PCI MicroTrans EQ Operation & Maintenance Manual
Text of the manual
Operation & Maintenance Manual
Engineered for accuracy, applicability,
durability and simplicity in HVAC air systems
and industrial process control loops
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
i
Revision Level 012
TABLE OF CONTENTS
TABLE OF CONTENTS ............................................................................................................................. i
1.
INTRODUCTION .............................................................................................................................. 1
1.1.
DESCRIPTION ............................................................................................................................ 1
1.2.
BASIC OPERATION .................................................................................................................. 1
1.3.
SPECIFICATIONS ...................................................................................................................... 1
1.3.1.
Power Supply ........................................................................................................................ 1
1.3.2.
Power Consumption .............................................................................................................. 1
1.3.3.
Accuracy ............................................................................................................................... 1
1.3.4.
Temperature Input Options ................................................................................................... 1
1.3.5.
Process Output Options......................................................................................................... 1
1.3.6.
High/Low Alarm Relay Outputs ........................................................................................... 2
1.4.
SAFETY ....................................................................................................................................... 2
1.4.1.
Electrical Connections .......................................................................................................... 2
1.4.2.
Static Electricity .................................................................................................................... 2
2.
PRODUCT DIMENSIONS ................................................................................................................ 3
2.1.
NEMA 1 MECHANICAL DIMENSIONS .................................................................................. 3
2.2.
NEMA 4 MECHANICAL DIMENSIONS .................................................................................. 4
3.
INSTALLATION ............................................................................................................................... 5
3.1.
ELECTRICAL & PNEUMATIC INSTALLATION ................................................................... 5
3.2.
TEMPERATURE TRANSMITTER CONNECTION ................................................................. 6
3.2.1.
4-20mA Output/2-Wire Loop Powered Temperature Transmitter ....................................... 6
3.2.2.
0-10VDC Output/24VAC Power 3-Wire Temperature Transmitter .................................... 6
3.2.3.
0-10VDC Output/24VDC Power 3-Wire Temperature Transmitter .................................... 7
3.2.4.
0-10VDC or 4-20mA from a Building Management System (BMS) ................................... 7
4.
INPUT/OUTPUT SET-UP ................................................................................................................. 8
4.1.
PROCESS OUTPUT .................................................................................................................... 8
4.2.
TEMPERATURE INPUT (OPTION) .......................................................................................... 8
5.
COMMON STARTUP CONFIGURATION CHANGES.................................................................. 9
5.1.
AREA FACTOR .......................................................................................................................... 9
5.2.
OPERATING RANGE .............................................................................................................. 10
5.3.
TEMPERATURE COMPENSATION FOR AIR DENSITY .................................................... 11
5.3.1.
Temperature Input Signal Selection.................................................................................... 11
5.3.2.
Temperature Units .............................................................................................................. 11
5.3.3.
Temperature Values ............................................................................................................ 11
5.3.4.
Temperature Input ............................................................................................................... 13
5.3.5.
Fixed Value ......................................................................................................................... 13
6.
ACTIVE DISPLAYS & KEY FUNCTIONS ................................................................................... 14
6.1.
POWER-UP INITIATION DISPLAY ....................................................................................... 14
6.2.
PROCESS DISPLAY DESCRIPTIONS ................................................................................... 14
6.3.
KEY FUNCTIONS .................................................................................................................... 15
7.
DISPLAY MENUS ........................................................................................................................... 16
7.1.
FIELD SETUP & TECH. CONFIGURATION MENUS .......................................................... 16
8.
FIELD SETUP MENUS ................................................................................................................... 17
8.1.
OPERATING RANGE .............................................................................................................. 17
8.2.
ZERO PRESSURE CALIBRATION ......................................................................................... 17
8.3.
ENGINEERING UNITS ............................................................................................................ 18
8.4.
LOCKDOWN ............................................................................................................................. 18
8.4.1.
Lockdown Value ................................................................................................................. 18
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
ii
Revision Level 012
8.4.2.
Lockdown Delay ................................................................................................................. 19
8.5.
FLOW CORRECTION .............................................................................................................. 19
8.5.1.
Flow Correction (K-Factor) ................................................................................................ 19
8.5.2.
Flow Correction (K-Factor Calculator) .............................................................................. 19
8.6.
AUTOZERO .............................................................................................................................. 20
8.6.1.
AutoZero Status .................................................................................................................. 20
8.6.2.
AutoZero Interval ................................................................................................................ 20
8.6.3.
AutoZero Test Interval ........................................................................................................ 21
8.7.
TEMPERATURE COMPENSATION ...................................................................................... 21
8.7.1.
Temperature Units .............................................................................................................. 21
8.7.2.
Temperature Values ............................................................................................................ 22
8.7.3.
Temperature Input ............................................................................................................... 23
8.7.4.
Fixed Value ......................................................................................................................... 23
8.8.
DISPLAY FILTER .................................................................................................................... 23
8.9.
PROCESS OUTPUT FILTER ................................................................................................... 24
8.10.
HIGH/LOW ALARM OPTIONS ........................................................................................... 24
8.10.1.
Alarm Status .................................................................................................................... 24
8.10.2.
Alarm Values................................................................................................................... 25
8.10.3.
Alarm Delay .................................................................................................................... 25
8.11.
DP DISPLAY FORMAT ....................................................................................................... 25
8.12.
FACTORY DEFAULTS ........................................................................................................ 26
9.
TECH CONFIGURATION MENUS ............................................................................................... 27
9.1.
AREA FACTOR ........................................................................................................................ 27
9.2.
MINIMUM CALIBRATION ..................................................................................................... 28
9.3.
50% CALIBRATION ................................................................................................................ 29
9.4.
SPAN CALIBRATION .............................................................................................................. 29
9.5.
TEMPERATURE FIXED VALUE ........................................................................................... 29
9.6.
ALTITUDE ................................................................................................................................ 30
9.7.
PROCESS OUTPUT CALIBRATION ...................................................................................... 31
9.7.1.
Minimum Calibration .......................................................................................................... 31
9.7.2.
Span Calibration.................................................................................................................. 31
9.8.
CORRECTION COEFFICIENT ................................................................................................ 31
9.8.1.
Probe Coefficient ................................................................................................................ 32
9.8.2.
Piezometer Ring Coefficient ............................................................................................... 32
9.9.
FOUR POINT FLOW CORRECTION...................................................................................... 33
9.10.
MAC ADDRESS (BACNET COMMUNICATION OPTION) ............................................. 34
9.11.
INSTANCE NUMBER (BACNET COMMUNICATION OPTION) ................................... 34
9.12.
MODBUS ID (MODBUS COMMUNICATION OPTION).................................................. 34
9.13.
BAUD RATE (BACNET & MODBUS COMMUNICATION OPTIONS) .......................... 35
10.
WARNING MESSAGES .............................................................................................................. 36
10.1.
INPUT PRESSURE OVERRANGE MESSAGE .................................................................. 36
10.2.
TRANSDUCER CALIBRATION MESSAGE ...................................................................... 36
10.3.
OPERATING RANGE MESSAGE ....................................................................................... 36
10.4.
NEW OPERATING RANGE MESSAGE ............................................................................. 36
11.
TROUBLESHOOTING GUIDE ................................................................................................... 37
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
1
Revision Level 012
1. INTRODUCTION
1.1.
DESCRIPTION
The MicroTransEQ Signal Processor employs current state-of-the-art digital microprocessor technology
to produce highly stable and accurate differential pressure and air flow measurements. The
MicroTransEQ is factory configured and calibrated to the exact specification determined at time of order.
Simple field configuration of engineering units, operating range, process noise filtering, alarm set points,
etc., are performed via password protected intuitive menus that are accessed through the integral six
button touch pad. Device monitoring and configuration can also be performed by a building
management system through a LonWorks®, BACnet®-MS/TP Master, or Modbus® Slave
communication network. Optional features include AutoZero; High/Low Remote Alarms; Temperature
Compensation; and LonWorks®, BACnet®-MS/TP Master, and Modbus® Slave communication.
1.2.
BASIC OPERATION
The transducer receives a differential pressure signal from the pressure or flow sensing element. This
signal is scaled and linearized before being displayed and transmitted out as a 4-20mA, 0-5VDC, or 0-
10VDC signal.
The AutoZero option detects and corrects any zero offset caused by large ambient temperature changes.
The Temperature Compensation option compensates the flow and velocity signal for density changes
caused by variations in the process air temperature. An external temperature transmitter or input signal
from the building management system is required.
1.3.
SPECIFICATIONS
1.3.1. Power Supply
20 to 28 VAC/DC
1.3.2. Power Consumption
Standard Unit: 216mA at 24VAC
150mA at 24VDC
Full Options:
250mA at 24VAC
175mA at 24VDC
1.3.3. Accuracy
±0.25% full scale (Standard)
±0.10% full scale (Optional)
1.3.4. Temperature Input Options
0-10VDC
4-20mA
1.3.5. Process Output Options
0-5VDC
0-10VDC
4-20mA (700Ω maximum load)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
2
Revision Level 012
1.3.6. High/Low Alarm Relay Outputs
Two single (1 form C) dry contacts rated for:
5 amps at 30VAC/DC
10 amps at 120VAC
1.4.
SAFETY
1.4.1. Electrical Connections
Before any electrical connections are made, ensure the POWER SWITCH is in the OFF position.
1.4.2. Static Electricity
The circuit board contains components which are susceptible to damage caused by static electrical
discharge. Should it be necessary to remove the circuit board from the enclosure, appropriate
precautions must first be taken to ensure that the operator and the circuit board are at the same electrical
potential.
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
3
Revision Level 012
2. PRODUCT DIMENSIONS
2.1.
NEMA 1 MECHANICAL DIMENSIONS
2.265"
7.625"
PG21(3/4")
PG13.5(1/2") - TYP OF 3
1,225
CONTROLS
INCORPORATED
PARAGON
PCI
ACFM
SIGNAL PROCESSOR
MicroTrans
4.625"
75 F
*
EQ
3.500"
8.250"
0.20" DIA (TYP OF 4)
I.D./DATA LABEL
1.4"
1.2"
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
4
Revision Level 012
2.2.
NEMA 4 MECHANICAL DIMENSIONS
PG21(3/4")
PG13.5(1/2")
PG13.5(1/2")
MOUNTING SCREW DIA. UP TO 1/4".
8.2"
(TYP OF 2)
PG13.5(1/2")
STANDARD
1/4" COMPRESSION OPTION
5.0"
I.D./DATA LABEL
PARAGON
INCORPORATED
CONTROLS
PCI
MicroTrans
SIGNAL PROCESSOR
1,225
75 F
ACFM
EQ
*
7.0"
3.12"
9.56"
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
5
Revision Level 012
3. INSTALLATION
3.1.
ELECTRICAL & PNEUMATIC INSTALLATION
-
NEMA 1 & 4 Option - Remove the cover by turning each corner cover mounting screw
counter clockwise.
-
Both NEMA 1 & NEMA 4 enclosures incorporate three 1/2 inch conduit connections and
one 3/4 inch conduit connection to interface all electrical wiring and pneumatic tubing to the
device. Determine which conduit connection will be used and remove the black plug and
install the appropriate conduit fitting (By Others).
-
The three electrical connectors (J1, J2, and J3) located on the MicroTransEQ board have
removable terminal blocks for ease of installing the interface wiring. (Caution - All electrical
connections must be made with the MicroTransEQ power switch in the OFF position).
J1
1
2
3
11 12 13 14 15 16 17 18
4 5
6
7
8
J3 (ALARM OPTION)
J2
ON
OFF
POWER
SWITCH
ENTER
ESC
10
9
LON
INPUT
TEMP.
mA
V
PROC.
OUTPUT
mA
V
10V
5V
(24VAC/DC)
POWER SUPPLY
ANALOG RECEIVING DEVICE
PROCESS OUTPUT
S1
S2 S4
+
-
+ 24VDC OUTPUT POWER
- TEMPERATURE INPUT(GND)
+ TEMPERATURE INPUT
+ NETWORK COMMUNICATIONS
- NETWORK COMMUNICATIONS
- ANALOG PROCESS OUTPUT(GND)
+ ANALOG PROCESS OUTPUT
8
10
9
EARTH GROUND
1
24VAC / DC
3
2
J1
4
6
7
5
J2
J3 (ALARM OPTION)
15
17
18
16
11
13
14
12
NC
LOW ALARM
NO
NC
COM
PURGE HOLD
HIGH ALARM
COM
NO
TYPICAL FLOW ELEMENT CONNECTION
CONNECTION
TOTAL (HIGH)
PRESSURE
CONNECTION
PRESSURE
STATIC (LOW)
Tp CONNECTION
FE-1000
Sp CONNECTION
REFER TO SECTION 2.4 FOR
PROPER TEMPERATURE
TRANSMITTER CONNECTION
SWITCH POSITIONS
SHOWN IN BLACK
S1 POSITION
INDICATING 4-20mA
TEMPERATURE INPUT
S2 AND S4 POSITIONS
INDICATING 0-10VDC
PROCESS OUTPUT
RP1
S3
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
6
Revision Level 012
3.2.
TEMPERATURE TRANSMITTER CONNECTION
Shielded cable is recommended for all connections between the MicroTransEQ and the Temperature
Transmitter.
3.2.1. 4-20mA Output/2-Wire Loop Powered Temperature Transmitter
J1
1
2
3
11 12 13 14 15 16 17 18
4 5
6
7
8
J3 (ALARM OPTION)
J2
ON
OFF
POWER
SWITCH
ENTER
ESC
10
9
LON
INPUT
TEMP.
mA
V
PROC.
OUTPUT
mA
V
10V
5V
(4-20mA LOOP
POWERED)
+
-
TRANSMITTER
S1
S2 S4
+ 24VDC OUTPUT POWER
- TEMPERATURE INPUT(GND)
+ TEMPERATURE INPUT
+ NETWORK COMMUNICATIONS
- NETWORK COMMUNICATIONS
- PROCESS OUTPUT(GND)
+ PROCESS OUTPUT
8
10
9
4
6
7
5
J2
TEMPERATURE
S1 SET TO
mA POSITION
3.2.2. 0-10VDC Output/24VAC Power 3-Wire Temperature Transmitter
J1
1
2
3
11 12 13 14 15 16 17 18
4 5
6
7
8
J3 (ALARM OPTION)
J2
ON
OFF
POWER
SWITCH
ENTER
ESC
10
9
LON
INPUT
TEMP.
mA
V
PROC.
OUTPUT
mA
V
10V
5V
S1
S2 S4
-
O
+ 24VDC OUTPUT POWER
- TEMPERATURE INPUT(GND)
+ TEMPERATURE INPUT
+ NETWORK COMMUNICATIONS
- NETWORK COMMUNICATIONS
- PROCESS OUTPUT(GND)
+ PROCESS OUTPUT
8
10
9
4
6
7
5
J2
TEMP. TRANSMITTER
(24VAC POWERED
/ 0-10VDC OUTPUT)
24VAC
POWER
SOURCE
+
-
+
S1 SET TO
V POSITION
Note: If the MicroTransEQ power source is 24VAC, the same power source can be used to power the
Temperature Transmitter.
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
7
Revision Level 012
3.2.3. 0-10VDC Output/24VDC Power 3-Wire Temperature Transmitter
J1
1
2
3
11 12 13 14 15 16 17 18
4 5
6
7
8
J3 (ALARM OPTION)
J2
ON
OFF
POWER
SWITCH
ENTER
ESC
10
9
LON
INPUT
TEMP.
mA
V
PROC.
OUTPUT
mA
V
10V
5V
S1
S2 S4
-
O
+ 24VDC OUTPUT POWER
- TEMPERATURE INPUT(GND)
+ TEMPERATURE INPUT
+ NETWORK COMMUNICATIONS
- NETWORK COMMUNICATIONS
- PROCESS OUTPUT(GND)
+ PROCESS OUTPUT
8
10
9
4
6
7
5
J2
TEMP. TRANSMITTER
(24VDC POWERED
/ 0-10VDC OUTPUT)
+
S1 SET TO
V POSITION
3.2.4. 0-10VDC or 4-20mA from a Building Management System (BMS)
J1
1
2
3
11 12 13 14 15 16 17 18
4 5
6
7
8
J3 (ALARM OPTION)
J2
ON
OFF
POWER
SWITCH
ENTER
ESC
10
9
LON
INPUT
TEMP.
mA
V
PROC.
OUTPUT
mA
V
10V
5V
S1
S2 S4
-
+ 24VDC OUTPUT POWER
- TEMPERATURE INPUT(GND)
+ TEMPERATURE INPUT
+ NETWORK COMMUNICATIONS
- NETWORK COMMUNICATIONS
- PROCESS OUTPUT(GND)
+ PROCESS OUTPUT
8
10
9
4
6
7
5
J2
TEMPERATURE. SIGNAL
FROM BMS SYSTEM
(0-10VDC / 4-20mA)
+
VERIFY CORRECT
S1 POSITION.
S1 UP=mA
S1 DOWN=V
Note: Verify Temperature Input switch (S1) position matches the input signal type (refer to Section 4.2).
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
8
Revision Level 012
4. INPUT/OUTPUT SET-UP
The MicroTransEQ has been configured and calibrated at the factory for the specific application. Refer
to the MicroTransEQ Set-Up label located on the left side of unit to verify correct Input/Output
configuration for the application. If input or output configuration changes are required refer to the tables
in the sections below and the figure in Section 3.1.
4.1.
PROCESS OUTPUT
To change the output configuration, set the S2 & S4 switches as follows:
Process Output
Range
S2
S4
Current
4-20mA
NA
mA
Voltage
0-10VDC
10V
V
Voltage
0-5VDC
5V
V
4.2.
TEMPERATURE INPUT (OPTION)
To change the input configuration, set the S1 switch as follows:
Temperature Input
S1 Switch Selection
4-20mA
mA
0-10VDC
V
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
9
Revision Level 012
5. COMMON STARTUP CONFIGURATION CHANGES
5.1.
AREA FACTOR
The Area Factor can be entered or modified as follows:
Step 1. From the active display, enter the Tech. Configuration Menu by pressing the Up/Down
keys simultaneously.
Step 2. Enter password number 1000 and press the Enter key.
Step 3. Press the Enter key once to access the Area Factor Menu.
Step 4. Enter the new Area Factor using the Up/Down/Left/Right keys.
Step 5. Press the Enter key once.
Step 6. Press the ESC key twice.
Step 7. The active display should now be displayed.
Tech. Config.
Password: 1000
Area Factor
Area Factor
Min Calibration
(FT2)
Span Calibration
Altitude
(001.000)
If the new Area Factor causes the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Area Factor Example below.
Warning Message:
Op Range Outside
Allowable Value
Reset to MAX F.S.
(Press Enter)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
10
Revision Level 012
Area Factor
(FT )
(001.000)
Area Factor
(FT )
Accepted
(001.200)
Op Range Outside
Allowable Value.
Reset to Max F.S.
(Press Enter)
Op Range value within
New Min/Max values
Op Range value exceeds
New Min/Max values
Entering a new Area
Factor and pressing
the Enter button will
calculate new Min &
Max Op Range values.
Warning Message
Operating Range
(ACFM)
(6,000 - 12,000)
(12,000)
Pressing the Enter button
will reset the current Op
Range value to the new
calculated Max. F.S value
which will represent 100%
of the process output value.
The Op Range value can be
changed and will represent
100% of the process output
signal (5vdc, 10vdc, or 20mA).
-Area Factor Example-
2
2
5.2.
OPERATING RANGE
The Operating Range allows the user to enter a value which will represent 100% of the process output
signal (5VDC, 10VDC, or 20mA). The menu will display the Maximum Full Scale Value possible for
the user to enter as the Operating Range. The Operating Range can be changed using the following
steps:
Step 1. From the active display, enter the Field Menu by pressing and holding the Enter key for
3 seconds.
Step 2. Press the Enter key once to access the Operating Range Menu.
Step 3. Enter the new Operating Range using Up/Down/Left/Right keys.
Step 4. Press the Enter key once.
Step 5. Press the ESC key twice.
Step 6. The active display should now be displayed.
Step 7. The Process Output is automatically rescaled to the new Operating Range.
Field Setup
Menu
Operating Range
Operating Range
Zero Calibration
( ACFM )
Engineering Units
(6,000-12,000)
Lockdown
(010,000)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
11
Revision Level 012
5.3.
TEMPERATURE COMPENSATION FOR AIR DENSITY
The Temperature Compensation option compensates the flow and velocity signal for density changes
caused by variations in the process air temperature. The following menus for configuration of
Temperature Compensation are only available if the Temperature Compensation option is purchased.
Additionally, an input signal from an external temperature transmitter or the building automation system
is required; see Section 3.2 for proper temperature transmitter connection.
5.3.1. Temperature Input Signal Selection
To change the input configuration, set the S1 switch as follows:
(Refer to Section 3.1 for S1 location on board)
Temperature Input
S1 Switch Selection
4-20mA
mA
0-10VDC
V
5.3.2. Temperature Units
The Temperature Units Menu allows the user to select the appropriate temperature units for the job.
Field Setup
Menu
Flow Correction
Temperature Units
Units
AutoZero
Temperature Values
(ºF / ºC)
Temp Comp.
Temperature Input
Display Filter
Fixed Value
(ºF)
5.3.3. Temperature Values
The Temperature Values Menu allows the factory or user to set the minimum and maximum temperature
range values that represent the input signal from the external temperature transmitter or the building
automation system.
Field Setup
Menu
Flow Correction
Temperature Units
Minimum Value
AutoZero
Temperature Values
(-030)
Temp Comp.
Temperature Input
Maximum Value
Display Filter
Fixed Value
(130)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
12
Revision Level 012
If the new temperature values cause the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Temperature Range Example
below.
Warning Message:
Op Range Outside
Allowable Value
Reset to MAX F.S.
(Press Enter)
Minimum Value
(-000)
Maximum Value
(000)
Op Range Outside
Allowable Value.
Reset to Max F.S.
(Press Enter)
Op Range value within
New Min/Max values
Op Range value exceeds
New Min/Max values
Entering a new Min &
Max Temperature
value and pressing the
Enter button will
calculate new Min &
Max Op Range values.
Warning Message
Operating Range
(ACFM)
(6,000 - 12,000)
(12,000)
Pressing the Enter button
will reset the current Op
Range value to the new
calculated Max. F.S value
which will represent 100%
of the process output value.
The Op Range value can be
changed and will represent
100% of the process output
signal (5vdc, 10vdc, or 20mA).
-Temperature Range Example-
Minimum Value
(-000)
Accepted
(100)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
13
Revision Level 012
5.3.4. Temperature Input
The Temperature Input Menu allows the user to select between three temperature input options (Fixed,
Variable, and Net) for the flow calculations. If Fixed is selected the default temperature value entered in
the Fixed Value Menu (see Section 5.3.5) is used. The Standard Fixed Value is 68˚F. If Variable is
selected an external temperature input signal is required (see Sections 5.3.1 through 5.3.3). If Net is
selected, the temperature input signal is obtained through network communications. The Net option is
only available if one of the communication options is ordered (see Sections 9.11 through 9.13). The
temperature value is only displayed on the LCD screen, if the Temperature Input is set to Variable or
Net.
Field Setup
Menu
Flow Correction
Temperature Units
Temp. Input
AutoZero
Temperature Values
(Fix/Var/Net)
Temp Comp.
Temperature Input
Display Filter
Fixed Value
(Variable)
5.3.5. Fixed Value
The Fixed Value Menu allows the user to enter a temperature value other than the standard value of 68˚F
for the flow calculations. This value will not be displayed on the LCD screen.
Field Setup
Menu
Flow Correction
Temperature Units
Fixed Value
AutoZero
Temperature Values
(˚F)
Temp Comp.
Temperature Input
Display Filter
Fixed Value
(+068)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
14
Revision Level 012
6. ACTIVE DISPLAYS & KEY FUNCTIONS
6.1.
POWER-UP INITIATION DISPLAY
Upon initial power-up, Software Revision information will be displayed on the graphic display for
approximately 5 seconds.
EQ-1
Software Rev. XX.XXX
Module Rev. XX.XXX
6.2.
PROCESS DISPLAY DESCRIPTIONS
After power-up initialization, the following information will appear on the graphic display depending
upon the options purchased.
*
75˚F *
75˚F *
0.0000
000,000
000,000
AutoZero Inch w.c.
High Alarm ACFM
Low Alarm ACFM
Pressure Monitoring with an
Auto Zero Cycle
Flow Monitoring with a
High Alarm Condition
Flow Monitoring with a
Low Alarm Condition
Number
Description
1
Process value
2
Air Flow temperature units in degree F or C (Temperature Compensation Option)
3
Flashing Asterisk indicates the CPU is functioning
4
Engineering units
5
Displayed during an AutoZero cycle (AutoZero Option)
6
Indicating High Alarm Value has been exceeded (High/Low Alarm Option)
7
Indicating Low Alarm Value has been exceeded (High/Low Alarm Option)
1
2
3
4
6
7
5
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
15
Revision Level 012
6.3.
KEY FUNCTIONS
The following figure and description identify the function of each Key.
J1
1
2
3
11 12 13 14 15 16 17 18
4 5
6
7
8
J3 (ALARM OPTION)
J2
ON
OFF
POWER
SWITCH
ENTER
ESC
10
9
LON
INPUT
TEMP.
mA
V
PROC.
OUTPUT
mA
V
10V
5V
S1
S2
S4
2
1
3
4
5
6
7
8
RP1
9
Number
Description
1
Enter Key - Allows a user to enter into the Field Menu, enter into a selected menu item, or
store into memory changes made to the program.
2
Up Key - Allows the user to scroll up in the menu list to a selected item or increase digits when
making value changes.
3
Right Key - When making changes to user values the Right Key allows the user to scroll to the
correct digit for changes.
4
Down Key - Allows the user to scroll down in the menu list to a selected item or decrease digits
when making value changes.
5
Left Key - When making changes to user values the Left Key allows the user to scroll to the
correct digit for changes.
6
Escape Key - The Escape Key allows the user to back out of the menu to the Active Display. If
a user starts to make a change and decides to cancel the change, the Escape Key will allow the
user to return to the Active Display without making the change.
7
Power Switch – Allows a user to turn power off to the Signal Processor during field wiring or
modifications to the device.
8
Lon Switch – Allows a user to send a unique Neuron device ID when connecting to a
LonWorks communication network.
9
RP1 – Allows a user to adjust the display contrast.
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
16
Revision Level 012
7. DISPLAY MENUS
7.1.
FIELD SETUP & TECH. CONFIGURATION MENUS
The following table shows the Field Setup and Tech. Configuration Menus for devices set to monitor
Flow, Velocity, and Pressure. The display will vary depending upon the options purchased.
MicroTransEQ Setup for Flow or Velocity
Field Setup Menu
(Press ENTER Key)
Tech. Configuration Menu
(Press UP/DOWN Keys simultaneously)
(Enter Password number 1000)
(Press ENTER Key)
Operating Range
Area Factor
Zero Calibration
Min Calibration
Eng. Units
Span Calibration
Lockdown
Temp Fixed Value
Flow Correction
Altitude
AutoZero (Optional)
Output Calibration
Temp Comp. (Optional)
Correction Coeff.
Display Filter
4PT Flow Corr
Output Filter
MAC Address (Optional)
Alarm Options (Optional)
Instance Number (Optional)
Factory Defaults
Modbus ID (Optional)
Baud Rate (Optional)
MicroTransEQ Setup for Pressure
Field Setup Menu
(Press ENTER Key)
Tech. Configuration Menu
(Press UP/DOWN Keys simultaneously)
(Enter Password number 1000)
(Press ENTER Key)
Operating Range
Min Calibration
Zero Calibration
50% Calibration
Eng. Units
Span Calibration
AutoZero (Optional)
Output Calibration
Display Filter
MAC Address (Optional)
Output Filter
Instance Number (Optional)
Alarm Options (Optional)
Modbus ID (Optional)
DP Display Format
Baud Rate (Optional)
Factory Defaults
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
17
Revision Level 012
8. FIELD SETUP MENUS
To set parameters under the Field Setup Menus refer to the following procedure, below subsections, and
Section 6.3 for Key functions.
Step 1.
Enter the Field Setup Menu by depressing and holding the Enter Key for 5
seconds.
Step 2.
Once in the Field Setup Menu, use the Up/Down Keys to highlight the required
parameter for configuration as shown in Sections 8.1 through 8.12. Press the Enter
Key once to access the highlighted parameter Menu.
Step 3.
Once in the parameter menu, the parameter can be changed using
Up/Down/Left/Right Keys. After the parameter has been changed, press the Enter
Key once. Then Press the ESC Key once to return to the Field Setup Menu.
Step 4.
After all of the required parameters have been configured, exit the Field Setup
Menu by pressing the ESC Key. The Process Display (see Section 6.2) will then
be displayed.
8.1.
OPERATING RANGE
The Operating Range allows the user to enter a value which will represent 100% of the process output
signal (5VDC, 10VDC, or 20mA). The menu will display the Maximum Full Scale Value possible for
the user to enter as the Operating Range.
Field Setup
Menu
Operating Range
Operating Range
Zero Calibration
( ACFM )
Engineering Units
(6,000-12,000)
Lockdown
(010,000)
8.2.
ZERO PRESSURE CALIBRATION
The Zero Calibration Menu allows the user to perform a zero transducer calibration to eliminate any
transducer zero shift.
(Caution: Before performing a zero calibration, disconnect the Total (High) and Static (Low)
pressure connections, perform a zero calibration and then reconnect the Total and Static pressure
connections).
Field Setup
Menu
Operating Range
Input Value
CPU Taking
Zero Calibration
(0.000) Inch w.c.
Samples
Engineering Units
Lockdown
(Press Enter)
(Please Wait)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
18
Revision Level 012
8.3.
ENGINEERING UNITS
A list of engineering units are available for the user to select from for display purposes to meet customer
requirements. Changing the engineering units will affect the process display and the alarm value menus.
Field Setup
Menu
Operating Range
Eng. Units
Zero Calibration
Engineering Units
(ACFM)
Lockdown
Standard
Flow
Units
Actual
Flow
Units
Standard
Velocity
Units
Actual
Velocity
Units
Pressure
Units
SCFM
ACFM
SFPM
AFPM
Inch w.c.
SCFH
L/S
Sm/s
Am/s
Pa
SL/S
Am3/S
%
%
KPa
Sm3/S
Am3/M
mm w.c.
Sm3/M
Am3/HR
%
Sm3/HR
%
%
8.4.
LOCKDOWN
Due to the high square root gain associated with very low delta p values, the display and process output
are locked to a zero value until the input value reaches the specified Lockdown Value that was entered.
Above the Lockdown Value the output is linear to air flow. The following menus are only available if
the MicroTransEQ is configured by Paragon at the time of order for flow or velocity.
8.4.1. Lockdown Value
The Lockdown Value can be changed from 0 to 20% of Operating Range Value. Lockdown Values can
be changed in 1% increments. The recommended standard is 10%.
Field Setup
Menu
Operating Range
Lockdown (0-20%)
Zero Calibration
(10)%
Engineering Units
Delay (0-20 sec)
Lockdown
(2) Sec
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
19
Revision Level 012
8.4.2. Lockdown Delay
The Lockdown Delay Menu allows the user to enter a lockdown time delay (0-20 seconds) that will
delay the display and output lockdown from occurring until the flow value or output value has remained
below the lockdown value for that duration.
Field Setup
Menu
Operating Range
Lockdown (0-20%)
Zero Calibration
(10)%
Engineering Units
Delay (0-20 sec)
Lockdown
(2) Sec
8.5.
FLOW CORRECTION
The Flow Correction Menu was incorporated into the MicroTransEQ to give the user an easy way to
make corrections to the display and output without changing the Op. Range Value entered by the factory
or user. The Flow Correction Menu would be used to correct for a constant error from zero to the
entered Op Range Value. The following menus are only available if the MicroTransEQ is configured by
Paragon at the time of order for flow or velocity.
8.5.1. Flow Correction (K-Factor)
If the user knows the % change required to match the balancers reading, select the K-Factor Menu and
enter this value for the K-Factor. The minimum and maximum allowable K-Factor Value is displayed in
the K-Factor Menu.
Field Setup
Menu
Flow Correction
Flow Correction
AutoZero
K-Factor
K-Factor Range
Temp Comp.
(0.85 / 1.3)
Display Filter
K-Factor Calc.
K=(01.000)
8.5.2. Flow Correction (K-Factor Calculator)
If the new K-factor Value needs to be calculated, select the K-Factor Calc. Menu, enter the
MicroTransEQ Displayed Value and actual Measured Value, press Enter and the % change will be
calculated and stored as the new K-Factor Value.
Field Setup
Menu
Flow Correction
Displayed Value
AutoZero
K-Factor
(000,000)
Temp Comp.
Measured Value
Display Filter
K-Factor Calc.
(000,000)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
20
Revision Level 012
-FLOW CORRECTION EXAMPLE-
The balancer is consistently measuring a value of 9,500 CFM, which is 500 CFM less than the 10,000
CFM value on the MicroTransEQ display. The user would then perform the following math function:
Measured Value / Displayed Value = K-Factor so 9,500 CFM / 10,000 CFM = 0.950. The user would
enter 0.950 for the K-Factor Flow Correction. If the K-Factor Calculator is used, the K- Factor Flow
Correction would automatically update the K Factor.
8.6.
AUTOZERO
The AutoZero option detects and corrects any zero offset caused by large ambient temperature changes.
The following menus for configuration of AutoZero are only available if the AutoZero option is
purchased.
8.6.1. AutoZero Status
The AutoZero Status Menu allows the user to turn the AutoZero function ON or OFF.
Field Setup
Menu
Flow Correction
AZ Status
AZ Status
AutoZero
AZ Interval
(ON/OFF)
Temp Comp.
AZ Test Interval
Display Filter
(ON)
8.6.2. AutoZero Interval
The AutoZero Interval Menu allows the user to select the AutoZero Interval from once an hour to once a
day in 1 hour increments. Use the UP/DOWN keys to select the interval value. Upon device power up,
an AutoZero cycle will occur after 20 seconds.
Field Setup
Menu
Flow Correction
AZ Status
AZ Interval
AutoZero
AZ Interval
(1 TO 24HR)
Temp Comp.
AZ Test Interval
Display Filter
(1)HR
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
21
Revision Level 012
8.6.3. AutoZero Test Interval
For troubleshooting or testing the AutoZero function, the AutoZero Test Interval Menu allows the user
to select an Auto Zero test frequency of once a minute to once every 30 minutes in 1 minute increments.
Use the UP/DOWN keys to select the interval value. If AutoZero Test Interval is turned ON for more
than 60 minutes, it will automatically default to OFF and the AutoZero Interval (see Section 8.6.2) will
be reactivated.
Field Setup
Menu
Flow Correction
AZ Status
AZ Test Interval
AutoZero
AZ Interval
(OFF)
Temp Comp.
AZ Test Interval
Interval
Display Filter
(1)Min
8.7.
TEMPERATURE COMPENSATION
The Temperature Compensation option compensates the flow and velocity signal for density changes
caused by variations in the process air temperature. The following menus for configuration of
Temperature Compensation are only available if the Temperature Compensation option is purchased.
Additionally, an input signal from an external temperature transmitter or the building automation system
is required; see Section 3.2 for proper temperature transmitter connection and Section 4.2 for
temperature input signal configuration.
8.7.1. Temperature Units
The Temperature Units Menu allows the user to select the appropriate temperature units for the job.
Field Setup
Menu
Flow Correction
Temperature Units
Units
AutoZero
Temperature Values
(ºF / ºC)
Temp Comp.
Temperature Input
Display Filter
Fixed Value
(ºF)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
22
Revision Level 012
8.7.2. Temperature Values
The Temperature Values Menu allows the factory or user to set the minimum and maximum temperature
range values that represent the input signal from the external temperature transmitter or the building
automation system.
Field Setup
Menu
Flow Correction
Temperature Units
Minimum Value
AutoZero
Temperature Values
(-030)
Temp Comp.
Temperature Input
Maximum Value
Display Filter
Fixed Value
(130)
If the new temperature values cause the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Temperature Range Example
below.
Warning Message:
Op Range Outside
Allowable Value
Reset to MAX F.S.
(Press Enter)
Minimum Value
(-000)
Maximum Value
(000)
Op Range Outside
Allowable Value.
Reset to Max F.S.
(Press Enter)
Op Range value within
New Min/Max values
Op Range value exceeds
New Min/Max values
Entering a new Min &
Max Temperature
value and pressing the
Enter button will
calculate new Min &
Max Op Range values.
Warning Message
Operating Range
(ACFM)
(6,000 - 12,000)
(12,000)
Pressing the Enter button
will reset the current Op
Range value to the new
calculated Max. F.S value
which will represent 100%
of the process output value.
The Op Range value can be
changed and will represent
100% of the process output
signal (5vdc, 10vdc, or 20mA).
-Temperature Range Example-
Minimum Value
(-000)
Accepted
(100)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
23
Revision Level 012
8.7.3. Temperature Input
The Temperature Input Menu allows the user to select between three temperature input options (Fixed,
Variable, and Net) for the flow calculations. If Fixed is selected the default temperature value entered in
the Fixed Value Menu (see Section 5.3.5) is used. The Standard Fixed Value is 68˚F. If Variable is
selected an external temperature input signal is required (see Sections 5.3.1 through 5.3.3). If Net is
selected, the temperature input signal is obtained through network communications. The Net option is
only available if one of the communication options is ordered (see Sections 9.11 through 9.13). The
temperature value is only displayed on the LCD screen, if the Temperature Input is set to Variable or
Net.
Field Setup
Menu
Flow Correction
Temperature Units
Temp. Input
AutoZero
Temperature Values
(Fix/Var/Net)
Temp Comp.
Temperature Input
Display Filter
Fixed Value
(Variable)
8.7.4. Fixed Value
The Fixed Value Menu allows the user to enter a temperature value other than the standard value of 68˚F
for the flow calculations. This value will not be displayed on the LCD screen.
Field Setup
Menu
Flow Correction
Temperature Units
Fixed Value
AutoZero
Temperature Values
(˚F)
Temp Comp.
Temperature Input
Display Filter
Fixed Value
(+068)
8.8.
DISPLAY FILTER
The Display Filter Menu allows the user to adjust the Display Filter rolling average algorithm by setting
the Sample Interval Time value in seconds and the number of rolling average Sample Counts. The
adjustment range of the Sample Interval Time is 0.10 to 65.5 seconds in 0.10 increments. The Sample
Count range is 0 to 150 Sample Counts. The Display Filter is independent of the Process Output Filter
Value (See Section 8.10).
Field Setup
Menu
Flow Correction
Sample Interval Time
AutoZero
(00.5)sec.
Temp Comp.
(0-150) Sample Count
Display Filter
(010)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
24
Revision Level 012
8.9.
PROCESS OUTPUT FILTER
The Process Output Filter Menu allows the user to adjust the Process Output Filters rolling average
algorithm by setting the Sample Interval Time value in seconds and the number of rolling average
Sample Counts. The adjustment range of the Sample Interval Time is 0.10 to 65.5 seconds in 0.10
increments. The Sample Count range is 0 to 150 Sample Counts. The Process Output Filter is
independent of the Display Filter Value (See Section 8.8).
Field Setup
Menu
Output Filter
Sample Interval Time
Alarm Options
(00.5)sec.
DP Display Format
(0-150) Sample Count
Factory Defaults
(010)
8.10. HIGH/LOW ALARM OPTIONS
The following menus for configuration of High/Low Alarms are only available if the High/Low Alarm
option is purchased.
8.10.1. Alarm Status
The Alarm Status allows the user to independently turn each alarm ON or OFF.
Field Setup
Menu
Output Filter
Alarm Status
Low Alarm
Alarm Options
Alarm Value
(On)
DP Display Format
Alarm Delay
High Alarm
Factory Defaults
(On)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
25
Revision Level 012
8.10.2. Alarm Values
The Alarm Value Menu allows the user to enter the Low or the High flow or pressure alarm value.
Alarm values will be displayed in the same engineering units selected in the Eng. Units Menu (see
Section 8.3).
-
High Alarm Function: The High Alarm activates if the flow or pressure exceeds the High
Alarm value and resets when the flow or pressure drops below the High Alarm Value.
-
Low Alarm Function: The Low Alarm activates if the flow or pressure drops below the Low
Alarm Value and resets when the flow or pressure exceeds the Low Alarm Value.
Field Setup
Menu
Output Filter
Alarm Status
Lo Alarm Value
Alarm Options
Alarm Value
(000,000)
DP Display Format
Alarm Delay
Hi Alarm Value
Factory Defaults
(100,000)
8.10.3. Alarm Delay
The Alarm Delay Menu allows the user to enter an alarm delay of 0 to 999 seconds before an alarm will
be activated. The alarm will be reset without a delay.
Field Setup
Menu
Output Filter
Alarm Status
Lo Alarm Delay
Alarm Options
Alarm Value
(000)Seconds
DP Display Format
Alarm Delay
Hi Alarm Delay
Factory Defaults
(000)Seconds
8.11. DP DISPLAY FORMAT
The DP Display Format Menu is only available when the MicroTransEQ is configured by Paragon at the
time of order for pressure; it allows the user to change the number of digits shown to the right of the
decimal point. Selections are 0 to 4 digits. Use the UP/DOWN keys to move the decimal point to the
left or right.
Field Setup
Menu
Output Filter
Number of Digits
Alarm Options
After Decimal
DP Display Format
Point.
Factory Defaults
(00.000)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
26
Revision Level 012
8.12. FACTORY DEFAULTS
If pressure calibration changes have been made incorrectly to the MicroTransEQ program, all pressure
calibration values and device settings can be restored to the original factory settings by selecting YES
and pressing Enter in both the Set To Factory Defaults Menu and the Verify Set To Factory Defaults
Menu (See Factory Defaults table below for a list of Saved Settings).
Field Setup
Menu
Output Filter
Set To
Verify Set To
Alarm Options
Factory Defaults
Factory Defaults
DP Display Format
Factory Defaults
(No)
(No)
FACTORY DEFAULTS
ITEM
SAVED SETTING
ITEM
SAVED SETTING
1
All Factory Calibration Points (12)
14
MAC Address
2
Area Factor
15
Instance Number
3
Operating Range
16
Engineering Units
4
4 Pt Flow Correction
17
Display Filter Values
5
Altitude
18
Output Filter
6
K-Factor
19
DP Display Format
7
Lockdown & Delay Values
20
Output Calibration
8
Flow Correction
21
AutoZero Status
9
Flow Coefficient
22
AutoZero Interval
10
Min. & Max. Temp Range Values
23
Temp. Units
11
Alarm Status
24
Temp. Input
12
Alarm Values
25
Temp. Fixed Value
13
Alarm Delay
26
Baud Rate
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
27
Revision Level 012
9. TECH CONFIGURATION MENUS
To set parameters under the Tech Configuration Menu, refer to the procedure below, associated
subsections and Section 6.3 for Key functions.
Step 1.
Enter the Tech Configuration Menu by pressing and holding the Up/Down Keys
simultaneously for 5 seconds.
Step 2.
Using the Up/Down/Left/Right Keys, enter password number 1000 and press the
Enter Key.
Step 3.
Once in the Tech Configuration Menu, use the Up/Down Keys to highlight the
required parameter for configuration as shown in Sections 9.1 through 9.13. Press
the Enter Key once to access the highlighted parameter Menu.
Step 4.
Once in the parameter menu, the parameter can be changed using the
Up/Down/Left/Right Keys. After the parameter has been changed, press the Enter
Key once. Then Press the ESC Key once to return to the Tech Configuration
Menu.
Step 5.
After all of the required parameters have been configured, exit the Tech
Configuration Menu by pressing the ESC Key. The Process Display (see Section
6.2) will then be displayed.
9.1.
AREA FACTOR
The Area Factor Menu allows the user to enter or modify an existing Area Factor. The Area Factor
Menu is only available if the MicroTransEQ is configured by Paragon at the time of order for flow or
velocity and for input from a non-amplified Pitot-type flow sensor.
Tech. Config.
Password: 1000
Area Factor
Area Factor
Min Calibration
(FT2)
50% Calibration
Span Calibration
(001.000)
If the new Area Factor causes the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Area Factor Example below.
Warning Message:
Op Range Outside
Allowable Value
Reset to MAX F.S.
(Press Enter)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
28
Revision Level 012
Area Factor
(FT )
(001.000)
Area Factor
(FT )
Accepted
(001.200)
Op Range Outside
Allowable Value.
Reset to Max F.S.
(Press Enter)
Op Range value within
New Min/Max values
Op Range value exceeds
New Min/Max values
Entering a new Area
Factor and pressing
the Enter button will
calculate new Min &
Max Op Range values.
Warning Message
Operating Range
(ACFM)
(6,000 - 12,000)
(12,000)
Pressing the Enter button
will reset the current Op
Range value to the new
calculated Max. F.S value
which will represent 100%
of the process output value.
The Op Range value can be
changed and will represent
100% of the process output
signal (5vdc, 10vdc, or 20mA).
-Area Factor Example-
2
2
9.2.
MINIMUM CALIBRATION
The Minimum Calibration Menu allows a user to perform a minimum transducer calibration. This value
will be placed in a different memory location and used until a Return to Factory Defaults is selected (see
Section 8.12). (Caution: Before performing a minimum calibration, disconnect the Total (High)
and Static (Low) Pressure connections, perform a minimum calibration and then reconnect the
Total and Static Pressure connections).
Tech. Config.
Password: 1000
Area Factor
Input Value
CPU Taking
Min Calibration
(0.0000) Inch W.C.
Samples
50% Calibration
Span Calibration
(Press Enter)
(Please Wait)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
29
Revision Level 012
9.3.
50% CALIBRATION
The 50% Calibration Menu is only available when the MicroTransEQ is configured by Paragon at the
time of order for pressure; it allows a user to perform a 50% transducer calibration to eliminate zero drift
in a bipolar transducer. This value will be placed in a different memory location and used until a Return
to Factory Defaults is selected (see Section 8.12).
Tech. Config.
Password: 1000
Area Factor
Input Value
CPU Taking
Min Calibration
(0.0285) inch w.c.
Samples
50% Calibration
Span Calibration
(Press Enter)
(Please Wait)
9.4.
SPAN CALIBRATION
The Span Calibration Menu allows the user to perform a span transducer calibration to eliminate any
possible transducer drift. This value will be placed in a different memory location than the Factory Span
memory location and used until a Return to Factory Defaults is selected (see Section 8.12).
Tech. Config.
Password: 1000
Area Factor
Input Value
CPU Taking
Min Calibration
(0.0570) Inch w.c.
Samples
50% Calibration
Span Calibration
(Press Enter)
(Please Wait)
9.5.
TEMPERATURE FIXED VALUE
When the Temperature Compensation option (see Section 8.7) is not ordered, the Fixed Value Menu
allows the user to enter a temperature value other than the standard value of 68˚F for the density
calculations. This value will not be displayed on the LCD screen.
Tech. Config.
Password: 1000
Temp. Fixed Value
Temp. Fixed Value
Altitude
ºF
Output Calibration
(+068)
Correction Coeff.
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
30
Revision Level 012
9.6.
ALTITUDE
The Altitude Menu allows user to enter the specific altitude for the job other than the standard value of 0
feet above mean sea level for the density calculations.
Tech. Config.
Password: 1000
Temp. Fixed Value
Altitude
Altitude
Output Calibration
(0000)Ft
Correction Coeff.
If the new Altitude causes the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Altitude Example below.
Warning Message:
Op Range Outside
Allowable Value
Reset to MAX F.S.
(Press Enter)
Altitude
(0000)Ft
Op Range Outside
Allowable Value.
Reset to Max F.S.
(Press Enter)
Op Range value within
New Min/Max values
Op Range value exceeds
New Min/Max values
Entering a new Altitude
and pressing the Enter
button will calculate
new Min & Max Op
Range values.
Warning Message
Operating Range
(ACFM)
(6,000 - 12,000)
(12,000)
Pressing the Enter button
will reset the current Op
Range value to the new
calculated Max. F.S value
which will represent 100%
of the process output value.
The Op Range value can be
changed and will represent
100% of the process output
signal (5vdc, 10vdc or 20mA).
-Altitude Example-
Altitude
Accepted
(0100)Ft
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
31
Revision Level 012
9.7.
PROCESS OUTPUT CALIBRATION
9.7.1. Minimum Calibration
The Minimum Calibration Menu allows the user to make output zero adjustments. Monitor the output
and with each Up or Down key depression, the output will increase or decrease by 0.01VDC or 0.01mA
depending on output selection.
Tech. Config.
Password: 1000
Temp. Fixed Value
Min Calibration
Use Up/Down
Altitude
Span Calibration
Buttons
Output Calibration
Adjust Output
Correction Coeff.
(Press Enter)
9.7.2. Span Calibration
The Span Calibration Menu allows the user to make output span adjustments. Span adjustments require
a low pressure air source adjusted to the Full Scale Value shown on the side label. Monitor the output
and with each Up or Down key depression, the output will increase or decrease by 0.01VDC or 0.01mA
depending on output selection.
Tech. Config.
Password: 1000
Temp. Fixed Value
Min Calibration
Use Up/Down
Altitude
Span Calibration
Buttons
Output Calibration
To Adjust Output
Correction Coeff.
(Press Enter)
9.8.
CORRECTION COEFFICIENT
The Correction Coefficient Menu is only available if the MicroTransEQ is configured by Paragon at the
time of order for flow or velocity. If the MicroTransEQ is configured for input from a non-amplified
Pitot-type flow sensor (such as those manufactured by Paragon) the menu in Section 9.8.1 will be
displayed. If the MicroTransEQ is configured for input from a piezometer ring or amplified differential
pressure flow sensor (manufactured by others) the menu in Section 9.8.2 will be displayed.
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
32
Revision Level 012
9.8.1. Probe Coefficient
The Probe Coefficient Menu allows the user to modify the formula constant of 1096.70 for a non-
amplified Pitot-type flow sensor.
Tech. Config.
Password: 1000
Temp. Fixed Value
Correction Coeff.
Altitude
Probe
Output Calibration
(1096.70)
Correction Coeff.
(001,096.70
The probe coefficient entered into the MicroTransEQ is based on the following equation:
ܸൌܥൈඨ∆ܲ
ߩ
Where:
ܸ = Velocity (afpm)
ܥ = Non-amplified Pitot-tube Coefficient, 1096.70
∆ܲ = Differential Pressure Measured by the Pitot-tube (in. w.c.)
ߩ = Actual Density (lb/ft3)
9.8.2. Piezometer Ring Coefficient
The Piezometer Ring Coefficient Menu allows a user to enter the correction coefficient associated with
the piezometer ring or amplified differential pressure flow sensor. Correction coefficients should be
obtained from the sensor or air handling unit manufacturer.
Tech. Config.
Password: 1000
Temp. Fixed Value
Correction Coeff.
Altitude
Piezometer Ring
Output Calibration
(000000.00)
Correction Coeff.
The piezometer ring coefficient entered into the MicroTransEQ is based on the following equation:
ܳൌܥோൈඨ∆ܲ
ߩ
Where:
ܳ
= Flow (acfm)
ܥோ = Piezometer Ring Coefficient
∆ܲ = Differential Pressure Measured by the Piezometer Ring (in. w.c.)
ߩ = Actual Density of Air (lb/ft3)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
33
Revision Level 012
Since ߩ is known for a given job site, some sensor and air handling unit manufacturers will include this
value (or the value for standard air density 0.075 lbm/ft3) in the factor F supplied, simplifying the above
equation to:
ܳൌܨൈ√∆ܲ
Where:
ܨൌܥோ
ඥߩ
ߩൌ ߩ or 0.075 (standard density) depending on the sensor or air handling unit manufacturer equation
for converting differential pressure to flow.
If a F value has been supplied by the fan or air handling unit manufacturer, this value will need to be
modified before entering the coefficient into the MicroTransEQ as shown below.
ܥோൌܨൈඥߩ
9.9.
FOUR POINT FLOW CORRECTION
The Four Point Flow Correction Menu allows the user to make corrections to the display and output
signal at 20% increments between 20% and 80% of Operating Range Value entered. The Displayed
Value is a fixed value determined by the percentage of Operating Range. The Measured Value is the
value determined by an independent balancer’s reading. The Four Point Flow Correction Menu is only
available if the MicroTransEQ is configured by Paragon at the time of order for flow or velocity.
Tech. Config.
Password: 1000
4PT Flow Corr
80,000 CFM
Displayed Value
MAC Address
60,000 CFM
80,000
Instance Number
40,000 CFM
Measured Value
20,000 CFM
79,500
80,000 CFM
Displayed Value
60,000 CFM
60,000
40,000 CFM
Measured Value
20,000 CFM
60,500
80,000 CFM
Displayed Value
60,000 CFM
40,000
40,000 CFM
Measured Value
20,000 CFM
40,100
80,000 CFM
Displayed Value
60,000 CFM
20,000
40,000 CFM
Measured Value
20,000 CFM
19,500
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
34
Revision Level 012
9.10. MAC ADDRESS (BACNET COMMUNICATION OPTION)
When the BACnet Communication option is ordered, the MAC Address Menu allows the user to set a
unique device address when connecting to a BACnet network. The default is 02. For additional
information refer to the Communication O&M.
Tech. Config.
Password: 1000
4PT Flow Corr
MAC Address
MAC Address
(Range = 02 to 254)
Instance Number
Modbus ID
(002)
9.11. INSTANCE NUMBER (BACNET COMMUNICATION OPTION)
When the BACnet Communication option is ordered, the Instance Number Menu allows the user to set a
unique device address when connecting to a BACnet network. The default is 1002. For additional
information refer to the Communication O&M.
Tech. Config.
Password: 1000
4PT Flow Corr
Instance Number
MAC Address
(Default = 1002)
Instance Number
Modbus ID
(01002)
9.12. MODBUS ID (MODBUS COMMUNICATION OPTION)
When the Modbus Communication option is ordered, the Modbus ID Menu allows the user to set a
unique device address when connecting to a Modbus network. The default is 02. For additional
information refer to the Communication O&M.
Tech. Config.
Password: 1000
4PT Flow Corr
Modbus ID
MAC Address
(Range = 01 to 254)
Instance Number
Modbus ID
(002)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
35
Revision Level 012
9.13. BAUD RATE (BACNET & MODBUS COMMUNICATION OPTIONS)
The Baud Rate Menu allows the user to set a unique network baud rate. The current BACnet protocol
supports 9.6, 19.2, 38.4 and 76.8 Kbps baud rate. Modbus communications supports 9.6, 19.2, 38.4,
57.6 and 115.2 Kbps baud rate. The default is 38.4 Kbps. For additional information refer to the
Communication O&M.
Tech. Config.
Password: 1000
Baud Rate
Baud Rate
(9.6, 19.2, 38.4, 76.8)
(38.4) Kbps
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
36
Revision Level 012
10. WARNING MESSAGES
10.1. INPUT PRESSURE OVERRANGE MESSAGE
If the input pressure exceeds the entered Operating Range Value, the following message will appear on
the display. It will alternate between the process display and the error message until the input falls
below the Operating Range Value.
- Caution -
Input Beyond
Operating Range
Selected
10.2. TRANSDUCER CALIBRATION MESSAGE
If during a transducer zero or span calibration process, the transducer output pressure value measured
exceeds ±20% of the expected value, the following message will appear on the display. Once the Enter
key is pressed, the display returns to the previous calibration menu.
Value entered is
Outside Factory
set limits
(Press Enter)
10.3. OPERATING RANGE MESSAGE
If the new values entered for Temperature Compensation, Area Factor, or Altitude (see Sections 8.7, 9.1,
and 9.6) causes the Operating Range Value to exceed the new calculated Maximum Full Scale Value,
the following message will appear on the display.
Op Range Outside
Allowable Value.
Reset to MAX F.S.
(Press Enter)5
10.4. NEW OPERATING RANGE MESSAGE
If a user enters a new Operating Range Value, the following message will appear on the display
notifying the user that if any 4 PT Flow Correction Values (see Section 9.9) were previously entered,
they will be reset. The message allows the user to confirm that the Operating Range change should be
made. To complete the Operating Range change, the user must use the UP/Down keys to change the
NO to a YES and press the ENTER key.
Value will
Reset 4PT
Flow Correction
Values
Make the Change
(NO)
(Press Enter)
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
37
Revision Level 012
11. TROUBLESHOOTING GUIDE
TROUBLESHOOTING TABLE
SYMPTOM
SOLUTION
1.
No Display or Back Light
1.
Verify ON/OFF switch is in ON position
2.
Verify correct input power and connection at 3 pin
connector J1
3.
Contact Factory
2.
Display background is too dark or
characters are too light.
1.
Adjust RP1 Display potentiometer located in the
upper left hand corner of the board. See
Section 6.3
3.
Display does not respond to input
pressure changes and Key pad
functions.
1.
Reset the unit by turning the ON/OFF switch OFF
and back ON.
2.
Contact Factory
4.
Display does not respond to input
pressure changes but does respond to
Key pad functions.
1.
Verify pneumatic input lines are not reversed at the
MicroTransEQ ports or the sensing element.
2.
Use a pneumatic gauge to measure the pneumatic
signal input to the MicroTransEQ. Verify the
signals are within the Op. Range Value shown on
the label located on the side of the enclosure.
3.
Contact Factory
5.
Display does not respond to Key Pad
functions
1.
Reset the unit by turning the ON/OFF switch to
OFF and then ON.
2.
Contact Factory
6.
CAUTION INPUT OVERRANGE
message on Display
1.
Verify data on ID Label located on side of
MicroTransEQ is correct for the application.
2.
Remove pneumatic signal lines. If display returns
to 0 reading, use a pneumatic gauge to measure the
pneumatic signal. Verify input signal is equal to or
less then the Op. Range D.P. Value on the ID
Label. If the display does not return to 0, a
pneumatic tube may be plugged by moisture
underneath the PC board. Consult the factory.
3.
Verify menu selections are set correctly:
Operating Range, Flow Correction, Temperature
Compensation, Area Factor, and Altitude
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
38
Revision Level 012
TROUBLESHOOTING TABLE
SYMPTOM
SOLUTION
6.
Continued
4.
If the Temperature Compensation Option is
installed, verify correct temperature input signal.
Verify that the temperature input is connected
correctly.
5.
Contact Factory
7.
Incorrect Temperature Reading
1.
Verify Temperature Transmitter specifications
match with MicroTransEQ ID Label
(Current/Voltage, Temperature Range)
2.
Verify Temperature Transmitter is connected
correctly to the MicroTransEQ (see Section 3.2).
3.
Verify Temperature Transmitter signal at the
MicroTransEQ connector J2 is correct.
4.
Contact Factory
8.
No Output signal or Incorrect Output
signal. Display is reading correct
value.
1.
Verify Process Output S2 & S4 switches are in the
correct position for the application (see Section 4.1
and the figure in Section 3.1.
2.
Disconnect Output signal wires and verify output
signal at MicroTransEQ connector J2 is correct.
3.
Verify correct Operating Range (see Section 5.2)
4.
Perform Output Cal (see Section 9.7)
5.
Contact Factory
9.
Incorrect Process Output Values after
changing Area Factor, Altitude, or
Temperature Value. Display readings
are correct.
1.
Re-Enter Operating Range Value in Field Menu
(see Section 5.2)
2.
Contact Factory
10. Unstable Display and Process Output
at very low flow.
1.
Increase Display and Process Filter
2.
Decrease Lockdown Value
3.
Increase Lockdown Delay Value
4.
Contact Factory
11. “AZ Error” text on display
1.
Turn Power Switch S3 Off and On to reset the
AutoZero valve
MicroTransEQ Operation & Maintenance Manual
Paragon Controls Incorporated
39
Revision Level 012
TROUBLESHOOTING TABLE
SYMPTOM
SOLUTION
11. Continued
2.
Check for a pinched tube beneath the main board.
(Caution: Remove power before removing board)
3.
Contact Factory
Paragon Controls Incorporated
P.O. Box 99, Forestville, CA 95436
http://www.paragoncontrols.com
Phone 707 / 579-1424
Revision Level 012