Dometic PGD1 Installation And Operation Instructions Manual
Read Online
Read the Dometic PGD1 Installation And Operation Instructions Manual online using the built-in PDF viewer.
Text of the manual
L-3499 | Form No. 338208 20200323 | ©2020 Dometic Corporation
WARNING
Cancer and Reproductive Harm
www.P65Warnings.ca.gov
VARC MODELS
EN
VARC Chiller Controls
Installation and Operation Instructions . . . .2
VARC Chiller Controls
1
Explanation of Symbols and Safety
Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.1
Recognize Safety Information . . . . . . . . . . . . .2
1.2
Understand Signal Words . . . . . . . . . . . . . . . .2
1.3
Supplemental Directives . . . . . . . . . . . . . . . . .3
1.4
General Safety Messages . . . . . . . . . . . . . . . .3
2 General Information . . . . . . . . . . . . . . . . . . . . . 3
2.1
Product Description . . . . . . . . . . . . . . . . . . . .3
2.2
Inputs and Outputs . . . . . . . . . . . . . . . . . . . . .6
2.3
Default Parameters . . . . . . . . . . . . . . . . . . . . . .8
3 Intended Use . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 12
5 Installation and Setup . . . . . . . . . . . . . . . . . . . 13
5.1
Initial Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.2
Multi-stage Wiring . . . . . . . . . . . . . . . . . . . . . 14
5.3
Touch Screen Connection . . . . . . . . . . . . . . 15
5.4
Firmware Verification . . . . . . . . . . . . . . . . . . . 15
5.5
Networking . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.6
Configuring Display Addresses . . . . . . . . . . 17
5.7
VARC Standard Wiring Diagram . . . . . . . . . . 18
6 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.1
Operational Modes . . . . . . . . . . . . . . . . . . . . 19
6.2
Powerup and Startup . . . . . . . . . . . . . . . . . . 21
6.3
Operating the Touch Screen . . . . . . . . . . . . 21
6.4
Operating the LCD Screen . . . . . . . . . . . . . .25
7 Maintenance Mode . . . . . . . . . . . . . . . . . . . . . 39
7.1
Accessing Maintenance Mode from the
LCD Screen . . . . . . . . . . . . . . . . . . . . . . . . . .39
7.2
Accessing Maintenance Mode from the
Touch Screen . . . . . . . . . . . . . . . . . . . . . . . . .39
8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 40
8.1
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
8.2
Envelope Zone Status Descriptions . . . . . . .44
9 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
10 Warranty Information . . . . . . . . . . . . . . . . . . . 44
Contents
Service Center & Dealer Locations
Visit: www.dometic.com
Read these instructions carefully. These instructions
MUST stay with this product.
1 Explanation of Symbols and
Safety Instructions
This manual has safety information and instructions to
help you eliminate or reduce the risk of accidents and
injuries.
1 .1 Recognize Safety Information
�
This is the safety alert symbol . It is used to alert
you to potential physical injury hazards. Obey all
safety messages that follow this symbol to avoid
possible injury or death.
1 .2 Understand Signal Words
A signal word will identify safety messages and property
damage messages, and also will indicate the degree or
level of hazard seriousness.
�
DANGER!
Indicates a hazardous situation that, if not avoided,
will result in death or serious injury.
�
WARNING
Indicates a hazardous situation that, if not avoided,
could result in death or serious injury.
�
CAUTION
Indicates a hazardous situation that, if not avoided,
could result in minor or moderate injury.
NOTICE: Used to address practices not related to
physical injury.
IIndicates additional information that is not related
to physical injury.
VARC Chiller Controls
General Information
1 .3 Supplemental Directives
To reduce the risk of accidents and injuries, please
observe the following directives before proceeding to
install or operate this appliance:
• Read and follow all safety information and
instructions.
• Read and understand these instructions before
installing or operating this product.
• The installation must comply with all applicable local
or national codes, including the latest edition of the
following standards:
–
American Coast Guard Standards (CG-ENG)
–
American Boat and Yacht Council (ABYC)
–
ANSI/NFPA70, National Electrical Code (NEC)
1 .4 General Safety Messages
�
WARNING: ELECTRICAL SHOCK, FIRE, AND/
OR EXPLOSION HAZARD . Failure to obey the
following warnings could result in death or
serious injury:
• Use only Dometic replacement parts and
components that are specifically approved for use
with the appliance.
• Avoid improper installation, adjustment, alterations,
service, or maintenance of the appliance. Service and
maintenance must be done by a qualified service
person only.
• Do not modify this product in any way. Modification
can be extremely hazardous.
• Use care when diagnosing and/or adjusting
components on a powered unit.
2 General Information
The Dometic Variable Capacity Chiller (VARC) includes
a microcontroller-based unit to control multiple chillers.
The multiple-chiller design provides flexibility in the
control application and improved controls and system
protection.
IThe images used in this document are for reference
purposes only. Components and component
locations may vary according to specific product
models. Measurements may vary ±0.38 in.
(10 mm).
2 .1 Product Description
This section describes some of the key design features
of the VARC, the control application, the LCD and touch
screen displays, and the inputs and outputs.
2 .1 .1 VARC Design Features
The VARC uses a precision Proportional Integral
Derivative (PID) loop control algorithm that manages
the capacity requirements of the system by modulating
the compressor speed and balancing chiller output with
the required load. The PID system differs greatly from
the on/off control of a standard chiller system, as the
PID modulates the speed of the compressor to increase
or decrease its capacity allowing for reduced current
consumption by the electrical system. This smooth
operation eliminates large swings in current on the
generator. This completely variable capacity chiller uses
an inverter to modulate the speed of the compressor to
achieve the desired chilled water setpoint. This allows
the compressor to run at a minimum speed of 30 Hz to a
maximum of 240 Hz depending on compressor model.
The VARC also uses the advanced technology of an
Electronic Expansion Valve (EEV). This provides more
precise control of superheat across a broad range of
conditions with no erratic swings as the valve reacts to
temperature and pressure changes (no “hunting”). Using
an advanced algorithm, the VARC maintains superior
superheat control over extreme operating conditions.
The VARC controller is internally grounded with isolation
between inputs and outputs.
The output relays offer double isolation so that different
voltages can be used for groups of relays.
For temperature measurements, the system uses NTC
type 10K@77° thermistors.
For both suction and discharge monitoring, the system
uses ratiometric 0–650 PSI (45 bar) range pressure
transducers.
VARC Chiller Controls
2 .1 .2 VARC Control Application
The built-in VARC control application supports the
following features:
• Selection and sequencing of up to six chillers
• Selection and sequencing of one Chilled Water Pump
(CWP) and one or more Sea Water Pumps (SWP)
• Selection and sequencing of up to six electric heaters
• Sequencing of devices for run time equalization
• Alarms and interlocks
• Load shedding
• Troubleshooting help
Sequencing for chillers, pumps, and heaters is the order
in which they start up and turn off. Sequencing is based
on run time, which is the amount of hours a specific
compressor, pump, or heater has run.
The VARC is factory programmed with the options
enabled for that system. Although the system offers
flexibility, these options can be enabled only by a factory
representative. Users can select Normal, Econo, or
Boost mode operation in a single-stage configuration.
2 .1 .3 PGD1 LCD Display
The PGD1 provides an LCD display and six buttons for
navigating the control software.
q
r
w
t
e
y
1 PGD1 LCD Display Components
q Alarm
r Scroll Up
w Program
t Enter
e Escape
y Scroll Down
2 .1 .4 PLDPRO LCD Display
The PLDPRO provides an LCD display and six buttons for
navigating the control software.
q
r
w
t
e
y
2 PLDPRO LCD Display Components
q Alarm
r Scroll Up
w Program
t Enter
e Escape
y Scroll Down
VARC Chiller Controls
General Information
2 .1 .5 LCD Buttons
The buttons on the PGD1 and PLDPRO operate as
described in the following table:
Button
Description
Alarm
This button flashes red if there is an
active alarm. Pressing this button
displays the active alarm screen. See
“Viewing Alarms for Each Stage” on
page 28.
Program
This button displays the system menus.
Use the scroll buttons to step through
the options. Press the Enter button to
select an option.
Escape
This button exits the current screen and
displays the previous screen. Pressing
this button multiple times displays the
Main screen.
Scroll Up and
Scroll Down
These buttons step through available
menu options, change values in fields
such as setpoints, and navigate from
page to page when the flashing cursor
is in the upper-left corner.
Enter
This button confirms menu option
selections. Pressing Enter repeatedly
moves the cursor the upper-left corner.
2 .1 .6 Touch Screen
This section describes the navigation buttons on the
Main screen.
3 Touch Screen: Main Screen with Navigation Buttons.
The navigation buttons function as follows:
• Enable: Enter setpoints, monitor chilled water
temperatures and monitor pump current information.
• Summary: View the state of HP, EH, FS, and water
temperature for all available stages. Tapping a stage
displays additional information on that stage.
• Chiller Stage: Monitors the refrigerant and chilled
water circuits. Provides hotspot icons that display
additional information when selected. Different icons
appear depending which options are installed. The
Forward and Back buttons navigate between stages.
• Trends: View a graphical display of water
temperature, water pressure, and compressor current.
Data is downloadable to a USB memory stick.
• Alarms: View and clear alarms. Pressing the buttons
at the top-right displays alarm history and other alarm
information.
• Remote Support: Enable third-party technical
support to view your system over an Internet
connection using a VNC (Virtual Network
Computing) server.
VARC Chiller Controls
2 .2 Inputs and Outputs
The VARC allows you to monitor analog inputs, digital inputs, and relay outputs to determine the status of the system.
2 .2 .1 Analog Inputs
IIf a temperature sensor is defective or not connected, the VARC generates an alarm for that sensor.
Input
I/O #
Board
I/O
Description
Chilled Water Return
Temperature Sensor
AI-1
B1
The chilled water supply sensor is continuously monitored whether in Cooling, Reverse Cycle,
or Electric Heat mode. It detects a high-temperature condition in the supply water from the
chiller. If the chilled water temperature is greater than or equal to 125 °F (52 °C), the following
occurs:
• In Reverse Cycle mode, all enabled compressor relays are de-energized, turning off the
compressors.
• In Electric Heating mode, all enabled heater relays are de-energized, turning off the
heating elements.
• A high temperature fault is generated.
• The compressor or electric heat relay re-energizes when the temperature drops to 110 °F
(43 °C).
You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled
stage. See “Viewing Alarms for Each Stage” on page 28.
Freeze Temperature
Setpoint
AI-2
B2
The chilled water supply sensor is continuously monitored whether in Cooling, Reverse Cycle,
or Electric Heat mode. It detects a freeze condition in the supply water of the chiller. If the
chilled water temperature is equal to or less than 36 °F (2 °C), the following occurs:
• The compressor relay is de-energized, shutting off the compressor.
• A low temperature fault is generated.
• The compressor relay re-energizes when the temperature reaches 42 °F (6 °C).
You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled
stage. See “Viewing Alarms for Each Stage” on page 28.
Condenser Freeze
Protection
AI-3
B3
The condenser outlet refrigerant temperature sensor monitors the condenser coil
temperature. In Heat mode, if the coil temperature drops below 30 °F (-1 °C), the VARC
automatically lowers the speed of the compressor to half the speed that it was currently
running. While performing this operation, the display indicates Freeze Defrost.
Suction Pressure 1
AI-6
B6
The VARC continuously monitors the suction pressure. If the suction pressure is below the
alarm setpoint for longer than the programmed time delay, a Low Suction Pressure fault is
generated.
You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled stage
See “Viewing Alarms for Each Stage” on page 28.
Discharge Pressure 1
AI-7
B7
The VARC continuously monitors the discharge pressure. If the discharge pressure is above
the alarm setpoint for longer than the programmed time, a High Discharge Pressure fault is
generated.
You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled
stage. See “Viewing Alarms for Each Stage” on page 28.
Pump Current
Monitoring
(Optional) 1
AI-9
(CW)
AI-10
(SW)
B-9 (CW)
B-10 (SW)
Pump current monitoring for the chilled water and Sea Water Pump (SWP) is an optional
feature. It requires the medium-sized PLC, instead of the standard smaller version. With this
option, you can view the current draw from each pump on the PGD1 display and the touch
screen.
1 The VARC has a proprietary algorithm that keeps the system from turning off immediately for low pressure or high pressure. The VARC gradually reduces its speed
to compensate for low or high pressure conditions.
VARC Chiller Controls
General Information
2 .2 .2 Digital Inputs
Digital inputs are used to monitor the status of the VARC protection circuits. At powerup, all discrete inputs are checked
before the system is enabled. Any faults detected on startup must be verified and cleared via the VARC before the system
will start normal operation. For information on clearing alarms, see “Viewing Alarms for Each Stage” on page 28.
Input
I/O #
Board I/O
Description
Refrigerant High Side
Pressure Limit
DI-1
DI-1
If the high pressure switch is tripped and turns off the compressor, the VARC acknowledges
an open circuit and generates a High Discharge Pressure fault. The VARC will not allow the
compressor relay to be re-energized until the high pressure switch is in the closed position.
You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled
stage. See “Viewing Alarms for Each Stage” on page 28.
Econo Mode Selection
DI-2
DI-2
This optional input is used to put the VARC into Econo mode. While Econo mode is enabled
by this input, the VARC cannot be put into Normal or Boost mode.
Chilled Water Flow
Switch
DI-3
DI-3
With the VARC in either Heat or Cool mode, the Flow switch must be closed prior to system
starting or a stage being enabled. In operation, if flow is lost for more than 10 consecutive
seconds, the following occurs:
• The compressor or heat relay is disabled for the stage that has lost flow.
• A Chilled Water Flow fault is generated.
• The VARC goes into lockout.
• A manual restart is required, after the system initiates, retries, and fails or exceeds timeout.
You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled
stage. See “Viewing Alarms for Each Stage” on page 28.
Load Shedding Input
DI-4
DI-4
The load shedding standard input is activated with a 230 V signal. When load shedding
becomes active, the VARC shuts off the compressor and maintains that state until the load
shedding input is disabled.
In a multi-stage operation, load shedding shuts down the stage with the highest run hours.
Every unit has a load shed input. The number of load shedding signals received (one per unit)
determines how many units are shut off according to run hours.
Electric Heat (E. H.)
Flow Switch
DI-5
DI-5
This optional switch is enabled through the factory settings. With the VARC in either Heat or
Cool mode, the Flow switch must be closed prior to system starting or a stage being enabled.
In operation, if flow is lost for more than 10 consecutive seconds, the following occurs:
• The electric heat is disabled for the stage that has lost flow.
• An Electric Heat Flow fault is generated.
• The VARC goes into lockout.
• A manual restart is required, after the system initiates, retries, and fails or exceeds timeout.
You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled
stage. See “Viewing Alarms for Each Stage” on page 28.
Cool Mode Selection
Switch
DI-6
DI-6
These switches allow for remote mode control. When using digital input mode selection, the
display cannot be used to change mode, but all other functions on the display are available.
Heat Mode Selection
Switches
DI-7
DI-7
2 .2 .3 Digital Relay Outputs
IIf a temperature sensor is defective or not connected, the VARC generates an alarm for that sensor.
Output
I/O #
Board I/O
Description
SWP
DO-1
NO1
Provides switched power to the contactor coils for the Sea Water Pump.
CWP
DO-2
NO2
Provides switched power to the contactor coils for the Chilled Water Pump.
Reversing Valve (RV)
DO-3
NO3
Provides switched power to the coils for the Reversing Valve.
VARC Chiller Controls
Output
I/O #
Board I/O
Description
Electric Heat (EH)
DO-4
NO4
Provides switched power to the contactor coils for electric heat.
Not used.
DO-5
NO5
This output is not used.
Not used.
DO-6
NO6
This output is not used.
Fault Alarm
DO-7
NO7/NC7
Provides a Normally Open (NO) contact point, which is closed for any fault condition. You can
use this output to power a light, relay, or interface to a ship’s monitoring system. The output on
this terminal is 230 VAC.
2 .2 .4 Analog Outputs
The analog outputs are not used.
Output
I/O #
Board I/O Description
Not used
AO-1
Y1
This output is not used.
Not used
AO-2
Y2
This output is not used.
Not used
AO-3
Y3
This output is not used.
2 .3 Default Parameters
The following table lists factory defaults for the compressor, inverter, and econo mode setpoint parameters (for other
VARC models, contact the factory).
Model
Compressor
Inverter Part Number
VARCX48
5KD184XAB21
PSD1* 12 Amp
VARCX60
TNB306FPGMT
PSD1* 12 Amp
VARCX72
5JD420XAA22
PSD1* 16 Amp
VARCX120
208–230V / 1PH
SIAM ANB66FVCMT
PSD2* 30 Amp 200V
208–230V / 3PH
SIAM ANB66FVCMT
PSD2* 40 Amp 200V
380–460V / 3PH
SIAM ANB66FVQMT
PSD1* 40 Amp 400V
The following table lists factory defaults for all other parameters (for other VARC models, contact the factory).
Parameter
VARCX48
VARCX60
VARCX72
VARCX120
Data Type
General Settings
Cooling Setpoint CCW Return
48
48
48
48
Degrees F
Cooling Setpoint CCW Supply
43
43
43
43
Degrees F
Heating Setpoint
110
110
110
110
Degrees F
Econo Mode
65%
65%
65%
65%
Percent
Superheat Setpoint
Cool and Heat
10
10
10
10
Degrees F
VARC Chiller Controls
General Information
Parameter
VARCX48
VARCX60
VARCX72
VARCX120
Data Type
Factory Settings
Control Temp Mode
CCW Supply
CCW Supply
CCW Supply
CCW Supply
Number of Stages
1
1
1
1
Electric Heat
No
No
No
No
Power Cycle
Retain Mode
Retain Mode
Retain Mode
Retain Mode
Logo
Dometic BLK
Dometic BLK
Dometic BLK
Dometic BLK
Background
Ocean
Ocean
Ocean
Ocean
Flow Switch
Yes
Yes
Yes
Yes
High Pressure Switch
Yes
Yes
Yes
Yes
Low Pressure Switch
No
No
No
No
EH Flow Switch
No
No
No
No
Load Shedding
Yes
Yes
Yes
Yes
SW Temp Inlet
Yes
Yes
Yes
Yes
Sea Water Pump Settings
Control
By Demand
By Demand
By Demand
By Demand
Off Delay
5
5
5
5
Seconds
Pump Current
No
No
No
No
Current Selection
10
10
10
10
Amps
Pump Control
Master
Master
Master
Master
Chilled Water Pump Settings
Control
Continuous
Continuous
Continuous
Continuous
Flow Prove Delay
10
10
10
10
Seconds
Off Delay
5
5
5
5
Seconds
Pump Current
No
No
No
No
Current Selection
10
10
10
10
Amps
Reversing Valve
RV Delay On Time
45
45
45
45
Seconds
Electric Heat
Stage Up Delay
60
60
60
60
Seconds
Stage Down Delay
20
20
20
20
Seconds
Compressor
Min On Time
60
60
60
60
Seconds
Min Off Time
10
10
10
10
Seconds
Min Time between Starts
60
60
60
60
Seconds
Load Up Time
10
10
10
10
Seconds
Force Rotation
12
12
12
12
Hours
Load Up Stg Delay
60
60
60
60
Seconds
Avg Supply Delay
240
240
240
240
Seconds
VARC Chiller Controls
Parameter
VARCX48
VARCX60
VARCX72
VARCX120
Data Type
Condenser Frost Protection
Cond Setpoint
30
30
30
30
Degrees F
Cond Band
2.5
2.5
2.5
2.5
Degrees F
Comp Speed
60
40
40
40
RPS
Compressor PID
Cntrl
P
P
P
P
K
50
50
50
50
Chilled Water High Temperature Limit Alarm
Setpoint
125
125
125
125
Degrees F
Off Band (SP-)
15
15
15
15
Degrees F
Retries
6
6
6
6
Retry Timeout
30
30
30
30
Minutes
Retry Delay
120
120
120
120
Seconds
Chilled Water Freeze Limit Alarm
Setpoint
36
36
36
36
Degrees F
Off Band (SP+)
5.4
5.4
5.4
5.4
Degrees F
Retries
6
6
6
6
Retry Timeout
10
10
10
10
Minutes
Retry Delay
120
120
120
120
Seconds
Chilled Water Flow Alarm
Retries
6
6
6
6
Retry Timeout
10
10
10
10
Minutes
Retry Delay
120
120
120
120
Seconds
High Discharge Pressure Alarm
Retries
6
6
6
6
Retry Timeout
30
30
30
30
Minutes
Retry Delay
120
120
120
120
Seconds
High Pressure Switch Alarm
Retry
6
6
6
6
Retry Timeout
30
30
30
30
Minutes
Retry Delay
120
120
120
120
Seconds
Low Suction Alarm
Low Suction Pressure
60
60
60
60
PSI
Delay
180
180
180
180
Seconds
Retries
6
6
6
6
Retry Timeout
30
30
30
30
Minutes
Retry Delay
120
120
120
120
Seconds
VARC Chiller Controls
General Information
Parameter
VARCX48
VARCX60
VARCX72
VARCX120
Data Type
Inverter Alarm
Retry
15
15
15
15
Retry Timeout
60
60
60
60
Minutes
Retry Delay
300
300
300
300
Seconds
Configuration Menu
Temperature Units
Degrees F
Degrees F
Degrees F
Degrees F
Pressure Units
PSI
PSI
PSI
PSI
VARC Chiller Controls
3 Intended Use
The VARC Chiller Control is a chiller control application
that supports touch screen and LCD interfaces.
This manual provides all necessary information for proper
operation of the VARC Chiller Control application.
NOTICE: Poor setup and misunderstood operating
parameters could result in unsatisfactory performance
and possibly failure.
The manufacturer accepts no liability for damage in the
following cases:
• Faulty assembly or connection
• Damage to the product resulting from mechanical
influences and excess voltage
• Alterations to the product without express permission
from the manufacturer
• Use for purposes other than those described in the
operating manual
Dometic Corporation reserves the right to modify
appearances and specifications without notice.
4 Specifications
The following table lists electrical specifications,
environmental specifications, and touch screen
dimensions, and setpoint ranges.
Electrical
Line Voltage
See Data Label
Frequency
Phase
Chilled Water Pump
Output
Sea Water Pump Output
Maximum Circuit Breaker
Size 1
Environmental
Maximum Ambient
Operating Temperature
140 °F (60 °C)
Touch Screen Dimensions
Height
5.79 in. (147 mm)
Width
7.36 in. (187 mm)
Depth
1.77 in. (45 mm)
1 Increase breaker size to include pump current if running pumps directly
from the system.
Setpoint Ranges1
Supply Control
Return Control
Cooling
42 °F (6 °C) to
55 °F (13 °C)
48 °F (9 °C) to
55 °F (13 °C)
Heating
95 °F (35 °C) to
115 °F (46 °C)
95 °F (35 °C) to
120 °F (49 °C)
1 You cannot enter setpoint values outside of these ranges.
VARC Chiller Controls
General Information
5 Installation and Setup
The VARC can be installed as a stand-alone chiller or as
part of a staged system. The factory default setting is as a
stand-alone chiller.
Installation for a staged system requires the following
steps:
1. Make the connections between each stage of the
chilled water and sea water.
2. Make the network connections between each stage
(physical and network addressing).
3. Check the firmware version.
4. Configure the remote control panel.
Chillers supplied on a frame package are configured and
wired as part of the build process.
IAs part of a correctly configured multi-stage system
there is no need to set differential/hysteresis
settings.
5 .1 Initial Wiring
�
WARNING: ELECTRICAL SHOCK HAZARD .
Exercise extreme care when working around
energized equipment. Failure to obey this warning
could result in death or serious injury.
1. Wire the sea water and chilled water pumps to
VARC 1 (no need for pump relays) as follows:
a. Remove the power cover.
b. Connect the pumps to the terminals on the front
of chiller 1, according to labeled connections.
Note: Daisy chaining outputs is not recommended if the
units have individual power sources. Verify the phase of
power before daisy chaining the outputs.
2. Wire the network connections from the network
connection ports (VARC 1 to VARC 2, VARC 2 to
VARC 3, and so forth).
Refer to the “Multi-stage Wiring” on page 14 for more
information on wiring the stages.
GND
GND
L2
L2
337430
337430
337430
337430
G
L1
L2
GND
R+/T+
R-/T-
L2
L2
L1
L1
L1
L1
w
q
e
r
t
y
4 Electrical Connections VARC 48
q Power Input
r Network Connection
and Touch Screen
w SW Pump (10 A max.)
t Load Shed Switch
e CW Pump (10 A max.)
y Elec. Heat Output
VARC Chiller Controls
5 Electrical Connections VARC 60/72
5 .2 Multi-stage Wiring
The following diagram shows how to wire multiple VARC stages.
24VAC/DC
L2
CW Return Manifold
CW Supply Manifold
Circ. Pump
Sea Pump
CW L1
VARC
Stage 1
Chiller
Stage 1
Chiller
Stage 2
Chiller
Stage 3
VARC
Stage 2
VARC
Stage 3
SW L1
Supply
Supply
Supply
Return
Return
Return
Flow Switch
Flow Switch
Flow Switch
Freeze Stat
Freeze Stat
Freeze Stat
GND
Touch Screen (optional)
Modbus Comm 3 Wire
Pump Outputs from VARC Stage 1
Remote PLC Display
(Optional)
3 Wire Communication
Cables (one per stage)
6 Multi-Stage Wiring Diagram
VARC Chiller Controls
General Information
�
WARNING: ELECTRICAL SHOCK HAZARD .
Verify that all units’ power lines are in unison
phasing, in order to eliminate the potential for a
short circuit. Failure to obey this warning could
result in death or serious injury.
5 .3 Touch Screen Connection
Make the following connections to the touch screen:
a. A 24 VDC supply to power the display
b. A three-core communication cable connected to
serial port 1, not port 2
Terminate the three-core communication cable on
Terminal Bus 3 (Modbus Com) on VARC 1.
q
w
e
r
7 Touch Screen Connections
q Power Input (24 V)
e Connection Port for
Remote Connectivity
w USB Port
r Communication
Connection from PICO
(3 Conductor, 18 G
wire)
5 .4 Firmware Verification
Chillers should come from the factory with the correct
firmware preloaded. However, it is worth checking
that the firmware versions of all chiller stages match, as
incompatible firmware can seem to work during initial
setup but then cause networking problems later.
To view the firmware version of a stage:
1. Press the Program button. See “LCD Buttons” on
page 5.
2. Scroll up or down to Technician, and then press Enter.
If prompted for a password, enter 3156.
3. Select Information.
The Information screen is displayed.
VARC Chiller Controls
4. Scroll down to view version information.
5. Repeat for each stage.
Verify that all stages have the same version number. In
the unlikely event that there is a difference between
stages, the PCB firmware must be updated by a
Dometic-approved technician.
5 .5 Networking
When setting up the stages for networking, ensure that
the chillers are not connected via Modbus connections.
Stage 1 requires minimal changes, so start with stage 2,
leaving stage 1 until last.
To set up networking, follow these steps:
1. Power off all stages except stage 2.
2. Press the Program button. See “LCD Buttons” on
page 5.
3. Go to Technician.
4. Scroll down to Service settings, then press Enter.
5. For Service Password, enter 3156.
6. Go to Stage Address.
7. Press Enter, then change address to 2 for chiller 2, 3
for chiller 3, and so forth.
8. Press the Scroll Down button to display the next
screen and change the number of stages. Press Enter
until the cursor is on Num of Stages, then change
from 1 to the correct number of stages for the current
system.
9. Repeat steps 2-8 for additional stages.
10. For stage 1, only perform step 8 to change the total
number of stages.
VARC Chiller Controls
General Information
5 .6 Configuring Display Addresses
1. Display the configuration screen:
a. PGD1: Press and hold the Up, Enter, and Down
buttons simultaneously for 6 seconds.
b. PLDPRO: Press and hold the Up, Down, and
Program Mode buttons simultaneously for 6
seconds.
To locate buttons, see “LCD Buttons” on page 5.
2. Press Enter to access the Display address setting, and
then scroll up or down to reach the address of the
display per stage:
a. Stage 1: 16
b. Stage 2: 17
c. Stage 3: 18
d. Stage 4: 19
e. Stage 5: 20
f. Stage 6: 21
The message “Display address has been changed”
appears, and then the display goes blank.
3. Repeat the three-button push from step 1 to enter the
configuration.
4. Press Enter three times or until you reach the next
screen.
5. Press Enter to go to the next screen.
6. Follow these steps to select the address for Trm1 & 2
and select if it is private or shared:
a. Press enter once to enter the address of Trm1, and
then scroll up or down to select the appropriate
address (for addresses, see step 2).
b. Press Enter.
–
The cursor under Priv/Shared begins flashing.
–
Scroll up or down to select Pr, then press Enter.
The cursor is next to Trm2.
–
Scroll up or down to select 32, then press Enter.
–
Scroll up or down to select Sh, then press Enter.
–
Press Enter two more times. The cursor is next to
Ok?No.
–
Scroll to select Yes, then press Enter.
7. Connect all stages together with the network cable.
The data for all of the stages appears on the main
screen.
8. If using a single common display or remote display, it
must be configured as address 32.
VARC Chiller Controls
5 .7 VARC Standard Wiring Diagram
The following diagrams show the component connections for the standard VARC 48 and VARC 72. The VARC 60 is not shown.
W
L1 L2L3G
U
A1
G
J14
J15
FT-1
FT-2
G0
+VDC
B1
B2
B3
B4
B5
B6
B7
GND
GND
R+/T+
R-/T-
TB3
TB1
TB2
TB4
4128003
337667
338027
338027
HPS1
FS1
GND
R-/T-
R+/T+
Vout
N03
N01
N02
C1
N06
N04
N05
NC7
N07
C3
C2
GND
Y1
Y2
Y3
+VDC
D11
D12
D13
D14
D15
D16
D17
DIC 1
GND
+5VR
A2
A1
A2
12
22
14
24
11
21
12
22
14
24
11
21
1 2 3 4 5 6 7
8 910
V W G
V(R)
W(C)
U(S)
V
U
Field Wiring
To Remote Display
Input Power 230VAC
(optional)
E.H. Flow
(optional)
Econo Mode
(optional)
Mode Selector Switch
(optional)
Display
Chilled Water Return
L2 230VAC (SW Pump)
MOD
Toroid
340098
Toroid
338082
Toroid
338084
GND
Econo
ORG
SW
CW
RV1
SW
CW
Econo Mode
Cool Mode
Heat Mode
Load Shedding
Cool
Chilled Water Supply
L1 230VAC (Output)
BUS
L1
(Load Shed) 230VAC L1
(Elec. Heat Contactor) 230VAC L1
Off
Off
Heat
Condenser Temp.
L1 230VAC (CW Pump)
COMM
L2
(Input) 230VAC L2
(Output) 230VAC L2
Suction Temp.
L2 230VAC (Output)
GND
GND
Suction Pressure
Discharge Temp.
Discharge Pressure
Power Speed
Drive
Display Splitter
Jumper Details
Bolt Comp
(Top View)
Expansion
Valve
Add Wire
Label
Display Splitter
(Under Top Cover)
Optional Wiring
8 Wiring Diagram VARC 48
W
V
U
C
NO
NC
1
3
5
2
4
6
8
7
J 14
J 15
SHL D
+VR L
R X/TX-
R X/TX+
GND
+VR L
GND
A
B
C
J 14
J 15
DISP L AY SP L ITTER
J UMP E R DE TAIL S
TO R E MOTE DISP L AY
9 Wiring Diagram VARC 72
VARC Chiller Controls
Operation
6 Operation
The VARC provides many operational features to
conserve energy, improve performance, and provide
system control.
6 .1 Operational Modes
The main operational modes determine whether the
VARC generates heat or cooling: Cool mode, Heat
mode, and Electric Heat mode. Pump operation is
coordinated with these modes.
The VARC also has Econo mode and a Maintenance
mode for troubleshooting.
The operational modes can also be selected using the
digital inputs if wired to the control board. These inputs
allow you to select Econo mode if enabled for either
cool or heat mode. Cool and Reverse cycle Heat mode
can be selected by using the digital input controls. This
allows the system to be switched between modes by
using a common switch or controlled through some
other automated system. These inputs do not support
Electric heat operation.
6 .1 .1 Cooling and Heating
The VARC supports a Cool mode and two heating
modes: Heat (reverse cycle heating) and Electric Heat.
Cool
When Cool is selected on the touch screen or the
LCD buttons, the VARC starts cooling according to the
temperature setpoint. The pumps operate as described
in “Pump Operation” on page 20.
Cool mode activity is as follows:
• If the return water/supply water temperature is
above the cooling setpoint and the staging delay has
elapsed, the board energizes the compressor relay.
• The compressor continues to run until the cooling
setpoint has been reached or an alarm condition
exists.
• A stage has a minimum run time of 60 seconds before
it can be turned off and a minimum off time of 10
seconds before it can be re-enabled. This minimum
on time is required to ensure that the system is not
cycling on and off and thereby not allowing the
compressor to properly warm-up. This ensures
proper oil lubrication of the system.
• If the system calls for a stage to be toggled on or off,
the next available stage that meets the staging criteria
is used.
• Load shedding occurs in multi-stage operation when
approaching the chilled water setpoint.
Compressor rotation is active during run mode:
• The compressor with the lowest running hours is
enabled first, and the compressor with the highest
running hours is disabled first.
• After chilled water and sea water flows are stable for
10 seconds (default), the first stage is enabled, and
the compressor starts.
• The first stage continues to run up to 100 percent
speed before enabling the next stage.
• If the PID loop requires demand, then the next stage
is enabled with a startup delay of three minutes
before running up to required speed.
Heat (Reverse Cycle Heating)
When Heat is selected on the touch screen or the LCD
buttons, the VARC starts heating according to the
temperature setpoint. The pumps operate as described
in “Pump Operation” on page 20.
Heat mode activity is as follows:
• There is a 45-second delay after the compressor
ramps up before it is energized.
• The reversing valve relay is energized to operate the
VARC in Reverse Cycle Heat mode.
• If the return/supply water temperature is below the
programmed heating setpoint and the staging delay
has elapsed, the VARC energizes the compressor
relay.
• The compressor continues to run and the reversing
valve remains energized until the heating setpoint has
been reached or an alarm condition exists.
VARC Chiller Controls
• If setpoint is reached, the compressor reduces its
speed to maintain the water temperature. Once it has
reached temperature and a hysteresis of one degree,
the compressor turns off and the reversing valve turns
off immediately.
• A stage has a minimum run time of 60 seconds before
it can be turned off and a minimum off time of 10
seconds before it can be re-enabled. If the system calls
for a stage to be toggled on or off, the next available
stage that meets the staging criteria is used.
Compressor rotation is active during run mode:
• The compressor with the lowest running hours
is enabled first and compressor with the highest
running hours is disabled first.
• Enable Reverse Cycle Heat only for the system.
• After chilled water and sea water flows are stable for
10 seconds (default), the first stage is enabled and the
compressor starts.
• The first stage continues to run up to 100 percent
speed before enabling the next stage.
• If the PID loop requires demand, the next stage is
enabled with a startup delay of three minutes before
running up to the required speed.
Electric Heat (Optional Heater Barrel)
When Electric Heat is selected on the touch screen or
LCD buttons, the VARC starts heating according to the
temperature setpoint.
The VARC energizes the heater relay if return/supply
water temperature is below the programmed setpoint
and the staging delay has elapsed in a multi-stage
configuration.
Heater rotation is active during run mode:
• The heater with the lowest running hours is enabled
first and the heater with the highest running hours is
disabled first.
• Enable Electric Heat only for the system.
• After chilled water flow is stable for 10 seconds, the
first stage is enabled and the electric heater starts.
• The first stage continues to run for five minutes before
enabling the next stage.
• If the PID loop requires demand, the next stage is
enabled.
6 .1 .2 Pump Operation
The pump modes adjust as required by the system
operating mode.
Chilled Water Pump
The chilled water pump relay closes if the system is in
Heat or Cool mode. The pump is enabled five seconds
prior to the first stage being enabled. The pump is on for
continuous operation when system is enabled.
Sea Water Pump
The sea water pump has selectable operating modes
between continuous operation or cycle-with-compressor
operation. The default configuration is to cycle with the
demand.
The sea water pump relay closes five seconds before the
compressor starts in Heat or Cool modes. It opens five
seconds after the last compressor cycle is completed. If
immersion heating is available and used, the sea water
pump is disabled.
6 .1 .3 Current Power Limiting
The Econo Mode provides control over the capacity of
the system. When the user enables econo mode, the
system is limited by the speed of the compressor.
The default value for econo mode is 65%. Under
setpoints, the user can adjust the Econo Mode value
between 35% and 90%.
VARC Chiller Controls
Operation
6 .1 .4 Maintenance
Maintenance mode is available for troubleshooting. See
“Maintenance Mode” on page 39.
6 .2 Powerup and Startup
The VARC Chiller Controller can be operated as a single-
stage or a multi-stage chiller plant. During initial setup,
you configure the system for the number of stages and
the available options. The VARC System is set for supply
water control, but it can be modified for return water
control, if needed.
6 .2 .1 Normal Stage Startup
The system has a time delay between the staging up of
the various stages:
1. Stage 1 is initiated and starts its operation.
2. When the PID determines that more capacity is
required, stage 2 is initiated.
3. When the system has maintained the chilled water
loop and the PID has determined that no additional
stage is required or has met capacity demand, it
reduces the speed of the compressors.
4. The compressors then operate at minimal speed to
maintain the chilled water loop. If the speed of the
compressor still exceeds the demand, the stage with
the most run hours is turned off.
6 .2 .2 Operational Checks
When the VARC is enabled, the system performs pre-
startup checks on all chilled water flow switches and HP
switches.
Individual stage faults disable only that stage.
6 .2 .3 Compressor Startup
The VARC utilizes a BLDC compressor that is capable
of operating at a very high frequency which requires
that the compressor have a ramped startup to establish
proper lubrication so as to not damage the compressor.
This startup has a ramp time and a minimal speed
operation that will last for 100 seconds to allow the
compressor to properly warm up before operating at
maximum speed.
The compressor minimum on time is 60 seconds and
minimum off time is 10 seconds with a minimum time
between starts of 60 seconds. These default parameters
allow the compressor to operate in a safe mode that will
not damage the compressor.
6 .3 Operating the Touch Screen
ISome screens contain pop-up screens with
information. To exit a pop-up, simply touch the X to
close the screen.
6 .3 .1 Basic VARC Operations
From the Chiller Enable screen, you can perform the
basic VARC operations:
• Change setpoints
• Select Cool, Heat, or Electric Heat
• Monitor water temperature and pump status
• Turn the VARC off
To display the Chiller Enable screen, from the Main
screen, tap Chiller Enable. See “Touch Screen” on
page 5.
VARC Chiller Controls
Figure 10 shows the controls on the Chiller Enable
screen.
q
w
t
y
u
i
e
r
10 Chiller Enable Screen
q Home
y Setpoints
w Power Button
u Chilled Water Pump
e Cool Button
i Sea Water Pump
r Heat Button
o Econo Mode Button
t Electric Heat Button
• Home: Displays the Main screen.
• Power Button: Turns the VARC off. When the VARC
is in a run state, this button is green.
• Cool Button: Lights up with the word COOL when
the VARC is cooling. Tapping this button puts the
VARC into cool mode.
• Heat Button: Lights up with the word HEAT when
the VARC is heating. Tapping this button puts the
VARC into heat mode.
• Electric Heat Button: Lights up with the words
ELECTRIC HEAT when electric heat is enabled.
Tapping this button puts the VARC into Electric Heat
mode. This button is visible only if the electric heat
option is installed.
• Setpoints: Displays the current setpoints for cooling
and heating. Tapping the numbers changes the
setpoints.
• Chilled Water Pump and Sea Water Pump:
Tapping this area takes you to the Pump Status
screen.
• Econo Mode Button: Tapping this button displays
the Econo Mode screen, which allows you to select
Normal or Econo Mode.
6 .3 .2 Selecting Econo Mode
1. From the Main screen, tap Chiller Enable. See “Touch
Screen” on page 5.
2. In the top-left corner of the Chiller Enable screen,
click the Econo Mode button.
The Econo Mode screen appears.
11 Econo Mode Screen
3. Select the desired mode from the Compressor
Current Mode menu.
4. Select the Eco Mode Setpoint value to change the
value of the econo mode.
5. To return to the Chiller Enable screen, in the top-left
corner, tap the left-arrow button.
VARC Chiller Controls
Operation
6 .3 .3 Viewing Chiller Status for Each
Stage
The Chiller Summary screen provides chiller status for all
stages. It also indicates if a stage is in Alarm Retry mode.
1. To display the Chiller Summary screen, from the Main
screen, tap Chiller Summary. See “Touch Screen” on
page 5.
2. To display a stage, tap its VARC number.
12 Chiller Summary
6 .3 .4 Monitoring Refrigerant and Chilled
Water Circuits
The Chiller Stage screen provides a graphic
representation of the refrigerant and chilled water
circuits.
To display the Chiller Stage screen, from the Main screen,
tap Chiller Stage. See “Touch Screen” on page 5.
13 Chiller Stage Screen
IDepending on installed options, different icons
appear as hotspots for navigation to open another
window. When the system is in run mode, additional
icons appear to indicate cooling and heating.
Using the Electronic Expansion Valve (EEV), you can
monitor the following parameters:
a. Valve position
b. Suction pressure and temperature
c. Superheat setpoint and actual value
To view EEV parameters, on the Chiller Stage Screen,
tap the Expansion Valve icon.
14 Expansion Valve Screen
6 .3 .5 Viewing and Downloading
Performance Data
The Trends screen provides graphical representation of
the VARC performance data.
1. To display the Trends screen, from the Main screen,
tap Trends. See “Touch Screen” on page 5.
2. To change the time frame, select a time from the
menu. The default is one month.
VARC Chiller Controls
15 Chiller Trends Screen
3. To download performance data, insert a USB drive
into the USB port on the VARC, and then tap the USB
button.
IIf you do not put the USB drive in first, you get the
message shown in Figure “16 USB Message” on
page 24.
16 USB Message
6 .3 .6 Viewing Active Alarms and
Downloading Alarm History
The Alarms screen shows all active alarms and allows you
to view the alarm history.
1. To display the Alarm screen, from the Main screen,
tap Alarms. See “Touch Screen” on page 5.
2. To reset alarms, press the RESET ALARMS button.
3. To display the alarm history, tap the History button.
17 Active Alarm Screen
4. To change the time frame, select a time from the menu.
18 Alarm History Screen
5. To download alarm history, insert a USB drive into the
USB port on the VARC, then tap the USB button.
19 Download Alarm History
VARC Chiller Controls
Operation
6 .3 .7 Enabling Remote Control for Third-
Party Support
The Remote Support screen allows you to set up the
VARC for control by third-party technical support.
1. To display the Remote Support screen, from the Main
screen, tap Remote Support. See “Touch Screen” on
page 5.
2. To enable or disable remote support, tap the Enable
Remote Support button. (Default is enabled.)
20 Enable Remote Support Screen
3. In the MobileVNC Settings dialog box, on the
Control tab, press Start to begin remote login and
press Stop to finish.
21 MobileVNC Settings Dialog Box
4. Use the settings on the Advanced tab to select
configuration options for the remote login.
22 MobileVNC Settings Advanced Tab
6 .4 Operating the LCD Screen
IThe following LCD instructions refer to the
PGD1 display. For the PLDPRO display, use the
corresponding buttons. See “PLDPRO LCD
Display” on page 4.
6 .4 .1 Understanding the Display Screens
The Main screen allows you to monitor single-stage
operation and additional stages in multi-stage operation.
The Main screen displays the following parameters:
a. Mode of operation (Econo or Normal)
b. Chilled water return temperature
c. Chilled water supply temperature
d. Condenser outlet temperature
IThe condenser outlet temperature is the freeze
control indicator for the condensers in heat mode.
Pressing the Scroll Down button moves through the
various parameters displayed on the LCD screen. In a
multi-stage configuration, you can scroll through the
parameters of the additional stages.
VARC Chiller Controls
The screens following the main screen contain
information for each stage.
1. The first screen displays the CW Supply and CW
Return temperatures, flow switch status (Fl) and high
pressure status.
2. The next screen displays compressor speed and
information to indicate if the system is in a safety
count down. Once this time has elapsed and other
time delays have been met, the VARC starts up.
3. The next screen displays the suction pressure, the
discharge pressure, the superheat value, and the sub-
cooling value being calculated by the system.
4. The following screens display the drive status. To
access these screens, press Enter:
5. The final screen displays an image of the refrigerant
circuit and showing the valve position.
6 .4 .2 Adjusting Setpoints
1. Press the Program button. See “LCD Buttons” on
page 5.
2. Go to Setpoints, then enter the user password
(1234).
3. Press Enter once to update the Heating setpoint,
by pressing the Scroll Up or Scroll Down buttons to
change the value. Press Enter again to change the
cooling setpoint.
VARC Chiller Controls
Operation
6 .4 .3 Enabling Electric Heat
1. Press the Program button. See “LCD Buttons” on
page 5.
2. Scroll down to Technician, then press enter.
3. Scroll down to Service settings, then press Enter.
4. Enter the service password 3156.
5. Scroll down to System Setup, then press enter.
6. Scroll down to Electric Heat, press Enter to select,
and then press the Scroll Up or Scroll Down buttons
to toggle the setting.
7. Press Enter to save.
6 .4 .4 Setting Time and Date
1. Press the Program button. See “LCD Buttons” on
page 5.
2. Scroll to Clock/Scheduler, then press Enter.
3. Press Enter.
The cursor flashes on the date field: mm/dd/yyyy.
4. Use the Scroll Up and Scroll Down buttons to select
the correct month. Press Enter, then press the Scroll
Up and Scroll Down buttons to select the correct day.
5. Press Enter, then use the Scroll Up and Scroll Down
buttons to select the year.
6. Press Enter.
a. The cursor drops down to the Hour field.
VARC Chiller Controls
7. Use the Scroll Up and Scroll Down buttons to select
the correct hour, then select the minute.
a. The cursor goes back to the Clock title. Settings
have been saved and you can exit to Main screen.
b. Daylight Savings Time is enabled by default. If
you wish to disable, scroll down from the Clock
screen.
6 .4 .5 Changing Temperature Display
Units
1. Press the Program button. See “LCD Buttons” on
page 5.
2. Go to Setpoints, then enter the password (3156).
3. Scroll down to the Temperature Units screen. Press
Enter to select. Use the Scroll Up and Scroll Down
buttons to toggle between options.
4. After selecting the desired option, press Enter to
return the cursor to the top of the screen.
5. Make this change to all stages so that it correctly
reflects temperature readings on the remote display.
6 .4 .6 Viewing Alarms for Each Stage
The Main screen indicates alarms by flashing the word
Alarm in the lower-right corner.
IThe PLDPRO display sounds a tone as well as
displaying the word Alarm in the lower-right corner.
The Alarm screen captures a snapshot of the system
parameters at the time of the fault.
The alarm history captures and displays the following
parameters:
a. Compressor speed
b. Chilled water return
c. Chilled water supply
d. Discharge pressure
e. Suction pressure
1. To view the alarm information for more than one
stage, you need to switch boards via the display or
look at the PLDPRO display for that stage.
2. Use the alarm logger to view the alarm history.
3. To clear an alarm when a fault has been corrected,
press and hold the Alarm button for five seconds to
clear the active alarm.
VARC Chiller Controls
Operation
6 .4 .7 LCD Screen Menu Maps
The following diagrams show the menu options for each
screen available through the LCD displays.
The Main screen is displayed at powerup. It displays the
essential system information.
IAn asterisk (*) indicates an option that is available
only when activated in the factory settings.
Main Status Screen
CW Supply Temp
##.#°F
Mode
Off/Cool/Heat/ El Ht*
CW Return temp
##.#°F
CW Supply temp
##.#°F
Cond. Outlet temp
##.#°F
Mode
Off/Cool/Heat/El Ht*
Pumps
CW
On/Off
SW
On/Off
Chiller Status
Normal/Econo
Maint Mode Active
Stage #
Auto/Disabled
Varc #1
CW supply temp
##.#°F
CW return temp
##.#°F
Flow status
Ok/Alm/Off
High pressure status
Ok/Alm/Off
Electric Heat*
Ok/Alm/Off
Ok/Alm/Off
EH FL*
Compressor speed
#.# Hz
Compressor speed
#.# rps
Compressor Current #.# A
Suction
Temperature
##.#°F
Pressure
##.# psi
Saturation Temp.
##.#°F
Discharge
Temperature
##.#°F
Pressure
##.# psi
Saturation Temp.
##.#°F
Super heat temp
##.#°F
Subcooling temp
##.#°F
VARC #* (if multistage)
Varc #1 information
Varc # 1 Information
Compressor Capacity Regulator
Required Capacity %
Actual Capacity
%
Actual Speed
rps
Drive Status
Motor Current
#.# A
Motor Voltage
# Vrms
DC Bus Voltage
### V
Drive Temperature ## °F
Drive Status
Stopped/Running
Fault
Flow Diagram
Super Heat
## °F
Compressor
## °F
EEV Open %
## %
EEV Open Stps
### stp
EEV
### psi
Std-by temp
## °F
23 Main Screen
VARC Chiller Controls
The Program menu provides access to user settings, the Factory screen, and the Technician screen.
Program
Setpoints
Clock/Scheduler
Input/Output
Alarm History
Board Switch
Technician
Factory
Analog Output
Output ##.# Vdc
Setpoints
Heating Temperature ##.# °F
Cooling Temperature ##.# °F
Electric Heat*
SP
##°F
Stg Up
Stg Down
1 SP - #°F
1 SP + #°F
Current Limiting
Mode
Normal/Boost/Econo
Econo
#.# Amps
Normal
#.# Amps
SW Pump Control
By Demand/By Unit On
Temperature Units
°F/°C
Pressure Units
psi/bar
Clock/Scheduler
Date
##/##/##
Hour
##:##
Day
###
DST
Enable/Disable
DST Enable
Transition
###
Start
###
End
###
Input/Output
Analog Input
Digital Input
Relay Output
Analog Outputs
Analog Input
CW Return Input B001
###
CW Supply Input B002
###
SW Inlet Input B003
###
Digital Input
Flow switch DI 3
Open/Close
Electric Heat Fl DI 5
Open/Close
High pressure switch DI 1
Open/Close
Load Shedding Switch DI 4
Open/Close
Cool Mode Switch DI 6
Open/Close
Heat Mode Switch DI 7
Open/Close
Relay Output
SW Pump Relay 1
On/Off
CW Pump Relay 2
On/Off
REV Valve Relay 3
On/Off
Electric Heat Rly 4
On/Off
Alarm Relay 7
On/Off
Board Switch
Unit address: ##
Switch to unit: ##
Technician
See Figure 25
Factory
See Figure 27
Alarm History
Alarm#
Message
Compressor Speed
###
CW Return
###
CW Supply
###
Discharge Pressure
###
Suction Pressure
###
24 Program
VARC Chiller Controls
Operation
The Technician menu requires the technician password (3156).
BMS Configuration
BMS Port No. #
Pr otocol
###### (scroll)
Address
#
Baud Rate
#####
Technician
Information
Commission
Working Hours
BMS Configuration
Service Settings
Manual Management
Pump Control
Information
Service Contact Phone
###-###-####
Version & Date
#.##
##/##/##
BIOS & Date
#.##
##/##/##
Boot & Date
#.##
##/##/##
Flash Ram
### Kb
T memory
###
## Cycle/s
#### ms
Power Cycle Status
Last Off Time
##/##/## ##:##:##
Last On Time
##/##/## ##:##:##
Length Time off
Days: #
Hrs: ##
Min: ##
EVO no.
FW Version
#.#
Service Version
#.#
Power+ no.1
Boot release
###
FW release
###
FW checksum
###
MC release
###
Hardware ID
###
Commission
Enter contact info
Name
####
Telephone No.
###-###-####
Update info?
Yes/No
Commission date
##:## ##/##/##
Commission system?
Yes/No
Working Hours
Run Hrs
Compressor
### h
Electric Heat*
### h
Chilled Water Pump ### h
Seawater Pump
### h
Service Settings
See Figure 26
Manual Management
Analog Input
Digital Input
Relay Output
Compressor & EEV
Analog Input
Man Ctrl
Man. Pos. Value
CW Return
B001 On/Off ##.#
##.#
CW Supply
B002 On/Off ##.#
##.#
SW Inlet
B003 On/Off ##.#
##.#
Digital Input
Man C trl
Man. Pos.
Value
Flow
DI 3 On/Off
Open/Close
Open/Close
El. Heat Fl
DI 5 On/Off
Open/Close
Open/Close
High Press
DI 1 On/Off
Open/Close
Open/Close
Load shed
DI 4 On/Off
Open/Close Open/Close
Relay Output
Man. C trl
Man. Pos. Value
SW Pump
Relay 1 On/Off
On/Off
CW Pump
Relay 2 On/Off
On/Off
Rev valve
Relay 3 On/Off
On/Off
Electric Heat Relay 4 On/Off
On/Off
Alarm
Relay 7 On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
Compressor & EEV
Enable manual valve position
Yes/No
Manual Valve position
# steps
Compressor
Mode
Auto/Man.
Manual Speed
###.# rps
Required cap.
##.# %
Actual cap.
##.# %
Actual Speed
###.# rps
Pump Control
Ctrl
Pos. Status
CW
On/Off On/Off On/Off
25 Program/Technician
VARC Chiller Controls
Stage Address
pLAN Board Addressing
Current Address
#
Change Address to
#
Unit Settings
No. of Stages
#
Service Settings
Working Hour Set
Probe Adjustments
Control Loops
Reset System
Stage Address
Stage Disable
System Setup
Probe Adjustments
Input Offset Value
CW Return
B001 ##.#
##.#
CW supply
B002 ##.#
##.#
SW Inlet
B003 ##.#
##.#
Probe adjust
S1 offset
##.# barg
S1 probe
##.# barg
S2 offset
##.# °C
S2 probe
##.# °C
S3 offset
##.# barg
S3 probe
##.# barg
S4 offset
##.# °C
S4 probe
##.# °C
Working Hour Set
Set Pt
Rst to 0?
Run H rs
Compressor
#### h
Yes/No
#### h
Electric Heat*
#### h
Yes/No
#### h
Chilled Water Pump #### h
Yes/No
#### h
Seawater Pump
#### h
Yes/No
#### h
Control Loops
Superheat Setpoint
Cool Setpoint
##°F
Heat Setpoint
##°F
Thermoregulator
Setpoint SH
##°F
LowSH threshold
##°F
LOP threshold temp
##°F
MOP threshold
##°F
Modulatin g Setup
Compressor
Input
#.#
Output
#.#
Setpoint
#.#
K
#
#
.#
Integration Time
Stage Disable
Stage Control Yes/No
Stage #
Auto/Disabled
System Setup
Water Loop Control
Supply/Return
Electric Heat
Yes/No
EH Flow Switch*
Yes/No
Varc Type
None/Varc48/60/72
Compressor
(Scroll if custom)
Power type
230 V / 16 A
Power set
230 V / 30 A
Set Defaults
Yes/No
Reset System
Clear Alarm History
Yes/No
Default Installation
Yes/No
26 Program/Technician/Service Settings
VARC Chiller Controls
Operation
The Factory menu requires the factory password, which is available only to authorized Dometic personnel.
Initialization
Erase user settings and install global default value
Yes/No
Clear all saved data Factory + User
Yes/No
Insert New Passwords
User
####
Technician (PW1)
####
Factory (PW2)
####
I/O Configuration
See Figure 32
Factory
Configuration
I/O Configuration
Factory Settings
Initialization
Factory Settings
See Figure 28
Configuration
Temperature Units
°F/°C
Pressure Units
psi/bar
Force clock enable
Yes/No
Clock mode
24h/12h
Disable Buzzer
Yes/No
Startup delay
### s
Enable Unit by
Digital Input
On/Off
Supervisor
On/Off
pLAN network
On/Off
Schedule
On/Off
Unit Control
Custom 1
On/Off
Custom 2
On/Off
Custom 3
On/Off
Custom 4
On/Off
Analog Input Filtering
Enable
Yes/No
Input 1
## s
Input 2
## s
Input 3
## s
Manual Control Reset
Enable
Yes/No
Time
# m
PW/Return Delay
### s
Scheduler
Holidays No.
##
Modbus Settings
1st Master
Baudrat e
#####
Stop bit
1/2
Parity Mode None/Even/Odd
Evo Configurator
Power+ n 1
Power + n1
See Figure 30
EVO Configuration
See Figure 29
27 Program/Factory
VARC Chiller Controls
In the following diagram, the dotted boxes indicate a breakout of the additional information that is contained below that
menu category.
Alarm Setup
Temperature Limits
Set Pt.
Off
Band
Retries
Set
Dis able
Status
CW High
##.#°C ##.#°F
#/## m
## s
#/## m
CW f reeze ##.#°C ##.#°F
#/## m
## s
#/## m
Delay
Retries
Set
Disable
Status
CW Flow
## s
#/## m
## s
#/## m
El Heat Fl
## s
#/## m
## s
#/## m
High Disch
Pressure
## s
#/## m
## s
#/## m
High Press
## s
#/## m
## s
#/## m
Low Suct
Pressure
## s
#/## m
## s
#/## m
Low Suction Pressure
Cool Set Point
##.# bar
Heat Set Point
##.# bar
Inverter
Retrys
#/## m
Set Disable
## s
Status
#/## m
CW Pump Shutdown
Cool Setpoint
##.# °F
Heat Setpoint
##.# °F
CW Alarm Delay
## s
Factory Settings
Varc Type
None/Varc48/
60/72/96
Compressor
Scroll to select
Refrigerant
R410A
Power type
Based on Inverter
Power set
Based on Inverter
Set Defaults
Yes/No
Control Temp
CCW supply/
CCW return
No. of stages
#
Electric Heat (EH)
Yes/No
Power Cycle
Retain Mode/Off
Logo
Select appropriate
Background
Select appropriate
Flow Switch
Yes/No
High Pressure Switch
Yes/No
Low Pressure Switch
Yes/No
EH Flow Switch*
Yes/No
Load Shedding
Yes/No
SW Temp Inlet
Yes/No
SW Pump settings
Control
By demand/
By unit on
Off Delay
## s
Pump Current
Yes/No
Current Select
10/30/50/75 A
CW Pump settings
Flow Prove Delay
## s
Off Delay
## s
Pump Current
Yes/No
Current Select
10/30/50/75 A
Reversing valve
RV delay time
## s
RV toggle time
## s
RV delay ON time
## s
Electric Heat
Stg Up delay
## s
Stg Down delay
## s
Compressor
Alarm Setup
Compressor
Econo mode SW
Yes/No
Minimum On
## s
Minimum Off
## s
Min Time between Starts
## s
Load Up Time
## s
Frost Protection
Condenser Setpoint
##.#°F
Condenser Band
##.#°F
Compressor Speed
##.# rps
Envelope Zone
(Envelope Status)
Control
Direct/Reverse/Both P/PID/P+I
K
##.#
Minimum
####
Maximum
####
DBd
##.#
Out
##
28 Program/Factory/Factory Settings
VARC Chiller Controls
Operation
Configuration
Valve
Select Type
Main Regulation
Select Type
Auxiliary Regulation
Select Type
Probe Configuration
Probe S1
Probe S2
Probe S3
Probe S4
Alarm
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Type
Select
Select
Select
Select
Minimum
#.# barg
#.# barg
Maximum
#.# barg
#.# barg
Alarm Min. #.# barg
## °C
#.# barg
## °C
Alarm Max. #.# barg
## °C
#.# barg
## °C
Alarm Mngt
Use backup
S3/valve at fixed
pos/valve forced
closed/no action
valve at fixed
pos/valve forced
closed/no action
Use backup
S3/valve at fixed
pos/valve forced
closed/no action
valve at fixed
pos/valve forced
closed/no action
Regulation
Valve opening at start-up
## %
Valve opened in standby
## %
Prepositioning delay
### s
Alarm delay
Low SH
### s
LOP
### s
MOP
### s
Alarm low suction temp
Threshold
## °C
Timeout
### s
Custom
Minimum steps
###
Maximum steps
###
Closing steps
###
Nom. Step rate
## Hz
Fast step rate
## Hz
Holding current
## mA
Duty cycle
## %
Opening synchronicity
Yes/No
Closing synchronicity Yes/No
EVO Configuration
Configuration
Regulation
Custom
29 Program/Factory/Configuration/EVO Configuration
VARC Chiller Controls
Regulation
See Figure 31
Custom
Motor Poles #
Motor Control Mode PM Motor/AC Motor Vector/AC Motor
Motor base freq.
###.# Hz
Motor base vol.
### Vrms
Motor rated current
##.# Arms
Motor power factor
##
Out current maximum
#.#%
Speed profile
Frequency # (1-3)
###.# Hz
Acc. # (1-4)
###.# Hz/s
Delay # (1-3)
### s
Delay execution
Always/Single
Force freq. 2
Enabled/Disabled
Deceleration ramp ###.# Hz/s
V/F Boost voltage
#.#%
V/F Freq. adjustment #.#%
V/F Volt. Adjustment #.#%
Motor Mag. Current
#.# A
Stator Resistance
# mOhm
Rotor Resistance
# mOhm
Stator/Ld inductance #.# mH
Leakage factor
#
Lq Inductance
#.# mH
Speed Loop Kp
##.# %
Speed Loop Ki
### ms
Magnetizing Time
### ms
Starting Current
#.# % #.# A
Freq. for Start Cur
#.# %
Crankcase heater
Auto/Force Off/Force On
Crankcase current
#.# % #.# A
STO alarm mngt
Manual Res/Disable/Auto Reset
Phase loss detection
Enable
Overload at Power-on
Reset/Restored
Enable Manual R/W Yes/No
Address
#
Read Value
#
Write Value
# Yes/No
Power + n1
Configuration
Regulation
Custom
Configuration
Motor Type
Select
Set Defaults
Yes/No
Save to Custom
Yes/No
Data Comm. Timeout
## s
U.M. speed
Hz/rps
Drive Replacement
Do Nothing/Download Parameters
30 Program/Factory/Configuration/Power + n1
VARC Chiller Controls
Operation
In the following diagram, the dotted boxes indicate a breakout of the additional information that is contained below that
menu category.
IAn asterisk (*) indicates an option that is available only when activated in the factory settings.
Regulation
Output frequency min
#.# Hz
Output frequency max
#.# Hz
Skip frequency set #(1-3)
#.# Hz
Skip frequency band #(1-3)
#.# Hz
Switching frequency
# kHz
Switching frequency derating
Disabled/Enabled
Speed derating mode
##
Stop mode
Ramp/Coast
Reverse Speed
Disabled/Enabled
Flying Start
Disabled/Enabled
Relay Configuration
Select
PTC Alarm
Disabled/Enabled
PTC Alarm delay
## s
Compressor Regulator
Start -up pressure differential control
Max pressure diff. admitted
#.# bar
Equalization mode
Equalztn valve/EEV Pre-Opening
Start -up failure control
Pressure diff. min. variation
#.# bar
Control period
## s
Restart delay
## s
Max Retry #
#
Speed Management
Start -up forced speed
##.# rps
Max speed
##.# rps
Min speed
##.# rps
Deceleration rate
#.# rps/s
Acceleration rate
#.# rps/s
Switch -off rate
#.# rps/s
Envelope Control
Speed reduction rate
#.# rps/s
Min speed admitted
#.# rps
Out of env. Alarm timeout
## s
Low press. diff. alarm timeout
## s
Discharge Gas Control High Discharge Temp.
Limit
##.# °C
Alarm
##.# °C
Speed Control due to Discharge Gas
Action Distance
##.# °C
Action Pause
## s
Comp. Speed Reduction
#.# %
EEV Regulation
Mode
Select from EEV Mode List
Discharge Temp Probe Comp Time
##.# s
Discharge
Super Heat
Temperature
Setpoint
##.# °C
##.# °C
Offset
##.# °C
##.# °C
Hystere sis
##.# °C
##.# °C
Envelope Control - Low ratio management
By EEV closing
Yes/No
By compressor speed
Yes/No
EEV Pre-Opening*
Max. Equalization
## s
EEV opening
##.# %
EEV Mode List
Suction Superheat
Discharge Temperature
Discharge Superheat
31 Program/Factory/Configuration/Power + n1 /Regulation
VARC Chiller Controls
Analog Inputs
Enable
CW Return
CW Supply
SW Inlet
On/Off
On/Off
On/Off
Channel
B001
B002
B003
Normal/High Res.
Normal/High Res.
Normal/High Res.
Input Type
Select/(On/Off)
Select/(On/Off)
Select/(On/Off)
On/Off
Direction
Reverse/Direct
Reverse/Direct
Reverse/Direct
Delay Time
## s
## s
## s
Value
Open/Closed
Open/Closed
Open/Closed
Select type
Minimum
##.#
##.#
##.#
Maximum
##.#
##.#
##.#
Offset
##.#
##.#
##.#
Value
##.#
##.#
##.#
Out of Range Alarm
Power Delay
# s
# s
# s
Run Delay
# s
# s
# s
Units
Temp/Press/Other
Temp/Press/Other
Temp/Press/Other
Digital Inputs
Switches
Enable
Channel
Action
Delay
Status
Flow
On/Off
#
Open/Close
### s
Open/Close
EH Flow*
On/Off
#
Open/Close
### s
Open/Close
High Press
On/Off
#
Open/Close
### s
Open/Close
Low Press
On/Off
#
Open/Close
### s
Open/Close
LoadShed
On/Off
#
Open/Close
### s
Open/Close
Econo Mode
On/Off
#
Open/Close
### s
Open/Close
Relay Output
Enable
Channel
Status
SW Pump
Yes/No
#
On/Off
CW Pump
Yes/No
#
On/Off
Rev Valve
Yes/No
#
On/Off
El Heat*
Yes/No
#
On/Off
Alarm
Yes/No
#
On/Off
Analog Output
Channel
# 0-6
Enable
Yes/No
Action
Direct/Reverse
Minimum
##.# Vdc
Maximum
##.# Vdc
I/O Configuration
Analog Inputs
Digital Inputs
Relay Outputs
Analog Outputs
32 Program/Factory/IO Configurations
Display Address
Display address setting
#
I/O Board address
#
Terminal config
Terminal configuration
P: 01 Adr
Priv/Shared
Trm1
16/17/18/…
Trm2
32
Trm3
None
33 Display Address
VARC Chiller Controls
Maintenance Mode
7 Maintenance Mode
In Maintenance mode you can disable any of the stages
in the system. This allows for ease of troubleshooting
and maintenance on one unit, while maintaining full
functionality for the other stages.
�
WARNING: ELECTRICAL SHOCK HAZARD .
Maintenance and repair should be performed
only by qualified technicians. Failure to obey this
warning could result in death or serious injury.
7 .1 Accessing Maintenance Mode
from the LCD Screen
1. In the Main screen, press Enter and scroll up or down
to select OFF, then press Enter to save.
2. To access the Maintenance mode menu, press
Program, scroll to Technician, and then press Enter.
3. Scroll to service settings, then press Enter.
4. Enter the service password: 3156.
5. Scroll to Stage Disable, then press Enter.
6. For Stage Control, change No to Yes, press Enter,
scroll up, and then press Enter.
The screen displays the stages.
7. Press Enter to access each stage, then scroll up or
down to change from Auto to Disabled.
7 .2 Accessing Maintenance Mode
from the Touch Screen
1. Tap the touch screen to view the menu buttons,
then tap Chiller Summary. See “Touch Screen” on
page 5.
IThe system must be in off mode to access
maintenance mode.
VARC Chiller Controls
2. Tap the wrench icon.
34 Chiller Summary
3. From the Chiller Control menu, select YES to enable
Maintenance mode.
35 Chiller Control Menu
4. To disable a stage, tap the menu to the right of the
stage number and select Disabled.
36 Disable Stage
5. Tap X to exit, then turn on the VARC.
8 Troubleshooting
The following tables describe the VARC alarm
characteristics and corrective actions.
�
WARNING: ELECTRICAL SHOCK HAZARD .
Failure to obey the following warnings could
result in death or serious injury:
• Exercise extreme care when working around
energized equipment.
• Maintenance and repair should be performed only by
qualified technicians.
8 .1 Alarms
In the event of a fault, the system does not generate an
alarm immediately, but instead applies an alarm retry
logic scheme. The system shuts down and attempts
the number of retries that is set on the parameters table
before creating an alarm that needs to be reset manually.
The following table describes the alarm conditions and
corrective actions to be taken.
VARC Chiller Controls
Troubleshooting
Alarm
Reset
Delay
Alarm
Relay
System Action
Corrective Actions
Alarms Power+ n˚1
None
1:Overcurrent
2:Motor Overload
3:Overvoltage
4:Undervoltage
5:Over Temp
6:Under Temp
7:Overcurrent HW
8:Motor Overtemp
9:Drive Failure
10:CPU Error
11:Param Default
12:DC bus ripple
13:Data Comms Fault
14:Drive thermistor
15:Autotune fault
16:Drive disabled
17:Motor Phase
18:Fan Fault
19:Speed Fault
20:PFC Failure
21:Overvoltage
22:Undervoltage
23:STO Detection
24:Reserved
25:Ground Fault
26:CPU Sync 1
27:CPU Sync 2
28:Drive overload
29:Reserved
…
99:Unexpected
inverter stop
Manual
Immediate
Yes
Turns off compressor
• Check the load.
• Check the network control
devices and cables.
• Check the input voltage.
• Using a 1000 V
megohmmeter, check the
motor and motor cables for
ground faults.
• Check the input and output
circuits for phase loss
detection.
• Check the condition of the
motor and load wiring.
Chilled Water Flow
After three
retries every
30 minutes,
must be reset
manually
Immediate
Yes
Turns off compressor or
heat relay
• Check for proper loop water
flow and make sure the
strainers are not clogged.
• Check for a defective flow
switch.
• Bleed air out of the loop
water.
• Check the loop water pump.
Chilled Water Return
Sensor Failure
Manual
Immediate
Yes
Turns off VARC
• Check the sensor for shorts
and opens.
• Compare the temperature
reading with the digital
thermometer.
Chilled Water Supply
High
Manual
10 sec
Yes
Turns off compressor or
heat relay
Check for low water flow due to
restrictions or pump wear.
Chilled Water Supply
Low
Manual
10 sec
Yes
Turns off compressor or
heat relay
Check for low water flow due to
restrictions or pump wear.
VARC Chiller Controls
Alarm
Reset
Delay
Alarm
Relay
System Action
Corrective Actions
Chilled Water Supply
Sensor Failure
Manual
Immediate
Yes
Turns off VARC
• Check the sensor for shorts
and opens.
• Compare the temperature
reading with the digital
thermometer.
Clock Board Fault or
Not Connected
Automatic
Immediate
Yes
Warning signal
Compressor Start
Failure
After 5 times
in 60 minutes,
must be reset
manually
10 sec
Warning signal
• Compare the voltage to the
compressor.
• Check the power inverter.
Condenser Out
Temperature Sensor
Failure
Manual
Immediate
Warning signal
• Check the sensor for shorts
and opens.
• Compare the temperature
reading with the digital
thermometer.
Electric Heat Run
Hours Exceeded
Yes
Turns off heater
Check heater the voltage.
Envelope Alarm
Manual
60 sec
Yes
Turns off compressor
EVD Evo High
Evaporation
Temperature (MOP)
Automatic
Immediate
Yes
Warning signal
Check the refrigerant charge.
EVD Evo Low
Evaporation
Temperature (LOP)
Automatic
Immediate
Yes
Warning signal
• Check the water flows.
• Check the refrigerant charge.
EVD Evo Low Suction
Temperature
Automatic
Immediate
Yes
Warning signal
Check the refrigerant charge.
EVD EVO Low
Superheat
Automatic
Immediate
Yes
Warning signal
• Check for proper refrigerant
charge as the system may be
overcharged.
• Check the water for low flow.
• Check the EEV movement
and functionality.
EVD Evo Probes fault
or disconnected (S1,
S2, S3, S4)
Automatic
Immediate
Yes
Turns off compressor
Check the condition of the wiring
and connections.
Frost Active
Manual
Immediate
Yes
Slows down
compressor
• Low temperature temp switch
tripped.
• Check the water flows.
• Check r the efrigerant charge.
High Discharge Gas
Temperature
Automatic
30 sec
Warning signal
Check for the proper refrigerant
pressure with the gauge.
VARC Chiller Controls
Troubleshooting
Alarm
Reset
Delay
Alarm
Relay
System Action
Corrective Actions
High Discharge
Pressure
After 3 retries
every 30 mins,
must be reset
manually
Immediate
Yes
Turns off VARC
• Check for the proper
refrigerant pressure with the
gauge. If normal, check for a
defective pressure switch.
• Check that there is proper sea
water and loop water flow.
• Check that water strainers are
not clogged.
• Check that the system is not
overcharged.
Inverter Model Not
Compatible
After 15 retries
every 60 mins,
must be reset
manually
Make sure Power+ is being used.
Low Pressure
Differential
Manual
90 sec
Yes
Turns off VARC
• Check the EEV motor.
• Use a gauge to check for
proper the refrigerant
pressure.
• Check suction the
temperature to verify that the
reversing valve is in proper
position.
Low Suction Pressure
After 3 retries
every 30 mins,
must be reset
Manually
60 sec
Yes
Turns off VARC
• Use a gauge to check for the
proper refrigerant pressure. If
normal, check for a defective
pressure switch.
• Check for the proper sea
water and loop water flow ‘
• Check that the water strainers
are not clogged.
• Check that the system is not
undercharged.
Power+ Device Offline
Automatic
30 sec
Yes
Turns off compressor
Power+ in Retry
Warning signal
Check the power supply.
Sea Water Inlet Low
Manual
10 sec
Yes
Warning signal
Low temperature due to
geographical climate.
Sea Water Inlet Sensor
Failure
Manual
Immediate
Yes
Warning signal
• Check the sensor for shorts
and opens
• Compare the temperature
reading with the digital
thermometer.
VARC Chiller Controls
8 .2 Envelope Zone Status
Descriptions
Refer to the following table for envelope alarms. The
alarm shows the zone number and the description
provides details.
Zone
Name
Description
1
Inside envelope
zone
Working point inside limits
2
High compression
ratio
Low gas density ->
maximum discharge
temperature
3
High condensing
pressure
Mechanical limit
4
Maximum motor
current
High gas density->
maximum torque
5
High evaporating
pressure
High gas density->
mechanical limit, noise
6
Low compression
ratio
Loss of contact between
spirals, vibrations
7
Low pressure
difference
Loss of lubrication
8
Low condensing
pressure
Low oil temperature ->
high viscosity -> poor
lubrication
9
Low evaporating
pressure
Low gas density -> low
motor cooling
9 Disposal
M
Place the packaging material in the appropriate
recycling waste bins, whenever possible. Consult
a local recycling center or specialist dealer for
details about how to dispose of the product in
accordance with all applicable national and local
regulations.
10 Warranty Information
LIMITED WARRANTY AVAILABLE AT
WWW.DOMETIC.COM/WARRANTY.
IF YOU HAVE QUESTIONS, OR TO OBTAIN A COPY
OF THE LIMITED WARRANTY FREE OF CHARGE,
CONTACT:
DOMETIC CORPORATION
MARINE CUSTOMER SUPPORT CENTER
2000 NORTH ANDREWS AVENUE
POMPANO BEACH, FLORIDA, USA 33069
1-800-542-2477
Mobile living made easy.
dometic .com
YOUR LOCAL
DEALER
dometic .com/dealer
YOUR LOCAL
SUPPORT
dometic .com/contact
YOUR LOCAL
SALES OFFICE
dometic .com/sales-offices
A complete list of Dometic companies, which comprise the Dometic Group, can be found in the public filings of:
DOMETIC GROUP AB Hemvärnsgatan 15 SE-17154 Solna Sweden