PCI MicroTrans EQ Operation & Maintenance Manual

Text of the manual

Operation & Maintenance Manual

Engineered for accuracy, applicability, durability and simplicity in HVAC air systems and industrial process control loops

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated i Revision Level 012 TABLE OF CONTENTS TABLE OF CONTENTS ............................................................................................................................. i 1. INTRODUCTION .............................................................................................................................. 1 1.1. DESCRIPTION ............................................................................................................................ 1 1.2. BASIC OPERATION .................................................................................................................. 1 1.3. SPECIFICATIONS ...................................................................................................................... 1 1.3.1. Power Supply ........................................................................................................................ 1 1.3.2. Power Consumption .............................................................................................................. 1 1.3.3. Accuracy ............................................................................................................................... 1 1.3.4. Temperature Input Options ................................................................................................... 1 1.3.5. Process Output Options......................................................................................................... 1 1.3.6. High/Low Alarm Relay Outputs ........................................................................................... 2 1.4. SAFETY ....................................................................................................................................... 2 1.4.1. Electrical Connections .......................................................................................................... 2 1.4.2. Static Electricity .................................................................................................................... 2 2. PRODUCT DIMENSIONS ................................................................................................................ 3 2.1. NEMA 1 MECHANICAL DIMENSIONS .................................................................................. 3 2.2. NEMA 4 MECHANICAL DIMENSIONS .................................................................................. 4 3. INSTALLATION ............................................................................................................................... 5 3.1. ELECTRICAL & PNEUMATIC INSTALLATION ................................................................... 5 3.2. TEMPERATURE TRANSMITTER CONNECTION ................................................................. 6 3.2.1. 4-20mA Output/2-Wire Loop Powered Temperature Transmitter ....................................... 6 3.2.2. 0-10VDC Output/24VAC Power 3-Wire Temperature Transmitter .................................... 6 3.2.3. 0-10VDC Output/24VDC Power 3-Wire Temperature Transmitter .................................... 7 3.2.4. 0-10VDC or 4-20mA from a Building Management System (BMS) ................................... 7 4. INPUT/OUTPUT SET-UP ................................................................................................................. 8 4.1. PROCESS OUTPUT .................................................................................................................... 8 4.2. TEMPERATURE INPUT (OPTION) .......................................................................................... 8 5. COMMON STARTUP CONFIGURATION CHANGES.................................................................. 9 5.1. AREA FACTOR .......................................................................................................................... 9 5.2. OPERATING RANGE .............................................................................................................. 10 5.3. TEMPERATURE COMPENSATION FOR AIR DENSITY .................................................... 11 5.3.1. Temperature Input Signal Selection.................................................................................... 11 5.3.2. Temperature Units .............................................................................................................. 11 5.3.3. Temperature Values ............................................................................................................ 11 5.3.4. Temperature Input ............................................................................................................... 13 5.3.5. Fixed Value ......................................................................................................................... 13 6. ACTIVE DISPLAYS & KEY FUNCTIONS ................................................................................... 14 6.1. POWER-UP INITIATION DISPLAY ....................................................................................... 14 6.2. PROCESS DISPLAY DESCRIPTIONS ................................................................................... 14 6.3. KEY FUNCTIONS .................................................................................................................... 15 7. DISPLAY MENUS ........................................................................................................................... 16 7.1. FIELD SETUP & TECH. CONFIGURATION MENUS .......................................................... 16 8. FIELD SETUP MENUS ................................................................................................................... 17 8.1. OPERATING RANGE .............................................................................................................. 17 8.2. ZERO PRESSURE CALIBRATION ......................................................................................... 17 8.3. ENGINEERING UNITS ............................................................................................................ 18 8.4. LOCKDOWN ............................................................................................................................. 18 8.4.1. Lockdown Value ................................................................................................................. 18

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated ii Revision Level 012 8.4.2. Lockdown Delay ................................................................................................................. 19 8.5. FLOW CORRECTION .............................................................................................................. 19 8.5.1. Flow Correction (K-Factor) ................................................................................................ 19 8.5.2. Flow Correction (K-Factor Calculator) .............................................................................. 19 8.6. AUTOZERO .............................................................................................................................. 20 8.6.1. AutoZero Status .................................................................................................................. 20 8.6.2. AutoZero Interval ................................................................................................................ 20 8.6.3. AutoZero Test Interval ........................................................................................................ 21 8.7. TEMPERATURE COMPENSATION ...................................................................................... 21 8.7.1. Temperature Units .............................................................................................................. 21 8.7.2. Temperature Values ............................................................................................................ 22 8.7.3. Temperature Input ............................................................................................................... 23 8.7.4. Fixed Value ......................................................................................................................... 23 8.8. DISPLAY FILTER .................................................................................................................... 23 8.9. PROCESS OUTPUT FILTER ................................................................................................... 24 8.10. HIGH/LOW ALARM OPTIONS ........................................................................................... 24 8.10.1. Alarm Status .................................................................................................................... 24 8.10.2. Alarm Values................................................................................................................... 25 8.10.3. Alarm Delay .................................................................................................................... 25 8.11. DP DISPLAY FORMAT ....................................................................................................... 25 8.12. FACTORY DEFAULTS ........................................................................................................ 26 9. TECH CONFIGURATION MENUS ............................................................................................... 27 9.1. AREA FACTOR ........................................................................................................................ 27 9.2. MINIMUM CALIBRATION ..................................................................................................... 28 9.3. 50% CALIBRATION ................................................................................................................ 29 9.4. SPAN CALIBRATION .............................................................................................................. 29 9.5. TEMPERATURE FIXED VALUE ........................................................................................... 29 9.6. ALTITUDE ................................................................................................................................ 30 9.7. PROCESS OUTPUT CALIBRATION ...................................................................................... 31 9.7.1. Minimum Calibration .......................................................................................................... 31 9.7.2. Span Calibration.................................................................................................................. 31 9.8. CORRECTION COEFFICIENT ................................................................................................ 31 9.8.1. Probe Coefficient ................................................................................................................ 32 9.8.2. Piezometer Ring Coefficient ............................................................................................... 32 9.9. FOUR POINT FLOW CORRECTION...................................................................................... 33 9.10. MAC ADDRESS (BACNET COMMUNICATION OPTION) ............................................. 34 9.11. INSTANCE NUMBER (BACNET COMMUNICATION OPTION) ................................... 34 9.12. MODBUS ID (MODBUS COMMUNICATION OPTION).................................................. 34 9.13. BAUD RATE (BACNET & MODBUS COMMUNICATION OPTIONS) .......................... 35 10. WARNING MESSAGES .............................................................................................................. 36 10.1. INPUT PRESSURE OVERRANGE MESSAGE .................................................................. 36 10.2. TRANSDUCER CALIBRATION MESSAGE ...................................................................... 36 10.3. OPERATING RANGE MESSAGE ....................................................................................... 36 10.4. NEW OPERATING RANGE MESSAGE ............................................................................. 36 11. TROUBLESHOOTING GUIDE ................................................................................................... 37

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 1 Revision Level 012 1. INTRODUCTION 1.1. DESCRIPTION The MicroTransEQ Signal Processor employs current state-of-the-art digital microprocessor technology to produce highly stable and accurate differential pressure and air flow measurements. The MicroTransEQ is factory configured and calibrated to the exact specification determined at time of order. Simple field configuration of engineering units, operating range, process noise filtering, alarm set points, etc., are performed via password protected intuitive menus that are accessed through the integral six button touch pad. Device monitoring and configuration can also be performed by a building management system through a LonWorks®, BACnet®-MS/TP Master, or Modbus® Slave communication network. Optional features include AutoZero; High/Low Remote Alarms; Temperature Compensation; and LonWorks®, BACnet®-MS/TP Master, and Modbus® Slave communication. 1.2. BASIC OPERATION The transducer receives a differential pressure signal from the pressure or flow sensing element. This signal is scaled and linearized before being displayed and transmitted out as a 4-20mA, 0-5VDC, or 0- 10VDC signal. The AutoZero option detects and corrects any zero offset caused by large ambient temperature changes. The Temperature Compensation option compensates the flow and velocity signal for density changes caused by variations in the process air temperature. An external temperature transmitter or input signal from the building management system is required. 1.3. SPECIFICATIONS 1.3.1. Power Supply 20 to 28 VAC/DC 1.3.2. Power Consumption Standard Unit: 216mA at 24VAC 150mA at 24VDC Full Options: 250mA at 24VAC 175mA at 24VDC 1.3.3. Accuracy ±0.25% full scale (Standard) ±0.10% full scale (Optional) 1.3.4. Temperature Input Options 0-10VDC 4-20mA 1.3.5. Process Output Options 0-5VDC 0-10VDC 4-20mA (700Ω maximum load)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 2 Revision Level 012 1.3.6. High/Low Alarm Relay Outputs Two single (1 form C) dry contacts rated for: 5 amps at 30VAC/DC 10 amps at 120VAC 1.4. SAFETY 1.4.1. Electrical Connections Before any electrical connections are made, ensure the POWER SWITCH is in the OFF position. 1.4.2. Static Electricity The circuit board contains components which are susceptible to damage caused by static electrical discharge. Should it be necessary to remove the circuit board from the enclosure, appropriate precautions must first be taken to ensure that the operator and the circuit board are at the same electrical potential.

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 3 Revision Level 012 2. PRODUCT DIMENSIONS 2.1. NEMA 1 MECHANICAL DIMENSIONS 2.265" 7.625" PG21(3/4") PG13.5(1/2") - TYP OF 3 1,225 CONTROLS INCORPORATED PARAGON PCI ACFM SIGNAL PROCESSOR MicroTrans 4.625" 75 F * EQ 3.500" 8.250" 0.20" DIA (TYP OF 4) I.D./DATA LABEL 1.4" 1.2"

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 4 Revision Level 012 2.2. NEMA 4 MECHANICAL DIMENSIONS PG21(3/4") PG13.5(1/2") PG13.5(1/2") MOUNTING SCREW DIA. UP TO 1/4". 8.2" (TYP OF 2) PG13.5(1/2") STANDARD 1/4" COMPRESSION OPTION 5.0" I.D./DATA LABEL PARAGON INCORPORATED CONTROLS PCI MicroTrans SIGNAL PROCESSOR 1,225 75 F ACFM EQ * 7.0" 3.12" 9.56"

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 5 Revision Level 012 3. INSTALLATION 3.1. ELECTRICAL & PNEUMATIC INSTALLATION - NEMA 1 & 4 Option - Remove the cover by turning each corner cover mounting screw counter clockwise. - Both NEMA 1 & NEMA 4 enclosures incorporate three 1/2 inch conduit connections and one 3/4 inch conduit connection to interface all electrical wiring and pneumatic tubing to the device. Determine which conduit connection will be used and remove the black plug and install the appropriate conduit fitting (By Others). - The three electrical connectors (J1, J2, and J3) located on the MicroTransEQ board have removable terminal blocks for ease of installing the interface wiring. (Caution - All electrical connections must be made with the MicroTransEQ power switch in the OFF position). J1 1 2 3 11 12 13 14 15 16 17 18 4 5 6 7 8 J3 (ALARM OPTION) J2 ON OFF POWER SWITCH ENTER ESC 10 9 LON INPUT TEMP. mA V PROC. OUTPUT mA V 10V 5V (24VAC/DC) POWER SUPPLY ANALOG RECEIVING DEVICE PROCESS OUTPUT S1 S2 S4 + - + 24VDC OUTPUT POWER - TEMPERATURE INPUT(GND) + TEMPERATURE INPUT + NETWORK COMMUNICATIONS - NETWORK COMMUNICATIONS - ANALOG PROCESS OUTPUT(GND) + ANALOG PROCESS OUTPUT 8 10 9 EARTH GROUND 1 24VAC / DC 3 2 J1 4 6 7 5 J2 J3 (ALARM OPTION) 15 17 18 16 11 13 14 12 NC LOW ALARM NO NC COM PURGE HOLD HIGH ALARM COM NO TYPICAL FLOW ELEMENT CONNECTION CONNECTION TOTAL (HIGH) PRESSURE CONNECTION PRESSURE STATIC (LOW) Tp CONNECTION FE-1000 Sp CONNECTION REFER TO SECTION 2.4 FOR PROPER TEMPERATURE TRANSMITTER CONNECTION SWITCH POSITIONS SHOWN IN BLACK S1 POSITION INDICATING 4-20mA TEMPERATURE INPUT S2 AND S4 POSITIONS INDICATING 0-10VDC PROCESS OUTPUT RP1 S3

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 6 Revision Level 012 3.2. TEMPERATURE TRANSMITTER CONNECTION Shielded cable is recommended for all connections between the MicroTransEQ and the Temperature Transmitter. 3.2.1. 4-20mA Output/2-Wire Loop Powered Temperature Transmitter J1 1 2 3 11 12 13 14 15 16 17 18 4 5 6 7 8 J3 (ALARM OPTION) J2 ON OFF POWER SWITCH ENTER ESC 10 9 LON INPUT TEMP. mA V PROC. OUTPUT mA V 10V 5V (4-20mA LOOP POWERED) + - TRANSMITTER S1 S2 S4 + 24VDC OUTPUT POWER - TEMPERATURE INPUT(GND) + TEMPERATURE INPUT + NETWORK COMMUNICATIONS - NETWORK COMMUNICATIONS - PROCESS OUTPUT(GND) + PROCESS OUTPUT 8 10 9 4 6 7 5 J2 TEMPERATURE S1 SET TO mA POSITION 3.2.2. 0-10VDC Output/24VAC Power 3-Wire Temperature Transmitter J1 1 2 3 11 12 13 14 15 16 17 18 4 5 6 7 8 J3 (ALARM OPTION) J2 ON OFF POWER SWITCH ENTER ESC 10 9 LON INPUT TEMP. mA V PROC. OUTPUT mA V 10V 5V S1 S2 S4 - O + 24VDC OUTPUT POWER - TEMPERATURE INPUT(GND) + TEMPERATURE INPUT + NETWORK COMMUNICATIONS - NETWORK COMMUNICATIONS - PROCESS OUTPUT(GND) + PROCESS OUTPUT 8 10 9 4 6 7 5 J2 TEMP. TRANSMITTER (24VAC POWERED / 0-10VDC OUTPUT) 24VAC POWER SOURCE + - + S1 SET TO V POSITION Note: If the MicroTransEQ power source is 24VAC, the same power source can be used to power the Temperature Transmitter.

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 7 Revision Level 012 3.2.3. 0-10VDC Output/24VDC Power 3-Wire Temperature Transmitter J1 1 2 3 11 12 13 14 15 16 17 18 4 5 6 7 8 J3 (ALARM OPTION) J2 ON OFF POWER SWITCH ENTER ESC 10 9 LON INPUT TEMP. mA V PROC. OUTPUT mA V 10V 5V S1 S2 S4 - O + 24VDC OUTPUT POWER - TEMPERATURE INPUT(GND) + TEMPERATURE INPUT + NETWORK COMMUNICATIONS - NETWORK COMMUNICATIONS - PROCESS OUTPUT(GND) + PROCESS OUTPUT 8 10 9 4 6 7 5 J2 TEMP. TRANSMITTER (24VDC POWERED / 0-10VDC OUTPUT) + S1 SET TO V POSITION 3.2.4. 0-10VDC or 4-20mA from a Building Management System (BMS) J1 1 2 3 11 12 13 14 15 16 17 18 4 5 6 7 8 J3 (ALARM OPTION) J2 ON OFF POWER SWITCH ENTER ESC 10 9 LON INPUT TEMP. mA V PROC. OUTPUT mA V 10V 5V S1 S2 S4 - + 24VDC OUTPUT POWER - TEMPERATURE INPUT(GND) + TEMPERATURE INPUT + NETWORK COMMUNICATIONS - NETWORK COMMUNICATIONS - PROCESS OUTPUT(GND) + PROCESS OUTPUT 8 10 9 4 6 7 5 J2 TEMPERATURE. SIGNAL FROM BMS SYSTEM (0-10VDC / 4-20mA) + VERIFY CORRECT S1 POSITION. S1 UP=mA S1 DOWN=V Note: Verify Temperature Input switch (S1) position matches the input signal type (refer to Section 4.2).

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 8 Revision Level 012 4. INPUT/OUTPUT SET-UP The MicroTransEQ has been configured and calibrated at the factory for the specific application. Refer to the MicroTransEQ Set-Up label located on the left side of unit to verify correct Input/Output configuration for the application. If input or output configuration changes are required refer to the tables in the sections below and the figure in Section 3.1. 4.1. PROCESS OUTPUT To change the output configuration, set the S2 & S4 switches as follows: Process Output Range S2 S4 Current 4-20mA NA mA Voltage 0-10VDC 10V V Voltage 0-5VDC 5V V 4.2. TEMPERATURE INPUT (OPTION) To change the input configuration, set the S1 switch as follows: Temperature Input S1 Switch Selection 4-20mA mA 0-10VDC V

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 9 Revision Level 012 5. COMMON STARTUP CONFIGURATION CHANGES 5.1. AREA FACTOR The Area Factor can be entered or modified as follows: Step 1. From the active display, enter the Tech. Configuration Menu by pressing the Up/Down keys simultaneously. Step 2. Enter password number 1000 and press the Enter key. Step 3. Press the Enter key once to access the Area Factor Menu. Step 4. Enter the new Area Factor using the Up/Down/Left/Right keys. Step 5. Press the Enter key once. Step 6. Press the ESC key twice. Step 7. The active display should now be displayed. Tech. Config. Password: 1000  Area Factor  Area Factor Min Calibration (FT2) Span Calibration Altitude (001.000) If the new Area Factor causes the existing Operating Range Value to be outside the new calculated Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value. This can be accomplished by performing the steps under Section 5.2. See Area Factor Example below. Warning Message: Op Range Outside Allowable Value Reset to MAX F.S. (Press Enter)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 10 Revision Level 012 Area Factor (FT ) (001.000) Area Factor (FT ) Accepted (001.200) Op Range Outside Allowable Value. Reset to Max F.S. (Press Enter) Op Range value within New Min/Max values Op Range value exceeds New Min/Max values Entering a new Area Factor and pressing the Enter button will calculate new Min & Max Op Range values. Warning Message Operating Range (ACFM) (6,000 - 12,000) (12,000) Pressing the Enter button will reset the current Op Range value to the new calculated Max. F.S value which will represent 100% of the process output value. The Op Range value can be changed and will represent 100% of the process output signal (5vdc, 10vdc, or 20mA). -Area Factor Example- 2 2 5.2. OPERATING RANGE The Operating Range allows the user to enter a value which will represent 100% of the process output signal (5VDC, 10VDC, or 20mA). The menu will display the Maximum Full Scale Value possible for the user to enter as the Operating Range. The Operating Range can be changed using the following steps: Step 1. From the active display, enter the Field Menu by pressing and holding the Enter key for 3 seconds. Step 2. Press the Enter key once to access the Operating Range Menu. Step 3. Enter the new Operating Range using Up/Down/Left/Right keys. Step 4. Press the Enter key once. Step 5. Press the ESC key twice. Step 6. The active display should now be displayed. Step 7. The Process Output is automatically rescaled to the new Operating Range. Field Setup Menu  Operating Range  Operating Range Zero Calibration ( ACFM ) Engineering Units (6,000-12,000) Lockdown (010,000)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 11 Revision Level 012 5.3. TEMPERATURE COMPENSATION FOR AIR DENSITY The Temperature Compensation option compensates the flow and velocity signal for density changes caused by variations in the process air temperature. The following menus for configuration of Temperature Compensation are only available if the Temperature Compensation option is purchased. Additionally, an input signal from an external temperature transmitter or the building automation system is required; see Section 3.2 for proper temperature transmitter connection. 5.3.1. Temperature Input Signal Selection To change the input configuration, set the S1 switch as follows: (Refer to Section 3.1 for S1 location on board) Temperature Input S1 Switch Selection 4-20mA mA 0-10VDC V 5.3.2. Temperature Units The Temperature Units Menu allows the user to select the appropriate temperature units for the job. Field Setup Menu  Flow Correction Temperature Units  Units AutoZero Temperature Values (ºF / ºC) Temp Comp.  Temperature Input Display Filter Fixed Value (ºF) 5.3.3. Temperature Values The Temperature Values Menu allows the factory or user to set the minimum and maximum temperature range values that represent the input signal from the external temperature transmitter or the building automation system. Field Setup Menu  Flow Correction Temperature Units Minimum Value AutoZero Temperature Values  (-030) Temp Comp.  Temperature Input Maximum Value Display Filter Fixed Value (130)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 12 Revision Level 012 If the new temperature values cause the existing Operating Range Value to be outside the new calculated Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value. This can be accomplished by performing the steps under Section 5.2. See Temperature Range Example below. Warning Message: Op Range Outside Allowable Value Reset to MAX F.S. (Press Enter) Minimum Value (-000) Maximum Value (000) Op Range Outside Allowable Value. Reset to Max F.S. (Press Enter) Op Range value within New Min/Max values Op Range value exceeds New Min/Max values Entering a new Min & Max Temperature value and pressing the Enter button will calculate new Min & Max Op Range values. Warning Message Operating Range (ACFM) (6,000 - 12,000) (12,000) Pressing the Enter button will reset the current Op Range value to the new calculated Max. F.S value which will represent 100% of the process output value. The Op Range value can be changed and will represent 100% of the process output signal (5vdc, 10vdc, or 20mA). -Temperature Range Example- Minimum Value (-000) Accepted (100)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 13 Revision Level 012 5.3.4. Temperature Input The Temperature Input Menu allows the user to select between three temperature input options (Fixed, Variable, and Net) for the flow calculations. If Fixed is selected the default temperature value entered in the Fixed Value Menu (see Section 5.3.5) is used. The Standard Fixed Value is 68˚F. If Variable is selected an external temperature input signal is required (see Sections 5.3.1 through 5.3.3). If Net is selected, the temperature input signal is obtained through network communications. The Net option is only available if one of the communication options is ordered (see Sections 9.11 through 9.13). The temperature value is only displayed on the LCD screen, if the Temperature Input is set to Variable or Net. Field Setup Menu  Flow Correction Temperature Units Temp. Input AutoZero Temperature Values (Fix/Var/Net) Temp Comp.  Temperature Input  Display Filter Fixed Value (Variable) 5.3.5. Fixed Value The Fixed Value Menu allows the user to enter a temperature value other than the standard value of 68˚F for the flow calculations. This value will not be displayed on the LCD screen. Field Setup Menu  Flow Correction Temperature Units Fixed Value AutoZero Temperature Values (˚F) Temp Comp.  Temperature Input Display Filter Fixed Value  (+068)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 14 Revision Level 012 6. ACTIVE DISPLAYS & KEY FUNCTIONS 6.1. POWER-UP INITIATION DISPLAY Upon initial power-up, Software Revision information will be displayed on the graphic display for approximately 5 seconds. EQ-1 Software Rev. XX.XXX Module Rev. XX.XXX 6.2. PROCESS DISPLAY DESCRIPTIONS After power-up initialization, the following information will appear on the graphic display depending upon the options purchased. * 75˚F * 75˚F * 0.0000 000,000 000,000 AutoZero Inch w.c. High Alarm ACFM Low Alarm ACFM Pressure Monitoring with an Auto Zero Cycle Flow Monitoring with a High Alarm Condition Flow Monitoring with a Low Alarm Condition Number Description 1 Process value 2 Air Flow temperature units in degree F or C (Temperature Compensation Option) 3 Flashing Asterisk indicates the CPU is functioning 4 Engineering units 5 Displayed during an AutoZero cycle (AutoZero Option) 6 Indicating High Alarm Value has been exceeded (High/Low Alarm Option) 7 Indicating Low Alarm Value has been exceeded (High/Low Alarm Option) 1 2 3 4 6 7 5

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 15 Revision Level 012 6.3. KEY FUNCTIONS The following figure and description identify the function of each Key. J1 1 2 3 11 12 13 14 15 16 17 18 4 5 6 7 8 J3 (ALARM OPTION) J2 ON OFF POWER SWITCH ENTER ESC 10 9 LON INPUT TEMP. mA V PROC. OUTPUT mA V 10V 5V S1 S2 S4 2 1 3 4 5 6 7 8 RP1 9 Number Description 1 Enter Key - Allows a user to enter into the Field Menu, enter into a selected menu item, or store into memory changes made to the program. 2 Up Key - Allows the user to scroll up in the menu list to a selected item or increase digits when making value changes. 3 Right Key - When making changes to user values the Right Key allows the user to scroll to the correct digit for changes. 4 Down Key - Allows the user to scroll down in the menu list to a selected item or decrease digits when making value changes. 5 Left Key - When making changes to user values the Left Key allows the user to scroll to the correct digit for changes. 6 Escape Key - The Escape Key allows the user to back out of the menu to the Active Display. If a user starts to make a change and decides to cancel the change, the Escape Key will allow the user to return to the Active Display without making the change. 7 Power Switch – Allows a user to turn power off to the Signal Processor during field wiring or modifications to the device. 8 Lon Switch – Allows a user to send a unique Neuron device ID when connecting to a LonWorks communication network. 9 RP1 – Allows a user to adjust the display contrast.

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 16 Revision Level 012 7. DISPLAY MENUS 7.1. FIELD SETUP & TECH. CONFIGURATION MENUS The following table shows the Field Setup and Tech. Configuration Menus for devices set to monitor Flow, Velocity, and Pressure. The display will vary depending upon the options purchased. MicroTransEQ Setup for Flow or Velocity Field Setup Menu (Press ENTER Key) Tech. Configuration Menu (Press UP/DOWN Keys simultaneously) (Enter Password number 1000) (Press ENTER Key) Operating Range Area Factor Zero Calibration Min Calibration Eng. Units Span Calibration Lockdown Temp Fixed Value Flow Correction Altitude AutoZero (Optional) Output Calibration Temp Comp. (Optional) Correction Coeff. Display Filter 4PT Flow Corr Output Filter MAC Address (Optional) Alarm Options (Optional) Instance Number (Optional) Factory Defaults Modbus ID (Optional) Baud Rate (Optional) MicroTransEQ Setup for Pressure Field Setup Menu (Press ENTER Key) Tech. Configuration Menu (Press UP/DOWN Keys simultaneously) (Enter Password number 1000) (Press ENTER Key) Operating Range Min Calibration Zero Calibration 50% Calibration Eng. Units Span Calibration AutoZero (Optional) Output Calibration Display Filter MAC Address (Optional) Output Filter Instance Number (Optional) Alarm Options (Optional) Modbus ID (Optional) DP Display Format Baud Rate (Optional) Factory Defaults

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 17 Revision Level 012 8. FIELD SETUP MENUS To set parameters under the Field Setup Menus refer to the following procedure, below subsections, and Section 6.3 for Key functions. Step 1. Enter the Field Setup Menu by depressing and holding the Enter Key for 5 seconds. Step 2. Once in the Field Setup Menu, use the Up/Down Keys to highlight the required parameter for configuration as shown in Sections 8.1 through 8.12. Press the Enter Key once to access the highlighted parameter Menu. Step 3. Once in the parameter menu, the parameter can be changed using Up/Down/Left/Right Keys. After the parameter has been changed, press the Enter Key once. Then Press the ESC Key once to return to the Field Setup Menu. Step 4. After all of the required parameters have been configured, exit the Field Setup Menu by pressing the ESC Key. The Process Display (see Section 6.2) will then be displayed. 8.1. OPERATING RANGE The Operating Range allows the user to enter a value which will represent 100% of the process output signal (5VDC, 10VDC, or 20mA). The menu will display the Maximum Full Scale Value possible for the user to enter as the Operating Range. Field Setup Menu  Operating Range  Operating Range Zero Calibration ( ACFM ) Engineering Units (6,000-12,000) Lockdown (010,000) 8.2. ZERO PRESSURE CALIBRATION The Zero Calibration Menu allows the user to perform a zero transducer calibration to eliminate any transducer zero shift. (Caution: Before performing a zero calibration, disconnect the Total (High) and Static (Low) pressure connections, perform a zero calibration and then reconnect the Total and Static pressure connections). Field Setup Menu  Operating Range Input Value CPU Taking Zero Calibration  (0.000) Inch w.c.  Samples Engineering Units Lockdown (Press Enter) (Please Wait)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 18 Revision Level 012 8.3. ENGINEERING UNITS A list of engineering units are available for the user to select from for display purposes to meet customer requirements. Changing the engineering units will affect the process display and the alarm value menus. Field Setup Menu  Operating Range Eng. Units Zero Calibration Engineering Units  (ACFM) Lockdown Standard Flow Units Actual Flow Units Standard Velocity Units Actual Velocity Units Pressure Units SCFM ACFM SFPM AFPM Inch w.c. SCFH L/S Sm/s Am/s Pa SL/S Am3/S % % KPa Sm3/S Am3/M mm w.c. Sm3/M Am3/HR % Sm3/HR % % 8.4. LOCKDOWN Due to the high square root gain associated with very low delta p values, the display and process output are locked to a zero value until the input value reaches the specified Lockdown Value that was entered. Above the Lockdown Value the output is linear to air flow. The following menus are only available if the MicroTransEQ is configured by Paragon at the time of order for flow or velocity. 8.4.1. Lockdown Value The Lockdown Value can be changed from 0 to 20% of Operating Range Value. Lockdown Values can be changed in 1% increments. The recommended standard is 10%. Field Setup Menu  Operating Range Lockdown (0-20%) Zero Calibration (10)% Engineering Units Delay (0-20 sec) Lockdown  (2) Sec

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 19 Revision Level 012 8.4.2. Lockdown Delay The Lockdown Delay Menu allows the user to enter a lockdown time delay (0-20 seconds) that will delay the display and output lockdown from occurring until the flow value or output value has remained below the lockdown value for that duration. Field Setup Menu  Operating Range Lockdown (0-20%) Zero Calibration (10)% Engineering Units Delay (0-20 sec) Lockdown  (2) Sec 8.5. FLOW CORRECTION The Flow Correction Menu was incorporated into the MicroTransEQ to give the user an easy way to make corrections to the display and output without changing the Op. Range Value entered by the factory or user. The Flow Correction Menu would be used to correct for a constant error from zero to the entered Op Range Value. The following menus are only available if the MicroTransEQ is configured by Paragon at the time of order for flow or velocity. 8.5.1. Flow Correction (K-Factor) If the user knows the % change required to match the balancers reading, select the K-Factor Menu and enter this value for the K-Factor. The minimum and maximum allowable K-Factor Value is displayed in the K-Factor Menu. Field Setup Menu  Flow Correction  Flow Correction AutoZero K-Factor  K-Factor Range Temp Comp. (0.85 / 1.3) Display Filter K-Factor Calc. K=(01.000) 8.5.2. Flow Correction (K-Factor Calculator) If the new K-factor Value needs to be calculated, select the K-Factor Calc. Menu, enter the MicroTransEQ Displayed Value and actual Measured Value, press Enter and the % change will be calculated and stored as the new K-Factor Value. Field Setup Menu  Flow Correction  Displayed Value AutoZero K-Factor (000,000) Temp Comp. Measured Value Display Filter K-Factor Calc.  (000,000)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 20 Revision Level 012 -FLOW CORRECTION EXAMPLE- The balancer is consistently measuring a value of 9,500 CFM, which is 500 CFM less than the 10,000 CFM value on the MicroTransEQ display. The user would then perform the following math function: Measured Value / Displayed Value = K-Factor so 9,500 CFM / 10,000 CFM = 0.950. The user would enter 0.950 for the K-Factor Flow Correction. If the K-Factor Calculator is used, the K- Factor Flow Correction would automatically update the K Factor. 8.6. AUTOZERO The AutoZero option detects and corrects any zero offset caused by large ambient temperature changes. The following menus for configuration of AutoZero are only available if the AutoZero option is purchased. 8.6.1. AutoZero Status The AutoZero Status Menu allows the user to turn the AutoZero function ON or OFF. Field Setup Menu  Flow Correction AZ Status  AZ Status AutoZero  AZ Interval (ON/OFF) Temp Comp. AZ Test Interval Display Filter (ON) 8.6.2. AutoZero Interval The AutoZero Interval Menu allows the user to select the AutoZero Interval from once an hour to once a day in 1 hour increments. Use the UP/DOWN keys to select the interval value. Upon device power up, an AutoZero cycle will occur after 20 seconds. Field Setup Menu  Flow Correction AZ Status AZ Interval AutoZero  AZ Interval  (1 TO 24HR) Temp Comp. AZ Test Interval Display Filter (1)HR

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 21 Revision Level 012 8.6.3. AutoZero Test Interval For troubleshooting or testing the AutoZero function, the AutoZero Test Interval Menu allows the user to select an Auto Zero test frequency of once a minute to once every 30 minutes in 1 minute increments. Use the UP/DOWN keys to select the interval value. If AutoZero Test Interval is turned ON for more than 60 minutes, it will automatically default to OFF and the AutoZero Interval (see Section 8.6.2) will be reactivated. Field Setup Menu  Flow Correction AZ Status AZ Test Interval AutoZero  AZ Interval (OFF) Temp Comp. AZ Test Interval  Interval Display Filter (1)Min 8.7. TEMPERATURE COMPENSATION The Temperature Compensation option compensates the flow and velocity signal for density changes caused by variations in the process air temperature. The following menus for configuration of Temperature Compensation are only available if the Temperature Compensation option is purchased. Additionally, an input signal from an external temperature transmitter or the building automation system is required; see Section 3.2 for proper temperature transmitter connection and Section 4.2 for temperature input signal configuration. 8.7.1. Temperature Units The Temperature Units Menu allows the user to select the appropriate temperature units for the job. Field Setup Menu  Flow Correction Temperature Units  Units AutoZero Temperature Values (ºF / ºC) Temp Comp.  Temperature Input Display Filter Fixed Value (ºF)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 22 Revision Level 012 8.7.2. Temperature Values The Temperature Values Menu allows the factory or user to set the minimum and maximum temperature range values that represent the input signal from the external temperature transmitter or the building automation system. Field Setup Menu  Flow Correction Temperature Units Minimum Value AutoZero Temperature Values  (-030) Temp Comp.  Temperature Input Maximum Value Display Filter Fixed Value (130) If the new temperature values cause the existing Operating Range Value to be outside the new calculated Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value. This can be accomplished by performing the steps under Section 5.2. See Temperature Range Example below. Warning Message: Op Range Outside Allowable Value Reset to MAX F.S. (Press Enter) Minimum Value (-000) Maximum Value (000) Op Range Outside Allowable Value. Reset to Max F.S. (Press Enter) Op Range value within New Min/Max values Op Range value exceeds New Min/Max values Entering a new Min & Max Temperature value and pressing the Enter button will calculate new Min & Max Op Range values. Warning Message Operating Range (ACFM) (6,000 - 12,000) (12,000) Pressing the Enter button will reset the current Op Range value to the new calculated Max. F.S value which will represent 100% of the process output value. The Op Range value can be changed and will represent 100% of the process output signal (5vdc, 10vdc, or 20mA). -Temperature Range Example- Minimum Value (-000) Accepted (100)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 23 Revision Level 012 8.7.3. Temperature Input The Temperature Input Menu allows the user to select between three temperature input options (Fixed, Variable, and Net) for the flow calculations. If Fixed is selected the default temperature value entered in the Fixed Value Menu (see Section 5.3.5) is used. The Standard Fixed Value is 68˚F. If Variable is selected an external temperature input signal is required (see Sections 5.3.1 through 5.3.3). If Net is selected, the temperature input signal is obtained through network communications. The Net option is only available if one of the communication options is ordered (see Sections 9.11 through 9.13). The temperature value is only displayed on the LCD screen, if the Temperature Input is set to Variable or Net. Field Setup Menu  Flow Correction Temperature Units Temp. Input AutoZero Temperature Values (Fix/Var/Net) Temp Comp.  Temperature Input  Display Filter Fixed Value (Variable) 8.7.4. Fixed Value The Fixed Value Menu allows the user to enter a temperature value other than the standard value of 68˚F for the flow calculations. This value will not be displayed on the LCD screen. Field Setup Menu  Flow Correction Temperature Units Fixed Value AutoZero Temperature Values (˚F) Temp Comp.  Temperature Input Display Filter Fixed Value  (+068) 8.8. DISPLAY FILTER The Display Filter Menu allows the user to adjust the Display Filter rolling average algorithm by setting the Sample Interval Time value in seconds and the number of rolling average Sample Counts. The adjustment range of the Sample Interval Time is 0.10 to 65.5 seconds in 0.10 increments. The Sample Count range is 0 to 150 Sample Counts. The Display Filter is independent of the Process Output Filter Value (See Section 8.10). Field Setup Menu  Flow Correction Sample Interval Time AutoZero (00.5)sec. Temp Comp. (0-150) Sample Count Display Filter  (010)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 24 Revision Level 012 8.9. PROCESS OUTPUT FILTER The Process Output Filter Menu allows the user to adjust the Process Output Filters rolling average algorithm by setting the Sample Interval Time value in seconds and the number of rolling average Sample Counts. The adjustment range of the Sample Interval Time is 0.10 to 65.5 seconds in 0.10 increments. The Sample Count range is 0 to 150 Sample Counts. The Process Output Filter is independent of the Display Filter Value (See Section 8.8). Field Setup Menu  Output Filter  Sample Interval Time Alarm Options (00.5)sec. DP Display Format (0-150) Sample Count Factory Defaults (010) 8.10. HIGH/LOW ALARM OPTIONS The following menus for configuration of High/Low Alarms are only available if the High/Low Alarm option is purchased. 8.10.1. Alarm Status The Alarm Status allows the user to independently turn each alarm ON or OFF. Field Setup Menu  Output Filter Alarm Status  Low Alarm Alarm Options  Alarm Value (On) DP Display Format Alarm Delay High Alarm Factory Defaults (On)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 25 Revision Level 012 8.10.2. Alarm Values The Alarm Value Menu allows the user to enter the Low or the High flow or pressure alarm value. Alarm values will be displayed in the same engineering units selected in the Eng. Units Menu (see Section 8.3). - High Alarm Function: The High Alarm activates if the flow or pressure exceeds the High Alarm value and resets when the flow or pressure drops below the High Alarm Value. - Low Alarm Function: The Low Alarm activates if the flow or pressure drops below the Low Alarm Value and resets when the flow or pressure exceeds the Low Alarm Value. Field Setup Menu  Output Filter Alarm Status Lo Alarm Value Alarm Options  Alarm Value  (000,000) DP Display Format Alarm Delay Hi Alarm Value Factory Defaults (100,000) 8.10.3. Alarm Delay The Alarm Delay Menu allows the user to enter an alarm delay of 0 to 999 seconds before an alarm will be activated. The alarm will be reset without a delay. Field Setup Menu  Output Filter Alarm Status Lo Alarm Delay Alarm Options  Alarm Value (000)Seconds DP Display Format Alarm Delay  Hi Alarm Delay Factory Defaults (000)Seconds 8.11. DP DISPLAY FORMAT The DP Display Format Menu is only available when the MicroTransEQ is configured by Paragon at the time of order for pressure; it allows the user to change the number of digits shown to the right of the decimal point. Selections are 0 to 4 digits. Use the UP/DOWN keys to move the decimal point to the left or right. Field Setup Menu  Output Filter Number of Digits Alarm Options After Decimal DP Display Format  Point. Factory Defaults (00.000)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 26 Revision Level 012 8.12. FACTORY DEFAULTS If pressure calibration changes have been made incorrectly to the MicroTransEQ program, all pressure calibration values and device settings can be restored to the original factory settings by selecting YES and pressing Enter in both the Set To Factory Defaults Menu and the Verify Set To Factory Defaults Menu (See Factory Defaults table below for a list of Saved Settings). Field Setup Menu  Output Filter Set To Verify Set To Alarm Options Factory Defaults  Factory Defaults DP Display Format Factory Defaults  (No) (No) FACTORY DEFAULTS ITEM SAVED SETTING ITEM SAVED SETTING 1 All Factory Calibration Points (12) 14 MAC Address 2 Area Factor 15 Instance Number 3 Operating Range 16 Engineering Units 4 4 Pt Flow Correction 17 Display Filter Values 5 Altitude 18 Output Filter 6 K-Factor 19 DP Display Format 7 Lockdown & Delay Values 20 Output Calibration 8 Flow Correction 21 AutoZero Status 9 Flow Coefficient 22 AutoZero Interval 10 Min. & Max. Temp Range Values 23 Temp. Units 11 Alarm Status 24 Temp. Input 12 Alarm Values 25 Temp. Fixed Value 13 Alarm Delay 26 Baud Rate

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 27 Revision Level 012 9. TECH CONFIGURATION MENUS To set parameters under the Tech Configuration Menu, refer to the procedure below, associated subsections and Section 6.3 for Key functions. Step 1. Enter the Tech Configuration Menu by pressing and holding the Up/Down Keys simultaneously for 5 seconds. Step 2. Using the Up/Down/Left/Right Keys, enter password number 1000 and press the Enter Key. Step 3. Once in the Tech Configuration Menu, use the Up/Down Keys to highlight the required parameter for configuration as shown in Sections 9.1 through 9.13. Press the Enter Key once to access the highlighted parameter Menu. Step 4. Once in the parameter menu, the parameter can be changed using the Up/Down/Left/Right Keys. After the parameter has been changed, press the Enter Key once. Then Press the ESC Key once to return to the Tech Configuration Menu. Step 5. After all of the required parameters have been configured, exit the Tech Configuration Menu by pressing the ESC Key. The Process Display (see Section 6.2) will then be displayed. 9.1. AREA FACTOR The Area Factor Menu allows the user to enter or modify an existing Area Factor. The Area Factor Menu is only available if the MicroTransEQ is configured by Paragon at the time of order for flow or velocity and for input from a non-amplified Pitot-type flow sensor. Tech. Config. Password: 1000  Area Factor  Area Factor Min Calibration (FT2) 50% Calibration Span Calibration (001.000) If the new Area Factor causes the existing Operating Range Value to be outside the new calculated Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value. This can be accomplished by performing the steps under Section 5.2. See Area Factor Example below. Warning Message: Op Range Outside Allowable Value Reset to MAX F.S. (Press Enter)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 28 Revision Level 012 Area Factor (FT ) (001.000) Area Factor (FT ) Accepted (001.200) Op Range Outside Allowable Value. Reset to Max F.S. (Press Enter) Op Range value within New Min/Max values Op Range value exceeds New Min/Max values Entering a new Area Factor and pressing the Enter button will calculate new Min & Max Op Range values. Warning Message Operating Range (ACFM) (6,000 - 12,000) (12,000) Pressing the Enter button will reset the current Op Range value to the new calculated Max. F.S value which will represent 100% of the process output value. The Op Range value can be changed and will represent 100% of the process output signal (5vdc, 10vdc, or 20mA). -Area Factor Example- 2 2 9.2. MINIMUM CALIBRATION The Minimum Calibration Menu allows a user to perform a minimum transducer calibration. This value will be placed in a different memory location and used until a Return to Factory Defaults is selected (see Section 8.12). (Caution: Before performing a minimum calibration, disconnect the Total (High) and Static (Low) Pressure connections, perform a minimum calibration and then reconnect the Total and Static Pressure connections). Tech. Config. Password: 1000  Area Factor Input Value CPU Taking Min Calibration  (0.0000) Inch W.C.  Samples 50% Calibration Span Calibration (Press Enter) (Please Wait)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 29 Revision Level 012 9.3. 50% CALIBRATION The 50% Calibration Menu is only available when the MicroTransEQ is configured by Paragon at the time of order for pressure; it allows a user to perform a 50% transducer calibration to eliminate zero drift in a bipolar transducer. This value will be placed in a different memory location and used until a Return to Factory Defaults is selected (see Section 8.12). Tech. Config. Password: 1000  Area Factor Input Value CPU Taking Min Calibration (0.0285) inch w.c. Samples 50% Calibration   Span Calibration (Press Enter) (Please Wait) 9.4. SPAN CALIBRATION The Span Calibration Menu allows the user to perform a span transducer calibration to eliminate any possible transducer drift. This value will be placed in a different memory location than the Factory Span memory location and used until a Return to Factory Defaults is selected (see Section 8.12). Tech. Config. Password: 1000  Area Factor Input Value CPU Taking Min Calibration (0.0570) Inch w.c. Samples 50% Calibration  Span Calibration  (Press Enter) (Please Wait) 9.5. TEMPERATURE FIXED VALUE When the Temperature Compensation option (see Section 8.7) is not ordered, the Fixed Value Menu allows the user to enter a temperature value other than the standard value of 68˚F for the density calculations. This value will not be displayed on the LCD screen. Tech. Config. Password: 1000  Temp. Fixed Value  Temp. Fixed Value Altitude ºF Output Calibration (+068) Correction Coeff.

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 30 Revision Level 012 9.6. ALTITUDE The Altitude Menu allows user to enter the specific altitude for the job other than the standard value of 0 feet above mean sea level for the density calculations. Tech. Config. Password: 1000  Temp. Fixed Value Altitude Altitude  Output Calibration (0000)Ft Correction Coeff. If the new Altitude causes the existing Operating Range Value to be outside the new calculated Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value. This can be accomplished by performing the steps under Section 5.2. See Altitude Example below. Warning Message: Op Range Outside Allowable Value Reset to MAX F.S. (Press Enter) Altitude (0000)Ft Op Range Outside Allowable Value. Reset to Max F.S. (Press Enter) Op Range value within New Min/Max values Op Range value exceeds New Min/Max values Entering a new Altitude and pressing the Enter button will calculate new Min & Max Op Range values. Warning Message Operating Range (ACFM) (6,000 - 12,000) (12,000) Pressing the Enter button will reset the current Op Range value to the new calculated Max. F.S value which will represent 100% of the process output value. The Op Range value can be changed and will represent 100% of the process output signal (5vdc, 10vdc or 20mA). -Altitude Example- Altitude Accepted (0100)Ft

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 31 Revision Level 012 9.7. PROCESS OUTPUT CALIBRATION 9.7.1. Minimum Calibration The Minimum Calibration Menu allows the user to make output zero adjustments. Monitor the output and with each Up or Down key depression, the output will increase or decrease by 0.01VDC or 0.01mA depending on output selection. Tech. Config. Password: 1000  Temp. Fixed Value Min Calibration  Use Up/Down Altitude Span Calibration Buttons Output Calibration  Adjust Output Correction Coeff. (Press Enter) 9.7.2. Span Calibration The Span Calibration Menu allows the user to make output span adjustments. Span adjustments require a low pressure air source adjusted to the Full Scale Value shown on the side label. Monitor the output and with each Up or Down key depression, the output will increase or decrease by 0.01VDC or 0.01mA depending on output selection. Tech. Config. Password: 1000  Temp. Fixed Value Min Calibration  Use Up/Down Altitude Span Calibration Buttons Output Calibration  To Adjust Output Correction Coeff. (Press Enter) 9.8. CORRECTION COEFFICIENT The Correction Coefficient Menu is only available if the MicroTransEQ is configured by Paragon at the time of order for flow or velocity. If the MicroTransEQ is configured for input from a non-amplified Pitot-type flow sensor (such as those manufactured by Paragon) the menu in Section 9.8.1 will be displayed. If the MicroTransEQ is configured for input from a piezometer ring or amplified differential pressure flow sensor (manufactured by others) the menu in Section 9.8.2 will be displayed.

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 32 Revision Level 012 9.8.1. Probe Coefficient The Probe Coefficient Menu allows the user to modify the formula constant of 1096.70 for a non- amplified Pitot-type flow sensor. Tech. Config. Password: 1000  Temp. Fixed Value Correction Coeff. Altitude Probe Output Calibration (1096.70) Correction Coeff.  (001,096.70 The probe coefficient entered into the MicroTransEQ is based on the following equation: ܸൌܥ௉ൈඨ∆ܲ ߩ௔ Where: ܸ = Velocity (afpm) ܥ௉ = Non-amplified Pitot-tube Coefficient, 1096.70 ∆ܲ = Differential Pressure Measured by the Pitot-tube (in. w.c.) ߩ௔ = Actual Density (lb/ft3) 9.8.2. Piezometer Ring Coefficient The Piezometer Ring Coefficient Menu allows a user to enter the correction coefficient associated with the piezometer ring or amplified differential pressure flow sensor. Correction coefficients should be obtained from the sensor or air handling unit manufacturer. Tech. Config. Password: 1000  Temp. Fixed Value Correction Coeff. Altitude Piezometer Ring Output Calibration (000000.00) Correction Coeff.  The piezometer ring coefficient entered into the MicroTransEQ is based on the following equation: ܳൌܥ௉ோൈඨ∆ܲ ߩ௔ Where: ܳ = Flow (acfm) ܥ௉ோ = Piezometer Ring Coefficient ∆ܲ = Differential Pressure Measured by the Piezometer Ring (in. w.c.) ߩ௔ = Actual Density of Air (lb/ft3)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 33 Revision Level 012 Since ߩ௔ is known for a given job site, some sensor and air handling unit manufacturers will include this value (or the value for standard air density 0.075 lbm/ft3) in the factor F supplied, simplifying the above equation to: ܳൌܨൈ√∆ܲ Where: ܨൌܥ௉ோ ඥߩ௘ ߩ௘ൌ ߩ௔ or 0.075 (standard density) depending on the sensor or air handling unit manufacturer equation for converting differential pressure to flow. If a F value has been supplied by the fan or air handling unit manufacturer, this value will need to be modified before entering the coefficient into the MicroTransEQ as shown below. ܥ௉ோൌܨൈඥߩ௘ 9.9. FOUR POINT FLOW CORRECTION The Four Point Flow Correction Menu allows the user to make corrections to the display and output signal at 20% increments between 20% and 80% of Operating Range Value entered. The Displayed Value is a fixed value determined by the percentage of Operating Range. The Measured Value is the value determined by an independent balancer’s reading. The Four Point Flow Correction Menu is only available if the MicroTransEQ is configured by Paragon at the time of order for flow or velocity. Tech. Config. Password: 1000  4PT Flow Corr  80,000 CFM Displayed Value MAC Address 60,000 CFM 80,000 Instance Number 40,000 CFM  Measured Value 20,000 CFM 79,500 80,000 CFM Displayed Value 60,000 CFM 60,000 40,000 CFM  Measured Value 20,000 CFM 60,500 80,000 CFM Displayed Value 60,000 CFM 40,000 40,000 CFM  Measured Value 20,000 CFM 40,100 80,000 CFM Displayed Value 60,000 CFM 20,000 40,000 CFM  Measured Value 20,000 CFM 19,500

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 34 Revision Level 012 9.10. MAC ADDRESS (BACNET COMMUNICATION OPTION) When the BACnet Communication option is ordered, the MAC Address Menu allows the user to set a unique device address when connecting to a BACnet network. The default is 02. For additional information refer to the Communication O&M. Tech. Config. Password: 1000  4PT Flow Corr MAC Address MAC Address  (Range = 02 to 254) Instance Number Modbus ID (002) 9.11. INSTANCE NUMBER (BACNET COMMUNICATION OPTION) When the BACnet Communication option is ordered, the Instance Number Menu allows the user to set a unique device address when connecting to a BACnet network. The default is 1002. For additional information refer to the Communication O&M. Tech. Config. Password: 1000  4PT Flow Corr Instance Number MAC Address (Default = 1002) Instance Number  Modbus ID (01002) 9.12. MODBUS ID (MODBUS COMMUNICATION OPTION) When the Modbus Communication option is ordered, the Modbus ID Menu allows the user to set a unique device address when connecting to a Modbus network. The default is 02. For additional information refer to the Communication O&M. Tech. Config. Password: 1000  4PT Flow Corr Modbus ID MAC Address (Range = 01 to 254) Instance Number Modbus ID  (002)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 35 Revision Level 012 9.13. BAUD RATE (BACNET & MODBUS COMMUNICATION OPTIONS) The Baud Rate Menu allows the user to set a unique network baud rate. The current BACnet protocol supports 9.6, 19.2, 38.4 and 76.8 Kbps baud rate. Modbus communications supports 9.6, 19.2, 38.4, 57.6 and 115.2 Kbps baud rate. The default is 38.4 Kbps. For additional information refer to the Communication O&M. Tech. Config. Password: 1000  Baud Rate  Baud Rate (9.6, 19.2, 38.4, 76.8) (38.4) Kbps

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 36 Revision Level 012 10. WARNING MESSAGES 10.1. INPUT PRESSURE OVERRANGE MESSAGE If the input pressure exceeds the entered Operating Range Value, the following message will appear on the display. It will alternate between the process display and the error message until the input falls below the Operating Range Value. - Caution - Input Beyond Operating Range Selected 10.2. TRANSDUCER CALIBRATION MESSAGE If during a transducer zero or span calibration process, the transducer output pressure value measured exceeds ±20% of the expected value, the following message will appear on the display. Once the Enter key is pressed, the display returns to the previous calibration menu. Value entered is Outside Factory set limits (Press Enter) 10.3. OPERATING RANGE MESSAGE If the new values entered for Temperature Compensation, Area Factor, or Altitude (see Sections 8.7, 9.1, and 9.6) causes the Operating Range Value to exceed the new calculated Maximum Full Scale Value, the following message will appear on the display. Op Range Outside Allowable Value. Reset to MAX F.S. (Press Enter)5 10.4. NEW OPERATING RANGE MESSAGE If a user enters a new Operating Range Value, the following message will appear on the display notifying the user that if any 4 PT Flow Correction Values (see Section 9.9) were previously entered, they will be reset. The message allows the user to confirm that the Operating Range change should be made. To complete the Operating Range change, the user must use the UP/Down keys to change the NO to a YES and press the ENTER key. Value will Reset 4PT Flow Correction Values Make the Change (NO) (Press Enter)

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 37 Revision Level 012 11. TROUBLESHOOTING GUIDE TROUBLESHOOTING TABLE SYMPTOM SOLUTION 1. No Display or Back Light 1. Verify ON/OFF switch is in ON position 2. Verify correct input power and connection at 3 pin connector J1 3. Contact Factory 2. Display background is too dark or characters are too light. 1. Adjust RP1 Display potentiometer located in the upper left hand corner of the board. See Section 6.3 3. Display does not respond to input pressure changes and Key pad functions. 1. Reset the unit by turning the ON/OFF switch OFF and back ON. 2. Contact Factory 4. Display does not respond to input pressure changes but does respond to Key pad functions. 1. Verify pneumatic input lines are not reversed at the MicroTransEQ ports or the sensing element. 2. Use a pneumatic gauge to measure the pneumatic signal input to the MicroTransEQ. Verify the signals are within the Op. Range Value shown on the label located on the side of the enclosure. 3. Contact Factory 5. Display does not respond to Key Pad functions 1. Reset the unit by turning the ON/OFF switch to OFF and then ON. 2. Contact Factory 6. CAUTION INPUT OVERRANGE message on Display 1. Verify data on ID Label located on side of MicroTransEQ is correct for the application. 2. Remove pneumatic signal lines. If display returns to 0 reading, use a pneumatic gauge to measure the pneumatic signal. Verify input signal is equal to or less then the Op. Range D.P. Value on the ID Label. If the display does not return to 0, a pneumatic tube may be plugged by moisture underneath the PC board. Consult the factory. 3. Verify menu selections are set correctly: Operating Range, Flow Correction, Temperature Compensation, Area Factor, and Altitude

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 38 Revision Level 012 TROUBLESHOOTING TABLE SYMPTOM SOLUTION 6. Continued 4. If the Temperature Compensation Option is installed, verify correct temperature input signal. Verify that the temperature input is connected correctly. 5. Contact Factory 7. Incorrect Temperature Reading 1. Verify Temperature Transmitter specifications match with MicroTransEQ ID Label (Current/Voltage, Temperature Range) 2. Verify Temperature Transmitter is connected correctly to the MicroTransEQ (see Section 3.2). 3. Verify Temperature Transmitter signal at the MicroTransEQ connector J2 is correct. 4. Contact Factory 8. No Output signal or Incorrect Output signal. Display is reading correct value. 1. Verify Process Output S2 & S4 switches are in the correct position for the application (see Section 4.1 and the figure in Section 3.1. 2. Disconnect Output signal wires and verify output signal at MicroTransEQ connector J2 is correct. 3. Verify correct Operating Range (see Section 5.2) 4. Perform Output Cal (see Section 9.7) 5. Contact Factory 9. Incorrect Process Output Values after changing Area Factor, Altitude, or Temperature Value. Display readings are correct. 1. Re-Enter Operating Range Value in Field Menu (see Section 5.2) 2. Contact Factory 10. Unstable Display and Process Output at very low flow. 1. Increase Display and Process Filter 2. Decrease Lockdown Value 3. Increase Lockdown Delay Value 4. Contact Factory 11. “AZ Error” text on display 1. Turn Power Switch S3 Off and On to reset the AutoZero valve

MicroTransEQ Operation & Maintenance Manual

Paragon Controls Incorporated 39 Revision Level 012 TROUBLESHOOTING TABLE SYMPTOM SOLUTION 11. Continued 2. Check for a pinched tube beneath the main board. (Caution: Remove power before removing board) 3. Contact Factory

Paragon Controls Incorporated

P.O. Box 99, Forestville, CA 95436 http://www.paragoncontrols.com Phone 707 / 579-1424 Revision Level 012