Paradox Esprit 748 express + Programming Manual
Text of the manual
SOFTWARE VERSION 3.00
CONTROL PANEL RESET:
Installer lock must be unlocked.
(Address 058: enter any value other than 147)
Power down reset
(1) Remove battery and AC to power down the unit.
(2) Connect a jumper between "reset jumper" pins.
(3) Connect AC and/or battery.
(4) Wait 3 seconds.
(5) Remove jumper.
Factory default installer and master codes will be reinstated. Values entered at addresses 008-043, 062-126 and 300-523
as well as all user codes, will be erased ([2ND] [2ND]). Programmed values of all other addresses do not change.
HEXA PROGRAMMING:
All digits from 0 to F are valid. Values are programmed into
memory locations from address 000 to 043 and from address
300 to 523.
1) Press [ENTER] + installer code.
2) [ENTER] will flash (programming mode).
3) Enter 3 digit memory address.
4) Current value will be displayed on keypad.
5) Enter 2 digit data.
6) Go to step 3 for next address.
To exit programming mode, press [CLEAR].
STREAMLINED SECTION PROGRAMMING
Can be used to program sections 00 to 66. (addresses 000 to 043 and 300 to 523)
Press [ENTER], installer code, and [7]. ([2ND] and [ENTER] keys alternately flash.)
Enter a 2-digit section number, followed by 8 digits to program that section (confirmation beep). Data will be saved
automatically and the software advances to the next programming section. To exit programming mode press [CLEAR].
INSTALLER CODE: (reset code 747474)
(addresses 000, 001, 002)
SECTION 00
Full access to programming, except access codes. (addresses 127-299) No access to arming/disarming. Can be used to
modify installer code. Use only numeric keys from [1] to [10]. (key [10] = 0)
PANEL ANSWER OPTIONS:
(address 003)
SECTION 00
First digit disables “Answering Machine Override” (key [2ND] or key [1]), or determines period of time between first and
second call (see table below). Second digit determines number of rings required before panel will answer. If [2ND][2ND]
is entered, panel will not answer. (Default value is [2ND] [8].)
- 1 -
Value of
2ND digit = 10
( 8 + 2 = 10)
Value of
1ST digit = 3
( 2 + 1 = 3)
VALUE = "3A"
HEXA DISPLAY
No display = SKIP (empty)
No light = 0
10 = [0] = [A]
If key is lit = 8 =
4 =
2 =
1
If key is lit = 8 =
4 =
2 =
1
TELEPHONE AND ACCOUNT NUMBERS: (reset empty)
If only one central station phone number is used, program the same number for telephone number 1 and 2.
[10]
= the number "0"
[BYP]
= switch from pulse to tone while dialing
[11]
= *
[MEM]
= pause 4 seconds
[12]
= #
[TRBL]
= end of number
COMPUTER TELEPHONE NUMBER: (View at addresses 008 to 015.)
02 __ / __ / __ / __ / __ / __ / __ / __ 03 __ / __ / __ / __ / __ / __ / __ / __
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
CENTRAL STATION TELEPHONE NUMBER 1: (View at addresses 016 to 023.)
04 __ / __ / __ / __ / __ / __ / __ / __
05 __ / __ / __ / __ / __ / __ / __ / __
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
CENTRAL STATION TELEPHONE NUMBER 2: (View at addresses 024 to 031.)
06 __ / __ / __ / __ / __ / __ / __ / __ 07 __ / __ / __ / __ / __ / __ / __ / __
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
ACCOUNT "A" AND "B": (View at addresses 032 to 035.)
08 ___ / ___ / ___ / ___
___ / ___ / ___ / ___
1
2
3
4
5
6
7
8
A
B
If only one account number is required, the same number must be entered for both account "A" and "B".
- 2 -
PG748EX
Press [TRBL] to end
phone number if less
than 16 digits are
programmed.
Press [TRBL] to end
phone number if less
than 16 digits are
programmed.
For 3 digit account
numbers, enter "skip"
([2ND]) as first digit.
Press [TRBL] to end
phone number if less
than 16 digits are
programmed.
Streamline
section
Streamline
section
Streamline
section
Streamline
section
Streamline
section
Streamline
section
Streamline
section
1st digit: value must be entered i.e.
2nd digit: time correction (See table)
1st digit: telephone 1 format
2nd digit: telephone 2 format
1st digit: PGM 1 type
2nd digit: PGM 2 type
[2
]
ND
036
037
038
039
09
PGM 1
PGM 2
PGM mask 1
PGM mask 2
040
041
042
043
___/___
___/___
/
___/___
___ ___
10
TIME CORRECTION:
(address 037 second digit)
[2
]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
ND - No adjustment
- Plus 4 sec.
- Plus 8 sec.
- Plus 12 sec.
- Plus 16 sec.
- Plus 20 sec.
- Plus 24 sec.
- Plus 28 sec.
[8]
[9]
[10]
[11]
[12]
[
]
[
]
[
]
- Minus 4 sec.
- Minus 8 sec.
- Minus 12 sec.
- Minus 16 sec.
- Minus 20 sec.
- Minus 24 sec.
- Minus 28 sec.
- Minus 32 sec.
BYP
MEM
TRBL
COMMUNICATOR FORMATS
Key
[2
]
[1]
[2]
[3]
[4]
[5]
ND
[6]
[7]
[8]
[9]
[10]
[
]
TRBL
=
slow (1400Hz, 1900Hz, 10bps)
= (1400Hz, 1800Hz, 10bps)
=
fast (1400Hz, 1900Hz, 20bps)
=
(2300Hz, 1800Hz, 20bps)
= (40bps with 1400Hz handshake)
= (40bps with 2300Hz handshake)
ADEMCO
SILENT KNIGHT
SESCOA
RADIONICS
RADIONICS
= with PARITY (1400Hz, 40bps)
= with PARITY (2300Hz, 40bps)
=
express
=
contact ID (programmable codes)
=
contact ID (all codes)
=
- no handshake (personal dialing)
RADIONICS
RADIONICS
ADEMCO
ADEMCO
ADEMCO
DTMF
[2 ]
ND
- 3 -
PG748EX
For addresses
to
, see pages 7 to 10.
044
126
CID
100:
110:
111:
112:
113
114:
115:
116:
117:
118:
120:
121:
122:
123:
130:
131:
132:
133:
136:
137:
138:
140:
150:
151:
152:
153:
154:
155:
156:
157:
158:
159:
161:
CID
300:
301:
302
305:
306:
309:
320:
321:
323:
350:
351:
354:
370:
371:
372:
373:
382:
383:
400:
401:
402:
403:
404:
407:
410:
441:
570:
572:
573:
574:
601:
602:
625:
PROG. VALUE
[2
]
[2
]
[2
]
[2
]
[2
]
[2
]
[2
]
[2
]
[2
]
[2
]
[2
]
[2
]
[2
]
[
]
[2
]
[
]
[2
]
[
]
[2
]
[
]
[
]
[
]
[2
]
ND
ND
ND
ND
ND
ND
ND
ND
ND
ND
ND
ND
ND
BYP
ND
MEM
ND
TRBL
ND
BYP
MEM
TRBL
ND
/ [1]
/ [2]
/ [3]
/ [4]
/ [5]
/ [6]
/ [7]
/ [8]
/ [9]
/ [10]
/ [11]
/ [12]
/
/
/
[1] /
[1] / [1]
[1] / [2]
[1] / [3]
[1] / [4]
[1] / [5]
[1] / [6]
[1] / [7]
[1] / [8]
[1] / [9]
[1] / [10]
[1] / [11]
[1] / [12]
[1] /
[1] /
[1] /
[2] /
[2] / [1]
PROG. VALUE
[2] / [2]
[2] / [3]
[2] / [4]
[2] / [5]
[2] / [6]
[2] / [7]
[2] / [8]
[2] / [9]
[2] / [10]
[2] / [11]
[2] / [12]
[2]
[
]
[2]
[
]
[2]
[
]
[3] / [2
]
[3] / [1]
[3] / [2]
[3] / [3]
[3] / [4]
[3] / [5]
[3] / [6]
[3] / [7]
[3] / [8]
[3] / [9]
[3] / [10]
[3] / [11]
[3] / [12]
[3]
[
]
[3]
[
]
[3]
[
]
[4] / [2
]
[4] / [1]
[4] / [2]
/
/
/
/
/
/
BYP
MEM
TRBL
ND
BYP
MEM
TRBL
ND
REPORTING CODE
MEDICAL
FIRE ALARM
FIRE SMOKE
COMBUSTION
WATER FLOW
HEAT
PULLSTATION
DUCT
FLAME
NEAR ALARM
PANIC ALARM
DURESS
SILENT PANIC
AUDIBLE PANIC
BURGLARY
PERIMETER BURG.
INTERIOR BURG.
24HR BURGLARY
BURGLARY OUTDOOR
BURGLARY TAMPER
BURGLARY NEAR ALARM
GENERAL ALARM
24 HOUR AUX
GAS DETECTED
REFRIGERATION
LOSS OF HEAT
WATER LEAKAGE
FOIL BREAK ALARM
DAY TROUBLE ALARM
LOW GAS LEVEL
HIGH TEMPERATURE
LOW TEMPERATURE
LOSS AIR FLOW
REPORTING CODE
SYSTEM TROUBLE
AC LOSS
LOW SYSTEM BATTERY
SYSTEM RESET
PROGRAM CHANGED
BATTERY TEST FAIL
SOUNDER/RELAY TROUBLE
BELL 1 TROUBLE
ALARM RELAY TROUBLE
COMMUNICATION TROUBLE
TELCO 1 FAULT
FAIL TO COMMUNICATE
PROTECTION LOOP TROUBLE
PROTECTION LOOP OPEN
PROTECTION LOOP SHORT
FIRE LOOP TROUBLE
SENSOR TROUBLE
SENSOR TAMPER
OPEN/CLOSE
OPEN/CLOSE BY USER #
GROUP OPEN/CLOSE
AUTOMATIC OPENING/CLOSING
LATE TO OPEN/CLOSE
REMOTE ARM DOWNLOAD
REMOTE ACCESS
OPEN/CLOSE - STAY MODE
BYPASS
24 HOUR ZONE BYPASS
BURGLARY BYPASS #
GROUP BYPASS
MANUAL TEST
PERIODIC TEST
TIME/DATE RESET
PROGRAMMABLE CONTACT ID EVENT CODES
All addresses from to (sections
to ) programmed with values other than
will report the contact
ID codes corresponding to the values programmed. Values to be programmed should be selected from this table.
300 523
11 66
[2
] [2
]
ND
ND
- 4 -
REPORTING CODES: (reset code = “empty"
)
All digits from
to
are valid. Enter
(skip) = digit will not be reported except for contact I.D. programmable codes.
(Select Contact I.D (all codes) - key
for both central station numbers at section
- address
.)
[2 ] [2 ]
[1]
[F]
[2 ]
[10]
09
038
ND
ND
ND
If CONTACT I.D. format (all codes) is selected, addresses 300 to 523 (sections 11 to 66) do not have to be programmed.
PG748EX
___/___
___/___
/
___/___
___ ___
Auto / Espload
Master
User code 1
User code 2
300
301
302
303
Streamline
section
Streamline
section
Data
Data
Description
Description
Address
Address
ARMING
CODES:
(closing)
___/___
___/___
/_
___/___
___
__
User code 23
User code 24
User code 25
User code 26
324
325
326
327
17
11
___/___
___/___
/
___/___
___ ___
User code 3
User code 4
User code 5
User code 6
304
305
306
307
___/___
___/___
/_
___/___
___
__
User code 27
User code 28
User code 29
User code 30
328
329
330
331
12
18
User code 7
User code 8
User code 9
User code 10
User code 15
User code 16
User code 17
User code 18
308
309
310
311
316
317
318
319
User code 31
User code 32
User code 33
User code 34
User code 39
User code 40
User code 41
User code 42
332
333
334
335
340
341
342
343
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
13
15
19
21
User code 11
User code 12
User code 13
User code 14
User code 19
User code 20
User code 21
User code 22
312
313
314
315
320
321
322
323
14
16
User code 35
User code 36
User code 37
User code 38
User code 43
User code 44
User code 45
User code 46
User code 47
User code 48
See next page
336
337
338
339
344
345
346
347
348
349
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
___/___
___/___
___/___
___/___
/_
___/___
___
__
___/___
___/___
/_
___/___
___
__
20
22
23
- 5 -
REPORTING CODES:
(reset code
)
"empty"
Streamline
section
Streamline
section
Data
Data
Description
Description
Address
Address
DISARMING
CODES:
(opening)
___/___
___/___
/_
___/___
___
__
User code 21
User code 22
User code 23
User code 24
372
373
374
375
29
___/___
___/___
/
___/___
___ ___
User code 1
User code 2
User code 3
User code 4
352
353
354
355
___/___
___/___
/_
___/___
___
__
User code 25
User code 26
User code 27
User code 28
376
377
378
379
24
30
User code 5
User code 6
User code 7
User code 8
User code 13
User code 14
User code 15
User code 16
356
357
358
359
364
365
366
367
User code 29
User code 30
User code 31
User code 32
User code 37
User code 38
User code 39
User code 40
380
381
382
383
388
389
390
391
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
25
27
31
33
User code 9
User code 10
User code 11
User code 12
User code 17
User code 18
User code 19
User code 20
360
361
362
363
368
369
370
371
26
28
User code 33
User code 34
User code 35
User code 36
User code 41
User code 42
User code 43
User code 44
User code 45
User code 46
User code 47
User code 48
384
385
386
387
392
393
394
395
396
397
398
399
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
___/___
___/___
___/___
___/___
___/___
___/___
/_
___/___
___
__
___/___
___/___
/_
___/___
___
__
32
34
35
Espload
Master
See previous page
350
351
___/___
___/___
Streamline
section
Streamline
section
Data
Data
Description
Description
Address
Address
ALARM CODES ZONE 1 TO 12:
ALARM CODES ZONE 13 TO 24:
___/___
___/___
/
___/___
___ ___
Zone 5
Zone 6
Zone 7
Zone 8
404
405
406
407
___/___
___/___
/_
___/___
___
__
Zone 13
Zone 14
N/A
N/A
Keypad 1
Keypad 2
412
413
414
415
37
39
Zone 9
Zone 10
Zone 11
Zone 12
408
409
410
411
N/A
N/A
N/A
N/A
416
417
418
419
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
38
40
N/A
N/A
N/A
N/A
420
421
422
423
___/___
___/___
/
___/___
___ ___
41
Zone 1
Zone 2
Zone 3
Zone 4
400
401
402
403
___/___
___/___
___/___
___/___
36
23
- 6 -
REPORTING CODES:
(reset code
)
"empty"
Streamline
section
Streamline
section
Streamline
section
Streamline
section
Data
Data
Data
Data
Description
Description
Description
Description
Address
Address
Address
Address
ZONE 1 TO 12 RESTORE CODES:
ZONE 1 TO 12 SHUTDOWN CODES:
ZONE 13 TO 24 RESTORE CODES:
ZONE 13 TO 24 SHUTDOWN CODES:
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
Zone 5
Zone 6
Zone 7
Zone 8
Zone 5
Zone 6
Zone 7
Zone 8
428
429
430
431
452
453
454
455
___/___
___/___
/_
___/___
___
__
___/___
___/___
/_
___/___
___
__
Zone 13
Zone 14
N/A
N/A
Keypad 1
Keypad 2
Zone 13
Zone 14
N/A
N/A
Keypad 1
Keypad 2
436
437
438
439
460
461
462
463
43
49
45
51
Zone 9
Zone 10
Zone 11
Zone 12
Zone 9
Zone 10
Zone 11
Zone 12
432
433
434
435
456
457
458
459
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
440
441
442
443
464
465
466
467
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
44
50
46
52
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
444
445
446
447
468
469
470
471
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
47
53
Zone 1
Zone 2
Zone 3
Zone 4
Zone 1
Zone 2
Zone 3
Zone 4
424
425
426
427
448
449
450
451
___/___
___/___
___/___
___/___
___/___
___/___
___/___
___/___
42
48
Streamline
section
Streamline
section
Data
Data
Description
Description
Address
Address
TAMPER 1 TO 12 TROUBLE CODES:
TAMPER 13 TO 24 TROUBLE CODES:
___/___
___/___
/
___/___
___ ___
Tamper 5
Tamper 6
Tamper 7
Tamper 8
476
477
478
479
___/___
___/___
/_
___/___
___
__
N/A
N/A
N/A
N/A
484
485
486
487
55
57
Tamper 9
Tamper 10
Tamper 11
Tamper 12
480
481
482
483
N/A
N/A
N/A
N/A
488
489
490
491
___/___
___/___
/
___/___
___ ___
___/___
___/___
/
___/___
___ ___
56
58
N/A
N/A
N/A
N/A
492
493
494
495
___/___
___/___
/
___/___
___ ___
59
Tamper 1
Tamper 2
Tamper 3
Tamper 4
472
473
474
475
___/___
___/___
___/___
___/___
54
3 Digit Decimal Value Programming
Used to program addresses 044 to 061. Values entered must contain 3 digits between "000" and "255". ([10] = 0)
Decimal value programming:
1) Press [ENTER] + installer code. ([ENTER] key will flash.)
2) Enter 3 digit address (044 to 061).
3) Current value will be displayed on keypad.
4) Enter 3 digit DECIMAL value.
5) Repeat from step 2 onward for next address.
To exit programming mode press [CLEAR].
044: ___/___/___ (hours) Auto arm time (between "000" and "023")
045: ___/___/___ (minutes) Auto arm time (between "000" and "059")
046: ___/___/___ (days) Auto test report every ? days (between "001" and "255") (000 = disabled)
047: ___/___/___ (hours) Auto test report (between "000" and "023")
048: ___/___/___ (minutes) Auto test report (between "000" and "059")
- 7 -
PG748EX
049: ___/___/___ (seconds) Exit delay (factory default 60 seconds)
050: ___/___/___ (seconds) Entry delay 1 (factory default 45 seconds)
051: ___/___/___ (seconds) Entry delay 2 (factory default 45 seconds)
052: ___/___/___ (minutes) Bell cut-off time (factory default 5 minutes)
053: ___/___/___ ( x 15 mSec.) Zone speed (factory default 600 mSec.)
054: ___/___/___ (minutes) Power failure report delay (factory default 30 minutes) (000 = disabled)
055: ___/___/___ ( x 15 minutes) "No movement" report time (factory default 8 hours) (000 = disabled)
056: ___/___/___ PGM timer setting (001 to 127 for seconds and 129 to 255 for minutes) (factory default 5 seconds)
Add 128 to desired value in minutes (i.e. for 5 minutes: enter 5 + 128 = 133)
057: ___/___/___ Intellizone delay (in seconds, minimum = 10 seconds) (factory default 48 seconds)
058: ___/___/___ Installer code lock (147 = locked, 000 = unlocked)
059: ___/___/___ (seconds) Programmable delay before alarm transmission (5 to 63 seconds) (000 = disabled)
060: ___/___/___ (seconds) Recent closing delay (000 = disabled)
061: ___/___/___ Future Use
FEATURE SELECT PROGRAMMING
Addresses 062-126. “ON”/”OFF” status of the key lights determines feature selection.
In programming mode, enter 3 digit memory address (062 to 126). To save entries, press [ENTER].
To exit programming mode press [CLEAR]. Reset = “OFF” for addresses 062 to 126.
Addresses 080 to 085 for future use.
- 8 -
PG748EX
- 9 -
stay arm / System A
enabled
enabled
Bell squawk on arm/disarm
Auto zone shutdown
See "Reporting" table
(1:1.5) Pulse USA
(1:2) Pulse Europe
enabled
enabled
enabled
Auto arm on time
Auto arm on no movement
[5]
[2]
PS1/Keyswitch = regular arm
[4]
enabled
Call back
[2
]
ND
[1]
See "TLM" table
[3]
enabled
PS1/keyswitch arming
[6]
generates only a report
Silent zone/panic generates a silent alarm
[11]
[8]
[10]
[7]
Pulse dialing
Partitioning
Tone dialing (DTMF)
enabled
[9]
[12]
086:
KEY
[
]
BYP
[
]
MEM
[
]
TRBL
OFF
/
ON
only after alarm
audible
enabled
audible
enabled
fire
on zone closure
4 digit
enabled
enabled
enabled
088:
OFF
/
ON
enabled
enabled
KEY
no EOL
Report zone restore on bell cut-off
Panic 2
Panic 3
Tamper Recognition
Panic 1
Automatic event buffer transmission
Always report disarm
Panic 2 silent
Panic 1 silent (PS1)
Panic 3 silent
6 digit access codes
Key
regular arm
[10]
Key
stay or system A arm
[11]
Beep on exit delay
Zones with EOL (1K
)
Ω
(keys
&
,
)
[1]
[3] PS1
(keys
&
[4]
[6])
(keys
&
)
[7]
[9]
TELEPHONE LINE MONITOR
TLM generates trouble only
TLM disabled
generates an alarm if armed
silent alarm becomes audible
(address
, key
has to be
)
086
[9]
OFF
KEY
[2 ]
ND
[1]
OFF OFF
ON
OFF
ON
ON
OFF
ON
Address 086, Key [2
] [1]
ND
OFF OFF
ON
OFF
ON
ON
OFF
ON
REPORTING OPTIONS
Regular reporting
Reporting disabled
Split reporting: Alarms
System report
Double reporting
KEY
DIALING SEQUENCE (tel. No.)
TYPE
[11]
[12]
1,2,1,2,1,2,1,2, fail to comm.
1,1,1,1,1,1,1,1, fail to comm.
2,2,2,2,2,2,2,2, fail to comm.
1,1,1,1,1,1,1,1, fail to comm.,
2,2,2,2,2,2,2,2, fail to comm.
*
On alarm, all reports are made to Tel. #1 until system is disarmed.
(Once disarmed, system reports are made to Tel. #2)
*
Address 086, Key [11] [12]
N/A
N/A
090:
Exclude power failure from trouble display
[2
]
ND
OFF
/ ON
[3]
[1]
enabled
[2]
stay / System A
Auto arm = regular arm
KEY
[6]
tamper follows zone bypass definition
No tamper bypass
[5]
[4]
enabled
enabled
enabled
[7]
[8]
[9]
[10]
[11]
[12]
FEATURE SELECT PROGRAMMING (continued)
(On/off status of key lights determines which feature is selected.)
Audible trouble warning
Keypad 1 zone supervision
Keypad 2 zone supervision
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
PS1 software version
Keypad software versions prior to
1.1
4.0 Keypad supervision must be OFF
}
PS1 software versions
onward
Keypad software versions
onward
2.0
4.0
Keypad supervision must be ON
}
(See Wiring Diagram)
PG748EX
TAMPER / WIRE FAULT DEFINITIONS
Exception: for 24 hour zones the tamper definition will follow the
audible/silent alarm definition of the 24 hour zone.
Silent zones will generate a silent alarm.
Tamper supervision
disabled
Alarm as per individual
zone definitions
No alarm, trouble code
reported
Audible alarm. Trouble and
alarm codes reported
Silent alarm. Trouble and
alarm codes reported
Always generate trouble
and alarm, audible or
silent as per individual
zone definitions
SYSTEM ARMED
**
**
Address 088, Key [10] [11]
*
SYSTEM DISARMED*
KEY
[11]
[10]
OFF OFF
OFF
ON
ON
OFF
ON
ON
KEY ACCESS PROGRAMMING
Programs features quickly, without entering addresses or section numbers.
To activate “key access programming”, press [ENTER], followed by installer, master or user code 1. (Code required
depends on the feature you wish to access - see below.) Press the key corresponding to the desired feature.
Press [ENTER] or [CLEAR] to exit.
key
[8]
Installer test mode
(installer code only)
In installer test mode, a confirmation beep (intermittent) indicates test is "on", a "rejection" beep (long)
indicates test is "off". The bell will squawk during walk testing to indicate opened, functional zones.
[9]
"Auto arming" time program
(all 3 codes)
Key [9] flashes. Enter two digits (00 to 23) for hours + 2 digits (00 to 59) for minutes.
[MEM]
"Panel time" and clear "trouble 8"
(all 3 codes)
Key [MEM] flashes. Enter two digits (00 to 23) for hours + 2 digits (00 to 59) for minutes.
[BYP]
Test report
(all 3 codes)
Reporting is enabled at address 086, keys [11], [12]. A value must be entered at address 512, and both
telephone and account numbers must be programmed.
[TRBL] Call Espload via telephone
(all 3 codes)
Panel identifier and PC password (addresses 004-007) and computer telephone number (addresses 008-015)
must be programmed.
[AWAY] Answer Espload
(all 3 codes)
This feature is available when using the ADP-1 adapter. In Espload, "blind dial" must be activated in "modem
setup" section, and panel phone number programmed (works also without ADP-1).
[STAY] Cancel communication attempts
(master code and user 1 can only stop calls to Espload)
Until next reportable event
(installer code - all communications)
When communicating with Espload, it is impossible to enter programming mode.
PG748EX
- 10 -
The system hardware will recognize the following zone conditions:
ZONE CONNECTIONS
ZONE connection, without EOL (N.C. contacts)
address 088, key [MEM] = "on"
key [10] = "off" (reset)
key [11] = "off" (reset)
address 090, key [8] = "off"
N.C. contacts see Figure 1
Keypad zones always use (1K OHM) EOL
ZONE connection, with EOL resistor (N.C. and N.O. contacts)
address 088, key [MEM] = "off" (reset)
key [10] = "off" (reset)
key [11] = "off" (reset)
address 090, key [8] = "off"
N.C. and/or N.O. contacts, see Figure 2
ZONE connection, with tamper recognition (N.C. contacts)
address 088, key [MEM] = "on"
key [10] =
key [11] =
address 090, key [8] = "off"
Tamper transmits separate code, see Figure 3
ZONE connection, with EOL, with tamper recognition, and with wire fault
(short circuit) recognition (N.C. contacts)
address 088, key [MEM] = "off"
key [10] =
key [11] =
address 090, key [8] = "off"
Tamper/wire fault transmits separate code, see Figure 4
- 11 -
PG748EX
See "Tamper/wire Fault Definitions
and Options"
See "Tamper/wire Fault Definitions
and Options"
ESPRIT 748EXPRESS CONNECTION DIAGRAMS
T - 1
R - 1
TIP
RING
DIALER
BELL
RELAY
PARADOX
SECURITY
SYSTEMS
To cabinet and
grounding rod
For zone connections
see diagrams below.
Can be used as
additional aux. power
terminals
-
+
-
+
AUX POWER 400mA max.
UL/ULC 250mA max. for 24 hr. standby.
To connect additional wiring to auxiliary power,
use the red (+) and black (-) keypad connectors.
Aux power will shut down if current exceeds 1A.
BELL OUTPUT
UL/ULC 650mA max.
will shut down if
current exceeds 3A.
BELL
SIREN
-
+
TRANSFO
A.C.
POWER
16.5VAC
40VA
Smoke and heat detectors
N.O. contacts
* Zone 3 = Fire zone if
zone definition
is "24 hour".
UL/ULC
12VDC / 7AH
UL: K12 model T16 V4O
ULC: Frost model FTC 1637
EOL
1KΩ
UL/ULC: Wheelock 46T-12
Warning: Improper
connection may result in
damage to the system.
KEYPAD
639/640
MAX 5 per system
KEYPAD
616/626/633
MAX 5 per system
N.C.
N.O.
1K
EOL
Ω
PS1
Keypad
1 or 2
Keypad
1 or 2
KEYSWITCH CONNECTION
KEYSWITCH
KYPD GRN
KYPD BLK
220Ω
S E C U R I T Y
S Y S T E M S
N.C.
N.O.
1K
EOL
Ω
*
1K
EOL
Ω
N.C.
N.C.
Keypad 1
Keypad 2
PS1 software version
Keypad software versions prior to
1.1
4.0 Keypad supervision must be OFF
}
PS1 software versions onward
Keypad software versions onward
2.0
4.0
Keypad supervision must be ON
}
*
(See Address
, key
)
090
[11] [12]
FIRE RESET
To program PGM1 to conduct 4 second smoke detector reset when
and
are pressed simultaneously:
[
] [
]
CLEAR
ENTER
Address =
(first digit)
Address =
039
[
]
040
[5] [10]
BYP
Address =
Address =
042
[2
] [6]
056
[10] [10] [4]
ND
FIRE ALARM ZONE CONNECTIONS
* PGM maximum 50mA
Smoke detector
power supervision
relay, 12VDC
COM
Smoke
detector
Smoke
detector
PGM
Z3
AUX
+
1K
EOL
Ω
+
+
-
-
Smoke detector must be 4 wire latching -
UL Falcon model 5454, ULC BRK 2412.
Power supervision relay model MR3-UL.
*
P
R
DOX
RMED
RE
DY
MAX 5
per system
For resistor values,
refer to 639/640
installation manuals.
Keyswitch can be used
in parallel with keypad
(or PS1).
GROUND START CIRCUIT
RNG
WHT
BLK
RED
YEL
MR3-UL
+AUX
PGM
WHT
BLK
RED
MR3-UL
+AUX
PGM
PGM OUTPUT RELAY
YEL
BRN
COM
N.C. N.O.
780 Industrial Blvd., St-Eustache, Montreal, Quebec, Canada J7R 5V3 Fax: (514) 491-2313 http://www.paradox.ca
Paradox Security Systems Graphic Dept
PRINTED IN CANADA
ESPRIT 748EXPRESS
WIRING DIAGRAM
BRN
GRY
GRN
RED
RJ31X
CA 38A
"TLM" LED: Short flash = OK
Long flash = Fault
Warning:
Disconnect
telephone line
before servicing.
Caution: Disconnect
battery before
replacing fuse.
Charging and battery test LED
(every 60 seconds)
OFF
= Disabled
Constant
= On Line
Four pin connector
can be used for
quick installation of
an Esprit keypad.
Service Keypad
+ AUX - GRN YEL
748HS
ESPRIT
748EXPRESS
ESPRIT