IFM AL1101 Operating Instructions Manual
Read Online
Read the IFM AL1101 Operating Instructions Manual online using the built-in PDF viewer.
Text of the manual
IO-Link Master with PROFINET interface
StandardLine
4 Ports
IP 65 / IP 66 / IP 67 / IP 69K
AL1101
IO-Link: 1.1.2
ifm firmware: 2.1.28 or higher
LR DEVICE: 1.3.1.x or higher
English
7391216 / 01 05 / 2018
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Content
Table of Contents
1
Preliminary note
5
1.1
Legal and copyright information ........................................................................................... 5
1.2
Purpose of the document ..................................................................................................... 5
1.3
Symbols and styles used ..................................................................................................... 6
1.4
Modification history .............................................................................................................. 6
2
Safety instructions
7
2.1
General ................................................................................................................................ 7
2.2
Required background knowledge ........................................................................................ 7
2.3
Safety symbols on the device .............................................................................................. 7
2.4
Tampering with the unit ........................................................................................................ 8
3
Intended use
9
3.1
Permitted use ....................................................................................................................... 9
3.2
Prohibited use ...................................................................................................................... 9
4
Function
10
4.1
Communication, parameter setting, evaluation .................................................................11
4.1.1
IO-Link ........................................................................................................................................ 11
4.1.2
PROFINET ................................................................................................................................. 11
4.1.3
Parameter setting ....................................................................................................................... 11
4.1.4
Visual indication ......................................................................................................................... 12
4.2
Digital inputs .......................................................................................................................12
4.3
IO-Link supply ....................................................................................................................12
5
Mounting
13
5.1
Mount the device ................................................................................................................13
6
Electrical connection
14
6.1
Remarks .............................................................................................................................14
6.2
Ethernet ports .....................................................................................................................15
6.3
IO-Link ports .......................................................................................................................16
6.3.1
Input circuit ................................................................................................................................. 16
6.3.2
IO-Link circuits ............................................................................................................................ 16
6.4
Connect the device ............................................................................................................17
7
Operating and display elements
18
7.1
Overview ............................................................................................................................18
7.2
LED indicators ....................................................................................................................19
7.2.1
Status LEDs ............................................................................................................................... 19
7.2.2
Ethernet interface ....................................................................................................................... 19
7.2.3
Voltage supply ............................................................................................................................ 20
7.2.4
IO-Link ports (Class A) ............................................................................................................... 20
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Content
8
Configuration
21
8.1
LR DEVICE ........................................................................................................................22
8.1.1
Remarks ..................................................................................................................................... 23
8.1.2
IoT: Configure access rights ....................................................................................................... 24
8.1.3
IoT: Configure the interface to the LR SMARTOBSERVER ....................................................... 25
8.1.4
Fieldbus: Set PROFINET interface ............................................................................................. 25
8.1.5
IO-Link ports: Activate data transfer to the LR SMARTOBSERVER .......................................... 26
8.1.6
IO-Link ports: Configure operating mode.................................................................................... 27
8.1.7
IO-Link ports: Set the device validation and data storage .......................................................... 28
8.1.8
Firmware: Reset device to factory settings ................................................................................. 29
8.1.9
Firmware: Reboot the device ...................................................................................................... 29
8.1.10
Configure IO-Link devices .......................................................................................................... 30
8.2
PROFINET .........................................................................................................................31
8.2.1
Install GSD file ............................................................................................................................ 32
8.2.2
Add the IO-Link master to the PROFINET network .................................................................... 33
8.2.3
Configure access rights .............................................................................................................. 35
8.2.4
Configure IO-Link ports .............................................................................................................. 36
8.2.5
Configure the PROFINET port .................................................................................................... 37
8.2.6
Configure IO-Link devices .......................................................................................................... 37
8.2.7
Read and write data cyclically .................................................................................................... 38
8.2.8
PROFINET: Read & write device information ............................................................................. 38
8.2.9
PROFINET: Programmers' notes ............................................................................................... 39
9
Operation
41
9.1
Identify device ....................................................................................................................41
9.2
Web interface: Read device and diagnostic information....................................................42
9.3
Firmware update ................................................................................................................43
9.4
Replace IO-Link device ......................................................................................................44
10
Maintenance
45
11
Factory settings
46
12
Accessories
47
13
Appendix
48
13.1
Technical data ....................................................................................................................49
13.1.1
Application .................................................................................................................................. 49
13.1.2
Electrical data ............................................................................................................................. 49
13.1.3
Inputs / outputs ........................................................................................................................... 49
13.1.4
Inputs.......................................................................................................................................... 50
13.1.5
Outputs ....................................................................................................................................... 50
13.1.6
Interfaces .................................................................................................................................... 50
13.1.7
Operating conditions .................................................................................................................. 51
13.1.8
Approvals / tests ......................................................................................................................... 51
13.1.9
Mechanical data ......................................................................................................................... 51
13.1.10
Electrical connection .................................................................................................................. 52
13.2
PROFINET .........................................................................................................................53
13.2.1
Parameter data ........................................................................................................................... 53
13.2.2
Cyclic data .................................................................................................................................. 56
13.2.3
Acyclic data ................................................................................................................................ 58
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Content
14
Index
61
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Preliminary note
Legal and copyright information
1
Preliminary note
Legal and copyright information ............................................................................................................... 5
Purpose of the document ......................................................................................................................... 5
Symbols and styles used .......................................................................................................................... 6
Modification history ................................................................................................................................... 6
14801
>
1.1
Legal and copyright information
1631
© All rights reserved by ifm electronic gmbh. No part of this manual may be reproduced and used
without the consent of ifm electronic gmbh.
All product names, pictures, companies or other brands used on our pages are the property of the
respective rights owners:
AS-i is the property of the AS-International Association, (→ www.as-interface.net)
CAN is the property of the CiA (CAN in Automation e.V.), Germany (→ www.can-cia.org)
CODESYS™ is the property of the 3S – Smart Software Solutions GmbH, Germany
(→ www.codesys.com)
DeviceNet™ is the property of the ODVA™ (Open DeviceNet Vendor Association), USA
(→ www.odva.org)
EtherNet/IP® is the property of the →ODVA™
EtherCAT® is a registered trade mark and patented technology, licensed by Beckhoff Automation
GmbH, Germany
IO-Link® (→ www.io-link.com) is the property of the →PROFIBUS Nutzerorganisation e.V.,
Germany
ISOBUS is the property of the AEF – Agricultural Industry Electronics Foundation e.V.,
Deutschland (→ www.aef-online.org)
Microsoft® is the property of the Microsoft Corporation, USA (→ www.microsoft.com)
PROFIBUS® is the property of the PROFIBUS Nutzerorganisation e.V., Germany
(→ www.profibus.com)
PROFINET® is the property of the →PROFIBUS Nutzerorganisation e.V., Germany
Windows® is the property of the →Microsoft Corporation, USA
>
1.2
Purpose of the document
22044
This document is only for device types "IO-Link master - PROFINET gateway (StandardLine) 4 port IP
65 / IP 66 / IP 67 / IP 69K" (art. no.: AL1101).
It is part of the device and contains information about the correct handling of the product.
► Read this document before using the device.
► Keep this document during the service life of the device.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Preliminary note
Symbols and styles used
>
1.3
Symbols and styles used
15989
WARNING
Death or serious irreversible injuries may result.
CAUTION
Slight reversible injuries may result.
NOTICE
Property damage is to be expected or may result.
Important note
Non-compliance can result in malfunction or interference
Information
Supplementary note
► ...
Request for action
>
...
Reaction, result
→ ...
"see"
abc
Cross-reference
123
0x123
0b010
Decimal number
Hexadecimal number
Binary number
[...]
Designation of pushbuttons, buttons or indications
>
1.4
Modification history
21676
Version
Topic
Date
00
New creation of document
05 / 2018
01
Correction IoT Core
05 / 2018
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Safety instructions
General
2
Safety instructions
General ..................................................................................................................................................... 7
Required background knowledge ............................................................................................................. 7
Safety symbols on the device ................................................................................................................... 7
Tampering with the unit ............................................................................................................................ 8
213
>
2.1
General
22068
The plant manufacturer is responsible for the safety of the plant in which the device is
installed.
If the device is used in a way that is not intended by the manufacturer, the protection
supported by the device may be impaired.
Non-observance of the instructions, operation which is not in accordance with use as
prescribed below, wrong installation or incorrect handling can affect the safety of operators
and machinery.
► Observe these operating instructions.
► Adhere to the warning notes on the product.
>
2.2
Required background knowledge
22046
This document is intended for specialists. Specialists are people who, based on their relevant training
and experience, are capable of identifying risks and avoiding potential hazards that may be caused
during operation or maintenance of the product.
The document contains information about the correct handling of the product.
>
2.3
Safety symbols on the device
15021
General warning
Observe instructions in chapter "Electrical connection" (→ Electrical connection (→ p. 14))!
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Safety instructions
Tampering with the unit
>
2.4
Tampering with the unit
11242
WARNING
Tampering with the units can affect the safety of operators and machinery!
Tampering with the units is not allowed.
In case of non-compliance our liability and warranty expire.
► Do not open the devices!
► Do not insert any objects into the devices!
► Prevent metal foreign bodies from penetrating!
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Intended use
Permitted use
3
Intended use
Permitted use ........................................................................................................................................... 9
Prohibited use ........................................................................................................................................... 9
18761
>
3.1
Permitted use
7610
The IO-Link master serves as a gateway between intelligent IO-Link devices and the fieldbus. The
device is designed for use without a control cabinet in the food industry.
>
3.2
Prohibited use
22053
The device may not be used beyond the limits of the technical data (→ Technical data (→ p. 49))!
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Function
Prohibited use
4
Function
Communication, parameter setting, evaluation ......................................................................................11
Digital inputs ...........................................................................................................................................12
IO-Link supply .........................................................................................................................................12
7482
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Function
Communication, parameter setting, evaluation
>
4.1
Communication, parameter setting, evaluation
IO-Link ....................................................................................................................................................11
PROFINET..............................................................................................................................................11
Parameter setting ...................................................................................................................................11
Visual indication ......................................................................................................................................12
7485
>
4.1.1
IO-Link
7773
The device offers the following IO-Link functions:
IO-Link master (IO-Link revision 1.0 and 1.1)
4 IO-Link ports for connection of IO-Link devices
Provision of process data of the connected IO-Link devices for LR SMARTOBSERVER monitoring
software (→ www.ifm.com)
>
4.1.2
PROFINET
2259
The device offers the following PROFINET functions:
Provision of the functions of a Profinet RT Device (Class B)
2 port switch for access to the PROFINET interface (X21/X22)
Gateway for transmission of the process and parameter data between the connected IO-Link
devices and the higher-level PROFINET controller
>
>
4.1.3
Parameter setting
7284
The device provides the following configuration options:
Parameter setting of the IO-Link master of the AL1101 with LR DEVICE parameter setting
software or PROFINET projection software
Parameter setting of the connected IO-Link devices (sensors, actuators) with LR DEVICE
parameter setting software or PROFINET projection software
Storage of parameter sets of the connected IO-Link devices for automatic recovery (data storage)
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Function
Digital inputs
>
4.1.4
Visual indication
7772
The device has the following visual indicators:
Status and error indication of the gateway, of the PROFINET connection and of the system
Status display of the voltage supply
Status and activity display of the Ethernet connection
Status, error and short circuit/overload indication of the IO-Link ports
>
4.2
Digital inputs
7584
The device has 4 additional digital inputs (type 2 according to EN 61131-2).
The digital inputs are on pin 2 of the IO-Link ports X01 ... X04.
All inputs refer to the potential of the device supply (pin 3).
>
4.3
IO-Link supply
7623
The device has 4 supplies for IO-Link devices.
The IO-Link ports X01...X04 are ports class A.
Every supply provides short circuit monitoring.
The device ensures fire protection for the connected IO-Link devices by providing a power-restricted
circuit at the IO-Link ports (according to IEC61010-1 and Class 2 according to UL1310).
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Mounting
Mount the device
5
Mounting
Mount the device ....................................................................................................................................13
22016
>
5.1
Mount the device
15540
► Disconnect the system from power before installation.
► For installation choose a flat mounting surface.
► Please observe the maximum tightening torque.
► Fix the unit to the mounting surface using 2 M5 mounting screws and washers.
Tightening torque: 1.8 Nm
► Ground the unit via the two mounting screws of the upper mounting lugs.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Electrical connection
Remarks
6
Electrical connection
Remarks .................................................................................................................................................14
Ethernet ports .........................................................................................................................................15
IO-Link ports ...........................................................................................................................................16
Connect the device .................................................................................................................................17
22017
>
6.1
Remarks
18076
A qualified electrician must connect the unit.
► Observe the national and international regulations for the installation of electrical
equipment.
Device is only suitable for operation on SELV/PELV voltages.
► Observe the information concerning IO-Link circuits (→ IO-Link circuits (→ p. 16))!
The device contains components that can be damaged or destroyed by electrostatic discharge
(ESD).
► Observe the required safety measures against electrostatic discharge!
The IP rating depends on the individual protection ratings of the unit, the applied connection
elements and the corresponding protective covers.
► For UL applications: For connecting the device and the IO-Link devices use UL certificated
cables of category CYJV or PVVA with a minimum temperature rating of 100°C.
► Depending on the mounting conditions, cables must be provided with a strain relief to
avoid unacceptable loads on the mounting points and M12 connections.
► Make sure that the M12 connection parts are correctly seated and mounted correctly. The
specified protection rating can not be guaranteed if this is not observed.
Wiring: → Technical data (→ p. 49)
The communication interfaces are seperated from the device supply according to EN61010-1
considering basis isolation as secondary circuit with maximum 30 V DC derived from the
applied voltage up to 300 V of overvoltage category II. The communication interfaces are
designed for a network environment 0 according to IEC TR62102.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Electrical connection
Ethernet ports
>
6.2
Ethernet ports
25397
► Connect the unit via the M12 socket X21 and/or X22 with the
PROFINET network (e.g. PROFINET PLC, additional PROFINET
device)
Tightening torque: 0.6...0.8 Nm
► Connect the unit via the M12 socket X21 and/or X22 to the IT
network (e.g. laptop/PC with installed LR DEVICE,
LR SMARTOBSERVER)
Tightening torque: 0.6...0.8 Nm
► For the connection, use M12 connectors with protection rating IP 65
/ IP 66 / IP 67 / IP 69K or higher (→ Accessories (→ p. 47)).
► Cover the unused sockets with M12 protective caps (art no.
E12542).
Tightening torque: 0.6...0.8 Nm
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Electrical connection
IO-Link ports
>
6.3
IO-Link ports
8526
Ports X01...X04: For use as IO-Link port class A:
► Connect the connector of the IO-Link devices with the M12 sockets
X01 ... X04.
Tightening torque: 0.6...0.8 Nm
Maximum cable length per IO-Link interface: 20 m
► For the connection, use M12 connectors with protection rating IP 65
/ IP 66 / IP 67 / IP 69K or higher (→ Accessories (→ p. 47)).
► Cover the unused sockets with M12 protective caps (art no.
E12542).
Tightening torque 0.6...0.8 Nm
>
6.3.1
Input circuit
18629
The inputs of the ports X01...X04 (pin 2) provide a type 2 behaviour according to standard EN61131-2,
the connected electronics must be rated for this electrically.
>
6.3.2
IO-Link circuits
1863
The IO-Link ports of the device meet the requirements of the IO-Link specification 1.0 bis 1.1.2.
The power supply of the connected IO-Link devices may only take place via the AL1101.
Further information: → Technical data (→ p. 49)
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Electrical connection
Connect the device
>
6.4
Connect the device
17542
► Disconnect power.
► Connect the device via M12 socket X31 to 24 V DC
(20...28 V SELV/PELV; according to EN61010-1, secondary circuit
with maximum 30 V DC derived from applied voltage up to 300 V of
overvoltage category II).
Tightening torque: 0.6...0.8 Nm
Maximum cable length: 25 m
► To connect the device, use M12 connectors with protection rating IP
65 / IP 66 / IP 67 / IP 69K or higher (→ Accessories (→ p. 47)).
When using cable length greater than 25 m keep in mind the voltage drop as well as the
required minimum voltage supply of 20 V!
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Operating and display elements
Overview
7
Operating and display elements
Overview .................................................................................................................................................18
LED indicators ........................................................................................................................................19
5440
>
7.1
Overview
22025
1
Status LEDs RDY, BF and SF
→ Status LEDs (→ p. 19)
2
Status LEDs LNK and ACT of the
PROFINET ports 1 (X21) and 2 (X22)
→ Ethernet interface (→ p. 19)
3
Status LED US of the power supply
(X31)
→ Voltage supply (→ p. 20)
4
Status LEDs IOL and DI of the IO-Link
ports Class A (X01...X04)
→ IO-Link ports (Class A) (→ p. 20)
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Operating and display elements
LED indicators
>
7.2
LED indicators
22024
The device only has the following LED indicators:
>
7.2.1
Status LEDs
22034
The RDY LED shows the status of the gateway.
The BF LED (Bus Failure) shows the status of the PROFINET connection.
The SF LED (System Failure) shows the status of the system.
Status LED
Description
RDY
green
on
Gateway functions properly
flashes 1 Hz
Error
flashes 5 Hz
Firmware update
off
Gateway does not function; Unit reboots
BF
red
on
Bus error
flashes 1 Hz
No connection to the PROFINET controller
off
error-free
SF
red
on
Error in gateway
At least 1 IO-Link device sends warning / alarm (temperature,
over/under current, over/under voltage, shortcut)
off
error-free
>
7.2.2
Ethernet interface
22027
Each Ethernet interface (X21, X22) has 2 LEDs (LNK and ACT). The LEDs indicate the status of the
Ethernet connection.
Status LED
Description
LNK
green
on
Ethernet connection established
off
No Ethernet connection
ACT
yellow
flashes
Data is transmitted via the Ethernet interface.
off
No data transmission
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Operating and display elements
LED indicators
>
7.2.3
Voltage supply
22026
The interface for voltage supply (X31) has the LED that is marked as US. The LED indicates the status
of the voltage supply.
Status LED
Description
US
green
on
The supply voltage Us is applied.
off
No supply voltage is applied or the applied supply voltage is too low.
>
7.2.4
IO-Link ports (Class A)
22029
Each IO-Link port Class A (X01 ... X04) has 2 LEDs marked as IOL and DI. The LEDs indicate the
status of the IO-Link port.
Status LED
Description
IOL
yellow
on
Interface configured as DI/DO: pin 4 (C/Q) =ON
off
Interface configured as DI/DO: pin 4 (C/Q) = OFF
green
on
IO-Link transmission functions properly
flashes 1 Hz
Interface configured as IO-Link, but no IO-Link transmission
red
on
Short circuit or overload in supply voltage
flashes 1 Hz
Transmission error
DI
yellow
on
Digital input: pin 2 (DI) = ON
off
Digital input : pin 2 (DI) = OFF
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
LED indicators
8
Configuration
LR DEVICE .............................................................................................................................................22
PROFINET..............................................................................................................................................31
22367
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
LR DEVICE
>
8.1
LR DEVICE
Remarks .................................................................................................................................................23
IoT: Configure access rights ...................................................................................................................24
IoT: Configure the interface to the LR SMARTOBSERVER ..................................................................25
Fieldbus: Set PROFINET interface ........................................................................................................25
IO-Link ports: Activate data transfer to the LR SMARTOBSERVER .....................................................26
IO-Link ports: Configure operating mode ...............................................................................................27
IO-Link ports: Set the device validation and data storage ......................................................................28
Firmware: Reset device to factory settings ............................................................................................29
Firmware: Reboot the device..................................................................................................................29
Configure IO-Link devices ......................................................................................................................30
22822
On delivery, the AL1101 is configured with the factory settings (→ Factory settings (→ p. 46)).
Required software: LR DEVICE (1.3.1.x or higher) (art.-no.: QA0011/QA0012)
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
LR DEVICE
>
8.1.1
Remarks
Offline parameter setting ........................................................................................................................23
VPN connection ......................................................................................................................................23
22369
>
Offline parameter setting
22405
The AL1101 supports the offline parameter setting. In this context, the user creates and stores a
configuration for the IO-Link master and the connected IO-Link devices without being connected to the
AL1101 (OFFLINE mode). The configuration created in this way can be stored as a file (*.lrp) and
loaded to the AL1101 and activated at a later date.
Further information about offline parameter setting: → Operating instructions LR DEVICE
>
VPN connection
22762
An active VPN connection blocks the access of the parameter setting software LR DEVICE to
the PROFINET interface of the AL1101.
► Deactivate the VPN connection in order to be able to access the AL1101 with the LR
DEVICE.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
LR DEVICE
>
8.1.2
IoT: Configure access rights
16555
The access rights define which instance may read and / or write the parameter data, process data and
event/diagnostic messages.
In order to configure the access rights to the IO-Link master:
► Select [IoT] menu.
>
The menu page shows the current settings.
► Set the following parameters as required:
Name
Description
Possible values
[Access Rights]
The access rights to the
parameter data, process data
and the event/diagnostic
messages of the IO-Link master
as well as the connected IO-Link
devices
[PROFINET + IoT]
PROFINET and IoT Core have read
and write access rights to parameters
and process data
PROFINET and have read
access rights to events/alarms
[PROFINET + IoT
(read-only)]
PROFINET has read and write access
rights to parameters and process data
PROFINET has read access rights to
events/alarms
IoT Core only has read access rights to
parameters, process data and
events/alarms
[IoT only]
IoT Core has read and write access
rights to parameters and process data
IoT has read access rights to
events/alarms
PROFINET has no access rights
► Save changed values on the device.
Parameter [Access Rights]:
Different parameter settings in the PROFINET projection software and the IoT applications
can result in undesired system behaviour. The set values of the PROFINET projection
software apply.
Changes of the parameter [Access Rights] are only effective after restarting the device.
To activate the changed access rights:
► Firmware: Reboot the device (→ p. 29)
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
LR DEVICE
>
8.1.3
IoT: Configure the interface to the LR SMARTOBSERVER
16552
To enable data transfer between the device and the LR SMARTOBSERVER monitoring software, the
LR SMARTOBSERVER monitoring software interface has to be configured.
► Select [IoT] menu.
>
The menu page shows the current settings.
► Set the following parameters as required:
Name
Description
Possible values
[IP address
LR SMARTOBSERVER]
IP address of the PC on which the
LR SMARTOBSERVER is installed.
Factory setting: 255.255.255.255
[Port
LR SMARTOBSERVER]
Port number that is used to send process
data to the LR SMARTOBSERVER
0
...
65535
Factory setting:: 35100
[Interval
LR SMARTOBSERVER]
Cycle time for the transfer of the process
data to the LR SMARTOBSERVER (value
in milliseconds)
[Off]
no transfer
500
...
2147483647
500 ms
...
2147483647 ms
[Application Tag]
Source identifier of the IO-Link master in
the structure of the
LR SMARTOBSERVER (String32)
Factory setting: AL1101
After changing the parameter [Port LR SMARTOBSERVER] or [Application Tag], it may take
120 seconds before the device establishes a new TCP connection.
To prevent the delay:
► Reboot the device after the parameter change.
► Save changed values on the device.
>
8.1.4
Fieldbus: Set PROFINET interface
25393
For the access of the PROFINET interface the Ethernet ports X21/X22 need to be set:
► Select [Fieldbus] menu.
>
The menu page shows the current settings.
► Set the following parameters as required:
Name
Description
Possible values
[IP address]
IP address of the PROFINET interface
Factory setting: 0.0.0.0
[Subnet mask]
Subnet mask of the IP network
Factory setting: 0.0.0.0
[Default gateway IP address]
IP adrress of the network gateway
Factory setting: 0.0.0.0
[MAC address]
MAC address of the PROFINETA interface
The value is firmly set.
[Fieldbus firmware]
► Save changed values on the device.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
LR DEVICE
>
8.1.5
IO-Link ports: Activate data transfer to the LR SMARTOBSERVER
16551
The user can decide separately for each IO-Link port if the process data of the connected IO-Link
devices should be transferred to the LR SMARTOBSERVER.
To transfer process data the interfaces to the LR SMARTOBSERVER have to be correctly
configured (→ IoT: Configure the interface to the LR SMARTOBSERVER (→ p. 25)).
To activate / deactivate data transfer:
► Select [Port x] menu (x = 1...4).
>
The menu page shows the current settings.
► Set the following parameters as required:
Name
Description
Possible values
[Transmission to
LR SMARTOBSERVER]
Transfer of process data of the
connected IO-Link device to
LR SMARTOBSERVER
[Disabled]
Process data is not transferred
[Enabled]
Process data is transferred
► Save changed values on the device.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
LR DEVICE
>
8.1.6
IO-Link ports: Configure operating mode
17439
The IO-Link ports X01...X04 of the device support the following operating modes:
Digital input (DI): binary input signal at pin 4 (C/Q) of the IO-Link port
Digital output (DO): binary output signal at pin 4 (C/Q) of the IO-Link port
IO-Link: IO-Link data transfer via pin 4 (C/Q) of the IO-Link port
The user can set the operating mode separately for each IO-Link port.
To set the operating mode of an IO-Link port:
► Select [Port x] menu (x = 1...4).
>
The menu page shows the current settings.
► Set the following parameters as required:
Name
Description
Possible values
[Mode]
Operating mode of the IO-Link port
[Disabled]
Port deactivated
[DI]
Operation as digital input
[DO]
Operation as digital output
[IO-Link]
Operation as IO-Link interface
[Cycle time actual]**
Current cycle time of the data transfer between
IO-Link master and IO-Link device on the port
(value in microseconds)
Parameter can only be read
[Cycle time preset]*
Cycle time of the data transfer between the
IO-Link master and the IO-Link device at the
port (value in microseconds)
0
The device automatically sets the
fastest possible cycle time.
1
...
132800
1 microsecond
...
132800 microseconds
[Bitrate]**
Current transmission rate of the data transfer
between the IO-Link master and the IO-Link
device on the port
Parameter can only be read
* ... Parameter only available if [Mode] = [IO-Link]
** ... Parameter only visible if the IO-Link device is connected to the IO-Link port.
► Save changed values on the device.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
LR DEVICE
>
8.1.7
IO-Link ports: Set the device validation and data storage
17945
In the operating mode "IO-Link" the user can set the behaviour of the IO-Link port with regard to
device validation and the storage / restoration of the parameter data of the connected IO-Link device.
To configure the device validation and the data storage:
► Select [Port x] menu (x = 1...4).
>
The menu page shows the current settings.
► Set the following parameters as required:
Name
Description
Possible values
[Validation / Data
Storage]
Supported IO-Link standard and
behaviour of the device during
connection of a new IO-Link
device on port x (x = 1...4)
[No check
and clear]
No verification of the vendor ID and device ID
No data storage
[Type
compatible
V1.0 device]
IO-Link device is compatible with the V1.0
IO-Link standard
Verification whether it is an IO-Link device of
the same type (validation via vendor ID and
device ID)
No data storage
[Type
compatible
V1.1 device]
IO-Link device is compatible with the V1.1
IO-Link standard
Verification whether it is an IO-Link device of
the same type (validation via vendor ID and
device ID)
No data storage
[Type
compatible
V1.1 device
with Backup
+ Restore]
IO-Link device is compatible with the V1.1
IO-Link standard
Verification whether it is an IO-Link device of
the same type (validation via vendor ID and
device ID)
The IO-Link master saves the parameter
values of the connected IO-Link device;
modifications of the parameter values are also
saved (observe the note!)
When connecting an IO-Link device with
factory settings, the parameter values stored in
the IO-Link master are restored automatically
on the IO-Link device.
[Type
compatible
V1.1 device
with Restore]
IO-Link device is compatible with the V1.1
IO-Link standard
Verification whether it is an IO-Link device of
the same type (validation via vendor ID and
device ID)
The IO-Link master saves the parameter
values of the connected IO-Link device once.
When connecting an IO-Link device with
factory settings, the parameter values stored in
the IO-Link master are restored automatically
on the IO-Link device.
[Vendor ID]
ID of the manufacturer that is to
be validated
0
...
65535
Factory setting: 0
ifm electronic: 310
[Device ID]
ID of the IO-Link device that is to
be validated
0
...
16777215
Factory setting: 0
► Save changed values on the device.
>
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
LR DEVICE
8.1.8
Firmware: Reset device to factory settings
7209
When the IO-Link master is reset, all parameters are set to the factory settings:
To reset the device to factory settings:
► Select [Firmware] menu.
>
The menu page shows the current settings.
► Click on [Factory Reset] to reset the device.
>
LR DEVICE sets the device to the factory settings.
>
8.1.9
Firmware: Reboot the device
18105
When rebooting the device, all settings are kept.
To restart the AL1101:
► Select [Firmware] menu.
>
The menu page shows the current settings.
► Click on [Reboot] to reboot the device.
>
LR DEVICE reboots the ifm IO-Link master.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
LR DEVICE
>
8.1.10
Configure IO-Link devices
11033
To configure the IO-Link devices connected to the device with the LR DEVICE parameter setting
software:
Requirements:
>
IO-Link master is correctly installed and connected to the LR DEVICE parameter setting software.
>
The IO-Link device is correctly connected to the AL1101.
>
Operating mode of the IO-Link port is "IO-Link" (→ IO-Link ports: Configure operating mode (→ p. 27)).
>
IoT has write access rights to the IO-Link master (→ IoT: Configure access rights (→ p. 24)).
1
Select IO-Link master
► Start LR DEVICE.
► Update IODD file library
OR:
Import IODD file of the IO-Link device manually.
► Scan network for devices.
>
LR DEVICE detects IO-Link master.
2
Add IO-Link device
► Under [ONLINE]: Click on the required IO-Link master.
>
LR DEVICE automatically detects the IO-Link devices connected to the IO-Link master (e.g. ifm sensor KG5065).
3
Configure IO-Link device
► Mouse click on the port to which the IO-Link device is connected.
>
LR DEVICE reads and shows the current parameter values of the IO-Link device.
► Configure IO-Link device.
Information about the available parameters of the IO-Link device: → IO Device Description
(IODD) of the IO-Link device
► Save the changed configuration on the IO-Link device.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
PROFINET
>
8.2
PROFINET
Install GSD file ........................................................................................................................................32
Add the IO-Link master to the PROFINET network ...............................................................................33
Configure access rights ..........................................................................................................................35
Configure IO-Link ports ..........................................................................................................................36
Configure the PROFINET port................................................................................................................37
Configure IO-Link devices ......................................................................................................................37
Read and write data cyclically ................................................................................................................38
PROFINET: Read & write device information ........................................................................................38
PROFINET: Programmers' notes ...........................................................................................................39
22758
On the field bus side, the device can be configured with the following options:
PROFINET projection software STEP 7 (version 5.5 SP 4 or higher)
PROFINET projection software TIA portal
Further information about operation and functions of the PROFINET parameter setting
software:
► Use the help function of the PROFINET projection software!
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
PROFINET
>
8.2.1
Install GSD file
22410
To represent the AL1101 in a field bus projection software (e.g. STEP 7), ifm provides a GSD file. The
user can download the GSD file from the ifm website (→ (www.ifm.com)). In the GSD file, all
parameters, process data, and their valid value ranges are defined.
To add the AL1101 to the STEP 7 hardware catalogue:
► Download GSD file of the AL1101 from the ifm website.
► Start STEP 7 application "HW Config".
► Select [Options] > [Install GSD files…].
>
The [Install GSD files] window appears.
► Click on [Browse …].
► Select the GSD file of the AL1101 and click on [OK] to adopt the file.
>
The selected GSD file appears in the list.
► Select the GSD file in the list and click on [Install].
>
STEP 7 installs the GSD file and adds the IO-Link master to the hardware catalogue.
After installation of the GSD file, the AL1101 is in the hardware catalogue in the following folder:
>
[PROFINET IO] > [Addiotional Field Devices] > [IO] > [ifm electronic]
1
AL1101
2
IO-Link ports
3
PROFINET modules
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
PROFINET
>
8.2.2
Add the IO-Link master to the PROFINET network
22406
The configuration of the PROFINET parameters is done via the PROFINET projection software.
The PROFINET parameters define which data is transmitted between AL1101 and the higher-level
PROFINET controller.
Requirements:
>
PROFINET has read and write permission on the AL1101 (→ IoT: Configure access rights (→ p. 24))
>
The GSD file of the AL1101 is installed (→ Install GSD file (→ p. 32))
1
Create/open project
► Create new PROFINET project.
OR
Open an existing PROFINET project.
► Configure PROFINET connection.
2
Add the IO-Link master to project
► Open STEP-7 application "HW Config".
>
Program window shows the hardware structure of the project.
► Open hardware catalogue.
► Move the [AL1101] node via drag&drop from the hardware catalogue to the PROFINET connection.
>
STEP 7 shows the device as PROFINET bus participant.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
PROFINET
3
Add IO-Link ports
► Move the [4 Ports] node via drag&drop from the hardware catalogue to slot 1 of the AL1101.
>
Step 7 shows available IO-Link interfaces.
► Save the project.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
PROFINET
>
8.2.3
Configure access rights
22760
In order to configure the access rights to the device:
1
Open device editor
► Open STEP-7 application "HW Config".
>
Program window shows the hardware structure of the project.
► Click on IO-Link master.
>
The device editor shows the current configuration of the IO-Link master.
2
Configure access rights
► Double click on the slot line [1.1 IO-Link Master]
>
The window [Properties IO-Link master] appears.
► Select [Parameters] tab.
► Set the following parameter as required: [Access Rights] (→ Parameter of the IO-Link master (→ p. 53))
► Click on [Add] to save the changes.
If parameter [Access Rights] = PROFINET + IoT:
Different parameter settings in the PROFINET projection software and the LR DEVICE may
cause undesired system behaviour. Parameter settings applied by the PROFINET projection
software always overrule the settings applied by LR DEVICE.
Changes of the parameter [Access Rights] are only effective after restarting the device
(→ Firmware: Reboot the device (→ p. 29))
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
PROFINET
>
8.2.4
Configure IO-Link ports
17306
In STEP 7, the following assignment of the PROFINET slots to the IO-Link ports of the device applies:
Slot
Subslot
IO Link port of AL1101
1
2
X01
3
X02
...
...
5
X04
Each sub-slot can be configured for cyclic transmission of process data with a PROFINET module.
The selected PROFINET module determines the operation type of the IO-link interface and the
configurable parameters.
Overview of the available PROFINET modules: → PROFINET modules (→ p. 56)
To add a PROFINET module to a sub-slot:
1
Open device editor
► In "HW Config": Click on IO-Link master.
>
The device editor shows the current configuration of the IO-Link master.
2
Add PROFINET module
► Open hardware catalogue.
► Drag and drop the required PROFINET module of the IO-Link master from the hardware catalogue to the slot.
>
The device editor shows the slot with the selected PROFINET module.
3
Set parameters of the PROFINET module
► Double click on the added slot.
>
Window [Properties] appears.
► Select [Paramerters] tab.
>
The page shows the current parameter settings of the IO-Link ports.
► Set the parameters as required (marked with X in table):
Operating mode of the IO-Link
ports
Available parameters
Fail Safe
Mode
Pattern
Value
Validation /
Data
storage
Vendor
ID (VID)
Device ID
Port cycle
time
IO-Link
Events
DI: Digital input
--
--
--
--
--
--
X
DO: Digital output
X
--
--
--
--
--
X
IO-Link: Input
--
--
X
X
X
X
X
IO-Link: Output
X
X
X
X
X
X
X
IO-Link: Input and output
X
X
X
X
X
X
X
Further information about the parameters of the PROFINET modules: → Parameters of the
IO-Link ports (→ p. 54)
► Click on [OK] to save the changes.
>
Changed settings are applied.
>
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
PROFINET
8.2.5
Configure the PROFINET port
22761
In order to configure the Ethernet interface of the AL1101:
Prerequisites
>
AL1101 is correctly integrated in the PROFINET project (→ Add the IO-Link master to the PROFINET network
(→ p. 33)).
1
Open object characteristics
► Start the application "HW Config"
► Click on AL1101.
► Select [Target System] > [Ethernet ...] > [Edit Ethernet Users].
>
[Edit Ethernet Users] window appears.
2
Search AL1101
► Click on [Browse ...] button.
>
[Browse Network] window appears.
► Click on [Start] button.
>
STEP 7 browses the PROFINET network for devices.
>
List shows found devices.
► Select AL1101 in list and click [OK] to adopt the device.
>
The [MAC address] shows the MAC address of the AL1101
3
Set IP address and network mask
► Click on the [Use IP parameters] selection field in group [Set IP configuration].
► Enter the required IP address in the [IP address] field.
► Enter the required subnet mask in the [Subnet mask] field.
4
Assign device names
► Enter the required PROFINET name in the [Device name] field.
► Click on the [Assign Name] button.
>
STEP 7 assigns the selected name to the AL1101.
► Click on the [Close] button to close the window.
>
8.2.6
Configure IO-Link devices
18428
The AL1101 supports the configuration of the connected IO-Link devices out of the PROFINET
projection software. The configurable parameters depend on the corresponding IO-Link device.
Information about the usable functions: → PROFINET: Programmers' notes (→ p. 39)
Available parameters of the IO-Link devices: → Operating instructions of the IO-Link device
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
PROFINET
>
8.2.7
Read and write data cyclically
17372
► To check the validity of the cyclic process data, evaluate the PQI byte (→ Mapping: IO-Link
port information).
Even with an interruption of the fieldbus connection the PQI byte indicates that the process
data is valid. This can have unintended impact on the control process.
► Take suitable measures to detect an interruption of the fieldbus connection.
>
8.2.8
PROFINET: Read & write device information
22783
I&M0 provide the user with device-specific basic information. This ensures reliable identification of the
device, the device's hardware and software components, and the manufacturer.
The datasets I&M1 to 3 offer the programmer the possibility to store project-specific information on the
device.
The programmer can access the I&M0 datasets of the slots 0 and 1 in the PROFINET projection
software via the following functions:
Information about the usable function blocks: → PROFINET: Programmers' notes (→ p. 39)
Further information about the I&M datasets: → I&M datasets (→ p. 58)
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
PROFINET
>
8.2.9
PROFINET: Programmers' notes
12761
The programmer can access on the following data from the PLC application:
Read device information of the AL1101
Read diagnostics and alarms
Set parameters of the connected IO-Link devices
The following sections show the available options.
Further information about the functional/operational blocks: → Help function of the PROFINET
projection software
>
Read and write I&M datasets
2261
Symbol / function
block
Meaning
Remarks
GET_IM_DATA / FB
Function block for reading the I&M datasets of
a device
GET_IM_DATA only supports the reading
of the I&M0 dataset
Input parameters:
IM_TYPE = 0
RDREC
Function block for acyclic reading of datasets
Input parameters:
I&M0: Index = 0xAFF0
I&M1: Index = 0xAFF1
I&M2: Index = 0xAFF2
I&M3: Index = 0xAFF3
WRREC
Function block for acyclic writing of datasets
Observe access rights on datasets!
Input parameters:
I&M1: Index = 0xAFF1
I&M2: Index = 0xAFF2
I&M3: Index = 0xAFF3
>
Detect diagnostics and alarms
2272
Symbol /
operational block
Meaning
Remarks
I/O_FLT1 /
OB82
Diagnostic alarms
I/O_FLT2 /
OB83
Pull/plug in alarms
RACK_FLT /
OB86
Module rack failure
Available alarms and diagnostic messages: → Diagnostic and alarms (→ p. 60)
>
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Configuration
PROFINET
Configure IO-Link devices
1860
Symbol / function
block
Description
Remarks
IO_LINK_DEVICE /
FB5001
Acyclic access to the parameters of an IO-Link
device
Input parameters:
CAP: Access point for function
AL1101: 0xB400
PORT: HW-ID: Slot/sub-slot of the IO-Link port
with connected IO-Link device
Port X01: 1
Port X02: 2
...
Port X04: 4
IOL_INDEX and IOL_SUBINDEX: depends on
the IO-Link device (→ operating instructions of
the IO-Link device)
IOL_CALL /
FB1
Acyclic access to the parameters of an IO-Link
devices (obsolete)
→ IO_LINK_DEVICE
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Operation
Identify device
9
Operation
Identify device .........................................................................................................................................41
Web interface: Read device and diagnostic information ........................................................................42
Firmware update .....................................................................................................................................43
Replace IO-Link device ..........................................................................................................................44
22368
>
9.1
Identify device
22816
In the online mode, the user can identify the device using the status LEDs RDY, BF and SF
► Start LR DEVICE.
► Scan network for devices.
>
LR DEVICE detects the device.
► Click on the selection field next to the device name.
>
The status LEDs on the unit flash asynchronously.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Operation
Web interface: Read device and diagnostic information
>
9.2
Web interface: Read device and diagnostic information
12744
In order to read the diagnostic information about the current device status via the web interface:
► Connect laptop/PC and AL1101 via the Ethernet internet.
► Start web browser.
► Enter the IP address of the AL1101 into the address field of the browser and press [ENTER] to confirm.
>
Web browser shows the web interface of the device.
>
The page shows the following data:
Table with connected IO-Link devices
Name
Description
[Port]
Number of the IO-Link interface
[Mode]
Operating mode of the IO-Link interface
[Comm. Mode]
Baud rate of the IO-Link interface
[MasterCycleTime]
Cycle time
[Vendor ID]
ID of the manufacturer of the IO-Link device
[Device ID]
ID of the IO-Link device
[Name]
Article number of the IO-Link device
For ifm articles: This article number is stored along with a link to the produkt page on
the ifm website.
[Serial]
Serial number of the IO-Link device
[LR Mode / Interval]
Cycle time for the communication with the SmartObserver
Diagnostic information of the device
Name
Description
[SW-Version]
[Current]
Current (in mA)
[Voltage]
Voltage (in mV)
[Short Circuit]
Number of detected short circuits
[Overload]
Number of detected overloads
[Undervoltage]
Number of detected under voltages
[Temperature]
Device temperature (in °C)
Version information of the installed firmware components
Name
Description
[Firmware]
Firmware version
[Container]
Version of the firmware container
[Bootloader Version]
Version of the boot loader
[Fieldbus Firmware]
Version of the PROFINET firmware
>
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Operation
Firmware update
9.3
Firmware update
22425
The new firmware is installed via the device's web interface.
If the firmware update is not successful, deactivate all connections to the PROFINET PLC, LR
SMARTOBSERVER and LR DEVICE and repeat the process.
► Close connection to PROFINET PLC.
► Set the parameter [IP address SmartObserver] to 255.255.255.255 or 0.0.0.0 (→ IoT:
Configure the interface to the LR SMARTOBSERVER (→ p. 25)).
► Stop the LRAgent.LRDevice service in the Windows task manager.
After the firmware update check the settings of the LR SMARTOBSERVER interface!
To install a new firmware version on the device:
Requirements
>
File with new firmware has been downloaded.
>
Ethernet connection between laptop/PC and device is established.
1
Call up web interface
► Start web browser.
► Enter the following into the address field of the browser and press [ENTER] to confirm:
http:///web/update
>
Web browser shows the [Firmware Update] page.
2
Load new firmware to AL1101
► Click on [Select file].
>
Dialogue window appears.
► Select the firmware file and click on [Open] in order to adopt the file.
► Click on [Submit] to start the firmware update.
>
Firmware is being loaded to the device.
>
After successful storage, the success message is displayed
3
Restart the device
► Click on [Restart device now] to restart the device.
>
The status LED RDY flashes quickly.
>
Firmware is updating.
► Follow the instructions in the browser.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Operation
Replace IO-Link device
>
9.4
Replace IO-Link device
7775
To replace an IO-Link device:
Requirement:
>
IO-Link device is with factory settings.
>
IO-Link device supports IO-Link standard 1.1 or higher.
1
Set data storage
► Set the following parameters of the IO-Link port:
Validation and Data Storage = [Type compatible V1.1 device with Restore]
► Save changes.
2
Replace IO-Link device
► Disconnect old IO-Link device from IO-Link master.
► Connect new IO-Link device with the same IO-Link port of the AL1101.
>
IO-Link master copies parameter values from the data memory to the new IO-Link device.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Maintenance
Replace IO-Link device
10
Maintenance
21577
The operation of the unit is maintenance-free.
► Clean the surface of the unit when necessary. Do not use any caustic cleaning agents for this!
► After use, dispose of the unit in an environmentally friendly way in accordance with the applicable
national regulations.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Factory settings
Replace IO-Link device
11
Factory settings
22671
In the factory settings, the device has the following parameter settings:
Parameters
Factory setting
[IP address]
0.0.0.0
[Subnet mask]
0.0.0.0
[IP gateway address]
0.0.0.0
[PROFINET name]
blank
Data Storage
empty
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Accessories
Replace IO-Link device
12
Accessories
17853
List of accessories of AL1101: → www.ifm.com > Product page > Accessories
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
Replace IO-Link device
13
Appendix
Technical data ........................................................................................................................................49
PROFINET..............................................................................................................................................53
ifm IoT Core ............................................................................................................................................60
7156
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
Technical data
>
13.1
Technical data
Application ..............................................................................................................................................49
Electrical data .........................................................................................................................................49
Inputs / outputs .......................................................................................................................................49
Inputs ......................................................................................................................................................50
Outputs ...................................................................................................................................................50
Interfaces ................................................................................................................................................50
Operating conditions ...............................................................................................................................51
Approvals / tests .....................................................................................................................................51
Mechanical data .....................................................................................................................................51
Electrical connection ...............................................................................................................................52
9011
>
13.1.1
Application
23710
Application
Application
Hygienic systems; I/O modules for field applications
Daisy-chain function
Fieldbus interface
>
13.1.2
Electrical data
22819
Electrical data
Operating voltage [V]
20...28 DC; (US; to SELV/PELV)
Current Consumption [mA]
300...3900; (US)
Protection class
III
Sensor supply US
Max. current load total [A]
3.6
>
13.1.3
Inputs / outputs
23711
Inputs / outputs
Total number of inputs and outputs
8; (configurable)
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
Technical data
>
13.1.4
Inputs
22820
Inputs
Number of digital inputs
8; (IO-Link Port Class A: 4 x 2)
Switching level high [V]
11...28 DC
Switching level low [V]
0...5 DC
Digital inputs protected against short circuits
yes
>
13.1.5
Outputs
22821
Outputs (digital)
Output function
4; (IO-Link Port Class A: 4 x 1)
Max. current load per output [mA]
200
Short-circuit protection
yes
>
13.1.6
Interfaces
22630
Interfaces
Communication interface
Ethernet; IO-Link
Communication interface
IO-Link; TCP/IP; PROFINET IO
Ethernet
Transmission standard
10Base-T; 100Base-TX
Transmission rate
10; 100
Protocol
TCP/IP; PROFINET IO
Factory settings
IP address: 0.0.0.0
Subnet mask: 0.0.0.0
Gateway IP address: 0.0.0.0
MAC address: see type label
IO-Link Master
Transmission type
COM 1 / COM 2 / COM 3
IO-Link revision
V1.1
Number of ports class A
4
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
Technical data
>
13.1.7
Operating conditions
22823
Operating conditions
Applications
Indoor use
Ambient temperature [°C]
-25...60
Storage temperature [°C]
-25...85
Max. perm. relative air humidity [%]
90
Max. height above sea level [m]
2000
Protection rating
IP 65; IP 66; IP 67
Pollution Degree
2
>
13.1.8
Approvals / tests
22824
Approval / tests
EMC
EN 61000-6-2
EN 61000-6-4
MTTF [Years]
90
>
13.1.9
Mechanical data
22825
Mechanical data
Weight [g]
271,6
Materials
Housing: PA grey; socket: stainless steel (1.4404 / 316L)
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
Technical data
>
13.1.10
Electrical connection
17850
Voltage supply IN X31
Plug and socket connection
M12
Wiring
1:
+ 24 V DC (US)
2:
-
3:
GND (US)
4:
-
Ethernet IN / OUT X21, X22
Plug and socket connection
M12
Wiring
1:
TX +
2:
RX +
3:
TX -
4:
RX -
5:
-
IoT X32
Plug and socket connection
M12
Wiring
1:
TX +
2:
RX +
3:
TX -
4:
RX -
5:
-
Process connection IO-Link ports Class A X01...X0
Plug and socket connection
M12
Wiring
1:
+ 24 V DC (US)
2:
DI
3:
GND (US)
4:
C/Q IO-Link
5:
-
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
PROFINET
>
13.2
PROFINET
Parameter data .......................................................................................................................................53
Cyclic data ..............................................................................................................................................56
Acyclic data ............................................................................................................................................58
22433
>
13.2.1
Parameter data
22786
Slot
Sub-slot
Name
Description
1
1
Master
Parameter data of the IO-Link master (→ Parameter of the IO-Link master (→ p. 53))
2
Port X01
Parameter data of the IO-Link ports (→ Parameters of the IO-Link ports (→ p. 54))
Fieldbus modules (→ PROFINET modules (→ p. 56))
3
Port X02
4
Port X03
5
Port X04
>
Parameter of the IO-Link master
22788
Parameter
Description
Possible values
[Access Rights]
The access rights to the
parameter data, process data and
events/diagnostic messages of
the IO-Link master and the
connected IO-Link devices
PROFINET +
LineRecorder
PROFINET and LR DEVICE have read
and write access rights to parameters
and process data
PROFINET and LR DEVICE have read
access rights to events/alarms
PROFINET +
LineRecorder (ro)
PROFINET has read and write access
rights to parameters and process data
PROFINET has read access rights to
events/alarms
LR DEVICE only has read access
rights to parameters, process data and
events/alarms
PROFINET only
PROFINET has read and write access
rights to parameters and process data
PROFINET has read access rights to
events/alarms
LR DEVICE has no access rights
(parameters, process data,
events/alarms, web interface, firmware
update)
keep setting
keeps settings
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
PROFINET
>
Parameters of the IO-Link ports
22787
Parameter
Description
Possible values
[Fail-safe mode]
Behaviour in case the PROFINET
connection is interrupted
No Fail Safe
deactivated
Fail Safe Reset Value reset to default values
Fail Safe Old Value
maintain the most recent valid process
value
Fail Safe with Pattern
set user-defined values
[Pattern Value]*
required values for the process
data in case the connection is
interrupted
(as hexadecimal value)
Pattern depends on the size of the
selected PROFINET module
Per byte:
0x00 ... 0xFF
[Port cycle time]
Cycle time of the data transmission at
the IO-Link port
as fast as possible
The device automatically sets the
fastest possible cycle time
2.0 ms
...
128.0 ms
2 milliseconds
...
128 milliseconds
[Validation / Data
Storage]
Supported IO-Link standard and
behaviour of the AL1101 when a new
IO-Link device is connected to the
IO-Link port
no check and clear
no verification of the vendor ID and
device ID
no data storage
Type compatible V1.0
device
IO-Link device is compatible with
the V1.0 IO-Link standard
Verification whether it is an IO-Link
device of the same type (validation
via vendor ID and device ID)
no data storage
Type compatible V1.1
device
IO-Link device is compatible with
the V1.1 IO-Link standard
Verification whether it is an IO-Link
device of the same type (validation
via vendor ID and device ID)
no data storage
Type compatible V1.1
device with Backup +
Restore
IO-Link device is compatible with
the V1.1 IO-Link standard
Verification whether it is an IO-Link
device of the same type (validation
via vendor ID and device ID)
The IO-Link master saves the
parameter values of the connected
IO-Link device; modifications of
the parameter values are also
stored (→ observe the note!)
When connecting an IO-Link device
with factory settings, the parameter
values stored in the IO-Link master
are restored automatically on the
IO-Link device.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
PROFINET
Parameter
Description
Possible values
Type compatible V1.1
device with Restore
IO-Link device is compatible with
the V1.1 IO-Link standard
Verification whether it is an IO-Link
device of the same type (validation
via vendor ID and device ID)
The IO-Link master stores the
parameter values of the connected
IO-Link device once if the data
memory of the AL1101 is empty.
When connecting an IO-Link device
with factory settings, the parameter
values stored in the IO-Link master
are restored automatically on the
IO-Link device.
[Vendor ID (VID)]
ID of the manufacturer that is to be
validated
0 ... 65535
ID of the manufacturer of the IO-Link
device (ifm electronic: 310)
[Device ID]
ID of the IO-Link device that is to be
validated
0 ... 16777215
ID of the IO-Link device
[IO-Link Events]
Enable / disable the transmission of
IO-Link events
Diabled
IO-Link won't be transmitted
Enabled
IO-Link events will be transmitted
* ... settings are only valid if [Fail Safe Mode] = Fail Safe with Pattern
If the parameter values of an IO-Link device are changed with IO_LINK_DEVICE, the backup
mechanism remains ineffective. The changed parameter values are not stored on the IO-Link
master.
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
PROFINET
>
13.2.2
Cyclic data
PROFINET modules ...............................................................................................................................56
PQI (Port Qualifier Information) ..............................................................................................................57
22429
>
PROFINET modules
22685
Module
Description
IO-Link 32I/32O + PQI
IO-Link activated
32 bytes input and output data and PQI
IO-Link 16I/16O + PQI
16 bytes input and output data and PQI
IO-Link 8I/8O + PQI
8 bytes input and output data and PQI
IO-Link 4I/4O + PQI
4 bytes input and output data and PQI
IO-Link 2I/ 2O + PQI
2 bytes input and output data and PQI
IO-Link 1I/1O + PQI
1 byte input and output data and PQI
IO-Link 1I/15O + PQI
1 byte input and 15 bytes output data and PQI
IO-Link 32I + PQI
32 bytes input data and PQI
IO-Link 16I + PQI
16 bytes input data and PQI
IO-Link 8I + PQI
8 bytes input data and PQI
IO-Link 4I + PQI
4 bytes input data and PQI
IO-Link 2I + PQI
2 bytes input data and PQI
IO-Link 1I + PQI
1 bytes input data and PQI
IO-Link 32O + PQI
32 bytes output data and PQI
IO-Link 16O + PQI
16 bytes output data and PQI
IO-Link 8O + PQI
8 bytes output data and PQI
IO-Link 4O + PQI
4 bytes output data and PQI
IO-Link 2O + PQI
2 bytes output data and PQI
IO-Link 1O + PQI
1 bytes output data and PQI
DI + PQI
IO-Link deactivated
Digital input and PQI
DO + PQI
Digital output and PQI
Disabled
deactivated
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
PROFINET
>
PQI (Port Qualifier Information)
22686
Port Qualifier Information (PQI) contains diagnostic information about the IO-Link port. In addition to
the process data, the IO-Link master sends the PQI to the PROFINET controller.
Bit
7
6
5
4
3
2
1
0
PQ
DE
DA
--
--
--
DI2
DI4
Legend:
[DI4]
Signal status of the digital input on pin 4 (DI)
FALSE
OFF
TRUE
ON
[DI2]
Signal status of the digital input on pin 2 (if used)
FALSE
OFF
TRUE
ON
[DA]
Device Available: shows if the IO-Link device has been recognised and if the
device is in the "preoperate" or in the "operate" state
FALSE
no device
TRUE
device detected
[DE]
Device Error: shows if an error or a warning occurred; Note: The user needs to
determine the cause of the fault separately via acyclic services.
FALSE
no error
TRUE
error detected
[PQ]
Port Qualifier: shows if IO data is valid
FALSE
invalid
TRUE
valid
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
PROFINET
>
13.2.3
Acyclic data
I&M datasets ...........................................................................................................................................58
Diagnostic and alarms ............................................................................................................................60
22427
>
I&M datasets
22778
The AL1101 supports the following I&M datasets (I&M = Identification & Maintenance):
>
I&M0 (Slot 0)
22779
Variable
Description
Access*
Size
Vendor ID
IO-Link ID of the manufacturer
r
2
OrderID
Order number of the device (numbers are separated by blanks)
r
20
Serial number
Serial number of the device (numbers separated by blanks)
r
16
Hardware revision
Hardware revision of the device
r
2
Software revision prefix
Prefix of the software revision of the device (V, R, P, U or T)
r
1
Software Revision
Software revision (numbers separated by blanks, e.g. x y z in "Vx.y.z")
r
3
Revision Counter
Revision counter; is incremented with each parameter change
r
2
Profile ID
ID of sub-module profile (Slot 0: 0x0000)
r
2
Profile Specific Type
additional value for profile ID; 0, if not used
r
2
IMVersion
I&M version (default value: 0x0101)
r
2
IMSupported
Suported I&M datasets (0x1110 for I&M1-3)
r
2
* ... r = only read
>
I&M1 (Slot 0)
22765
Variable
Description
Access*
Size
TagFunction of submodule
function of the device (ASCII, padded with spaces)
r/w
32
TagLocation of submodule
Location of the device in the plant (ASCII, padded with spaces)
r/w
22
* ... r/w = read and write
>
I&M2 (Slot 0)
22780
Variable
Description
Access*
Size
Installation_Date
Installation date of the device (ASCII, padded with spaces)
r/w
16
reserved
r/w
38
* ... r/w = read and write
>
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
PROFINET
I&M3 (Slot 0)
22781
Variable
Description
Access*
Size
Descriptor
Description of the device (ASCII, padded with spaces)
r/w
54
* ... r/w = read and write
>
I&M0 (Slot 1)
22782
Variable
Description
Access*
Size
Vendor ID
IO-Link ID of the manufacturer
r
2
OrderID
Order number of the device (numbers are separated by blanks)
r
20
Serial number
Serial number of the device (numbers separated by blanks)
r
16
Hardware revision
Hardware revision of the device
r
2
Software revision prefix
Prefix of the software revision of the device (V, R, P, U or T)
r
1
SOFTWARE_REVISION
Software revision (numbers separated by blanks, e.g. x y z in "Vx.y.z")
r
3
REVISION_COUNTER
Revision counter; is incremented with each parameter change
r
2
Profile ID
ID of the sub-module profile (Slot 1: 0x4E01 = IOLink)
r
2
Profile Specific Type
additional value for profile ID; 0, if not used
r
2
IMVersion
I&M version (default value: 0x0101)
r
2
IMSupported
Supported I&M datasets (0x0E for I&M1-3)
r
2
* ... r = only read
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Appendix
PROFINET
>
Diagnostic and alarms
22784
ECD
code
Name
Description
Type
0x02
EVNT_CODE_M_PDU_CHECK
Receive frame with CRC error
Alarm
0x1B
EVNT_CODE_S_RETRY
Repetitions detected
Alarm
0x1E
EVNT_CODE_P_SHORT
Short circuit on C/Q cable detected
Diagnostics
0x1F
EVNT_CODE_P_SENSOR
Error in the sensor supply
Diagnostics
0x20
EVNT_CODE_P_ACTOR
Error in the actuator supply
Diagnostics
0x21
EVNT_CODE_P_POWER
Error in the power supply of the IO-Link master
Diagnostics
0x28
EVNT_CODE_DSREADY_NOACTION
Data storage completed, but no action, since CRC was
correct
Alarm
0x29
DS_FAULT_IDENT
Sensor does not match the content of the data memory
Alarm
0x2A
DS_FAULT_SIZE
Sensor parameters too large for data memory
Alarm
0x2B
DS_FAULT_UPLOAD
Error during data memory transmission from the sensor
Alarm
0x2C
DS_FAULT_DOWNLOAD
Error during data memory transmission to the sensor
Alarm
0x2F
DS_FAULT_DEVICE_LOCKED
Error during data storage because the device is blocked
Alarm
0x32
EVNT_CODES_DSREADY_DOWNLOAD
Parameter transmission to the sensor finished
Alarm
0x33
EVNT_CODE_DSREADY_UPLOAD
Parameter transmission from the sensor finished
Diagnostics
>
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Index
14
Index
A
Accessories ........................................................................................... 47
Acyclic data ............................................................................................ 58
Add the IO-Link master to the PROFINET network .............................. 33
Appendix ................................................................................................ 48
Application ............................................................................................. 49
Approvals / tests .................................................................................... 51
C
CAN standard units................................................................................ 39
Communication, parameter setting, evaluation ..................................... 11
Configuration ......................................................................................... 21
Configure access rights ......................................................................... 35
Configure IO-Link devices ........................................................ 30, 37, 40
Configure IO-Link ports ......................................................................... 36
Configure the PROFINET port............................................................... 37
Connect the device ................................................................................ 17
Cyclic data ............................................................................................. 56
D
Detect diagnostics and alarms .............................................................. 39
Diagnostic and alarms ........................................................................... 60
Digital inputs .......................................................................................... 12
E
Electrical connection ........................................................................14, 52
Electrical data ........................................................................................ 49
Ethernet interface .................................................................................. 19
Ethernet ports ........................................................................................ 15
F
Factory settings ..................................................................................... 46
Fieldbus
Set PROFINET interface ............................................................................... 25
Firmware
Reboot the device ......................................................................................... 29
Reset device to factory settings .................................................................... 29
Firmware update .................................................................................... 43
Function ................................................................................................. 10
G
General .................................................................................................... 7
I
I&M datasets .......................................................................................... 58
I&M0 (Slot 0) .......................................................................................... 58
I&M0 (Slot 1) .......................................................................................... 59
I&M1 (Slot 0) .......................................................................................... 58
I&M2 (Slot 0) .......................................................................................... 58
I&M3 (Slot 0) .......................................................................................... 59
Identify device ........................................................................................ 41
Input circuit ............................................................................................ 16
Inputs ..................................................................................................... 50
Inputs / outputs ...................................................................................... 49
Install GSD file ....................................................................................... 32
Intended use ............................................................................................ 9
Interfaces ............................................................................................... 50
IO-Link ................................................................................................... 11
IO-Link circuits ....................................................................................... 16
IO-Link ports .......................................................................................... 16
Activate data transfer to the LR SMARTOBSERVER .................................. 26
Configure operating mode............................................................................. 27
Set the device validation and data storage................................................... 28
IO-Link ports (Class A) .......................................................................... 20
IO-Link supply ........................................................................................ 12
IoT
Configure access rights ................................................................................. 24
Configure the interface to the LR SMARTOBSERVER................................ 25
L
LED indicators ....................................................................................... 19
Legal and copyright information .............................................................. 5
LR DEVICE ............................................................................................ 22
M
Maintenance .......................................................................................... 45
Mechanical data ..................................................................................... 51
Modification history .................................................................................. 6
Mount the device ................................................................................... 13
Mounting ................................................................................................ 13
O
Offline parameter setting ....................................................................... 23
Operating and display elements ............................................................ 18
Operating conditions .............................................................................. 51
Operation ............................................................................................... 41
Outputs .................................................................................................. 50
Overview ................................................................................................ 18
P
Parameter data ...................................................................................... 53
Parameter of the IO-Link master ........................................................... 53
Parameter setting .................................................................................. 11
Parameters of the IO-Link ports ............................................................ 54
Permitted use ........................................................................................... 9
PI controller .............................................................................................. 5
PQI (Port Qualifier Information) ............................................................. 57
Preliminary note ....................................................................................... 5
PROFINET ................................................................................ 11, 31, 53
Programmers' notes ...................................................................................... 39
Read & write device information ................................................................... 38
PROFINET modules .............................................................................. 56
Prohibited use .......................................................................................... 9
Purpose of the document ........................................................................ 5
R
Read and write data cyclically ............................................................... 38
Read and write I&M datasets ................................................................ 39
Remarks...........................................................................................14, 23
Replace IO-Link device ......................................................................... 44
Required background knowledge ............................................................ 7
S
Safety instructions ................................................................................... 7
Safety symbols on the device .................................................................. 7
ifm Operating Instructions IO-Link Master with PROFINET interface StandardLine 4 Ports IP 65 / IP 66 / IP 67 / IP 69K (AL1101)
05 / 2018
Index
Status LEDs ........................................................................................... 19
Symbols and styles used ......................................................................... 6
T
Tampering with the unit ........................................................................... 8
Technical data ....................................................................................... 49
V
Visual indication ..................................................................................... 12
Voltage supply ....................................................................................... 20
VPN connection ..................................................................................... 23
W
Web interface
Read device and diagnostic information....................................................... 42