VIPA TP 610C CAN Manual
Text of the manual
Order no.: VIPA HB160E_TP
Reference: RE_610-3B2J0
Rev. 09/09
This manual is part of the documentation package
with order number VIPA HB160E_TP and relevant for:
Product
Order number
as of state:
HW
OS
TP 610C CAN
VIPA 610-3B2J0
01
Windows® CE V. 5.0
Manual VIPA HMI
Subject to change to cater for technical progress.
The information in this manual is supplied without warranties. Information is
subject to change without notice.
© Copyright 2009 VIPA, Gesellschaft für Visualisierung und Prozess-
automatisierung mbH
Ohmstraße 4, D-91074 Herzogenaurach,
Tel.: +49 (91 32) 744 -0
Fax.: +49 (91 32) 744-1864
Email: [email protected]
http://www.vipa.de
Hotline:
+49 (91 32) 744-1150
All rights reserved.
The content of this manual was carefully examined to ensure that it
conforms with the described hardware and software.
However, discrepancies can not be avoided. The specifications in this
manual are examined regularly and corrections will be included in
subsequent editions.
We gratefully accept suggestions for improvement.
VIPA
is a registered trademark of VIPA Gesellschaft
für Visualisierung und Prozessautomatisierung mbH.
Microsoft, Windows and Windows Logo are either registered trademarks or
trademarks of Microsoft Cooperation in the USA and/or other countries.
Any other trademarks referred to in the text are the trademarks of the
respective owner and we acknowledge their registration.
Disclaimer of
liability
Trademarks
About this manual
Manual VIPA HMI
Subject to change to cater for technical progress.
About this Manual
The manual describes the Touch Panel TP 610C CAN from VIPA. Here
you find detailed descriptions of the Touch Panel beside a product
overview. Here you get information about structure, project engineering
and operation of the Touch panels from VIPA.
Chapter 1:
Hardware description
During this chapter you get hints for deployment of the Touch Panel
TP 610C CAN from VIPA.
Besides of a description of the single components of the Touch Panel, you
will also find the dimensions that are required for the installation. The
chapter closes with the technical data.
Chapter 2:
Deployment Touch Panel
This chapter deals with the employment of the Touch Panel.
At the start of the chapter you receive information about the assembly and
the connection of the Touch Panel. The main part of the chapter introduces
Windows® CE and the various communication options offered by the Touch
Panel.
Chapter 3:
Installation guidelines
This chapter helps you to install an interference-free automation system.
First, possible interference sources and their interaction mechanisms are
shown, followed by basic rules for guaranteeing EMC. Afterwards you'll find
information about assembly and cabling following EMC rules.
Overview
Manual VIPA HMI
Contents
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
i
Contents
User considerations................................................................................. 1
Safety information.................................................................................... 2
Chapter 1
Hardware description ..................................................... 1-1
Safety information for Users................................................................. 1-2
Properties............................................................................................. 1-3
Structure .............................................................................................. 1-4
Components......................................................................................... 1-6
Dimensions ........................................................................................ 1-10
Technical Data ................................................................................... 1-11
Chapter 2
Deployment Touch Panel ............................................... 2-1
Installation............................................................................................ 2-2
Commissioning..................................................................................... 2-4
Connection to a PLC system................................................................ 2-6
Operating system Windows® CE.......................................................... 2-7
Communication via ActiveSync .......................................................... 2-12
Integrated Server ............................................................................... 2-15
Access to the network resources........................................................ 2-22
Integration to WLAN network ............................................................. 2-24
Firmware update ................................................................................ 2-26
Chapter 3
Installation Guidelines.................................................... 3-1
Basic rules for the EMC-equitable assembly of installations................. 3-2
EMC-equitable assembly...................................................................... 3-6
EMC-equitable cabling ......................................................................... 3-7
Special precautions providing high noise immunity ............................ 3-11
Checklist for the EMC-compliant installation of controllers ................. 3-12
Appendix
..........................................................................................A-1
Index ....................................................................................................A-1
Manual VIPA HMI
User considerations
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
1
User considerations
This manual describes the Touch Panels from VIPA. The manual consists
of chapters. Every chapter provides the description of one specific topic.
It describes the installation, project engineering, usage and the technical
data.
This Documentation is targeted at users who have a background in
automation technology and profound knowledge about Windows® operating
systems.
This manual provides the following guides:
• An overall table of contents at the beginning of the manual
• An overview of the topics for every chapter
• An index at the end of the manual.
The manual is available in:
• printed form, on paper
• in electronic form as PDF-file (Adobe Acrobat Reader)
[Button]
Buttons are put in brackets e.g. [NEXT] or [OK].
[Key]
Key entry are put in brackets e.g. [STRG]+[A].
Display
output
Display outputs are illustrated as Courier e.g.
\flashdisk>
Keyboard
entry
Keyboard entries are illustrated as Courier bold e.g.
\flashdisk> Dir
Terms
Menues, Display elements, terms are italicised.
Important passages in the text are highlighted by following icons and
headings:
Danger!
Immediate or likely danger.
Personal injury is possible.
Attention!
Damages to property is likely if these warnings are not heeded.
Note!
Supplementary information and useful tips.
Objective and
contents
Guide to the
document
Availability
Description
conventions
Icons
Headings
Manual VIPA HMI
2
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Safety information
The Operation devices are constructed and manufactured for:
• VIPA CPUs 11x, 21x, 31x, 51x and S7-300/400 from Siemens
• communication and process control
• industrial applications
• operation within the environmental conditions specified in the technical
data
Danger!
This device is not certified for applications in
• explosive environments (EX-zone)
The manual must be available to all personnel in the
• project design department
• installation department
• commissioning
• operation
The following conditions must be met before using or commissioning
the components described in this manual:
• Modification to the process control system should only be carried out
when the system has been disconnected from power!
• Installation and modifications only by properly trained personnel
• The national rules and regulations of the respective country must be
satisfied (installation, safety, EMC ...)
National rules and regulations apply to the disposal of the unit!
Application
specifications
Documentation
Disposal
Manual VIPA HMI
Chapter 1 Hardware description
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
1-1
Chapter 1
Hardware description
During this chapter you get hints for deployment of the Touch Panel
TP 610C CAN from VIPA.
Besides of a description of the single components of the Touch Panel, you
will also find the dimensions that are required for the installation. The
chapter closes with the technical data.
Topic
Page
Chapter 1
Hardware description ..................................................... 1-1
Safety information for Users................................................................. 1-2
Properties............................................................................................. 1-3
Structure .............................................................................................. 1-4
Components......................................................................................... 1-6
Dimensions ........................................................................................ 1-10
Technical Data ................................................................................... 1-11
Overview
Content
Chapter 1 Hardware description
Manual VIPA HMI
1-2
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Safety information for Users
VIPA modules make use of highly integrated components in MOS-
technology. These components are extremely sensitive to over-voltages
that can occur during electrostatic discharges.
The following symbol is attached to modules that can be destroyed by
electrostatic discharges:
The symbol is located on the module, the module rack or on packing
material and it indicates the presence of electrostatic sensitive equipment.
It is possible that electrostatic sensitive equipment is destroyed by energies
and voltages that are far less than the human threshold of perception.
These voltages can occur where persons do not discharge themselves
before handling electrostatic sensitive modules and they can damage
components thereby, causing the module to become inoperable or
unusable. Modules that have been damaged by electrostatic discharges
may fail after a temperature change, mechanical shock or changes in the
electrical load.
Only the consequent implementation of protection devices and meticulous
attention to the applicable rules and regulations for handling the respective
equipment can prevent failures of electrostatic sensitive modules.
Modules have to be shipped in the original packing material.
When you are conducting measurements on electrostatic sensitive
modules you should take the following precautions:
• Floating instruments must be discharged before use.
• Instruments must be grounded.
Modifying electrostatic sensitive modules you should only use soldering
irons with grounded tips.
Attention!
Personnel and instruments should be grounded when working on
electrostatic sensitive modules.
Handling of
electrostatic
sensitive modules
Shipping of
electrostatic
sensitive modules
Measurements
and alterations on
electrostatic
sensitive modules
Manual VIPA HMI
Chapter 1 Hardware description
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
1-3
Properties
The Touch Panel allows you to visualize and alter operating states and
recent process values of a connected PLC.
The VIPA Touch Panel is a compact and modular embedded PC based on
Windows® CE. Besides of the extensive Windows® CE functions the Touch
Panel offers varied communication possibilities. Here the Touch Panel can
simply be configured, controlled and remoted. By including a selectable
HMI/SCADA runtime the Touch Panel is particularly suitable for monitoring
and controlling of process cycles.
• Microsoft Windows® CE V. 5.0 (full version as option)
• Different HMI/SCADA-Runtime selectable
• 800MHz pulse frequency
• Work memory 128Mbyte
about 1800Mbyte memory for user data on Board
• CF-Card II and MMC/SD card slot
• Horizontal and vertical display selectable in 90° steps
• RS232, RS485, RS422, CAN, Ethernet,
USB-A and USB-B interfaces on board
• Robust aluminium die casting case
• Display resolution 800 x 600 / 600 x 800 (64k colors)
• Battery backed clock
• Resistive touch screen
• Eeasy mounting via integrated pivoted lever
• Protection class IP65 (frontal)
Type
Order number
Description
TP 610C CAN
VIPA 610-3B2J0
10.4" SVGA TFT color, CAN interface, RS232,
RS422/485, 2xUSB-A, USB-B, 2xEthernet RJ 45 (switch)
General
TP 610C CAN
610-3B2J0
Order data
Chapter 1 Hardware description
Manual VIPA HMI
1-4
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Structure
[1]
Slot for storage medium
(CF, SD/MMC)
[2]
Connection for interfaces and
power supply
Touch P anel
1
2
3
[3]
Display with touch sensitive area
(touch screen)
[1]
Compact Flash
[2]
MMC / SD
1
2
Note!
Please regard that the Touch Panel always has to be supplied with external
voltage!
Front view
Side view
Manual VIPA HMI
Chapter 1 Hardware description
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
1-5
1
2
3
4
5
6
7
8
9
[1]
RS422/485 interface COM 2
[2]
RS232 interface COM 1
[3]
CAN interface
[4]
2x "Host"-USB-A interface
[5]
"Slave"-USB-B interface
[6], [7]
RJ45 jack for Ethernet Communication (switch)
[8]
Slot for DC 24V voltage supply
[9]
Slot for CF/SD/MMC storage medium
Bottom view
(Interfaces)
TP 610C CAN
10.4''
610-3B2J0
Components
Chapter 1 Hardware description
Manual VIPA HMI
1-6
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Components
The following memory systems are available for every Touch Panel:
• 128Mbyte work memory
• 1Gbyte Flash-Disk (ca. 1800Mbyte for user data)
• USB storage media using "Host"-USB-A interface
• Slot for CF (Type II)
• Slot for MMC/SD
Every Touch Panel has a work memory with a size of 128Mbyte. The work
memory is not buffered and is deleted after shut down. Please regard that
also registry entries are stored in the work memory that are set back to
default settings after the next re-boot. You may save them permanently by
means of the KuK Tools (within consignment).
As internal permanent storage medium every Touch Panel has a flash disc
with a size of 1Gbyte (about 1800Mbyte user data). After the start of
Windows® CE this memory is listed as Flashdisk at My Device.
The connection of USB sticks and USB drives by use of the "Host"-USB-A
interface is supported by the Touch Panel. After connection the storage
media is listed as Hard Disk at My Device.
Slot for CF
Here you may plug a CompactFlash type II. The card may be plugged
and removed during runtime and is immediately listed as Storage Card at
My Device.
Every CompactFlash storage module has a pulling edge. Hold the
CompactFlash in the way that the pulling edge points to the left side. Push
the storage module without much power into the slot until the impact. To
remove the card touch it at the pulling edge and pull.
At this slot you may plug storage modules of the type SD or MMC. The
card may be plugged and removed during runtime and is immediately listed
as SDMMC Card at My Device.
Please take care to plug the according card as shown at the backside of
the Touch Panel.
Security flap for
memory cards
At the left side of the Touch Panel are the card slots for memory cards.
The cards are visibly covered by a security flap and are thus secured from
slipping out.
Please take care to pull the security flap back before plugging or pulling a
memory card like shown in the illustration and put it back again afterwards.
When plugging, the security flap additionally snaps into position above the
plugged memory card.
Memory
management
Work memory
Flash disc
USB storage media
Slot for SD/MMC
Manual VIPA HMI
Chapter 1 Hardware description
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
1-7
• Logical states represented by voltage differences between the 4 cores
• Serial bus connection in 4-wire technology using full duplex mode
• Data communications up to a max. distance of 500m
• Data communication rate up to 115.2kBaud
9pin jack
Connection RS422 (isolated)
Pin
RS422/485
1
n.c.
2
n.c.
3
TxD+ (Line A)
4
RxD+ (Line A)
5
M5V
6
P5V
7
n.c.
8
TxD- (Line B)
5
4
3
2
1
9
8
7
6
9
RxD- (Line B)
TxD+ (A)
TxD- (B)
RxD+ (A)
RxD- (B)
Shield
RS422
Periphery
3
8
4
9
M5V
TxD+
TxD-
RxD+
RxD-
P5V
5
6
• Serial bus connection in 2-wire technology using half duplex mode
Connection RS485 (isolated)
TxD+ (A)
TxD- (B)
RxD+ (A)
RxD- (B)
Shield
RS485
Periphery
3
8
4
9
M5V
RxD+/TxD+
RxD-/TxD-
P5V
5
6
Periphery
RxD+/TxD+
RxD-/TxD-
9pin jack
Connection CAN
Pin Assignment
1 reserved
2 CAN low
3 CAN Ground
4 reserved
5 Shield
6 reserved
7 CAN high
8 reserved
5
4
3
2
1
9
8
7
6
9 reserved
Master
Slave
CAN high
CAN Ground
Shield
Shield
CAN low
CAN Ground
CAN high
Shield
120Ω
7
2
3
120Ω
CAN low
RS422/485
interface
Connection
RS422/485
CAN interface
Chapter 1 Hardware description
Manual VIPA HMI
1-8
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
• Interface is compatible to the COM interface of a PC
• Logical signals as voltage levels
• Point-to-point links with serial full-duplex transfer in two-wire technology
up to 15m distance
• Data transfer rate up to 115.2kBaud
9pin plug
Connection RS232
Pin
RS232
1
CD
2
RxD
3
TxD
4
DTR
5
GND
6
DSR
7
RTS
8
CTS
1
2
3
4
5
6
7
8
9
9
RI
RxD
TxD
GND
TxD
RxD
3
2
GND
5
RTS
CTS
7
8
Shield
RS232
Periphery
Shield
An RJ45 jack provides the interface to the twisted pair cable, required for
Ethernet. The pin assignment of this jack is as follows:
8pin RJ45 jack:
Pin
Signal
1
Transmit +
2
Transmit -
3
Receive +
4
-
5
-
6
Receive -
7
-
8
-
RS232 interface
Connection RS232
Ethernet
connection
1
2
3
4
5
6
7
8
Manual VIPA HMI
Chapter 1 Hardware description
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
1-9
Using the "Host"-USB-A interface mouse, keyboard, USB stick ore USB
hard discs can be connected.
The pin assignment is as follows:
"Host"-USB-A:
Pin
Assignment
1
VCC
2
DM
3
DP
1
2
3
4
4
GND
For project transfer with Microsoft ActiveSync a programming cable can be
connected using the "Slave"-USB-B interface.
The pin assignment is as follows:
"Slave"-USB-B:
Pin
Assignment
1
VCC
2
DM
3
DP
2
1
3
4
4
GND
The USB-A interface of your PC can be connected to the "Slave"-USB-B
interface of your Touch Panel deploying the USB programming cable.
The USB programming cable is delivered by VIPA with order No.
VIPA 670-0KB10.
The Touch Panel has got an integrated power supply. The power supply
has to be provided with DC 24V (20.4 ... 28.8V). For this you find an
according DC 24V slot at the bottom side.
DC 24V
The power supply is protected against inverse polarity and overcurrent.
"Host"-USB-A
"Slave"-USB-B
VIPA USB-B
Programming cable
Power supply
Chapter 1 Hardware description
Manual VIPA HMI
1-10
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Dimensions
installation width
installation hight
installation
depth
width
height
For the installation of the Touch Panel in control cabinets and desks the
following dimensions are necessary:
Front panel width
1.5 ... 6mm
Installation cutting (W x H)
287 x 217mm
Front panel (W x H)
304 x 233mm
Back side (W x H x D)
285 x 215 x 45mm
Installation depth
45mm
Note!
The degrees of protection are only guaranteed when the following is
observed:
• Material thickness at the mounting cut-out: 1.5 ... 6mm
• the deviation from the plane for the panel cut-out is ≤0.5mm. This
condition must be fulfilled for the mounted HMI device
• Permissible surface roughness in the area of the seal: ≤120µm
(friction coefficient 120)
Installation
dimensions
10.4''
610-3B2J0
Manual VIPA HMI
Chapter 1 Hardware description
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
1-11
Technical Data
TP 610C CAN
Electrical data
VIPA 610-3B2J0
Nominal supply voltage
DC 24V (20.4 ... 28.8V)
ESD/Burst
Acc. IEC 61000-4-2 / IEC 61000-4-4 (up to level 3)
Shock resistance
Acc. IEC 60068-2-6 / IEC 60068-2-27 (1G/12G)
Level of noise suppression
Acc. IEC 61000-6-4
mark of conformity and certification
CE
Clock and housing
Processor
Xscale 800MHz
Clock
Hardware clock, buffered
Housing - protection class
Solid aluminium case
- Front
IP 65
- Back
IP 20
Environment conditions
Mounting position
horizontally/vertically
Operating temperature
0 ... +50°C
Relative humidity max.
85%
Storing / Transport temperature
-20 to +60°C
Display
Size
10.4"
Resolution
600 x 800 / 800 x 600
Colors
TFT color (64K colors)
MTBF Backlights (25°C)
ca. 50000h
Peripherals
Touch screen
resistive
external Mouse, Keyboard
USB
Memory
Type
1GB Flash / 128Mbyte RAM
Available memory for user data
ca. 1800Mbyte
CF Card Slot Type II
yes
SD/MMC Push-Push-Slot
yes
Interfaces
CAN
yes
serial
RS232 COM 1
serial
RS422/485 isoliert COM 2
USB
2xUSB-A, 1xUSB-B
Ethernet
2x10/100 RJ45 (switch)
Electrical Data
Nominal supply voltage
DC 24V (20.4 ... 28.8V)
Nominal current
0.7A
Box
Fixing
via 9 integrated pivoted lever
Dimensions and weight
Front (WxH)
304 x 233mm
Back (WxHxD)
285 x 215 x 45mm
Integration cut-out (WxH)
287 x 217mm (Front panel width: 1.5 ... 6mm)
Weight
1.8kg
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-1
Chapter 2
Deployment Touch Panel
This chapter deals with the employment of the Touch Panel.
At the start of the chapter you receive information about the assembly and
the connection of the Touch Panel. The main part of the chapter introduces
Windows® CE and the various communication options offered by the Touch
Panel.
Topic
Page
Chapter 2
Deployment Touch Panel ............................................... 2-1
Installation............................................................................................ 2-2
Commissioning..................................................................................... 2-4
Connection to a PLC system................................................................ 2-6
Operating system Windows® CE.......................................................... 2-7
Communication via ActiveSync .......................................................... 2-12
Integrated Server ............................................................................... 2-15
Access to the network resources........................................................ 2-22
Integration to WLAN network ............................................................. 2-24
Firmware update ................................................................................ 2-26
Overview
Content
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-2
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Installation
The Touch Panel is suitable for the installation in operating tables and
control cabinet fronts. The installation happens via the backside. The
Touch Panel is provided with a patented integrated fixing technique that
allows an easy connection with a simple screwdriver.
Due to the fact that the Touch Panel has a plug connector for bus
connection and voltage supply, a fast and easy device change is possible.
For the installation into a operating tableau and control cabinet fronts, the
Touch Panel requires the following front plate cutting:
W
H
Touch Panel
W x H in mm
610-3B2J0
287 x 217
The fixing technique is integrated in the casing of the Touch Panel and
accessible via the backside.
For the installation, a small slit screwdriver is required. Push the operator
panel [3] from the front side into the front panel cutting [1] until it touches
the panel with the seal [2]. Now bolt the lever [5] clockwise with the
screwdriver [4] until it rotates to the outside. Further screwing bolts the
lever to the front panel until it holds this to the control cabinet front.
1
2
3
4
5
Overview
Installation cutting
Installation
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-3
For the cabling of the DC 24V power supply green plugs with CageClamp
technology are deployed. The spring-clip connector technology simplifies
the wiring requirements for signaling and power cables. In contrast to
screw terminal connections, spring-clip wiring is vibration proof.
Here also you may connect wires with a cross-section of 0.08mm2 to
2.5mm2. You can use flexible wires without end case as well as stiff wires.
You fix the conductors to the CageClamps like this:
DC 24V
1
2
3
[1]
Round opening for wires
[2]
Locking (orange) for screwdriver
[3]
Test point for 2mm test tip
1
2
3
The picture on the left side shows the cabling step by step from top view.
• For cabling you push the locking vertical to the inside with a suiting
screwdriver and hold the screwdriver in this position.
• Insert the insulation-striped wire into the round opening. You may use
wires with a cross-section from 0.08mm2 to 2.5mm2.
• By removing the screwdriver the wire is connected safely with the plug
connector via a spring.
Connect
power supply
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-4
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Commissioning
Attention!
• Before commissioning the device must be brought to room temperature.
• At condensation the device must be absolutely dry before connected to
power.
• To avoid overheat during operation the device must not be laid open to
direct sun light.
• After opening the control cabinet or desk, there are parts with possible
dangerous voltage available.
• For all signal connections only screened cables are permitted.
• Signal cables must not be let within the same cable shaft as high
voltage cables.
As soon as the Touch Panel is provided by power supply the Touch Panel
starts with the VIPA Startup Manager:
The VIPA Startup Manager has the following buttons:
A project is started within the VIPA Startup Manager after a configured time
was passed. The project may be started immediately by means of [Start].
Depending on the installed visualization software the project to be started
may either be selected with [Select] or within the editor of the visualization
software. For an automatically start of the project the project may once be
started manually by [Start] if necessary.
The VIPA Startup Manager is closed by [Exit] and it is returned to
Windows® CE.
With [Backup] the files of the Flashdisk and the Registry settings may be
stored.
The backed up files may be restored by [Restore].
VIPA Startup
Manager
Start
Select
Exit
Backup
Restore
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-5
The settings of the VIPA Startup Manager are stored in the file
StartupMngr.dat. This file may be found on the Touch Panel at My Device
> Flashdisk.
Within this file the settings of the VIPA Startup Manager may be changed
by parameters.
Note!
This file is hidden as default. To make this file visible within Windows® CE
every option of My Device > View > Options is to be deactivated.
Depending on the installed visualization software the following parameters
are used:
Parameter
Meaning
VISUALISATION
Indicates which visualization software is used.
LOCATION
Indicates the file location of the visualization software.
FILE
Path and file name of the last started project.
FONT
Indicates the storage location of additional fonts to be registered.
PASSWORD
Here a password may be entered. Before returning to Windows® CE
you are asked for this password.
BACKROUND
Path and file name of the background picture.
AUTOLAUNCHDELAY
Here a delay time in seconds may be set. If this time is passed the
preset project is started automatically.
Please consider this during setting parameters:
Parameter and value is always be connected by "=". Blanks are not
allowed. For the parameter names capitals are to be used.
The whole path is to be used when entering a file location e.g.
BACKGROUND=\flashdisk\background.jpg
Settings
Parameter of
StartupMngr.dat
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-6
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Connection to a PLC system
For the inclusion into your PLC system several HMI/SCADA project-
engineering platforms are at your disposal that has to be installed at an
external PC. Here you may create your project, where appropriate simulate
it and transfer it to the Touch Panel via a connection that you’ve entered
before. Via the at the Touch Panel pre-installed runtime version of the
HMI/SCADA project engineering platforms your project is run able.
By using the according communication driver, the Touch Panel supports
connecting options to the PLC via field bus and Ethernet.
During the operation your operating device communicates with the
according PLC and reacts to the application courses in the PLC according
to the configured processes. Via dialogs configured before, process values
may be monitored graphically, altered and evaluated.
HMI/
SCADA
Fieldbus,
Ethernet
Touch Panel
MS ActiveSync, ftp, http, Telnet, VNC
MMC/SD/CF
PC
...
CPU
SPS
CPU
SPS
...
Touch Panel
HMI/SCADA
Runtime
- ftp-Server
- http-Server
- Telnet
- VNC
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-7
Operating system Windows® CE
Within the consignment of the Touch Panel is the operating system
Microsoft Windows® CE V. 5.0. It is an OEM licensed English version. The
newly developed standard Windows® CE allows devices that are
communicating with each other to exchange information with Windows®
based devices and to establish connections to the Internet.
Microsoft Windows® CE is a 32bit, open and scalable platform for a
multiplicity of communication and data processing devices. The functions
like multi-tasking and multi-threading are supported by this operating
system.
As default Microsoft Windows® CE Core 5.0 is delivered and optionally
Microsoft Windows® CE Professional Plus 5.0. The version may be found
at a label at the backside of your Touch Panel.
This version is a Windows® operating system reduced to the absolute
essentials with mouse operation (touch screen) that requires only small
hardware resources. Here the 2 icons "My Device" and "Recycle Bin" may
exclusively be found at the Desktop.
The Professional-Plus version is an enhanced Core version. Here among
others some file viewer, an Internet browser and bluetooth support are
integrated. On the desktop besides many icons a mouse pointer is
displayed at the pen position. As soon as the pen is hold at one position
the context menu is displayed.
Features Windows® CE
Core 5.0
Professional
Plus 5.0
ftp, http, Telnet and VNC server
x
x
RAS server
-
x
ActiveSync file transfer
(USB, RS232, Ethernet)
x
x
RDP (Remote Desktop Protocol)
-
x
Internet Explorer 6
-
x
Registry Editor
x
x
WordPad
-
x
Mouse pointer
-
x
USB keyboard driver
x
x
HP printer driver
(COM, Ethernet, USB)
x
x
Bluetooth USB stick support
(Keyboard, mouse, modem, network)
-
x
WLAN Support (SD Card, USB-Stick)
x
x
File viewer for Word, Excel,
PowerPoint and PDF
-
x
VIPA Startup Manager
x
x
Windows® CE
Windows® CE
Core 5.0
Windows® CE
Professional Plus 5.0
Differences Core- and
Professional-Plus
version
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-8
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Please regard that for the deployment of Windows® CE a thorough
knowledge of operating Windows® are assumed. Here are only shown the
differences to a "standard" Windows® operating system.
You’re operating the Touch Panel by means of a pencil res. with the finger.
When touching an area at the touch screen this area is recognized and the
program reacts accordingly. The following types of entry are differentiated:
Double click
A double click has to be executed like mouse operation by touching the
area at the screen twice. A double click on an object open res. executes
this.
Drag
By tapping on an object and then dragging you may move the object on the
screen. If no object is selected, a frame is created by the dragging that
selects the touched objects.
Characteristics with Windows® CE Professional Plus V. 5.0
In the Professional Plus version mouse functions are fully supported. As
soon as the touch screen is touched with the pen, a mouse pointer is
shown on the desktop at the pen position.
To show the context menu you can either press the right key of your
mouse connected by USB or hold the pen on one position.
The windows may be moved via the head bar. Here you may also find the
[OK] button to confirm entries and the [X] button for exiting the dialog.
You may not exit Windows®. By switching the power supply off and on
again you may restart Windows®. Before a reboot you should always save
your data res. close all running applications to avoid data loss.
Note!
Please regard that made changes are set back after PowerOFF-PowerON
and are only stored via Save Registry which is to be found at
Start > Programs > KuK Tools.
Differences to the
standard Windows®
operation
Pen entry
Navigation within
the dialog window
Exit Windows®
(shut down)
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-9
1
2
3
1
Icon
Via icons on the desktop you gain direct access to the application related to
the icon.
2
Desktop
The desktop is the screen that is shown after login at Windows® CE. It
contains e.g. links to the mostly used applications res. system components.
3
Task bar
The task bar is part of the desktop. When opening an application, a
document or a window, every running object is displayed as button on the
task bar. Via this buttons you may easily change between the open
windows.
Basically the task bar has the following structure:
3
4
5
6
7
8
1
2
1
Start button
This button offers you access to all components of your Touch Panel like
e.g. applications, system settings, file browser etc.
2
Open
applications
For every open application a button is to be found in the task bar. There is
no button for minimizing. The switch between the applications happens via
this buttons.
3
Network
connection
As soon as your Touch Panel is connected via Ethernet you may here
display the Ethernet address.
If there is no connection via Ethernet, the symbol is displayed crossed out.
4
Desktop
direction
This symbol allows you to switch between 2 desktop directions. The position
setting happens in steps of 90° and can be set via double click in a dialog
window.
5
Keyboard
layout
If you’ve connected a keyboard you may choose the wanted language
layout via this button.
6
Time
This area shows the time that you may change via double click.
7
Show desktop All windows are minimized and the desktop is shown.
8
Software
keyboard
This button displays a keyboard at the screen. "Hide Input Panel" hides the
keyboard again.
Structure
Task bar
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-10
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
The button
allows you to select one of the available software
keyboards. At the moment the following standard keyboards are
implemented:
Normal:
At pushed SHIFT key:
At pushed [a´ü] key:
Note!
Please regard that the umlauts äöü may exclusively entered via the
software keyboard Keyboard.
Normal:
At pushed SHIFT key:
Meaning:
Home Position 1
End End
BS Backspace
up ↑
dn ↓
lt ←
rt →
pgup Page ↑
pgdn Page ↓
ins Insert
del Delete
Tab Tabulator
Shift
Caps/Lock
The software keyboard allows you to enter key entries without connecting
an external keyboard. As soon as an entry is required the software
keyboard is automatically shown.
Hide Input Panel hides the keyboard again.
Software keyboard
Software keyboard
Keyboard
Software keyboard
Large KB
Hide keyboard
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-11
Due to the fact that many components of the Control Panel are concurring
with the system control of Windows®, most of the description is here
dispensed. The description of the control panel components relevant for
operating the Touch Panel is to be found in the following:
Set display
Via Start > Settings > Control Panel > Display the dialog windows for the
display properties opens. Here you may change the settings for the monitor
options.
For example you may adjust the brightness and contrast via the register
Settings.
Calibrate touch screen
If your touch screen does not always react on a double click or recognizes
the position of an entry not precisely, you may call the dialog Stylus via
Start > Settings > Control Panel.
In the register Double-Tap you may use the grid pattern to preset a double
click velocity and test this on the symbol below. OK takes over the set
value. The calibration of the touch screens happens via the register
Calibration by following the instructions.
Set Ethernet parameters
The dialog field for pre-setting an Ethernet address is to be found at
Start > Settings > Network and Dial-up Connections.
The default setting is address assignment via DHCP.
System properties (System)
Here you receive information about the version of the current Windows®
operating system, the memory load and sharing (alterations here are not
taken over into the registry) and about the copyright.
The register Device Name allows you to change the device name that is
e.g. shown during Ethernet communication.
Note!
All alterations made here are cleared after PowerOFF-PowerON. To store
them permanently into the registry file you have to store them explicitly. For
this, call “Save Registry” at Start > Programs > KuK Tools. Use [OK] to
store the data in the registry file.
System setting
(Control Panel)
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-12
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Communication via ActiveSync
ActiveSync is a communication platform developed by Microsoft especially
for mobile computers to synchronize data between a mobile device and a
PC via USB res. Ethernet. Many developer tools res. SCADA project-
engineering tools use ActiveSync for the data transfer.
Before you may access the Touch Panel from the PC via ActiveSync you
have to install it at the PC.
ActiveSync is freeware and may be downloaded from www.microsoft.de.
• Download the ActiveSync from the Microsoft website and start the file
MSASYNC.EXE.
The following dialog window appears:
• Start the installation with [Next].
• Choose an installation directory and click on [Next].
→ ActiveSync is installed.
After the installation the dialog window "establish connection" is opened. If
your Touch Panel shall be available via Ethernet you have to install a point-
to-point connection first.
• Start the search run with [Next]:
Overview
Installation
Establish
connection
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-13
Now you may install a "partnership" via an USB connection with the
following approach:
• Connect your Touch Panel via the "Device"-USB-B jack with your PC
and turn on the Touch Panel. → The USB device (Touch Panel) is
recognized and the dialog window "new partnership" opens.
• Choose "yes" that you want to fix a partnership and push [Next].
• In the now opening window, de-activate all synchronization settings and
click on [Next]:
• [Finish] establishes the partnership.
Now you may access the Touch Panel with ActiveSync via USB.
Note!
To keep the settings also after power on, you have to store them to the
registry with START > Programs > KuK Tools > Save Registry.
Install partnership
for USB communi-
cation
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-14
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Please regard, Ethernet communication is only supported by ActiveSync up
to Version 3.8.
If your Touch Panel shall be available via Ethernet you have to install a
partnership for USB communication first like shown above. Afterwards you
may configure a partnership for Ethernet communication after the following
approach:
• To enable the Touch Panel to be accessed via Ethernet you have to
activate the option "enable network connection" in ActiveSync via
File > Connection Settings:
• Disconnect the USB cable of the Touch Panel.
• Confirm the message that the device could not be found.
• Start the communication program required for ActiveSync at the Touch
Panel via START > Programs > Communication > Act.Sync Netw and
click on [Connect].
Now you may access the Touch Panel with ActiveSync via Ethernet.
Note!
To keep the settings also after power on, you have to store them to the
registry with START > Programs > KuK Tools > Save.
Install partnership
via Ethernet
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-15
Integrated Server
The Touch Panel has several integrated server that enable a remote
maintenance within a network. Some servers only allow access by means
of entering User name and Password. Per default the following login data
are used:
User name:
wince
Password:
vipatp
You must not change the user name. But you may change the password
via the registry.
For this, start the editor via START > Programs > Registry Editor. The
entry for the password is to be found at:
HKEY_LOCAL_MACHINE/KUKINIT/DefaultPasswd
Please remember to store the changes to the registry via START >
Programs > KuK Tools before switching off.
Per default the following server are integrated:
• ftp server (activated)
• http server (activated)
• Telnet (activated)
• VNC (not activated)
Phrases that are used in the description of the server:
A client is an application that uses the service of a server within a network.
For example, a web browser is a client because at every call of a website it
sends a request to a web server and receives an answer.
A server is an application that waits for the contact request of a client
application and exchanges messages with it after contact start. This
communication type is called Client-Server communication.
Computer within a network where at least one server is running.
Data transfer Server → Client
Data transfer Client → Server
Login data
Change password
Overview
Phrases
Client
Server
Host
Download
Upload
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-16
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
By means of an ftp server data between client and server can be
exchanged. Here you may copy, delete or create files and directories.
For in the meanwhile an ftp client (Internet Explorer) is integrated in
Windows®, this is the easiest method for remote maintenance of the Touch
Panel.
Depending on the ftp client your PC has to fulfill the following conditions for
an ftp connection. If there are still problems with the ftp access ask your
system administrator.
• ftp access possible with version 5.5 or higher
• use passive ftp mode
• activate directory view for ftp sites
For the adjustment choose in the Internet Explorer Options > Internet
options, register "extended" in the area "Browsing” and set the following
settings:
- activate: "activate directory view for ftp sites"
- activate: "use passive ftp..."
The settings are taken over when re-starting the Internet Explorer.
• Ftp access only possible with version 6.0 or higher, you need no further
settings.
ftp server
Conditions for
ftp access
Internet Explorer
Netscape
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-17
In the following the establishing of an ftp connection between a Windows®
based PC (here Windows® 2000) with Internet Explorer as ftp client and
your Touch Panel is shown.
• Connect your Touch Panel with the network where your PC is a member
via an Ethernet cable.
• Switch on your Touch Panel.
As soon as your Touch Panel is connected via Ethernet, you may monitor
the IP address data via
.
• After you’ve confirmed the pre-settings, start your ftp client and enter the
following text into the "address bar":
• ftp://wince:vipatp@IP-Adresse
The following window appears:
Here you may execute the wanted file operations.
Establishing a
ftp connection
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-18
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
The Touch Panel has an integrated http server (web server) that allows
depending on the access the administration of the Touch Panel res. of
websites in the Touch Panel. The administrative access to the http server
happens via Ethernet from the PC by setting the IP address of the Touch
Panel with attached "Admin" type.
By means of websites you may e.g. publish online documentations for a
connected PC or go online with applications at the PC.
As web admin you have access to all functions that are required for
uploading and administrating of websites at the Touch Panel. Additionally
you may set the access rights for user and create user groups. More
detailed information about creating and administrating of websites at the
Touch Panel is to be found in the online documentation of the web servers.
The login as web admin requires the following steps:
• Start the web browser at your PC and enter the following into the
address bar: IP address/webadmin
• Enter the following into the authentification:
User name: wince
Password:
vipatp
Remember to store your changes permanently in the registry via Start
> Programs > KuK Tools > Save Registry!
Sys admin provides you with system administration rights for the
administration of the Touch Panel. Here you may see system information
and may administrate files, processes and registry entries.
The login as sys admin requires the following steps:
• Start the web browser at your PC and enter the following into the
address bar: IP address/sysadmin
• Enter the following into the authentification:
User name: admin
Password:
vipatp
As sys admin you have access to the following functions:
Group
Area
Description
System Tools
System Info
System information about hardware,
memory sharing and date/time.
Processes
Shows all running processes. Via "Kill"
these can be terminated singularly res. be
started with the field "Launch process".
File Browser
Drives
File manager that offers all relevant
functions for administration of files and
directories.
Registry Editor Registry key Registry editor for deleting, altering and
creating of registry entries.
http server
Web admin
Sys admin
Functions
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-19
Telnet is a text based client-server protocol on TCP level. By means of a
Telnet client like e.g. the "MS-DOS console" in your Windows® operating
system you may execute text based all file remote functions at your Touch
Panel like copy, delete and create files and directories. You may also start
applications. Terminating an application is not possible.
The establishing of a Telnet connection is password protected and has the
following approach:
• Start a Telnet client like for example "MS-DOS console" at your PC and
enter the following into the address bar:
telnet IP address
When the connection is established, the Touch Panel asks for the user
name and the password.
• Enter the following:
Login:
wince
Password:
vipatp
(entry is hidden)
After entering valid user data a command line for entries appears:
By entering Exit res. closing the window you may terminate the Telnet
connection at any time.
Telnet server
Establishing a
Telnet connection
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-20
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
After establishment of a Telnet connection the Touch Panel provides you
with commands. A list of possible commands with a short description is
available via the command help.
By beginning with "help" before a command you receive help to this
command.
Commands
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-21
The Touch Panel has an integrated VNC server (virtual network control)
that allows the total control of the Touch Panel with a PC via network. For
this, a window displays the current Touch Panel content for remote control.
The operating happens via PC keyboard and mouse. Using VNC the
context menu functions are available via the right mouse button.
Condition for the VNC communication is that the VNC server is started at
the Touch Panel and a VNC client at the PC. You may download a VNC
client as Freeware from Internet.
Note!
Since with the VNC server all safety attitudes can be gone around, you
should use these exclusively for start-up! For this reason the VNC server is
on delivery deactivated.
The VNC connection establishment has the following approach:
• Click on
and open the "Windows" directory.
• You have to deactivate every option at View > Options to show the VNC
server file.
• Start the VNC server by executing the file KUKVncSVR.exe. To show
the server has been started the symbol
appears in the task bar.
You may also start the VNC server at the Touch Panel via a Telnet
connection by entering the command kukvncsvr in the command
console with an active Telnet connection.
• Now start the VNC client vncviewer.exe at your PC.
• Click on [Options] and de-activate the field "Emulate 3 Buttons..." like
shown at Mouse.
• Enter the IP address of the Touch Panel at VNC server. With [OK] a
VNC connection is established and the screen content of the Touch
Panel is monitored within a window.
Closing the VNC window terminates the VNC connection, the server keeps
running.
VNC server
Establishing a
VNC connection
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-22
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Access to the network resources
The Touch Panel allows you to access shared resources in a Microsoft
network like drives and printer. Here you may assign existing public
directories or printer in the network to local directories or printer in the
Touch Panel.
Condition for this is that you login at the network with your user name and
password.
The assignment of a network resource happens in the Touch Panel via the
command console "Command Prompt". Start the command console with
START > Programs > Command Prompt.
The access to the network resource happens with the commands Net view
and Net use.
Shared resources of a network PC can be listed with the command: \> net
view PC-Name
For example net view testserver lists all shared resources of the
network PC "test server". To test the physical connection a PING to the IP
address of the network PC may be executed if there are problems while
contacting the network PC.
The connection of a local name at the Touch Panel with a shared drive of
the network PC happens with the following approach:
• Enter the following in the command prompt:
\> net use local_name \\network drive /user:User name
• Enter user name, password and where app. user group.
After the successful login the following message appears:
Successfully mapped to network name.
The connected network drive is then available at the Touch Panel with the
local name via My Device at Network.
Local_Name: data, network drive: testserver\archive, User name:gast
Entry: \> net use data \\testserver\archive /user:gast
The connected network drive is then available via \network\data at the
Touch Panel.
Overview
List released
resources
Connect net drive
Example:
\> net view testserver
Shared resources on \\testserver:
Share name Type Used as Comment
---------------------------------------------------------------
Archive Disk (null) Process data
KyoEDV Print (null) Kyocera FS-680 Printer
Command completed successfully
\> █
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-23
The configuration of a network printer happens with the following approach:
• Enter the following into the command prompt:
\> net use printer name network printer
Example:
Printer name: Printer, network printer: \\testserver\printer
Entry: \> net use printer \\testserver\printer
• Enter user name, password and where app. user group.
After the successful login the following message appears
Successfully mapped to network printer
The printer may now be accessed as "network\printer".
For example you may print the content of the current directory with \> dir
> network\printer.
The listing of all network connections of your Touch Panel happens via
\> net use
You may terminate already assigned network resources via
\> net use local_name /d
Example: \> net use data /d deletes the network connection to the
drive "archive" of "test server".
Note!
To keep the settings also after power on, you have to store them to the
registry with START > Programs > KuK Tools > Save Registry.
Configure network
printer
Test print
List network
connections
Terminate network
connections
\> net use
Connected resources:
Status Local Name Remote Name
----------------------------------------------------------------
Connected data \\testserver\archiv
Connected printer \\testserver\printer
Command completed successfully
\> █
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-24
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Integration to WLAN network
By plugging a WLAN card there is the possibility to integrate your Touch
Panel to a WLAN network. For this driver for the corresponding WLAN
hardware are pre-installed.
Please regard only SDIO WLAN cards are supported which drivers are pre-
installed in the Touch Panel. In the Touch Panel driver exist for the
following SDIO cards:
• Socketcom P300
• Spectec SDW821
• JustMobile Wireless LAN Card.
• PowerON the Touch Panel.
• Plug the SDIO card → the SDIO card is identified and a dialog window,
which shows the available WLAN networks, is opened.
• Continue with "WLAN integration".
Please regard only WLAN-USB sticks are supported with the chip of the
company Funkwerk inside!
• PowerOFF the Touch Panel.
• Plug the WLAN USB stick to the USB-A interface.
• PowerON the Touch Panel → the driver name is requested.
• Enter "prisma02" → now your card is installed and activated.
Note!
To keep the settings also after PowerON, you have to store them to the
registry with START > Programs > KuK Tools > Save Registry.
Directly after installation a dialog window is shown. Here the available
WLAN networks are displayed.
Chose the corresponding network and click to [Connect].
At a safety-relevant network set the network parameters and enter the
network key. If the parameters are correct the connection is established.
Overview
WLAN via
SDIO card
Installation
WLAN via
USB stick
Installation
WLAN integration
Manual VIPA HMI
Chapter 2 Deployment Touch Panel
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
2-25
If the Touch Panel should connect automatically to your WLAN network
after startup, so the automatically connection is to be activated.
For this open the register "Wireless Information" in the dialog window and
click to the [Advanced...] button.
The following window is shown:
By activating of "Automatically connect to non-preferred networks" an
automatically connection to the chosen network is established as soon as
the network is available.
Please do not forget to store the settings with the KuK Tools as shown
above.
Automatically
connect to WLAN
Chapter 2 Deployment Touch Panel
Manual VIPA HMI
2-26
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Firmware update
You may execute a firmware update via SD or CF card. The newest
firmware version may be ordered by the VIPA Panel Support.
Attention!
When installing a new firmware you have to be extremely careful. Under
certain circumstances you may destroy the Touch Panel, for example if the
voltage supply is interrupted during transfer or if the firmware file is
defective. In this case, please call the VIPA Panel Support!
Please regard that the firmware to be transferred is not checked by the
Touch Panel. Always use the firmware, which you received for exactly this
Touch Panel from our Panel Support.
•
For new firmware contact the VIPA Panel Support. They will send you
the appropriate firmware as zip file via mail.
•
Unzip the zip file and store it at your PC.
•
Copy the unzipped files into the root directory of your memory card. As
memory card a SD or CF card may be used.
•
Switch off the power supply from your panel. Plug the memory card to
your panel and switch on the power supply again. → As soon as a new
firmware is found at the memory card, it is downloaded to the Touch
Panel and the message "Update please wait" is displayed. If the
update is finished (after max. 5min.) "Update finished" is displayed.
•
Switch off the Power supply from your Panel. Remove the memory
card and switch on the power supply again. Now the Touch Panel
starts up with the new firmware.
If there is no message "Update finished" displayed after maximally 15
minutes or the Touch Panel does not start-up after firmware update, you
should contact the VIPA Panel Support.
Note!
Please regard depending upon the used version the Touch Panel may be
adjusted again!
The following adjustments could be necessary:
•
New calibration of the touch screen
•
Depending on the visualization software the license key may be re-
entered. More may be found in the documentation of the visualization
software.
Do not forget to store the settings durably with the KuK Tools. For this go
to Start > Programs > KuK Tool > KuK Tool and store the settings with
[Store].
Overview
Proceeding
Adjustments
Manual VIPA HMI
Chapter 3 Installation Guidelines
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
3-1
Chapter 3
Installation Guidelines
The chapter "Installation Guidelines" gives you information about the
interference-immune installation of Programmable Logic Controls (PLC)
together with a Touch Panel.
Here we describe possible paths in which interference can enter the
controller, how you ensure the electromagnetic compatibility (EMC) and
how to approach shielding and screening issues.
Topic
Page
Chapter 3
Installation Guidelines.................................................... 3-1
Basic rules for the EMC-equitable assembly of installations................. 3-2
EMC-equitable assembly...................................................................... 3-6
EMC-equitable cabling ......................................................................... 3-7
Special precautions providing high noise immunity ............................ 3-11
Checklist for the EMC-compliant installation of controllers ................. 3-12
Overview
Content
Chapter 3 Installation Guidelines
Manual VIPA HMI
3-2
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Basic rules for the EMC-equitable assembly of installations
The term electromagnetic compatibility (EMC) refers to the ability of an
electrical device to operate properly in an electromagnetic environment
without interference from the environment or without the device causing
illegal interference to the environment.
The Operation Panels are developed for applications in harsh industrial
environments and complies with EMC requirements to a large degree. In
spite of this you should implement an EMC strategy before installing any
components, which should include any possible source of interference.
Electromagnetic interference can enter your system in many different ways:
Fields
Bus
Power
PE
I/O-Signal
Automation
System
Interference is coupled into your system in different ways, depending in the
propagation medium (conducted or not conducted) and the distance to the
interference source.
We differentiate between:
• galvanic coupling
• capacitate coupling
• inductive coupling
• radiated power coupling
What is EMC?
Possible sources
for disturbances
Manual VIPA HMI
Chapter 3 Installation Guidelines
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
3-3
The following table shows the four different coupling mechanisms, their
causes and possible interference sources.
Coupling mechanism
Cause
Typical source
Galvanic coupling
Automation
System
Disruptor
galvanic
coupling line
Galvanic or metallic coupling
always occurs when two
current circuits have a
common line.
• Pulsed devices
(Net influence from
transducers and foreign net
devices)
• Starting motors
• Different potential of
component cubicles with
common current supply
• Static discharges
Capacitate coupling
Automation
System
Disruptor
capacitive
coupling line
Capacitate or electric coupling
occurs between conductors
with different potential.
The coupling is proportionate
to the time wise change of the
voltage.
• Interference through parallel
signal lines
• Static discharge of the
personnel
• Contactors
Inductive coupling
Automation
System
Disruptor
inductive
coupling
line
wanted signal
Inductive or magnetic coupling
occurs between two current
active line loops.
The magnetic flows associated
with the currents induct
interference voltages.
The coupling is proportional to
the time related change of the
current.
• Transducers, motors,
electric welding devices
• Parallel net cables
• Cables with toggled currents
• Signal cable with high
frequency
• Unused coils
Radiate power coupling
Automation
System
Disruptor
radiated
coupling
line
One talks of radiate power
coupling, when an electro-
magnetic wave meets a line
circuit.
The hit of the wave inducts
currents and voltages.
• Sender in the neighborhood
(e.g. walkie-talkie)
• Sparking lines
(sparking plugs, collector of
electric motors, welding
devices)
Coupling
mechanisms and
interference
sources
Chapter 3 Installation Guidelines
Manual VIPA HMI
3-4
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
In many cases, adherence to a set of very elementary rules is sufficient to
ensure EMC. For this reason we wish to advise you to heed the following
rules:
During the installation of your automation units you should ensure
that any inactive metal components are grounded via a proper large-
surface earth!
• Interconnect any inactive metal components via low-impedance
conductors with a large cross-sectional area.
• Execute screw connections at coated and anodized metal parts either
with special contact washer or remove the isolating protective film.
• Install a central connection between the chassis ground and the
earthing/protection system.
Ensure that cabling is routed properly during installation!
• Divide the cabling into different cable groups
(High voltage lines, power supply lines, signal lines, data lines).
• Always install high voltage lines and signal or data lines in separate
channels or bundles.
• Install signal and data lines as close as possible to any metallic ground
surfaces (e.g. frames, metal rails, sheet metal).
Ensure that the screening of lines is grounded properly!
• Data lines must be screened. The screen has to be laid both-sided.
• Analog lines must be screened. Where low-amplitude signals are
transferred it may be advisable to connect the screen on one side of the
cable only.
• Attach the screening of cables to the ground rail by means of large-
surface connectors located as close as possible to the point of entry.
Clamp cables mechanically by means of cable clamps. Route the
connected screen to the modules without interruptions, but don't
connect the screen again.
• Ensure that the ground rail has a low-impedance connection to the
cabinet/cubicle.
• Use only metallic or metallic covers for the plugs of screened data lines.
Basic rules for
ensuring EMC
Manual VIPA HMI
Chapter 3 Installation Guidelines
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
3-5
In critical cases you should implement special EMC measures!
• Connect snubber networks to all inductive loads that are not controlled
by special EMC modules.
• Use incandescent lamps for illumination purposes inside cabinets or
cubicles, do not use of fluorescent lamps.
Create a single reference potential and ensure that all electrical
equipment is grounded wherever possible!
• Ensure that grounding measures are implemented effectively. The
controllers are earthend to provide protection and for functional reasons.
• Provide a star-shaped connection between the plant, cabinets/cubicles
and the grounding/ protection system. In this way you can avoid ground
loops.
• Where potential differences exist you must install sufficiently large
equipotent bonding conductors between the different parts of the plant.
Chapter 3 Installation Guidelines
Manual VIPA HMI
3-6
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
EMC-equitable assembly
Mostly, measures for suppressing interference voltages are only taken,
when the control is already in commission and the perfect receive of a
wanted signal is disturbed.
Causes for such interference's are in the most cases inadequate reference
potentials, coming from mistakes at the device assembly and installation.
When assembling the devices, you have to ensure the large-surface
grounding of the inactive metal parts. A correctly done grounding supports
an unambiguous reference potential for the control and reduces the impact
of coupled interference's.
Grounding means the conducting connection of all inactive metal parts.
The sum of all interconnected inactive parts is called Ground.
Inactive parts are all conductive parts electrically separated from all active
parts by means of a basic isolation and that may only get voltage in case of
an error.
The ground must not adopt dangerous contact voltage even in case of an
error. Thus you have to connect the ground with the protected earth
conductor. To avoid ground loops, local distant ground constructions
(cubicles, construction and machine parts) have to be connected with the
protected earth conductor system in star-topology.
Please regard at grounding:
• Connect the inactive metal parts as carefully as the active ones.
• Take care of impedance-low metal-metal-connections, for e.g. with
large-surface and well conductive contacts.
• If you include coated or anodized metal parts in the grounding, you have
to come through the isolating protection layers. For this you may use
special contact washers or remove the isolation layer.
• Protect the connection points from corrosion, e.g. with grease.
• Moveable grounding parts (e.g. cubicle doors) have to be connected via
flexible ground strips. The ground strips should be short and have a
large surface, because the surface is decisive for the diversion of high
frequency interference's.
Guidelines for
assembling and
grounding of
inactive metal
parts
Manual VIPA HMI
Chapter 3 Installation Guidelines
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
3-7
EMC-equitable cabling
Content of this section is the line routing of bus, signal and supply lines.
Object of the line routing is to suppress the "slurring" at parallel lines.
For an EMC-equitable routing of the lines it is convenient to divide the
cables in different groups and install each group itself:
Group A
• screened bus and data lines
• screened analog lines
• unshielded lines for direct voltage ≤ 60V
• unshielded lines for alternating voltage ≤ 25V
• Coaxial cables for monitors
Group B
• unshielded lines for direct voltage >60V and ≤400V
• unshielded lines for alternating voltage >25V and ≤400V
Group C
• unshielded lines for direct and alternating voltage >400V
Group D
• Lines for H1 respectively TCP/IP
Line routing
Line routing inside
and outside of
cubicles
Chapter 3 Installation Guidelines
Manual VIPA HMI
3-8
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Following the table you may see the conditions for the cabling of the line
groups by combining the single groups:
Group A
Group B
Group C
Group D
Group A
[1]
[2]
[3]
[4]
Group B
[2]
[1]
[3]
[4]
Group C
[3]
[3]
[1]
[4]
Group D
[4]
[4]
[4]
[1]
[1]
The lines may be installed in common bundles or cable trusses.
[2]
The lines have to be installed in different bundles or cable trusses
(without min. distance).
[3]
The lines have to be installed in different bundles or cable trusses
inside of cubicles and outside of the cubicle but inside the building
in separated cable trusses with a min. distance of 10cm.
[4]
The lines have to be installed in different bundles or cable trusses
with a min. distance of 50cm.
Wherever possible, exterior cabling should be installed on metallic cable
trays. A galvanic connection must be provided for joints between cable
trays.
You must abide by the applicable lightning protection and grounding
regulations when installing exterior cables.
Attention!
Where cables and signal lines for PLC equipment are installed outside of
buildings, the conditions for internal and external lightning protection must
be satisfied.
• Exterior lines should either be installed in metallic conduit pipes that is
grounded on both ends or in steel-reinforced concrete cable trunks with
continuously connected reinforcing.
• Signal lines should be protected against overvoltage by varistors or by
lightning arrester filled with rare gas.
• Install these protective elements at the location where the cables enter
the building.
Note!
Any lightning protection system must be based on an individual
assessment of the entire plant. For questions please contact VIPA GmbH.
Combination of
groups
Line routing
outside of
buildings
Lightning
protection
Manual VIPA HMI
Chapter 3 Installation Guidelines
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
3-9
Potential differences can occur between different sections when controllers
and peripheral equipment are connected by means of non-isolated
connections or the screens of screened cables are connected at both ends
and grounded on different sections of the plant.
One reason for a potential difference can be that different sections of the
plant are powered from different power sources. These potential
differences must be reduced by means of equipotential bonding conductors
to ensure that the electronic equipment employed on the plant operates
properly.
• The lower the impedance of the equipotential bonding conductor, the
higher the effectiveness of potential equalization.
• The impedance of the equipotential bonding conductor must not exceed
10% of the impedance of the screen where screened signal lines are
connected between the different sections of the plant and the screening
is connected to ground/neutral on both sides.
• The cross-sectional area of the equipotential bonding conductor must be
calculated to carry the maximum equalization current. The following
cross-sections have been successfully employed:
- 16mm2 Cu for equipotential bonding conductors up to 200m
- 25mm2 Cu for equipotential bonding conductors exceeding 200m.
• Use copper or galvanized steel for equipotential bonding conductors.
These must be connected to ground/neutral by means of large-surface
connections that are protected from corrosion.
• The equipotential bonding conductor should be installed in such a
manner that it includes the smallest surface between the bonding
conductor and the signal lines.
Screening is one method commonly used to reduce (attenuate) the
interference pick-up from magnetic, electrical or electromagnetic fields.
• Interference on screens is conducted to ground by the conductive
connection between the screen and the screening rain/enclosure. To
avoid interference from these currents it is very important that the
neutral connection is a low-impedance connection.
• You should only use of cables that are provided with a braided screen.
The degree of screening should be more than 80%.
• Avoid cables with foil-type screens as the foil is easily damaged by
tension and pressure at the point of attachment; this can result in
reduced effectiveness of the screening action.
• As a rule you should always ground the screens of cables on both ends.
This is the only way in which you can ensure that high frequency
interference is attenuated properly.
Equipotential
bonding
Rules for
equipotential
bonding
Screening of lines
and cables
Chapter 3 Installation Guidelines
Manual VIPA HMI
3-10
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
In exceptional cases it may be necessary to ground the screen on one side
only. However, this will only attenuate the lowest frequencies. The one-
sided grounding of screens may provide advantages when:
• It is not possible to install an equipotential bonding conductor
• Analogue signals (a few mV or µA) must be transmitted
• Foil-type screening (static screening) is employed.
You should always use metallic or metallic covers for serial data lines.
Connect the screen of the data line to the cover. Do not connect the
screen to PIN 1 of the connector!
In case of stationary operations it is recommended that the remove the
insulation from the screened cable without cutting the screen and to attach
this point to the screening/neutral rail.
Note!
Potential differences can give rise to an equalization current via the screen
connected between the two ground connections.
In this case you must install an additional equipotential bonding conductor.
Please observe the following points when you handle the screens:
• Use only metallic cable clamps when connecting the screening of
cables. These clamps must provide a good electrical contact and a
large-surface connection to the screen.
• Attach the screens to the screening rail directly at the point where the
cables enter the enclosure.
The screening conductor must be continued to the module without
interruption, however, it must not be connected to the module!
One-sided
grounding of
screens
Connecting the
screen
Manual VIPA HMI
Chapter 3 Installation Guidelines
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
3-11
Special precautions providing high noise immunity
Inductors controlled by your programmable controller (e.g. contactors and
relays) do not normally require additional snubber networks or suppressors
as the respective modules have been provided with the required
components.
Snubber networks must only be connected to inductors when output
circuits can be disabled by means of additional contacts (e.g. relay
contacts). In this case the integrated suppressors on the module are also
disabled.
You can connect diodes to suppress back-emc, varistors or RC-networks
to the inductors.
Connections of
DC-activated inductors
Connections of
AC-activated inductors
using a diode
using a Z-diode using a varistor
using RC-network
-
+
+
-
Every cubicle must be provided with a power outlet for the PU. These
outlets must be wired to the distribution system, which is also used to
connect the neutral conductor for the cubicle.
The cubicle illumination should consist of incandescent lights, e.g.
LINESTRA-lamps. Avoid using fluorescent lamps as these lamps can
cause interference.
If you can not avoid using fluorescent lamps you should implement the
steps outlined in the following figure.
[1]
Fluorescent lamp
[2]
Screen above the lamp
[3]
Screened cable
[4]
Switch with metallic cover
1
3
4
5
2
[5]
Line filter or screened power
cable
Inductors require
snubber networks
Equipotential
bonding
Power outlet for
PGs
Cubicle
illumination
Suppression of
fluorescent lamps
in cubicles
Chapter 3 Installation Guidelines
Manual VIPA HMI
3-12
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
Checklist for the EMC-compliant installation of controllers
EMV-measures
Space for Notes
Connection of the inactive parts
You should take special care to check the connections of:
• Module racks
• Frames
• Screen and protected earth conductor
Are all the inactive metal parts interconnected by means of
large-surface and low-impedance connections?
Has a proper connection been installed with respect to the
ground/protected earth conductor system?
Has the isolation been removed from varnished and anodized
surfaces or have these connections been fitted with special
contact washer?
Have the connection been protected from corrosion, e.g. by
means of grease?
Have doors been grounded by means of grounding straps
connected to the body of the cubicle?
Cable routing
Cabling divided into groups?
Power cables (230 ... 400V) and signal lines installed in
separate channels or bunches?
Potential compensating
When installing the equipment at separate locations, check
the installation of the potential compensating line.
Cable screen
All covers of plugs are metallic?
All analog and data lines installed screened?
Line screens attached to the screening or the protected earth
conductor?
Have the screens been connected by means of large-surface
and low-impedance cable clamps?
Cable screens grounded both-sided where possible?
Inductors
Have the coils of contactors controlled by means of contacts
been connected to snubber networks?
Manual VIPA HMI
Index
HB160E - TP - RE_610-3B2J0 - Rev. 09/09
A-1
Appendix
A Index
A
Access data ................................2-15
ActiveSync ..................................2-12
C
CAN interface ...............................1-7
CF.................................................1-6
Commissioning .............................2-4
Components .................................1-6
Control Panel ..............................2-11
D
Deployment...................................2-1
Dimensions.................................1-10
E
EMC..............................................3-2
Basic rules ................................3-4
Checklist installation ...............3-12
Coupling mechanisms ..............3-3
Disturbance-free operation.....3-11
Equipotential bonding ...............3-9
equitable assembly...................3-6
equitable cabling.......................3-7
Interferences.............................3-2
Lightning protection ..................3-8
Screening..................................3-9
Ethernet connection......................1-8
F
Firmware update.........................2-26
Flash disc......................................1-6
ftp server.....................................2-16
H
http server...................................2-18
I
Installation.....................................2-2
cutting .......................................2-2
guidelines..................................3-1
L
Login data ...................................2-15
M
Memory management...................1-6
MMC .............................................1-6
N
net use........................................ 2-22
net view ...................................... 2-22
Network
Access.................................... 2-22
connection.............................. 2-23
printer ..................................... 2-23
P
Partnership ................................. 2-13
Password.................................... 2-15
PLC connection ............................ 2-6
Power supply.........................1-9, 2-3
Properties ..................................... 1-3
R
RS232........................................... 1-8
RS422/485.................................... 1-7
S
Safety Information ........................ 1-2
SD................................................. 1-6
Server......................................... 2-15
Software keyboard...................... 2-10
Startup behavior ........................... 2-4
Startup Manager........................... 2-4
Structure....................................... 1-4
Sys admin................................... 2-18
System setting............................ 2-11
T
Task bar ....................................... 2-9
Technical Data............................ 1-11
Telnet.......................................... 2-19
U
USB
Storage media.......................... 1-6
USB-A ...................................... 1-9
USB-B ...................................... 1-9
V
VNC server................................. 2-21
W
Web admin ................................. 2-18
Windows® CE ............................... 2-7
WLAN......................................... 2-24
Work memory............................... 1-6