FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

TECHNICAL GUIDE SPLIT-SYSTEM HEAT PUMPS 10 SEER – R-22 MODELS: E*RA036 THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) MODELS: 036-048 (3 PH) MODELS: 060, 090 (3 PH) Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.york.com Additional rating information can be found at www.ari.org/aridirectory. LISTED ISO 9001 Certified Quality Management System DESCRIPTION The 10 SEER Series heat pumps is the outdoor part of a ver- satile system of heat pumps. It is designed to be custom- matched with one of UPG’s complete line of evaporator sec- tions, with each serving a specific function. Matching Air Han- dlers are available for upflow, downflow, or horizontal applications to provide a complete system. Electric Heaters are available, if required. Add-On coils are available for use with upflow, downflow, or horizontal furnaces and air han- dlers. WARRANTY 1-year limited parts warranty. 5-year limited compressor warranty. FEATURES • QUALITY COILS - The coil is constructed of copper tube and aluminum fins. • COIL PROTECTION - Coils are protected from damage by a polymer mesh applied between the coil face, and a PVC coated steel coil guard. • PROTECTED COMPRESSOR - The compressor is inter- nally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating condi- tions occur. A liquid line filter-drier further protects the compressor. • DURABLE FINISH - Cabinet is made of pre-painted steel. The pre-treated flat galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted-textured finish insure less fading when exposed to sunlight. • LOWER INSTALLED COST - Installation time and costs are reduced by easy power and control wiring connections. Discharge line heat exchanger knockouts are provided, if required. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimen- sion means less space is required on the ground or roof. • TOP DISCHARGE - The warm air from the top mounted fan is blown up away from the structure and any landscap- ing. This allows compact location on multi-unit applica- tions. • LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and com- pressor operating sounds. • LOW MAINTENANCE - Long life permanently lubricated motor-bearings need no annual servicing. • EASY SERVICE ACCESS - Fully exposed refrigerant con- nections, a single panel covering the electrical controls, and the molex plug in the control box connecting the con- denser fan make for easy servicing of the unit. • SECURED SERVICE VALVES - Secured re-usable ser- vice valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging. • U.L. and C.U.L. listed - approved for outdoor application. Certified in accordance with the Unitary Small Equipment cer- tification program, which is based on ARI Standard 210/240.

Unitary Products Group

All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. Physical and Electrical Data MODEL E1RA036S25 E2RA048S25 E1RA060S25 E1RA036S46 E2RA048S46 E1RA060S46 Unit Supply Voltage 208/230-3-60 460 - 3 - 60 Normal Voltage Range 1 187 to 252 432 to 504 Minimum Circuit Ampacity 15.0 18.9 24.5 8.0 10.1 12.0 Max. Qvercurrent Device Amps 2 25 30 40 15 15 20 Compressor Type3 Inertia ScrollD ScrollC Inertia ScrollD ScrollC Compressor Amps Rated Load 10.9 14.1 18.6 5.8 7.0 9.0 Locked Rotor 78 125 128 40 55 63 Crankcase Heater Yes No No Yes No No Fan Motor Amps Rated Load 1.4 1.3 1.3 .8 .7 .8 Fan Diameter Inches 18 22 24 18 22 24 Fan Motor Rated HP 1/4 1/4 1/4 1/4 1/5 1/4 Nominal RPM 1,100 850 850 1,100 825 850 Nominal CFM 2,750 3,500 3,100 2,750 3,500 3,100 Coil Face Area Sq. Ft. 12.58 19.65 18.00 12.58 19.65 18.00 Rows Deep 1 1 2 1 1 2 Fin / Inches 14 13 14 14 13 14 Liquid Line Set OD (Field Installed) 3/8 3/8 3/8 3/8 3/8 3/8 Vapor Line Set OD (Field Installed) 3/4 7/8 7/8 3/4 7/8 7/8 Unit Charge (Lbs. - Oz.) 4 5 - 12 8 - 3 11 - 3 5 - 12 8 - 3 11 - 3 Charge Per Foot, Oz. .68 .70 .70 .68 .70 .70 Operating Weight Lbs. 178 232 243 178 232 243 1. Rated in accordance with ARI Standard 110, utilization range “A”. 2. Dual element fuses or HACR circuit breaker. 3. All scrolls listed with a superscript “D” are Danfoss scrolls. All scrolls listed with a superscript “C” are Copeland scrolls. 4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value. C A B DIMENSIONS Unit Model Dimensions (Inches) Refrigerant Connection Service Valve Size A1 1. Including fan guard. B C Liquid Vapor 036 25 35 23 3/8” 3/4” 048 33 37 27 7/8” 060 26 43 32 7/8”

Unitary Products Group

3 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of intercon- necting line tubing. 2. Verify the orifice size and additional charge required for specific evaportor coil in the system using the above table. 3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above. 4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaportor + adder for line set. 5. If the orifice in the evaportor was changed, verify the evaportor nameplate has been marked with the correct orifice size. Additional R-22 Charge / Orifice Size for Various Matched Systems Outdoor Unit E1RA036S(25,46) E1RA048S(25,46) E1RA060S(25,46) Unit Orifice (s) 1 71, 81 81, 84, 87 99 Factory R-22 Charge, lbs-oz 5 - 12 8 - 3 11 - 3 Indoor Coil System Orifice = Additional Charge, Oz FC/MC/PC35(B,C)3X 81 + 8 – – FC/MC/PC/UC36(A,B,C)3X 71 + 7 – – FC/MC/PC/UC42(B,C)3X 81 + 8 – – FC/MC/PC/UC48C3X – 87 + 6 – FC/MC/PC/UC48D3X – 87 + 6 – FC/MC/PC/UC60C3X – 84 + 4 99 + 0 FC/MC/PC/UC60D3X – 84 + 4 99 + 0 AHP36C3X 81 + 13 84 + 3 – AHP42C3X 81 + 13 84 + 3 – AHP/SHP48D3X – 84 + 4 99 + 0 AHP60D3X – 84 + 4 99 + 0 G1NA036S17L 71 + 7 – – G1NA048S21D 71 + 7 81 + 8 – G1NA048S24P – 81 + 8 – G1UA048S21/24 81 + 13 84 + 3 – G1UA060S24 – 84 + 4 99 + 0 G1FA048S21/24 81 + 13 84 + 3 – G1FA060S24 – 84 + 4 99 + 0 G2FD042S21 81 + 8 – – G2FD048S21/24 – 87 + 6 – G2FD060S24 – 84 + 4 99 + 0 FOOTNOTES: 1. These orifices are packed in the instruction/warranty packet of each outdoor unit.

Unitary Products Group

- = Not applicable COOLING CAPACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL1 MODEL COOLING MODEL ELECTRIC 2 HEAT KW W RATED CFM NET MBH SEER W/O TXV SEER WITH TXV3 EER TOTAL SENS. 3 PH 10 SEER HP WITH MA / MC / N-AH / G2FD E1RA036S(25,46) MA12BN2,4 10 17 FC/MC35B3X 1250 34.4 25.3 10 – 8.95 MA12BN2,4 10 17 FC/MC36B3X 1250 34.4 25.3 10 – 8.95 MA12BN2,4 10 17 FC/MC42B3X 1250 34.4 25.3 10 – 8.95 N1AHC1646 10, 15 21 G2FD042(S,H)21 1250 34.2 25.3 10 – 8.95 E2RA048S(25,46 MA16CN4 10, 15 21 FC/MC48C3X 1600 45.5 33.7 10 – 9.45 MA20DN2 10, 15, 25 24 FC/MC48D3X 1725 45.5 33.7 10 – 9.45 MA20DN4 10, 15, 29 24 FC/MC48D3X 1725 45.5 33.7 10 – 9.45 N1AHC1646 10, 15 21 G2FD048(S,H)21 1600 45.5 33.7 10 – 9.45 N1AHD2046 10, 15, 29 24 G2FD048(S,H)24 1600 45.5 33.7 10 – 9.45 E1RA060S(25,46) MA20DN4 10, 15, 29 24 FC/MC60D3X 2000 57.0 41.0 10 – 9.80 N1AHD2046 10, 15, 29 24 G2FD048(S,H)24 1700 57.0 41.0 10 – 9.80 3 PH 10 SEER HP WITH AHP / SHP / F2RP / RC / FP / FC4,5 E1RA036S25 F2RP/FP036 5, 8, 10, 15, 19 21 – 1250 34.0 24.9 10 – 9.00 F2RD/FP042 5, 8, 10, 15 21 – 1250 34.0 25.6 10 – 9.00 AHP36C3X 10, 15 21 – 1250 34.0 25.6 10 – 9.00 AHP42C3X 10, 15, 18 21 – 1250 34.0 25.6 10 – 9.00 E2RA048S25 F2FP048 5, 8, 10, 15, 20, 25 24 – 1600 45.0 33.5 10 – 9.40 F2FP060 5, 8, 10, 15, 20, 25 24 – 1600 46.5 34.4 10 – 9.60 AHP/SHP48D3X 10, 15, 18 24 – 1600 46.5 34.4 10 – 9.60 E1RA060S25 F2FP060 5, 8, 10, 15, 20, 25 24 – 1700 56.0 40.0 10 – 9.40 AHP/SHP60D3X 10, 15 24 – 1700 56.0 40.0 10 – 9.40 Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210/240. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow. KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor. EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period. 1. G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number. 2. Single phase units require single phase 2HK heaters. 3. TXV = Use 1TV700 Series Kit. 4. To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC. models. All ratings remain the same. 5. FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D. standard.

Unitary Products Group

5 * Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up. COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RATED CFM NET MBH SEER W/O TXV SEER + TXV1 + TDR* EER TOTAL SENS. E1RA036S(25,46 1100 1400 21,24 G1FA048S21 1250 34.4 24.7 10 – 9.05 17 G1NA036S17L 1250 35.0 26.2 10 – 9.00 21 G1NA048S21D 1250 35.0 26.2 10 – 8.95 21,24 G1UA048S21 1250 34.4 24.7 10 – 9.05 21 G2FD042S21 1250 34.2 25.3 10 – 8.95 17,21 FC/MC/PC35*3X 1250 34.4 24.7 10 – 9.5 14,17,21 FC/MC/PC/UC36*3X 1250 34.4 24.7 10 – 9.5 17,21 FC/MC/PC/UC42*3X 1250 34.4 24.7 10 – 9.5 E2RA048S(25,46 1400 1800 21,24 G1FA048S21 1600 45.5 32.7 10 – 9.30 21 G1NA048S21D 1600 45.0 31.2 10 – 9.50 21,24 G1UA048S21 1600 45.5 32.7 10 – 9.30 21,24 G2FD048(S,H)21,24 1600 45.5 33.7 10 – 9.40 21 FC/MC/PC/UC48C3X 1600 45.5 32.7 10 – 9.30 24 FC/MC/PC/UC48D3X 1600 45.5 32.7 10 – 9.30 E1RA060S(25,46) 1600 2100 21,24 G1FA060S21,24 1700 57.0 41.0 10 – 9.80 21,24 G1UA060S21,24 1700 57.0 41.0 10 – 9.80 24 G2FD060(S,H)24 1700 57.0 41.0 10 – 9.80 21 FC/MC/PC/UC60C3X 1725 57.0 41.0 10 – 9.80 24 FC/MC/PC/UC60D3X 2000 57.0 41.0 10 – 9.80 1. TXV = Use 1TV700 Series Kit.

Unitary Products Group

COP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. COP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. HEATING PERFORMANCE - With Air Handler UNIT MODEL* COIL1 MODEL ARI HEATING2 OUTDOOR TEMP3 47°F 17°F HSPF -3°F 7°F 17°F 27°F 37°F 47°F 57°F MBH COP MBH COP STD MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW E1RA036S(25,4 F2RP/F2FP036 34.0 3.00 20.4 2.16 7.2 15.5 2.40 15.6 2.54 20.4 2.80 24.9 3.03 29.9 3.20 34.0 3.32 38.5 3.50 AHP36,42 34.0 3.00 20.4 2.16 7.2 15.5 2.40 15.6 2.54 20.4 2.80 24.9 3.03 29.9 3.20 34.0 3.32 38.5 3.50 E2RA048S(25,46 F2FP048 37.0 3.08 31.4 2.32 7.5 20.8 3.64 26.1 3.80 31.4 3.97 36.7 4.13 40.1 4.27 47.0 4.47 54.6 4.71 AHP48,60 37.0 3.08 31.4 2.32 7.5 20.8 3.64 26.1 3.80 31.4 3.97 36.7 4.13 40.1 4.27 47.0 4.47 54.6 4.71 E1RA060S(25,46) F2FP060 58.5 3.12 39.0 2.34 7.6 26.0 4.48 32.5 4.68 39.0 4.88 42.1 4.98 45.1 5.07 58.5 5.49 65.0 5.70 AHP48,60 58.5 3.12 39.0 2.34 7.6 26.0 4.48 32.5 4.68 39.0 4.88 42.1 4.98 45.1 5.07 58.5 5.49 65.0 5.70 1. Rated CFM same as for cooling. 2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation. 3. Integrated heating capacities include the effect of defrost cycles in the temperature range where they occur. HEATING PERFORMANCE - With Furnace Coils UNIT MODEL* COIL1 MODEL ARI HEATING2 OUTDOOR TEMP3 47°F 17°F HSP F -3°F 7°F 17°F 27°F 37°F 47°F 57°F MBH COP MBH COP STD MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW E1RA036S25,46 G2FD042(S,H)21 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.94 29.5 3.15 34.0 3.32 40.5 3.50 G1NA036S17L 35.0 3.20 22.0 2.26 7.6 13.3 2.62 17.7 2.74 22.0 2.85 23.3 2.71 24.5 2.57 35.0 3.21 39.3 3.32 G1NA048S21D 35.0 3.20 22.0 2.26 7.6 13.3 2.62 17.7 2.74 22.0 2.85 23.3 2.71 24.5 2.57 35.0 3.21 39.3 3.32 G1UA048S21 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.95 29.5 3.15 34.0 3.32 40.5 3.50 G1FA048S21 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.95 29.5 3.15 34.0 3.32 40.5 3.50 FC/MC/PC35*3X 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.95 29.5 3.15 34.0 3.32 40.5 3.50 FC/MC/PC/UC36*3X 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.95 29.5 3.15 34.0 3.32 40.5 3.50 FC/MC/PC/UC42*3X 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.95 29.5 3.15 34.0 3.32 40.5 3.50 E2RA048S25,46 G2FD048(S,H)21,24 47.0 3.02 31.2 2.32 7.5 21.0 3.56 26.1 3.75 31.2 3.94 36.3 4.13 40.1 4.32 47.0 4.56 54.1 4.59 G1NA048S21D 47.0 2.96 31.2 2.30 7.5 20.7 3.52 25.9 3.75 31.2 3.98 35.2 4.13 39.2 4.29 47.0 4.65 52.3 4.88 G1UA048S21 47.0 3.00 31.2 2.30 7.50 20.9 3.60 26.1 3.79 31.2 3.98 36.3 4.16 42.0 4.39 47.0 4.56 54.0 4.61 G1FA048S21 47.0 3.00 31.2 2.30 7.5 20.9 3.60 26.1 3.79 31.2 3.98 36.3 4.16 42.0 4.39 47.0 4.59 54.0 4.61 FC/MC/PC/UC48C3X 47.0 3.02 31.2 2.32 7.5 21.0 3.56 26.1 3.75 31.2 3.94 36.3 4.13 40.1 4.32 47.0 4.56 54.1 4.59 FC/MC/PC/UC48D3X 47.0 3.02 31.2 2.32 7.5 21.0 3.56 26.1 3.75 31.2 3.94 36.3 4.13 40.1 4.32 47.0 4.56 54.1 4.59 E1RA060S25,46 G2FD060(S,H)24 58.0 3.20 38.5 2.40 7.7 25.5 4.29 32.0 4.50 3.9 4.70 42.1 4.91 45.7 5.11 58.0 5.31 64.5 5.51 G1UA060S24 58.0 3.20 38.5 2.40 7.7 25.5 4.29 32.0 4.50 3.9 4.70 42.1 4.91 45.7 5.11 58.0 5.31 64.5 5.51 G1FA060S24 58.0 3.20 38.5 2.40 7.7 25.5 4.29 32.0 4.50 3.9 4.70 42.1 4.91 45.7 5.11 58.0 5.31 64.5 5.51 FC/MC/PC/UC60C3X 58.0 3.20 38.5 2.40 7.7 25.5 4.29 32.0 4.50 3.9 4.70 42.1 4.91 45.7 5.11 58.0 5.31 64.5 5.51 FC/MC/PC/UC60D3X 58.0 3.20 38.5 2.40 7.7 25.5 4.29 32.0 4.50 3.9 4.70 42.1 4.91 45.7 5.11 58.0 5.31 64.5 5.51 1. Rated CFM same as for cooling. 2. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no supplemental elec- tric heat operation. 3. Integrated heating capacities include the effect of defrost cycles in the temperature range where they occur.

Unitary Products Group

7 ACCESSORIES Refer to Price Manual for specific model numbers. Start Assist Kit (2SA067*) Blower Time Delay - Available to increase efficiency when installed. Installs on indoor section and maintains blower for approximately one minute after cooling thermostat has been satisfied. Hard Start Kits - Provides required starting torque for use with Thermal Expansion Valve Kit. Low Temperature Cutout (2LT06700224) - Prevents heat pump operation below -10°F ambient temperature. Compressor Blanket - Designed to further reduce the nor- mal operating sound. Add-on Fossil Fuel Control - Interface controls for use with gas, oil furnaces and the heat pump system are available. Thermal Expansion Valve Kit - 1TVM700 Series TXV kit used to improve system performance. Outdoor Thermostat (2TD06700124) - Provides additional staging of supplemental electric heat. Room Thermostats - A wide selection of matching thermo- stats is available to provide features required for any installa- tion. 2H/1C, manual changeover electronic non-programmable thermostat. 3H/2C, non-programmable digital thermostat. 3H/2C, auto/manual changeover, electronic programmable, 7-day, thermostat. * For the most current accessory information, refer to the price book or consult factroy. SOUND POWER RATINGS* * Rated in accordance with ARI 270-95 Standards. TYPICAL INSTALLATION UNIT MODEL (dBA) 018 80 024 80 030 80 036 82 042 82 048 77 060 82 MINIMUM 24” SERVICE ACCESS CLEARANCE ON ONE SIDE 60” OVERHEAD CLEARANCE 10” CLEARANCE COIL AREA WEATHERPROOF DISCONNECT SWITCH THERMOSTAT TO FURNACE OR AIR HANDLER TERMINAL BLOCK NEC CLASS 1 WIRING NEC CLASS 2 WIRING TO INDOOR COIL SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT CONTROL ACCESS PANEL NOTE: ALL OUTDOOR WIRING MUST BE WEATHERPROOF.

Unitary Products Group

TYPICAL FIELD WIRING - 3 PH (036 - 060) TYPICAL FIELD WIRING - 3 PH (090) THERMOSTAT INDOOR UNIT OUTDOOR UNIT LOW VOLTAGE TERMINAL BLOCK IN AIR HANDLER WITH ELECTRIC HEAT 3,4 DEFROST CONTROL 1 FIELD INSTALLED JUMPER GND. SCREW CONTACTOR T2 T1 L2 L1 M R L or X Y O W G T 2 E 2 R R Y Y O O W2 W W1 C X G W1 GND. LUG POWER WIRING 24V CONTROL WIRING (NEC CLASS 2) JUMPER TERMINALS E AND W TOHEAT ON FIRST STAGE DURING EMERGENCY HEAT. 1 2 TERMINAL NOT USED ON ALL THERMOSTATS. POWER WIRING 208/230-3-60 460-3-50 3CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS. 4 CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER. B or C ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES RED BLK YEL ORG BRN PUR WHT /66 5 GRAY FOR USE WITH OPTIONAL OUTDOOR THERMOSTAT KITS. B or C POWER SUPPLY 208/230-3-60 460-3-50 T3 L3 CC GRY 5 THERMOSTAT INDOOR UNIT OUTDOOR UNIT LOW VOLTAGE TERMINAL BLOCK IN AIR HANDLER WITH ELECTRIC HEAT 3,4 DEFROST CONTROL 1 FIELD INSTALLED JUMPER GND. SCREW CONTACTOR T2 T1 L2 L1 M R X Y O W G T 2 E 2 R R Y Y O O W W W1 C X 53 G GND. LUG POWER WIRING 24V CONTROL WIRING (NEC CLASS 2) JUMPER TERMINALS E AND W TOHEAT ON FIRST STAGE DURING EMERGENCY HEAT. 1 2 TERMINAL NOT USED ON ALL THERMOSTATS. POWER WIRING 208/230-3-60 460-3-50 3 CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS. 4 CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER. B or C ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES RED BLK YEL ORG BRN PUR WHT /66 C POWER SUPPLY 208/230-3-60 460-3-50 T3 L3 X 60 60 5 FIELD INSTALLED JUMPER 3TERMINAL NOT USED ON ALL THERMOSTATS. 5 REQUIRED ON ALL ELECTRIC HEAT

Unitary Products Group

9 Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature. COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. E1RA036S(25,46) INDOOR COIL MODEL NO. F2RP/F2FP036 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1000 1250 1400 ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70 ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57 75 T.C. 38.1 35.0 32.5 29.4 38.6 35.5 32.9 29.9 38.8 35.7 33.2 30.2 S.C. 22.9 22.9 22.1 23.6 24.1 24.2 23.4 24.8 24.9 24.9 24.1 25.5 KW 3.15 3.08 3.02 2.94 3.16 3.10 3.03 2.96 3.17 3.10 3.04 2.97 85 T.C. 37.6 34.6 32.0 28.9 38.1 35.1 32.7 29.4 38.3 35.3 33.0 29.7 S.C. 23.3 23.4 22.6 23.9 24.8 24.9 24.1 25.3 25.7 25.7 25.0 26.1 KW 3.39 3.30 3.22 3.12 3.40 3.32 3.24 3.14 3.41 3.33 3.25 3.15 95 T.C. 36.2 33.3 30.9 27.7 36.7 33.7 31.4 28.3 36.8 34.0 31.6 28.6 S.C. 23.3 23.3 22.6 23.7 24.9 24.9 24.0 25.4 25.8 25.9 24.9 26.2 KW 3.71 3.60 3.51 3.38 3.72 3.62 3.53 3.40 3.74 3.64 3.55 3.42 105 T.C. 34.4 31.5 29.2 26.3 34.7 32.0 29.6 26.8 35.0 32.2 29.9 27.3 S.C. 22.9 22.9 22.1 23.3 24.5 24.5 23.5 24.7 25.6 25.5 24.6 25.5 KW 4.03 3.90 3.79 3.63 4.06 3.93 3.82 3.67 4.06 3.94 3.82 3.71 115 T.C. 32.2 29.6 27.4 24.7 32.6 30.0 27.8 25.5 32.8 30.2 28.1 25.8 S.C. 22.2 22.2 21.4 22.4 23.9 23.8 22.9 23.8 24.8 24.8 23.8 24.1 KW 4.34 4.19 4.05 3.88 4.37 4.22 4.09 3.93 4.38 4.24 4.10 3.96 125 T.C. 30.0 27.7 25.6 23.1 30.5 28.0 26.0 24.2 30.6 28.2 26.3 24.3 S.C. 21.5 21.5 20.6 21.5 23.3 23.1 22.2 22.9 24.0 24.1 23.1 22.7 KW 4.65 4.48 4.31 4.13 4.68 4.51 4.36 4.19 4.70 4.54 4.38 4.21 NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM. Air Handler Coil T.C. S.C. KW MA12BN2,4 FC/MC35B3X 1.01 1.02 1.01 MA12BN2,4 FC/MC36B3X 1.01 1.02 1.01 MA12BN2,4 FC/MC42B3X 1.01 1.02 1.01 MA12BN2,4 G2FD042(S,H)21 1.01 1.02 1.01 AHP42C3X – 1.00 1.00 1.00 F2RP/F2FP042 – 1.00 1.00 1.00 – G1FA048S21 1.01 0.99 1.01 – G1NA036S17L 1.03 1.05 1.03 – G1NA048S21D 1.03 1.05 1.04 – FC/MC/PC35*3X 1.01 0.99 1.01 – FC/MC/PC/UC36*3X 1.01 0.99 1.01 – FC/MC/PC-UC42*3X 1.01 0.99 1.01 – G1UA048S21 1.01 0.99 1.01 – G2FD042(S,H)21 1.01 1.02 1.01

Unitary Products Group

Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature. COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. E2RA048S(25,46) INDOOR COIL MODEL NO. F2FP048 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1300 1450 1550 ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70 ID WB (°F) 72 67 62 57 72 67 62 57 72 67 62 57 75 T.C. 52.3 48.3 45.0 40.6 53.0 49.0 45.7 41.3 53.4 49.4 46.1 41.9 S.C. 32.5 32.8 31.7 33.5 34.0 34.3 33.2 35.1 35.0 35.2 34.1 36.3 KW 4.14 4.07 4.02 3.95 4.16 4.08 4.04 3.97 4.17 4.09 4.05 3.97 85 T.C. 50.9 47.0 43.7 39.4 51.5 47.6 44.4 40.3 51.9 48.0 44.7 40.6 S.C. 32.4 32.6 31.6 33.3 34.0 34.2 33.2 35.1 35.2 35.4 34.2 36.2 KW 4.44 4.36 4.30 4.22 4.46 4.38 4.32 4.24 4.47 4.38 4.33 4.25 95 T.C. 48.8 45.0 41.8 37.9 49.2 45.5 42.4 38.4 49.6 45.8 42.7 38.7 S.C. 32.0 32.2 31.2 32.9 33.6 33.8 32.9 34.5 34.9 35.1 33.8 35.6 KW 4.87 4.79 4.73 4.64 4.90 4.81 4.74 4.66 4.91 4.81 4.76 4.67 105 T.C. 46.1 42.5 39.5 35.8 46.6 43.0 40.1 36.3 46.4 43.3 40.4 36.7 S.C. 31.0 31.1 30.1 32.0 32.9 32.9 31.9 33.7 33.8 34.3 32.9 35.1 KW 5.37 5.28 5.22 5.12 5.38 5.30 5.22 5.14 5.34 5.30 5.24 5.14 115 T.C. 43.2 39.9 37.0 33.5 43.6 40.3 37.6 34.2 43.8 40.6 37.9 35.0 S.C. 29.9 30.2 29.2 30.7 31.8 32.1 30.8 32.8 32.9 33.1 31.8 34.5 KW 5.90 5.80 5.74 5.66 5.90 5.80 5.76 5.66 5.92 5.83 5.78 5.68 125 T.C. 40.3 37.3 34.6 31.2 40.6 37.6 35.0 32.1 41.2 37.9 35.3 33.3 S.C. 28.8 29.3 28.2 29.4 30.7 31.3 29.7 31.9 32.0 31.9 30.8 33.9 KW 6.43 6.32 6.27 6.20 6.42 6.30 6.31 6.18 6.50 6.36 6.31 6.22 NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM. Air Handler Coil T.C. S.C. KW MA16CN2,4 FC/MC48C3X 1.00 1.00 0.97 N1AHC1646 G2FD048(S,H)21 1.00 1.00 0.97 MA20DN2,4 FC/MC48D3X 1.00 1.00 0.97 N1AHD2046 G2FD048(S,H)24 1.00 1.00 0.97 AHP/SHP48D3X – 1.02 1.01 1.02 F2FP060 – 1.02 1.01 1.02 – G1FA048S21 1.00 0.97 0.98 – G1NA048S21D 0.99 0.93 0.95 – G1UA048S21 1.00 0.97 0.98 – FC/MC/PC/UC48C,D3X 1.00 1.00 0.97 – G2FD048(S,H)21,24 1.00 1.00 0.97

Unitary Products Group

11 Multipliers for determining the performance with other indoor sections. NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature. COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. E1RA060S(25,46 INDOOR COIL MODEL NO. G2FD060(S,H)24 CONDENSER ENTERING AIR TEMPERATURE ID CFM 1600 1800 2000 ID DB (°F) 85 80 75 85 80 75 85 80 75 ID WB (°F) 71 67 63 71 67 63 71 67 63 65 T.C. 63.0 61.1 60.7 62.9 60.9 61.1 62.9 60.6 61.4 S.C. 39.6 39.7 40.3 41.6 41.5 42.2 43.7 43.3 44.1 KW 3.71 3.66 3.68 3.71 3.66 3.67 3.71 3.67 3.67 75 T.C. 62.3 59.8 57.9 62.5 60.0 58.5 62.6 60.1 59.0 S.C. 39.6 39.3 39.1 41.8 41.3 41.1 43.9 43.3 43.1 KW 4.20 4.14 4.12 4.21 4.15 4.13 4.21 4.16 4.13 85 T.C. 61.7 58.5 55.1 62.0 59.1 55.9 62.3 59.6 56.6 S.C. 39.6 38.9 38.0 41.9 41.1 40.1 44.2 43.3 42.2 KW 4.70 4.63 4.57 4.71 4.64 4.58 4.72 4.65 4.60 95 T.C. 61.0 57.2 52.3 61.5 58.2 53.3 62.0 59.1 54.2 S.C. 39.6 38.5 36.8 42.0 40.9 39.0 44.4 43.3 41.2 KW 5.19 5.11 5.01 5.21 5.13 5.04 5.22 5.14 5.06 105 T.C. 58.3 53.9 49.1 59.1 54.7 49.9 60.0 55.6 50.7 S.C. 38.5 37.2 35.4 41.0 39.6 37.6 43.6 41.9 39.8 KW 5.78 5.67 5.55 5.80 5.69 5.57 5.82 5.71 5.60 115 T.C. 55.5 50.5 45.9 56.8 51.3 46.5 58.0 52.1 47.1 S.C. 37.4 35.9 34.0 40.1 38.2 36.2 42.7 40.5 38.3 KW 6.36 6.22 6.08 6.39 6.25 6.11 6.41 6.27 6.13 NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM. Air Handler Coil T.C. S.C. KW MA20DN2,4 FC/MC60D3X 1.00 1.00 1.00 N1AHD2046 G2FD060(S,H)24 1.00 1.00 1.00 AHP/SHP60D3X – 0.98 0.98 1.02 F2FP060 – 0.98 0.98 1.02 – G1FA060S21,24 1.00 1.00 1.00 – G1UA060S21,24 1.00 1.00 1.00 – FC/MC/PC/UC60*3X 1.00 1.00 1.00

Unitary Products Group

Multipliers for determining the performance with other indoor sections. HEATING PERFORMANCE DATA CONDENSING UNIT MODEL NO E1RA036S(25,46) EVAPORATOR COIL MODEL NO F2RP/F2FP036 AIR TEMP. ENTERING OUTDOOR UNIT AIR TEMP. ENTERING INDOOR COIL ID CFM 1000 1250 1400 MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P. 60 60 41.6 3.37 3.62 42.0 3.30 3.73 41.3 3.27 3.70 70 39.1 3.54 3.24 40.2 3.49 3.37 40.2 3.49 3.38 80 37.4 3.70 2.97 39.1 3.67 3.12 39.7 3.69 3.16 47 60 35.3 3.17 3.26 35.7 3.15 3.32 34.8 3.15 3.24 70 33.1 3.32 2.93 34.0 3.32 3.00 33.8 3.33 2.98 80 31.5 3.46 2.67 32.7 3.48 2.76 33.3 3.49 2.80 40 60 30.2 3.02 2.94 31.2 3.03 3.02 31.9 3.05 3.08 70 28.7 3.14 2.68 29.5 3.16 2.74 30.4 3.18 2.81 80 27.1 3.28 2.43 27.9 3.30 2.48 28.9 3.32 2.55 30 60 26.1 2.89 2.65 27.4 2.93 2.74 27.5 2.96 2.73 70 24.4 2.96 2.42 25.8 3.01 2.51 26.1 3.04 2.51 80 22.4 3.07 2.14 23.8 3.13 2.23 24.3 3.16 2.25 17 60 21.4 2.66 2.36 21.9 2.71 2.37 22.0 2.74 2.36 70 19.7 2.73 2.12 20.4 2.79 2.15 20.7 2.82 2.15 80 18.0 2.79 1.89 18.9 2.86 1.94 19.3 2.89 1.96 10 60 18.1 2.50 2.12 18.8 2.56 2.16 19.1 2.60 2.16 70 16.5 2.55 1.90 17.4 2.62 1.95 17.7 2.66 1.96 80 14.8 2.58 1.68 15.8 2.65 1.75 16.2 2.69 1.77 NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM. Air Handler Coil MBH KW COP MA12BN2,4 FC/MC35B3X 1.01 1.02 1.01 MA12BN2,4 FC/MC36B3X 1.01 1.02 1.01 MA12BN2,4 FC/MC42B3X 1.01 1.02 1.01 MA12BN2,4 G2FD042(S,H)21 1.00 1.00 1.00 AHP42C3X – 1.00 1.00 1.00 F2RP/F2FP042 – 1.00 1.00 1.00 – G1FA048S21 1.00 1.00 1.00 – G1NA036S17L 1.03 0.97 1.07 – G1NA048S21D 1.03 0.97 1.07 – FC/MC/PC35*3X 1.01 0.99 1.01 – FC/MC/PC/UC36*3X 1.01 0.99 1.01 – FC/MC/PC-UC42*3X 1.01 0.99 1.01 – G1UA048S21 1.00 1.00 1.00 – G2FD042(S,H)21 1.00 1.00 1.00

Unitary Products Group

13 Multipliers for determining the performance with other indoor sections. HEATING PERFORMANCE DATA CONDENSING UNIT MODEL NO E2RA048S(25,46) EVAPORATOR COIL MODEL NO F2RP/F2FP048 AIR TEMP. ENTERING OUTDOOR UNIT AIR TEMP. ENTERING INDOOR COIL ID CFM 1250 1400 1550 MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P. 60 60 53.4 4.86 3.23 52.9 4.72 3.28 52.2 4.25 3.61 70 54.2 4.76 3.34 54.1 4.61 3.44 53.7 4.14 3.80 80 54.1 5.57 2.85 54.4 5.39 2.96 54.4 4.83 3.30 47 60 47.0 4.54 3.03 46.6 4.45 3.07 46.5 4.05 3.36 70 46.9 4.56 3.02 47.0 4.47 3.08 47.2 4.06 3.41 80 46.3 5.24 2.59 46.9 5.13 2.68 47.3 4.65 2.98 40 60 37.7 3.54 3.12 42.9 4.31 2.92 43.4 3.93 3.24 70 37.3 3.98 2.75 42.9 4.40 2.86 42.6 4.13 3.02 80 36.6 5.79 1.85 42.5 5.00 2.50 40.0 5.47 2.14 30 60 37.7 4.01 2.76 38.7 4.03 2.82 37.9 3.70 3.00 70 36.7 4.16 2.58 38.2 4.22 2.65 38.4 3.93 2.86 80 35.3 4.60 2.25 37.3 4.70 2.33 38.7 4.44 2.55 17 60 32.2 3.67 2.57 32.7 3.68 2.61 33.0 3.40 2.85 70 30.8 3.98 2.27 31.4 3.97 2.32 31.8 3.66 2.55 80 29.4 4.30 2.00 30.1 4.29 2.06 30.6 3.94 2.28 10 60 29.2 3.46 2.48 29.6 3.46 2.51 30.1 3.19 2.77 70 27.5 3.81 2.12 27.9 3.80 2.15 28.4 3.51 2.37 80 25.8 4.02 1.88 26.3 4.02 1.92 26.7 3.71 2.12 NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM. Air Handler Coil MBH KW COP MA16CN2,4 FC/MC48C3X 1.00 1.00 0.97 N1AHC1646 G2FD048(S,H)21 1.00 1.02 0.98 MA20DN2,4 MC48D3X 1.00 1.02 0.98 N1AHD2046 G2FD048(S,H)24 1.00 1.02 0.98 AHP/SHP48D3X – 1.01 1.02 0.99 F2FP060 – 1.01 1.02 0.99 – G1FA048S21 1.00 1.02 0.98 – G1NA048S21D 1.00 1.04 0.96 – G1UA048S21 1.00 1.03 0.97 – FC/MC/PC/UC48C,D3X 1.00 1.03 0.97 – G2FD048(S,H)21,24 1.00 1.03 0.97

Unitary Products Group

Multipliers for determining the performance with other indoor sections. HEATING PERFORMANCE DATA CONDENSING UNIT MODEL NO E1RA060S(25,46) EVAPORATOR COIL MODEL NO G2FD060(S,H)24 AIR TEMP. ENTERING OUTDOOR UNIT AIR TEMP. ENTERING INDOOR COIL ID CFM 1600 1800 2000 MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P. 60 60 63.6 5.09 3.67 61.9 4.98 3.64 60.1 4.87 3.62 70 64.8 5.33 3.56 63.5 5.18 3.59 62.2 5.04 3.62 80 65.9 5.60 3.45 65.1 5.39 3.54 64.2 5.20 3.62 47 60 56.9 4.15 4.03 55.7 4.02 4.06 54.4 3.90 4.10 70 58.3 4.62 3.70 58.0 4.54 3.75 56.3 4.35 3.80 80 59.7 5.19 3.38 59.0 5.03 3.44 58.2 4.88 3.50 40 60 54.5 4.05 3.95 53.3 3.93 3.97 52.0 3.81 4.00 70 53.7 4.41 3.57 53.4 4.32 3.63 53.2 4.22 3.69 80 52.9 4.87 3.19 53.6 4.78 3.29 54.3 4.71 3.38 30 60 49.6 3.89 3.74 49.8 3.80 3.84 49.9 3.72 3.93 70 47.7 4.18 3.34 48.0 4.10 3.44 48.4 4.02 3.53 80 45.8 4.57 2.94 46.3 4.47 3.04 46.8 4.39 3.13 17 60 40.6 3.56 3.34 41.0 3.51 3.42 41.3 3.46 3.50 70 38.8 3.86 2.94 39.2 3.80 3.02 39.7 3.74 3.11 80 36.9 4.26 2.54 37.5 4.18 2.63 38.0 4.10 2.71 10 60 36.3 3.53 3.01 36.7 3.46 3.11 37.1 3.38 3.21 70 34.3 3.82 2.63 34.7 3.74 2.72 35.2 3.67 2.81 80 32.2 4.19 2.25 32.7 4.12 2.33 33.2 4.05 2.40 NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM. Air Handler Coil MBH KW COP MA20DN2,4 FC/MC60D3X 1.00 1.00 1.00 N1AHD2046 G2FD060(S,H)24 1.00 1.00 1.00 AHP/SHP60D3X – 1.01 1.03 0.98 F2FP060 – 1.01 1.03 0.98 – G1FA060S21,24 1.00 1.00 1.00 – G1UA060S21,24 1.00 1.00 1.00 – FC/MC/PC/UC60*3X 1.00 1.00 1.00

Subject to change without notice. Printed in U.S.A.

279104-YTG-B-0307 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 279104-YTG-A-1106 Unitary 5005 Norman Product York OK Group Drive 73069 NOTES