O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
About this document........................................................................
5
1.1
Purpose of this document........................................................................
5
1.2
Scope.........................................................................................................
5
1.3
Target groups and structure of these operating instructions................
5
1.4
Additional information..............................................................................
5
1.5
Symbols and document conventions......................................................
6
2
Safety information............................................................................
7
2.1
General safety notes................................................................................
7
2.2
Intended use.............................................................................................
7
2.3
Improper use.............................................................................................
7
2.4
Requirements for the qualification of personnel....................................
8
3
Product description...........................................................................
9
3.1
Construction and function........................................................................
9
3.2
Product characteristics............................................................................
9
3.2.1
Device overview.......................................................................
9
3.2.2
Interfaces.................................................................................
9
3.2.3
Compatible sensor types.........................................................
10
3.2.4
Restart interlock......................................................................
10
3.2.5
External device monitoring......................................................
10
3.2.6
Cross-circuit detection.............................................................
10
3.2.7
Status indicators......................................................................
10
4
Project planning................................................................................
12
4.1
Manufacturer of the machine..................................................................
12
4.2
Operating entity of the machine..............................................................
12
4.3
Design........................................................................................................
12
4.4
Electrical integration.................................................................................
13
4.4.1
Enabling current paths............................................................
13
4.4.2
Application diagnostic output.................................................
13
4.4.3
Restart interlock......................................................................
14
4.4.4
External device monitoring (EDM)..........................................
14
4.4.5
Connection diagrams..............................................................
15
4.5
Testing plan...............................................................................................
15
4.5.1
Minimum requirements for the regular thorough check.......
16
5
Mounting............................................................................................. 17
5.1
Safety.........................................................................................................
17
5.2
Mounting procedure.................................................................................
17
5.3
Disassembly..............................................................................................
18
5.4
Device replacement..................................................................................
18
6
Electrical installation........................................................................
20
6.1
Device connection....................................................................................
20
CONTENTS
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
3
Subject to change without notice
Status indicator (LED)...............................................................................
24
9
Decommissioning.............................................................................
25
9.1
Protecting the environment......................................................................
25
10
Technical data.................................................................................... 26
10.1
Data sheet.................................................................................................
26
10.2
Dimensional drawings..............................................................................
30
10.3
Internal circuitry........................................................................................
31
11
Ordering information........................................................................
32
11.1
Ordering information for ReLy..................................................................
32
12
Annex..................................................................................................
33
12.1
Compliance with EU directives.................................................................
33
13
List of figures.....................................................................................
34
14
List of tables....................................................................................... 35
CONTENTS
4
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
About this document
1.1
Purpose of this document
These operating instructions contain the information required during the life cycle of the
safety relay.
These operating instructions must be made available to everyone who works with the
safety relay.
1.2
Scope
This document only applies to a ReLy safety relay with the following type label entries in
the Operating Instructions field:
•
8020866
1.3
Target groups and structure of these operating instructions
These operating instructions are intended for the following target groups: project devel‐
opers (planners, developers, designers), installers, electricians, safety experts (such as
CE authorized representatives, compliance officers, people who test and approve the
application), operators, and maintenance personnel.
These operating instructions are organized by the life phases of the device: project
planning, mounting, electrical installation, commissioning, operation and maintenance.
The table below shows the target groups and how – for many applications – these are
typically divided up between the manufacturer and the entity operating the machine in
which the device is to be integrated:
Area of responsibility
Target group
Specific chapters of these operating instruc‐
tions 1)
Manufacturer
Project developers
(planners, developers,
designers)
"Project planning", page 12
"Technical data", page 26
Installers
"Mounting", page 17
Electricians
"Electrical installation", page 20
Safety experts
"Project planning", page 12
"Commissioning", page 23
"Technical data", page 26
Operating entity
Operators
"Troubleshooting", page 24
Maintenance person‐
nel
"Troubleshooting", page 24
"Ordering information", page 32
1)
Chapters not listed here are intended for all target groups. All target groups must follow all of the safety
and warning instructions in all chapters of the operating instructions!
In other applications, the operating organization is also the manufacturer of the equip‐
ment with the corresponding allocation of the target groups.
1.4
Additional information
www.sick.com
The following information is available on the Internet:
•
This document in other languages
•
Data sheets and application examples
•
CAD data and dimensional drawings
ABOUT THIS DOCUMENT 1
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
5
Subject to change without notice
Certificates (e.g. EU declaration of conformity)
•
Guide for Safe Machinery Six steps to a safe machine
1.5
Symbols and document conventions
The following symbols and conventions are used in this document:
Safety notes and other notes
DANGER
Indicates a situation presenting imminent danger, which will lead to death or serious
injuries if not prevented.
WARNING
Indicates a situation presenting possible danger, which may lead to death or serious
injuries if not prevented.
CAUTION
Indicates a situation presenting possible danger, which may lead to moderate or minor
injuries if not prevented.
NOTICE
Indicates a situation presenting possible danger, which may lead to property damage if
not prevented.
NOTE
Indicates useful tips and recommendations.
Instructions to action
b
The arrow denotes instructions to action.
1.
The sequence of instructions for action is numbered.
2.
Follow the order in which the numbered instructions are given.
✓
The check mark denotes the result of an instruction.
LED symbols
These symbols indicate the status of an LED:
o
The LED is off.
Ö The LED is flashing.
O
The LED is illuminated continuously.
1 ABOUT THIS DOCUMENT
6
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
General safety notes
DANGER
If the safety component is integrated incorrectly, the dangerous state may be ended to
late.
b
Plan the integration of the safety component in accordance with the machine
requirements, see "Project planning", page 12.
DANGER
Hazard due to lack of effectiveness of the protective device
In the case of non-compliance, it is possible that the dangerous state of the machine
may not be stopped or not stopped in a timely manner.
b
Please read this document carefully and make sure that you understand the con‐
tent fully before working with the device.
b
Follow all safety notes in this document.
Improper installation or manipulation can lead to serious injuries.
2.2
Intended use
The safety relay is an evaluation unit for emergency stop pushbuttons and safety
switches for switching safety-related circuits on and off.
The safety relay complies with class A, group 1 as per EN 55011. Group 1 encom‐
passes all ISM devices in which intentionally generated and/or used conductor-bound
RF energy that is required for the inner function of the device itself occurs.
The safety relay must only be used within the limits of the prescribed and specified
technical data and operating conditions at all times.
Incorrect use, improper modification or manipulation of the safety relay will invalidate
any warranty from SICK; in addition, any responsibility and liability of SICK for damage
and secondary damage caused by this is excluded.
UL/CSA applications
If the product is being used in accordance with UL 508 or CSA C22.2 No. 14, the follow‐
ing conditions must also be met:
•
To protect the device’s 24-volt voltage supply, use a fuse with a maximum voltage
of 4 A and a minimum of 30 V DC in accordance with UL 248.
NOTE
The safety functions have not be evaluated by UL. Authorization is in accordance with
UL 508, general applications.
2.3
Improper use
The safety relay is not suitable for the following applications (this list is not exhaustive):
•
At altitudes of over 4,000 m above sea level
•
In explosion-hazardous areas
SAFETY INFORMATION 2
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
7
Subject to change without notice
Requirements for the qualification of personnel
The protective device must be configured, installed, connected, commissioned, and ser‐
viced by qualified safety personnel only.
Project planning
For project planning, a person is considered competent when he/she has expertise and
experience in the selection and use of protective devices on machines and is familiar
with the relevant technical rules and national work safety regulations.
Mechanical mounting, electrical installation, and commissioning
For the task, a person is considered qualified when he/she has the expertise and expe‐
rience in the relevant field and is sufficiently familiar with the application of the protec‐
tive device on the machine to be able to assess whether it is in an operationally safe
state.
Operation and maintenance
For operation and maintenance, a person is considered competent when he/she has
the expertise and experience in the relevant field and is sufficiently familiar with the
application of the protective device on the machine and has been instructed by the
machine operator in its operation.
2 SAFETY INFORMATION
8
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
Construction and function
The safety relay ReLy EMSS1 is an electrical switching device with inputs and outputs.
The safety capable inputs of the safety relay are connected to safety sensors or safety
switches.
2 safety capable inputs control the internal relays, which are used to reliably switch the
enabling current paths.
The enabling current paths close only when the two safety capable inputs close within
3 s of one another.
Actuators with positively guided contacts are connected to the enabling current paths.
3.2
Product characteristics
3.2.1
Device overview
PWR
OUT
13
23
I1
Y1
14
24
I2
Y2
A2
RELY
1
2
3
4
S1
X1
A1
R1
X2
Figure 1: Device overview
1
Device unlocking
2
LEDs
3
Front connector unlocking
4
Front connector
3.2.2
Interfaces
Inputs
•
2 safety capable inputs
•
Input for reset pushbutton or external device monitoring
Outputs
•
2 enabling current paths (safe)
•
2 application diagnostic outputs (not safe)
•
3 test outputs (not safe)
PRODUCT DESCRIPTION 3
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
9
Subject to change without notice
Compatible sensor types
The safety relay is suitable for safety sensors and safety switches with volt-free output
contacts, e.g.:
•
Dual-channel safety command devices (emergency stop pushbutton, rope pull
switch, etc.)
•
Dual-channel, contact-based interlocking devices (safety locking devices and
safety switches)
•
Dual-channel, magnetic safety switches with reed contacts
3.2.4
Restart interlock
A restart interlock can be implemented with a reset pushbutton.
3.2.5
External device monitoring
Permanent external device monitoring can be implemented using external wiring.
3.2.6
Cross-circuit detection
A cross-circuit is detected on the safety capable inputs.
3.2.7
Status indicators
LEDs
PWR
OUT
13
23
I1
Y1
14
24
I2
Y2
A2
RELY
S1
X1
A1
R1
X2
PWR
OUT
13
23
I1
Y1
14
24
I2
Y2
A2
RELY
R1
A1
S1
X1
X2
EMSS1
1085345
Figure 2: LEDs
The labeled positions are only partially assigned LEDs. The positions and their labeling
(except for the upper 2 lines) also show the pin assignment of the terminals on the front
connector.
Table 1: Safety relay indicators
Labeling
Color
Function
PWR
Green/Red
Voltage supply
OUT
Green
Enabling current paths
I1
Green
Safety capable input
I2
Green
Safety capable input
S1
Green
Reset pushbutton input, exter‐
nal device monitoring (EDM)
3 PRODUCT DESCRIPTION
10
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
Application diagnostic output
Y2
Green
Application diagnostic output
(reset required)
Further topics
•
"Status indicator (LED)", page 24
PRODUCT DESCRIPTION 3
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
11
Subject to change without notice
Manufacturer of the machine
DANGER
Failure to comply with manufacturer’s obligations
Hazard due to lack of effectiveness of the protective device
b
Carry out a risk assessment before using the safety relay.
b
Do not manipulate, open or modify the components of the safety relay.
b
Make sure the safety relay is only repaired by the manufacturer or by someone
authorized by the manufacturer. Improper repair can lead to a loss of the protec‐
tive function.
4.2
Operating entity of the machine
DANGER
Failure to observe operator obligations
Hazard due to lack of effectiveness of the protective device
b
Changes to the machine and changes to the mechanical mounting of the safety
relay necessitate a new risk assessment. The results of this risk assessment may
require the entity operating the machine to meet the obligations of a manufac‐
turer.
b
Apart from the procedures described in this document, the components of the
safety relay must not be opened or modified.
b
Do not carry out any repair work on components. Improper repair of the safety
relay can lead to a loss of the protective function.
4.3
Design
The safety relay must be installed in a control cabinet with an enclosure rating of IP54
or higher.
The safety relay must be installed on a mounting rail (35 mm) in accordance with IEC
60715.
Space requirements in the control cabinet
To ensure sufficient air circulation and cooling, sufficient distance must be kept in the
control cabinet above and below the safety relay.
Sufficient distance must be kept for the connected cables before the safety relay (front
side).
4 PROJECT PLANNING
12
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
Figure 3: Distances in control cabinet
Required distance:
•
Above and below the safety relay: ≥ 50 mm
•
In front of the safety relay: ≥ 25 mm
4.4
Electrical integration
Important information
DANGER
Hazard due to lack of effectiveness of the protective device
In the case of non-compliance, it is possible that the dangerous state of the machine
may not be stopped or not stopped in a timely manner.
b
Ensure the safety relay is supplied with supply voltage in all operating statuses.
b
Ensure that the supply voltage of the safety relay is not connected via safety sen‐
sors or safety switches in order to switch the enabling current paths.
4.4.1
Enabling current paths
DANGER
Hazard due to lack of effectiveness of the protective device
b
Ensure the enabling current paths are supplied by the same voltage supply.
4.4.2
Application diagnostic output
Application diagnostic output Y1
The signal of the Y1 application diagnostic output changes as soon as the enabling cur‐
rent paths switch. The application diagnostic output is not safe.
PROJECT PLANNING 4
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
13
Subject to change without notice
Table 2: Switching behavior of application diagnostic output Y1
State of enabling current paths
State of application diagnostic output Y1
Closed
0 V
Open
24 V
Application diagnostic output Y2
Application diagnostic output Y2 outputs the “Reset required” signal with a frequency of
1 Hz, e.g. for the connection of a signal lamp.
4.4.3
Restart interlock
Important information
DANGER
Hazard due to unexpected starting of the machine
Death or severe injury
If you connect the safety relay to an emergency stop pushbutton, you must use the
restart interlock.
Restart interlock
A reset pushbutton must be connected to allow the restart interlock to be used. The
reset pushbutton must be attached outside of the hazardous area. It must not be possi‐
ble to access the reset pushbutton from inside the hazardous area. The entire haz‐
ardous area must be highly visible for all operators from the reset pushbutton.
Further topics
•
"Device connection", page 20
4.4.4
External device monitoring (EDM)
External device monitoring (EDM)
With static external device monitoring, the safety relay tests whether the controlled
actuators (contactors) have dropped out when the device is switched on.
Further topics
•
"Device connection", page 20
4 PROJECT PLANNING
14
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
+24 V DC
0 V
k2
k1
Reset
F0
E210667/00/2018-11-15
State
RES
Figure 4: ReLy EMSS1 connection diagram, with restart interlock and external device monitoring
(EDM)
K2
K1
X1
Y1
Y2
24
X2
A2
14
I1
I2
S1
A1
R1
23
13
RLY3-EMSS1
F2
F1
L+
L–
+24 V DC
0 V
k2
k1
F0
E210668/00/2018-11-15
State
2
4
1
3
RE13
Figure 5: ReLy EMSS1 connection diagram, without restart interlock, with external device moni‐
toring (EDM)
4.5
Testing plan
The safety relay must be thoroughly checked by appropriately qualified safety personnel
during commissioning, after modifications, and at regular intervals, see "Thorough
check", page 23.
PROJECT PLANNING 4
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
15
Subject to change without notice
The regular thorough checks serve to assess the effectiveness of the safety relay and to
identify defects as a result of modifications or other influences (e.g., damage or manip‐
ulation).
The manufacturer and user must define the type and frequency of the thorough checks
on the machine on the basis of the application conditions and the risk assessment.
Determination of the thorough checks must be documented in a traceable manner.
4.5.1
Minimum requirements for the regular thorough check
The following thorough checks must be carried out at regular intervals:
•
Thorough check of the housing for damage
•
Thorough check of the cables for damage
•
Thorough check of the safety relay for signs of misuse or manipulation
•
Thorough check of the safety function
The minimum test interval depends on the applicable safety capability of the overall
application, see table 5, page 26.
4 PROJECT PLANNING
16
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
Hazard due to unexpected starting of the machine
Hazard due to electrical voltage
b
Make sure that the outputs of the safety relay have no effect on the machine dur‐
ing mounting and electrical installation.
b
Make sure that the safety relay and the connected components are isolated from
all voltage sources during mounting and electrical installation of the device and
during mounting/dismantling of the front connector.
NOTICE
Enclosure rating IP20 only applies if the front connector is mounted.
5.2
Mounting procedure
Prerequisites
•
Mounting is done in accordance with EN 50274 and electrical installation in
accordance with IEC 60204-1 in the control cabinet with enclosure rating IP54.
•
Mounting is done on a 35 mm mounting rail (IEC 60715).
•
The mounting rail is connected to the functional earth.
•
The safety relay is installed in a vertical orientation (on a horizontal mounting rail).
•
There is at least 50 mm of space for air circulation above and below the safety
relay.
•
There is at least 25 mm of space in front of the safety relay (front side). More
space may be needed depending on the connections.
Approach
Click
Figure 6: Mounting
b
Attach safety relay to mounting rail.
MOUNTING 5
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
17
Subject to change without notice
Figure 7: Disassembly
1.
Press the unlocking mechanism on the upper side of the safety relay towards the
back.
2.
Loosen safety relay from the mounting rail.
5.4
Device replacement
Overview
In event of a defect, exchange the device and reuse the front connector with the con‐
nected cables.
Approach
1.
Disconnect device and the connected components from all voltage sources.
2.
Take front connector with connected cables off the defective device: Press the
unlocking mechanism of the front connector downwards and pull out the front con‐
nector.
5 MOUNTING
18
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
Figure 8: Dismantling front connector
3.
Remove the defective device.
4.
Mount new device.
5.
Mount front connector with connected cables to the new device: First mount in the
device with bent hook and then engage in the housing.
Click
13
16
15
Figure 9: Mounting the front connector
✓
The front connector engages with an audible click.
MOUNTING 5
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
19
Subject to change without notice
Hazard due to lack of effectiveness of the protective device
In the case of non-compliance, it is possible that the dangerous state of the machine
may not be stopped or not stopped in a timely manner.
b
Ensure the safety relay is supplied with supply voltage in all operating statuses.
b
Ensure that the supply voltage of the safety relay is not connected via safety sen‐
sors or safety switches in order to switch the enabling current paths.
DANGER
Hazard due to unexpected starting of the machine
Hazard due to electrical voltage
b
Make sure that the outputs of the safety relay have no effect on the machine dur‐
ing mounting and electrical installation.
b
Make sure that the safety relay and the connected components are isolated from
all voltage sources during mounting and electrical installation of the device and
during mounting/dismantling of the front connector.
NOTICE
Enclosure rating IP20 only applies if the front connector is mounted.
Prerequisites
•
Electrical installation is done in conformity with IEC 60204-1.
•
The mounting rail is connected to the functional earth.
•
The voltage supply and connected signals meet the requirements for safety extra-
low voltage (EN 61140) or NEC Class 2 (UL 1310).
•
The external voltage supply must be capable of bridging a brief power failure of
20 ms as specified in IEC 60204-1. Suitable power supply units are available as
accessories from SICK.
•
The safety outputs and external device monitoring (EDM) must be wired within the
control cabinet.
•
When using the safety relay with voltages larger than the safety extra-low voltage:
The N/C contacts of the controlled contactors must be safely isolated from the
other contactor contacts.
•
Contact fuse with safety fuse gG or circuit breaker C: 6 A, maximum short-circuit
protection I ≤ 400 A.
•
The ground connection of all connected devices must have the same potential as
A2.
•
All connected devices and the reset pushbutton comply with the required category
in accordance with ISO 13849-1 and SILCL in accordance with IEC 62061 (e.g.
shielded single sheathed cables, separate installation).
6 ELECTRICAL INSTALLATION
20
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
Figure 10: Terminals on front connector
Table 3: Pin assignment of the terminals
Terminal
Description
13, 14 1) 2)
Enabling current path
23, 24 1) 2)
Enabling current path
I1 3)
Safety capable input
I2 3)
Safety capable input
S1 2) 4)
Reset pushbutton input, external device monitoring (EDM)
R1
Test pulse output
X1 3)
Test pulse output
X2 3)
Test pulse output
Y1
Application diagnostic output (NC)
Y2
Application diagnostic output (reset required)
A1
Voltage supply 24 V DC
A2
Voltage supply 0 V DC
1)
The enabling current paths must be supplied by the same voltage supply.
2)
The enabling current path and external device monitoring (EDM) must be wired within the control cabinet.
3)
Connect dual-channel switching elements of the safety sensors between X1 and I1 or X2 and I2.
4)
•
Use with restart interlock, with external device monitoring (EDM): Connect the N/C contacts of the
actuators between voltage supply Uv, the N/O contact of the reset pushbutton and S1.
•
Use with restart interlock, without external device monitoring (EDM): Connect the N/O contact of
the reset pushbutton between S1 and voltage supply UV.
•
Use without restart interlock, with external device monitoring (EDM): Connect the N/C contacts of
the actuators between R1 and S1.
•
Use without restart interlock, without external device monitoring (EDM): Connect R1 and S1 with a
wire jumper.
Complementary information
To protect and increase the service life of contact outputs, equip all connected loads
with varistors or RC elements. The response times will increase depending on the sup‐
pressor used.
ELECTRICAL INSTALLATION 6
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
21
Subject to change without notice
"Connection diagrams", page 15
6 ELECTRICAL INSTALLATION
22
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
Dangerous state of the machine
During commissioning, the machine or the protective device may not yet behave as you
have planned.
b
Make sure that there is no-one in the hazardous area during commissioning.
7.2
Thorough check
Requirements for the thorough check during commissioning and in certain situations
The device and its application must be thoroughly checked in the following situations:
•
Before commissioning
•
After changes to the configuration or the safety function
•
After changes to the mounting or the electrical installation
•
After exceptional events, such as after manipulation has been detected, after
modification of the machine, or after replacing components
The thorough check ensures the following:
•
All relevant regulations are complied with and the device is effective in all of the
machine’s operating modes.
•
The documentation accurately reflects the state/condition of the machine, includ‐
ing the protective device.
The thorough checks must be carried out by qualified safety personnel or specially qual‐
ified and authorized personnel, and must be documented in a traceable manner.
COMMISSIONING 7
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
23
Subject to change without notice
Hazard due to lack of effectiveness of the protective device
In the case of non-compliance, it is possible that the dangerous state of the machine
may not be stopped or not stopped in a timely manner.
b
Immediately shut the machine down if the behavior of the machine cannot be
clearly identified.
b
If a machine fault cannot be definitively determined or safely rectified, immediately
shut the machine down.
b
Secure the machine so that it cannot switch on unintentionally.
NOTE
Additional information on troubleshooting can be found at the responsible SICK sub‐
sidiary.
8.2
Status indicator (LED)
Table 4: Fault indicators and operational statuses
LED
Status
Possible cause
PWR
o
No supply voltage
All LEDs
Ö All colors
Initialization with LED test
PWR
O Green
No fault
PWR
Ö Red
• Supply voltage too low temporarily or per‐
manently
• Internal error
PWR
Ö Red/green
Error
Additional LEDs flash for accurate diagnosis.
OUT
o
Enabling current paths open
OUT
O Green
Enabling current paths closed
OUT
Ö Green
Error in enabling current path
S1
Ö Green
When using without restart interlock: Input
error (e.g. stuck at HIGH)
S1
O Green
Reset pushbutton actuated, N/C contact of the
actuator closed
I1 and I2
Ö Green, alternate
Input error: discrepancy time expired
I1 and I2
Ö Green, simultane‐
ous
Input error: cross-circuit, process error
Y1
o
Enabling current paths closed
Y1
O Green
Enabling current paths open
Y2
o
Output with LOW status
Y2
Ö Green
Reset required
Y2
O Green
Reset pushbutton actuated
8 TROUBLESHOOTING
24
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
Protecting the environment
The device has been designed to minimize its impact on the environment. It consumes
only a minimum of energy and natural resources.
b
Always act in an environmentally responsible manner at work. For this reason,
please note the following information regarding disposal.
Always dispose of serviceableness devices in compliance with local/national rules and
regulations with respect to waste disposal.
NOTE
We will be glad to help you dispose of these devices on request.
DECOMMISSIONING 9
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
25
Subject to change without notice
Table 5: Safety-related parameters
Desired safety integrity level (IEC 61508) 1)
SIL3
SIL2
SIL1
SIL claim limit
(IEC 62061)
SILCL3
SILCL2
SILCL1
Cate‐
gory (ISO 13849-1)
4
3
3
Performance level (ISO
13849-1)
PL e
PL d
PL c
Hardware error toler‐
ance
1
Maximum test interval
of the safety function
1 month
1 year
–
MTTFD (single chan‐
nel) (ISO 13849-1)
300 years
100 years
100 years
PFHD (mean probability of a dangerous failure per hour) 2)
For operating
heights ≤ 2,000 m
above sea level
1 × 10-9
1 × 10-8
1 × 10-7
For operating
heights 2,000...
4,000 m above sea
level
5 × 10-9
5 × 10-8
1 × 10-7
PFDavg (mean probability of a dangerous failure on demand) 2)
For operating
heights ≤ 2,000 m
above sea level
5 × 10-5
5 × 10-4
5 × 10-3
For operating
heights 2,000...
4,000 m above sea
level
2.5 × 10-4
2.5 × 10-3
5 × 10-3
TM (mission time)
20 years (ISO 13849-1)
Safe status when a
fault occurs
The normally open is open; in other words, the safety-related enabling
current paths are interrupted.
Stop category
0 (IEC 60204-1)
1)
The required safety integration level depends on your application.
2)
If service life curve is adhered to, see figure 12, page 30.
Table 6: Mechanical data
Weight
130 g
Mounting
Mounting rail (IEC 60715)
Connection type
Spring terminals
Stripping length
8 mm
Wire cross-section
Single wire (1×)
0.2 mm2 … 1.5 mm2
Fine wire (1×)
0.2 mm2 … 1.5 mm2
10 TECHNICAL DATA
26
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
Fine wire with ferrule with plastic collar (2×,
same cross-section)
≤ 0.5 mm2
Fine wire with ferrules with or without collar
(1×)
0.25 mm2 … 1.0 mm2
For UL and CSA applications
26 AWG … 14 AWG
(use only copper wire (60/75 °C))
Table 7: Electrical data - operating data
Supply voltage UV
24 V DC (16,8 V DC … 30 V DC) (safety extra-
low voltage) 1) 2)
Rated voltage
24 V DC
Residual ripple Uss
2.4 V
Power consumption
≤ 1.3 W
Power-up delay after supply voltage applied
≤ 5 s
1)
The external voltage supply must be capable of bridging a brief power failure of 20 ms as specified in
IEC 60204-1. Suitable power supply units are available as accessories from SICK.
Protect supply voltage against short-circuit.
2)
For use according to the requirements of ANSI/UL 508, ANSI/UL 60947-5-1 and ANSI/UL 60947-1, volt‐
age supply UV must be protected with 4 A.
Table 8: Electrical data - inputs (I1, I2, S1)
Input voltage HIGH
24 V DC (11 V DC … 30 V DC)
Input voltage LOW
0 V DC (–3 V DC … 5 V DC)
Input capacity
≤ 15 nF
Input current
4 mA … 6 mA
Reset time
Manual
≤ 250 ms
Automatic
≤ 250 ms
Actuation time of reset button
140 ms ... 30 s
Minimum power-up delay 1)
80 ms
Minimum switch-off time 2)
5 ms
Concurrence monitoring
≤ 3,000 ms
Length of cable (single)
≤ 100 m
1)
Time in which an input signal must have the HIGH status before the outputs switch.
2)
Time in which an input signal must have the LOW status before the outputs switch.
Table 9: Electrical data - test pulse outputs (X1, X2, R1)
Type of output
PNP semiconductor output, short-circuit pro‐
tected
Output voltage
(UV – 3 V) … UV
Test pulse interval
40 ms
Test pulse width
2 ms
Length of cable (single)
≤ 100 m
Cable resistance
≤ 10 Ω
Table 10: Electrical data - application diagnostic output (Y1, Y2)
Type of output
PNP semiconductor output, short-circuit pro‐
tected
TECHNICAL DATA 10
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
27
Subject to change without notice
(UV – 3 V) … UV
Output current
≤ 120 mA
Table 11: Electrical data - enabling current paths (13, 14, 23, 24)
Response time
Dual-channel switch-off with positive open‐
ing normally closed contacts
10 ms
Dual-channel switch off (without positive
opening, e.g. reed switch)
14 ms 1)
Minimum switch-off time 2)
100 ms
Number of enabling current paths (normally
open, safe)
2
Contact type
Positively guided
Contact material
Silver alloy, gold flash plated
Switching voltage
At altitudes up to 2,000 m above sea level
10 V DC … 250 V DC
10 V AC … 250 V AC
At altitudes 2,000 m above sea level …
4,000 m above sea level
10 V DC … 150 V DC
10 V AC … 150 V AC
Switching current
10 mA … 6 A, see figure 11, page 29, see
figure 12, page 30
Sum current:
≤ 12 A
Utilization category
AC-15: 230 V, 5 A (IEC 60947-5-1)
DC-13 (0.1 Hz): 24 V, 4 A (IEC 60947-5-1)
DC switching capacity
0.1 W … 200 W, see figure 11, page 29
AC switching capacity
0.1 VA … 1,500 VA
Switching frequency
≤ 1 Hz
Mechanical service life
10 × 106 Switching operations
Contact fuse with safety fuse gG or circuit
breaker C
6 A
Max. short-circuit protection
≤ 400 A
Rated insulation voltage
At altitudes up to 2,000 m above sea level
250 V AC
At altitudes up to 2,000 m above sea level …
4,000 m above sea level
150 V AC
Overvoltage category
III
Contamination degree
2
Rated impulse withstand voltage Uimp
6 kV
1)
Applies to devices with version ≥ V1.10.0 in the “HW” type label entry.
With devices with smaller version numbers or without the “HW” type label entry: Response time ≤ 12 ms;
response time with simultaneous dual-channel switch-off = 10 ms.
2)
Time the enabling current paths of the safety relay remain open before closing again.
Table 12: Ambient data
Enclosure rating
IP20 (IEC 60529)
Ambient operating temperature
At altitudes up to 2,000 m above sea level
(UL/CSA: surrounding air temperature)
–25 °C … +55 °C
10 TECHNICAL DATA
28
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
At altitudes 2,000 m above sea level …
3,000 m above sea level
–25 °C to 50 °C
At altitudes 3,000 m above sea level …
4,000 m above sea level
–25 °C … +45 °C
Storage temperature
–25 °C … +70 °C
Permissible operating height
≤ 4,000 m
Air humidity
10% … 95%, non-condensing for climatic con‐
ditions according to IEC 61131-2
Emitted interference
In accordance with IEC 61000-6-4
Immunity to interference
In accordance with IEC 61326-3-1
In accordance with IEC 61000-6-2
In accordance with IEC 60947-5-1
0,1
0,5
1,0
5,0
10
0
50
100
150
200
250
U (VDC) →
I (A) →
1
2
Figure 11: Switch-off delay without continuous arcing
1
Inductive load L/R 40 ms
2
Resistive load
TECHNICAL DATA 10
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
29
Subject to change without notice
DC 1: 24V
AC 1: 230V
AC 15: 230V
DC 13: 24V
Figure 12: Electrical service life
1
Switching operations × 1,000
2
Switching current (A)
10.2
Dimensional drawings
64,4
120,7
124,6
128,3
85,5
87,7
18
20,1
78,7
Figure 13: Dimensional drawing
10 TECHNICAL DATA
30
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
Figure 14: Internal circuitry
TECHNICAL DATA 10
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
31
Subject to change without notice
Ordering information for ReLy
Table 13: Ordering information
Part
Usage
Type code
Part number
ReLy EMSS1
Interlock safety switch
RLY3-EMSS1
1085345
11 ORDERING INFORMATION
32
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
Compliance with EU directives
EU declaration of conformity (extract)
The undersigned, representing the manufacturer, herewith declares that the product is
in conformity with the provisions of the following EU directive(s) (including all applicable
amendments), and that the standards and/or technical specifications stated in the EU
declaration of conformity have been used as a basis for this.
Complete EU declaration of conformity for download
You can call up the EU declaration of conformity and the current operating instructions
for the protective device by entering the part number in the search field at
www.sick.com (part number: see the type label entry in the “Ident. no.” field).
ANNEX 12
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
33
Subject to change without notice
List of figures
1.
Device overview.............................................................................................................9
2.
LEDs.............................................................................................................................10
3.
Distances in control cabinet...................................................................................... 13
4.
ReLy EMSS1 connection diagram, with restart interlock and external device moni‐
toring (EDM)................................................................................................................ 15
5.
ReLy EMSS1 connection diagram, without restart interlock, with external device
monitoring (EDM)........................................................................................................15
6.
Mounting..................................................................................................................... 17
7.
Disassembly................................................................................................................18
8.
Dismantling front connector...................................................................................... 19
9.
Mounting the front connector....................................................................................19
10.
Terminals on front connector.....................................................................................21
11.
Switch-off delay without continuous arcing...............................................................29
12.
Electrical service life...................................................................................................30
13.
Dimensional drawing..................................................................................................30
14.
Internal circuitry..........................................................................................................31
13 LIST OF FIGURES
34
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
8020868/ZX84/2018-11-15 | SICK
Subject to change without notice
List of tables
1.
Safety relay indicators................................................................................................ 10
2.
Switching behavior of application diagnostic output Y1.......................................... 14
3.
Pin assignment of the terminals................................................................................21
4.
Fault indicators and operational statuses................................................................ 24
5.
Safety-related parameters......................................................................................... 26
6.
Mechanical data......................................................................................................... 26
7.
Electrical data - operating data..................................................................................27
8.
Electrical data - inputs (I1, I2, S1).............................................................................27
9.
Electrical data - test pulse outputs (X1, X2, R1).......................................................27
10.
Electrical data - application diagnostic output (Y1, Y2)........................................... 27
11.
Electrical data - enabling current paths (13, 14, 23, 24)........................................ 28
12.
Ambient data...............................................................................................................28
13.
Ordering information.................................................................................................. 32
LIST OF TABLES 14
8020868/ZX84/2018-11-15 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy EMSS1
35
Subject to change without notice
Further locations at www.sick.com
Australia
Phone +61 (3) 9457 0600
1800 33 48 02 – tollfree
E-Mail [email protected]
Austria
Phone +43 (0) 2236 62288-0
E-Mail [email protected]
Belgium/Luxembourg
Phone +32 (0) 2 466 55 66
E-Mail [email protected]
Brazil
Phone +55 11 3215-4900
E-Mail [email protected]
Canada
Phone +1 905.771.1444
E-Mail [email protected]
Czech Republic
Phone +420 2 57 91 18 50
E-Mail [email protected]
Chile
Phone +56 (2) 2274 7430
E-Mail [email protected]
China
Phone +86 20 2882 3600
E-Mail [email protected]
Denmark
Phone +45 45 82 64 00
E-Mail [email protected]
Finland
Phone +358-9-25 15 800
E-Mail [email protected]
France
Phone +33 1 64 62 35 00
E-Mail [email protected]
Germany
Phone +49 (0) 2 11 53 01
E-Mail [email protected]
Hong Kong
Phone +852 2153 6300
E-Mail [email protected]
Hungary
Phone +36 1 371 2680
E-Mail [email protected]
India
Phone +91-22-6119 8900
E-Mail [email protected]
Israel
Phone +972-4-6881000
E-Mail [email protected]
Italy
Phone +39 02 27 43 41
E-Mail [email protected]
Japan
Phone +81 3 5309 2112
E-Mail [email protected]
Malaysia
Phone +603-8080 7425
E-Mail [email protected]
Mexico
Phone +52 (472) 748 9451
E-Mail [email protected]
Netherlands
Phone +31 (0) 30 229 25 44
E-Mail [email protected]
New Zealand
Phone +64 9 415 0459
0800 222 278 – tollfree
E-Mail [email protected]
Norway
Phone +47 67 81 50 00
E-Mail [email protected]
Poland
Phone +48 22 539 41 00
E-Mail [email protected]
Romania
Phone +40 356-17 11 20
E-Mail [email protected]
Russia
Phone +7 495 283 09 90
E-Mail [email protected]
Singapore
Phone +65 6744 3732
E-Mail [email protected]
Slovakia
Phone +421 482 901 201
E-Mail [email protected]
Slovenia
Phone +386 591 78849
E-Mail [email protected]
South Africa
Phone +27 (0)11 472 3733
E-Mail [email protected]
South Korea
Phone +82 2 786 6321
E-Mail [email protected]
Spain
Phone +34 93 480 31 00
E-Mail [email protected]
Sweden
Phone +46 10 110 10 00
E-Mail [email protected]
Switzerland
Phone +41 41 619 29 39
E-Mail [email protected]
Taiwan
Phone +886-2-2375-6288
E-Mail [email protected]
Thailand
Phone +66 2 645 0009
E-Mail [email protected]
Turkey
Phone +90 (216) 528 50 00
E-Mail [email protected]
United Arab Emirates
Phone +971 (0) 4 88 65 878
E-Mail [email protected]
United Kingdom
Phone +44 (0)17278 31121
E-Mail [email protected]
USA
Phone +1 800.325.7425
E-Mail [email protected]
Vietnam
Phone +65 6744 3732
E-Mail [email protected]