09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85
Adapt Siemens (AS) Control
Supply & Extract Ventilation with Heat Recovery
Installation Manual
1.0 SAFETY INFORMATION
• The provision of the electrical supply and the connection of the unit to the electrical supply must
be carried out by a qualified electrician.
• Isolate from power supply before removing any covers. During installation / maintenance ensure
all covers are fitted before switching on the mains supply.
• All-pole disconnection from the mains as shown in the wiring diagram must be incorporated
within the fixed wiring and shall have a minimum contact separation of 3mm in accordance with
latest edition of the wiring regulations.
• This unit must be earthed.
• Ducting must be securely fixed with screws to the spigot to prevent access to live parts. Duct
runs terminating close to the fan must be adequately protected by suitable guards.
• This appliance should not be used by children or persons with reduced physical, sensory or
mental capabilities or lack of experience and knowledge, unless they have been given supervision
or instruction concerning the safe use of the appliance by a person responsible for their safety.
Children shall not play with the appliance. Cleaning and user maintenance shall not be carried
out by children.
1.1 Symbols
GENERAL WARNING
Signifies a general warning regarding hazard specified by supplementary information.
ELECTRIC SHOCK
This unit must be completely electrically isolated before any panels are removed. Check
mains supply and control connections.
ROTATING PARTS
This unit contains fast moving rotational parts which may start automatically. It is the
sole responsibility of the installer to adequately guard these components.
REFER TO INSTRUCTION MANUAL
Read and understand the installation and maintenance manual before installing,
operating or maintaining this product.
1.2 Important Information
This manual contains important information on the safe and
appropriate assembly, transport, commissioning, operation,
maintenance, disassembly and simple troubleshooting of the product.
While the product has been manufactured according to the accepted
rules of current technology, there is still a danger of personal injury or
damage to equipment if the following general safety instructions and
the warnings contained in these instructions are not complied with.
•Read these instructions completely and thoroughly before
working with the product.
•Keep these instructions in a location where they are accessible
to all users at all times.
•Always include the operating instructions when you pass the
product on to third parties.
1.3 Personal Protective Equipment
The following minimum Personal Protective Equipment (PPE) is
recommended when interacting with Nuaire product:
•Protective Steel Toed Shoes - when handling heavy objects.
•Full Finger Gloves (Marigold PU800 or equivalent) - when
handling sheet metal components.
•Semi Fingerless Gloves (Marigold PU3000 3DO or equivalent)
- when conducting light work on the unit requiring tactile
dexterity.
•Safety Glasses - when conducting any cleaning/cutting operation
or exchanging filters.
•Reusable Half Mask Respirators - when replacing filters which
have been in contact with normal room or environmental air.
Nuaire would always recommend a site specific risk assessment by a
competent person to determine if any additional PPE is required.
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
2.0 INTRODUCTION
The information contained in this document provides details of
installation, operation and maintenance for installers and users of
the XBOXER XBC75 & 85 Supply and Extract Ventilation Units with
Heat Recovery.
This supply and extract air handling unit range comprises an
combination of high efficiency centrifugal fans with EC motors, a
counterflow design plate heat exchanger, filters, optional heaters
(LPHW and Electric) and a casing with high mass acoustic treatment.
The one-piece ventilation unit shall be constructed with double
skinned Aluzinc panels on an aluminium Pentapost frame with integral
acoustic mineral fibre ensuring low breakout noise levels. The unit
shall incorporate a high efficiency aluminium counterflow plate heat
exchanger matrix with a thermal efficiency of up to 92%, fitted with
a segmented 100% bypass facility and actuator (patent app. for)
operating under automatic control.
A range of matched, side by side internal and external attenuators
(horizontal units) and double deck internal and external attenuators
(vertical units) with a similar construction method to that of the unit is
available.
General information regarding performance and specifications for the
equipment may be obtained from our Technical Literature, and / or
project specific documentation.
2.1 XBC Unit Code Description
1
2
-
3
-
4
5
-
7
-
8
XBC
75
-
H
-
L
AS
-
R
-
WP
1. Range:
XBOXER
2. Unit Size:
75, 85
3. Unit Layout:
H = Horizontal
V = Vertical
4. Heating Type:
E = Electric
L = LPHW
N = No Heating
5. Control Type:
AS = Adapt Siemens
6. Unit Handing:
No Affix = Left Hand Arrangement
R = Right Hand Arrangement
7. Unit Roof:
No Suffix = Standard Unit (No Roof)
WP = Twin Pitched Roof (Factory Fitted)
2.2 Matched Attenuator Code Description
1
2
-
3
-
4
5
-
6
XBC
75
-
H
-
SIL
900
-
WP
1. Range:
XBOXER
2. Unit Size:
75, 85
3. Unit Layout:
H = Horizontal
V = Vertical
4. Ancillary Type:
SIL = Attenuator
5. Attenuator Length:
900 = 900mm
6. Unit Roof:
No Suffix = Standard Unit (No Roof)
WP = Twin Pitched Roof (Factory Fitted)
3.0 DELIVERY
3.1 Receiving Equipment
All equipment is inspected prior to despatch and leaves the factory in
good condition. Upon receipt of the equipment an inspection should be
made and any damage indicated on the delivery note.
Particulars of damage and/or incomplete delivery should be endorsed
by the driver delivering the goods before offloading by the purchaser.
No responsibility will be accepted for damage sustained during the
offloading from the vehicle or on the site thereafter. All claims for
damage and/or incomplete delivery must be reported to Nuaire within
two days of receipt of the equipment.
3.2 Vehicle Offloading / Equipment Handling
XBC unit sections will be delivered to site in one section. The weight
of the unit modules and palletised items is displayed on the unit rating
plate or on the packaging. Some of the modules have an ‘uneven’
weight distribution, and this will be indicated by labelling where
appropriate. Ensure that lifting and handling equipment is adequately
rated. Offloading and positioning of the equipment is the responsibility
of the purchaser.
Spreaders should be used when lifting with slings to avoid damage
to the casings. Care must be taken to ensure that slings are correctly
positioned to avoid crushing and twisting of the unit castings. Where
channels and/or support frames are bolted to the underside of the unit
casing, slings or fork-lift arms should be positioned to locate in the
apertures in the channels. If Lifting Eyes have been supplied / fitted it is
recommended that they are used.
CAUTION: The XBC75 & 85 fan units have an uneven weight
distribution, please refer to the unit labelling before lifting /
offloading the unit.
Palletised.
Slings via spreaders fitted to unit with base frame.
1 Lifting Examples
3.3 Storage
The equipment must be stored in a dry, internal location. Ductwork
connection apertures shall be sealed against the ingress of dust, water
and vermin. If the storage period is to exceed two months, contact
Nuaire for guidance on the appropriate “mothballing” procedures. Do
not stack units, modules or components.
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
This will provide access to filters, coil, fan, heat exchanger,
condensate tray and pump. All models: The weather roof is part of
the unit code and is factory fitted only. Example: XBC85-V-LESWP.
Note: Codes with ‘R’ i.e. (XBC75-G4B-HR) refer to right hand unit
versions.
4.0 DIMENSIONS & WEIGHTS
4.1 Horizontal Units (XBC75-H, XBC85-H)
The unit is designed for side access as standard and must be
installed with a minimum of clearance of 650mm from a wall or
barrier.
C
K
B
M
J
E
F
G
A
2 Horizontal Unit Dimensions (mm) and Weights (kg)
*Includes unit and 76mm high base frame.
Unit Code
Unit Dimensions (mm)
Control Dimensions (mm)
Unit Weight
(kg)
Packed
Weight
(kg)
A
B
C
J
K
M
E
F
G
XBC75-H-***
2800
2126
876*
940
740
940
250
730
800
720
902
XBC85-H-***
2800
2126
876*
940
740
940
250
730
800
835
942
4.2 Horizontal Unit (XBC75-H, XBC85-H) Ancillaries
4.3
1
5
2
4
3
5
3
6
3 Horizontal Unit Ancillary References
4.3.1 Units With Weather Kits
Ref.
No.
XBC Unit Code
Description
Dimensions (mm)
Weight
(kg)
Width
Height
Length
1
XBC75-H-***WP
Horizontal XBC75 Unit With Twin Pitched Roof
2000
1001
2800
720
1
XBC75-H-***-R-WP
Right Handed Horizontal XBC75 Unit With Twin Pitched Roof
2000
1001
2800
720
1
XBC85-H-***WP
Horizontal XBC85 Unit With Twin Pitched Roof
2000
1001
2800
835
1
XBC85-H-***-R-WP
Right Handed Horizontal XBC85 Unit With Twin Pitched Roof
2000
1001
2800
835
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
4.3.2 Weather Terminals
Ref.
No.
XBC Ancillary Code
Description
Dimensions (mm)
Weight
(kg)
Width
Height
Length
2
XBC75-H-RT
Weather Terminal For Horizontal XBC75 Units
940
740
700
8
2
XBC85-H-RT
Weather Terminal For Horizontal XBC85 Units
940
740
700
8
4.3.3 Filter Module Options
Ref.
No.
XBC Ancillary Code
Description
Dimensions (mm)
Weight
(kg)
Width
Height
Length
3
XBC75-F7B/G4P-H
F7 Bag / G4 Panel For Horizontal XBC75 Units
2000
876
600
115
3
XBC85-F7B/G4P-H
F7 Bag / G4 Panel For Horizontal XBC85 Units
2000
876
600
115
3
XBC75-F7B/G4P-HR
F7 Bag / G4 Panel For Right Handed Horizontal XBC75 Units
2000
876
600
115
3
XBC85-F7B/G4P-HR
F7 Bag / G4 Panel For Right Handed Horizontal XBC85 Units
2000
876
600
115
3
XBC75-G4B-H
G4 Bag For Horizontal XBC75 Units
2000
1001
600
115
3
XBC85-G4B-H
G4 Bag For Horizontal XBC95 Units
2000
1001
600
115
3
XBC75-G4B-HR
G4 Bag For Right Handed Horizontal XBC75 Units
2000
1001
600
115
3
XBC85-G4B-HR
G4 Bag For Right Handed Horizontal XBC85 Units
2000
1001
600
115
3
XBC75-F7B/G4P-HWP
F7 Bag / G4 Panel With Twin Pitched Roof For Horizontal XBC75 Units
2000
876
600
117
3
XBC85-F7B/G4P-HWP
F7 Bag / G4 Panel With Twin Pitched Roof For Horizontal XBC85 Units
2000
876
600
117
3
XBC75-F7B/G4P-HRWP
F7 Bag / G4 Panel With Twin Pitched Roof For Right Handed Horizontal XBC75 Units
2000
876
600
117
3
XBC85-F7B/G4P-HRWP
F7 Bag / G4 Panel With Twin Pitched Roof For Right Handed Horizontal XBC85 Units
2000
876
600
117
3
XBC75-G4B-HWP
G4 Bag with weather roof For Horizontal XBC75 Units
2000
1001
600
117
3
XBC85-G4B-HWP
G4 Bag with weather roof For Horizontal XBC85 Units
2000
1001
600
117
3
XBC75-G4B-HRWP
G4 Bag with weather roof For Right Handed Horizontal XBC75 Units
2000
1001
600
117
3
XBC85-G4B-HRWP
G4 Bag with weather roof For Right Handed Horizontal XBC75 Units
2000
1001
600
117
4.3.4 Dampers
Ref.
No.
XBC Ancillary Code
Description
Dimensions (mm)
Weight
(kg)
Width
Height
Length
4
XBC75-H-MD24V
Motorised dampers 24V for Horizontal XBC75 Adapt Siemens (AS) control units
620
560
165
14
4
XBC85-H-MD24V
Motorised dampers 24V for Horizontal XBC85 Adapt Siemens (AS) control units
840
700
165
25
4
XBC75-H-MD-NC
Damper with no actuator and extended spindle for Horizontal XBC75 Units
620
560
165
18
4
XBC85-H-MD-NC
Damper with no actuator and extended spindle for Horizontal XBC85 Units
840
700
165
29
4.3.5 Matching Attenuator Pairs (Side By Side, Supplied As One
Piece)
Ref.
No.
XBC Ancillary Code
Description
Dimensions (mm)
Weight
(kg)
Width
Height
Length
5
XBC75-H-SIL900
Side by side silencer with base frame for Horizontal XBC75 Units
2000
876
900
225
5
XBC85-H-SIL900
Side by side silencer with base frame for Horizontal XBC85 Units
2000
876
900
225
5
XBC75-H-SIL900-WP
Side by side silencer with base frame and weather roof for Horizontal XBC75 Units
2000
1001
900
250
5
XBC85-H-SIL900-WP
Side by side silencer with base frame and weather roof for Horizontal XBC85 Units
2000
1001
900
250
4.3.6 Frost Coils (Side By Side, Supplied As One Piece)
Ref.
No.
XBC Ancillary Code
Description
Dimensions (mm)
Weight
(kg)
Width
Height
Length
5
XBC75-FCL-LAS-H
Left Handed LPHW side by side module with base frame for Adapt Siemens (AS) control units
2000
876
600
113
5
XBC85-FCL-LAS-H
Left Handed LPHW side by side module with base frame for Adapt Siemens (AS) control units
2000
876
600
113
5
XBC75-FCL-RAS-H
Right Handed LPHW side by side module with base frame for Adapt Siemens (AS) control units
2000
876
600
155
5
XBC85-FCL-RAS-H
Right Handed LPHW side by side module with base frame for Adapt Siemens (AS) control units
2000
876
600
155
5
XBC75-FCE-LAS-H
Left Handed Electric side by side module with base frame for Adapt Siemens (AS) control units
2000
876
600
113
5
XBC85-FCE-LAS-H
Left Handed Electric side by side module with base frame for Adapt Siemens (AS) control units
2000
876
600
113
5
XBC75-FCE-RAS-H
Right Handed Electric side by side module with base frame for Adapt Siemens (AS) control units
2000
876
600
121
5
XBC85-FCE-RAS-H
Right Handed Electric side by side module with base frame for Adapt Siemens (AS) control units
2000
876
600
121
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
4.4 Vertical Units (XBC75-V, XBC85-V)
The unit is designed for side access as standard and must be
installed with a minimum of clearance of 650mm from a wall or
barrier.
This will provide access to filters, coil, fan, heat exchanger,
condensate tray and pump. All models: The weather roof is part of
the unit code and is factory fitted only. Example: XBC85-V-LATWP.
Note: Codes with ‘R’ i.e. (XBC75-G4B-HR) refer to right hand unit
versions.
4 Vertical Unit Dimensions (mm) and Weights (kg)
Unit Code
Unit Dimensions (mm)
Control Dimensions (mm)
Unit Weights
Packed Weights
A
B
C
J
F
H
W
D
(kg)
(kg)
XBC75-H-***
2500
954
1416
610
894
60
954
2500
630
730
XBC85-H-***
3000
1000
1676
940
740
65
1000
3000
780
880
*Includes unit and 76mm high base frame.
4.5 Vertical Units (XBC75-V, XBC85-V) Ancillaries
5 Vertical Unit Ancillary References
3
1
5
2
5
6
3
4
5
1
4.5.1 Unit With Weather Kits
Ref.
No.
XBC Unit Code
Description
Dimensions (mm)
Weight
(kg)
Width
Height
Length
1
XBC75-V-***WP
Vertical XBC75 Unit With Twin Pitched Roof
954
1476
2500
630
1
XBC75-V-***-RWP
Right Handed Vertical XBC75 Unit With Twin Pitched Roof
954
1476
2500
630
1
XBC85-V-***WP
Vertical XBC85 Unit With Twin Pitched Roof
1000
1741
3000
780
1
XBC85-V-***-RWP
Right Handed Vertical XBC85 Unit With Twin Pitched Roof
1000
1741
3000
780
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
4.5.2 Weather Terminals
Ref.
No.
XBC Ancillary Code
Description
Dimensions (mm)
Weight
(kg)
Width
Height
Length
2
XBC75-RT
Weather Terminal For Vertical XBC75 Units
842
570
610
8
2
XBC85-RT
Weather Terminal For Vertical XBC85 Units
940
740
700
10
4.5.3 Filter Module Options
Ref.
No.
XBC Ancillary Code
Description
Dimensions (mm)
Weight
(kg)
Width
Height
Length
3
XBC75-F7B/G4P
F7 Bag / G4 Panel For Vertical XBC75 Units
954
1416
600
90
3
XBC85-F7B/G4P
F7 Bag / G4 Panel For Vertical XBC85 Units
1000
1676
600
105
3
XBC75-F7B/G4P-R
F7 Bag / G4 Panel For Right Handed Vertical XBC75 Units
954
1416
600
90
3
XBC85-F7B/G4P-R
F7 Bag / G4 Panel For Right Handed Vertical XBC85 Units
1000
1676
600
105
3
XBC75-G4B
G4 Bag For Vertical XBC75 Units
954
1416
600
90
3
XBC85-G4B
G4 Bag For Vertical XBC95 Units
1000
1676
600
105
3
XBC75-G4B-R
G4 Bag For Right Handed Vertical XBC75 Units
954
1416
600
90
3
XBC85-G4B-R
G4 Bag For Right Handed Vertical XBC85 Units
1000
1676
600
105
3
XBC75-F7B/G4P-WP
F7 Bag / G4 Panel With Twin Pitched Roof For Vertical XBC75 Units
954
1476
600
92
3
XBC85-F7B/G4P-WP
F7 Bag / G4 Panel With Twin Pitched Roof For Vertical XBC85 Units
1000
1741
600
107
3
XBC75-F7B/G4P-RWP
F7 Bag / G4 Panel With Twin Pitched Roof For Right Handed Vertical XBC75 Units
954
1476
600
92
3
XBC85-F7B/G4P-RWP
F7 Bag / G4 Panel With Twin Pitched Roof For Right Handed Vertical XBC85 Units
1000
1741
600
107
3
XBC75-G4B-WP
G4 Bag with weather roof For Vertical XBC75 Units
954
1476
600
92
3
XBC85-G4B-WP
G4 Bag with weather roof For Vertical XBC85 Units
1000
1741
600
107
3
XBC75-G4B-RWP
G4 Bag with weather roof For Right Handed Vertical XBC75 Units
954
1476
600
924
3
XBC85-G4B-RWP
G4 Bag with weather roof For Right Handed Vertical XBC75 Units
1000
1741
600
107
4.5.4 Dampers
Ref.
No.
XBC Ancillary Code
Description
Dimensions (mm)
Weight
(kg)
Width
Height
Length
4
XBC75-V-MD24V
Motorised dampers 24V for Vertical XBC75 units with Adapt Siemens (AS) control
620
560
165
14
4
XBC85-V-MD24V
Motorised dampers 24V for Vertical XBC85 units with Adapt Siemens (AS) control
840
700
165
20
4
XBC75-V-MD-NC
Damper no actuator with extended spindle for Vertical XBC75 Units
620
560
165
14
4
XBC85-V-MD-NC
Damper no actuator with extended spindle for Vertical XBC85 Units
840
700
165
20
4.5.5 Matching Attenuator Pairs (Double Deck, Supplied As One
Piece)
Ref.
No.
XBC Ancillary Code
Description
Dimensions (mm)
Weight
(kg)
Width
Height
Length
5
XBC75-V-SIL900
Double deck silencer with base frame for Horizontal XBC75 Units
954
1416
900
180
5
XBC85-V-SIL900
Double deck silencer with base frame for Horizontal XBC85 Units
1000
1676
900
200
5
XBC75-V-SIL900-WP
Double deck silencer with base frame and weather roof for Horizontal XBC75 Units
954
1476
900
185
5
XBC85-V-SIL900-WP
Double deck silencer with base frame and weather roof for Horizontal XBC85 Units
1000
1741
900
205
4.5.6 Frost Coils (Double Deck, Supplied As One Piece)
Ref.
No.
XBC Ancillary Code
Description
Dimensions (mm)
Weight
(kg)
Width
Height
Length
6
XBC75-FCL-LAS-V
Left Hand LPHW double deck module with base frame for Adapt Siemens (AS) control units
954
1416
600
115
6
XBC85-FCL-LAS-V
Left Hand LPHW double deck module with base frame for Adapt Siemens (AS) control units
1000
1676
600
120
6
XBC75-FCL-RAS-V
Right Hand LPHW double deck module with base frame for Adapt Siemens (AS) control units
954
1416
600
115
6
XBC85-FCL-RAS-V
Right Hand LPHW double deck module with base frame for Adapt Siemens (AS) control units
1000
1676
600
120
6
XBC75-FCE-LAS-V
Left Hand Electric double deck module with base frame for Adapt Siemens (AS) control units
954
1416
600
100
6
XBC85-FCE-LAS-V
Left Hand Electric double deck module with base frame for Adapt Siemens (AS) control units
1000
1676
600
105
6
XBC75-FCE-RAS-V
Right Hand Electric double deck module with base frame for Adapt Siemens (AS) control units
954
1416
600
100
6
XBC85-FCE-RAS-V
Right Hand Electric double deck module with base frame for Adapt Siemens (AS) control units
1000
1676
600
105
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
5.0 ACCESS CONCEPTS
In this product range, several unique concepts have been
implemented with a view to simplifying the installation design.
Isolate before removing any panels
•The unit must be installed with at least 650mm clearance from a
wall / barrier. With this absolute minimum clearance, the unit may
be connected to the power supply and control connection.
1000mm clearance is required to remove the LPHW coil and
electric heater.
•With this clearance, unit filters may be changed, and the fans
coils, heat exchanger and condensate tray may be inspected and
cleaned if necessary.
•The LPHW and Electrical heater settings, coil bleed and drain, and
all other control adjustments are similarly accessible.
•Side access, where possible, is preferred in all cases in terms of safe
working access to the equipment under the CDM regulations.
•Note however, that access in the situation is difficult and
additional time should be allocated. For convenience it is preferred
that wherever possible, this minimum access provision is not
adopted, and it is recommended that a minimum of around
600mm clearance (as stated in ADF 2010) is allowed.
•Where these arrangements are not suitable, the Consultant’s
and Contractor’s project specific requirements will always be
accommodated where possible.
5.1 Horizontal Units (e.g. XBC75-H, XBC85-H)
6 Horizontal Unit Access
Access covers on both sides of the fan unit
Control cover
7 Horizontal Unit Overview With Lid Removed Showing Air Paths
Intake
Extract
from room
Exhaust
Supply
to room
G4 Filter
Counterflow
Heat Exchanger
8mm outside dia.
condensate drain.
Condensate pump
fitted as standard
with alarm facility
Control
LPHW or Electric Heater Battery
5.2 Vertical Units (e.g. XBC75-V, XBC85-V)
8 Vertical Unit Access
All access panels
are located on one
side of the fan unit
Note: Unit must be isolated before panels are removed.
9 Vertical Unit Overview With Lid Removed Showing Air Paths
Side View
Internal control
panel
Intake
Supply
Extract
Discharge
End View
G4 Panel Filter access
Slide out fans
LPHW or Electric
Heater Battery
Base Frame
(76mm High)
8mm outside dia. condensate drain.
Condensate pump fitted as standard
with alarm facility.
6.0 MECHANICAL INSTALLATION
Installation must be completed by competent persons, in accordance
with good industry practice and should conform to all governing and
statutory bodies i.e. IEE, CIBSE, etc.
The unit will be labelled with the direction of air flow. The direction
convention must be observed during installation.
The unit may only be operated in its intended horizontal
installation plane. The unit MUST be fully levelled during
installation (this is essential to ensure that condensate drains
correctly).
The units are heavy, and should be mounted using suitable methods
of support. The supporting structure must be assessed for structural
suitability.
If these units are being fitted into a ceiling void a suitable support
structure must be provided under each unit, the base frame provided is
NOT suitable for this purpose.
LPHW Coils, if fitted, are tested during manufacture to 16 Bar (using
dry compressed air). Coil and valve assemblies are similarly tested to 10
Bar. Operation of standard equipment is rated at PN6, if the intended
system requires higher operating pressures; please contact the Nuaire
Technical department for advice.
Electrical connections to the unit shall be made in accordance with the
appropriate product; and installation wiring diagrams, and shall use
appropriately sized and rated cables.
Only the prepared apertures in the unit casing may be used for cable
entry. Do not drill or cut the unit casing for this purpose. Cable access
points are provided at the ends of the control enclosure.
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
If the control is rotated to aid connection of cables, please ensure that
sufficient flexibility is provided in the final connection run.
To avoid conflict with the unit access panels, it is recommended
that electrical and plumbing service connections to the unit are run
at 90 degrees to the main air flow axis.
Control circuit connections must be segregated (i.e. routed separately)
from power connections.
The unit rating label shows the maximum electrical load of the
equipment. Connections to the unit may include single phase supply
connections, and a variety of control circuits.
Only the prepared apertures in the unit casing may be used for cable
entry. Do not drill or cut the unit casing for this purpose.
The equipment must be earthed and earth-bonded. Means of local
isolation for maintenance purposes are generally required (by others).
Ensure that all mains connections are isolated.
Heat recovery components and modules that incorporate cooling
coils may produce condensation during use. An insulated drip tray and
condensate pump is provided. The drain connection must be connected
to a suitable drainage point (Figures 10 & 11).
6.1 Condensate Pump
The condensate pump incorporates an alarm function. If the water
level in the condensate tray exceeds a maximum level (for example, as
a result of the discharge tube becoming blocked or frozen), the alarm
contact will open. This contact is internally connected to the heat
exchanger bypass actuator, and the unit will automatically be placed
into bypass mode, preventing further condensate production. Unit
operation will otherwise be unaffected.
Maximum flow rate = 12 l/h
Maximum head = 20m Vertical, 100m Horizontal
Pipe Connection size (Condensate) XBOXER XBC = 8 mm
6.2 Pre-Commissioning
Not all of the components listed here are necessarily included with
the equipment supplied.
10 Customer Connections (Control Side of Horizontal Unit)
LPHW or electric heater
supply connections
Control box
Access to condensate
tray and pump
Condensate drain
connection Ø 8mm push-fit
6.2.1 Filters
Remove filter access panels (observe and note airflow direction labels),
inspect filters for contamination with construction debris, replace as
necessary. Replace access panels.
Filter pressure drops will depend on actual flow rate and condition.
Observe and record filter pressure drops after performance
commissioning. Typically, filter “dirty” condition occurs when the initial
filter “clean” readings have been increased by 125Pa.
If filter manometers, pressure switches or indicators have been fitted,
they should be set or adjusted to reflect the commissioned system
operation.
11 Customer Connections (Control Side of Vertical Unit)
LPHW or electric heater
supply connections
Control box
Access to condensate
tray and pump
Condensate drain
connection
Ø 8mm push-fit
Fixed panel for
customer connections
6.2.2 Heating Coils LPHW
Observe the Flow and Return connection labels on the unit. Drain and
bleed valves are located on the coil. Other valves may be required in the
system pipe-work depending on the installation (by others).
Where the wet system is at risk of frost damage, the addition of a
proprietary anti-freeze solution to the water is recommended. Note
that any frost protection offered by the unit’s integral control system
will not operate if the power supply to the unit is interrupted.
Ecosmart frost protection is activated on any Ecosmart unit fitted with
LPHW heating, when the outlet air temperature is 4ºC or below. The
unit reacts by shutting down the fan to prevent a ‘wind chill’ effect
reducing the temperature to a point whereby the coil could freeze
and burst. The unit will also drive open the LPHW valve to a fully open
position to allow full water flow through the coil and the main PCB
will close the ‘Heat demand’ contacts. These contacts could be used to
send a signal to activate the boiler and/or valve to open to provide heat
if not already doing so.
Piped connections should be made to the unit using appropriate
techniques, and all pipework must be independently supported. No hot
work is permitted within one metre of the unit.
Ensure that installed pipework runs do not prevent or restrict access to
the unit at any point.
The completed installation (including the connections within the unit,
as these may be disturbed during installation) shall be pressure tested
to the project engineer’s specification (This is a condition of the unit
warranty).
6.2.3 Electric Heaters
Heater Capacity: XBC75 – 3ph, 12Kw
XBC85 – 3ph, 18Kw
The Electric Heater requires a 3ph supply which is independent from
the main unit supply. Connections to be made through the low level
fixed panel. The Electric Heater may be withdrawn to allow access to
the Heater Controller without the need for wiring to be disconnected
(Ensure the mains supply is isolated before removing any access panels
and any adjustments are made to the Heater Controller).
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
6.2.4 Fan Sections
Access to the fan section is via lift off panels. For non-Ecosmart units,
wiring to the fan motor / unit terminal box should be mechanically
protected and in made in accordance with the details on the motor
name plate and diagram attached to the unit.
With the unit electrically isolated, rotate the fan impeller / drive
manually, checking that it spins freely. Check all fixings are secure.
Units must not be operated without all access panels in place – damage
to equipment or injury to personnel may result. Units must not be
operated unless control interlocks are in place – damage to equipment
may result.
Test run motor for condition and correct rotation. Check that the
correct current overloads are fitted and that the current being drawn
does not exceed the motor nameplate value. Excessive current
normally indicates that the ductwork system resistance is different to
design.
6.2.5 Motorised Dampers
If Nuaire matched silencers (Horizontal: XBC75-H-SIL900, Vertical:
XBC75-V-SIL900) are being fitted to the fan unit, the motorised
damper (Horizontal: XBC75-H-MD24V, Vertical: XBC75-V-MD24V )
needs to be fitted after the silencer.
This ensures that breakout noise levels are kept to a minimum.
•Fully interlocking parallel blades, half inch diameter electroplated
mild steel spindle.
•Nylatron bushes and external nylon/aluminium blade
interconnection linkage.
•Fitted with drive open/drive close actuator complete with switch.
•Motorised damper wiring will require connection on site and
possible extension of the cable looms.
Motorised Damper
drive open/drive close
actuator complete with switch.
p
e
e
d
m
m
5
6
1
12 Motorised Damper Actuator
6.3 Constant Pressure Range (CP) - Controlling Static
Pressure at Fan Inlet
Ecosmart constant pressure extract fans are supplied to control the
static pressure at the fan inlet.
This set up is suitable for the majority of applications. When ancillaries
with high pressure losses are fitted to the inlet side of the fan, the low
pressure tapping must be moved from the fan chamber to a location
upstream of the ancillaries, as shown below in Figure 13.
Failure to do this will result in excessive pressure being applied to the
dampers at the rooms when the system is running in trickle mode.
13 Typical Constant Pressure Setup
Riser
Ancillaries
Riser
Inlet
e.g. Silencer
Pressure
Balancing
Branch
Damper
Balancing
Branch
Damper
Extract Fan
To atmosphere
Sensor
High Low
Pressure
Flexible tubing
New Pressure Tapping
Airflow
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
6.4 Filter Pressure Switch
XBC 75 & 85 units come with pre fitted pressure tappings and tubing
for use with the fitted dirty filter alarms on both the supply and extract
air streams. The IP54 pressure switch is equipped with a red visual LED
alarm which will illuminate when the pressure reading surpasses that
set by the adjustable knob.
6.4.1 Setting Switch Pressure
Make certain that there is no voltage on the electrical connections
before you carry out any setting on the pressure switch, there is the
possibility of an electric shock if you accidentally touch live parts.
Nuaire recommend the pressure switch be set to trigger when the
filters experience a 125 Pa increase above the clean filter resistance for
the largest commissioned airflow rate. Use the adjustment dial to set
the pressure at which the switch will trip. When the pressure falls below
this set value, the switch returns to its resting position.
6.4.2 Switch Wiring
The cable gland is designed for cables with alternative sheath diameters
of 7 mm or 10 mm. Only use these sizes, otherwise the screw cable
connection cannot seal adequately. The connections are intended for
6.3mm crimp-type sockets.
Remove switch cover. Wire the main unit to the terminal block within
the switch as per the below wiring diagrams (Figure 14) ensuring the
feed line is fused to suit Max 1.5A / 250 Vac. Refit switch cover.
14 Switch Wiring
Schematic Diagram
Pressure Sensor Internals
2 - NO
3 - C
1 - NC
3 - C Contacts 2 - NO
when the difference between
positive & negative pressure
is equal to the set pressure.
Customer 240 V
Connection
Customer 240V
Connection
Internal Connection
Customer Connection
*Note 1: NC has been
blanked off.
*Note 2: Pressure setting
of 125Pa above clean filter
pressure is recommended.
*Note 3: If a different
arrangement is required,
then the internal LED con-
nections can be removed.
240 V
Indicator
240 V
Indicator
Sensor Diagram
2 - NO
1 - NC
*Note 2
*Note 3
*Note 1
Differential
Pressure
Setting
3 - C
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
6.5 Hardware Positions
6.5.1 Key To Hardware Positions
A. Supply Fan (Drive & Health)
B. Supply Air Temperature Sensor
C. Extract Air Temperature Sensor
D. Thermal Trip (Electric Heater Only)
E. LPHW Heater (LPHW Models Only)
F. Bypass Damper Drive
G. Condensate Pump Alarm
H. Fresh Air Temperature
I. Extract Fan (Drive & Health)
6.5.2 Horizontal Units
BB
CC
EXTRACT
SUPPLY
INLET
DISCHARGE
AA
DD
EE
GG
HH
FF
F
II
B
C
15 Horizontal Unit Hardware Positioning
6.5.3 Vertical Units
CC
EE
HH
II
FF
EXTRACT
SUPPLY
INLET
DISCHARGE
AA
BB
DD
GG
E
FF
I
H
F
C
16 Vertical Unit Hardware Positioning
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
7.0 ELECTRICAL INSTALLATION
Before commencing work, make sure that the unit, switched live
and Nuaire control are electrically isolated from the mains supply.
The electrical wiring must be carried out by competent persons, in
accordance with good industry practice and should conform to all
governing and statutory bodies i.e. IEE, CIBSE etc.
7.1 Supply
The control is powered by a 400Vac 50Hz 3 phase supply. This must be
isolated local to the unit and fitted with appropriate over-current and
fault protection.
7.1.1 Electric Heater Supply
For models with electric heating, the heating circuit is powered by a
separate, higher current, 400VAC 3ph supply. This must be isolated
local to the unit and fitted with appropriate over-current protection.
The main supply is still required.
Electric Heater models require two separate supplies, each with an
appropriate overcurrent current protection device.
7.2 Volt Free Contacts
Volt free contacts are not fused. If these are used to power any external
equipment, the installer must provide adequate fusing or other
protections.
Volt free relay contacts are rated at 5A resistive, 0.5A inductive.
Run Connections: The relay is powered when the fan is running
(contacts are used when an I/O damper
is installed).
Fault Connections: No Fault - The relay is powered.
Fault - The relay is unpowered.
Heat Demand:
The relay is powered when heating is selected.
Cool Demand:
The relay is powered when cooling is selected.
7.3 Switched Live
Switch Live (SL) terminal - A signal of 100-230V AC will activate the
switched live signal.
Switch Live 2 Boost (SL2) terminal - A signal of 100-230V AC will
activate the switched live 2 (Fan Boost) signal.
A signal from an isolating transformer will produce an unpredictable
result and is not recommended.
Volt free versions of the switched live signals are also available at
terminals T33-T34 & T35-T36. Link two contacts to activate the signal.
7.4 Damper Connections
A fan start delay can be imposed to allow the damper time to open and
is adjustable via the strategy.
7.5 Network Settings
Default IP address:
192.168.11.12
Subnet mask:
255.255.255.0
A copy of the strategy is stored in the EDoS (Engineering Data on Site)
portion of memory.
7.6 Connection Chart
Description
TD
Short
Name
Subsystem
Signal
Address
Block
Type
Signal
Type
Unit
Min
Max
Fresh Air Temp
AHU’2Sensors’1FreshAir
1FreshAir
C
1.1
AI
R1K
°C
0
50
Supply Air Temp
AHU’2Sensors’2SupAIr
2SupAIr
C
1.2
AI
R1K
°C
-50
80
Extract Air Temp
AHU’2Sensors’3ExtAir
3ExtAir
C
1.3
AI
R1K
°C
-50
80
CO2 Sensor
AHU’2Sensors’4CO2
4CO2
C
1.4
AI
U10
ppm
0
2000
Fan Speed Cntrl
AHU’2Sensors’5FnSdCnt
5FnSdCnt
C
1.5
AI
U10
%
0
10
Alm Ctritical
AHU’3DigIns’AlmCritC1
AlmCritC1
C
1.6
BI
D20
Nml/Alm
Alm Maintenance
AHU’3DigIns’AlmFitC2
AlmFltC2
C
1.7
BI
D20
Nml/Alm
Enable Hware
AHU’3DigIns’EnaHW
EnaHW
C
1.8
BI
D20
No, Yes
Boost Ena Hware
AHU’3DigIns’BoostHW
BoostHW
C
1.9
BI
D20
No, Yes
OCC PIR Hware
AHU’3DigIns’OccPIR
OccPIR
C
1.10
BI
D20
UnOcc/Occ
SupFan AirFlo
AHU’3DigIns’SpFnDPS
SpFnDPS
C
1.11
BI
D20
NoFlo/Flow
ExtFan AirFlo
AHU’3DigIns’ExtFnDPS
ExtFnDPS
C
1.12
BI
D20
NoFlow/Flow
Extract Speed
AHU’6Outpts’4ExtFan
4ExtFan
C
4.1
AO
Y10S
%
0
100
Supply Speed
AHU’6Outpts’3SupFan
3SupFan
C
4.2
AO
Y10S
%
0
100
Heating Sig
AHU’6Outpts’7HtgSig
7HtgSig
C
4.3
AO
Y10S
%
0
100
Cooling SIg
AHU’6Outpts’91ClgSig
91ClgSig
C
4.1
AO
Y10S
%
0
100
Bypass Dmp
AHU’6Outpts’5DmpCnt
5DmpCnt
C
5.1
BO
Q250
Reclaim/Bypass
Fault Relay
AHU’6Outpts’92FltRly
92FltRly
C
5.2
BO
Q250
Off, On
Fan Enabled Rly
AHU’6Outpts’2FanEna
2FanEna
C
5.3
BO
Q250
Off, On
Chilled Dmd Relay
AHU’6Outpts’8ClgDmd
8ClgDmd
C
5.4
BO
Q250
No, Yes
Heat Dmd Relay
AHU’6Outpts’6HtgDmd
6HtgDmd
C
5.5
BO
Q250
No, Yes
IO Damper
AHU’6Outpts’11IODmp
11IODmp
C
5.6
BO
Q250
Close, Open
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
7.7 Terminal Connections
7.7.1 Push In Termination
Stripped solid conductors, fine-stranded conductors with ferrules, or
ultrasonically “bonded” conductors are simply pushed in until they hit
the backstop, no tool is required.
17 Push In Terminal Connections
7.7.2 Termination Of Fine Stranded Conductors
Open the clamp by inserting an operating tool (as shown below)
until it clicks into position. Then insert the conductor and remove the
operating tool to complete the connection.
18 Fine Stranded Terminal Connections
7.7.3 Conductor Removal
Insert an operating tool in to the operating slot to remove the
conductor, just like the original CAGE CLAMP® terminals blocks.
19 Removing Terminal Connections
7.7.4 Fitting Jumpers
Terminal blocks can be connected together to increase the number of
terminals at the same potential using push-in jumpers. In these cases
the terminals are treated as one conductor.
20 Jumper Connections
7.7.5 Jumper Removal
Insert the operating tool blade between the jumper and the partition
wall of the dual jumper slots, then lift up the jumper.
21 Removing Jumpers
7.7.6 Double Deck Terminal Block
Each deck has a different potential (2-conductor), which creates a space
saving on the rail. Decks can be commoned to adjacent terminal blocks
and/or the top to the bottom deck.
22 Double Deck Terminal Blocks
7.7.7 Earth Terminal Blocks
The earth terminal block (green/yellow) has a direct electrical
connection to the DIN rail, with the earthing foot (earth connection
only).
23 Earth Terminal Blocks
7.7.8 Fuse Terminals
Replaceable cartridge fuses are housed in quick release fuse terminals.
24 Fuse Terminal Blocks
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
7.8 Physical Layout Diagrams
7.8.1 Horizontal Units
25 Physical Layout - Horizontal Units
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
7.8.2 Vertical Units
26 Physical Layout - Vertical Units
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
7.9 Wiring Diagrams
All inter-connections between circuit boards, blowers and sensors
are made at the factory. This diagram only shows the essential field
wiring points for clarity.
27 Wiring Diagram - No Heater / LPHW
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
28 Wiring Diagram - Electric Heater
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
8.0 FROST COIL (OPTIONAL ANCILLARY)
All inter-connections between circuit boards, blowers and sensors are
made at the factory. This diagram only shows the essential field wiring
points for clarity.
8.1 LPHW Frost Coils
8.1.1 Wiring
The heater requires a 230V~50Hz single phase supply connection to
power the thermostat and valve actuator. Remove the top cover from
the terminal box by rotating the four fixing screws half a turn, revealing
the terminal block marked LEN.
29 Wiring - LPHW Frost Coil Ancillary
230VAC
Fused
Supply
8.1.2 Setting 'Frost Condition' Temperature
The LPHW heater frost coil is only enabled if the frost stat reads a ‘frost
condition’. A ‘frost condition’ temperature adjustment dial is provided
as part of the frost coil controls. The ‘frost condition’ temperature is
easily adjustable from -10 to +10°C by inserting a small screwdriver
into the adjuster aperture and rotating the spindle clockwise or
anticlockwise. It is recommended that the ‘frost condition’ temperature
is set at 4°C.
8.2 Electric Frost Coils
8.2.1 Wiring
The heater requires two connections; the relay link up and the
400V~50Hz three phase supply connection to power the heater
element. Remove the top cover from the terminal box by rotating the
four fixing screws half a turn, revealing the terminal block.
The relay connection between main controls and the frost coil module
can now be made.
8.2.2 Setting 'Frost Condition' Temperature
The electric heater frost coil is only enabled if the frost stat reads
a ‘frost condition’, the over-temperature cut-out is healthy AND a
24vac fan run signal is received from the main control panel. A ‘frost
condition’ temperature adjustment dial is provided as part of the frost
coil controls. The ‘frost condition’ temperature is easily adjustable from
-10 to +10°C by inserting a small screwdriver into the adjuster aperture
and rotating the spindle clockwise or anticlockwise. Once enabled
the electric heater frost coil will provide its maximum heat output
to achieve the ‘frost condition’ temperature set by the frost stat. It is
recommended that the ‘frost condition’ temperature is set at 4°C.
32 Wiring - Electric Frost Coil Ancillary
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
9.0 CONTROLS
30 Controller
9.1 Controllable Items
•Inlet damper (if fitted).
•Extract damper (if fitted).
•Heat recovery & bypass damper.
•Heating coil.
•Supply fan speed.
•Extract fan speed.
9.2 Enable Signal
The unit can be enabled via the following methods:
•Software switch via strategy.
•Switched live (230VAC) input, PIR etc. via digital input.
•Low voltage contacts via digital input.
•Night cooling / summer free-cooling strategy.
When the enable signal is removed, the unit will run on for a time
defined by the run-on setpoint. If an electric heater is fitted, the fans
will automatically run-on for an extra 2 minutes, without heating, in
order to dissipate residual heat.
9.3 Occupancy Control
When a Trend occupancy sensor is selected via UI4 & 5 software
module, the control will look for a Trend OCC-U sensor in the
appropriate input.
An occupied signal will give an enable signal.
•0V = Occupied
•14V = Unoccupied
9.4 Boost Speed
When the control receives a boost signal the fans will run at boost
speed. Once the signal is removed the fans will run on for a time
defined by the boost run-on setpoint.
9.5 Trickle Speed
When trickle mode is active, the fans will run at their minimum speed
even when there is no enable signal. Heating and cooling will also
function in this mode if available.
9.6 CO2 Control
When a CO2 sensor is connected, CO2 control is enabled via the
CO2 software switch and an enable signal is received, ventilation
will increase to reduce CO2 concentration the target CO2 setpoint.
The target CO2 sensor setpoint can be changed as one of the
commissioning setpoints.
9.7 Supply Temperature Control
While an enable signal is present, this mode modulates heating,
cooling & heat exchanger bypass dampers with the aim of the supply
air reaching the temperature setpoint. Please note that heating and
cooling outputs will only function if the HeatingType or CoolingType
setpoints are set to heating or cooling options.
9.8 Frost Protection
Should the internal temperature of the unit fall below a value defined
in the commissioning variables, the control will override all heating/
cooling logic to open the LPHW or CW control valves, if fitted. This is
to allow any protective flow through the heating/cooling coils. The
supply fan will also stop and the appropriate frost protection software
module will enter an alarm state. This period will last for a minimum of
5 minutes by default. The fault relay will also open.
Please note that frost protection will only function if the HeatingType
or CoolingType switches are set to LPHW or CW.
9.9 Night Cooling / Summer Free Cooling
Once enabled in software, this routine uses an individual time schedule
to cool the fabric of the building at night using only the external air.
This mode only functions if the daytime temperature is above the
setpoint, cooling is possible and if the cooling air is not too cold.
9.10 Alarms
9.10.1 Critical Alarm (Latching)
Once in critical alarm state the unit will drive all heating and cooling
outputs to 0V. Other functions continue as normal. The critical alarm is
latched and required manual reset to clear.
Causes of critical alarm:
•Fan fail via alarm circuit 1.
•Heater overtemp via alarm circuit 1.
9.10.2 Maintenance Alarms (Non-Latching)
Once in maintenance alarm state the only action taken is de-energising
of the fault relay. Once the trigger is removed, the alarm will reset
automatically.
Causes of maintenance alarm:
•Sensor failure
•Low supply temperature, default 8°C.
•Frost protection routine active, default 4°C (Only runs if water
valves are selected as fitted).
•Excessively high supply temperature reading (Will stop heating).
•Filter fault
All alarms have a hold off period set by the setpoint “Alarm delay”.
9.10.3 Thermal Trip
In case of software failure, as a final resort, the electric heater is
protected by a fail-safe thermal overload switch. This switch disables
the heater controller via a contactor once the temperature reaches
80°C. When this occurs, the critical alarm will latch in software.
Once the unit cools, the contactor will re-engage but the heater signal
will remain at 0V until the critical fault is reset in software or by power
cycle.
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
9.11 Touch Screen Display (PMX10)
31 PMX10 Touch Screen Control
Below is an optional control solution ancillary for your application. For
the full range and technical details, please contact Nuaire.
Local operator unit for monitoring and operation of ONE PX compact
or PX modular automation station.
•High-grade display with adjustable contrast.
•Easy operation with a push-dial, giving direct access to the
required plant information.
•Choice of generic view or "Favourites" view for operation and
display of plant functions (alarm handling, time schedules,
calendars, set point adjustments, display of measured values, etc.).
•System date and time setting
•Optimized for use in a fixed location
The PXM10 (9" x 5") unit is suitable for mounting in control panel fronts
or vertical panels (e.g. remote operating panels or similar units). The
unit is also suitable for DIN rail snap mounting.
10.0 MAINTENANCE
It is important that maintenance checks are recorded and that the
schedule is always adhered to, in all cases, the previous report should
be referred to.
Before commencing work, make sure that the unit and Nuaire
control are electrically isolated from the mains supply. In some
Ecosmart units and in some third party controls, variable speed drives
(inverters) are used to provide fan speed control. After the fan is
isolated, allow at least 5 minutes for the capacitors in the inverter to
discharge before commencing any work on the unit.
10.1 Routine Maintenance
•Clean all areas of unit and treat any areas of corrosion.
•Check all access doors for leakage and if necessary locks should be
adjusted and any replacement gasket materials should be replaced
as required.
•Any drain trays should be cleaned and repaired if necessary.
10.2 Every 3 Months
•Check filters and change/clean if required, failure to do so may
impair the performance and energy efficiency of this unit.
Typically filters should be changed when the filters experience a
125 Pa increase above the clean filter resistance for the largest
commissioned airflow rate.
•Ensure condensate drains are cleaned clear and that water can
flow freely from unit.
•Check fin coil banks and heat exchangers. If necessary clean with a
soft brush or vacuum. Check for signs of contamination.
10.3 Annually
•Thoroughly inspect the unit and its components for corrosion,
acting immediately to treat/restore any damaged areas.
•All electrical terminals within the unit should be tightened.
•Check all earth connections.
•Check control dampers blades.
•Check operation of damper actuators and linkages and adjust as
necessary.
•Coil faces should be inspected and any dust removed.
•Check any thermal wheel belt, motor, bearings, seals and if
necessary clean with a soft brush or vacuum cleaner.
11.0 WARRANTY
A 5 year warranty on Ecosmart Control models, Basic Control models
have a 2 year warranty. The warranty starts from the day of delivery and
includes parts and labour for the first year. The remaining period covers
replacement parts only.
This warranty is void if the equipment is modified without
authorisation, is incorrectly applied, misused, disassembled, or not
installed, commissioned and maintained in accordance with the details
contained in this manual and general good practice.
The product warranty applies to the UK mainland and in accordance
with Clause 14 of our Conditions of Sale. Customers purchasing from
outside of the UK should contact Nuaire International Sales office for
further details.
Failure to maintain the unit as recommended will invalidate the
warranty.
12.0 END-OF-LIFE AND RECYCLING
Where possible Nuaire use components which can be largely recycled
when the product reaches its end-of-life:
•Fans, motors, controls, actuators, cabling and other electrical
components can be segregated into WEEE recycling streams.
•Sheet metal parts, aluminium extrusion, heating/cooling coils and
other metallic items can be segregated and fully recycled.
•EPP, plastic ducting, nylon corner pieces, plastic heat exchangers,
packaging material and other plastic components can be
segregated into mixed plastic and widely recycled.
•Cardboard packaging, wood, used filters and other paper
components can be largely recycled or fully processed in energy
from waste centres.
•Remaining Items can be further segregated and processed in
accordance with the zero waste hierarchy. Please call After Sales
Support for further information on items not listed above.
Ensure that Nuaire product is made safe from any electrical / water
/ refrigerant supplies before dismantling commences. This work
should only be undertaken by a qualified person in accordance with
local authority regulations and guidelines, taking into account all
site based risks.
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
13.0 AFTER SALES AND REPLACEMENT PARTS
For technical assistance or further product information, including spare
parts and replacement components, please contact the After Sales
Department.
If ordering spares please quote the serial number of the unit together
with the part number, if the part number is not known please give a full
description of the part required. The serial number will be found on the
identification plate attached to the unit casing.
Part Number
Description
XBC75-V-FILTERKIT XBC75 Replacement G4 Panel Filters x4
776187
XBC75 Replacement Blower Assembly x1 (18kg)
XBC75-H-FILTERKIT XBC85 Replacement G4 Panel Filters x4
776188
XBC85 Replacement Blower Assembly x1 (37kg)
13.1 Blower Replacement
Remove 4x fixings and slide blower out of unit to replace. Caution:
Blowers are heavy, see description above for weight.
13.2 Filter Replacement
Remove retaining plate and slide filters out of unit to replace.
Telephone 02920 858 400
[email protected]
Technical or commercial considerations may, from time to time,
make it necessary to alter the design, performance and dimensions
of equipment and the right is reserved to make such changes without
prior notice.
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
DECLARATION OF INCORPORATION AND INFORMATION FOR SAFE INSTALLATION,
OPERATION AND MAINTENANCE
INFORMATION FOR SAFE INSTALLATION, OPERATION AND MAINTENANCE
OF NUAIRE VENTILATION EQUIPMENT
We declare that the machinery named below is intended to be assembled with
other components to constitute a system of machinery. All parts
except for moving parts requiring the correct installation of safety guards comply
with the essential requirements of the Machinery Directive. The
machinery shall not be put into service until the system has been
declared to be in conformity with the provisions of the EC Machinery
Directive.
Designation of machinery:
XBOXER XBC Ecosmart Adapt (AS)
models
Machinery Types:
Supply & Extract fans with Heat
Recovery
Relevant EC Council Directives:
2006/42/EC (Machinery Directive)
Applied Harmonised Standards:
BS EN ISO 12100, BS EN ISO 13857
EN60204-1, BS EN ISO 9001
Applied National Standards:
BS848 Parts 1, 2.2 and 5
Signature of manufacture representatives:
Name:
Position:
Date:
1)C. Biggs
Technical Director
2)A. Jones
Manufacturing Director
To comply with EC Council Directives 2006/42/EC Machinery Directive and 2014/30/EU (EMC).
To be read in conjunction with the relevant product documentation (see 2.1)
1.0
GENERAL
1.1
The equipment referred to in this Declaration of Incorporation is supplied by Nuaire to
be assembled into a ventilation system which may or may not include additional
components.
The entire system must be considered for safety purposes and it is the responsibility of
the installer to ensure that all of the equipment is installed in compliance with the
manufacturers recommendations and with due regard to current legislation and codes
of practice.
2.0
INFORMATION SUPPLIED WITH THE EQUIPMENT
2.1
Each item of equipment is supplied with a set of documentation which provides the
information required for the safe installation and maintenance of the equipment.
This may be in the form of a Data sheet and/or Installation and Maintenance instruction.
2.2
Each unit has a rating plate attached to its outer casing. The rating plate provides
essential data relating to the equipment such as serial number, unit code and electrical
data. Any further data that may be required will be found in the documentation.
If any item is unclear or more information is required, contact Nuaire.
2.3
Where warning labels or notices are attached to the unit the instructions given must be
adhered to.
3.0
TRANSPORTATION, HANDLING AND STORAGE
3.1
Care must be taken at all times to prevent damage to the equipment. Note that shock
to the unit may result in the balance of the impeller being affected.
3.2
When handling the equipment, care should be taken with corners and edges and that
the weight distribution within the unit is considered. Lifting gear such as slings or ropes
must be arranged so as not to bear on the casing.
3.3
Equipment stored on site prior to installation should be protected from the weather and
steps taken to prevent ingress of contaminants.
4.0
OPERATIONAL LIMITS
4.1
It is important that the specified operational limits for the equipment are adhered to
e.g. operational air temperature, air borne contaminants and unit orientation.
4.2
Where installation accessories are supplied with the specified equipment eg.
wall mounting brackets. They are to be used to support the equipment only.
Other system components must have separate provision for support.
4.3
Flanges and connection spigots are provided for the purpose of joining to duct work
systems. They must not be used to support the ductwork.
4.4
Local Environment - Humidity. Ambient humidity (the humidity at the unit’s installed
location) shall be within the range: 10 to 95% (for controls, non-condensing).
Air humidity (the humidity of the air passing through the unit) shall be within the
range: 10 to 95% (for controls, non-condensing).
5.0
INSTALLATION REQUIREMENTS
In addition to the particular requirements given for the individual product, the following
general requirements should be noted.
5.1
Where access to any part of equipment which moves, or can become electrically live are
not prevented by the equipment panels or by fixed installation detail (e.g. ducting), then
guarding to the appropriate standard must be fitted.
5.2
The electrical installation of the equipment must comply with the requirements of the
relevant local electrical safety regulations.
5.3
For EMC all control and sensor cables should not be placed within 50mm or on the same
metal cable tray as 230V switched live, lighting or power cables and any cables not
intended for use with this product.
6.0
COMMISSIONING REQUIREMENTS
6.1
General pre-commissioning checks relevant to safe operation consist of the following:
Ensure that no foreign bodies are present within the fan or casing.
Check electrical safety. e.g. Insulation and earthing.
Check guarding of system.
Check operation of Isolators/Controls.
Check fastenings for security.
6.2
Other commissioning requirements are given in the relevant product documentation.
7.0
OPERATIONAL REQUIREMENTS
7.1
Equipment access panels must be in place at all times during operation of the unit, and
must be secured with the original fastenings.
7.2
If failure of the equipment occurs or is suspected then it should be taken out of service
until a competent person can effect repair or examination. (Note that certain ranges of
equipment are designed to detect and compensate for fan failure).
8.0
MAINTENANCE REQUIREMENTS
8.1
Specific maintenance requirements are given in the relevant product documentation.
8.2
It is important that the correct tools are used for the various tasks required.
8.3
If the access panels are to be removed for any reason the electrical supply to the unit
must be isolated.
8.4
A minimum period of two minutes should be allowed after electrical disconnection before
access panels are removed. This will allow the impeller to come to rest.
NB: Care should still be taken however since airflow generated at some other point
in the system can cause the impeller to “windmill” even when power is not present.
8.5
Care should be taken when removing and storing access panels in windy conditions.
Note: All standards used were current and valid at the date of signature.
13. 05. 16.
13. 05. 16.
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
NOTES
09. 06. 21. Document Number 671786
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
XBC75 & 85 (AS Control)
Installation Manual
NOTES