KE2 Evaporator Efficiency Condensed Quick Start Manual
Read Online
Read the KE2 Evaporator Efficiency Condensed Quick Start Manual online using the built-in PDF viewer.
Text of the manual
Q.1.64 July 2021
KE2 EvaporatorEfficiency
Condensed Quick Start Guide
thermsolutions
This reference should remain on site
with the installed contactor panel.
© Copyright 2021 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Parts List
The following parts are included:
Kit #20178 with 120/208-240 VAC controller
Kit #20844❶ with 120/208-240 VAC controller
Kit #20631❷ with 120/208-240 VAC controller
Kit #20222❸ Beacon® I & II replacement
(1) KE2 Evaporator Efficiency controller
(1) high voltage safety shield
(3) 15’ colored temperature sensors❶❷❸*
(4) 90 degree quick disconnects
(5) self-tapping screws
(2) course thread screws &
(1) fine thread machine screw with lock washer
(1) KE2 Terminal Board with fuses
(1) KE2 Evap Navigation sticker
(2) 1/2” plastic knockout plugs
(4) wire ties (rated for low temp)
(1) air sensor mount
(1) 5-position pluggable connector (for EEV)
(4) 3-position pluggable connectors (for power in, transducer and 3A
relays)
(8) 2-position pluggable connectors (for sensors and digital input, analog
output)
(1) 120 Voltage jumper
(1) 208-240V Voltage jumper (already installed on KE2 Evap)
(1) Split Bushing (for high voltage shield)
(1) EC Motor Relay (120V & 240 V) kit (not shown)
20844 KE2 Ultimate Install kit includes KE2 Mounting Box pn 20687 and 40’
colored temperature sensors
20631 kit does not include temperature sensors
20222 Beacon® kit includes an extra temperature sensor, and pressure transducer with cable.
* To function properly, the controller requires a room temp sensor (T2Air - blue) and a coil
temp sensor (T3Coil - yellow) . KE2 Therm strongly recommends the third sensor is used as
2nd coil temp sensor (T4Aux - green).
Supplies List - All accessories required for the controller to work are
supplied. However, truck stock items are required for the installation.
(2) Conduit to go between the controller and the evaporator
(2) Conduit connectors (straight or elbow as required)
(11) High voltage wires matched to the load of the heaters, fans, liquid line
solenoid, alarm (if used), and the controller.
(8) Spade Connectors matched to gauge of high voltage wires
Wire labeling (numbers, colors, etc.)
Additional wire ties
18 gauge twisted shielded pair (if extending sensor wires)
Foam insulation if running wires outside the space.
Silicone (for sealing any box penetrations)
Popular Accessories - The following parts are available separately:
Wire Harness- 10’ pn 20736, 25’ pn 20670, 40’ pn 20737
Mounting Box pn 20687
Door Switch pn 20543
Buzzer & Light Combo (120VAC) pn 20973
Further information on accessories can be found in KE2 Condensed Catalog 411.
A
C
D
E
F
G
H
I
J
K
L
M
N
B
O
P
L
M
N
D
E
O
P
F
B
Left Arrow & Right Arrow
Use to move between Menus columns
Up Arrow & Down Arrow
Scroll through Menu Parameters
ENTER Press and hold ENTER for 3 seconds, when
display is blinking changes can be made.
BACK Press BACK to return to the previous view.
Press and hold ENTER for 3 seconds.
Change settings:
Save changes:
Moving through controller menus:
Return to Main Menu:
Lights:
Red - critical alarm (system not running)
Yellow - non-critical alarm (system running)
Green - compressor should be on
- compressor waiting on timer to start/stop
ENTER Press ENTER to go from parameter to value.
Toggle beween
description & value :
Menu Layout:
Variables
Manual*
(view only)
Alarms
(view only)
ENTER
Setpoints
Enter
Password
NO ALARM
EMAIL FAILURE
ROOM TEMP
DERIVATIVE
ROOM TEMP
FIRMWARE VERSION
MANUAL CONTROL
CLEAR MD
Controller Navigation
ENTER
ENTER
BACK Press BACK 3 - 4 times
If you lose your place:
* For manual defrost use MANUAL CONTROL
BACK
24-hour Emergency Support: 1.888.337.3358
www.ke2therm.com
pn 21061 9-14
A
C
G
H
I
J
K
Q
NOTE: All sensors
can be used for any
purpose and are
interchangeable,
colors are for ease of
identification only.
Video 046 How to Wire the KE2 Evap Controller
Video 033 How to Confirm the KE2 Evap is Wired
Correctly
Video 068 How to Determine Proper Coil Sensor
Location
Video 069 How to Properly Install a Coil Sensor
Video 032 Initial Defrost Sequence
Visit our YouTube channel for videos
on KE2 Evap installation and setup.
Introduction Mode
Applying power to the controller for the first time causes it to enter Introduction
Mode. Introduction Mode consists of as little as 4 setpoints that must be con-
figured to begin controlling the system.
Mechanical Valve
(TEV) - 4 steps
Preset EEV
5 steps
Custom EEV
8 steps
Room Temp
Room Temp
Room Temp
Defrost Type
Defrost Type
Defrost Type
Valve Type
Valve Type
Valve Type
KE2 Smart Access
Refrigerant
Refrigerant
KE2 Smart Access
Motor Type (Unipolar/Bipolar)
Motor Step Rate
Max Valve Steps
KE2 Smart Access
Controller Webpages
Logging in is required to make changes via the controller webpages.
The defaults are:
User Name: ke2admin
Password: ke2admin
IMPORTANT: The User Name and Password should be changed from the
default for security purposes.
NOTE: When making changes from the display the password is “2222”
Complete Instructions
Please visit:
http://ke2therm.com/product/ke2-evaporatorefficiency/
and click the Link to Literature button.
— OR —
use this QR code:
youtube.com/ke2therm
*
Q
R
© Copyright 2021 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.1.64 July 2021
Page 2
KE2 EvaporatorEfficiency
Condensed Quick Start Guide
BL/BK
OR/BK
Y/BK
FAN/S
HEATERS
LL SOLENOID/COMP RELAY
BK/OR
L1
WT/R
L2
HS
GND
P/N 20996
12 AMP
20 AMP
3 AMP
OR NEUTRAL
HEATERS
thermsolutions®
NO NC
COM
NO NC
COM
COM
NC
NO
COM
NC
N0
Solenoid Relay
Defrost
Relay
Fan
Relay
208-240
Power Input
Voltage Jumper
208-240 Default
L1
Ground
L2
COM
NC
NO
COM
NC
N0
Auxiliary Relay
Yellow with black stripe 16 AWG
Black with yellow stripe (L1) 16 AWG
Blue with black stripe 14 AWG
Black with blue stripe (L1) 14 AWG
LLS/Compressor
Fans
Black with white (L1) 16 AWG
White with red (L2/neutral) 16 AWG
Green (Ground) 16 AWG
Power
Orange with black stripe 12 AWG
Black with Orange stripe (L1) 12 AWG
Defrost Heaters
Supply Voltage
FAN
MOTOR
FAN
MOTOR
FAN
MOTOR
EVAPORATOR
FANS
HEATER LIMIT SWITCH
DEFROST HEATERS
LIQUID LINE SOLENOID
N.C.
R/W
BL/BK
BK
BL/BK
FROM
CONTROLLER
EC MOTOR
RELAY
See Q.1.30 Figure 3 for wiring
of the EC Motor Relay.
Wiring Schematic - Controller New Installation
Wiring Schematic - Controller New Installation
Q
Use Split Bushing ("Q" in the kit) to
prevent chaffing of the high volt-
age wires if routing through the
high voltage shield
© Copyright 2021 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.1.64 July 2021
Page 3
KE2 EvaporatorEfficiency
Condensed Quick Start Guide
Step ❹ - The fourth prompt is whether KE2 SMART ACCESS is ENABLED or
DISABLED. KE2 SMART ACCESS allows you to easily view your controller online.
Make your selection by using the i or j arrow, and then press and hold
ENTER for three seconds.
These are the only setpoints required to begin controlling the system. For setup
with multi-evaporator applications see bulletins Q.5.10 and Q.1.32
Adjusting Controller Parameters
The controller has the ability to access an abundance of information from the
4-digit alphanumeric display. However, the controller requires a password, add-
ing a degree of protection from unwanted modifications. The controller will
prompt the user for a PASSWORD when the user attempts to access setpoints
they do not have permission to change.
The Controller Navigation illustration on page 4 shows the menu structure of the
controller. The default display of the controller always shows the actual room
temperature, defrost, or any alarm condition. Pressing the g or h arrow will
move from the default display to the next menu column. The VARIABLES menu
column consists of the current sensor readings, and the relays’ state.
The User Password (1111) only provides access to the ROOM TEMP setpoint.
For the protection of the system, access to the SETPOINT and MANUAL control
requires an Installer Password (2222).
Pressing the BACK button at any time will return the user to next level up the
menu. A second/third press will either return to the Main Menu, or to the room
temperature reading.
User Interface
❹ Controller Setup: Four Step Intro Mode
Applying power to the controller for the first time causes it to enter Introduction
Mode. Introduction Mode consists of as little as 4 setpoints that must be config-
ured for the KE2 Evap to begin controlling the system.
Step ❶ - The first setpoint the user is asked to enter is the desired ROOM TEMP.
The default value is -00.0ºF, and the right most 0 will be flashing. Use
the g and h arrows to change the digit being modified. If you want the room
temperature warmer, press the i arrow, and if you want it colder, press the j
arrow. Once you have the proper room temp, press and hold
ENTER for three
seconds.
Step ❷ - Next, the controller will display DEFROST TYPE, and then display
ELECTRIC, for electric defrost. The controller is designed to work with electric, hot
gas, and air defrosts. Change this value by pressing the i or j arrow. Once you
have the correct value, press and hold
ENTER for three seconds.
Step ❸ - The controller now prompts for the expansion valve type, and dis-
plays MECHANICAL as the default. If you have a mechanical valve, press and hold
ENTER for three seconds. If you have an electric valve, use the i or j arrow
to move to the correct valve. With the correct electric valve displayed, press and
hold
ENTER for three seconds. NOTE: If you select an electric valve, you will then
be prompted to specify the REFRIGERANT.
The KE2 Evap may also be applied to user defined CUSTOM electric valves. When
CUSTOM is selected, the user is prompted to select MOTOR TYPE, MOTOR STEP
RATE, and MAX VALVE STEPS.
IMPORTANT: Determine the coil sensor location
When arriving on site, put the system into defrost and observe where the frost on the coil
disappears last. Place one sensor in each of the last two places where the frost disappears
❶. Monitor the coil’s air entering and air exiting side. Often the last place frost disappears is on
the air exiting side, near the right or left end. Verify all heating elements are working properly.
Sensor location is often approximately 1 to 1-1/2” away from the right and left edges of the ac-
tive coil surface, and typically near the bottom 1/3rd of the evaporator. Ice tends to grow from
the edges inward , but verify coil sensor locations by observing a defrost. Do not install coil
sensor on the U-bends.
The sensor needs to be as far away from the defrost heat sources as possible.
Note: To prevent sensor wire damage from sharp edges, insert plug I into coil housing - ❷.
Plug is inserted in the inner housing to access the coil. Puncture plug to insert sensor wire.
❸ the sensor should touch two circuit tubes. When inserting the sensor into the coil, the tip
should touch one of the circuit tubes. Don’t locate it next to the heating elements - position it
half way between the heaters if possible. In ❹ the probe is inserted into the fins approximately
1/16” deeper than the stainless shielding. Pinch the fins gently together, securing the sensor.
This provides thermal ballast too, ensuring a complete defrost.
Alternate method - As the defrost termination sensor, it is important the sensor does not ter-
minate defrost before all frost is removed from the coil. In some installations, inserting the sen-
sor into the coil may position it too close to the defrost heat source. An alternate method of
positioning places the sensor vertically between the coil fins, see ❺. Pinch fins together gently,
securing the sensor.
Extending sensor wires
After the sensors are mounted, route them back to the controller. If the wires must be ex-
tended, use 18 gauge twisted shielded pairs. Max recommended length for 18 gauge: 100ft.
When running the wires back to the controller, do not induce noise on the sensor wires. This
occurs when sensor wires are located near high voltage lines (defined by UL as greater than
30V.) Do not run high voltage and low voltage wires in the same conduit.
If crossing a high voltage line, run the sensor wiring at right angles to minimize noise.
Verify where frost is last to
disappear by initiating a defrost,
and observing last spot to clear.
Verify where frost is
last to disappear
(often on air exiting side).
Item I from Parts List on page 1
❶
❷
❺
❹
❸
© Copyright 2021 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.1.64 July 2021
Page 4
KE2 EvaporatorEfficiency
Condensed Quick Start Guide
Q.1.64 July 2021 supersedes all prior publications
KE2 Therm Solutions
12 Chamber Dr. . Washington, MO 63090
636-266-0140 . www.ke2therm.com
Menu
Parameters:
MANUAL CONTROL
MANUAL VALVE4
CLEAR ALARMS
MANUAL COMPRESSOR RELAY
MANUAL DEFROST RELAY
MANUAL FAN RELAY
MANUAL AUX RELAY
FACTORY RESET
WEB PASSWORD RESET
KE2 SMART ACCESS
DHCP
DOD INIT
CLEAR MD
Menus:
Variables
Manual
(view only)
Non-adjustable
NO ALARM
PRESSURE SENSOR
SUCTION TEMP SENSOR
AIR TEMP SENSOR
COIL TEMP SENSOR
AUX TEMP SENSOR
HIGH SUPERHEAT
LOW SUPERHEAT
HIGH AIR TEMP
LOW AIR TEMP
EXCESS DEFROST
DEFR TERM ON TIME
DOOR SWITCH
COMMUNICATION ERROR
EXT ALARM
EMAIL FAILURE
Alarms
(view only)
ENTER
ENTER
ROOM TEMP
COIL TEMP
SYSTEM MODE
SUPERHEAT
SUCTION PRESSURE
T1 SUCTION TEMP1
SATURATION TEMP
VALVE % OPEN4
T4 AUX TEMP1
COMPRESSOR RELAY
DEFROST RELAY
FAN RELAY
AUX RELAY
DIG 1 STATUS
DIG 2 STATUS
DIG 3 STATUS
IP OCTET 1
IP OCTET 2
IP OCTET 3
IP OCTET 4
SUBNET MASK OCTET 1
SUBNET MASK OCTET 2
SUBNET MASK OCTET 3
SUBNET MASK OCTET 4
FIRMWARE VERSION
1 T1 & T4 are parameters
and can be set to various
functions. The default for
T1 is Suction Temp, the
default for T4 is Coil Temp.
2 The Setpoint paramenters
shown in BOLD (Valve
Type, Room Temp
Setpoint and Defrost
Mode) need to be set by
the user prior to start up.
The other Setpoint
Parameters can also be
adjusted, however the
factory setpoints are
generally correct for most
applications.
3 The Setpoint parameters
shown in ITALIC are
displayed only when a
Custom EEV is used.
4 Displayed when an EEV is
used.
5 Only available if mechani-
cal valve is selected. When
using an electric valve T1
is fxed as suction
temperature.
6 The Setpoint parameters
shown in BOLD ITALIC are
active for bonded
controllers only.
7 Only displayed when Run
Time Defrost is selected.
ROOM TEMP2
DEFROST TYPE2
VALVE TYPE2
MOTOR TYPE3
MOTOR STEP RATE3
MAX VALVE STEPS3
SUPERHEAT4
MAX OPERATING PRES4
REFRIGERANT
AUX TEMP 4 MODE
AUX TEMP 1 MODE5
AUX RELAY MODE
FAN SPEED
MIN COMP RUN TIME
MIN COMP OFF TIME
REFRIG FAN MODE
DEFROST MODE
DEFROSTS / DAY
1ST DEFROST DELAY
DEFROST FAN STATE
DEFROST TERM TEMP
DEFROST PARAMETER/MAX DEFROST TIME
DRAIN TIME
COMP RUN TIME7
ELEC DEFROST MODE
FAN DELAY TEMP
MAX FAN DELAY TIME
PUMP DOWN TIME
MULTI AIR TEMP CTRL
MULTI EVAP COOL6
MULTI EVAP DEFROST 6
MULTI EVAP SENSOR6
HIGH TEMP ALARM OFFSET
HIGH TEMP ALARM DELAY
LOW TEMP ALARM OFFSET
LOW TEMP ALARM DELAY
DOOR ALARM DELAY
DIG IN 1 MODE
DIG IN 1 STATE
DIG IN 2 MODE
DIG IN 2 STATE
DIG IN 3 MODE
DIG IN 3 STATE
2ND ROOM TEMP
SUCT PRES OFFSET
SUCT TEMP OFFSET
AIR TEMP OFFSET
COIL TEMP OFFSET
AUX TEMP OFFSET
TEMP UNITS
AIR TEMP DIFF
EXTREME TEMP DIFF
PROPORTIONAL
INTEGRAL
DERIVATIVE
Setpoints
Options for
DIG IN STATUS
DISABLED
2ND (ROOM) TEMP
DOOR SWITCH
EXT ALARM
SYSTEM OFF
LIGHT SWITCH
DEFROST LOCKOUT
DEFROST INTERLOCK
Enter
Password
Left & Right arrows move
between Menus
Up & Down arrows scroll
through Menu Parameters
ENTER Press & hold ENTER for
3 seconds, when display
begins blinking changes
can be made
BACK Press BACK to return to
the previous view.
ENTER Press & hold ENTER for
3 seconds to save change
Change settings:
Save setting
changes:
Move through
menus:
Return to
Main Menu:
Indicator Lights
Red - critical alarm (system is not running)
Yellow - non-critical alarm (system running)
Green - Liquid Line Solenoid (LLS) relay energized
Green fashing - waiting on min. run or min. of
timer to energize/de-energize LLS relay
ENTER Press ENTER to go from
parameter to value.
Toggle between
description &
value :
Navigating Menus