Redlion PM-50 Installation Manual
Read Online
Read the Redlion PM-50 Installation Manual online using the built-in PDF viewer.
Text of the manual
Drawing No. LP1140
Effective 08/2021
1
PM-50 Digital Input Graphical Panel Meters
Installation Guide
Visit www.redlion.net for how-to videos, full user manual and
additional support.
GENERAL DESCRIPTION
Red Lion’s Graphical Panel Meters, PM-50, is a platform of
meters designed to increase operator productivity and expose
critical plant floor data for use in project scheduling and process
improvements. Local operators can easily relate to the more
intuitive graphical display. Additional displays could be added to
provide even more data. The meters feature on-board Wi-Fi,
RS-485/Modbus and optional Ethernet or RS-232.
PM-50 features a 4.3" or 3.5" Color Graphical Touchscreen.
With an appearance like many smart devices, the display includes
a status bar and menu selections for easy operation. Recognizing
a swipe gesture allows multiple screens to be accessed.
Touchscreen push buttons can be displayed on the screen or
hidden during operation. The meters mount in standard industrial
hole sizes, 1/8 DIN and 1/16 DIN respectively.
On power-up, a Programming Wizard will assist you to get
started. You may also select a Programming App, Web Server, or
the traditional button/menu style for your programming needs.
For OEM customers a microSD Card allows for quick programming
and installation, saving time and money.
The Digital model accepts various pulse sensors. Onboard
outputs include two Solid State Outputs that can take up to 30 V
source voltage with software configurable source or sink options.
User inputs are also available to provide external interface and
control when required.
The PM-50 platform includes modular construction to add
additional capabilities. External modules can easily be installed in
the field to add a variety of output and communication options.
As safety advances through the Automation Industry, DC is the
more common choice for power. However, there are still many
requirements for AC power and they can be accommodated with
our AC to DC Power Module.
PACKAGE CHECKLIST
This product package should contain the items listed below. If
any items are missing or damaged, contact Red Lion immediately.
- PM-50 Digital Input Panel Meter
- Accessory Pack
- Installation Guide
SAFETY SUMMARY
All safety related regulations, local codes and instructions that
appear in this document or on equipment must be observed to
ensure personal safety and to prevent damage to either the
device or equipment connected to it.
Do not use these products to replace proper safety interlocking.
No software-based device (or any other solid-state device) should
ever be designed to be responsible for the maintenance of
personnel safety or consequential equipment not equipped with
safeguards. Red Lion disclaims any responsibility for damages,
either direct or consequential, that result from the use of this
equipment in a manner not specified.
CAUTION: Risk of Danger
Read complete instructions prior to installation and
operation of the unit.
ATTENTION : Risque de danger
Lire les instructions complètes avant l’installation et
l’utilisation de l’appareil.
WARNING - EXPLOSION HAZARD - When in hazardous
locations, disconnect power before replacing or wiring
modules.
AVERTISSEMENT - RISQUE D’EXPLOSION - Dans les
endroits dangereux, débranchez l’alimentation électrique
avant de remplacer ou de câbler les modules.
This equipment is suitable for use in Class I, Division 2,
Groups A, B, C, D, or non-hazardous locations only.
Cet équipement est adapté à une utilisation dans des
endroits de classe I, Division 2, Groupes A, B, C, D, ou
dans des endroits non dangereux seulement.
z Universal Digital (pulsed) Inputs
z 4.3" (1/8 DIN) or 3.5" (1/16 DIN) 18-bit color display with
resistive touchscreen and swipe gesture
z DC powered, AC powered with optional module
z Choice of programming options
z Data Access Point; communication choices - Wi-Fi, RS-485/
Modbus and optional Ethernet or RS-232
z NEMA 4X/IP65 sealed front bezel
FOR USE IN HAZARDOUS LOCATIONS:
Class I, Division 2, Groups A, B, C, and D
T4A
C
US
US
UL
R
LISTED
IND.CONT. EQ.
E317425
Drawing No. LP1140
Effective 08 2021
GENERAL METER SPECIFICATIONS
Note: The PM-50 4.3 inch host accepts a maximum of 5
modules while the 3.5 inch host accepts a maximum of 3.
Only one module from each function type (i.e. communication,
relay, analog output) can be installed.
1. POWER: The meter is intended to be powered by NEC/CEC
class 2, IEC/EN/UL 60950-1 LPS or UL/CSA 601010-1
Limited Energy power source.
MODEL
4.3-INCH
3.5-INCH
Input Voltage (Volts)
10-30 VDC
10-30 VDC
Max Power PM-50 only
4.6 W
4.6 W
Max Power PM-50, with modules
12 W
12 W
Host Isolation: 500 Vrms for 1 min. to all inputs and outputs.
2. DISPLAY: 4.3" or 3.5" Color TFT display with resistive analog
touch screen
SIZE
4.3-INCH
3.5-INCH
TYPE
TFT
TFT
COLORS
262,144
262,144
PIXELS
480 X 272
320 X 240
BRIGHTNESS
420 cd/m2
540 cd/m2
LED BACKLIGHT LIFE*
30,000 HR TYP.
30,000 HR TYP.
* Lifetime at room temperature (25°C)
3. SENSOR POWER:
+24 VDC, ±5% @ 50 mA max.
4. COUNTER DISPLAYS: 9 digits available
Display Range: -99,999,999 to 999,999,999
Over Range Display: Overrange
Under Range Display: Underrange
Display Designators: Cnt-A, Cnt-B, Cnt-C
Maximum Count Rates: 50% duty cycle
If Setpoints Disabled: 35 KHz for all modes except Quadrature
x4 (32 KHz)
If Setpoint(S) Enabled: 20 KHz for any mode except
Quadrature x1 (19 KHz), Quadrature x2 (17 KHz) and
Quadrature x4 (10 KHz)
5. RATE DISPLAYS: 6-digit
Maximum Frequency: 50 KHz
Minimum Frequency: 0.001 Hz
Display Update Time: 0.1 to 999.9 seconds
Accuracy: ±0.01%
6. SIGNAL INPUTS (INPUT A and INPUT B):
Software configurable input types including switch contacts,
TTL outputs, magnetic pickups and all standard RLC
sensors. Inputs are configurable for current sinking or
current sourcing outputs with input filtering for low
frequency signals or switch contact debounce. Not isolated
from the sensor input common.
Logic: Input trigger levels VIL = 1.2 V max.; VIH = 3.75 V min.
Sink: Adds internal 7.8 KΩ pull-up resistor to +5 VDC, 0.7
mA max
Source: Adds internal 3.9 KΩ pull-down resistor, 7.3 mA
max. at 28 VDC, VMAX = 30 VDC
Magnetic Pickup:
VIN_PK = 200 mV; VIN_HSYS = 100 mV; Must also have SRC
selection turned on through software
VMAX = ± 40 VPEAK or 28 Vrms
Dual Count Modes:
When any dual count mode is used, then User Inputs 1 and/
or 2 will accept the second signal of each signal pair. The user
inputs do not have the Logic/Mag, HI/LO Freq, and Sink/
Source software selections. The user inputs are inherently a
logic input with no low frequency filtering implemented in
software. The user input may only be selected for sink/
source by the User Input Active parameter.
7. USER INPUTS: Two programmable user inputs
Max. Continuous Input: 30 VDC
Isolation to Sensor Input Common: Not isolated.
Logic State: User programmable for sink/source (Lo/Hi)
INPUT STATE
LO/SINK
HI/SOURCE
20 KΩ pull-up to +3.3 V
20 KΩ pull-down
Active
VIN < 0.9 VDC
VIN > 2.4 VDC
Inactive
VIN > 2.4 VDC
VIN < 0.9 VDC
8. MEMORY: Nonvolatile memory retains all programmable
parameters and display values.
Memory Card: microSD slot accepts up to 32 GB capacity
cards in FAT16/FAT32 format.
9. RS485 SERIAL PORT: Uses Modbus protocol
Baud Rate: Up to 115,200
Data Format: 7/8 bit; odd, even, or no parity; 1 or 2 stop bits
Isolation: 500 Vrms to sensor, user power and digital inputs.
Not isolated to solid state outputs
10. Wi-Fi CAPABILITIES:
Wi-Fi: Power output up to 20.5 dBm
Frequency:
TECHNOLOGY
CHANNELS
FREQUENCIES
Wi-Fi
1-13
2412-2484 MHz
Note: Channel/frequency limitation is enforced based on
configured country/region code.
Wi-Fi Compliance: TCP/IP; 802.11 b/g/n
11. ON-BOARD DUAL SSR OUTPUTS: Both outputs must be
used either in SINKING or in SOURCING mode together.
Sinking Mode:
Type: Switched DC, N-channel open drain MOSFET
Max Sink Current: 100 mA
VDS ON: 0.3 V @ 100 mA
VDS MAX: 30 VDC
Offstate Leakage Current: 0.5 mA max
Sourcing Mode:
Type: Switched DC, P-channel open source MOSFET
Max Source Current: 100 mA
VDS ON: 0.3 V @ 100 mA
VDS MAX: 30 VDC
Offstate Leakage Current: 0.5 mA max
12. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -10 to 55 °C
Storage Temperature Range: -20 to 60 °C
Operating and Storage Humidity: 0 to 85% max. RH non-
condensing
Vibration to IEC 68-2-6: Operational 5-500 Hz, 2 g
Shock to IEC 68-2-27: Operational 20 g (10 g relay)
Altitude: Up to 2000 meters
Installation Category II, Pollution Degree 2 as defined in IEC/
EN 60664-1.
13. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
FCC ID#: 2AC7Z-ESP32WROOM32U
UL Hazardous: File # E317425
Type 4X Indoor/IP65 Enclosure rating (Face only) for all models
IP20 Enclosure rating (Rear of unit)
14. CONNECTIONS: High compression spring-clamp terminal
block
Effective 08 2021
Drawing No. LP1140
3.23
(82.09)
3.74 (95.09)
0.56
(14.25)
7.45 (189.22)
WITH MAXIMUM NUMBER OF 3 MODULES
3.63 (92.20)
WITHOUT MODULES
1.76
(44.70)
1.78
(45.19)
2.46
(62.42)
3.5 Inch Display
3.34
(84.91)
4.87 (123.59)
3.63 (92.20)
WITHOUT MODULES
0.56
(14.25)
6.31 (160.31)
WITH MAXIMUM OF 5 MODULES
1.76
(44.70)
2.46
(62.40)
3.62 (91.95)
4.3 Inch Display
DIMENSIONS In inches (mm)
Wire Strip Length: 0.32-0.35" (8-9 mm)
Wire Gauge Capacity: Four 28 AWG (0.32 mm) solid,
two 20 AWG (0.61 mm) or one 16 AWG (2.55 mm)
15. CONSTRUCTION: This unit is rated NEMA 4X/IP65 for
indoor use only. IP20 Touch safe. One piece bezel/ case. Flame
resistant. Panel gasket, module locks, and mounting panel latch
included.
16. MOUNTING REQUIREMENTS: Maximum panel thickness is
0.25" (6.35 mm). For NEMA 4X/IP65 sealing, a steel panel with
a minimum thickness of 0.04" (1.02 mm) is recommended.
Panel Latch Screw Torque: 5.0 lbf-in (0.56 Nm) CAUTION: DO
NOT OVERTIGHTEN
17. WEIGHT:
4.3: 11.5 oz (326 g)
3.5: 8.1 oz (229.6 g)
INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not exceed
its own operating temperature and provides good air circulation.
Placing the unit near devices that generate excessive heat should
be avoided.
The PM-50 4.3 and 3.5 inch models meet NEMA 4X/IP65
requirements when properly installed. This unit is designed for
through-panel mounting. The mounting surface should have a
minimum thickness of 0.04" (1.02 mm) and maximum thickness of
0.25" (6.35 mm). Cut the mounting hole per the dimensions
shown in the diagram. Care should be taken to remove any loose
material from the mounting cut-out to prevent that material from
falling into the unit during installation. Prepare the panel cutout
to the dimensions shown.
For hazardous location installation the following shall be taken
into consideration:
- The device shall be panel mounted in a tool accessible
enclosure with a minimum ingress protection rating of at
least IP64 as defined in IEC/EN 60529.
- This device is open-type and must be mounted in a suitable
dust-tight end-enclosure in accordance with articles 500
and 502 of the NEC and positioned so only the face of the
display is exposed.
- Must be wired using Division 2 wiring methods as specified
in article 501-4(b), 502-4(b), and 503-3(b) of the National
Electric Code, NFPA 70 for installation within the United
States, or as specified in section 19-152 of Canadian
Electrical Code for installation in Canada.
3.62
(92)
1.77
(45)
4.3 Inch Meter
1.77
(45)
1.77
(45)
3.5 Inch Meter
Drawing No. LP1140
Effective 08 2021
METER INSTALLATION
Slide the panel gasket over the rear of the unit to the back of
the bezel. The unit should be installed fully assembled. Insert the
unit into the panel cutout.
While holding the unit in place, place either the top or bottom
panel latch on the rear of the unit closest to the panel cutout so
that the tabs of the panel latch engage in the slots on the case.
Repeat this process with the other half of the panel latch. Secure
the latch with the panel mounting screws provided. To achieve a
proper seal, tighten the latch screws evenly until the unit is snug
in the panel (Torque to approximately 5 in-lbs [56 N-cm]). Do not
over-tighten the screws.
EMC INSTALLATION GUIDELINES
Although Red Lion Controls products are designed with a high
degree of immunity to Electromagnetic Interference (EMI), proper
installation and wiring methods must be followed to ensure
compatibility in each application. The type of the electrical noise,
source or coupling method into a unit may be different for various
installations. Cable length, routing, and shield termination are
very important and can mean the difference between a successful
or troublesome installation. Listed are some EMI guidelines for a
successful installation in an industrial environment.
1. A unit should be mounted in a metal enclosure, which is
properly connected to protective earth.
2. Use shielded cables for all Signal and Control inputs. The
shield connection should be made as short as possible. The
connection point for the shield depends somewhat upon the
application. Listed below are the recommended methods of
connecting the shield, in order of their effectiveness.
a. Connect the shield to earth ground (protective earth) at one
end where the unit is mounted.
b. Connect the shield to earth ground at both ends of the cable,
usually when the noise source frequency is over 1 MHz.
3. Never run Signal or Control cables in the same conduit or
raceway with AC power lines, conductors, feeding motors,
solenoids, SCR controls, and heaters, etc. The cables should
be run through metal conduit that is properly grounded. This
is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if
the installation is near a commercial radio transmitter. Also,
Signal or Control cables within an enclosure should be routed
as far away as possible from contactors, control relays,
transformers, and other noisy components.
4. Long cable runs are more susceptible to EMI pickup than
short cable runs.
5. In extremely high EMI environments, the use of external EMI
suppression devices such as Ferrite Suppression Cores for
signal and control cables is effective. The following EMI
suppression devices (or equivalent) are recommended:
Fair-Rite part number 0443167251 (Red Lion #FCOR0000)
Line Filters for input power cables:
Schaffner # FN2010-1/07 (Red Lion #LFIL0000)
6. To protect relay contacts that control inductive loads and to
minimize radiated and conducted noise (EMI), some type of
contact protection network is normally installed across the
load, the contacts or both. The most effective location is
across the load.
a. Using a snubber, which is a resistor-capacitor (RC) network or
metal oxide varistor (MOV) across an AC inductive load is very
effective at reducing EMI and increasing relay contact life.
b. If a DC inductive load (such as a DC relay coil) is controlled
by a transistor switch, care must be taken not to exceed the
breakdown voltage of the transistor when the load is
switched. One of the most effective ways is to place a
diode across the inductive load. Most Red Lion products
with solid state outputs have internal zener diode
protection. However external diode protection at the load is
always a good design practice to limit EMI. Although the
use of a snubber or varistor could be used.
Red Lion part numbers: Snubber: SNUB0000
Varistor: ILS11500 or ILS23000
7. Care should be taken when connecting input and output
devices to the instrument. When a separate input and output
common is provided, they should not be mixed. Therefore a
sensor common should NOT be connected to an output
common. This would cause EMI on the sensitive input
common, which could affect the instrument’s operation.
Visit http://www.redlion.net/emi for more information on EMI
guidelines, Safety and CE issues as they relate to Red Lion
products.
4.3 Inch Meter
3.5 Inch Meter
Effective 08 2021
Drawing No. LP1140
WIRING
All power, input and output (I/O) wiring must be in accordance
with Class I, Division 2 wiring methods and in accordance with
the authority having jurisdiction. Electrical connections are made
via pluggable spring-clamp terminal blocks. It is recommended
that the power supplied to the meter be protected by a fuse or
circuit breaker.
When wiring the meter, refer to the label on the unit for pin-out
numbering against those shown in the wiring drawings for proper
wire position. Strip and connect the wire according to the
terminal block specifications on Page 3. Use a small screwdriver
to press down on tab next to the terminal position to open the
spring clamp. Insert the wire into the terminal position and then
remove the screwdriver to engage the spring-clamp.
POWER WIRING
Must use a Class 2 circuit according to
National Electrical Code (NEC), NFPA-70 or
Canadian Electrical Code (CEC), Part I, C22.1 or
a Limited Power Supply (LPS) according to IEC/
EN 60950-1 or Limited-energy circuit according
to IEC/EN 61010-1.
+
-
1
2
VDC +
VDC -
10 to 30 VDC
DC Power
INPUT SIGNAL WIRING
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the controller
application, the sensor input common must be suitably isolated from hazardous live earth referenced voltages; or input common must
be at protective earth ground potential. If not, hazardous live voltage may be present at the User Inputs and User Input Common
terminals. Appropriate considerations must then be given to the potential of the user input common with respect
to earth common, and the common of the isolated plug-in modules with respect to input common.
14
15
MAGNETIC PICKUP
INP COM
INP A
14
15
to 2.5 mA MAX.
Resistor to limit current
AC
INP COM
INP A
14
10
15
2.2KΩ
INP COM
+24V EXC
INP A
NPN O.C.
10
14
15
+24V EXC
INP COM
INP A
PNP O.C.
10
14
15
+24V EXC
INP COM
INP A
14
15
+5V
COMM
DIODE
INP COM
INP A
14
15
INP COM
INP A
10
15
+24V EXC
INP A
10
14
15
+24V EXC
INP COM
INP A
AC Inputs From Tach Generators, Etc.
Input A
Two Wire Proximity, Current Source
Input A
Magnetic Pickup
Input A
Current Sourcing Output
Input A
Interfacing With TTL
Input A
Current Sinking Output
Input A
Switch or Isolated Transistor; Current Sink
Input A
16
10
14
15
NPN O.C.
+24V EXC
INP B
INP COM
INP A
Current Sink Output; Quad/Direction
Single Counter A
Switch or Isolated Transistor; Current Source
Input A
Emitter Follower; Current Source
Input A
16
10
14
15
NPN O.C.
NPN O.C.
13
Rate
Count
USER 1
+24V EXC
INP B
INP COM
INP A
10
12
13
14
NPN O.C.
Count A
15
16
NPN O.C.
Count B
USER 2
USER 1
+24V EXC
INP B
INP COM
INP A
Current Sink Output; Quad/Direction
Counter A
& Rate B
Counter A &
Counter B
Current Sink Output; Quad/Direction
Ensure software configuration is set to correspond with your required application wiring.
User Input Configured in Sink Position in Software
User Input Configured in Sink Position in Software
Shaded areas not recommended for counting applications.
Software Configuration - Select Mag Mode
If using Single Counter B, then wire signal to 16 and Quad/Direction to 12.
Settings configured in Software.
Drawing No. LP1140
Effective 08 2021
USER INPUT WIRING
User Input terminal does not need to be wired in order to remain in the inactive state.
Sinking Logic
When the parameter is
programmed to Low, check
with device GUI option. The
user inputs of the controller
are internally pulled up to
+3.3 V with 20 KΩ
resistance. The input is
active when it is pulled low
(<0.9 V).
Sourcing Logic
When the parameter is
programmed to High, check
with device GUI option. The
user inputs of the controller
are internally pulled down to
0 V with 20 KΩ resistance.
The input is active when a
voltage greater than 2.4 VDC
is applied.
USER/EXC COM
USER 1
USER 2
12
13
11
OR
12
11
13
+
-
(30V max.)
SUPPLY
V
USER 1
USER 2
OR
USER/EXC COM
ON-BOARD DUAL SSR WIRING
Sinking Mode
Sourcing Mode
100 mA PER OUTPUT
SSR OUTPUTS SINKING MODE
LOAD
4
OP1
OP2
LOAD
OP COM
5
6
30V
+ -
3
OP EXT POWER
100 mA PER OUTPUT
SSR OUTPUTS SOURCING MODE
+ -
OP EXT POWER
3
LOAD
4
OP1
5
OP2
LOAD
30V
6
OP COM
The SSR outputs require meter configuration to address their functionality.
The drawings below illustrate the wiring for each option.
RS485/MODBUS
Transmit
Enable
+5V
130K
B (-)
A (+)
COM
130K
RX
TX
8
7
9
RS485 2-WIRE CONNECTIONS
See appropriate document for instructions on module installation and wiring support.
CONFIGURING A PM-50
Various options are available to configure your PM-50 so you
can choose the one that fits your requirement.
Programming Wizard
On initial power up a Programming Wizard will offer assistance.
Proceeding with the Wizard will help with the basic configuration
including screen set-up, selecting the input and programming the
output. After completion your device will display the items you
selected. Additional capabilities can be accessed via the Programming
App, Web Server, or manually entering the programming.
Web Interface
To configure the device for web access, login as Admin and
follow the below steps to setup Wi-Fi:
1. Go to System → Network Configuration → Wi-Fi Configuration
2. Enable Wi-Fi as “ON” and select the right arrow
3. From here, make your Wi-Fi configuration selections based on
your connection setup.
App Connectivity
Programming and monitoring of the device can be done via an
App. Go to the App Store and search for PM50 by Red Lion.
Install the app on your smart device. With Wi-Fi enabled,
monitoring and controlling of the device can be done through the
app. Now programming the device is as easy as making some
selections and downloading to the device.
Effective 08 2021
Drawing No. LP1140
INSERTION/REMOVAL OF THE microSD CARD
The microSD Card can be used to flash new firmware on
PM-50 by placing an image file on the formatted microSD card. It
can also be used to import previous configuration through
import/export configuration menu. The card is then inserted into
the PM-50 slot located next to the terminals on the bottom side
of the unit. Refer to the User manual for more information on the
proper names and locations of the files.
After inserting the microSD card into the unit, navigate to the
Device/Misc. Configuration/Firmware Upload screen on the
PM-50 to upload the latest firmware version.
MicroSD Card
Orientation
4.3 Inch Meter
MicroSD Card
Orientation
3.5 Inch Meter
ORDERING INFORMATION
DESCRIPTION
PART NUMBER
Graphical Panel Meter, 4.3" Display, Digital Input
PM500D0400800F00
Graphical Panel Meter, 3.5" Display, Digital Input
PM500D0301600F00
Accessories
TYPE
DESCRIPTION
PART NUMBER
Modules
RS232 Serial Communications Module
PMM000CM23200000
Ethernet Communications Module
PMM000CMENT00000
Analog Output Module
PMM000I0AN000000
Dual Setpoint Relay Output Module
PMM000I0RL200000
Quad Setpoint Relay Output Module
PMM000I0RL400000
AC to DC Power Module
PMM000PWACP00000
Misc.
Replacement Rear Cover/Bus Board with Spacer Module (4.3" model only)
PMA000CP00800000
Conversion Panel 92 mm x 75 mm to 1/8 DIN
PMA000MK00800000
Conversion Panel 68 mm x 68 mm to 1/16 DIN
PMA000MK01600000
Replacement Module Lock Pins
PMA000MKLP00000
4.3" Protective Screen Overlay
PMA000SP00800000
3.5" Protective Screen Overlay
PMA000SP01600000
MicroSD Card
SD032G00
Drawing No. LP1140
Effective 08 2021
RED LION CONTROLS TECHNICAL SUPPORT
If for any reason you have trouble operating, connecting, or
simply have questions concerning your new product, contact Red
Lion’s technical support.
Support: support.redlion.net
Website: www.redlion.net
Inside US: +1 (877) 432-9908
Outside US: +1 (717) 767-6511
Red Lion Controls, Inc.
20 Willow Springs Circle York, PA 17406
TRADEMARK ACKNOWLEDGMENTS
Wi-Fi® and the Wi-Fi logo are registered trademarks of Wi-Fi
Alliance.
COPYRIGHT
©2021 Red Lion Controls, Inc. All rights reserved. Red Lion
and the Red Lion logo are trademarks of Red Lion Controls,
Inc. All other company and product names are trademarks of
their respective owners.
LIMITED WARRANTY
(a) Red Lion Controls Inc. (the “Company”) warrants that all Products shall be free from defects in material and
workmanship under normal use for the period of time provided in “Statement of Warranty Periods” (available at
www.redlion.net) current at the time of shipment of the Products (the “Warranty Period”). EXCEPT FOR THE
ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT TO THE
PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY; (B) WARRANTY OF FITNESS FOR
A PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY
RIGHTS OF A THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW, COURSE OF DEALING, COURSE
OF PERFORMANCE, USAGE OF TRADE OR OTHERWISE. Customer shall be responsible for determining that a
Product is suitable for Customer’s use and that such use complies with any applicable local, state or federal law.
(b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a
result of Customer’s failure to store, install, commission or maintain the Product according to specifications; (ii)
Customer alters or repairs such Product without the prior written consent of Company.
(c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its
sole discretion, either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that,
if Company so requests, Customer shall, at Company’s expense, return such Product to Company.
(d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER’S SOLE AND EXCLUSIVE
REMEDY AND COMPANY’S ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET
FORTH IN PARAGRAPH (a).
BY INSTALLING THIS PRODUCT, YOU AGREE TO THE TERMS OF THIS WARRANTY, AS WELL AS ALL OTHER
DISCLAIMERS AND WARRANTIES IN THIS DOCUMENT.