Mircom FA-300 Series Operation & User’s Manual
Read Online
Read the Mircom FA-300 Series Operation & User’s Manual online using the built-in PDF viewer.
Text of the manual
LED Fire Alarm Control Panel
LT-953 Rev. 0
June 2004
User Guide
Advanced Life Safety Solutions
ZONE DISCONNECT
ZONE DISCONNECT
INFO
GROUND
FAULT
CPU
FAULT
REMOTE
TROUBLE
LAMP
TEST
AC
ON
COMMON
ALARM
COMMON
SUPERVISORY
COMMON
TROUBLE
BATTERY
TROUBLE
BUZZER
SILENCE
FIRE
DRILL
SIGNAL
SILENECE
SYSTEM
RESET
AUXILIARY
DISCONNECT
LAMP
TEST
MENU
Advanced Life Safety Solutions
FA-300 SERIES
Fire Alarm Control Panel
Advanced Life Safety Solutions
FA-300 SERIES
Fire Alarm Control Panel
ZONE DISCONNECT
ZONE DISCONNECT
INFO
GROUND
FAULT
CPU
FAULT
REMOTE
TROUBLE
LAMP
TEST
AC
ON
COMMON
ALARM
COMMON
SUPERVISORY
COMMON
TROUBLE
BATTERY
TROUBLE
BUZZER
SILENCE
FIRE
DRILL
SIGNAL
SILENECE
SYSTEM
RESET
AUXILIARY
DISCONNECT
LAMP
TEST
MENU
FA-300 Series LED Fire Alarm Control Panel User Guide
i
Contents
Contents................................................................................................................................... i
Introduction ............................................................................................................................. 1
About this Manual ................................................................................................................ 1
Technical Support ................................................................................................................ 1
Main Display ............................................................................................................................ 2
The Buzzer and LED Indicators ............................................................................................. 3
Common LED Indicators...................................................................................................... 3
Alarm Circuit Indicators........................................................................................................ 5
Supervisory Circuit Indicators .............................................................................................. 5
Monitor Circuit Indicators ..................................................................................................... 6
Trouble-only Circuit Indicators ............................................................................................. 6
Signal Circuit Indicators ....................................................................................................... 6
Main Display Buttons.............................................................................................................. 7
Circuit (Zone) Disconnect Buttons........................................................................................ 8
Glossary................................................................................................................................... 9
FA-300 Series LED Fire Alarm Control Panel User Guide
1
Introduction
About this Manual
This user’s guide provides information on the main indicators and controls of the FA-300 Fire Alarm Control Panel.
Specifically, with this manual you will learn about what the LEDs indicate and what the buttons on the main display
do.
Refer to the Glossary on page 9 for an explanation of commonly used terms in this manual.
Technical Support
For all technical support inquiries, please contact Mircom’s Technical Support Department between 8 A.M. and 5
P.M. (EDT) Monday through Friday, excluding holidays.
Email: [email protected]
Local Phone: 905-695-3535
Toll-Free Phone: 1-888-449-3535
Local Fax: 905-660-4113
Toll-Free Fax: 1-888-660-4113
Refer to the diagram below for the LED indicators and control buttons locations.
The main display panel on the main fire alarm control board consists of:
• 18 common LED indicators (top half of display)
• Eight common buttons (top half of display)
• Up to 12 Initiating circuit alarm LEDs and 12 initiating circuit trouble LED indicators
• Four indicating circuit LEDs (labeled NAC- Notifying Appliance Circuit)
• Up to sixteen disconnect buttons (12 for initiating circuit & four for indicating circuits)
LED indicators may be amber, red, or green, and may illuminate continuously (steady), or at one of two flash rates:
• Fast flash (supervisory): 120 flashes per minute
• Trouble flash (trouble): 20 flashes per minute
Paper labels for buttons and indicators
Each display is supplied with laser printable labels. These labels slide into the plastic label templates on the panel.
The label paper for the main display includes English and French versions (Mircom # NP-2005.
WALK
TEST
REMOTE
TROUBLE
CPU FAIL
GROUND
FAULT
SIGNAL
SILENCE
FIRE
DRILL
ACK
GENERAL
ALARM
SYSTEM
RESET
AUX
DISCONNECT
LAMP
TEST
BUZZER
SILENCE
A.C.
ON
COMMON
ALARM
COMMON
SUPV
COMMON
TROUBLE
BATTERY
TROUBLE
ZONE-1
DISCONNECT
ZONE-3
DISCONNECT
ZONE-5
DISCONNECT
ZONE-7
DISCONNECT
ZONE-9
DISCONNECT
ABORT
ZONE-2
DISCONNECT
ZONE-4
DISCONNECT
ZONE-6
DISCONNECT
ZONE-8
DISCONNECT
ZONE-10
DISCONNECT
MANUAL
RELEASE
NAC-1
DISCONNECT
RELEASE
CIRCUIT-1
NAC-2
DISCONNECT
RELEASE
CIRCUIT-2
FA-300 Series LED Fire Alarm Control Panel User Guide
3
The Buzzer and LED Indicators
Common LED Indicators
Buzzer
The buzzer sounds if there is a fire alarm, a supervisory alarm, or a trouble in the fire alarm system. It turns off if the
condition causing the buzzer to sound goes away or if the Buzzer Silence Button is pressed.
AC On LED
Common Alarm LED
Common Supervisory LED
Common Trouble LED
Remote Trouble LED
Fire Drill LED
Acknowledge LED
General Alarm LED
The green AC On LED illuminates steadily as long as the main power is above minimum level. The
indicator turns off when the level falls below the minimum level and the panel switches to standby
(battery) power.
The red Common Alarm LED will illuminate steadily whenever there is a fire alarm. If the panel is set
for two stage operation, pressing the red General Alarm button will also turn on the Common Alarm
indicator. This indicator will remain on until the system is reset.
The amber Common Supervisory LED illuminates at the fast flash rate when there is a supervisory
alarm in the fire alarm system. For non-latching supervisory alarms, the Supervisory LED will turn
off when the condition causing the alarm goes away. For latching supervisory alarms, this LED
remains on until the panel is reset.
The amber Common Trouble LED flashes at the trouble flash rate when the panel detects any
trouble condition. For non-latching trouble conditions, the Common Trouble LED will turns off when
the condition causing the alarm goes away. For latching trouble conditions, this LED remains on
until the panel is reset.
The amber Remote Trouble LED flashes at the trouble flash rate if the panel detects a trouble at the
City Tie or UDACT module, communication trouble with a remote annunciator, or a local trouble at a
remote annunciator.
The amber Fire Drill LED illuminates steadily after the Fire Drill button is pressed. This LED remains
on until the Fire Drill button is pressed again.
If the panel is configured as a two-stage system, the amber Acknowledge LED flashes at the fast
flash rate while the Auto General Alarm timer is timing out. The Acknowledge indicator illuminates
steadily when the General Alarm timer is cancelled by the pressing of the Acknowledge or Signal
Silence buttons. If the Auto General Alarm timer times out and puts the panel into general alarm,
this LED turns off.
If the panel is configured as a two-stage system, the red General Alarm LED illuminates steadily
when the General Alarm button is pushed, a General Alarm Initiating circuit is activated, or the Auto
General Alarm timer times out. Once the General Alarm LED has turned on, it will stay active until
the panel is reset.
A.C.
ON
COMMON
ALARM
COMMON
SUPV
COMMON
TROUBLE
REMOTE
TROUBLE
FIRE
DRILL
ACK
GENERAL
ALARM
The Buzzer and LED Indicators
4
Walk Test LED
CPU Fail LED
Auxiliary Disconnect LED
Signal Silence LED
Battery Trouble LED
Ground Fault LED
System Reset LED
The amber Walk Test indicator illuminates steadily to indicate that the panel is in walk test mode. If
the panel is left in this mode for over an hour with no operator activity, the panel will return to normal
and the Walk Test indicator will turn OFF.
The CPU Fail LED flashes amber at the trouble flash rate to indicate a microprocessor failure on the
main board.
The amber Auxiliary Disconnect LED flashes at the trouble rate when the Auxiliary Disconnect
button is pressed. It turns off when the Auxiliary Disconnect button is pressed a second time. When
on, the Auxiliary Disconnect LED signifies that auxiliary alarm relay and relay adder modules (if
disconnect is enabled) are not activated. If installed and enabled, the city tie module and the smart
relay annunciator relays are also inactive.
The Signal Silence indicator flashes amber at the trouble rate when indicating circuits are silenced
either by the Signal Silence button or by the Auto Signal Silence timer. It turns off when the signals
are re-sounded by a subsequent alarm or when the panel is reset.
The amber Battery Trouble LED flashes at the trouble rate when the battery is either low or
disconnected.
The amber Ground Fault LED flashes at the trouble rate when the ground fault detector detects a
ground fault on any field wiring. It turns off when the ground fault is cleared.
The amber System Reset LED illuminates for a short time when the System Reset button is
pressed.
WALK
TEST
CPU FAIL
AUX
DISCONNECT
SIGNAL
SILENCE
BATTERY
TROUBLE
GROUND
FAULT
SYSTEM
RESET
FA-300 Series LED Fire Alarm Control Panel User Guide
5
Alarm Circuit Indicators
This operation applies to Initiating Circuits configured as Verified Alarm, Non-Verified Alarm, Water flow Alarm,
Sprinkler Alarm, or General Alarm Circuits. The following table summarizes the indications at different events:
Supervisory Circuit Indicators
This operation applies to initiating circuits configured as latching or non-latching supervisory circuits. The following
table summarizes the indications in response to different events:
Event
Circuit Trouble LED
Configuration
Open circuit or (Style D)/(Class A) trouble
Flashes at the trouble
rate (amber)
Verified Alarm
Non-Verified Alarm
Water Flow Alarm
Sprinkler Alarm
General Alarm
Disconnected
Flashes at the trouble
rate (amber)
Circuit in Alarm
OFF
Event
Circuit Trouble LED
Configuration
Circuit in Alarm
Steady (red)
Pre-alarm
Fast flash rate (red)
Verified Alarm
Sprinkler Alarm
Water flow Alarm
Active circuit reconnected
OFF
Event
Circuit Trouble LED
Configuration
Open circuit or (Style D)/(Class A) trouble
Flashes at the trouble
rate (amber)
Latching Sup.
Non-Latching Sup.
Disconnected
Flashes at the trouble
rate (amber)
Circuit in Alarm
OFF
Event
Circuit Trouble LED
Configuration
Circuit in Alarm
Steady (amber)
Latching Sup.
Non-Latching Sup.
Active circuit reconnected
Fast flash rate (amber)
The Buzzer and LED Indicators
6
Monitor Circuit Indicators
This operation applies to initiating circuits configured as monitor circuits. The following table summarizes the
indications in response to different events:
Trouble-only Circuit Indicators
This operation applies to initiating circuits configured as Trouble-Only Circuits. The following table summarizes the
indications in response to different events:
Signal Circuit Indicators
This operation applies to indicating circuits of any type. The Circuit Trouble Indicator flashes amber at the Trouble
Rate to indicate short-circuit or open-circuit trouble, or if the circuit is Disconnected.
Event
Circuit Trouble LED
Configuration
Open circuit or (Style D)/(Class A)
trouble
Flashes at the trouble rate
(amber)
Monitor
Disconnected
Flashes at the trouble rate
(amber)
Circuit Active
OFF
Event
Circuit Trouble LED
Configuration
Circuit Active
Steady (amber)
Monitor
Active circuit reconnected
Fast flash rate (amber)
Event
Circuit Trouble LED
Configuration
Open circuit or (Style D)/(Class A)
trouble
Flashes at the trouble rate
(amber)
Trouble Only
Disconnected
Flashes at the trouble rate
(amber)
Short Circuit
Flashes at the trouble rate
(amber)
Event
Circuit Trouble LED
Configuration
Open Circuit
Flashes at the trouble rate
(amber)
Signal
Disconnected
Flashes at the trouble rate
(amber)
Short Circuit
Flashes at the trouble rate
(amber)
FA-300 Series LED Fire Alarm Control Panel User Guide
7
Main Display Buttons
System Reset Button
Signal Silence Button
Fire Drill Button
Acknowledge Button
General Alarm Button (or Info button for single stage system)
Auxiliary Disconnect Button
Lamp Test Button
Buzzer Silence Button
The System Reset button resets the fire alarm control panel and all circuits.
Pressing the Signal Silence button when the panel is in alarm deactivates any silenceable signal
devices in the fire alarm system. Non-Silenceable signal devices are unaffected. If you press the
Signal Silence button a second time, or if there is a subsequent alarm, the signals will re-sound. If
the panel has been configured with a Signal Silence Inhibit timer, this button will not work until the
timer times out. This button also does not work if you have pressed the Fire Drill button.In a two
stage system, if the Auto General Alarm timer has timed out, this button also performs the same
function as the Acknowledge button.
Pressing the Fire Drill button will simulate a fire alarm by activating the fire alarm signals without
transmitting an alarm to the central station. To cancel the fire drill, press the button again. If the fire
alarm system goes into a real alarm while you are performing a fire drill, this button will not turn off
the signals or activate any programmed relays.
If the panel is not configured for two-stage operation, this button is not active. If the panel is
configured for two-stage operation, pressing the Acknowledge button while the Auto General Alarm
timer is timing (there is an alarm in the panel, but it is still in the first stage), the timer is cancelled
and the amber Acknowledge LED illuminates steadily.
If the panel is not configured for two-stage operation, this button does nothing. If the panel is
configured for two-stage operation, pressing the General Alarm button immediately sends the
panel into second stage general alarm. It will also re-activate the signals if they have been silenced
during general alarm. The general alarm condition remains active until the panel is reset.
Pressing the Auxiliary Disconnect button activates the auxiliary disconnect function. Pressing the
button again de-activates this function.
Pressing and holding the Lamp Test button causes all front panel LEDs to illuminate and sounds
the buzzer. Use this button to test that all LEDs in the main display are working. If you hold the
Lamp Test button for more than ten seconds, the Trouble LED will illuminate.
Pressing the Buzzer Silence button while the buzzer is sounding silences the buzzer. The buzzer
will resound if there is a subsequent event. Pressing the button when the buzzer is not sounding
has no effect.
SIGNAL
SILENCE
SIGNAL
SILENCE
FIRE
DRILL
ACK
GENERAL
ALARM
AUX
DISCONNECT
LAMP
TEST
BUZZER
SILENCE
Circuit (Zone) Disconnect Buttons
8
Circuit (Zone) Disconnect Buttons
Circuit (zone) disconnect buttons are provided for all initiating and indicating circuits on the fire alarm control panel.
These buttons are located beside their respective indicating LEDs.
Pressing a circuit disconnect button disconnects that circuit from the system and turns on its trouble indicator. While
a circuit is disconnected, the panel will ignore all changes in the status (alarms and troubles) of that circuit. Circuit
disconnect buttons are toggle switches; therefore, pressing an activated button a second time will reconnect the
circuit.
Disconnecting an active latching initiating circuit such as alarms, water-flow alarm, sprinkler alarm, general alarm,
and latching supervisory does not affect its status until the panel is reset. Disconnecting active non-latching initiating
circuits including non-latching supervisory and trouble-only causes them to behave as if the alarm situation has
disappeared. Disconnecting an active indicating circuit immediately deactivates the circuit.
When an initiating circuit disconnect button is pressed a second time, the panel checks the state of the circuit. If the
circuit is active and will cause a false alarm, the Status LED flashes for ten seconds at the fast flash rate (red for
alarm or amber for supervisory) without processing the input. If the circuit is not re-disconnected by then, it will be
processed as a new input.
FA-300 LED Fire Alarm Panel User Guide
9
Glossary
Alarm
Condition
Occurs when devices such as detectors, pull stations, or sprinklers are activated.
In a single stage system, this condition will activate all signalling devices
throughout the building. In a two stage system, this condition will activate an alert
signal and the General Alarm timer.
Circuits
Refers to an actual electrical interface and can be classified as initiating
(detection), indicating (signal), or relay. The terms “circuit” and “zone” are often
used interchangeably in the fire alarm industry.
Fast Flash Rate
120 flashes per minute is the rate at which an LED will flash to indicate a
supervisory alarm.
General Alarm
Timer
In a two stage system, the general alarm timer begins timing when the panel is in
the alert stage. When the general alarm timer times out, the system will go into a
general alarm, where all signals in the building will sound.
Indicating
Circuit
A circuit in a fire alarm system that is connected to audible or visual signalling
devices.
Initiating
Circuit
A circuit in a fire alarm system that is connected to detectors, pull stations, or
sprinkler flow switches.
Latching Circuit A circuit that, when activated, will cause a condition on the panel that cannot be
cleared until the panel is reset.
LED
The light-emitting diodes (LEDs) of the FA-300 are coloured either amber, red, or
green. When lit, LEDs provide information regarding the status of the panel.
Monitor
Condition
Occurs when dampers open or close, when supply and return fans are running,
etc.
Non-latching
Circuit
A circuit that, when activated, will cause a condition on the panel that will be
cleared once the circuit is deactivated. This term is used to describe supervisory
and trouble circuits.
Non-
Silenceable
Circuit
A signal circuit that cannot be silenced by pressing the Signal Silence button.
Relay Circuit
A circuit in a fire alarm system that connects relay devices (e.g. fan damper relays,
etc.).
Remote
Annunciator
A device that visually indicates, either by LCD or LEDs, the floor or zone where the
alarm originated.
Single Stage
System
A type of fire alarm system that immediately sounds all the signals throughout the
building when an alarm is detected in any part of the system.
Silenceable
Circuit
A signal circuit that can be silenced by pressing the Signal Silence button.
Occurs when the sprinkler system is disconnected or turned off.
Trouble
Condition
Occurs when an abnormal condition such as a problem in the wiring, battery or
power circuits exists in the fire alarm system.
Trouble Flash
Rate
20 flashes per minute is the rate at which an LED will flash to indicate a trouble
condition.
Two Stage
System
A type of fire alarm system that causes an alert signal to sound when an alarm is
detected in any part of the system. An alert signal advises designated persons of a
fire emergency. If the alert signal is not acknowledged within five minutes of its
initiation, an alarm (evacuation) signal will automatically sound throughout the
building.
Walk Test
A test performed by a technician to ensure that each detection device is connected
to the panel and working properly.
Zones
A fire alarm protected area that consists of at least one circuit. The terms “circuit”
and “zone” are often used interchangeably in the fire alarm industry.
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: 905-660-4655 Fax: 905-660-4113
Mircom 2004
Printed in Canada
Subject to change without prior notice
www.mircom.com
Advanced Life Safety Solutions
U.S.A.
60 Industrial Parkway
Cheektowaga, NY 14227
Tel: 1-888-660-4655 Fax: 1-888-660-4113