Condair Cube Operation Manual
Read Online
Read the Condair Cube Operation Manual online using the built-in PDF viewer.
Text of the manual
This document and the information disclosed herein are proprietary data of Condair Group
AG. Neither this document, nor the information contained herein shall be reproduced, used,
or disclosed to others without the written authorisation of Condair Group AG, except to the
extent required for installation or maintenance of recipient's equipment.
Liability Notice
Condair Group AG does not accept any liability due to incorrect installation or operation of
the equipment or due to the use of parts/components/equipment that are not authorised
by Condair Group AG.
Copyright Notice
© Condair Group AG, All rights reserved.
Technical modifications reserved.
Thank you for purchasing your Condair Cube
4
1.2
Notes on the operation manual
4
2
For your safety
5
3
Quickstart
6
4
Product overview
7
4.1
Components
7
4.2
Main screen view
8
4.2.1 Traffic light display of the measured values
9
4.3
Application overviews
10
4.3.1 View health chart
10
4.3.2 View historical readings
11
4.3.3 Settings
11
5
Calibration
12
5.1
Manual Calibration
12
5.2
Auto calibration
14
6
Time and date setting
15
7
Options
17
7.1
SD card
17
7.2
Power bank
17
7.3
Display on large screen
17
8
Scope of delivery
18
9
Disposal/Recycling
19
10�
Product�specification�
20
10.1
Technical data Sensirion SCD40
20
10.1.1 CO2 Sensing Performance
20
10.1.2 Humidity Sensing Performance
20
10.1.3 Temperature Sensing Performance
20
11
Appendix
21
11.1
CE declaration of conformity
21
Thank you for purchasing your Condair Cube
The Condair Cube uses a sensor to detect CO2, relative humidity and temperature
in the ambient environment and is primarily intended for indoor use.
The Condair Cube incorporates the latest technical advances and meets all rec-
ognized safety standards. Nevertheless, improper use of the Condair Cube may
result in danger to the user or third parties. Further, Condair shall not be liable for
any incorrect readings and any damage resulting therefrom.
To ensure a safe, proper, and economical operation of the Condair Cube please
observe and comply with all information contained in the present documentation
as well as in the separate documentations of the components installed in the
Condair Cube.
If you have questions after reading this documentation, please contact your Condair
representative. They will be glad to assist you.
1.2
Notes on the operation manual
Limitation
The subject of this operation manual is the Condair Cube. The various op-
tions and accessories are only described as necessary for proper operation of the
equipment.
This operation manual is restricted to the operation of the Condair Cube and is
meant for users of this device.
Please note that some illustrations in this manual may include options and acces-
sories that may not be standard or available in your country. Please check with
your Condair representative for availability and specification details.
Safekeeping
Please keep this operation manual in a safe place, where it can be immediately
accessed. If the equipment changes hands, the documentation must be passed
on to the new owner
If the documentation gets misplaced, please contact your Condair representative.
Language versions
This operation manual is available in various languages. Please contact your
Condair representative for information.
For your safety
2
For your safety
General
Every person operating the Condair Cube must have read and understood these
instructions before use.
Knowledge of the contents of this manual for the Condair Cube is a basic require-
ment for protecting against any kind of danger, to prevent faulty installations, and
to operate the Condair Cube safely and correctly.
All symbols, signs and markings applied to the components of the Condair Cube
must be observed and kept in readable state.
Intended use
The Condair Cube is intended exclusively for indoor use. Any other type of ap-
plication is considered as not conforming with the intended purpose and may lead
to deviating results being displayed by the Condair Cube. Any warranty claim will
be voided if the device is not used for its intended purpose. Intended use also
includes observing all the information contained in this manual.
Prohibited�modifications�to�the�unit
No�modifications�must�be�undertaken on the Condair Cube without the express
written consent of the manufacturer.
For the replacement of defective components only use original accessories and
spare parts available from your Condair representative.
1. Switch on the Condair Cube: To do this, press the power button inside
the cavity on the lower, left side of the cube (see product overview).
Note:
When the Condair Cube is plugged in via the USB cable, it switches on
automatically. Fully charge the device before using it for the first time.
2. Place the Condair Cube upright in the room where you want to check
the room air. The Cube must be placed as shown in the figure below, so
that the sensor on the back of the Cube is reached by the room air and
the excess heat can escape through the ventilation slots.
3. Once the Condair Cube is in place, it requires an adjustment time of ap-
prox. 20 minutes until all values are displayed correctly. In particular, the
temperature may deviate during the first phase after switching on, since
the sensor is not yet at operating temperature.
4. When the Condair Cube is put into operation for the first time, it must be
calibrated. This procedure is described in chapter 5.
1 housing from 2 parts
–
Display with rechargeable battery (M5core2)
–
Sensor (Sensirion SCD40)
–
USB charging cable
–
Optional Micro SD card (not included in delivery)
Button1
Button 2
LED (green)
Ventilation slots
Slot for Micro SD card
Sensor
Housing
Display
Power button
USB charging cable port
Main screen view
ppm
%RH
°C
CO2
10:15
21.08.2021
85%
ppm
%RH
°C
28
21
1092
CO2
CO2 value
Time
Date
Battery status
Menu
Humidity value
Temperature value
Time/Date:
Shows the current time and date.
Battery status:
Shows the current state of charge of the battery. The display
ranges from 0-100 %.
CO2 value:
Displays the current CO2 content in the air. The value is
given in ppm (parts per million).
Temperature value:
Displays the current temperature value in °C (Celsius).
Humidity value:
Displays the current relative humidity of the ambient air.
Indication in %RH.
Menu bar:
Via the menu bar you can access the various submenus.
– Health chart
– Settings
– Graphical view of the temporal courses of CO2,
humidity and temperature
Button 1:
Turn on screen and increase brightness
Button 2:
Turn off screen and reduce brightness
LED:
When the display is darkened via button 2, the LED lights
up green as an operating indicator.
The circles around the values show the current state of the value in the manner
of a traffic light system:
Green – Healthy (Everything in the optimal range)
Yellow – Acceptable (Caution: Need for action)
Red
– Critical (Critical readings)
CO2
Green circle:
CO2 content of the ambient air is optimal.
(value is ≤ 800 ppm)
Yellow circle:
CO2 content in the ambient air is increased. Ventilation recom-
mended. (value is between > 800 and ≤ 1200 ppm)
Red circle:
CO2 content in the ambient air is critical. Ventilation necessary.
(value is > 1200 ppm)
Relative humidity
Green circle:
Relative humidity of the ambient air is at an optimum.
(value is between ≥ 40 and ≤ 60 % rH)
Yellow circle:
Relative humidity of the ambient air is rather low or rather high.
(value is between ≥ 30 and < 40 % rH or > 60 and < 70 % rH)
Red circle:
Relative humidity of the ambient air is too low or too high.
(value is < 30 % rH or ≥ 70 % rH)
Temperature
Green circle:
Comfortable ambient temperature.
(value is between ≥ 20 and < 23.5 °C)
Yellow circle:
Ambient temperature is rather low or high.
(value is ≥ 17 and < 20 °C or ≥ 23.5 and < 27 °C)
Red circle:
The comfortable temperature range is undershot or overshot.
(value is < 17 °C or ≥ 27 °C)
Note:
Please note that the sensor requires an adjustment time of up to 20 minutes after
switching on, a reset or when moving to a different location, until the temperature
reading is displayed correctly.
4.3.1 View health chart
18°C
22°C
26°C
20%
40%
60%
80%
ppm
CO2
800
1200
10:15
21.08.2021
85%
CO2 display in bar format
Currently measured value
Range "healthy"
Range "acceptable"
Temperature
Air humidity
The range "healthy" represents the air quality, which provides increased health
protection and is perceived as pleasant.
The ranges "healthy, "acceptable" and "critical" are distinguished.
The aim is that the current measured value (red point) of the room air is in the inner
green diamond and thus in the "healthy" range.
In the upper area of the view, the currently measured CO2 content of the room air
is displayed in a bar view. If the current measured value is outside the green range,
the room should be ventilated to reduce the CO2 content in the room.
Note:
If the currently measured value is displayed as a gray dot at the edge of the diagram,
it indicates that the measured value is outside the displayed range.
4.3.2 View historical readings
18
22
26
h
1
2
3
4
°C
°C21
10:15
21.08.2021
85%
Currently measured value
Historical measured values
This view shows the course of the measured room temperature over a maximum
of 4 hours.
For every 10 minutes of measurement, a bar is displayed which shows the average
value measured. This is colored according to the described traffic light system. See
chapter chapter 4.2.1. If the bar is yellow or red, the temperature was too low or
too high on average over the last 10 minutes, taking the health chart into account.
A 4-hour chart is available for all measured values of CO2, temperature and humidity.
These views are accessible via the arrow keys on the side of the circle.
4.3.3 Settings
CO2
10:15
21.08.2021
85%
Alarm settings
Calibration CO2
Time and date settings
Via the 3 icons you can call the different submenus:
–
Alarm settings
–
Calibration CO2
–
Time and date settings
Tap once on the respective icon to enter the submenus.
For accurate measurement results of the CO2 content, the Condair Cube must be
calibrated regularly. Two different calibration options are available:
–
Auto calibration
–
Manual calibration
5.1
Manual Calibration
To calibrate the sensor manually, proceed as follows:
1. Menu → Settings → Calibration CO2
CO2
10:15
21.08.2021
85%
CO2
CO2
Manual
Auto
2. Place the sensor outdoors, for example outside the window in fresh air.
Outside air is used as a reference, since it normally has a value of ap-
prox. 400 ppm.
Start
10:15
21.08.2021
85%
3. Press "Start" to start calibration.
4. The measurement takes approx. 3 minutes This is displayed graphically
with a bar graph and a percentage. The sensor resets its CO2 value
several times during this time.
ppm
CO2
10:15
21.08.2021
85%
21
44%
5. After the calibration is completed, the Cube automatically switches to the
main page.
ppm
%RH
°C
CO2
10:15
21.08.2021
85%
ppm
%RH
°C
28
21
1092
CO2
6. Check the CO2 value. If it is within the range of 400 +/-25 ppm, the
calibration was successful. If the value is above or below this, repeat the
calibration.
Important:
The sensor must be calibrated during the first start-up.
Also, if you place the Cube in a new geographical location, it must be recalibrated
for accurate measurement results.
By default, the auto calibration is activated, whereby the sensor calibrates its
value independently. It is important here that the sensor is in operation as
permanently as possible and is exposed to fresh outside air at least once a
week (approx. 10 min).
During auto-calibration, the lowest measured value over one week is taken
as the reference value and recalibrated to 400 ppm.
Note: This setting is also saved when the cube is switched off.
1. Menu → Settings → Calibration CO2
2. Auto calibration
3. Enable or disable auto calibration
If the Condair Cube is not operated permanently, it is recommended to deactivate the
auto calibration and to perform a manual calibration when using the Condair Cube.
CO2
10:15
21.08.2021
85%
CO2
CO2
Manual
Auto
OFF
CO2
Auto
Time and date setting
6
Time and date setting
The Condair Cube has an internal RTC (RealTimeClock) which is used for the time
and date display. Time and date run for approx. 2 months when the unit is switched
off and without charging the Cube. Afterwards, both must be reset.
Follow the procedure below to reset the time and date:
1. Menu → Settings → Time and date settings
CO2
10:15
21.08.2021
85%
2. Set the desired time using the up/down arrow keys.
The time format is defined as follows:
hh:mm:ss (Hours:Minutes:Seconds)
Ok
:
:
10:15
21.08.2021
85%
10
15
33
3. Confirm the entry with "Ok".
Time and date setting
4. Enter the desired date in the next screen.
The date format is defined as follows:
dd:mm:yy (Day:Month:Year)
Ok
:
:
10:15
21.08.2021
85%
21
08
21
5. Confirm the entry with "Ok" to complete the date entry.
An optional memory card can be integrated via the SD card slot on the right side of
the Cube. If a memory card is detected during the start-up process, the measured
values are saved to the memory card every minute. With the help of Excel, this
data can be displayed and analyzed.
Recommended memory card:
SANDISK microSDXC 16GB+AD memory card (16 GB, 98 MB/s, grey/red) or similar.
7.2
Power bank
To extend the battery life of the Condair Cube, you can use any power bank with
a 5V USB connection.
7.3
Display on large screen
It is possible to connect the Condair Cube to an external monitor via a PC. To do this,
connect the Condair Cube to the PC via the USB cable and install the necessary
drivers. Then open the Condair Cube Tool to start the display on an external monitor.
The values are updated at intervals of 30 seconds.
Note:
The minimum resolution for correct display of the values is 1024x768. Note that
individual setting of zoom factors may have the negative effect on the display.
Components no longer in use cannot be disposed in domestic waste. Please
dispose of the individual components in accordance with local regulations at the
authorised collecting point.
If you have any questions, please contact the responsible authority or your local
Condair representative.
Thank you for your contribution to environmental protection.
10.1 Technical data Sensirion SCD40
10.1.1 CO2 Sensing Performance
Default conditions of 25 °C, 50 % RH, ambient pressure 1013 mbar, default pe-
riodic measurement and 3.3 V supply voltage apply to values in the table below,
unless otherwise stated.
Parameter
Conditions
Value
CO2 output range
–
0 – 40'000 ppm
CO2 measurement accuracy
400 ppm – 2'000 ppm
± (50 ppm + 5 % of reading)
Repeatability
Typical
± 10 ppm
Response time
T63 %, typical
60 s
Accuracy drift per year with au-
tomatic selfcalibration algorithm
enabled
Typical
± (5 ppm + 0.5 % of reading)
10.1.2 Humidity Sensing Performance
Parameter
Conditions
Value
Humidity measurement range
–
0 % RH – 100 % RH
Accuracy (typ.)
15 °C – 35 °C,
20 % RH – 65 % RH
± 6 % RH
-10 °C – 60 °C
± 9 % RH
Repeatability
Typical
± 0.4 % RH
Response time
T63 %, typical
90 s
Accuracy drift
–
< 0.25 % RH / year
10.1.3 Temperature Sensing Performance
Parameter
Conditions
Value
Temperature measurement range
–
-10 °C – 60 °C
Accuracy (typ.)
15 °C – 35 °C
± 0.8 °C
-10 °C – 60 °C
± 1.5 °C
Repeatability
–
± 0.1 °C
Response time
T63 %, typical
120 s
Accuracy drift
–
< 0.03 °C / year
11.1 CE declaration of conformity
Condair Group AG
Gwattstrasse 17
8808 Pfäffikon, Switzerland
Tel. +41 55 416 61 11, Fax +41 55 588 00 07
[email protected], www.condairgroup.com
EC
Konformitätserklärung
Declaration of conformity
Déclaration de conformité
Wir,
Condair Group AG
CH-8808 Pfäffikon SZ
erklären in alleiniger Verantwortung,
dass das Produkt
We,
Condair Group AG
CH-8808 Pfäffikon SZ
declare under our sole responsibility, that
the product
Nous,
Condair Group AG
CH-8808 Pfäffikon SZ
déclarons sous notre seule
responsabilité, que le produit
Condair Cube
auf das sich diese Erklärung bezieht,
mit den folgenden Normen oder
normativen Dokumenten
übereinstimmt
to which this declaration relates is in
conformity with the following standards or
other normative standards
auquel se réfère cette déclaration est
conforme aux normes ou autres
documents normatifs
EN 55032
EN 61000-3-2
EN 61000-3-3
EN 301489-1 V2.2.3
EN 301489-17 V3.2.3
EN 300328 V2.2.2
und den Bestimmungen der folgenden
Richtlinien entspricht
and is corresponding to the following
provisions of directives
et est conforme aux dispositions des
directives suivantes
RED-Richtlinie 2014/53/EU
EMC-Richtlinie 2014/30/EU
ROHS Neufassung der Richtlinie
2011/65/EG
RED directive 2014/53/EU
EMC directive 2014/30/EU
ROHS recast directive 2011/65/EC
Directive RED 2014/53/EU
Directive EMC 2014/30/EU
Directive de refonte ROHS
2011/65/CE
Pfäffikon , September 01, 2021
Condair Group AG
Eric Roth
Head of Engineering
Adrian Spörri
Corporate Systems Manager
2603018 DE/EN/FR 2109
Condair Group AG
Gwattstrasse 17, 8808 Pfäffikon SZ, Switzerland
Phone +41 55 416 61 11, Fax +41 55 588 00 07
[email protected], www.condairgroup.com
CONSULTING, SALES AND SERVICE:
CH94/0002.00