passwords,
user displays 5–22
Log off 5–19
Log on 5–19
User 5–22
Login dialog 5–19
M
Memory 2–2
Memory card 1–3
Eject 5–5
Using 5–4
Menu 6–5
Menu items
Configurable 6–5
Miscellaneous 1–4
N
Navigation
Loader menu 4–11
Navigation
in lists 5–10
O
OP 77B
Connecting 4–1
Installation 3–1
Operating 5–1
Operating
Alarms 6–8
OP 77B 5–1
Project 5–8
Recipes 6–1
Operating elements
Front side 5–1
Other 5–3
Operating recipes 6–1
Operating system
Operating Instructions (Compact) OP 77B
6AV6691-1EA01-0AB0
7–3
Index
Load 4–10
Options 1–3
Overview 1–1
P
Power supply 1–5, 2–2
Connecting 4–8
print
Labeling strips 5–6
Project
Help 5–18
Input 5–11
Operating 5–8
User administration
5–20
R
Recipe list 6–2
Recipe views
Menu 6–5
Recipes 6–1
Reverse battery protection
4–8
RS 232 1–6
RS 422 1–5
RS 485 1–5
S
Scaled drawings 1–4
Side view 1–2
Softkeys 2–1, 5–3, 5–8
global 5–8
labeling 5–6
local 5–8
Switch settings 4–5
Switching on 4–9, 4–10
System keys 2–1, 5–3
T
Technical data 2–1
Terminology
Recipe views 6–1
Time 5–18
Type of fixation 3–3
U
USB 1–6
User
Log on 5–22
User administration 5–20
V
Values
alphanumeric 5–12
numeric 5–11
Symbolic 5–17