Dometic PGD1 Installation And Operation Instructions Manual

Specifications

Brand: Dometic
Category: Control Unit
Model: PGD1 (Installation And Operation Instructions Manual)
File Type: PDF
File Size: —
Pages: 48

Read Online

Read the Dometic PGD1 Installation And Operation Instructions Manual online using the built-in PDF viewer.

Text of the manual

L-3499 | Form No. 338208 20200323 | ©2020 Dometic Corporation

WARNING Cancer and Reproductive Harm www.P65Warnings.ca.gov VARC MODELS EN VARC Chiller Controls Installation and Operation Instructions . . . .2

VARC Chiller Controls

1 Explanation of Symbols and Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.1 Recognize Safety Information . . . . . . . . . . . . .2 1.2 Understand Signal Words . . . . . . . . . . . . . . . .2 1.3 Supplemental Directives . . . . . . . . . . . . . . . . .3 1.4 General Safety Messages . . . . . . . . . . . . . . . .3 2 General Information . . . . . . . . . . . . . . . . . . . . . 3 2.1 Product Description . . . . . . . . . . . . . . . . . . . .3 2.2 Inputs and Outputs . . . . . . . . . . . . . . . . . . . . .6 2.3 Default Parameters . . . . . . . . . . . . . . . . . . . . . .8 3 Intended Use . . . . . . . . . . . . . . . . . . . . . . . . . . 12 4 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 12 5 Installation and Setup . . . . . . . . . . . . . . . . . . . 13 5.1 Initial Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 13 5.2 Multi-stage Wiring . . . . . . . . . . . . . . . . . . . . . 14 5.3 Touch Screen Connection . . . . . . . . . . . . . . 15 5.4 Firmware Verification . . . . . . . . . . . . . . . . . . . 15 5.5 Networking . . . . . . . . . . . . . . . . . . . . . . . . . . 16 5.6 Configuring Display Addresses . . . . . . . . . . 17 5.7 VARC Standard Wiring Diagram . . . . . . . . . . 18 6 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 6.1 Operational Modes . . . . . . . . . . . . . . . . . . . . 19 6.2 Powerup and Startup . . . . . . . . . . . . . . . . . . 21 6.3 Operating the Touch Screen . . . . . . . . . . . . 21 6.4 Operating the LCD Screen . . . . . . . . . . . . . .25 7 Maintenance Mode . . . . . . . . . . . . . . . . . . . . . 39 7.1 Accessing Maintenance Mode from the LCD Screen . . . . . . . . . . . . . . . . . . . . . . . . . .39 7.2 Accessing Maintenance Mode from the Touch Screen . . . . . . . . . . . . . . . . . . . . . . . . .39 8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 40 8.1 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 8.2 Envelope Zone Status Descriptions . . . . . . .44 9 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 10 Warranty Information . . . . . . . . . . . . . . . . . . . 44 Contents Service Center & Dealer Locations Visit: www.dometic.com Read these instructions carefully. These instructions MUST stay with this product. 1 Explanation of Symbols and Safety Instructions This manual has safety information and instructions to help you eliminate or reduce the risk of accidents and injuries. 1 .1 Recognize Safety Information � This is the safety alert symbol . It is used to alert you to potential physical injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death. 1 .2 Understand Signal Words A signal word will identify safety messages and property damage messages, and also will indicate the degree or level of hazard seriousness. � DANGER! Indicates a hazardous situation that, if not avoided, will result in death or serious injury. � WARNING Indicates a hazardous situation that, if not avoided, could result in death or serious injury. � CAUTION Indicates a hazardous situation that, if not avoided, could result in minor or moderate injury. NOTICE: Used to address practices not related to physical injury. IIndicates additional information that is not related to physical injury.

VARC Chiller Controls

General Information 1 .3 Supplemental Directives To reduce the risk of accidents and injuries, please observe the following directives before proceeding to install or operate this appliance: • Read and follow all safety information and instructions. • Read and understand these instructions before installing or operating this product. • The installation must comply with all applicable local or national codes, including the latest edition of the following standards: – American Coast Guard Standards (CG-ENG) – American Boat and Yacht Council (ABYC) – ANSI/NFPA70, National Electrical Code (NEC) 1 .4 General Safety Messages � WARNING: ELECTRICAL SHOCK, FIRE, AND/ OR EXPLOSION HAZARD . Failure to obey the following warnings could result in death or serious injury: • Use only Dometic replacement parts and components that are specifically approved for use with the appliance. • Avoid improper installation, adjustment, alterations, service, or maintenance of the appliance. Service and maintenance must be done by a qualified service person only. • Do not modify this product in any way. Modification can be extremely hazardous. • Use care when diagnosing and/or adjusting components on a powered unit. 2 General Information The Dometic Variable Capacity Chiller (VARC) includes a microcontroller-based unit to control multiple chillers. The multiple-chiller design provides flexibility in the control application and improved controls and system protection. IThe images used in this document are for reference purposes only. Components and component locations may vary according to specific product models. Measurements may vary ±0.38 in. (10 mm). 2 .1 Product Description This section describes some of the key design features of the VARC, the control application, the LCD and touch screen displays, and the inputs and outputs. 2 .1 .1 VARC Design Features The VARC uses a precision Proportional Integral Derivative (PID) loop control algorithm that manages the capacity requirements of the system by modulating the compressor speed and balancing chiller output with the required load. The PID system differs greatly from the on/off control of a standard chiller system, as the PID modulates the speed of the compressor to increase or decrease its capacity allowing for reduced current consumption by the electrical system. This smooth operation eliminates large swings in current on the generator. This completely variable capacity chiller uses an inverter to modulate the speed of the compressor to achieve the desired chilled water setpoint. This allows the compressor to run at a minimum speed of 30 Hz to a maximum of 240 Hz depending on compressor model. The VARC also uses the advanced technology of an Electronic Expansion Valve (EEV). This provides more precise control of superheat across a broad range of conditions with no erratic swings as the valve reacts to temperature and pressure changes (no “hunting”). Using an advanced algorithm, the VARC maintains superior superheat control over extreme operating conditions. The VARC controller is internally grounded with isolation between inputs and outputs. The output relays offer double isolation so that different voltages can be used for groups of relays. For temperature measurements, the system uses NTC type 10K@77° thermistors. For both suction and discharge monitoring, the system uses ratiometric 0–650 PSI (45 bar) range pressure transducers.

VARC Chiller Controls

2 .1 .2 VARC Control Application The built-in VARC control application supports the following features: • Selection and sequencing of up to six chillers • Selection and sequencing of one Chilled Water Pump (CWP) and one or more Sea Water Pumps (SWP) • Selection and sequencing of up to six electric heaters • Sequencing of devices for run time equalization • Alarms and interlocks • Load shedding • Troubleshooting help Sequencing for chillers, pumps, and heaters is the order in which they start up and turn off. Sequencing is based on run time, which is the amount of hours a specific compressor, pump, or heater has run. The VARC is factory programmed with the options enabled for that system. Although the system offers flexibility, these options can be enabled only by a factory representative. Users can select Normal, Econo, or Boost mode operation in a single-stage configuration. 2 .1 .3 PGD1 LCD Display The PGD1 provides an LCD display and six buttons for navigating the control software. q r w t e y 1 PGD1 LCD Display Components q Alarm r Scroll Up w Program t Enter e Escape y Scroll Down 2 .1 .4 PLDPRO LCD Display The PLDPRO provides an LCD display and six buttons for navigating the control software. q r w t e y 2 PLDPRO LCD Display Components q Alarm r Scroll Up w Program t Enter e Escape y Scroll Down

VARC Chiller Controls

General Information 2 .1 .5 LCD Buttons The buttons on the PGD1 and PLDPRO operate as described in the following table: Button Description Alarm This button flashes red if there is an active alarm. Pressing this button displays the active alarm screen. See “Viewing Alarms for Each Stage” on page 28. Program This button displays the system menus. Use the scroll buttons to step through the options. Press the Enter button to select an option. Escape This button exits the current screen and displays the previous screen. Pressing this button multiple times displays the Main screen. Scroll Up and Scroll Down These buttons step through available menu options, change values in fields such as setpoints, and navigate from page to page when the flashing cursor is in the upper-left corner. Enter This button confirms menu option selections. Pressing Enter repeatedly moves the cursor the upper-left corner. 2 .1 .6 Touch Screen This section describes the navigation buttons on the Main screen. 3 Touch Screen: Main Screen with Navigation Buttons. The navigation buttons function as follows: • Enable: Enter setpoints, monitor chilled water temperatures and monitor pump current information. • Summary: View the state of HP, EH, FS, and water temperature for all available stages. Tapping a stage displays additional information on that stage. • Chiller Stage: Monitors the refrigerant and chilled water circuits. Provides hotspot icons that display additional information when selected. Different icons appear depending which options are installed. The Forward and Back buttons navigate between stages. • Trends: View a graphical display of water temperature, water pressure, and compressor current. Data is downloadable to a USB memory stick. • Alarms: View and clear alarms. Pressing the buttons at the top-right displays alarm history and other alarm information. • Remote Support: Enable third-party technical support to view your system over an Internet connection using a VNC (Virtual Network Computing) server.

VARC Chiller Controls

2 .2 Inputs and Outputs The VARC allows you to monitor analog inputs, digital inputs, and relay outputs to determine the status of the system. 2 .2 .1 Analog Inputs IIf a temperature sensor is defective or not connected, the VARC generates an alarm for that sensor. Input I/O # Board I/O Description Chilled Water Return Temperature Sensor AI-1 B1 The chilled water supply sensor is continuously monitored whether in Cooling, Reverse Cycle, or Electric Heat mode. It detects a high-temperature condition in the supply water from the chiller. If the chilled water temperature is greater than or equal to 125 °F (52 °C), the following occurs: • In Reverse Cycle mode, all enabled compressor relays are de-energized, turning off the compressors. • In Electric Heating mode, all enabled heater relays are de-energized, turning off the heating elements. • A high temperature fault is generated. • The compressor or electric heat relay re-energizes when the temperature drops to 110 °F (43 °C). You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled stage. See “Viewing Alarms for Each Stage” on page 28. Freeze Temperature Setpoint AI-2 B2 The chilled water supply sensor is continuously monitored whether in Cooling, Reverse Cycle, or Electric Heat mode. It detects a freeze condition in the supply water of the chiller. If the chilled water temperature is equal to or less than 36 °F (2 °C), the following occurs: • The compressor relay is de-energized, shutting off the compressor. • A low temperature fault is generated. • The compressor relay re-energizes when the temperature reaches 42 °F (6 °C). You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled stage. See “Viewing Alarms for Each Stage” on page 28. Condenser Freeze Protection AI-3 B3 The condenser outlet refrigerant temperature sensor monitors the condenser coil temperature. In Heat mode, if the coil temperature drops below 30 °F (-1 °C), the VARC automatically lowers the speed of the compressor to half the speed that it was currently running. While performing this operation, the display indicates Freeze Defrost. Suction Pressure 1 AI-6 B6 The VARC continuously monitors the suction pressure. If the suction pressure is below the alarm setpoint for longer than the programmed time delay, a Low Suction Pressure fault is generated. You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled stage See “Viewing Alarms for Each Stage” on page 28. Discharge Pressure 1 AI-7 B7 The VARC continuously monitors the discharge pressure. If the discharge pressure is above the alarm setpoint for longer than the programmed time, a High Discharge Pressure fault is generated. You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled stage. See “Viewing Alarms for Each Stage” on page 28. Pump Current Monitoring (Optional) 1 AI-9 (CW) AI-10 (SW) B-9 (CW) B-10 (SW) Pump current monitoring for the chilled water and Sea Water Pump (SWP) is an optional feature. It requires the medium-sized PLC, instead of the standard smaller version. With this option, you can view the current draw from each pump on the PGD1 display and the touch screen. 1 The VARC has a proprietary algorithm that keeps the system from turning off immediately for low pressure or high pressure. The VARC gradually reduces its speed to compensate for low or high pressure conditions.

VARC Chiller Controls

General Information 2 .2 .2 Digital Inputs Digital inputs are used to monitor the status of the VARC protection circuits. At powerup, all discrete inputs are checked before the system is enabled. Any faults detected on startup must be verified and cleared via the VARC before the system will start normal operation. For information on clearing alarms, see “Viewing Alarms for Each Stage” on page 28. Input I/O # Board I/O Description Refrigerant High Side Pressure Limit DI-1 DI-1 If the high pressure switch is tripped and turns off the compressor, the VARC acknowledges an open circuit and generates a High Discharge Pressure fault. The VARC will not allow the compressor relay to be re-energized until the high pressure switch is in the closed position. You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled stage. See “Viewing Alarms for Each Stage” on page 28. Econo Mode Selection DI-2 DI-2 This optional input is used to put the VARC into Econo mode. While Econo mode is enabled by this input, the VARC cannot be put into Normal or Boost mode. Chilled Water Flow Switch DI-3 DI-3 With the VARC in either Heat or Cool mode, the Flow switch must be closed prior to system starting or a stage being enabled. In operation, if flow is lost for more than 10 consecutive seconds, the following occurs: • The compressor or heat relay is disabled for the stage that has lost flow. • A Chilled Water Flow fault is generated. • The VARC goes into lockout. • A manual restart is required, after the system initiates, retries, and fails or exceeds timeout. You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled stage. See “Viewing Alarms for Each Stage” on page 28. Load Shedding Input DI-4 DI-4 The load shedding standard input is activated with a 230 V signal. When load shedding becomes active, the VARC shuts off the compressor and maintains that state until the load shedding input is disabled. In a multi-stage operation, load shedding shuts down the stage with the highest run hours. Every unit has a load shed input. The number of load shedding signals received (one per unit) determines how many units are shut off according to run hours. Electric Heat (E. H.) Flow Switch DI-5 DI-5 This optional switch is enabled through the factory settings. With the VARC in either Heat or Cool mode, the Flow switch must be closed prior to system starting or a stage being enabled. In operation, if flow is lost for more than 10 consecutive seconds, the following occurs: • The electric heat is disabled for the stage that has lost flow. • An Electric Heat Flow fault is generated. • The VARC goes into lockout. • A manual restart is required, after the system initiates, retries, and fails or exceeds timeout. You must acknowledge and clear the fault prior to re-enabling the VARC or the disabled stage. See “Viewing Alarms for Each Stage” on page 28. Cool Mode Selection Switch DI-6 DI-6 These switches allow for remote mode control. When using digital input mode selection, the display cannot be used to change mode, but all other functions on the display are available. Heat Mode Selection Switches DI-7 DI-7 2 .2 .3 Digital Relay Outputs IIf a temperature sensor is defective or not connected, the VARC generates an alarm for that sensor. Output I/O # Board I/O Description SWP DO-1 NO1 Provides switched power to the contactor coils for the Sea Water Pump. CWP DO-2 NO2 Provides switched power to the contactor coils for the Chilled Water Pump. Reversing Valve (RV) DO-3 NO3 Provides switched power to the coils for the Reversing Valve.

VARC Chiller Controls

Output I/O # Board I/O Description Electric Heat (EH) DO-4 NO4 Provides switched power to the contactor coils for electric heat. Not used. DO-5 NO5 This output is not used. Not used. DO-6 NO6 This output is not used. Fault Alarm DO-7 NO7/NC7 Provides a Normally Open (NO) contact point, which is closed for any fault condition. You can use this output to power a light, relay, or interface to a ship’s monitoring system. The output on this terminal is 230 VAC. 2 .2 .4 Analog Outputs The analog outputs are not used. Output I/O # Board I/O Description Not used AO-1 Y1 This output is not used. Not used AO-2 Y2 This output is not used. Not used AO-3 Y3 This output is not used. 2 .3 Default Parameters The following table lists factory defaults for the compressor, inverter, and econo mode setpoint parameters (for other VARC models, contact the factory). Model Compressor Inverter Part Number VARCX48 5KD184XAB21 PSD1* 12 Amp VARCX60 TNB306FPGMT PSD1* 12 Amp VARCX72 5JD420XAA22 PSD1* 16 Amp VARCX120 208–230V / 1PH SIAM ANB66FVCMT PSD2* 30 Amp 200V 208–230V / 3PH SIAM ANB66FVCMT PSD2* 40 Amp 200V 380–460V / 3PH SIAM ANB66FVQMT PSD1* 40 Amp 400V The following table lists factory defaults for all other parameters (for other VARC models, contact the factory). Parameter VARCX48 VARCX60 VARCX72 VARCX120 Data Type General Settings Cooling Setpoint CCW Return 48 48 48 48 Degrees F Cooling Setpoint CCW Supply 43 43 43 43 Degrees F Heating Setpoint 110 110 110 110 Degrees F Econo Mode 65% 65% 65% 65% Percent Superheat Setpoint Cool and Heat 10 10 10 10 Degrees F

VARC Chiller Controls

General Information Parameter VARCX48 VARCX60 VARCX72 VARCX120 Data Type Factory Settings Control Temp Mode CCW Supply CCW Supply CCW Supply CCW Supply Number of Stages 1 1 1 1 Electric Heat No No No No Power Cycle Retain Mode Retain Mode Retain Mode Retain Mode Logo Dometic BLK Dometic BLK Dometic BLK Dometic BLK Background Ocean Ocean Ocean Ocean Flow Switch Yes Yes Yes Yes High Pressure Switch Yes Yes Yes Yes Low Pressure Switch No No No No EH Flow Switch No No No No Load Shedding Yes Yes Yes Yes SW Temp Inlet Yes Yes Yes Yes Sea Water Pump Settings Control By Demand By Demand By Demand By Demand Off Delay 5 5 5 5 Seconds Pump Current No No No No Current Selection 10 10 10 10 Amps Pump Control Master Master Master Master Chilled Water Pump Settings Control Continuous Continuous Continuous Continuous Flow Prove Delay 10 10 10 10 Seconds Off Delay 5 5 5 5 Seconds Pump Current No No No No Current Selection 10 10 10 10 Amps Reversing Valve RV Delay On Time 45 45 45 45 Seconds Electric Heat Stage Up Delay 60 60 60 60 Seconds Stage Down Delay 20 20 20 20 Seconds Compressor Min On Time 60 60 60 60 Seconds Min Off Time 10 10 10 10 Seconds Min Time between Starts 60 60 60 60 Seconds Load Up Time 10 10 10 10 Seconds Force Rotation 12 12 12 12 Hours Load Up Stg Delay 60 60 60 60 Seconds Avg Supply Delay 240 240 240 240 Seconds

VARC Chiller Controls

Parameter VARCX48 VARCX60 VARCX72 VARCX120 Data Type Condenser Frost Protection Cond Setpoint 30 30 30 30 Degrees F Cond Band 2.5 2.5 2.5 2.5 Degrees F Comp Speed 60 40 40 40 RPS Compressor PID Cntrl P P P P K 50 50 50 50 Chilled Water High Temperature Limit Alarm Setpoint 125 125 125 125 Degrees F Off Band (SP-) 15 15 15 15 Degrees F Retries 6 6 6 6 Retry Timeout 30 30 30 30 Minutes Retry Delay 120 120 120 120 Seconds Chilled Water Freeze Limit Alarm Setpoint 36 36 36 36 Degrees F Off Band (SP+) 5.4 5.4 5.4 5.4 Degrees F Retries 6 6 6 6 Retry Timeout 10 10 10 10 Minutes Retry Delay 120 120 120 120 Seconds Chilled Water Flow Alarm Retries 6 6 6 6 Retry Timeout 10 10 10 10 Minutes Retry Delay 120 120 120 120 Seconds High Discharge Pressure Alarm Retries 6 6 6 6 Retry Timeout 30 30 30 30 Minutes Retry Delay 120 120 120 120 Seconds High Pressure Switch Alarm Retry 6 6 6 6 Retry Timeout 30 30 30 30 Minutes Retry Delay 120 120 120 120 Seconds Low Suction Alarm Low Suction Pressure 60 60 60 60 PSI Delay 180 180 180 180 Seconds Retries 6 6 6 6 Retry Timeout 30 30 30 30 Minutes Retry Delay 120 120 120 120 Seconds

VARC Chiller Controls

General Information Parameter VARCX48 VARCX60 VARCX72 VARCX120 Data Type Inverter Alarm Retry 15 15 15 15 Retry Timeout 60 60 60 60 Minutes Retry Delay 300 300 300 300 Seconds Configuration Menu Temperature Units Degrees F Degrees F Degrees F Degrees F Pressure Units PSI PSI PSI PSI

VARC Chiller Controls

3 Intended Use The VARC Chiller Control is a chiller control application that supports touch screen and LCD interfaces. This manual provides all necessary information for proper operation of the VARC Chiller Control application. NOTICE: Poor setup and misunderstood operating parameters could result in unsatisfactory performance and possibly failure. The manufacturer accepts no liability for damage in the following cases: • Faulty assembly or connection • Damage to the product resulting from mechanical influences and excess voltage • Alterations to the product without express permission from the manufacturer • Use for purposes other than those described in the operating manual Dometic Corporation reserves the right to modify appearances and specifications without notice. 4 Specifications The following table lists electrical specifications, environmental specifications, and touch screen dimensions, and setpoint ranges. Electrical Line Voltage See Data Label Frequency Phase Chilled Water Pump Output Sea Water Pump Output Maximum Circuit Breaker Size 1 Environmental Maximum Ambient Operating Temperature 140 °F (60 °C) Touch Screen Dimensions Height 5.79 in. (147 mm) Width 7.36 in. (187 mm) Depth 1.77 in. (45 mm) 1 Increase breaker size to include pump current if running pumps directly from the system. Setpoint Ranges1 Supply Control Return Control Cooling 42 °F (6 °C) to 55 °F (13 °C) 48 °F (9 °C) to 55 °F (13 °C) Heating 95 °F (35 °C) to 115 °F (46 °C) 95 °F (35 °C) to 120 °F (49 °C) 1 You cannot enter setpoint values outside of these ranges.

VARC Chiller Controls

General Information 5 Installation and Setup The VARC can be installed as a stand-alone chiller or as part of a staged system. The factory default setting is as a stand-alone chiller. Installation for a staged system requires the following steps: 1. Make the connections between each stage of the chilled water and sea water. 2. Make the network connections between each stage (physical and network addressing). 3. Check the firmware version. 4. Configure the remote control panel. Chillers supplied on a frame package are configured and wired as part of the build process. IAs part of a correctly configured multi-stage system there is no need to set differential/hysteresis settings. 5 .1 Initial Wiring � WARNING: ELECTRICAL SHOCK HAZARD . Exercise extreme care when working around energized equipment. Failure to obey this warning could result in death or serious injury. 1. Wire the sea water and chilled water pumps to VARC 1 (no need for pump relays) as follows: a. Remove the power cover. b. Connect the pumps to the terminals on the front of chiller 1, according to labeled connections. Note: Daisy chaining outputs is not recommended if the units have individual power sources. Verify the phase of power before daisy chaining the outputs. 2. Wire the network connections from the network connection ports (VARC 1 to VARC 2, VARC 2 to VARC 3, and so forth). Refer to the “Multi-stage Wiring” on page 14 for more information on wiring the stages. GND GND L2 L2 337430 337430 337430 337430 G L1 L2 GND R+/T+ R-/T- L2 L2 L1 L1 L1 L1 w q e r t y 4 Electrical Connections VARC 48 q Power Input r Network Connection and Touch Screen w SW Pump (10 A max.) t Load Shed Switch e CW Pump (10 A max.) y Elec. Heat Output

VARC Chiller Controls

5 Electrical Connections VARC 60/72 5 .2 Multi-stage Wiring The following diagram shows how to wire multiple VARC stages. 24VAC/DC L2 CW Return Manifold CW Supply Manifold Circ. Pump Sea Pump CW L1 VARC Stage 1 Chiller Stage 1 Chiller Stage 2 Chiller Stage 3 VARC Stage 2 VARC Stage 3 SW L1 Supply Supply Supply Return Return Return Flow Switch Flow Switch Flow Switch Freeze Stat Freeze Stat Freeze Stat GND Touch Screen (optional) Modbus Comm 3 Wire Pump Outputs from VARC Stage 1 Remote PLC Display (Optional) 3 Wire Communication Cables (one per stage) 6 Multi-Stage Wiring Diagram

VARC Chiller Controls

General Information � WARNING: ELECTRICAL SHOCK HAZARD . Verify that all units’ power lines are in unison phasing, in order to eliminate the potential for a short circuit. Failure to obey this warning could result in death or serious injury. 5 .3 Touch Screen Connection Make the following connections to the touch screen: a. A 24 VDC supply to power the display b. A three-core communication cable connected to serial port 1, not port 2 Terminate the three-core communication cable on Terminal Bus 3 (Modbus Com) on VARC 1. q w e r 7 Touch Screen Connections q Power Input (24 V) e Connection Port for Remote Connectivity w USB Port r Communication Connection from PICO (3 Conductor, 18 G wire) 5 .4 Firmware Verification Chillers should come from the factory with the correct firmware preloaded. However, it is worth checking that the firmware versions of all chiller stages match, as incompatible firmware can seem to work during initial setup but then cause networking problems later. To view the firmware version of a stage: 1. Press the Program button. See “LCD Buttons” on page 5. 2. Scroll up or down to Technician, and then press Enter. If prompted for a password, enter 3156. 3. Select Information. The Information screen is displayed.

VARC Chiller Controls

4. Scroll down to view version information. 5. Repeat for each stage. Verify that all stages have the same version number. In the unlikely event that there is a difference between stages, the PCB firmware must be updated by a Dometic-approved technician. 5 .5 Networking When setting up the stages for networking, ensure that the chillers are not connected via Modbus connections. Stage 1 requires minimal changes, so start with stage 2, leaving stage 1 until last. To set up networking, follow these steps: 1. Power off all stages except stage 2. 2. Press the Program button. See “LCD Buttons” on page 5. 3. Go to Technician. 4. Scroll down to Service settings, then press Enter. 5. For Service Password, enter 3156. 6. Go to Stage Address. 7. Press Enter, then change address to 2 for chiller 2, 3 for chiller 3, and so forth. 8. Press the Scroll Down button to display the next screen and change the number of stages. Press Enter until the cursor is on Num of Stages, then change from 1 to the correct number of stages for the current system. 9. Repeat steps 2-8 for additional stages. 10. For stage 1, only perform step 8 to change the total number of stages.

VARC Chiller Controls

General Information 5 .6 Configuring Display Addresses 1. Display the configuration screen: a. PGD1: Press and hold the Up, Enter, and Down buttons simultaneously for 6 seconds. b. PLDPRO: Press and hold the Up, Down, and Program Mode buttons simultaneously for 6 seconds. To locate buttons, see “LCD Buttons” on page 5. 2. Press Enter to access the Display address setting, and then scroll up or down to reach the address of the display per stage: a. Stage 1: 16 b. Stage 2: 17 c. Stage 3: 18 d. Stage 4: 19 e. Stage 5: 20 f. Stage 6: 21 The message “Display address has been changed” appears, and then the display goes blank. 3. Repeat the three-button push from step 1 to enter the configuration. 4. Press Enter three times or until you reach the next screen. 5. Press Enter to go to the next screen. 6. Follow these steps to select the address for Trm1 & 2 and select if it is private or shared: a. Press enter once to enter the address of Trm1, and then scroll up or down to select the appropriate address (for addresses, see step 2). b. Press Enter. – The cursor under Priv/Shared begins flashing. – Scroll up or down to select Pr, then press Enter. The cursor is next to Trm2. – Scroll up or down to select 32, then press Enter. – Scroll up or down to select Sh, then press Enter. – Press Enter two more times. The cursor is next to Ok?No. – Scroll to select Yes, then press Enter. 7. Connect all stages together with the network cable. The data for all of the stages appears on the main screen. 8. If using a single common display or remote display, it must be configured as address 32.

VARC Chiller Controls

5 .7 VARC Standard Wiring Diagram The following diagrams show the component connections for the standard VARC 48 and VARC 72. The VARC 60 is not shown. W L1 L2L3G U A1 G J14 J15 FT-1 FT-2 G0 +VDC B1 B2 B3 B4 B5 B6 B7 GND GND R+/T+ R-/T- TB3 TB1 TB2 TB4 4128003 337667 338027 338027 HPS1 FS1 GND R-/T- R+/T+ Vout N03 N01 N02 C1 N06 N04 N05 NC7 N07 C3 C2 GND Y1 Y2 Y3 +VDC D11 D12 D13 D14 D15 D16 D17 DIC 1 GND +5VR A2 A1 A2 12 22 14 24 11 21 12 22 14 24 11 21 1 2 3 4 5 6 7 8 910 V W G V(R) W(C) U(S) V U Field Wiring To Remote Display Input Power 230VAC (optional) E.H. Flow (optional) Econo Mode (optional) Mode Selector Switch (optional) Display Chilled Water Return L2 230VAC (SW Pump) MOD Toroid 340098 Toroid 338082 Toroid 338084 GND Econo ORG SW CW RV1 SW CW Econo Mode Cool Mode Heat Mode Load Shedding Cool Chilled Water Supply L1 230VAC (Output) BUS L1 (Load Shed) 230VAC L1 (Elec. Heat Contactor) 230VAC L1 Off Off Heat Condenser Temp. L1 230VAC (CW Pump) COMM L2 (Input) 230VAC L2 (Output) 230VAC L2 Suction Temp. L2 230VAC (Output) GND GND Suction Pressure Discharge Temp. Discharge Pressure Power Speed Drive Display Splitter Jumper Details Bolt Comp (Top View) Expansion Valve Add Wire Label Display Splitter (Under Top Cover) Optional Wiring 8 Wiring Diagram VARC 48 W V U C NO NC 1 3 5 2 4 6 8 7 J 14 J 15 SHL D +VR L R X/TX- R X/TX+ GND +VR L GND A B C J 14 J 15 DISP L AY SP L ITTER J UMP E R DE TAIL S TO R E MOTE DISP L AY 9 Wiring Diagram VARC 72

VARC Chiller Controls

Operation 6 Operation The VARC provides many operational features to conserve energy, improve performance, and provide system control. 6 .1 Operational Modes The main operational modes determine whether the VARC generates heat or cooling: Cool mode, Heat mode, and Electric Heat mode. Pump operation is coordinated with these modes. The VARC also has Econo mode and a Maintenance mode for troubleshooting. The operational modes can also be selected using the digital inputs if wired to the control board. These inputs allow you to select Econo mode if enabled for either cool or heat mode. Cool and Reverse cycle Heat mode can be selected by using the digital input controls. This allows the system to be switched between modes by using a common switch or controlled through some other automated system. These inputs do not support Electric heat operation. 6 .1 .1 Cooling and Heating The VARC supports a Cool mode and two heating modes: Heat (reverse cycle heating) and Electric Heat. Cool When Cool is selected on the touch screen or the LCD buttons, the VARC starts cooling according to the temperature setpoint. The pumps operate as described in “Pump Operation” on page 20. Cool mode activity is as follows: • If the return water/supply water temperature is above the cooling setpoint and the staging delay has elapsed, the board energizes the compressor relay. • The compressor continues to run until the cooling setpoint has been reached or an alarm condition exists. • A stage has a minimum run time of 60 seconds before it can be turned off and a minimum off time of 10 seconds before it can be re-enabled. This minimum on time is required to ensure that the system is not cycling on and off and thereby not allowing the compressor to properly warm-up. This ensures proper oil lubrication of the system. • If the system calls for a stage to be toggled on or off, the next available stage that meets the staging criteria is used. • Load shedding occurs in multi-stage operation when approaching the chilled water setpoint. Compressor rotation is active during run mode: • The compressor with the lowest running hours is enabled first, and the compressor with the highest running hours is disabled first. • After chilled water and sea water flows are stable for 10 seconds (default), the first stage is enabled, and the compressor starts. • The first stage continues to run up to 100 percent speed before enabling the next stage. • If the PID loop requires demand, then the next stage is enabled with a startup delay of three minutes before running up to required speed. Heat (Reverse Cycle Heating) When Heat is selected on the touch screen or the LCD buttons, the VARC starts heating according to the temperature setpoint. The pumps operate as described in “Pump Operation” on page 20. Heat mode activity is as follows: • There is a 45-second delay after the compressor ramps up before it is energized. • The reversing valve relay is energized to operate the VARC in Reverse Cycle Heat mode. • If the return/supply water temperature is below the programmed heating setpoint and the staging delay has elapsed, the VARC energizes the compressor relay. • The compressor continues to run and the reversing valve remains energized until the heating setpoint has been reached or an alarm condition exists.

VARC Chiller Controls

• If setpoint is reached, the compressor reduces its speed to maintain the water temperature. Once it has reached temperature and a hysteresis of one degree, the compressor turns off and the reversing valve turns off immediately. • A stage has a minimum run time of 60 seconds before it can be turned off and a minimum off time of 10 seconds before it can be re-enabled. If the system calls for a stage to be toggled on or off, the next available stage that meets the staging criteria is used. Compressor rotation is active during run mode: • The compressor with the lowest running hours is enabled first and compressor with the highest running hours is disabled first. • Enable Reverse Cycle Heat only for the system. • After chilled water and sea water flows are stable for 10 seconds (default), the first stage is enabled and the compressor starts. • The first stage continues to run up to 100 percent speed before enabling the next stage. • If the PID loop requires demand, the next stage is enabled with a startup delay of three minutes before running up to the required speed. Electric Heat (Optional Heater Barrel) When Electric Heat is selected on the touch screen or LCD buttons, the VARC starts heating according to the temperature setpoint. The VARC energizes the heater relay if return/supply water temperature is below the programmed setpoint and the staging delay has elapsed in a multi-stage configuration. Heater rotation is active during run mode: • The heater with the lowest running hours is enabled first and the heater with the highest running hours is disabled first. • Enable Electric Heat only for the system. • After chilled water flow is stable for 10 seconds, the first stage is enabled and the electric heater starts. • The first stage continues to run for five minutes before enabling the next stage. • If the PID loop requires demand, the next stage is enabled. 6 .1 .2 Pump Operation The pump modes adjust as required by the system operating mode. Chilled Water Pump The chilled water pump relay closes if the system is in Heat or Cool mode. The pump is enabled five seconds prior to the first stage being enabled. The pump is on for continuous operation when system is enabled. Sea Water Pump The sea water pump has selectable operating modes between continuous operation or cycle-with-compressor operation. The default configuration is to cycle with the demand. The sea water pump relay closes five seconds before the compressor starts in Heat or Cool modes. It opens five seconds after the last compressor cycle is completed. If immersion heating is available and used, the sea water pump is disabled. 6 .1 .3 Current Power Limiting The Econo Mode provides control over the capacity of the system. When the user enables econo mode, the system is limited by the speed of the compressor. The default value for econo mode is 65%. Under setpoints, the user can adjust the Econo Mode value between 35% and 90%.

VARC Chiller Controls

Operation 6 .1 .4 Maintenance Maintenance mode is available for troubleshooting. See “Maintenance Mode” on page 39. 6 .2 Powerup and Startup The VARC Chiller Controller can be operated as a single- stage or a multi-stage chiller plant. During initial setup, you configure the system for the number of stages and the available options. The VARC System is set for supply water control, but it can be modified for return water control, if needed. 6 .2 .1 Normal Stage Startup The system has a time delay between the staging up of the various stages: 1. Stage 1 is initiated and starts its operation. 2. When the PID determines that more capacity is required, stage 2 is initiated. 3. When the system has maintained the chilled water loop and the PID has determined that no additional stage is required or has met capacity demand, it reduces the speed of the compressors. 4. The compressors then operate at minimal speed to maintain the chilled water loop. If the speed of the compressor still exceeds the demand, the stage with the most run hours is turned off. 6 .2 .2 Operational Checks When the VARC is enabled, the system performs pre- startup checks on all chilled water flow switches and HP switches. Individual stage faults disable only that stage. 6 .2 .3 Compressor Startup The VARC utilizes a BLDC compressor that is capable of operating at a very high frequency which requires that the compressor have a ramped startup to establish proper lubrication so as to not damage the compressor. This startup has a ramp time and a minimal speed operation that will last for 100 seconds to allow the compressor to properly warm up before operating at maximum speed. The compressor minimum on time is 60 seconds and minimum off time is 10 seconds with a minimum time between starts of 60 seconds. These default parameters allow the compressor to operate in a safe mode that will not damage the compressor. 6 .3 Operating the Touch Screen ISome screens contain pop-up screens with information. To exit a pop-up, simply touch the X to close the screen. 6 .3 .1 Basic VARC Operations From the Chiller Enable screen, you can perform the basic VARC operations: • Change setpoints • Select Cool, Heat, or Electric Heat • Monitor water temperature and pump status • Turn the VARC off To display the Chiller Enable screen, from the Main screen, tap Chiller Enable. See “Touch Screen” on page 5.

VARC Chiller Controls

Figure 10 shows the controls on the Chiller Enable screen. q w t y u i e r 10 Chiller Enable Screen q Home y Setpoints w Power Button u Chilled Water Pump e Cool Button i Sea Water Pump r Heat Button o Econo Mode Button t Electric Heat Button • Home: Displays the Main screen. • Power Button: Turns the VARC off. When the VARC is in a run state, this button is green. • Cool Button: Lights up with the word COOL when the VARC is cooling. Tapping this button puts the VARC into cool mode. • Heat Button: Lights up with the word HEAT when the VARC is heating. Tapping this button puts the VARC into heat mode. • Electric Heat Button: Lights up with the words ELECTRIC HEAT when electric heat is enabled. Tapping this button puts the VARC into Electric Heat mode. This button is visible only if the electric heat option is installed. • Setpoints: Displays the current setpoints for cooling and heating. Tapping the numbers changes the setpoints. • Chilled Water Pump and Sea Water Pump: Tapping this area takes you to the Pump Status screen. • Econo Mode Button: Tapping this button displays the Econo Mode screen, which allows you to select Normal or Econo Mode. 6 .3 .2 Selecting Econo Mode 1. From the Main screen, tap Chiller Enable. See “Touch Screen” on page 5. 2. In the top-left corner of the Chiller Enable screen, click the Econo Mode button. The Econo Mode screen appears. 11 Econo Mode Screen 3. Select the desired mode from the Compressor Current Mode menu. 4. Select the Eco Mode Setpoint value to change the value of the econo mode. 5. To return to the Chiller Enable screen, in the top-left corner, tap the left-arrow button.

VARC Chiller Controls

Operation 6 .3 .3 Viewing Chiller Status for Each Stage The Chiller Summary screen provides chiller status for all stages. It also indicates if a stage is in Alarm Retry mode. 1. To display the Chiller Summary screen, from the Main screen, tap Chiller Summary. See “Touch Screen” on page 5. 2. To display a stage, tap its VARC number. 12 Chiller Summary 6 .3 .4 Monitoring Refrigerant and Chilled Water Circuits The Chiller Stage screen provides a graphic representation of the refrigerant and chilled water circuits. To display the Chiller Stage screen, from the Main screen, tap Chiller Stage. See “Touch Screen” on page 5. 13 Chiller Stage Screen IDepending on installed options, different icons appear as hotspots for navigation to open another window. When the system is in run mode, additional icons appear to indicate cooling and heating. Using the Electronic Expansion Valve (EEV), you can monitor the following parameters: a. Valve position b. Suction pressure and temperature c. Superheat setpoint and actual value To view EEV parameters, on the Chiller Stage Screen, tap the Expansion Valve icon. 14 Expansion Valve Screen 6 .3 .5 Viewing and Downloading Performance Data The Trends screen provides graphical representation of the VARC performance data. 1. To display the Trends screen, from the Main screen, tap Trends. See “Touch Screen” on page 5. 2. To change the time frame, select a time from the menu. The default is one month.

VARC Chiller Controls

15 Chiller Trends Screen 3. To download performance data, insert a USB drive into the USB port on the VARC, and then tap the USB button. IIf you do not put the USB drive in first, you get the message shown in Figure “16 USB Message” on page 24. 16 USB Message 6 .3 .6 Viewing Active Alarms and Downloading Alarm History The Alarms screen shows all active alarms and allows you to view the alarm history. 1. To display the Alarm screen, from the Main screen, tap Alarms. See “Touch Screen” on page 5. 2. To reset alarms, press the RESET ALARMS button. 3. To display the alarm history, tap the History button. 17 Active Alarm Screen 4. To change the time frame, select a time from the menu. 18 Alarm History Screen 5. To download alarm history, insert a USB drive into the USB port on the VARC, then tap the USB button. 19 Download Alarm History

VARC Chiller Controls

Operation 6 .3 .7 Enabling Remote Control for Third- Party Support The Remote Support screen allows you to set up the VARC for control by third-party technical support. 1. To display the Remote Support screen, from the Main screen, tap Remote Support. See “Touch Screen” on page 5. 2. To enable or disable remote support, tap the Enable Remote Support button. (Default is enabled.) 20 Enable Remote Support Screen 3. In the MobileVNC Settings dialog box, on the Control tab, press Start to begin remote login and press Stop to finish. 21 MobileVNC Settings Dialog Box 4. Use the settings on the Advanced tab to select configuration options for the remote login. 22 MobileVNC Settings Advanced Tab 6 .4 Operating the LCD Screen IThe following LCD instructions refer to the PGD1 display. For the PLDPRO display, use the corresponding buttons. See “PLDPRO LCD Display” on page 4. 6 .4 .1 Understanding the Display Screens The Main screen allows you to monitor single-stage operation and additional stages in multi-stage operation. The Main screen displays the following parameters: a. Mode of operation (Econo or Normal) b. Chilled water return temperature c. Chilled water supply temperature d. Condenser outlet temperature IThe condenser outlet temperature is the freeze control indicator for the condensers in heat mode. Pressing the Scroll Down button moves through the various parameters displayed on the LCD screen. In a multi-stage configuration, you can scroll through the parameters of the additional stages.

VARC Chiller Controls

The screens following the main screen contain information for each stage. 1. The first screen displays the CW Supply and CW Return temperatures, flow switch status (Fl) and high pressure status. 2. The next screen displays compressor speed and information to indicate if the system is in a safety count down. Once this time has elapsed and other time delays have been met, the VARC starts up. 3. The next screen displays the suction pressure, the discharge pressure, the superheat value, and the sub- cooling value being calculated by the system. 4. The following screens display the drive status. To access these screens, press Enter: 5. The final screen displays an image of the refrigerant circuit and showing the valve position. 6 .4 .2 Adjusting Setpoints 1. Press the Program button. See “LCD Buttons” on page 5. 2. Go to Setpoints, then enter the user password (1234). 3. Press Enter once to update the Heating setpoint, by pressing the Scroll Up or Scroll Down buttons to change the value. Press Enter again to change the cooling setpoint.

VARC Chiller Controls

Operation 6 .4 .3 Enabling Electric Heat 1. Press the Program button. See “LCD Buttons” on page 5. 2. Scroll down to Technician, then press enter. 3. Scroll down to Service settings, then press Enter. 4. Enter the service password 3156. 5. Scroll down to System Setup, then press enter. 6. Scroll down to Electric Heat, press Enter to select, and then press the Scroll Up or Scroll Down buttons to toggle the setting. 7. Press Enter to save. 6 .4 .4 Setting Time and Date 1. Press the Program button. See “LCD Buttons” on page 5. 2. Scroll to Clock/Scheduler, then press Enter. 3. Press Enter. The cursor flashes on the date field: mm/dd/yyyy. 4. Use the Scroll Up and Scroll Down buttons to select the correct month. Press Enter, then press the Scroll Up and Scroll Down buttons to select the correct day. 5. Press Enter, then use the Scroll Up and Scroll Down buttons to select the year. 6. Press Enter. a. The cursor drops down to the Hour field.

VARC Chiller Controls

7. Use the Scroll Up and Scroll Down buttons to select the correct hour, then select the minute. a. The cursor goes back to the Clock title. Settings have been saved and you can exit to Main screen. b. Daylight Savings Time is enabled by default. If you wish to disable, scroll down from the Clock screen. 6 .4 .5 Changing Temperature Display Units 1. Press the Program button. See “LCD Buttons” on page 5. 2. Go to Setpoints, then enter the password (3156). 3. Scroll down to the Temperature Units screen. Press Enter to select. Use the Scroll Up and Scroll Down buttons to toggle between options. 4. After selecting the desired option, press Enter to return the cursor to the top of the screen. 5. Make this change to all stages so that it correctly reflects temperature readings on the remote display. 6 .4 .6 Viewing Alarms for Each Stage The Main screen indicates alarms by flashing the word Alarm in the lower-right corner. IThe PLDPRO display sounds a tone as well as displaying the word Alarm in the lower-right corner. The Alarm screen captures a snapshot of the system parameters at the time of the fault. The alarm history captures and displays the following parameters: a. Compressor speed b. Chilled water return c. Chilled water supply d. Discharge pressure e. Suction pressure 1. To view the alarm information for more than one stage, you need to switch boards via the display or look at the PLDPRO display for that stage. 2. Use the alarm logger to view the alarm history. 3. To clear an alarm when a fault has been corrected, press and hold the Alarm button for five seconds to clear the active alarm.

VARC Chiller Controls

Operation 6 .4 .7 LCD Screen Menu Maps The following diagrams show the menu options for each screen available through the LCD displays. The Main screen is displayed at powerup. It displays the essential system information. IAn asterisk (*) indicates an option that is available only when activated in the factory settings. Main Status Screen CW Supply Temp ##.#°F Mode Off/Cool/Heat/ El Ht* CW Return temp ##.#°F CW Supply temp ##.#°F Cond. Outlet temp ##.#°F Mode Off/Cool/Heat/El Ht* Pumps CW On/Off SW On/Off Chiller Status Normal/Econo Maint Mode Active Stage # Auto/Disabled Varc #1 CW supply temp ##.#°F CW return temp ##.#°F Flow status Ok/Alm/Off High pressure status Ok/Alm/Off Electric Heat* Ok/Alm/Off Ok/Alm/Off EH FL* Compressor speed #.# Hz Compressor speed #.# rps Compressor Current #.# A Suction Temperature ##.#°F Pressure ##.# psi Saturation Temp. ##.#°F Discharge Temperature ##.#°F Pressure ##.# psi Saturation Temp. ##.#°F Super heat temp ##.#°F Subcooling temp ##.#°F VARC #* (if multistage) Varc #1 information Varc # 1 Information Compressor Capacity Regulator Required Capacity % Actual Capacity % Actual Speed rps Drive Status Motor Current #.# A Motor Voltage # Vrms DC Bus Voltage ### V Drive Temperature ## °F Drive Status Stopped/Running Fault Flow Diagram Super Heat ## °F Compressor ## °F EEV Open % ## % EEV Open Stps ### stp EEV ### psi Std-by temp ## °F 23 Main Screen

VARC Chiller Controls

The Program menu provides access to user settings, the Factory screen, and the Technician screen. Program Setpoints Clock/Scheduler Input/Output Alarm History Board Switch Technician Factory Analog Output Output ##.# Vdc Setpoints Heating Temperature ##.# °F Cooling Temperature ##.# °F Electric Heat* SP ##°F Stg Up Stg Down 1 SP - #°F 1 SP + #°F Current Limiting Mode Normal/Boost/Econo Econo #.# Amps Normal #.# Amps SW Pump Control By Demand/By Unit On Temperature Units °F/°C Pressure Units psi/bar Clock/Scheduler Date ##/##/## Hour ##:## Day ### DST Enable/Disable DST Enable Transition ### Start ### End ### Input/Output Analog Input Digital Input Relay Output Analog Outputs Analog Input CW Return Input B001 ### CW Supply Input B002 ### SW Inlet Input B003 ### Digital Input Flow switch DI 3 Open/Close Electric Heat Fl DI 5 Open/Close High pressure switch DI 1 Open/Close Load Shedding Switch DI 4 Open/Close Cool Mode Switch DI 6 Open/Close Heat Mode Switch DI 7 Open/Close Relay Output SW Pump Relay 1 On/Off CW Pump Relay 2 On/Off REV Valve Relay 3 On/Off Electric Heat Rly 4 On/Off Alarm Relay 7 On/Off Board Switch Unit address: ## Switch to unit: ## Technician See Figure 25 Factory See Figure 27 Alarm History Alarm# Message Compressor Speed ### CW Return ### CW Supply ### Discharge Pressure ### Suction Pressure ### 24 Program

VARC Chiller Controls

Operation The Technician menu requires the technician password (3156). BMS Configuration BMS Port No. # Pr otocol ###### (scroll) Address # Baud Rate ##### Technician Information Commission Working Hours BMS Configuration Service Settings Manual Management Pump Control Information Service Contact Phone ###-###-#### Version & Date #.## ##/##/## BIOS & Date #.## ##/##/## Boot & Date #.## ##/##/## Flash Ram ### Kb T memory ### ## Cycle/s #### ms Power Cycle Status Last Off Time ##/##/## ##:##:## Last On Time ##/##/## ##:##:## Length Time off Days: # Hrs: ## Min: ## EVO no. FW Version #.# Service Version #.# Power+ no.1 Boot release ### FW release ### FW checksum ### MC release ### Hardware ID ### Commission Enter contact info Name #### Telephone No. ###-###-#### Update info? Yes/No Commission date ##:## ##/##/## Commission system? Yes/No Working Hours Run Hrs Compressor ### h Electric Heat* ### h Chilled Water Pump ### h Seawater Pump ### h Service Settings See Figure 26 Manual Management Analog Input Digital Input Relay Output Compressor & EEV Analog Input Man Ctrl Man. Pos. Value CW Return B001 On/Off ##.# ##.# CW Supply B002 On/Off ##.# ##.# SW Inlet B003 On/Off ##.# ##.# Digital Input Man C trl Man. Pos. Value Flow DI 3 On/Off Open/Close Open/Close El. Heat Fl DI 5 On/Off Open/Close Open/Close High Press DI 1 On/Off Open/Close Open/Close Load shed DI 4 On/Off Open/Close Open/Close Relay Output Man. C trl Man. Pos. Value SW Pump Relay 1 On/Off On/Off CW Pump Relay 2 On/Off On/Off Rev valve Relay 3 On/Off On/Off Electric Heat Relay 4 On/Off On/Off Alarm Relay 7 On/Off On/Off On/Off On/Off On/Off On/Off On/Off Compressor & EEV Enable manual valve position Yes/No Manual Valve position # steps Compressor Mode Auto/Man. Manual Speed ###.# rps Required cap. ##.# % Actual cap. ##.# % Actual Speed ###.# rps Pump Control Ctrl Pos. Status CW On/Off On/Off On/Off 25 Program/Technician

VARC Chiller Controls

Stage Address pLAN Board Addressing Current Address # Change Address to # Unit Settings No. of Stages # Service Settings Working Hour Set Probe Adjustments Control Loops Reset System Stage Address Stage Disable System Setup Probe Adjustments Input Offset Value CW Return B001 ##.# ##.# CW supply B002 ##.# ##.# SW Inlet B003 ##.# ##.# Probe adjust S1 offset ##.# barg S1 probe ##.# barg S2 offset ##.# °C S2 probe ##.# °C S3 offset ##.# barg S3 probe ##.# barg S4 offset ##.# °C S4 probe ##.# °C Working Hour Set Set Pt Rst to 0? Run H rs Compressor #### h Yes/No #### h Electric Heat* #### h Yes/No #### h Chilled Water Pump #### h Yes/No #### h Seawater Pump #### h Yes/No #### h Control Loops Superheat Setpoint Cool Setpoint ##°F Heat Setpoint ##°F Thermoregulator Setpoint SH ##°F LowSH threshold ##°F LOP threshold temp ##°F MOP threshold ##°F Modulatin g Setup Compressor Input #.# Output #.# Setpoint #.# K # # .# Integration Time Stage Disable Stage Control Yes/No Stage # Auto/Disabled System Setup Water Loop Control Supply/Return Electric Heat Yes/No EH Flow Switch* Yes/No Varc Type None/Varc48/60/72 Compressor (Scroll if custom) Power type 230 V / 16 A Power set 230 V / 30 A Set Defaults Yes/No Reset System Clear Alarm History Yes/No Default Installation Yes/No 26 Program/Technician/Service Settings

VARC Chiller Controls

Operation The Factory menu requires the factory password, which is available only to authorized Dometic personnel. Initialization Erase user settings and install global default value Yes/No Clear all saved data Factory + User Yes/No Insert New Passwords User #### Technician (PW1) #### Factory (PW2) #### I/O Configuration See Figure 32 Factory Configuration I/O Configuration Factory Settings Initialization Factory Settings See Figure 28 Configuration Temperature Units °F/°C Pressure Units psi/bar Force clock enable Yes/No Clock mode 24h/12h Disable Buzzer Yes/No Startup delay ### s Enable Unit by Digital Input On/Off Supervisor On/Off pLAN network On/Off Schedule On/Off Unit Control Custom 1 On/Off Custom 2 On/Off Custom 3 On/Off Custom 4 On/Off Analog Input Filtering Enable Yes/No Input 1 ## s Input 2 ## s Input 3 ## s Manual Control Reset Enable Yes/No Time # m PW/Return Delay ### s Scheduler Holidays No. ## Modbus Settings 1st Master Baudrat e ##### Stop bit 1/2 Parity Mode None/Even/Odd Evo Configurator Power+ n 1 Power + n1 See Figure 30 EVO Configuration See Figure 29 27 Program/Factory

VARC Chiller Controls

In the following diagram, the dotted boxes indicate a breakout of the additional information that is contained below that menu category. Alarm Setup Temperature Limits Set Pt. Off Band Retries Set Dis able Status CW High ##.#°C ##.#°F #/## m ## s #/## m CW f reeze ##.#°C ##.#°F #/## m ## s #/## m Delay Retries Set Disable Status CW Flow ## s #/## m ## s #/## m El Heat Fl ## s #/## m ## s #/## m High Disch Pressure ## s #/## m ## s #/## m High Press ## s #/## m ## s #/## m Low Suct Pressure ## s #/## m ## s #/## m Low Suction Pressure Cool Set Point ##.# bar Heat Set Point ##.# bar Inverter Retrys #/## m Set Disable ## s Status #/## m CW Pump Shutdown Cool Setpoint ##.# °F Heat Setpoint ##.# °F CW Alarm Delay ## s Factory Settings Varc Type None/Varc48/ 60/72/96 Compressor Scroll to select Refrigerant R410A Power type Based on Inverter Power set Based on Inverter Set Defaults Yes/No Control Temp CCW supply/ CCW return No. of stages # Electric Heat (EH) Yes/No Power Cycle Retain Mode/Off Logo Select appropriate Background Select appropriate Flow Switch Yes/No High Pressure Switch Yes/No Low Pressure Switch Yes/No EH Flow Switch* Yes/No Load Shedding Yes/No SW Temp Inlet Yes/No SW Pump settings Control By demand/ By unit on Off Delay ## s Pump Current Yes/No Current Select 10/30/50/75 A CW Pump settings Flow Prove Delay ## s Off Delay ## s Pump Current Yes/No Current Select 10/30/50/75 A Reversing valve RV delay time ## s RV toggle time ## s RV delay ON time ## s Electric Heat Stg Up delay ## s Stg Down delay ## s Compressor Alarm Setup Compressor Econo mode SW Yes/No Minimum On ## s Minimum Off ## s Min Time between Starts ## s Load Up Time ## s Frost Protection Condenser Setpoint ##.#°F Condenser Band ##.#°F Compressor Speed ##.# rps Envelope Zone (Envelope Status) Control Direct/Reverse/Both P/PID/P+I K ##.# Minimum #### Maximum #### DBd ##.# Out ## 28 Program/Factory/Factory Settings

VARC Chiller Controls

Operation Configuration Valve Select Type Main Regulation Select Type Auxiliary Regulation Select Type Probe Configuration Probe S1 Probe S2 Probe S3 Probe S4 Alarm Enable/Disable Enable/Disable Enable/Disable Enable/Disable Type Select Select Select Select Minimum #.# barg #.# barg Maximum #.# barg #.# barg Alarm Min. #.# barg ## °C #.# barg ## °C Alarm Max. #.# barg ## °C #.# barg ## °C Alarm Mngt Use backup S3/valve at fixed pos/valve forced closed/no action valve at fixed pos/valve forced closed/no action Use backup S3/valve at fixed pos/valve forced closed/no action valve at fixed pos/valve forced closed/no action Regulation Valve opening at start-up ## % Valve opened in standby ## % Prepositioning delay ### s Alarm delay Low SH ### s LOP ### s MOP ### s Alarm low suction temp Threshold ## °C Timeout ### s Custom Minimum steps ### Maximum steps ### Closing steps ### Nom. Step rate ## Hz Fast step rate ## Hz Holding current ## mA Duty cycle ## % Opening synchronicity Yes/No Closing synchronicity Yes/No EVO Configuration Configuration Regulation Custom 29 Program/Factory/Configuration/EVO Configuration

VARC Chiller Controls

Regulation See Figure 31 Custom Motor Poles # Motor Control Mode PM Motor/AC Motor Vector/AC Motor Motor base freq. ###.# Hz Motor base vol. ### Vrms Motor rated current ##.# Arms Motor power factor ## Out current maximum #.#% Speed profile Frequency # (1-3) ###.# Hz Acc. # (1-4) ###.# Hz/s Delay # (1-3) ### s Delay execution Always/Single Force freq. 2 Enabled/Disabled Deceleration ramp ###.# Hz/s V/F Boost voltage #.#% V/F Freq. adjustment #.#% V/F Volt. Adjustment #.#% Motor Mag. Current #.# A Stator Resistance # mOhm Rotor Resistance # mOhm Stator/Ld inductance #.# mH Leakage factor # Lq Inductance #.# mH Speed Loop Kp ##.# % Speed Loop Ki ### ms Magnetizing Time ### ms Starting Current #.# % #.# A Freq. for Start Cur #.# % Crankcase heater Auto/Force Off/Force On Crankcase current #.# % #.# A STO alarm mngt Manual Res/Disable/Auto Reset Phase loss detection Enable Overload at Power-on Reset/Restored Enable Manual R/W Yes/No Address # Read Value # Write Value # Yes/No Power + n1 Configuration Regulation Custom Configuration Motor Type Select Set Defaults Yes/No Save to Custom Yes/No Data Comm. Timeout ## s U.M. speed Hz/rps Drive Replacement Do Nothing/Download Parameters 30 Program/Factory/Configuration/Power + n1

VARC Chiller Controls

Operation In the following diagram, the dotted boxes indicate a breakout of the additional information that is contained below that menu category. IAn asterisk (*) indicates an option that is available only when activated in the factory settings. Regulation Output frequency min #.# Hz Output frequency max #.# Hz Skip frequency set #(1-3) #.# Hz Skip frequency band #(1-3) #.# Hz Switching frequency # kHz Switching frequency derating Disabled/Enabled Speed derating mode ## Stop mode Ramp/Coast Reverse Speed Disabled/Enabled Flying Start Disabled/Enabled Relay Configuration Select PTC Alarm Disabled/Enabled PTC Alarm delay ## s Compressor Regulator Start -up pressure differential control Max pressure diff. admitted #.# bar Equalization mode Equalztn valve/EEV Pre-Opening Start -up failure control Pressure diff. min. variation #.# bar Control period ## s Restart delay ## s Max Retry # # Speed Management Start -up forced speed ##.# rps Max speed ##.# rps Min speed ##.# rps Deceleration rate #.# rps/s Acceleration rate #.# rps/s Switch -off rate #.# rps/s Envelope Control Speed reduction rate #.# rps/s Min speed admitted #.# rps Out of env. Alarm timeout ## s Low press. diff. alarm timeout ## s Discharge Gas Control High Discharge Temp. Limit ##.# °C Alarm ##.# °C Speed Control due to Discharge Gas Action Distance ##.# °C Action Pause ## s Comp. Speed Reduction #.# % EEV Regulation Mode Select from EEV Mode List Discharge Temp Probe Comp Time ##.# s Discharge Super Heat Temperature Setpoint ##.# °C ##.# °C Offset ##.# °C ##.# °C Hystere sis ##.# °C ##.# °C Envelope Control - Low ratio management By EEV closing Yes/No By compressor speed Yes/No EEV Pre-Opening* Max. Equalization ## s EEV opening ##.# % EEV Mode List Suction Superheat Discharge Temperature Discharge Superheat 31 Program/Factory/Configuration/Power + n1 /Regulation

VARC Chiller Controls

Analog Inputs Enable CW Return CW Supply SW Inlet On/Off On/Off On/Off Channel B001 B002 B003 Normal/High Res. Normal/High Res. Normal/High Res. Input Type Select/(On/Off) Select/(On/Off) Select/(On/Off) On/Off Direction Reverse/Direct Reverse/Direct Reverse/Direct Delay Time ## s ## s ## s Value Open/Closed Open/Closed Open/Closed Select type Minimum ##.# ##.# ##.# Maximum ##.# ##.# ##.# Offset ##.# ##.# ##.# Value ##.# ##.# ##.# Out of Range Alarm Power Delay # s # s # s Run Delay # s # s # s Units Temp/Press/Other Temp/Press/Other Temp/Press/Other Digital Inputs Switches Enable Channel Action Delay Status Flow On/Off # Open/Close ### s Open/Close EH Flow* On/Off # Open/Close ### s Open/Close High Press On/Off # Open/Close ### s Open/Close Low Press On/Off # Open/Close ### s Open/Close LoadShed On/Off # Open/Close ### s Open/Close Econo Mode On/Off # Open/Close ### s Open/Close Relay Output Enable Channel Status SW Pump Yes/No # On/Off CW Pump Yes/No # On/Off Rev Valve Yes/No # On/Off El Heat* Yes/No # On/Off Alarm Yes/No # On/Off Analog Output Channel # 0-6 Enable Yes/No Action Direct/Reverse Minimum ##.# Vdc Maximum ##.# Vdc I/O Configuration Analog Inputs Digital Inputs Relay Outputs Analog Outputs 32 Program/Factory/IO Configurations Display Address Display address setting # I/O Board address # Terminal config Terminal configuration P: 01 Adr Priv/Shared Trm1 16/17/18/… Trm2 32 Trm3 None 33 Display Address

VARC Chiller Controls

Maintenance Mode 7 Maintenance Mode In Maintenance mode you can disable any of the stages in the system. This allows for ease of troubleshooting and maintenance on one unit, while maintaining full functionality for the other stages. � WARNING: ELECTRICAL SHOCK HAZARD . Maintenance and repair should be performed only by qualified technicians. Failure to obey this warning could result in death or serious injury. 7 .1 Accessing Maintenance Mode from the LCD Screen 1. In the Main screen, press Enter and scroll up or down to select OFF, then press Enter to save. 2. To access the Maintenance mode menu, press Program, scroll to Technician, and then press Enter. 3. Scroll to service settings, then press Enter. 4. Enter the service password: 3156. 5. Scroll to Stage Disable, then press Enter. 6. For Stage Control, change No to Yes, press Enter, scroll up, and then press Enter. The screen displays the stages. 7. Press Enter to access each stage, then scroll up or down to change from Auto to Disabled. 7 .2 Accessing Maintenance Mode from the Touch Screen 1. Tap the touch screen to view the menu buttons, then tap Chiller Summary. See “Touch Screen” on page 5. IThe system must be in off mode to access maintenance mode.

VARC Chiller Controls

2. Tap the wrench icon. 34 Chiller Summary 3. From the Chiller Control menu, select YES to enable Maintenance mode. 35 Chiller Control Menu 4. To disable a stage, tap the menu to the right of the stage number and select Disabled. 36 Disable Stage 5. Tap X to exit, then turn on the VARC. 8 Troubleshooting The following tables describe the VARC alarm characteristics and corrective actions. � WARNING: ELECTRICAL SHOCK HAZARD . Failure to obey the following warnings could result in death or serious injury: • Exercise extreme care when working around energized equipment. • Maintenance and repair should be performed only by qualified technicians. 8 .1 Alarms In the event of a fault, the system does not generate an alarm immediately, but instead applies an alarm retry logic scheme. The system shuts down and attempts the number of retries that is set on the parameters table before creating an alarm that needs to be reset manually. The following table describes the alarm conditions and corrective actions to be taken.

VARC Chiller Controls

Troubleshooting Alarm Reset Delay Alarm Relay System Action Corrective Actions Alarms Power+ n˚1 None 1:Overcurrent 2:Motor Overload 3:Overvoltage 4:Undervoltage 5:Over Temp 6:Under Temp 7:Overcurrent HW 8:Motor Overtemp 9:Drive Failure 10:CPU Error 11:Param Default 12:DC bus ripple 13:Data Comms Fault 14:Drive thermistor 15:Autotune fault 16:Drive disabled 17:Motor Phase 18:Fan Fault 19:Speed Fault 20:PFC Failure 21:Overvoltage 22:Undervoltage 23:STO Detection 24:Reserved 25:Ground Fault 26:CPU Sync 1 27:CPU Sync 2 28:Drive overload 29:Reserved … 99:Unexpected inverter stop Manual Immediate Yes Turns off compressor • Check the load. • Check the network control devices and cables. • Check the input voltage. • Using a 1000 V megohmmeter, check the motor and motor cables for ground faults. • Check the input and output circuits for phase loss detection. • Check the condition of the motor and load wiring. Chilled Water Flow After three retries every 30 minutes, must be reset manually Immediate Yes Turns off compressor or heat relay • Check for proper loop water flow and make sure the strainers are not clogged. • Check for a defective flow switch. • Bleed air out of the loop water. • Check the loop water pump. Chilled Water Return Sensor Failure Manual Immediate Yes Turns off VARC • Check the sensor for shorts and opens. • Compare the temperature reading with the digital thermometer. Chilled Water Supply High Manual 10 sec Yes Turns off compressor or heat relay Check for low water flow due to restrictions or pump wear. Chilled Water Supply Low Manual 10 sec Yes Turns off compressor or heat relay Check for low water flow due to restrictions or pump wear.

VARC Chiller Controls

Alarm Reset Delay Alarm Relay System Action Corrective Actions Chilled Water Supply Sensor Failure Manual Immediate Yes Turns off VARC • Check the sensor for shorts and opens. • Compare the temperature reading with the digital thermometer. Clock Board Fault or Not Connected Automatic Immediate Yes Warning signal Compressor Start Failure After 5 times in 60 minutes, must be reset manually 10 sec Warning signal • Compare the voltage to the compressor. • Check the power inverter. Condenser Out Temperature Sensor Failure Manual Immediate Warning signal • Check the sensor for shorts and opens. • Compare the temperature reading with the digital thermometer. Electric Heat Run Hours Exceeded Yes Turns off heater Check heater the voltage. Envelope Alarm Manual 60 sec Yes Turns off compressor EVD Evo High Evaporation Temperature (MOP) Automatic Immediate Yes Warning signal Check the refrigerant charge. EVD Evo Low Evaporation Temperature (LOP) Automatic Immediate Yes Warning signal • Check the water flows. • Check the refrigerant charge. EVD Evo Low Suction Temperature Automatic Immediate Yes Warning signal Check the refrigerant charge. EVD EVO Low Superheat Automatic Immediate Yes Warning signal • Check for proper refrigerant charge as the system may be overcharged. • Check the water for low flow. • Check the EEV movement and functionality. EVD Evo Probes fault or disconnected (S1, S2, S3, S4) Automatic Immediate Yes Turns off compressor Check the condition of the wiring and connections. Frost Active Manual Immediate Yes Slows down compressor • Low temperature temp switch tripped. • Check the water flows. • Check r the efrigerant charge. High Discharge Gas Temperature Automatic 30 sec Warning signal Check for the proper refrigerant pressure with the gauge.

VARC Chiller Controls

Troubleshooting Alarm Reset Delay Alarm Relay System Action Corrective Actions High Discharge Pressure After 3 retries every 30 mins, must be reset manually Immediate Yes Turns off VARC • Check for the proper refrigerant pressure with the gauge. If normal, check for a defective pressure switch. • Check that there is proper sea water and loop water flow. • Check that water strainers are not clogged. • Check that the system is not overcharged. Inverter Model Not Compatible After 15 retries every 60 mins, must be reset manually Make sure Power+ is being used. Low Pressure Differential Manual 90 sec Yes Turns off VARC • Check the EEV motor. • Use a gauge to check for proper the refrigerant pressure. • Check suction the temperature to verify that the reversing valve is in proper position. Low Suction Pressure After 3 retries every 30 mins, must be reset Manually 60 sec Yes Turns off VARC • Use a gauge to check for the proper refrigerant pressure. If normal, check for a defective pressure switch. • Check for the proper sea water and loop water flow ‘ • Check that the water strainers are not clogged. • Check that the system is not undercharged. Power+ Device Offline Automatic 30 sec Yes Turns off compressor Power+ in Retry Warning signal Check the power supply. Sea Water Inlet Low Manual 10 sec Yes Warning signal Low temperature due to geographical climate. Sea Water Inlet Sensor Failure Manual Immediate Yes Warning signal • Check the sensor for shorts and opens • Compare the temperature reading with the digital thermometer.

VARC Chiller Controls

8 .2 Envelope Zone Status Descriptions Refer to the following table for envelope alarms. The alarm shows the zone number and the description provides details. Zone Name Description 1 Inside envelope zone Working point inside limits 2 High compression ratio Low gas density -> maximum discharge temperature 3 High condensing pressure Mechanical limit 4 Maximum motor current High gas density-> maximum torque 5 High evaporating pressure High gas density-> mechanical limit, noise 6 Low compression ratio Loss of contact between spirals, vibrations 7 Low pressure difference Loss of lubrication 8 Low condensing pressure Low oil temperature -> high viscosity -> poor lubrication 9 Low evaporating pressure Low gas density -> low motor cooling 9 Disposal M Place the packaging material in the appropriate recycling waste bins, whenever possible. Consult a local recycling center or specialist dealer for details about how to dispose of the product in accordance with all applicable national and local regulations. 10 Warranty Information LIMITED WARRANTY AVAILABLE AT WWW.DOMETIC.COM/WARRANTY. IF YOU HAVE QUESTIONS, OR TO OBTAIN A COPY OF THE LIMITED WARRANTY FREE OF CHARGE, CONTACT: DOMETIC CORPORATION MARINE CUSTOMER SUPPORT CENTER 2000 NORTH ANDREWS AVENUE POMPANO BEACH, FLORIDA, USA 33069 1-800-542-2477

Mobile living made easy.

dometic .com YOUR LOCAL DEALER dometic .com/dealer YOUR LOCAL SUPPORT dometic .com/contact YOUR LOCAL SALES OFFICE dometic .com/sales-offices A complete list of Dometic companies, which comprise the Dometic Group, can be found in the public filings of: DOMETIC GROUP AB Hemvärnsgatan 15 SE-17154 Solna Sweden

Other Control Unit Manuals