INSTRUCTIONS MANUAL
SETPOINT OUTPUT OPTION
INTRODUCTION TO THE KOSMOS SERIES
This manual does not constitute a formal agreement.
All information given in this manual is subject to
change without notice.
The serie KOSMOS brings a new philosophy in digital panel
instrumentation by using multipurpose, modular-concept
devices providing a rich array of basic functions and
advanced capabilities.
With a fully MODULAR DESIGN, it is possible to implement a
wide variety of applications simply by adding the desired
option(s).
Built-in intelligence allows the meter to recognize the options
installed and implement the necessary parameters to properly
function within desired parameters. The basic instrument
without output options omits these data in the program
routines.
CALIBRATION is performed at the factory eliminating the
need for adjustment potentiometers. Any circuit or option
liable to be adjusted incorporates a memory where calibration
parameters are stored, making it possible the optional cards
be totally interchangeable without need of any subsequent
adjustments.
Custom CONFIGURATION for specific applications can be
made quickly and easily through three or five front panel
keys, following structured choice menus aided by display
prompts at each programming step.
Other features of the KOSMOS family include :
CONNECTIONS via plug-in terminal blocks without
screws and CLEMP-WAGO clips cable retention system.
DIMENSIONS
Models ALPHA & BETA 96x48x120 mm DIN 43700
Models JUNIOR, JUNIOR20, & MICRA 96x48x60 mm DIN
43700
CASE MATERIAL UL-94 V0-rated poly-carbonate.
PANEL INSTALLATION by means of single part
fingertip without screws.
To guarantee the meter s technical specifications, its is advised
to check calibration parameters at periodical intervals according
to the ISO9001 standards for the particular application
operating criteria.
Re-calibration of the meter should be made at the factory or in
a qualified laboratory.
1 . GENERAL INFORMATION SETPOINTS OPTION................................................................................................................. 4
2 . SETUP AND CONNECTIONS
2.1 - INSTALLATION............................................................................................................................................ 5
2.2 - CONNECTION........................................................................................................................................... 6-7
2.3 TECHNICAL SPECIFICATIONS...................................................................................................................... 7
3 . MODE OF WORKING
3.1 INDEPENDENT SETPOINTS....................................................................................................................... 8-9
3.2 ASSOCIATED SETPOINTS ............................................................................................................................ 9
3.3 AUTO-TRACK............................................................................................................................................ 10
4 . PROGRAMMING
4.1. MODELS MICRA ............................................................................................................... 11-12-13-14-15-16
4.2. MODELS ALPHA ............................................................................................................... 17-18-19-20-21-22
4.2. MODEL BETA-M ...........................................................................................23-24-25-26-27-28-29-30-31-32
An option of 2 or 4 SETPOINTS, programmable within the full
display range, can be incorporated to the unit thus providing
alarm and control capabilities by means of individual LED
indicators and relay or transistor outputs.
All the setpoints provide independently programmable value,
time delay (in seconds), asymmetrical or symetrical hysteresis
(in counts of display) and selectable HI/LO acting.
The setpoints are also configurable to activate independently
(each one activates at its corresponding programmed value) or
tracking one another (setpoint 2 can be conditioned by the
action of setpoint 1, setpoint 4 by setpoint 3). Such latter
function is included in the programming menus with the name
of "TRAC" and, in case of the setpoint 2, it can be manual or
automatic.
The setpoint option consists of a plug-in additional card that
once installed to the meter's main board, activates its own
programming module. The setpoints programming may be
locked out by means of DIP-switches located on the main
board to prevent from accidental or unauthorized changes.
The available alarm/setpoint output options are the following:
2RE: 2 SPDT relays rated 8A
4RE: 4 SPST relays rated 5A*
4OP: 4 isolated open-collector transistors NPN
4OPP: 4 isolated open-collector transistors PNP
These type of outputs, capable of carrying out a wide variety
of control operations and processing of limit values, increases
notably the unit's performance qualities thanks to the
possibility of combining basic alarm functions with advanced
safety and control applications.
* from nº O5397
1. SETPOINTS OPTION
2. SETUP AND CONNECTIONS
5
2.1
INSTALLATION
Lift out the electronics assembly from the case and use a
screw-driver to push on the junctions between the case and
the shadow areas to detach them from the case. See fig1.
The so performed orifice will allow any of the setpoints
board output connectors be brought out at the rear of the
instrument.
The option is installed by plugging the
connector in the main board location as shown
in fig. 2 .
Insert the card pin in the corresponding main board
slot (see figure) and push down to attach both connectors.
If the instrument is to be installed in high vibrating
environments, it is recommended to solder the card to the
main board making use of the copper tracks on both sides of
the card pin and around the main board hole on its solder
side.
Before inserting the electronics in the case, you should
verify that the access to the setpoints programming module
is enabled, as this is the first operation to be made once the
instrument is powered up.
MICRAs
ALPHA/ BETA
2RE- 4RE 4OP - 4OPP
fig. 2
2.2 - CONNECTION
NOTE : In case that the outputs are used to drive inductive
loads, it is recommended to add an RC network between the
coil terminals (preferably) or between the relay contacts to
limit electromagnetic effects.
LCIA-01 - 2 RELAYS OPTION
PIN 4 = N. Open 2
PIN 1 = N. Open 1
PIN 5 = COMMON 2
PIN 2 = COMMON 1
PIN 6 = N. Closed 2
PIN 3 = N. Closed 1
LCIA-02 - 4 RELAY OPTION
PIN 4 = RL4
PIN 1 = RL1
PIN 5 = Non connected
PIN 2 = RL2
PIN 6 = COMMON
PIN 3 = RL3
LCIA-03 - 4 OPTOS NPN OPTION
PIN 4 = OP4
PIN 1 = OP1
PIN 5 = Non connected
PIN 2 = OP2
PIN 6 = COMMON
PIN 3 = OP3
LCIA-04 - 4 OPTOS PNP OPTION
PIN 4 = OP4
PIN 1 = OP1
PIN 5 = Non connected
PIN 2 = OP2
PIN 6 = COMMON
PIN 3 = OP3
Fig. 6.1: Rear view of basic
instrumment with Relay / Opto
output option.
Fig. 6.2: Connection diagram
for 2RE
Fig. 6.3: Connection diagram
for 4RE
Fig. 6.4: Connection diagram
for 4OP
Fig. 6.5: Connection diagram
for 4OPP
COMMON
COMMON
COMMON
RELAY
1
RELAY 2
RELAY 4
RELAY
1
RELAY
2
RELAY
1
3
2
CN6
CN7
4
6
5
2.3 TECHNICAL SPECIFICATIONS
2RE OPTION
Max. current (resistive load) ................................... 8 A
Max. Power........................................2000 V @ 192 W
Max. Voltage................................. 250 V AC/ 150 V DC
Contact resistance...................................... max. 3 m
Switching time ...........................................max. 10 ms
4RE OPTION
Max. current (resistive load) ................................... 5 A
Max. Power........................................1250 V A/ 150 W
Max. Voltage................................. 277 V AC/ 125 V DC
Contact resistance.....................................max. 30 m
Switching time ...........................................max. 10 ms
4OP OPTION
Max. Voltage...................................................50 V DC
Max. current ..................................................... 50 mA
Leakage current.....................................100 A (max.)
Switching time ..........................................1 ms (max.)
4OPP OPTION
Max. Voltage...................................................50 V DC
Max. current ..................................................... 50 mA
Leakage current.....................................100 A (max.)
Switching time ..........................................1 ms (max.)
All options are opto-isolated with respect to the input
signal and main supply.
CONNECTORS
To perform wiring connections, remove
the terminal block from the meter's
connector, strip the wire leaving
from 7 to 10mm exposed and insert it
into the proper terminal while pushing the
fingertip down to open the clip inside
the connector as indicated in the figure.
Proceed in the same manner with all pins and plug the
terminal block into the corresponding meter's connector.
Each terminal can admit cables of section comprised between
0.08mm² and 2.5mm² (AWG 26 ÷ 14).
The blocks provide removable adaptors into each terminal to
allow proper fastening for cable sections of <0.5 mm².
INSTALLATION
To meet the requirements of the directive EN61010-1, where
the unit is permanently connected to the mains supply it is
obligatory to install a circuit breaking device easy reachable
to the operator and clearly marked as the disconnect device.
WARNING
In order to guarantee electromagnetic compatibility, the
following guidelines for cable wiring must be followed:
-
Power supply wires must be routed separated from
signal wires. Never run power and signal wires in the
same conduit.
-
Use shielded cable for signal wiring and connect the
shield to ground of the indicator (pin2 CN1).
-
The cable section must be 0.25 mm
I f
not
installed and used according to these
instructions, protection against hazards may be
impaired.
3. METHODS OF OPERATION
8
DESCRIPTION OF OPERATION
All the setpoints can operate independently or in association
with another in a variety of combinations to suit specific
operating conditions.
3.1 INDEPENDENT SETPOINTS.
As programmed like independent setpoints, the alarm
outputs activate when the display value reaches the user-
programmed value. The independent alarms programming
requires definition of the following basic parameters :
a. HI/LO ACTING MODE.
In HI mode, the output activates when the display rises
above the setpoint level and in LO mode, the output
activates when the display falls below the setpoint.
b. PROGRAMMABLE TIME DELAY or HYSTERESIS.
Each output action can be deferred by a programmable time
delay or hysteresis level.
The time delay is the time that takes the output to activate
after passing through the setpoint in the up or down
direction, while the hysteresis band can be selected
asymmetrical (only acts on the output deactivation edge) or
symmetrical (operates on both sides of the setpoint).
The time delay can be set from 0 to the maximum
displayable value in seconds and can have a decimal place.
The hysteresis can be programmed, in counts, within the full
display range. The decimal point appears in the same
position as programmed in the display configuration module.
Fig. 1 Delay action (dly)
Fig. 2 Asymmetrical hysteresis
The figure 1 shows the action of the symmetrical hysteresis.
In order to clarify the drawing, it has been represented one
only alarm in the cases of HI and LO acting. The 100% of
the programmed hysteresis (hys-2) is added to each side of
the setpoint, thus creating a band around the setpoint within
which the output is activated (mode HI) or deactivated
(mode LO). This band can be as large as twice the maximum
number of counts of the display.
The hold up of the alarm action by means of this type of
hysteresis can be useful in operations in which it is necessary
to keep the alarm condition between two specified points.
As an example, let's suppose that it is wanted to control a
quantity composed of two other in proportion of 1000 and
2000kg. By programming the first setpoint at 500 with hys-2
= 500 and the second setpoint at 2000 with hys-2 = 1000,
the alarm output should control the first quantity from 0 to
1000 and the second quantity from 1000 to 3000.
3.2 ASSOCIATED SETPOINTS
The SET2 and SET4 setpoints can be programmed to "track"
SET1 and SET3 respectively. This type of alarms does not
activate as compared with a preprogrammed display value
but at a programmable fixed distance from the activation of
their pre-alarms.
The programming of these alarms requires to determine first
the pre-alarm setpoint value (for example SET1 = 200).
Then, instead of programming the SET2, it is assigned an
offset between this and the first alarm (for example TRACK2
= 50). Although SET1 is changed, the alarm 2 (if not
changed) will always activate 50 counts above SET1. If a
negative tracking value should have been programmed (-
50), the alarm 2 would activate 50 counts below the SET1.
The figure .2. shows an example of positive (TRACK2) and
negative tracking (TRACK4).
Fig 1. Symmetrical hysteresis
Fig 2. Tracking setpoints
In some measurement systems and particularly in
weighing and dosage applications, the mechanical parts and
the system structure makes it impossible to shut off
operations at a given point (due to response times, weight in
fly ...) this causing an extra quantity of material be settled
after the interrupting action.
As an application example of the "AUTO TRACK"
function, let's comment the effect known as "weight in fly".
The "weight in fly" effect is produced in those systems in
which some kind of recipient is to be filled with a
preprogrammed quantity of material. Each time this quantity
is reached, an alarm output stops the filling mechanism.
However, the quantity of material which is still on air at the
moment of shutting off the process, is deposited in the
recipient exceeding from the desired measure.
The automatic track function (AUTO TRAC) is
specially designed to compensate for this out of limit
quantity.
This function is based on controlling the quantity in which
the programmed limit is surpassed and using this excess to
activate the shut off signal so that, including the out of limit
quantity, the final measure suits the desired value.
Only the alarm 2 provides automatic track function. The auto
tracking is implemented by programming SET1 for the
desired limit value and SET2 for "AUTO TRAC" opera-tion
(initially it takes the same value as SET1).
SET1 = Desired setpoint value
SET2 = AUTO TRAC
When, despite the alarm that shuts off the process
activates, still a little quantity of material exceeding from
SET1 is deposited, the excess is registered in the peak
memory as "TRAC" value and subtracted from SET2.
This way, in successive measurements the output of
SET2 will take charge of interrupting the operations one
moment before the display reaches the programmed value.
The extra quantity will then complete the measure until the
required level.
We remark that the track value is continuously
updated according to process needs.
MICRAS MODEL PROGRAMMING INSTRUCTIONS
3s?
T O IN P UT
C O N FIG U RA T IO N
M O DU L E
T O D IS PL A Y
C O N FIG U R A T IO N
M O DU L E
T O S ER IA L
O U T P UT
C O N FIG U RA T IO N
M IO D U L E
SETPOINTS PROGRAMMING MODULE
DESCRIPTION
The diagram represented on page 12 shows the setpoints programming module, which is valid for the MICRA models with 2RE
option.
Apart from the setpoint values, this option permits the user to program the following parameters :
The relays control mode ("HI" for activation above the setpoint or "LO" for activation below the setpoint)
The action mode (time delay or asymmetrical hysteresis ).
The amount of time delay in seconds or hysteresis in counts of display.
ACCESS TO THE PROGRAMMING OF THE SETPOINT VALUES
The setpoints values are directly accessible from the Pro stage in any of the programming modules
From the run mode, press "ENTER" to get access to the programming mode. Press "" and leave it to enter in the first setpoint
programming phase.
ACCESS TO THE CONTROL MODE PROGRAMMING
From the run mode, press "ENTER" to access to the programming routines ; the display will show Pro and the PROG LED will
activate. Press repeatedly the "" key until the SET1 and SET2 LED's activate.
A press of "ENTER" at this point provides access to the programming of various options as indicated on page 31.
This programming routine can be locked out (refer to the instrument instructions manual).
SETPOINTS PROGRAMMING MENU
The setpoint values change can always be accessed from any of the Pro levels even if the
programming routines are locked out.
The figure 14.1 shows the Pro indication, where the
key provides access to the
programming modules or, a press of
ENTER returns the meter to the normal operation.
To get access to the programming of the setpoint values, press the
key from this
stage (or from any other with Pro indication).
A press of
ENTER
made at previous step presents on display the current value for the
setpoint 1 with the SET1 LED activated and the last digit in flash.
If you desire to change the flashing digit value, press repeatedly the
key to rotate
from 0 to 9 and, once the digit has taken the desired value, press to move to the next
digit to be modified. Repeat these operations until the required value
for the
setpoint 1 is registered on the display and press
ENTER
to validate the entry and pass to
the next program step.
After, the initial value for the setpoint 2 appears on display (the SET2 LED activates) with
the last digit in flash.
Proceed as in the previous section :
changes the value of the active digit and
advances to the next digit to be modified.
Once the desired value is composed on the display, a press
ENTER of will return the
meter to the run mode saving the programmed parameters.
TARE
MAX/MI
N
DATA
ENTE
R
RS232C
RS485
MIN
TARE
PROG
SET 1
SET 2
MAX
F4
F2
F3
F1
The indication shown in figure 15.1 appears on the display to indicate that the next
step is to program the setpoint1 operating parameters (led Setpoint 1 activated). After
2 seconds or by a press
ENTER , the meter allows access to this menu.
The display then shows two digits: the leftmost one corresponds to the output mode
(HI or LO) and the rightmost one corresponds to the delay unit (time -delay- or counts
of display -hysteresis-) according to the table below the figure. Use the
key to
change the active digit value (in flashing) and the
key to go to the next digit to
be set.
Press
ENTER to validate selections and advance to the next phase.
[15.1] Setpoint 1 Configuration
Depending on previous phase choice, the display will show for 2 seconds the
indication corresponding to the selected delay units before giving access to the time
delay or hysteresis magnitude programming (dLY) or (HYS). After 2 seconds or by a
press of
ENTER , the initially programmed numerical value appears on the display with
the first digit in flashing. To program the desired value (from 0 to 9999 counts of
hysteresis or from 0 to 99 seconds of time delay) use the
key to increment the
active digit value and the
key to advance to the next digit to be modified.
Repeat this procedure until desired value is completed on the display and press
ENTER
to validate and access to the programming of the setpoint 2 parameters.
[15.2] SET2 Hysteresis/Delay
15
If a two relay option is installed the instrument will allow to enter on the following routines: activation mode, delay or hysteresis
and setpoint program lockout.
From programming mode (Pro stage, see fig. 15.1), press
key to access to the setpoint configuration, indication "SET". To
program the setpoint numerical values, from the run mode press
ENTER to call the Pro stage and press
to access the first
setpoint value.
LEFT DIGIT
VALUE
RIGHT DIGIT
VALUE
MODE HI=0
MODE LO=1
DELAY=0
HYSTERESIS=1
TARE
MAX/MI
N
DATA
ENTE
R
RS232C
RS485
MIN
TARE
PROG
SET 1
SET 2
MAX
F4
F2
F3
F1
TARE
MAX/MI
N
DATA
ENTE
R
RS232C
RS485
MIN
TARE
PROG
SET 1
SET 2
MAX
F4
F2
F3
F1
The figure 16.3 shows one of the two options available at this stage [LC O = setpoint
values programming enabled (unlocked) or LC 1 = setpoint values programming
disabled (locked)].
If wanted to modify this parameter, use the
key to switch to the desired
option. If you decide to lock the setpoint values, it will be also necessary to lock out
the entire program routines.
Press
ENTER to validate the choice, save programmed data and return to the run
mode (indication Stor).
[16.3] Setpoint Program lockout
The indication shown in figure 16.1 appears on the display to indicate that the next
step is to program the setpoint 2 operating parameters (led Setpoint 2 activated).
After 2 seconds or by a press
ENTER , the meter allows access to this menu.
The display then shows two digits; the one on left corresponds to the output mode
(HI or LO) and the rightmost one to the delay unit (time -delay- or counts of display
-hysteresis-). See table in figure 16.1. Use the
key to change the active digit
value (in flashing) and the
key to go to the next digit to be modified.
Press
ENTER to validate changes and advance to the next phase.
[16.1] Setpoint 2
The display shows for 2 seconds the indication corresponding to the selected delay
units before giving access of the time delay or hysteresis magnitude programming
(dLY) or (HYS). After 2 seconds or by a press
ENTER , the initially programmed
numerical value appears on the display with the first digit in flashing. To change the
value (from 0 to 9999 counts of hysteresis or from 0 to 99 seconds of time delay) use
the
key to increment the active digit value and the
key to advance to
the next digit to be modified. Repeat this procedure until desired value is completed
on the display and press
ENTER to validate and advance to the next step.
[16.2] SET2 Histeresis/Delay
16
LEFT DIGIT
VALUE
RIGHT DIGIT
VALUE
MODE HI=0
MODE LO=1
DELAY=0
HYSTERESIS=1
TARE
MAX/MI
N
DATA
ENTE
R
RS232C
RS485
MIN
TARE
PROG
SET 1
SET 2
MAX
F4
F2
F3
F1
TARE
MAX/MI
N
DATA
ENTE
R
RS232C
RS485
MIN
TARE
PROG
SET 1
SET 2
MAX
F4
F2
F3
F1
TARE
MAX/MI
N
DATA
ENTE
R
RS232C
RS485
MIN
TARE
PROG
SET 1
SET 2
MAX
F4
F2
F3
F1
MODULE 3 - SETPOINTS
DEFINITION
The left diagram shows the entire MODULE 3 that
allows to program the alarm/setpoint operation and is
activated when one of the following output options 2RE-
4RE-4OP-4OPP are installed.
Each one of the three menus is dedicated to a
specific configuration parameter and is composed of four
levels corresponding to each four of the setpoints (in case
that a 2-relay option (2RE) is installed, only the first two
levels will appear in the routines).
The configuration of the parameters relating one of the
setpoints is made in a single step of each menu. The LEDs
1, 2, 3 and 4 illuminate by turn as the program advances
one step of the menu, to indicate which of the setpoints is
being treated at each time.
At the end of a complete sequence, a press of "ENTER"
causes deactivation of all the LED indicators except "PROG"
and activates the "STORE" LED for a few seconds. The
programmed data is stored in the memory and the
instrument returns to the reading of the variable under
measure.
key to move from the run mode to the programming mode. Press
three time the
and press again
ENTER
to access to the programming menus.
Each menu activates a different combination of the "A" and "B" LEDs. From this stage,
the
key permits selection of a specific menu and the
ENTER
key provides
access to the programming of the parameters contained in the selected menu.
The figure shows the setpoint 1 programming step. The rest of the setpoints are
programmed in the same manner, each one activating its corresponding LED. By
means of the
key (modify value of the active digit) and the
key
(advances to the next digit to the right), compose the desired setpoint value with sign
between -32000 and +32000. It is not necessary to program the value of the setpoint
2 when it is going to have automatic track function, for its value will not be taken into
account. Remember that, if the alarm is going to have manual track function
(setpoints 2 or 4), the programmable value is not the setpoint value but the offset
between this and its main alarm.
ENTER : Validates the programmed value and goes to the programming of
the next setpoint.
ESC
: Returns the meter to the normal operation.
19
ACCESS TO THE SETPOINTS PROGRAMMING
B
A
TARE
HOLD
LIMIT
MAX
MIN
DATA
DSP2
INP2
FLT
STORE
DSP1
INP1
2
1
4
3
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
PROG
TEACH
PRG
RUN
B
A
TARE
HOLD
LIMIT
MAX
MIN
DATA
DSP2
INP2
FLT
STORE
DSP1
INP1
2
1
4
3
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
PROG
TEACH
PRG
RUN
From the entry stage of the module 3 (Fig. 35.1), press the
ENTER
key to access to
the menus and the
key to move to the stage of entry into the menu "3B -
MODE" indicated in figure 37.1. This menu allows to determine the features applied to
each alarm. The "PROG" LED (programming mode indicator), "LIMIT" LED (setpoint
programming
indicator) and "B" LED (menu indicator) remain active during the
whole phases of this menu. Press
ENTER if you want to access this menu.
: Skips over this menu and goes to the menu 3AB for programming
the delay or hysteresis levels.
ESC
: Returns the meter to the normal operation.
1st digit : Allows disabling the setpoint "0", enabling the setpoint
"1" or enabling the setpoint latch "2".
2nd digit : Mode HIGH "0" or LOW "1".
3rd digit : Alarm activation with time delay (DLY) "0", asymmetrical
hysteresis (HYS-1) "1" or symmetrical hysteresis (HYS-2) level "2".
4th digit : Activation by net value "0", by manual Track "1", by gross
value "2", by peak value "3", by valley value "4" or auto Track "5".
5th digit : Alarm indication by LED "0" or by LED plus display blinking
"1".
ENTER : Validates and goes to the next setpoint configuration.
ESC
: Returns the meter to the normal operation.
20
MENU 3B - OPERATION MODE CONFIGURATION
B
A
TARE
HOLD
LIMIT
MAX
MIN
DATA
DSP2
INP2
FLT
STORE
DSP1
INP1
2
1
4
3
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
PROG
TEACH
PRG
RUN
B
A
TARE
HOLD
LIMIT
MAX
MIN
DATA
DSP2
INP2
FLT
STORE
DSP1
INP1
2
1
4
3
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
PROG
TEACH
PRG
RUN
The figure at left represents the first menu step corresponding to the setpoint 1 (LED
1 energized). The rest of the setpoints are accessible by pressing
ENTER key once
programmed the preceding one. Each digit represents one different operating
parameter which is activated with a numbers according to the table. Starting from the
left :
First digit
0 = OFF
1 = ON
2 = ON (latch)
Second digit
0 = HI
1 = LO
Third digit
0 = Delay
1 = Hyst_1
2 = Hyst_2
Fourth digit
0 = Net value
1 = manual Track
2 = Gross value
3 = Peak value
4 = Valley value
5 = auto Track
Fifth digit
0 = LED alarm
1 = LED alarm
& display bl inking.
Press the ENTER button to move from the run to the
programming mode. Press the LIMIT key for fast access to
the programming of the setpoint values.
The previously programmed setpoint values appear on the
display successively at each push of ENTER . The setpoint
number is indicated by the LED's 1, 2, 3 or 4. The LED's
"PROG"(programming mode indication) and "LIMIT" (setpoint
programming indication) are active during all menu steps. (See
the fig. to configure the setpoint values).
Please check the lock-out programming level (see section on
Programming lock out/Access levels , on instrument s manual).
With both switches to the ON position, it is impossible to
change the setpoint values but the entry to this routine
remains accessible for viewing programmed data.
21
B
A
TARE
HOLD
LIMIT
MAX
MIN
DATA
DSP2
INP2
FLT
STORE
DSP1
INP1
2
1
4
3
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
PROG
TEACH
PRG
RUN
FAST ACCESS TO THE PROGRAMMING OF THE SETPOINT VALUES
The ALPHA models provide four LED's for alarm status
indication. The LED's are labeled from 1 to 4 although
when the 2 relay option (2RE) is installed, only the first
two are used.
During the normal operation, these indicators are
activated when the corresponding setpoint output goes
active and, in the programming mode, they allow to
identify the setpoint that is being programmed.
The programmed setpoint values (even if they are
inhibited) can be viewed during the meter's normal
operation by successively pressing the "LIMIT" key.
Each press of "LIMIT" causes the main display to read
one of the setpoints. The setpoint number is indicated by
the LED's 1, 2, 3 or 4 while the "LIMIT" LED activates for
as long as the setpoints are being displayed.
An example of what indications are present during the display
of a setpoint is show in the above figure, in this case, the
SET2 is being displayed.
In case that the SET2 or SET4 alarms are configured for
tracking operation, the value displayed is not the setpoint
value but the offset between this and the one of their
corresponding main alarm.
When positive over-range (+oUFLo) or negative over-range
occurs (-oUFLo), all the outputs and LED indicators
corresponding to the setpoints de-energize.
22
B
A
TARE
HOLD
LIMIT
MAX
MIN
DATA
DSP2
INP2
FLT
STORE
DSP1
INP1
2
1
4
3
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
PROG
TEACH
PRG
RUN
RUN MODE INDICATIONS
Only setpoint 2 & 4
only setpoint 2
24
MODEL BETA-M PROGRAMMING INSTRUCTIONS
S E t P t S
3 0
- S E t 2 -
3 2
- S E t 2 -
3 2
- o n -
3 2 - S E t 2 -
- o F F -
3 2 - S E t 2 -
± 8 8 8 8 8
3 2 - S E t 2 -
- n E t -
3 2 - S E t 2 -
- G r o S -
3 2 - S E t 2 -
- P E A K -
3 2 - S E t 2 -
- V A L -
- M o d E -
3 2
- H I -
- M o d E -
3 2
- L o -
d L y
3 2
H Y S 1
3 2
H Y S 2
3 2
3 2 - S E t 2 -
- t r A c -
- t r A C -
3 2
S E t
3 2 - t r A C -
A u t o
3 2 - t r A C -
± 8 8 8 8 8
- L A t c H
3 2
- n o -
3 2 - L A t c H
- Y E S -
- P r o -
- b L I n K
3 2
- n o -
3 2 - b L I n K
- Y E S -
d L y
3 2
8 8 8 8.8
3 2 H Y S 1
8 8 8 8 8
3 2 H Y S 2
8 8 8 8 8
- S E t 1 -
3 1
- S E t 4 -
3 4
- S E t 3 -
3 3
Menu 30 - Setpoints
The diagram of page 42 corresponds to the menu 30 of
setpoints programming that is valid for the output options 2RE,
4RE, 4OP y 4OPP. If you only have the output option 2 relays
(2RE) it will only appear the 31 & 32 menus corresponding to
the setpoints SET1 & SET2.
Each output is programmed independently by means of ,
finalized the programming sequence of each setpoint, by
pressing the key
ENTER
the display shows the indication
"-Pro-", wherefrom you can access to the 30 menu to
configure the rest of the setpoints.
The setpoints SET1 and SET3 can only be programmed for
independent action, the SET2 and SET4 can be activated
independent from the first or tracking the first. In this case
SET2 depends on SET1 and SET 4 depends on SET3. The
setpoint 2 has automatic tracking.
The setpoint outputs can act in relationship with the net,
gross, peak or valley value. There are two control modes, HI
or LO, with programmable delay or hysteresis values.
The setpoints can be configured as "latch". With this
configuration, the led indicator remains activated after the
alarm condition has finished. The setpoint reset can only be
done by means of the logical function num. 25.
It is possible to configure the display blink option when a
setpoint is activated.
Access to the setpoints programming
Press
ENTER
to go from run mode to programming mode.
Press
to pass to the level shown in the figure.
Press
ENTER
one more time and in the display will appear the
indication "31 SET-1" corresponding to the input in the
programming menu of setpoint 1. Now we are in the menu
level selection, where
ENTER
allows access to the setpoints
programming in the display and
allows to pass to the
next setpoint configuration.
Considerations
about
programming
instructions
Since all setpoints have the same programming sequence as
free alarms (see. 44 to 47), we have changed the setpoint
number in the figures by the symbol "# ", this way the
instructions sequence is valid for all selected number.
In the setpoints 2 and 4 programming, the selection of the
"-on-" or "trAC" option (see fig. 44.2), brings you different
sub-routines. Each one is explained in different sections on
pages 48 and 49.
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
25
The figure shows the input display in the programming menu of one of the outputs
where the symbol "# " represents the setpoint number that you are going to program.
To select other setpoint, press
until the desired number appears in the place of
#.
ENTER
Access to the programming of the setpoint shown in display.
ESC
Pass to the input configuration level (indication "-Pro-").
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
#
#
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
#
#
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
#
#
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
#
#
Select "-on-" to program the setpoint
as independent alarm.
Press
ENTER
and the display shows
the figure 29.1. indication.
The option "-trAC-" is the tracking
function that only appears in the
programming menus of SET2 and
SET4. Select "-trAC-" to program the
setpoint as manual or automatic
tracking alarm.
Press
ENTER and go to page 32.
Select "-oFF-" to disable the action
of
the
output
relay
or
opto
corresponding to the setpoint you are
programming.
Press
ENTER
to go back to the
"-Pro-"
indication
that
give you
access to the programming mode.
26
Submenu 31, 32, 33 & 34 - SETPOINTS
[28.1] Start
[28.2] Setpoints Run mode
Once on the selected menu in the step before, the options represented in the figures are shown. The option "-trAC-" appears in
the setpoints 2 & 4 programming menu only. By pressing
, go to desired option display and press the key
ENTER .
Select comparison of the setpoints with the net value "-nEt-", with the gross
value "-GroS-", with the peak value "-PEAK-" or with the valley value "-VAL-".
ENTER
Validate the introduced data and go to introduce the setpoint value.
ESC
Return to the programming access level (indication "-Pro-").
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
#
#
Compose using the keys
and
de setpoint value between
"-99999" and "+99999".
ENTER
Validate the introduced data and go to select the activation mode.
ESC
Return to the programming access level (indication "-Pro-").
Select "-HI-" to activate the output over the setpoint value or
"-Lo-" to activate the output under the setpoint value.
ENTER
Validate the selection and go to the activation delay programming.
ESC
Return to the programming access level (indication "-Pro-").
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
#
#
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
#
27
If you have selected "-on-" in step 28.2
[29.1] Comparison
[29.2] setpoint value
[29.3] Activation mode
The secondary display shows three delay options in the output action. Select
one of them: "dLY" = delay or "HYS 1" = asymmetrical hysteresis or "HYS 2" =
symmetrical hysteresis.
ENTER
Validate the selection and go to program the delay value.
ESC
Return to the programming access level (indication "-Pro-").
Compose using the keys
and
the delay value between "-9999.9" and
"+9999.9" seconds.
ENTER
Validate the introduced data and go to select the control mode.
ESC
Return to the programming access level (indication "-Pro-").
Select "-no-" or "-YES-" to configure the setpoint as "latch".
ENTER
Validate the selection and go to program the blink.
ESC
Return to the programming access level (indication "-Pro-").
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
#
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
#
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
#
28
If you have selected "-on-" in step 28.2
[30.1] Activation delay
[30.2] Delay value
[30.3] Setpoint LATCH
Select "-no-" or "-YES-" to make the main display blink when the setpoint is
activated.
ENTER
Validate the selection and go to the programming access level ("-Pro-").
ESC
Return to the programming access level (indication "-Pro-").
29
If you have selected "-on-" in step 28.2
[31.1] Blink
The function "-trAC-" is only available in the SET2 and SET4 alarms.
As you can see the auxiliary display shows the number 2 instead of de # ; this is the
only alarm that has automatic tracking, by this way, in the SET4 configuration menu,
this indication is omitted and you access right to the setpoint value programming) .
In the menu 32, there are two options: manually program the tracking value from
SET1 (in this case select "SET" = manual) or allow the process to select the necessary
value (select "AUto" = auto)
ENTER
If "AUto" has been selected, the ENTER key returns the instrument to the
entry level in the programming mode (indication "-Pro-"). If "SET" has been selected,
the ENTER key goes to the next menu step (fig. 48.2) where the SET2 or SET4 value
can be programmed.
ESC
Return to the programming access level (indication "-Pro-").
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
Compose using the keys
and
the tracking value between "-99999" and
"+99999". Remember that the SET2 will track the SET1 and SET4 tracking the SET3.
ENTER
Validate the introduced data and return to the programming access level
(indication "-Pro-").
ESC
Return to the programming access level (indication "-Pro-").
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
#
30
If you have selected "-trAC-" in step 28.2
[32.1] Activation mode
[32.2] Setpoint value
There is an easy way to access only to the setpoints value
configuration. From the run mode (RUN), press
ENTER , we
enter in the programming mode (PROG) and then the key
LIMIT .
The setpoint values appears by pressing the key
ENTER . The
secondary display shows the selected setpoint. And the main
display shows the setpoint value with the left digit blinking
(see fig. 33.1 ). By the keys
and
compose the
desired setpoint value, between "-99999" and "+99999".
If it is not possible to modify the setpoints value, it is because
of the programming is blocked. Check the BETA-M manual for
info about blocking programming.
The setpoint values can be configured if we have the
connector function number 24 activated, that allows the
programming and the use of the setpoints value without relay
or opto output option. See the programmable functions table in
the BETA-M manual.
31
DIRECT ACCESS TO THE SETPOINTS VALUE
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
[33.1] Configuration of setpoint 1 value.
The BETA-M has four LED indicators situated at the right side
of the display to show the alarm status. The LEDs are
numerated from 1 to 4 but with the output option 2RE, only
the first two are used.
The programmed setpoint values, even if they are inactive, can
be visualized during the normal device run mode by pressing
the key
LIMIT .
The visualization of any setpoint value does not affect the
measure reading in the main display; the setpoint value is
indicated in the secondary display while in the auxiliary
appears the letter "L" followed by the number of the
corresponding visualized setpoint.
In case of the setpoints SET2 and SET4, the letter "L" in the
auxiliary display is changed by "t" (followed by the numbers 2
and 4) when they are tracking SET1 and SET3.
If SET2 has been programmed as auto tracking, when you
recall the setpoints by pressing the key
LIMIT , the auxiliary
display and the secondary shows, in the first press, the
indication "L1" and the SET1 value. The second press display
the indication "t" and the tracking value. The next press shows
the setpoints 3 and 4 if they are installed and finally turn off
the displays.
32
RUN MODE INDICATIONS
[34.1] setpoint 1 value visualization. The led 1
indicates the activation of setpoint.
The setpoint value remains in the display until a new press of
key
LIMIT is done, that shows the next setpoint value,
MAX/MIN
shows the peak value or
ENTER
that gives you access to the
programming mode.
When overflow ("oUFLo"), all the output and LED indicators
corresponding to the setpoints are inactive, except the ones
configured as latch.
TARE
RESET
LIMIT
MAX/MIN
DATA
ESC
ENTER
M
A
X
M
I
N
HOLD
TARE
1
2
3
4
DISEÑOS Y TECNOLOGIA, S.A.
Polígono Industrial Les Guixeres
C/ Xarol 8 C
08915 BADALONA-SPAIN
Tel : +34 - 93 339 47 58
Fax : +34 - 93 490 31 45
E-mail : [email protected]
www.ditel.es
INSTRUCTIONS FOR THE RECYCLING
This electronic instrument is covered by the 2002/96/CE European Directive so, it is properly marked with
the crossed-out wheeled bin symbol that makes reference to the selective collection for electrical and
electronic equipment which indicates that at the end of its lifetime, the final user cannot dispose of it as
unsorted municipal waste.
In order to protect the environment and in agreement with the European legislation regarding waste of
electrical and electronic equipments from products put on the market after 13 August 2005, the user can
give it back, without any cost, to the place where it was acquired to proceed to its controlled treatment and
recycling.