No. CP-SS-1896E
BC-R35 Series
Burner Controllers
Summary
BC-R35 Series burner controllers are combustion safety
controllers specifically designed for batch operation
(systems which start and stop at least once within 24 hours). They
ensure safety by automatically controlling the ignition,
combustion monitoring, and fuel shutoff of oil and gas
burners with proportional control. They are also equipped with
a 7-segment display that can be used in maintenance, a trial
operation mode that is convenient for trial-run operation
and adjustment, and other features.
Add i t iona l l y, t he BC - R35 i s equ ipped w i t h host
communications (RS-485) and Smart Loader Package
functions, allowing troubleshooting and more detailed
observation of status.
Features
Compliant with JIS standards
• Safe construction of combustion systems and equipment
- Pre-purge and ignition timing in compliance with JIS B
8407:2012 (forced-air burners) and JIS B 8415:2008
(combustion equipment in compliance with the safety
principles for industrial incinerators).
- POC (proof of closure), based on shutoff valve closure
confirmation switch input
• JIS-compliant burner controller safety design
- Safety design in compliance with JIS C 9730 (automatic
electrical controls for household and similar use)
- EN 298 compliance (certification pending)
Easy mounting and replacement
• DIN rail mounting
- Easily mountable in the same way as other control
devices and control relays
• Uses sub-base structure
- Structure separates the sub-base from the main unit It is
possible to change only the main unit, leaving the wired-in
sub-base in place
Precautions on equipment instrumentation
Extensive communications with external devices
• Equipped with a 7-segment display
- 7-segment display for sequence codes and warning
codes
- Press the DISP switch to display the flame voltage.
• External status output
- States such as ignition failure, flame failure, and
combustion detected are output digitally (and used as
panel displays)
• Warning reset by contact input
• Equipped with a trial-run operation mode
- The control motor can be forced to full open and full closed
outputs to adjust the high and low fire positions and check
the airflow volume
• Equipped with host communications (RS-485), allowing
remote observation of status
• Status checking by the Smart Loader Package
(1) The equipment used in the combustion safety system was designed with careful consideration of laws, standards, safety guidelines, and
the like. If the system is designed to a foreign specification, refer to laws and standards in the relevant country.
Main Safety Policies in Japan
- Technical policy on Safety Standards for Combustion Equipment in Industrial Furnaces: Ministry of Health, Labour and Welfare
- Combustion equipment in compliance with the safety principles for industrial incinerators - JIS B 8415
- Forced Draught Burners - Part 1: Gas Burners - JIS B 8407-1
- Forced Draught Burners - Part 2: Oil Burners - JIS B 8407-2
- The index of safety technology of industrial gas combustion equipment: Japan Gas Association
- Index of safety technology of gas boiler combustion facilities: Japan Gas Association
(2) This device monitors for failures in the relay contacts used for combustion load (IG, PV, MV) output. An E09 error is output if a voltage
occurs at a load terminal, due to a ground fault or wiring error, when this device is not outputting a load. If an E09 error occurs when this
device is installed, recheck the wiring and eliminate the factors causing the error.
(3) If the wiring from this device exceeds the recommended length, prevent malfunction due to the effects of external noise by running wires
from the control panel to the casing through a conduit, keeping a distance between power lines and input lines, and other measures.
Check the operation of the system on installation.
(4) A reset signal must always be input near the equipment (burner, etc.), not remotely.
If a reset is input while it is not possible to confirm safety, there is the risk of explosion.
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
Specifications
Item
Description
Application
Batch-operated combustion systems burning gas, oil, or gas/oil mixture
Compatible flame detector
AUD100/ 100/ 120 series UV sensor, flame rod
AFD100/110 series visible light flame detector , contact input
Sequence
Sequence timing
Pre-purge
Ignition
standby
Pilot ignition
(main ignition) *1
Pilot only (Hi sole-
noid valve ignition
standby) *1
Main ignition (Hi
solenoid valve
ignition) *1
Main burner
stabilization
Low fire
shutdown
Postpurge
35 s, 45 s, 60 s, 3
min (select
by model
number)
*2
7.5±1 s
4.5±0.5 s
8.5±1 s
4.5±0.5 s
8.5±1 s
45 s max.
20±2 s
Flame response
AUD100/110/120 series UV
sensor
Flame rod
AFD series visible
light flame
detector
Contact input
2 s max (nominally 1.5 s)
(when flame voltage is 3 V)
2 s max (nominally 1.5 s)
(when flame voltage is 2 V)
2 s max (nominally 1.5 s)
(20 lx -> 0 lx)
1 s max (nominally 0.8 s)
(
3 s max. when combined with AUR300
)
series controller (with flame response 2s
max.) for continuous operation
Reset timing
1 s or longer (main unit reset switch or contact reset input) *4
Warning detection
timing
False flame
Airflow
switch
error 1
Airflow
switch
error 2
Interlock
error
Low fire
interlock
error 1
Low fire
interlock
error 2
High fire
interlock
error
POC
(shutoff
valve
closure
check) error
5 s
1 s max.
180 s
1 s
1 s max.
180 s
180 s
3 s
Airflow switch
monitoring
Yes (checks for switch error #1, error #2)
Ignition failure
Lockout
Flameout
Lockout
Low fire shutdown *3
After confirming low combustion position when stopped, moves to postpurge (selected according to model).
Electrical
specifications
Rated power
supply voltage
AUD100/110/120 series UV
sensor
Flame rod
AFD series visible light
flame detector
Contact input
100 Vac, 200 Vac, or 220 Vac, 50/60 Hz
100 to 230 Vac, 50/60 Hz
Allowable power supply
voltage
85 to 110 % of rated power supply
Power consumption
10 W or less
Voltage resistance
1,500 Vac for 1 min, or 1,800 Vac for 1s
Between each terminal and ground, except for combustion sensor connection terminals (terminals 14, 15)
Insulation resistance
At least 50 MΩ, 500 Vdc megger
Between each terminal and ground, except for combustion sensor connection terminals (terminals 13, 14)
Contact rating
Blower
motor
(electromag-
netic breaker)
Ignition
transformer
Pilot valve
(main valve Lo solenoid
valve) *1
Main valve
(main valve Hi solenoid
valve) *1
Warning
Control motor open
output,
close output,
proportional output
100 VA
300 VA
200 VA
200 VA
75 VA
200 VA
Monitor outputs
4, maximum 30mA each
Combustion detection
level
AUD100/110/120 series UV
sensor
Flame rod
AFD100/110 series visible
light flame detector
Contact input
When ignition is detected:
1.5 to 4.5 Vdc
When extinction is detected:
0.2 to 0.6 Vdc
When ignition is detected:
1.5 to 4.5 Vdc
When extinction is detected:
0.0 to 0.2 Vdc
When ignition is detected:
1.3 Vdc or less
When extinction is detected:
0.5 Vdc or more
When ignition is detected:
Short between F and G
When flame is not detected:
Open between F and G
Flame voltage
output
Recommended flame volt-
age: must be stable at
2 Vdc or above
Flame voltage output range:
0.2 to 4.5 Vdc
Recommended flame volt-
age: must be stable at
2 Vdc or above
Flame voltage output range:
0.0 to 4.5 Vdc
Flame voltage output range:
0.2 to 4.8 Vdc
When ignition is detected:
4.0 Vdc or more
When flame is not detected:
0.5 Vdc or less
Input
Start input, lockout interlock input, contact reset input, airflow switch input, POC (shutoff valve closure check) input, high fire interlock, low fire
interlock
* Each input is a non-voltage contact input, with allowable contact resistance up to 500 Ω
Lifespan
10 years when used for eight hours per day, or 100,000 start/stop cycles (at 25 °C, room temperature, rated voltage)
Host com-
munication
specifications
Communications
standard
RS-485
Transmission route
3-wire system
Transmission speed
4800, 9600, 19200 bps
Transmission distance
Max. 500 m
Communication method
Semi-duplex
Synchronization method
Asynchronous
Data format
8 data bits, 1 stop bit, even parity, odd parity 8 data
bits, 2 stop bits, even parity, odd parity
Device address
1 to 32
Connection method
1: N (max. 15 units)
Miscellaneous
Based on RS-485
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
*1 Item in ( ) is for the case of direct ignition.
*2 Visible light flame detector and contact input are 35s only.
*3 Visible light flame detector and contact input model do not have the low fire shutdown function.
*4 During postpurge after a warning, no reset input is accepted until postpurge is complete.
Also, reset input is not accepted if no warning has occurred.
Transporta- tion
and stor- age
condi- tions
Ambient tempera- ture
-20 to +70°C
Ambient humidity
5 to 95 % RH (no condensation)
Vibration
0 to 9.8 m/s2 (10 to 150 Hz, 1 octave/minute, 10 cycles, in each of XYZ directions)
Shock
0 to 300 m/s2
Packaged drop test
60 cm drop height (free drop onto 1 corner, 3 edges, 6 sides)
Operating
conditions
Ambient tempera- ture
-20 to +60 °C
Ambient humidity
10 to 90 % RH (no condensation)
Vibration
0 to 3.2 m/s2 (10~150Hz, 1 octave/minute, 10 cycles, in each of XYZ directions)
Shock
0 to 9.8 m/s2
Mounting angle
Reference plane +/-10 °
Dust
0.3 mg/m3 or less
General
specifications
Protective structure
IP40 (with a sideboard ( 81447515-001) attached to the sub-base (BC-R05)) IP10 (sub-base
(BC-R05) only)
Excess voltage cat-
egory
II
Pollution degree
PD2
Case color
Black
Case material
Denatured PPE resin (UL94-V0 PTI materials group IIIa)
Structure
Sub-base and main unit
Mounted
orientation
Vertical or horizontal
However, in horizontal mounting the 7-segment display must face directly upward (DIN rail
mounting or direct mounting through base screw holes)
Standards
JIS C 9730-2-5
EN 298 (0063BS1427)
Dimensions
W95 × H105 × D110 mm
Weight
Approximately 600 g (incl. sub-base)
Wiring types and max. wiring length
- Start, airflow switch, lockout interlock, POC (shutoff valve proof of closure), low fire interlock, high fire interlock Copper IV wire
with 600 V vinyl insulation, 1.25 mm2, recommended condition: 20 m or less,
maximum wiring length: 100 m
- Contact reset
Copper IV wire with 600 V vinyl insulation, 1.25 mm2, maximum wiring length: 10 m
- AUD100/110/120 (F, G)
Copper IV wire with 600 V vinyl insulation, 1.25 mm2, maximum wiring length: 100 m
- Flame rod (F, G)
RG-11U (JAN standard: US DoD compliant specification) or equivalent, 5C2V, 7C2V (JIS standard) Recommended condition: 20 m
or less, maximum wiring length: 30 m
- AUD100/110 (F, G)
Copper IV wire with 600 V vinyl insulation, 1.25 mm2, maximum wiring length: 10 m
- RS-485 communications (3-wire system)
0.2 to 1.5 mm2 shielded, twisted pair cable (recommended) Maximum wiring length: 500 m
- Signal line for flame voltage output
IV wire, 0.75 mm2 or larger, max. wiring length 10 m
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
Model number composition
(Note: The dedicated sub-base and sideboard are not provided with the BC-R35 controller. Order them separately.)
Flame detector: Flame rod / UV sensor (AUD100/110)
Example: BC-R35B1G0500
I
II
III
IV
V
VI
VII
Description
Base
model
number
Commu-
nications
function
Flame
detector
Power
supply
Function
code
Timing
code
Addition-
al func-
tions
BC-R
Burner Controller
35
RS-485, with Smart Loader Package function
B
Flame rod (Ionization)
C
UV sensor (AUD100/110/120)
1
100 Vac
2
200 Vac
6
220 Vac
G
Interrupted pilot type, No low fire stop
J
Interrupted pilot type, Low fire stop available
L
Direct ignition type, No low fire stop
N
Direct ignition type, Low fire stop available
050
Pre-purge time 35 s
086
Pre-purge time 45 s
122
Pre-purge time 60 s
158
Pre-purge time 3 min
0
None
D
With inspection record (with data)
Flame detector: Visible light flame detector AFD100/110 series
I
II
III
IV
V
VI
VII
Example: BC-R35A7G0500
I
II
III
IV
V
VI
VII
Description
Base
model
number
Commu-
nications
function
Flame
detector
Power
supply
Function
code
Timing
code
Addition-
al func-
tions
BC-R
Burner Controller
35
RS-485, with Smart Loader Package function
A
Visible light flame detector
7
100-230 Vac
G
Interrupted pilot type , No low fire stop)
L
Direct ignition type, No low fire stop
050
Pre-purge time 35 s
0
None
D
With inspection record (with data)
Flame detector: Contact input
Example: BC-R35F7G0490
I
II
III
IV
V
VI
VII
Description
Base
model
number
Commu-
nications
function
Flame
detector
Power
supply
Function
code
Timing
code
Addition-
al func-
tions
BC-R
Burner Controller
35
RS-485, with Smart Loader Package function
F
Contact input
7
100-230 Vac
G
Interrupted pilot type, No low fire stop
L
Direct ignition type, No low fire stop
049
Pre-purge time 35 s
Flame failure response timing 1 s max
121
Pre-purge time 60 s
Flame failure response timing 1 s max
0
None
D
With inspection record (with data)
I
II
III
IV
V
VI
VII
I
II
III
IV
V
VI
VII
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
Compatible flame detector (sold separately)
UV sensor
Model number
Name
Notes
AUD15C1000
Advanced UV sensor
tube unit
Use a dedicated socket for the AUD100C/110C/120C
AUD100C100_
Dedicated socket for the AUD15
Lead wire type
AUD15C1000, sold separately
AUD100C1000-A15
AUD15C1000 in package
AUD110C100_
Dedicated socket for the AUD15
Terminal board type
AUD15C1000, sold separately
AUD110C1000-A15
AUD15C1000 in package
AUD120C120_
Dedicated socket for the AUD15
1/2-inch mounting type
Without G1/2 adapter, AUD15C1000, sold separately
AUD120C121_
With G1/2 adapter, AUD15C1000, sold separately
_: 0: standard product, D with inspection record (with data), T tropicalization treatment (AUD110C only), B with inspection record (with data) + tropicalization treatment (AUD110C only)
Flame rod
Model number
Name
Notes
C7007A
Flame rod holder
Discontinued
C7008A
Flame rod assembly
Discontinued
Visible light flame detector
Model number
Name
Notes
AFD100A0700
Visible light flame detector
Light reception direction: front, top-view type
AFD100B0700
Light reception direction: side, side-view type
AFD110A0000
G3/4-inch flange mounting type
Options (sold separately)
Model number
Product name
Notes
BC-R05A100
Dedicated sub-base for BC-R
Required for all products in the BC-R35 series
81447514-001
Connector for front wiring
Weidmueller model number : BL3.5/11F, compatible wire: 0.2-1.5mm2(AWG28-14)
81447514-002
Connector for front wiring (For
right-side wiring)
Weidmueller model number : BL3.5/11/270F, compatible wire: 0.2-1.5mm2(AWG28-14)
81447515-001
Sideboards
Contains two. Not included in the sub-base.
SLP-BCRJ71
Smart Loader Package
(No cable)
81441177-001
USB loader cable
FSP136A100
Analog flame meter
81447519-001
Jack cover
(Included with the controller.)
81447531-001
Front connector cover
Packaged with mounting screws (Included with the controller.)
81447596-001
R4780/R4715-compatible mounting
plate
For use when replacing R4715, R4780, R440H, R4751, or R4781
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
Terminal numbers, front panel item names
Front
Display
Sub-base (sold separately)
Reset switch *2
Display switch
Front connector cover
(connector is behind cover)
Loader jack
DIN rail clamp
Terminal board
Terminal numbers
Front terminals
Sub-base terminals
No.
Function
No.
Function
25
Flame voltage output (+)
31
Power supply for moni- tor
output
26
Flame voltage output (-)
32
Monitor output, combus-
tion
27
Host communications
(RS-485) DA
33
Monitor output, ignition
failure
28
Host communications
(RS-485) DB
34
Monitor output, flame failure
29
Host communications
(RS-485) SG
35
Monitor output, lockout
interlock input
30
NC
*1 After lockout is released, even if the start input is ON, the unit will not start
for 5 seconds to ensure operation stability.
*2 During postpurge, reset is disabled for 20 seconds.
Connector for front wiring
(81447514-001) terminal layout
Connector for front wiring (for right side wiring)
(81447514-002) terminal layout
Mounting screw
25
Mounting screw
25
Wiring fastener
screw
Wiring
35
Mounting screw
Wiring fastener
screw
Mounting screw
Wiring
35
No.
Function
No.
Function
1
Output for the blower
motor (electromagnetic
breaker)
13
Warning output
2
AC power supply (L1)
14
Flame detector (F)
3
AC power supply (L2 (N))
15
Flame detector (G)
4
Output common 1
16
Input common 1
5
Output common 2
17
Input common 2
6
Ignition transformer
output
18
Low fire interlock input
7
Pilot valve output
19
High fire interlock input
8
Main valve output
20
Start input *1
9
Control motor output
common
21
Airflow switch input
10
Control motor propor-
tional output
22
Lockout interlock input
11
Control motor open
output
23
POC (shutoff valve clo-
sure check) input
12
Control motor closed
output
24
Contact reset input *2
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
7-segment display, LED display, switches
If this device detects a flame failure etc., it isolates the load and applies a lockout. During lockout, the relevant diagnostic function code
is displayed on the 7-segment display.
Part Name
7-segment LED (green)
When normal: sequence code/ flame voltage
When an error occurs: Warning code/ flame voltage
Switch
Flame voltage/ sequence code Flame
voltage/ warning code display switch
Flame LED (green)
Lit when flame signal is detected. Off
when flame signal is off.
Loader jack
POC function selection Communications jack
for dedicated SLP
BC-R main unit fastening screw
BC-R main unit fastening screw
Reset switch
Switch to cancel lockout
(Press and hold for approximately 1s)
ALARM LED (red)
Lit during lockout.
Off when there is no lockout.
Front connector
Flame voltage output (0-5V)
Monitor output (semiconductor relay output) Host
communications (RS-485)
Warning codes
Display
Name
Content
Interlock error
Lockout interlock
1
False flame
Combustion signal was detected for 5s during start check and pre-purge
Airflow switch error 1
The airflow switch turned Off during combustion
Airflow switch error 2
The airflow switch stayed On for 3 minutes during start check
The airflow switch stayed off for 3 minutes during pre-purge
High fire interlock error
During pre-purge, no high fire interlock input was detected for three minutes after high fire position
output.
Low fire interlock error 1
The low fire interlock turned off between pilot ignition and main stabilization
Low fire interlock error 2
The low fire interlock remained Off for three minutes during ignition standby
Ignition failure
Ignition could not be detected with pilot ignition (interrupted pilot type)
Ignition could not be detected with main trial (direct ignition type)
7
Flame failure
The flame signal disappeared in the sequence after pilot ignition (interrupted pilot type)
The flame signal disappeared in the sequence after main trial (direct ignition type)
8
POC (shutoff valve proof of
closure) error*
The shutoff valve closure check switch was detected to be Off (open) when the main valve was closed
The shutoff valve closure check switch was detected to be On (closed) when the main valve was open
+
Sub-code (2 digits)
Device error
Voltage error detected in output from the ignition transformer, pilot valve, or main valve, etc.
*
Replace the burner controller, and if there is a warning code E8, POC may have been set by the equipment manufacturer as disabled.
Sequence codes
• Interrupted pilot type
• Direct ignition type
Examples of sequence codes and warning codes
• Warning code: E0 to E8
• Alarm code: E9 + sub-code (2 digits)
Switches every 0.8s
Switches every 0.8s
Display
Status content
P 1
Start check
Pre-purge
Ignition standby
Main ignition
Hi solenoid valve ignition standby
Hi solenoid valve ignition
P7
Main stabilization
P8
Steady combustion
PL
Low fire shutdown
Postpurge
--
Stop
Display
Status content
P 1
Start check
Pre-purge
Ignition standby
Pilot ignition
Pilot only
Main ignition
P7
Main stabilization
P8
Steady combustion
PL
Low fire shutdown
Postpurge
--
Stop
(Sub-code)
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
Internal block circuit, external connection terminals (1-24 on sub-base, 25-35 on front connector)
Interrupted pilot type (excluding the BC-R35F)
Direct ignition type
Note: - Use contact reset (terminal 24) input in isolation. It cannot be used in conjunction with other BC-R contact reset inputs.
- Output common (terminals 4, 5) and input common (terminal 16, 17) cannot be used in conjunction with other BC-R contact reset inputs.
- Host communications (RS-485) and Smart Loader Package compatibility are only available on the BC-R35.
*1 Content in ( ) describes the situation when three-position (Off-Lo-Hi) control is used. If other than three-position control is used, connect to main valve
(terminal 7).
*2 See Page 9 for the wiring for using a proportional controller and ECM3000E.
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
For compliance with the standard on remote control of boilers (Standards circular No. 0331001) when using the BC-
R35F
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
External Dimensions
• BC-R35 Burner Controller
(Unit: mm)
BC-R main unit fastening screw
Model number
A
81447514-001
10.6
81447514-002
14.6
• Sub-base BC-R05A100 (sold separately)
61
Sub-base (sold separately)
95
110
Connector for
front wiring
Sub-base (sold separately)
BC-R main unit fastening screw
A
DIN rail clamp
64
M3.5 (terminal screw)
ø12 knockout hole
ø12 knockout hole
Sub-base mounting hole
Sub-base mounting hole
95
62.5
DIN rail clamp
61
Knockout hole
16
Knockout hole
27
105
17
27
17
105
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
• Sideboard 81447515-001 (sold separately)
(Unit: mm)
30.7
Sub-base
Sub-base
ø19 knockout hole
Sideboard
Sideboard
ø19 knockout hole
23.9
46.6
73.5
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
BC-R
Main unit
BC-R
Main unit
BC-R
Main unit
Installation orientation
Install the device in the orientation shown below.
Display area
OK
OK
Do not install it in the orientations illustrated below.
Mounting in a Panel
[1] Screw two M4 screws into the panel.
[2] Use the screws to mount the sub-base on the panel.
(Maximum tightening torque: 1.2 N·m)
(Unit: mm)
M4
62.5
(2 locations)
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
Operation Sequence
About the sequence except Normal Operation, please watch "BC-R35 User's manual No. CP-SP-1389E".
1-1. Normal operation (interrupted pilot type, without low fire shutdown)
[7-segment display]
--
P1
P2
P3
P4
P5
P6
P7
P8
P9
--
Input
Power supply
Start input
Airflow switch
POC (shutoff valve closure check)
Lockout interlock
High fire interlock
Low fire interlock
Combustion signal
Reset
Output
Blower motor (electromagnetic breaker)
Ignition transformer
Pilot valve
Main valve
Warning output
Control motor open
Control motor closed
Control motor proportional
Monitor output
Combustion
Flameout
No ignition
Lockout interlock
Start check time
Approximately 2 s
Pre-purge time
Ignition standby time
Main stabilization time Main
ignition time
Postpurge time
Pilot ignition time
Pilot only time
1-2. Normal operation (interrupted pilot type with low fire shutdown)
[7-segment display]
--
P1
P2
P3
P4
P5
P6
P7
P8
PL
P9
--
Input
Power supply
Start input
Airflow switch
POC (shutoff valve closure check)
Lockout interlock
High fire interlock
Low fire interlock
Combustion signal
Reset
Output
Blower motor (electromagnetic breaker)
Ignition transformer
Pilot valve
Main valve
Warning output
Control motor open
Control motor closed
Control motor proportional
Monitor output
Combustion
Flameout
No ignition
Lockout interlock
Start check time
Pre-purge time
Ignition standby time
Main stabilization time Main
ignition time
Postpurge time Low
fire shutdown
Approximately 2 s
Pilot ignition time Pilot only time
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
1-3. Normal operation (direct ignition type without low fire shutdown)
[7-segment display]
--
P1
P2
P3
P4
P5
P6
P7
P8
P9
--
Input
Power supply
Start input
Airflow switch
POC (shutoff valve closure check)
Lockout interlock
High fire interlock
Low fire interlock
Combustion signal
Reset
Output
Blower motor (electromagnetic breaker)
Ignition transformer
Main valve (Lo solenoid valve)*
Main valve (Hi solenoid valve)*
Warning output
Control motor open
Control motor closed
Control motor proportional
Monitor output
Combustion
Flameout
No ignition
Lockout interlock
Start check time
Approximately 2 s
Pre-purge time
Ignition standby time
Main stabilization time Hi
solenoid valve ignition time
Postpurge time
Main ignition time
Hi solenoid valve ignition standby time
*
Content in ( ) describes the situation when three-position (Off-Lo-Hi) control is used.
If other than three-position control is used, only look at the main valve (Lo solenoid valve)
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
1-4. Normal operation (direct ignition type with low fire shutdown)
[7-segment display]
--
P1
P2
P3
P4
P5
P6
P7
P8
PL
P9
--
Input
Power supply
Start input
Airflow switch
POC (shutoff valve closure check)
Lockout interlock
High fire interlock
Low fire interlock
Combustion signal
Reset
Output
Blower motor (electromagnetic breaker)
Ignition transformer
Main valve (Lo solenoid valve)*
Main valve (Hi solenoid valve)*
Warning output
Control motor open
Control motor closed
Control motor proportional
Monitor output
Combustion
Flameout
No ignition
Lockout interlock
Start check time
Pre-purge time
Ignition standby time
Main stabilization time Hi
solenoid valve ignition time
Postpurge time Low
fire shutdown
Approximately 2 s
Main ignition time Hi solenoid valve ignition standby time
*
Content in ( ) describes the situation when three-position (Off-Lo-Hi) control is used.
If other than three-position control is used, only look at the main valve (Lo solenoid valve)
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
Customer Specification Check Sheet, BC-R35 Series
This sheet is for selecting the optimum BC-R35 Series product to suit the customer’s specification. Use it to
facilitate communications with our sales staff.
Equipment name
Equipment summary
Flame detector used
(draw a circle around the applicable product)
Flame rod / UV sensor (AUD100 series) /
Visible light flame detector (AFD100 series) / contact input
(For a UV sensor: Write the model No.)
(With a visible light flame detector: Write the model No.)
Ignition method (circle the applicable product)
Direct ignition type / time-limited pilot ignition type
Low fire shutdown
Yes/No
Power supply voltage (circle the applicable voltage)
100 Vac / 200 Vac / 220 Vac
Sequence
Pre-purge
Seconds or minutes
Ignition standby
s
Pilot only
s
Main ignition
s
Main stabilization
s
Postpurge
s
Input
(Write whether or not
there is input, the
specification,
etc.)
Lockout interlock input
Start input
Contact reset input
Airflow switch input
High fire interlock input
Low fire interlock input
POC (shutoff valve closure check) input
MEMO
บริษัท เอดีดี เฟอร์เนส จ ำกัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมรำชชนนี แขวงศำลำธรรมสพน์ เขตทวีวัฒนำ กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
https://www.add-furnace.com E-mail: [email protected]
Specifications are subject to change without notice.
1-12-2 Kawana, Fujisawa
Kanagawa 251-8522 Japan
https://www.azbil.com/
(13)
1st Edition: Oct. 2014
3rd Edition: Dec. 2020
No part of this publication may be reproduced or duplicated
without the prior written permission of Azbil Corporation.
Please read “Terms and Conditions” from the following URL
before ordering and use.
https://www.azbil.com/products/factory/order.html
16