Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or
equivalent, service agency, or the gas supplier.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for noncompliance.
IMPORTANT
This unit must be matched with an indoor coil as specified
with AHRI. For AHRI Certified system matchups and
expanded ratings, visit www.LennoxPros.com. Coils
previously charged with HCFC-22 must be flushed.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
WARNING
Electric Shock Hazard. Can cause injury or
death. Unit must be properly grounded in
accordance with national and local codes.
Line voltage is present at all components when
unit is not in operation on units with single-
pole contactors. Disconnect all remote electric
power supplies before opening access panel.
Unit may have multiple power supplies.
ML16XP1
Table of Contents
Installation Clearances....................................................2
Model Number Identification............................................2
Dimensions......................................................................3
Specifications..................................................................4
Typical Unit Parts Arrangement.......................................6
Operating Gauge Set and Service Valves.......................6
Unit Placement ...............................................................8
Removing and Installing Louvered Panels......................9
New or Replacement Line Set.......................................10
Brazing Connections ....................................................12
Flushing Line Set and Indoor Coil.................................15
Installing Indoor Metering Device..................................16
Leak Test Line Set and Indoor Coil ...............................17
Evacuating Line Set and Indoor Coil ............................18
Electrical........................................................................19
System Operation ........................................................21
System Configuration....................................................21
Defrost System ............................................................24
Maintenance ................................................................26
Wiring and Sequence of Operation ............................28
Servicing Units Void of Charge ....................................32
Start-Up .......................................................................32
Service Literature
UNIT INFORMATION
Corp. 1818-L8
March 3, 2020
ML16XP1 (HFC-410A) SERIES OUTDOOR UNITS
General Information
These instructions are intended as a general guide and do
not supersede national or local codes in any way. Consult
authorities having jurisdiction before installation.
The Merit® ML16XP1 model is designed for use with
HFC-410A refrigerant only. This unit must be installed with
an approved indoor air handler or coil. For AHRI Certified
system matchups and expanded ratings, visit www.Len-
noxPros.com.
This outdoor unit is designed for use in systems that use
the following refrigerant metering device:
• Check thermal expansion valve (CTXV)
IMPORTANT: Special procedures are required for clean-
ing the all-aluminum coil in this unit. See page 26 in this
instruction for information.
Service clearance of 30 in. (762 mm) must be maintained on
one of the sides adjacent to the control box.
Clearance to one of the other three sides must be
36 in. (914 mm)
Clearance to one of the remaining two sides may be
A clearance of 24 in. must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.
Model Number Identification
Nominal Cooling Capacity
018 = 1.5 tons
024 = 2 tons
030 = 2.5 tons
036 = 3 tons
042 = 3.5 tons
048 = 4 tons
060 = 5 tons
ML 16 X P 1 - 036 - 230 A 0 1
Nominal SEER
Refrigerant Type
X = R-410A
Revision Level
Voltage
230 = 208/230V-1 phase-60hz
Product Tier
ML = Merit® Series
Unit Type
P = Heat Pump Outdoor Unit
Cooling Stages
1 = Single Stage Compressor
Ratings Revision Level
STANDOFF KIT (4)
(FIELD INSTALLED)
4-3/8
INLET
AIR
INLET
AIR
TOP VIEW
INLET
AIR
INLET
AIR
SUCTION LINE
CONNECTION
LIQUID LINE
CONNECTION
6-3/8
(162)
TOP VIEW BASE SECTION
COMPRESSOR
COIL DRAIN OUTLETS
(Around perimeter of base)
OPTIONAL UNIT
STAND-OFF KIT (4)
(Field Installed)
(111)
4-3/8
4-3/8
4-3/8
4-3/8
6-3/8
(162)
(111)
(111)
(111
(
)
111)
4-3/8
(111)
2 (51)
3/4 (19)
2-3/4 (70)
ELECTRICAL
INLETS
1 Sound Rating Number (dBA)
76
76
76
76
Connections
(sweat)
Liquid line (o.d.) - in.
3/8
3/8
3/8
3/8
Vapor (Suction) line (o.d.) - in.
3/4
3/4
3/4
7/8
Refrigerant
2 R-410A charge furnished
6 lbs. 6 oz.
6 lbs. 11 oz.
7 lbs. 10 oz.
8 lbs. 7 oz.
Outdoor
Coil
Net face area - sq. ft.
Outer coil
24.5
18.7
18.7
22.2
Inner coil
- - -
18.0
18.0
21.5
Tube diameter - in.
5/16
5/16
5/16
5/16
No. of rows
1
2
2
2
Fins per inch
22
22
22
22
Outdoor
Fan
Diameter - in.
22
22
22
26
No. of blades
3
3
3
3
Motor hp
1/6
1/6
1/6
1/3
Cfm
2670
2575
2575
3700
Rpm
867
866
866
820
Watts
160
163
163
200
Shipping Data - lbs. 1 pkg.
180
188
188
214
ELECTRICAL DATA
Line voltage data - 60hz - 1 ph
208/230V-1ph
208/230V-1ph
208/230V-1ph
208/230V-1ph
3 Maximum overcurrent protection (amps)
20
20
25
35
4 Minimum circuit ampacity
12.2
13.6
16.4
20.9
Compressor
Rated load amps
9
10.1
12.3
14.7
Locked rotor amps
48
52
63
75
Power factor
0.98
0.98
0.96
0.99
Outdoor Fan Motor
Full load amps
1.0
1.0
1.0
2.6
Locked rotor amps
1.9
1.9
1.9
- - -
OPTIONAL ACCESSORIES - ORDER SEPARATELY
iComfort® M30 Smart Wi-Fi Thermostat
15Z69
•
•
•
•
Remote Outdoor Temperature Sensor
X2658
•
•
•
•
Compressor Crankcase Heater
94M04
•
•
•
93M05
•
Compressor Hard Start Kit
LG
88M91
•
•
•
•
Compressor Sound Cover
69J03
•
•
•
•
Compressor Low Ambient Cut-Off
45F08
•
•
•
•
Freezestat
3/8 in. tubing
93G35
•
•
•
•
5/8 in. tubing
50A93
•
•
•
•
Indoor Blower Off Delay Relay
58M81
•
•
•
•
Loss of Charge Switch Kit
84M23
•
•
•
•
5 Low Ambient Kit
54M89
•
•
•
•
Mild Weather Kit
11B97
•
•
•
•
Monitor Kit - Service Light
76F53
•
•
•
•
Outdoor
Thermostat Kit
Thermostat
10Z23
•
•
•
•
Mounting Box
31461
•
•
•
•
Refrigerant Line Sets
L15-41-20 L15-41-40
L15-41-30 L15-41-50
•
•
•
L15-65-30 L15-65-40
L15-65-50
•
Unit Stand-Off Kit
94J45
•
•
•
•
NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage.
1 Sound Rating Number rated in accordance with test conditions included in AHRI Standard 270.
2
additional refrigerant charge required.
3 HACR type breaker or fuse.
4 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
5 Crankcase Heater and Freezestat are recommended with Low Ambient Kit
1 Sound Rating Number (dBA)
79
80
80
Connections
(sweat)
Liquid line (o.d.) - in.
3/8
3/8
3/8
Vapor (Suction) line (o.d.) - in.
7/8
7/8
1-1/8
Refrigerant
2 R-410A charge furnished
10 lbs. 12 oz.
10 lbs. 7 oz.
10 lbs. 4 oz.
Outdoor
Coil
Net face area- sq. ft.
Outer coil
29.1
29.1
29.1
Inner coil
28.2
28.2
28.2
Tube diameter - in.
5/16
5/16
5/16
No. of rows
2
2
2
Fins per inch
22
22
22
Outdoor
Fan
Diameter - in.
26
26
26
No. of blades
3
3
4
Motor hp
1/3
1/3
1/3
Cfm
4150
4150
4250
Rpm
820
820
820
Watts
216
216
245
Shipping Data - lbs. 1 pkg.
263
263
268
ELECTRICAL DATA
Line voltage data - 60hz - 1 ph
208/230V-1ph
208/230V-1ph
208/230V-1ph
3 Maximum overcurrent protection (amps)
40
40
50
4 Minimum circuit ampacity
25
25.8
30.4
Compressor
Rated load amps
15.9
18.5
22.2
Locked rotor amps
112.3
124
127.9
Power factor
0.99
0.99
0.99
Outdoor Fan Motor
Full load amps
2.6
2.6
2.6
OPTIONAL ACCESSORIES - ORDER SEPARATELY
iComfort® M30 Smart Wi-Fi Thermostat
15Z69
•
•
•
Remote Outdoor Temperature Sensor
X2658
•
•
•
Compressor Crankcase Heater
93M05
•
•
•
Compressor Hard Start Kit
LG
88M91
•
•
Copeland
10J42
•
•
Compressor Sound Cover
69J03
•
•
•
Compressor Low Ambient Cut-Off
45F08
•
•
•
Freezestat
3/8 in. tubing
93G35
•
•
•
5/8 in. tubing
50A93
•
•
•
Indoor Blower Off Delay Relay
58M81
•
•
•
Loss of Charge Switch Kit
84M23
•
•
•
5 Low Ambient Kit
54M89
•
•
•
Mild Weather Kit
11B97
•
•
•
Monitor Kit - Service Light
76F53
•
•
•
Outdoor
Thermostat Kit
Thermostat
10Z23
•
•
•
Mounting Box
31461
•
•
•
Refrigerant Line Sets
L15-65-30 L15-65-40
L15-65-50
•
•
Unit Stand-Off Kit
94J45
•
•
•
NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage.
1 Sound Rating Number rated in accordance with test conditions included in AHRI Standard 270.
2
additional refrigerant charge required.
3 HACR type breaker or fuse.
4 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
5 Crankcase Heater and Freezestat are recommended with Low Ambient Kit
Typical Unit Parts Arrangement
REVERSING VALVE
BI-FLOW FILTER DRIER
HIGH PRESSURE SWITCH
CHECK / EXPANSION VALVE
VAPOR LINE SERVICE VALVE
LIQUID LINE SERVICE VALVE
DISCHARGE LINE
LOW PRESSURE SWITCH
FIGURE 1. Typical Plumbing Arrangement
Operating Gauge Set and Service Valves
TORQUE REQUIREMENTS
When servicing or repairing heating, ventilating, and air
conditioning components, ensure the fasteners are appro-
priately tightened. Table 1 lists torque values for fasteners.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc
- Rockwell Harness Scale minimum). Fully insert the
wrench into the valve stem recess.
Service valve stems are factory-torqued (from 9 ft-lbs
for small valves, to 25 ft-lbs for large valves) to prevent
refrigerant loss during shipping and handling. Using an
Allen wrench rated at less than 50Rc risks rounding
or breaking off the wrench, or stripping the valve stem
recess.
See the Lennox Service and Application Notes #C-08-1
for further details and information.
IMPORTANT
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted
snugly over the cap before tightening.
TABLE 1. Torque Requirements
Parts
Recommended Torque
Service valve cap
8 ft.- lb.
11 NM
Sheet metal screws
16 ft.- lb.
2 NM
Machine screws #10
28 ft.- lb.
3 NM
Compressor bolts
90 in.- lb.
10 NM
Gauge port seal cap
8 ft.- lb.
11 NM
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold
gauge set that features low loss anti-blow back fittings.
Manifold gauge set used with HFC-410A refrigerant sys-
tems must be capable of handling the higher system oper-
ating pressures. The gauges should be rated for use with
pressures of 0 - 800 psig on the high side and a low side
of 30” vacuum to 250 psig with dampened speed to 500
psi. Gauge hoses must be rated for use at up to 800 psig
of pressure with a 4000 psig burst rating.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for re-
moving refrigerant, flushing, leak testing, evacuating,
checking charge and charging. Each valve is equipped
with a service port which has a factory-installed valve
stem. Figure 2 provides information on how to access and
operate both angle and ball service valves
(VALVE STEM SHOWN
CLOSED) INSERT HEX
WRENCH HERE
SERVICE PORT CORE
SERVICE PORT CAP
ANGLE-TYPE SERVICE VALVE
(FRONT-SEATED CLOSED)
SERVICE PORT
CORE
TO OUTDOOR UNIT
STEM CAP
(VALVE STEM SHOWN OPEN)
INSERT HEX WRENCH HERE
TO INDOOR
UNIT
ANGLE-TYPE SERVICE VALVE
(BACK-SEATED OPENED)
BALL (SHOWN
CLOSED)
SERVICE PORT
CORE
TO INDOOR UNIT
TO OUTDOOR
UNIT
TO OPEN ROTATE STEM
COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM
CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
CAP
STEM CAP
VALVE
STEM
SERVICE VALVES ANGLE AND BALL
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex-head extension (3/16” for liquid line valve sizes and 5/16” for vapor line valve sizes) to back
the stem out counterclockwise as far as it will go.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve,
roate stem counterclockwise 90°. To close rotate stem clockwise
90°.
12
3
4
5
6
7
8
9
1011 12
1/12 TURN
To Access Service Port:
A service port cap protects the service port core from contamination and
serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as
follows:
With torque wrench: Finger tighten and
torque cap per table 3.
Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn
an additional 1/6 turn clockwise.
12
3
4
5
6
7
8
9
101112
1/6 TURN
WHEN SERVICE VALVE IS CLOSED, THE SERVICE PORT IS OPEN
TO THE LINE SET AND INDOOR UNIT.
When service valve is OPEN, the service port is
open to linE set, indoor and outdoor unit.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the
primary seal. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and
then torque cap per table 3.
Without Torque Wrench: Fi
en and use an appropriately sized
wrench to turn an additional 1/12 turn
clockwise.
NOTE — A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
FIGURE 2. Angle and Ball Service Valves
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE
OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY
FROM BUILDING STRUCTURE.
DETAIL A
DETAIL B
INSTALL UNIT AWAY
FROM WINDOWS
TWO 90 ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION
GROUND LEVEL
MOUNTING
SLAB
BUILDING
STRUCTURE
DISCHARGE AIR
FIGURE 3. Placement and Slab Mounting
Unit Placement
See Unit Dimensions on page 3 for sizing mounting slab,
platforms or supports. Refer to page 2 for mandatory in-
stallation clearance requirements.
CAUTION
In order to avoid injury, take proper precaution when
lifting heavy objects..
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
• Some localities are adopting sound ordinances based
on the unit's sound level registered from the adjacent
property, not from the installation property. Install the
unit as far as possible from the property line.
• When possible, do not install the unit directly outside
a window. Glass has a very high level of sound trans-
mission. For proper placement of unit in relation to a
window see the provided illustration in figure 3, detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab
should be high enough above grade so that water from
higher ground will not collect around the unit. The slab
should have a slope tolerance as described in figure 3,
detail B.
ROOF MOUNTING
Install the unit a minimum of 6 inches (152 mm) above the
roof surface to avoid ice build-up around the unit. Locate
the unit above a load bearing wall or area of the roof that
can adequately support the unit. Consult local codes for
rooftop applications.
If unit coil cannot be mounted away from prevailing winter
winds, a wind barrier should be constructed. Size barrier
at least the same height and width as outdoor unit. Mount
barrier 24 inches (610 mm) from the sides of the unit in the
direction of prevailing winds.
NOTICE
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil, causing the
rubber to swell. Bubbles in the rubber roofing material
can cause leaks. Protect the roof surface to avoid
exposure to refrigerant and oil during service and
installation. Failure to follow this notice could result in
damage to roof surface.
Removing and Installing Louvered Panels
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel,
nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown
around and battered.
WARNING
REMOVAL
STEP 1
INSERT PANEL UNDER UNIT
TOP CAP LIP AND LIFT
SLIGHTLY TO CLEAR SIDE LIP
OF PANEL FROM BASE.
STEP 2
PANEL INSTALLATION
TO REMOVE PANEL,
REMOVE MOUNTING
SCREWS SECURING
PANEL TO THE UNIT.
SLIGHTLY LIFT PANEL IN
ORDER TO CLEAR SIDE
LIPS OF PANEL FROM
BASE OF UNIT.
STEP 3
TILT PANEL OUT SLIGHTLY
AND PULL DOWNWARD
TO REMOVE.
STEP 1
STEP 2
MOVE PANEL IN TOWARDS UNIT.
ALIGN LEFT/RIGHT SIDE LIPS OF
PANEL WITH GROOVE INSERTS
ALONG LEFT/RIGHT SIDE OF UNIT.
TOP CAP
BASE
SIDE
GROOVE
STEP 3
SECURE PANEL, WITH
MOUNTING SCREWS.
PANEL LEFT
PANEL RIGHT
PANEL CENTER
CORNER
POST
CORNER POST
PANEL CENTER
CORNER
POST
FIGURE 4. Louvered Panels
New or Replacement Line Set
This section provides information on new installation or
replacement of existing line set. If a new or replacement
line set is not required, then proceed to Brazing Connec-
tions on page .
If refrigerant lines are routed through a wall, seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the refrig-
erant lines will not create unnecessary vibration and sub-
sequent sounds.
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines
from the outdoor unit (braze connections) to the indoor
unit coil (flare or braze connections). Use Lennox L15
(braze, non-flare) series line set, or use field-fabricated
refrigerant lines as listed in table 2.
TABLE 2
REFRIGERANT LINE SET – INCHES (MM)
Model
Valve Field
Connections
Recommended Line Set
Liquid
Line
Vapor
Line
Liquid
Line
Vapor
Line
L15 Line Sets
-018
3/8 in.
(10 mm)
3/4 in.
(19 mm)
3/8 in.
(10 mm)
3/4 in.
(19 mm)
L15-41
15 ft. - 50 ft.
(4.6 m - 15 m)
-024
-030
-036
3/8 in.
(10 mm)
7/8 in.
(22 mm)
3/8 in.
(10 mm)
7/8 in.
(22 mm)
L15-65
15 ft. - 50 ft.
(4.6 m - 15 m)
-042
-048
-060
3/8 in.
(10 mm)
1-1/8 in.
(28 mm)
3/8 in.
(10 mm)
1-1/8 in.
(28 mm)
Field Fabricated
NOTE - Some applications may require a field-provided 7/8" to
1-1/8" adapter.
NOTE – When installing refrigerant lines longer than 50
feet, contact Lennox Technical Support Product Applica-
tions for assistance or Lennox piping manual. To obtain
the correct information from Lennox, be sure to communi-
cate the following points:
• Model (ML16XP1) and size of unit (e.g. -060).
• Line set diameters for the unit being installed as listed in
table 2 and total length of installation.
• Number of elbows and if there is a rise or drop of the
piping.
IMPORTANT
Mineral oils are not compatible with HFC-410A. If oil
must be added, it must be a Polyol ester oil.
The compressor is charged with sufficient Polyol ester oil
for line set lengths up to 50 feet. Recommend adding oil to
system based on the amount of refrigerant charge in the
system. No need to add oil in system with 20 pounds of
refrigerant or less. For systems over 20 pounds - add one
ounce for every five pounds of refrigerant.
Recommended topping-off POE oils are Mobil EAL ARC-
TIC 22 CC or ICI EMKARATE RL32CF.
MATCHING WITH NEW OR EXISTING INDOOR COIL
AND LINE SET
The RFC1-metering line consisted of a small bore copper
line that ran from condenser to evaporator coil. Refrig-
erant was metered into the evaporator by utilizing tem-
perature/pressure evaporation effects on refrigerant in the
small RFC line. The length and bore of the RFC line cor-
responded to the size of cooling unit. If the ML16XP1 is
being used with either a new or existing indoor coil which
is equipped with a liquid line which served as a meter-
ing device (RFCI), the liquid line must be replaced prior to
the installation of the ML16XP1 unit. Typically a liquid line
used to meter flow is 1/4” in diameter and copper.
LINE SET ISOLATION
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing operations.
Perform operations only in well-ventilated areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting
of refrigerant (CFC’s and HCFC’s) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for non-compliance.
IMPORTANT
If this unit is being matched with an approved line set
or indoor unit coil that was previously charged with
mineral oil, or if it is being matched with a coil which
was manufactured before January of 1999, the coil and
line set must be flushed prior to installation. Take care to
empty all existing traps. Polyol ester (POE) oils are used
in Lennox units charged with HFC-410A refrigerant.
Residual mineral oil can act as an insulator, preventing
proper heat transfer. It can also clog the expansion
device and reduce system performance and capacity.
Failure to properly flush the system, per this instruction
and the detailed Installation and Service Procedures
manual will void the warranty.
ANCHORED HEAVY NYLON
WIRE TIE OR AUTOMOTIVE
MUFFLER‐TYPE HANGER
STRAP LIQUID LINE TO
VAPOR LINE
WALL
STUD
LIQUID LINE
NON-CORROSIVE
METAL SLEEVE
VAPOR LINE - WRAPPED
IN ARMAFLEX
AUTOMOTIVE
MUFFLER‐TYPE HANGER
REFRIGERANT LINE SET — TRANSITION
FROM VERTICAL TO HORIZONTAL
Line Set Isolation — The following illustrations are
examples of proper refrigerant line set isolation:
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR
WIRE TIE
WIRE TIE (AROUND
VAPOR LINE ONLY)
FLOOR JOIST OR
ROOF RAFTER
TAPE OR
WIRE TIE
To hang line set from joist or rafter, use either metal strapping material
or anchored heavy nylon wire ties.
8 FEET (2.43 METERS)
STRAP THE VAPOR LINE TO THE JOIST
OR RAFTER AT 8 FEET (2.43 METERS)
INTERVALS THEN STRAP THE LIQUID
LINE TO THE VAPOR LINE.
FLOOR JOIST OR
ROOF RAFTER
REFRIGERANT LINE SET — INSTALLING
HORIZONTAL RUNS
NOTE — Similar installation practices should be used if line set is
to be installed on exterior of outside wall.
PVC
PIPE
FIBERGLASS
INSULATION
CAULK
OUTSIDE
WALL
VAPOR LINE WRAPPED
WITH ARMAFLEX
LIQUID
LINE
OUTSIDE WALL
LIQUID LINE
VAPOR LINE
WOOD BLOCK
BETWEEN STUDS
STRAP
WOOD BLOCK
STRAP
SLEEVE
WIRE TIE
WIRE TIE
WIRE TIE
INSIDE WALL
REFRIGERANT LINE SET — INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
INSTALLATION
LINE SET
NOTE — Insulate liquid line when it is routed through areas where the
surrounding ambient temperature could become higher than the
temperature of the liquid line or when pressure drop is equal to or greater
than 20 psig.
NON-CORROSIVE
METAL SLEEVE
IMPORTANT — Refrigerant lines must not contact structure.
NON-CORROSIVE
METAL SLEEVE
8 FEET (2.43 METERS)
IMPORTANT — Refrigerant lines must not contact wall
WARNING — Polyol ester (POE) oils used with HFC-410A
refrigerant absorb moisture very quickly. It is very important that the
refrigerant system be kept closed as much as possible. DO NOT
remove line set caps or service valve stub caps until you are ready
to make connections.
FIGURE 5. Line Set Installation
Use the procedures outlined in figures 6 and 7 for brazing
line set connections to service valves.
WARNING
Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing torch
to a pressurized system may result in ignition
of the refrigerant and oil mixture. Check the
high and low pressures before applying heat.
WARNING
When using a high pressure gas such as
nitrogen to pressurize a refrigeration or air
conditioning system, use a regulator that can
control the pressure down to 1 or 2 psig (6.9
to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing operations.
Perform operations only in well-ventilated areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
IMPORTANT
Allow braze joint to cool before removing the wet rag
from the service valve. Temperatures above 250ºF can
damage valve seals.
IMPORTANT
Use silver alloy brazing rods with 5% minimum silver
alloy for copper-to-copper brazing. Use 45% minimum
alloy for copper-to-brass and copper-to-steel brazing.
WARNING
Fire, Explosion and Personal Safety hazard.
Failure to follow this warning could result in
damage, personal injury or death.
Never use oxygen to pressurize or purge
refrigeration lines. Oxygen, when exposed
to a spark or open flame, can cause fire and/
or an explosion, that could result in property
damage, personal injury or death.
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE
VALVES
OUTDOOR
UNIT
LIQUID LINE
VAPOR LINE
LIQUID LINE SERVICE
VALVE
SUCTION /
VAPOR LINE
SERVICE
VALVE
ATTACH
GAUGES
INDOOR
UNIT
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
A
Connect gauge set low pressure side to
liquid line service valve (service port).
B
Connect gauge set center port to bottle of
nitrogen with regulator.
C
Remove core from valve in suction / vapor
line service port to allow nitrogen to escape.
NITROGEN
HIGH
LOW
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
B
A
C
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
Flow regulated nitrogen (at 1 to 2 psig) through the low-side refrigeration gauge set into the liquid line service port valve, and out of the suction /
vapor line service port valve.
CUT AND DEBUR
CAP AND CORE REMOVAL
Cut ends of the refrigerant lines square (free from nicks or dents)
and debur the ends. The pipe must remain round. Do not crimp end
of the line.
Remove service cap and core from
both the suction / vapor and liquid line
service ports.
1
2
LIQUID LINE SERVICE
VALVE
SERVICE
PORT
CORE
SERVICE PORT
CAP
SERVICE
PORT
CORE
SERVICE
PORT CAP
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
COPPER TUBE
STUB
SERVICE VALVE
CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
REDUCER
3
SUCTION / VAPOR LINE
SERVICE VALVE
LINE SET SIZE IS SMALLER
THAN CONNECTION
FIGURE 6. Brazing Procedures
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
LIQUID LINE SERVICE VALVE
LIQUID LINE
BRAZE LINE SET
Wrap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Water
saturated cloths must remain water saturated throughout the brazing and cool-down process.
WATER SATURATED
CLOTH
IMPORTANT — Allow braze joint to cool. Apply
additional water saturated cloths to help cool brazed
joint. Do not remove water saturated cloths until piping
has cooled. Temperatures above 250ºF will damage
valve seals.
6
SUCTION / VAPOR LINE
WATER SATURATED
CLOTH
SUCTION / VAPOR LINE
SERVICE VALVE
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both
services valves to cool piping. Once piping is cool, remove all water saturated cloths. Refer to the unit installation instructions for the next step
in preparing the unit.
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
PREPARATION FOR NEXT STEP
7
WARNING
1. FIRE, PERSONAL INJURY, OR PROPERTY
DAMAGE may result if you do not wrap a water
saturated cloth around both liquid and suction line
service valve bodies and copper tube stub while
brazing in the line set! The braze, when complete,
must be quenched with water to absorb any residual
heat.
2. Do not open service valves until refrigerant lines and
indoor coil have been leak-tested and evacuated.
Refer to procedures provided in this supplement.
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use
additional water saturated cloths underneath the valve body to protect the base paint.
4
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections
5
FIGURE 7. Brazing Procedures (continued)
Flushing Line Set and Indoor Coil
SENSING
LINE
TEFLON® RING
FIXED ORIFICE
BRASS NUT
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
LIQUID LINE ORIFICE HOUSING
DISTRIBUTOR TUBES
DISTRIBUTOR
ASSEMBLY
REMOVE AND DISCARD
WHITE TEFLON® SEAL
(IF PRESENT)
A
On fully cased coils, remove the coil access and plumbing panels.
B
Remove
sembly.
C
Using two wrenches, disconnect liquid line from liquid
ing. T
cess.
D
Remove and discard fixed orifice, valve stem assembly if present and
Teflon® washer as illustrated above.
E
Use a field-provided fitting to temporarily reconnect the liquid line to the
indoor unit's liquid line orifice housing.
TYPICAL EXISTING FIXED ORIFICE
REMOVAL PROCEDURE (UNCASED
COIL SHOWN)
TYPICAL EXISTING EXPANSION VALVE REMOVAL
PROCEDURE (UNCASED COIL SHOWN)
TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
VAPOR
LINE
DISTRIBUTOR
ASSEMBLY
DISTRIBUTOR
TUBES
LIQUID
LINE
MALE EQUALIZER
LINE FITTING
EQUALIZER
LINE
CHECK
EXPANSION
VALVE
TEFLON®
RING
STUB END
TEFLON®
RING
SENSING BULB
LIQUID LINE
ORIFICE
HOUSING
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
A
On fully cased coils, remove the coil access and plumbing panels.
B
Remove any shipping clamps holding the liquid line and distributor
assembly.
C
Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
D
Remove the vapor line sensing bulb.
E
Disconnect the liquid line from the check expansion valve at the liquid
line assembly.
F
Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this
process.
G
Remove and discard check expansion valve and the two Teflon® rings.
H
Use a field-provided fitting to temporary reconnect the liquid line to the
indoor unit's liquid line orifice housing.
LOW
HIGH
EXISTING
INDOOR
UNIT
GAUGE
MANIFOLD
INVERTED CYLINDER
CONTAINS CLEAN
HCFC22* TO BE USED
FOR FLUSHING.
LIQUID LINE SERVICE
VALVE
INLET
DISCHARGE
TANK
RETURN
CLOSED
OPENED
RECOVERY CYLINDER
RECOVERY MACHINE
NEW
OUTDOOR
UNIT
VAPOR LINE
SERVICE VALVE
VAPOR
LIQUID
1
A
Inverted HCFC-22 cylinder with clean refrigerant* to the vapor service
valve.
B
HCFC-22 gauge set (low side) to the liquid line valve.
C
HCFC-22 gauge set center port to inlet on the recovery machine with an
empty recovery tank to the gauge set.
D
Connect recovery tank to recovery machines per machine instructions.
CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE
A
B
C
D
B
OR
FLUSHING LINE SET
A
Set the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the
recovery machine to pull a vacuum on the existing system line
set and indoor unit coil.
B
Invert the cylinder of clean HCFC-22* and open its valve to allow
liquid refrigerant to flow into the system through the vapor line
valve. Allow the refrigerant to pass from the cylinder and through
the line set and the indoor unit coil before it enters the recovery
machine.
C
After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC-22
vapor is recovered. Allow the recovery machine to pull the
system down to 0.
D
Close the valve on the inverted HCFC-22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.
The line set and indoor unit coil must be flushed with at least the
same amount of clean refrigerant* that previously charged the
system. Check the charge in the flushing cylinder before
proceeding.
1A
2
3
1B
*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system
has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.
FIGURE 8. Removing Metering Device and Flushing
Installing Indoor Metering Device
A
Attach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and
screws provided.
NOTE — Confirm proper thermal contact between vapor line
and expansion bulb before insulating the sensing bulb once
installed.
B
Connect the equalizer line from the expansion valve to
the equalizer vapor port on the vapor line. Finger tighten
the flare nut plus 1/8 turn (7 ft-lbs) as illustrated below.
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
VAPOR
LINE
LIQUID LINE
ORIFICE
HOUSING
DISTRIBUTOR
TUBES
LIQUID LINE
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
SENSING
LINE
EQUALIZER
LINE
EXPANSION
VALVE
TEFLON®
RING
(Uncased Coil Shown)
Sensing bulb insulation is required if
mounted external to the coil casing. sensing
bulb installation for bulb positioning.
STUB
END
TEFLON®
RING
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
DISTRIBUTOR
ASSEMBLY
A
Remove the field-provided fitting that temporary
reconnected the liquid line to the indoor unit's distributor
assembly.
B
Install one of the provided Teflon® rings around the
stubbed end of the expansion valve and lightly lubricate
the connector threads and expose surface of the Teflon®
ring with refrigerant oil.
C
Attach the stubbed end of the expansion valve to the
liquid line orifice housing. Finger tighten and use an
appropriately sized wrench to turn an additional 1/2 turn
clockwise as illustrated in the figure above, or 20 ft-lb.
D
Place the remaining Teflon® washer around the other
end of the expansion valve. Lightly lubricate connector
threads and expose surface of the Teflon® ring with
refrigerant oil.
E
Attach the liquid line assembly to the expansion valve.
Finger tighten and use an appropriately sized wrench to
turn an additional 1/2 turn clockwise as illustrated in the
figure above or 20 ft-lb.
ON 7/8” AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O'CLOCK
POSITION. NEVER MOUNT ON
BOTTOM OF LINE.
12
ON LINES SMALLER THAN
7/8”,
MOUNT
SENSING
BULB AT EITHER THE 3 OR
9 O'CLOCK POSITION.
12
BULB
VAPOR LINE
VAPOR LINE
NOTE — NEVER MOUNT ON BOTTOM OF LINE.
BULB
BULB
BULB
VAPOR LINE
FLARE NUT
COPPER FLARE
SEAL BONNET
MALE BRASS EQUALIZER
LINE FITTING
FLARE SEAL CAP
OR
1
2
3
4
5
6
7
8
9
10
11 12
1/2 Turn
SENSING BULB INSTALLATION
EQUALIZER LINE INSTALLATION
1
2
3
4
5
6
7
8
9
10
11 12
1/8 Turn
A
Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port
on the vapor line as illustrated in the figure to the right.
B
Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on
the vapor line as illustrated in the figure to the right.
INDOOR EXPANSION VALVE INSTALLATION
FIGURE 9. Installing Indoor Expansion Valve
This outdoor unit is designed for use in systems that use a
check / expansion valve metering device at the indoor coil.
See the Lennox ML16XP1 Product Specification bulletin
for approved expansion valve kit match-ups. The expan-
sion valve unit can be installed internal or external to the
indoor coil.
In applications where an uncased coil is being installed in
a field-provided plenum, install the expansion valve in a
manner that will provide access for field servicing of the
expansion valve. Refer to below illustration for reference
during installation of expansion valve unit.
The Clean Air Act of 1990 bans the intentional venting
of refrigerant (CFC’s and HCFC’s) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for non-compliance.
IMPORTANT
If this unit is being matched with an approved line set
or indoor unit coil that was previously charged with
mineral oil, or if it is being matched with a coil which
was manufactured before January of 1999, the coil and
line set must be flushed prior to installation. Take care to
empty all existing traps. Polyol ester (POE) oils are used
in Lennox units charged with HFC-410A refrigerant.
Residual mineral oil can act as an insulator, preventing
proper heat transfer. It can also clog the expansion
device and reduce system performance and capacity.
Failure to properly flush the system, per this instruction
and the detailed Installation and Service Procedures
manual will void the warranty.
Leak Test Line Set and Indoor Coil
WARNING
When using a high pressure gas such as
nitrogen to pressurize a refrigeration or air
conditioning system, use a regulator that can
control the pressure down to 1 or 2 psig (6.9
to 13.8 kPa).
IMPORTANT
Leak detector must be capable of sensing HFC
refrigerant.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal
injury or death.
TO VAPOR
SERVICE VALVE
HFC-410A
MANIFOLD GAUGE SET
OUTDOOR UNIT
HIGH
LOW
NITROGEN
A
With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. Open the valve
on the HFC-410A cylinder (vapor only).
B
Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit. Weigh in a trace amount of HFC-410A. [A
trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC-410A cylinder
and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder.
C
Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
D
Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set
and the indoor unit.
E
After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak
detector.
F
After leak testing disconnect gauges from service ports.
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the
following procedure to test for leaks:
A
Connect an HFC-410A manifold gauge set high pressure
hose to the vapor valve service port.
NOTE — Normally, the high pressure hose is connected to
the liquid line port. However, connecting it to the vapor port
better protects the manifold gauge set from high pressure
damage.
B
With both manifold valves closed, connect the cylinder of
HFC-410A refrigerant to the center port of the manifold gauge
set.
NOTE — Later in the procedure,
the HFC-410A container will be
replaced
by
the
nitrogen
container.
1
CONNECT GAUGE SET
2
TEST FOR LEAKS
A
B
FIGURE 10. Leak Test
Evacuating Line Set and Indoor Coil
A
Open both manifold valves and start the vacuum pump.
B
Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE — During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure
indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE — The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of
pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C
When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:
Close manifold gauge valves
Close valve on vacuum pump
Turn off vacuum pump
Disconnect manifold gauge center port hose from vacuum pump
Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.
Open manifold gauge valves to break the vacuum in the line set and indoor unit.
Close manifold gauge valves.
D
Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
E
Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
F
When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an
upright cylinder of HFC-410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and
indoor unit.
G
Perform the following:
OUTDOOR
UNIT
TO VAPOR
SERVICE VALVE
TO LIQUID LINE
SERVICE VALVE
MICRON
GAUGE
VACUUM PUMP
A34000 1/4 SAE TEE WITH
SWIVEL COUPLER
500
MANIFOLD
GAUGE SET
HFC-410A
RECOMMEND
MINIMUM 3/8” HOSE
A
Connect low side of manifold gauge set
with 1/4 SAE in-line tee to vapor line
service valve
B
Connect high side of manifold gauge
set to liquid line service valve
C
Connect micron gauge available
connector on the 1/4 SAE in-line tee.
D
Connect the vacuum pump (with
vacuum gauge) to the center port of the
manifold gauge set. The center port
line will be used later for both the
HFC-410A and nitrogen containers.
HIGH
LOW
1
2
3
4
5
6
7
8
9
10
11
12
1/6 TURN
NITROGEN
1
CONNECT GAUGE SET
A
B
C
D
2
EVACUATE THE SYSTEM
NOTE — Remove cores from service valves (if not already done).
Close manifold gauge valves.
Shut off HFC-410A cylinder.
Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
Replace stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn as illustrated.
FIGURE 11. Evacuating the System
Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
capable of accurately measuring down to 50 microns.
WARNING
Possible equipment damage.
Avoid deep vacuum operation. Do not use compressors
to evacuate a system. Extremely low vacuum can cause
internal arcing and compressor failure. Damage caused
by deep vacuum operation will void warranty.
Evacuating the system of non-condensables is critical for
proper operation of the unit. Non-condensables are de-
fined as any gas that will not condense under tempera-
tures and pressures present during operation of an air
conditioning system. Non-condensables and water suc-
tion combine with refrigerant to produce substances that
corrode copper piping and compressor parts.
Electrical
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the cur-
rent Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air han-
dler for low-voltage control power (24VAC - 40 VA mini-
mum).
WARNING
Electric Shock Hazard. Can cause injury or
death. Unit must be properly grounded in
accordance with national and local codes.
Line voltage is present at all components
when unit is not in operation on units with
single-pole contactors. Disconnect all remote
electric power supplies before opening
access panel. Unit may have multiple power
supplies.
Refer to the unit nameplate for minimum circuit ampacity, and maximum
fuse or circuit breaker (HACR per NEC). Install power wiring and properly
sized disconnect switch.
NOTE — Units are approved for use only with copper conductors.
Ground unit at disconnect switch or to an earth ground.
SIZE CIRCUIT AND INSTALL SERVICE
DISCONNECT SWITCH
NOTE — 24VAC, Class II circuit connections are made in the control
panel.
Install room thermostat (ordered separately) on an inside wall
approximately in the center of the conditioned area and 5 feet (1.5m) from
the floor. It should not be installed on an outside wall or where it can be
affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
INSTALL THERMOSTAT
SERVICE
DISCONNECT
SWITCH
MAIN FUSE BOX/
BREAKER PANEL
HEAT PUMP UNIT
(TWO-STAGE)
X2658 OUTDOOR SENSOR IS REQUIRED FOR OUTDOOR
TEMPERATURE DISPLAY, DEW POINT CONTROL, HEAT PUMP AND
DUAL FUEL BALANCE POINTS.
COMFORTSENSE
7500
R
R
R
W3
H
W2
W2
W1
W1
W1
O
O
O
L
L
Y1
Y1
Y1
Y2
Y2
G
G
C
C
C
T
T
D
B
Y2
DS
O. D.
SENSOR
(X2658)
Y2
OUT
BL
1
1
CUT ON-BOARD LINK R -O.
CUT ON-BOARD LINK R-DS WHEN DEHUMIDIFICATION TERMINAL IS USED.
CUT ON-BOARD LINK Y1-Y2 FOR TWO-STAGE HP
2
2
3
3
FIELD-PROVIDED JUMPER BETWEEN Y2 OUT BL ON HEAT
PUMP TO Y2.
CONNECTED ON UNIT WITH LSOM. RESISTOR KIT (CAT # 47W97)
IS REQUIRED WHEN CONNECTING THE COMFORTSENSE 7000
WITH THE LSOM 2.
Y1-Y2
2-STAGE
COMPR
R-O
HEAT
PUMP
R-DS
DEHUM
OR
HARMONY
CUT FOR OPTION
AIR
HANDLER
CONTROL
IMPORTANT - USE CARE WHEN CUTTING LINKS TO
PREVENT DAMAGE TO CONTROL. SEE INSTALLATION
INSTRUCTION FOR FURTHER DETAILS.
Typical Field Wiring — Heat Pump Application with
CBA38MV
FIGURE 12
YELLOW
BLUE (NOT REQUIRED FOR SINGLE STAGE)
RED
BLACK
PURPLE
PURPLE
BLACK
BLUE
RED
FAN RELAY (NOT REQUIRED
WITH SINGLE−SPEED
OUTDOOR FAN)
OUTDOOR
SENSOR
(X2658)
COMFORTSENSE
7500 THERMOSTAT
OUTDOOR UNIT
CUT ON-BOARD LINK R -O.
CUT ON-BOARD LINK Y1-Y2 FOR TWO-STAGE A/C ONLY
CUT ON-BOARD LINK R-DS WHEN DEHUMIDIFICATION
TERMINAL IS USED.
T
T
BROWN (NOT USED FOR APPLICATIONS WITHOUT LSOM
Y1-Y2
2-STAGE
COMPR
R-O
HEAT
PUMP
R-DS
DEHUM
OR
HARMONY
CUT FOR OPTION
RESISTOR KIT (CAT # 47W97) IS REQUIRED
WHEN CONNECTING THE COMFORTSENSE
7000 WITH THE LSOM 2.
IMPORTANT - USE CARE WHEN CUTTING LINKS TO
PREVENT DAMAGE TO CONTROL. SEE INSTALLATION
INSTRUCTION FOR FURTHER DETAILS.
CBA38MV
AIR
HANDLER
CONTROL
Heat Pump Application — Humiditrol® and
Second-Stage Outdoor Fan Relay Wiring with
CBA38MV
FIGURE 13
Some scroll compressors have an internal vacuum
protector that will unload scrolls when suction pressure
goes below 20 psig. A hissing sound will be heard when
the compressor is running unloaded. Protector will
reset when low pressure in system rises above 40 psig.
DO NOT REPLACE COMPRESSOR.
The outdoor unit and indoor blower cycle on demand from
the room thermostat. If the thermostat blower switch is in
the ON position, the indoor blower operates continuously.
Bi-Flow Liquid line Filter Drier
The unit is equipped with a large-capacity bi-flow filter dri-
er which keeps the system clean and dry. If replacement is
necessary, order another of the same design and capac-
ity. The replacement filter drier must be suitable for use
with HFC-410A refrigerant.
Low Pressure Switch (S87)
The ML16XP1 is equipped with an auto-reset low pres-
sure switch which is located on the vapor line. The switch
shuts off the compressor when the vapor pressure falls
below the factory setting. This switch, which is ignored
during defrost operation, closes at pressures at or above
40 + 5 psig (276 + 34 kPa) and opens at 25 + 5 psig (172
+ 34 kPa). It is not adjustable.
Low Pressure Switch Bypass (S41) (Optional)
For use in applications where the heat pump is operated
in outdoor ambient temperatures below 15°F.
• Prevents nuisance trips form the low pressure switch
• Wired in parallel with the low pressure switch
High Pressure Switch (S4)
The ML16XP1 is equipped with an auto-reset high pres-
sure switch (single-pole, single-throw) which is located on
the liquid line. The switch shuts off the compressor when
discharge pressure rises above the factory setting. The
switch is normally closed and is permanently adjusted to
trip (open) at 590 + 15 psig (4068 + 103 kPa).
NOTE – A Schrader core is under the pressure switches.
Crankcase Heater (HR1) and Thermostat Switch (S40)
Certain units are equipped with a belly band type crank-
case heater. HR1 prevents liquid from accumulating in the
compressor. The HR1 is controlled by a single pole, single
throw thermostat switch (S40) located on the liquid line.
On all units, the heater is on when there is no compressor
operation.
Thermal Protection Switch (S173) – Compressor
Mounted
Some ML16XP1 units are equipped with a compressor
mounted normally closed temperature switch that pre-
vents compressor damage due to overheating caused
by internal friction. The switch is located on top of the
compressor casing (see figure 1). This switch senses
the compressor casing temperature and opens at 239-
257°F (115°C-125°C) to shut off compressor operation.
The auto-reset switch closes when the compressor cas-
ing temperature falls to 151-187°F (66°C-86°C), and the
compressor is re-energized. This single-pole, single-throw
(SPST) bi-metallic switch is wired in series with the 24V Y
input signal to control compressor operation.
System Configuration
Demand Defrost Control (A108)
The demand defrost control measures differential tem-
peratures to detect when the system is performing poorly
because of ice build-up on the outdoor coil. The control
self-calibrates when the defrost system starts and after
each system defrost cycle. The demand defrost control
components are shown in figure 14.
• Demand defrost control connections, jumpers and LED
locations are shown in figure 14.
• Demand defrost control connections, jumpers and LED
descriptions are listed on table 3.
• Demand defrost control status, fault and lockout LEDs
are listed in table 4.
24V TERMINAL STRIP
CONNECTIONS
(P2)
DIAGNOSTIC LEDS
(DS1 AND DS2)
PRESSURE
SWITCH CIRCUIT
CONNECTIONS
TEST PINS (P1)
Note - Component locations vary by board manufacturer.
SENSOR CONNECTION
(COIL AND AMBIENT
SENSORS)
(P4)
REVERSING VALVE
(O OUT)
DELAY PINS
(P5)
LOW AMBIENT
THERMOSTAT PINS
(P3)
DEFROST TERMINATION
PIN SETTINGS (P1)
Demand Defrost
Control (A108)
FIGURE 14. Demand Defrost Control (A108)
DEMAND DEFROST CONTROL (A108) INPUTS, OUTPUTS AND CONFIGURABLE SETTINGS
Control
Locations
Control Label or
Description
Purpose
Function
P1
50, 70, 90, 100
Defrost Temperature
Termination Shunt (Jumper)
Pins
The demand defrost control (illustrated in figure 17) has selections which
are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The shunt termination
pin is factory-set at 50°F (10°C). If the temperature shunt is not installed,
the default termination temperature is 90°F (32°C).
P2
W1
24VAC Thermostat Input /
Output
24VAC input / output from indoor thermostat to indoor unit.
C
24VAC Common
24VAC common.
L
Thermostat Service Light
Thermostat service light connection.
R
24VAC
24VAC.
Y2
Thermostat Input
Controls the second stage operation of the unit.
O
Thermostat Input
Reversing valve solenoid.
Y1
Thermostat Input
Controls the operation of the unit.
P3
55, 50, 45, 40
Low Ambient Thermostat
Pins
Provides selection of the Y2 compressor lock-in temperature. Valid
options are 40, 45, 50 and 55 degrees Fahrenheit.
P4
DIS-YEL
Coil Sensor
(P4-5) Ground connection for outdoor coil temperature sensor.
(P4-6) Connection for outdoor coil temperature sensor.
AMB-BLACK
Ambient Sensor
(P4-3) Ground connection for outdoor ambient temperature sensor.
(P4-4) Connection for outdoor ambient temperature sensor.
COIL-BROWN
Discharge Sensor
No discharge sensor is used; replaced by 10K resistor.
P5
DELAY
Delay Mode
The demand defrost control has a field-selectable function to reduce
occasional sounds that may occur while the unit is cycling in and out of
the defrost mode. When a jumper is installed on the DELAY pins, the
compressor will be cycled off for 30 seconds going in and out of the
defrost mode. Units are shipped with jumper installed on DELAY pins.
NOTE - The 30-second off cycle is NOT functional when TEST pins on
P1 are jumpered.
P6
TST, PS DF, C, R, O, Y1, Y2
Factory Test Connectors
No field use.
DS1
RED LED
Diagnostic LED
Demand defrost control LEDs may be OFF, ON, or FLASHING to
indicate diagnostic conditions which are described in table 3.
DS2
GREEN LED
FAN
TWO CONNECTORS
Condenser Fan Operation
These two connections provide power for the condenser fan.
O OUT
O OUT
24 VAC output
24 VAC output connection for reversing valve.
LO-PS
LO-PS
Low-Pressure Switch
When the low pressure switch trips, the demand defrost control will cycle
off the compressor, and the strike counter in the demand defrost control
will count one strike. The low pressure switch is ignored under the
following conditions:
during the defrost cycle and 90 seconds after the termination of
defrost
when the average ambient sensor temperature is below 0°F (-18°C)
during 90 seconds following the start of the compressor
during TEST mode.
Y2 OUT
Y2 OUT
24 VAC Output
24 VAC output for second-stage compressor solenoid.
Y1 OUT
Y1 OUT
24 VAC Common Output
24 VAC common output, switched for enabling compressor contactor.
HS-PS
HS-PS
High-Pressure Switch
When the high pressure switch trips, the demand defrost control will cycle
off the compressor, and the strike counter in the demand defrost control
will count one strike.
L
L
Service Light Output
24VAC service light output.
24V
24V
24 Volt output
24VAC typically used to supply power to the Lennox System Operation
Monitor (LSOM). Not used in this system.
This section addresses:
• Emergency Heat
• Defrost System Overview
• Defrost Control Connections, Jumper Settings and Fea-
tures
• Operational Mode Overview (Calibration, Normal and
Defrost)
• Defrost Cycle Actuation
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room
thermostats. This feature is applicable when isolation of
the outdoor unit is required, or when auxiliary electric heat
is staged by outdoor thermostats. When the room thermo-
stat is placed in the emergency heat position, the outdoor
unit control circuit is isolated from power and field-provid-
ed relays bypass the outdoor thermostats. An amber indi-
cating light simultaneously comes on to remind the home-
owner that he is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit
shutdown, but it should also be used following a power
outage if power has been off for over an hour and the out-
door temperature is below 50°F (10°C). System should be
left in the emergency heat mode at least six hours to allow
the crankcase heater sufficient time to prevent compres-
sor slugging.
DEFROST SYSTEM OVERVIEW
The control monitors ambient temperature, outdoor coil
temperature, and total run time to determine when a de-
frost cycle is required. The coil temperature probe is de-
signed with a spring clip to allow mounting to the outside
coil tubing. The location of the coil sensor is important for
proper defrost operation.
NOTE – The demand defrost control accurately measures
the performance of the system as frost accumulates on the
outdoor coil. This typically will translate into longer running
time between defrost cycles as more frost accumulates on
the outdoor coil before the demand defrost control initiates
defrost cycles.
DEFROST CONTROL CONNECTIONS, JUMPERS
SETTINGS AND FEATURES
Defrost Temperature Termination Jumper Settings (P1)
The demand defrost control selections are: 50, 70, 90 and
100°F (10, 21, 32 and 38°C). The shunt termination pin
is factory set at 50°F (10°C). If temperature shunt is not
installed, default termination temperature is 90°F (32°C).
Test Pins (P1) Function
Placing the jumper on the field test pins (P1) allows the
technician to:
• Clear short cycle lockout
• Clear five-strike fault lockout
• Cycle the unit in and out of defrost mode
Place the unit in defrost mode to clear the coil
Compressor Delay Mode (P5)
The demand defrost control has a field-selectable function
to reduce occasional sounds that may occur while the unit
is cycling in and out of the defrost mode. When a jumper
is installed on the DELAY pins, the compressor will be
cycled off for 30 seconds going in and out of the defrost
mode. Units are shipped with jumper installed on DELAY
pins.
NOTE - The 30 second off cycle is NOT functional when
jumpering the TEST pins.
DEMAND DEFROST CONTROL (A108) DIAGNOSTIC LEDS
The state (Off, On, Flashing) of two LEDs on the demand defrost control (DS1 [Red] and DS2 [Green]) indicate diagnostics
conditions that are described in table 4.
TABLE 4
DEMAND DEFROST CONTROL (A108) DIAGNOSTIC LEDS
DS1 and DS2 System Status, Fault and Lockout Codes
DS2
Green
DS1
Red
Type
Condition/Code
Possible Cause(s)
Solution
OFF
OFF
Status
Power problem
No power (24V) to demand defrost
control terminals R and C or demand
defrost control failure.
1.Check control transformer power (24V).
2.If power is available to demand defrost control and
trol.
Simultaneous SLOW
Flash
Status
Normal operation
Unit operating normally or in standby
mode.
None required.
Alternating SLOW
Flash
Status
5-minute anti-short cycle delay
Initial power up, safety trip, end of
room thermostat demand.
None required (jumper TEST pins to override)
Simultaneous
FAST
Flash
Fault
Ambient Sensor Problem
Sensor being detected open or shorted or out of temperature range. Demand defrost control
will revert to time/temperature defrost operation. (System will still heat or cool).
Alternating
FAST Flash
Fault
Coil Sensor Problem
Sensor being detected open or shorted or out of temperature range. Demand defrost control
will not perform demand or time/temperature defrost operation. (System will still heat or cool.)
ON
ON
Fault
Demand Defrost Control Failure
Indicates that demand defrost control has internal component failure. Cycle 24VAC power to
demand defrost control. If code does not clear, replace demand defrost control.
OFF
SLOW
Flash
Fault
Low Pressure Fault
Restricted air flow over indoor or
outdoor coil.
Improper refrigerant charge in
system.
Improper
metering
device
installed or incorrect operation
of metering device.
Incorrect or improper sensor
location
or
connection
to
system.
Remove any blockages or restrictions from coils
and/or fans. Check indoor and outdoor fan
motor for proper current draws.
Check system charge using subcooling
method.
Check system operating pressures and
compare to unit subcooling tables in this
instruction or located on unit access panel.
Make sure all pressure switches and sensors
have secure connections to system to prevent
refrigerant leaks or errors in pressure and
temperature measurements.
OFF
ON
Lockout
Low Pressure Lockout
SLOW
Flash
OFF
Fault
High Pressure Fault
ON
OFF
Lockout
High Pressure Lockout
SLOW
Flash
ON
Fault
Discharge Line Temperature Fault
This code detects shorted sensor or high discharge temperatures. If the discharge line
temperature exceeds a temperature of 285ºF (140ºC) during compressor operation, the
demand defrost control will de-energize the compressor contactor output (and the defrost
output if active). The compressor will remain off until the discharge temperature has dropped
below 225ºF (107ºC).
sh
ON
Lockout
Discharge Line Temperature
Lockout
OFF
Fast
Flash
Fault
Discharge Sensor Fault
The demand defrost control detects open sensor or out of temperature sensor range. This fault
is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the
sensor resistance is not within range after 90 seconds, the demand defrost control will count
one fault. After 5 faults, the demand defrost control will lock out.
Fast
Flash
OFF
Lockout
Discharge Sensor Lockout
(Each fault adds 1 strike to that code's counter; 5 strikes per code = LOCKOUT)
Field Operation Checklist for Two-Stage Modulation Compressors
Unit Readings
Y1 - First‐Stage
Expected results during Y2 demand
(Toggle switch On)
Y2 - Second‐Stage
Compressor
Voltage
Same
Amperage
Higher
Outdoor Unit Fan Motor
Amperage
Same or Higher
Temperature
Ambient
Same
Outdoor Coil Discharge Air
Higher
Compressor Discharge Line
Higher
Indoor Return Air
Same
Indoor Coil Discharge Air
Lower
Pressures
Suction (Vapor)
Lower
Liquid
Higher
4 - Check all wiring for loose connections.
5 - Check for correct voltage at unit (unit operating).
6 - Check amp draw on outdoor fan motor.
Motor Nameplate:_________ Actual:__________.
7 - Inspect drain holes in coil compartment base and
clean if necessary.
NOTE – If insufficient heating or cooling occurs, the
unit should be gauged and refrigerant charge should be
checked.
Outdoor Coil
It may be necessary to flush the outdoor coil more fre-
quently if it is exposed to substances which are corrosive
or which block airflow across the coil (e.g., pet urine, cot-
tonwood seeds, fertilizers, fluids that may contain high
levels of corrosive chemicals such as salts)
• Outdoor Coil – The outdoor coil may be flushed with a
water hose.
• Outdoor Coil (Sea Coast) – Moist air in ocean locations
can carry salt, which is corrosive to most metal. Units
that are located near the ocean require frequent in-
spections and maintenance. These inspections will de-
termine the necessary need to wash the unit including
the outdoor coil. Consult your installing contractor for
proper intervals/procedures for your geographic area or
service contract.
Indoor Unit
1. Clean or change filters.
2. Lennox blower motors are prelubricated and perma-
nently sealed. No more lubrication is needed.
3. Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.
4. Belt Drive Blowers - Check belt for wear and proper
tension.
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor.
Motor Nameplate:_________ Actual:__________.
Indoor Coil
1 - Clean coil if necessary.
2 - Check connecting lines, joints and coil for evidence
of oil leaks.
3 - Check condensate line and clean if necessary.
HOMEOWNER
Cleaning of the outdoor unit's coil should be performed by
a trained service technician. Contact your dealer and set
up a schedule (preferably twice a year, but at least once a
year) to inspect and service your outdoor unit. The follow-
ing maintenance may be performed by the homeowner.
IMPORTANT
After testing has been completed, properly reposition
test jumper across desired timing pins
Maintenance
DEALER
WARNING
Electric Shock Hazard. Can cause injury or
death. Unit must be properly grounded in
accordance with national and local codes.
Line voltage is present at all components
when unit is not in operation on units with
single-pole contactors. Disconnect all remote
electric power supplies before opening
access panel. Unit may have multiple power
supplies.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or
equivalent, service agency, or the gas supplier.
NOTICE !
Failure to follow instructions will cause damage to
the unit.
This unit is equipped with an aluminum coil.
Aluminum coils may be damaged by exposure to
solutions with a pH below 5 or above 9. The alumi-
num coil should be cleaned using potable water
at a moderate pressure (less than 50psi). If the
coil cannot be cleaned using water alone, Lennox
recommends use of a coil cleaner with a pH in the
range of 5 to 9. The coil must be rinsed thoroughly
after cleaning.
In coastal areas, the coil should be cleaned with
potable water several times per year to avoid corro-
sive buildup (salt).
Maintenance and service must be performed by a quali-
fied installer or service agency. At the beginning of each
cooling season, the system should be checked as follows:
Outdoor Unit
1 - Clean and inspect outdoor coil (may be flushed with
a water hose). Ensure power is off before cleaning.
2 - Outdoor unit fan motor is pre-lubricated and sealed.
No further lubrication is needed.
3 - Visually inspect all connecting lines, joints and coils
for evidence of oil leaks.
Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure
of the unit to treated water (i.e., sprinkler systems,
soakers, waste water, etc.) will corrode the surface of
the steel and aluminum parts, diminish performance
and affect longevity of the unit.
Outdoor Coil
The outdoor unit must be properly maintained to ensure
its proper operation.
• Please contact your dealer to schedule proper inspec-
tion and maintenance for your equipment.
• Make sure no obstructions restrict airflow to the outdoor unit.
• Grass clippings, leaves, or shrubs crowding the unit can
cause the unit to work harder and use more energy.
• Keep shrubbery trimmed away from the unit and peri-
odically check for debris which collects around the unit.
Routine Maintenance
In order to ensure peak performance, your system must
be properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
1 - Air Filter – Ask your Lennox dealer to show you
where your indoor unit's filter is located. It will be
either at the indoor unit (installed internal or external
to the cabinet) or behind a return air grille in the wall
or ceiling. Check the filter monthly and clean or
replace it as needed.
2 - Disposable Filter – Disposable filters should be
replaced with a filter of the same type and size.
NOTE – If you are unsure about the filter required for your
system, call your Lennox dealer for assistance.
3 - Reusable Filter – Many indoor units are equipped
with reusable foam filters. Clean foam filters with
a mild soap and water solution; rinse thoroughly;
allow filter to dry completely before returning it to
the unit or grille.
NOTE – The filter and all access panels must be in place
any time the unit is in operation.
4 - Electronic Air Cleaner – Some systems are
equipped with an electronic air cleaner, designed
to remove airborne particles from the air passing
through the cleaner. If your system is so equipped,
ask your dealer for maintenance instructions.
5 - Indoor Unit – The indoor unit's evaporator coil is
equipped with a drain pan to collect condensate
formed as your system removes humidity from the
inside air. Have your dealer show you the location
of the drain line and how to check for obstructions.
(This would also apply to an auxiliary drain, if
installed.)
Thermostat Operation
See the thermostat homeowner manual for instructions on
how to operate your thermostat.
Heat Pump Operation
Your new Lennox heat pump has several characteristics
that you should be aware of:
• Heat pumps satisfy heating demand by delivering large
amounts of warm air into the living space. This is quite
different from gas- or oil-fired furnaces or an electric fur-
nace which deliver lower volumes of considerably hotter
air to heat the space.
• Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor coil
during the heating cycle when temperatures are below
45°F (7°C). An electronic control activates a defrost cy-
cle lasting 5 to 15 minutes at preset intervals to clear the
outdoor coil of the frost.
• During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The
thermostat may engage auxiliary heat during the defrost
cycle to satisfy a heating demand; however, the unit will
return to normal operation at the conclusion of the de-
frost cycle.
Extended Power Outage
The heat pump is equipped with a compressor crankcase
heater which protects the compressor from refrigerant
slugging during cold weather operation.
If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the EMER-
GENCY HEAT setting to obtain temporary heat without
the risk of serious damage to the heat pump.
In EMERGENCY HEAT mode, all heating demand is sat-
isfied by auxiliary heat; heat pump operation is locked out.
After a six-hour compressor crankcase warm-up period,
the thermostat can be switched to the HEAT setting and
normal heat pump operation may resume.
Preservice Check
If your system fails to operate, check the following before
calling for service:
• Verify room thermostat settings are correct.
• Verify that all electrical disconnect switches are ON.
• Check for any blown fuses or tripped circuit breakers.
• Verify unit access panels are in place.
• Verify air filter is clean.
• If service is needed, locate and write down the unit
model number and have it handy before calling.
Accessories
For update-to-date information, see any of the following
publications:
• Lennox ML16XP1 Product Specification bulletin
• Lennox Product Catalog
• Lennox Price Book
ML16XP1 OPERATING SEQUENCE
This is the sequence of operation for ML16XP1 series
units. The sequence is outlined by numbered steps which
correspond to circled numbers on the adjacent diagram.
The steps are identical for both cooling and first stage
heating demand with the exception reversing valve L1
is energized during cooling demand and de-energized
during heating demand.
NOTE – Transformer in indoor unit supplies power (24
VAC) to the thermostat and outdoor unit controls.
COOLING:
Internal thermostat wiring energizes terminal O by cooling
mode selection, energizing the reversing valve L1.
1 - Demand initiates at Y1 in the thermostat.
2 - 24VAC energizes compressor contactor K1.
3 - K1-1 N.O. closes, energizing compressor (B1) and
outdoor fan motor (B4).
END OF COOLING DEMAND:
4 - Demand is satisfied. Terminal Y1 is de-energized.
5 - Compressor contactor K1 is de-energized.
6 - K1-1 opens and compressor (B1) and outdoor fan
motor (B4) are de-energized and stop immediately.
FIRST STAGE HEAT:
Internal thermostat wiring de-energizes terminal O by
heating mode selection, de-energizing the reversing valve
L1.
See steps 1, 2 and 3.
End of FIRST STAGE HEAT:
See steps 4, 5 and 6.
DEFROST MODE:
When a defrost cycle is initiated, the control energizes
the reversing valve solenoid and turns off the condenser
fan. The control will also put 24VAC on the “W1” (auxil-
iary heat) line. The unit will stay in this mode until either
the coil sensor temperature is above the selected termi-
nation temperature, the defrost time of 14 minutes has
been completed, or the room thermostat demand cycle
has been satisfied. (If the temperature select shunt is not
installed, the default termination temperature will be 90°F.)
If the room thermostat demand cycle terminates the cycle,
the defrost cycle will be held until the next room thermo-
stat demand cycle. If the coil sensor temperature is still
below the selected termination temperature, the control
will continue the defrost cycle until the cycle is terminated
in one of the methods mentioned above. If a defrost is ter-
minated by time and the coil temperature did not remain
above 35°F (2°C) for 4 minutes the control will go to the
30-minute Time/Temperature mode.
Servicing Units Void of Charge
If the outdoor unit is void of refrigerant, clean the system
using the procedure described below.
1 - Leak check system using procedure outlined on
page 17.
2 - Evacuate the system using procedure outlined on
page 18.
3 - Use nitrogen to break the vacuum and install a new
filter drier in the system.
4 - Evacuate the system again using procedure
outlined on page 18.
5 - Weigh in refrigerant.
Start-Up
IMPORTANT
If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start-up to prevent
compressor damage as a result of slugging.
1 - Rotate fan to check for binding.
2 - Inspect all factory and field-installed wiring for loose
connections.
3 - After evacuation is complete, open the liquid line
and suction line service valves to release the
refrigerant charge (contained in outdoor unit) into
the system.
4 - Replace the stem caps and tighten as specified in
Operating Service Valves on page 7.
5 - Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit's
nameplate. If not, do not start the equipment until
you have consulted with the power company and
the voltage condition has been corrected.
6 - Set the thermostat for a cooling demand. Turn
on power to the indoor indoor unit and close the
outdoor unit disconnect switch to start the unit.
7 - Recheck voltage while the unit is running. Power
must be within range shown on the nameplate.
8 - Check system for sufficient refrigerate by using
the procedures listed under Start-Up and Charging
Procedures.
9 - Recheck voltage while the unit is running. Power
must be within range shown on the nameplate.
Start-Up and Performance Checklist
Job Name
Job no.
Date
Job Location
City
State
Installer
City
State
Unit Model No.
Serial No.
Service Technician
Nameplate Voltage
Rated Load Ampacity
Compressor
Outdoor Fan
Maximum Fuse or Circuit Breaker
Electrical Connections Tight?
Indoor Filter clean?
Supply Voltage (Unit Off)
Indoor Blower RPM
S.P. Drop Over Indoor (Dry)
Outdoor Coil Entering Air Temp.
Discharge Pressure
Vapor Pressure
Refrigerant Charge Checked?
Refrigerant Lines:
Leak Checked?
Properly Insulated?
Outdoor Fan Checked?
Service Valves:
Fully Opened?
Caps Tight?
Thermostat
Voltage With Compressor Operating
Calibrated?
Properly Set?
Level?