Clevertronics CLP CWSQLED Series Installation & Maintenance Instruction Leaflet

Specifications

Brand: Clevertronics
Category: Lighting Equipment
Model: CLP CWSQLED Series (Installation & Maintenance Instruction Leaflet)
File Type: PDF
File Size: —
Pages: 2

Read Online

Read the Clevertronics CLP CWSQLED Series Installation & Maintenance Instruction Leaflet online using the built-in PDF viewer.

Text of the manual

21 August 2020

Clevertest and Clevertest Plus Refer to the supplementary operation guide supplied with the Product. After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red flashing for a period up to 2 minutes. The diffuser will require removal to gain access to the Test/Status Switch and LED. Maintained fittings (CWSQLEDM-yy-zz) cannot be scanned with a camera using the Clevertest Plus App as the maintained light source interferes with the camera scanning function. To register the fitting manually enter the serial number from the QR code and visually read the test result and enter manually into Clevertest Plus App. Zoneworks, HIVE and DATA Monitored Options Fittings with part numbers -ZW, -HVG, -DATA are fitted with Zoneworks communications modules (nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides a multifunction indication of the status of the fitting during testing and normal operation: Option State LED Operation ZW, HVG, DATA Commissioned LED on Solid (Green) ZW, DATA Un-commissioned Batt plugged-in: yellow 1s, green 1s Batt unplugged: red 1s, off 1s HVG Un-commissioned With network connectivity Batt plugged-in: yellow 1s, green 1s Batt unplugged: red 1s, off 1s HVG Un-commissioned Without network connectivity Batt plugged-in: yellow 250mS, green 250mS, yellow 250mS, green 250mS, green 1s Batt unplugged: red 250mS, off 250mS, red 250mS,off 250mS, off 1s ZW, DATA Emergency Light Test In Progress LED flashes at yellow 5s , 0ff 1s HVG Emergency Light Test In Progress LED flashes at yellow 1s , 0ff 1s In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA version) DALI EM Option Luminaires with part numbers having -DALI are fitted with DALI modules (nodes) that facilitate connection and integration to 3rd Party Lighting Control Systems. Before installing the -DALI fitting please confirm that the Lighting Control System has the capability to monitor DALI Emergency Luminaires. The -DALI fitting will be addressed and configured into the control system by the Lighting Control System Commissioning Technicians and not Clevertronics. State LED Operation Commissioned/ Un-commissioned LED on Solid (Green) Emergency Light Test in progress LED flashes at 1s On (Yellow) & 1s Off “IDENTIFY COMMAND” Fitting goes into emergency mode for 10 seconds A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network. DALI connections are marked as Da Da. CLP™ Argonaut Square LED Emergency Light Installation & Maintenance Instruction Leaflet NOTE: Standard product codes with this symbol are enabled with Clevertest Plus capability. Please refer to the operation guide supplied with the product for details. Australia (Head Office) Website: www.clevertronics.com.au Email: [email protected] Phone: +61 3 9559 2700 Fax: +61 3 9559 2799 UK OFFICE 362 Stockley Close West Drayton UB7 9BL Phone: 01895 430 255 Models: CWSQLEDx-uu-yy-zz-vv Testing: Options: Manual Test zz = Blank Non-Maintained x = N Zoneworks zz = ZW Maintained x = M Z/W DATA zz = DATA Microwave Sensor Hi/Lo Control yy = MS-HL DALI REG zz = DALI Microwave Sensor Control yy = MS ZW Hive zz = HVG Low Output uu = LO Black Body vv = BLK Spare Parts: 1550290 BATT: LP 6.4V 3.2Ah.200mm lead.Stick.Brkt 1190320 Sensor: M/Wave Motion, SK-503L DC (for -MS-HL) 1330120 LED Driver – GDY250, 26W 42VDC 610mA 1330039 25W DALI Driver - Programmed to 250mA - 32mA (for -LO) 8002840 PCA: SQ LED Array, 215mm, 400K, 3020 LED UKM02370050001 CCPLED-3W-CKIT, LED Power Pack, 3W, LP, OWC UKM02870130001 CCPLED-3W-CKIT-HVGEXT, LED Power Pack, 3W, HVG, LP, OWC 1190325 SENSOR:M/Wave Motion, SK-601 On/Off (for -MS) Important: It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, ensure that the electricity supply has been switched off and isolated. Installation must be carried out in accordance with the relevant British Standards.

21 August 2020

Installation: The CLP Argonaut Square (CWSQLEDx) can be installed either Ceiling or Wall Mounted. • Remove the four (4) screws holding the diffuser to the base. • Remove the four (4) screws holding the gear tray to the base. • Determine the cable access point. There are 2 locations on opposite sides of the fitting for cable gland/conduit entry. Entry can also be from the back of the base. Drill out the desired cable entry point. • Drill out 4 of the mounting points in the base (see image below). • Using the base as a guide, mark the 4 holes for mounting and one for mains access if using back cable entry. • Mount the base using appropriate fixings and seal these fixings with silicone (fill any additional entry points with silicone also) • Route the power inside the base. • Connect the 240VAC ( ,LSW, LEM, N) supply to the terminal block of the gear tray. • Install the gear tray to the base. • Apply power to the fitting and test per the instructions. • If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four Segment Marking on the product will include an ‘’F’’ in third segment block. Dimensions: Note: This luminaire (with reinforced insulation between control/LED terminal and AC supply) contains non- user replaceable light source and battery - to be replaced (if required, refer installation instructions for battery replacement) by Clevertronics service personnel/agents or a registered electrician. Battery Replacement: 1. Prior to any work, isolate the power to the luminaire that requires battery replacement 2. Open the fitting by removing the securing screws holding the diffuser, support diffuser doing this. 3. Remove gear tray by removing screws, support gear tray during this process. 4. Remove the Battery Connector from the Emergency Driver. 5. Remove the battery from the gear tray by removing mounting screws. 6. Replace battery, re-install screws and connect to Emergency Driver. 7. Reinstall the Gear Tray. 8. Refit the diffuser, ensure diffuser is aligned to maintain the weatherproof seal. Testing: Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 hours. Conduct the following tests with the Maintained Mode Off: • The emergency lamp must illuminate for at least 180 min after disconnection from the mains. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the situation and once completed, the unit must pass a subsequent test. • Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On. • Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non- maintained operation).. Trouble Shooting: Below are a list of common problems and their possible causes. Fault: The Green LED Test Switch indicator is not illuminated. Check: A.C. is connected and is turned on. Battery is connected Test Switch for damage. Fault: Lamp does not illuminate in emergency mode. Check: A.C. is connected. Lamp is correctly inserted. Battery is connected Fault: Lamp illuminates in emergency mode, but only stays on for a short period. Check: Battery has been allowed to charge for at least 24 hours. Battery for damage. Caution: On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries discharged or “cycled”. The Li-ion battery in the luminaire has been selected to give excellent long life performance in a controlled IEC 60598-2-22 testing environment. Excessive battery cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty claims, as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms. Warranty: For Product Warranty information and Terms and Conditions of Sales please refer to our website https://clevertronics.co.uk/product-warranty-statement/ Mounting Holes Cable Entry

Other Lighting Equipment Manuals