Johnson Controls P2000 Hardware Installation

File Specifications

Brand: Johnson Controls
Category: Controller
Model: P2000 (Hardware Installation), prN9LHP7MTpbI
File Type: PDF
File Size: —
Pages: 25 pages

Download PDF

Download Johnson Controls P2000 Manual (25 pages)

Read Online:

Read the Johnson Controls P2000 Hardware Installation online using the built-in PDF viewer.

Key Pages of Document

24-10707-15 Revision E

December 2017 P2000 Security Management System CKM-EP1502 authentic Mercury™ controller hardware installation ...

All Rights Reserved

No part of this document may be reproduced without the prior permission of Johnson Controls. If this document is translated from the original English version by Johnson Controls, all reasonable endeavors will be used to ensure the accuracy of translation. Johnson Controls shall not be liable for any transla ...

Declarations of Conformity

United States: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and ...

UNDERWRITERS LABORATORIES COMPLIANCE VERIFICATION SHEET

The following model number is listed under Underwriters Laboratories® (UL) 1076 for Proprietary Burglar Alarm Units and Systems, UL 294 for Access Control Systems Units and Underwriters Laboratories of Canada ULC/ORD-C1076-86. CKM-EP1502 When installed at the site the following requirements must be met ...

Hardware Installation Manual

24-10707-15 Rev. E 1 CKM-EP1502 CONTROLLER This document provides hardware installation and setup instructions for CKM-EP1502, the authentic Mercury™ intelligent dual reader controller. This document is divided into the following sections: • General Information on page 1 • Mounting Information on page 2 • Wir ...

Hardware Installation Manual

24-10707-15 Rev. E 2 MOUNTING INFORMATION Figure 1: CKM-EP1502 Hardware ...

Hardware Installation Manual

24-10707-15 Rev. E 3 WIRING INFORMATION This sections covers the following: • Cable Routing • Input Power, Cabinet Tamper, and UPS Fault Input Wiring • Communication Wiring • Reader Wiring • Input Circuit Wiring • Relay Circuit Wiring Cable Routing The cables should run in grounded conduit or at least two ...

Hardware Installation Manual

24-10707-15 Rev. E 4 Input Power, Cabinet Tamper, and UPS Fault Input Wiring The CKM-EP1502 requires 12-24 VDC power. Locate power source as close to the unit as possible. IMPORTANT: Connect power with minimum of 18 AWG wire. Connect the GND signal to earth ground in one location within the system. Multiple earth gro ...

Hardware Installation Manual

24-10707-15 Rev. E 5 Figure 3: CKM-EP1502 Communications Wiring Reader Wiring Each reader port supports Wiegand, magnetic stripe, and two-wire RS- 485 electrical interfaces. Power to the reader is selectable: 12 VDC (VIN must be greater than 20 VDC), or power is passed through (PT) from the input voltage of the CKM-E ...

Hardware Installation Manual

24-10707-15 Rev. E 6 Input Circuit Wiring Typically, you use these inputs to monitor door position, request to exit, or alarm contacts. You can configure input circuits as unsupervised or supervised. When request to exit (REX) input is supervised, the strike remains locked when a transition to open state or short sta ...