eta Fresh water module 33 Operating Instructions Manual
Read Online
Read the eta Fresh water module 33 Operating Instructions Manual online using the built-in PDF viewer.
Text of the manual
A-4716 Hofkirchen an der Trattnach
Tel: +43 (0) 7734 / 22 88 -0
Fax: +43 (0) 7734 / 22 88 -22
[email protected]
www.eta.co.at
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2
Warranty, guarantee and liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2
CE-Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1
Technical data "Fresh water module 33" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2
Technical data "Fresh water module 44" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3
Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4
Information for installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.1
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2
Select installation site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.3
Connecting piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.4
Circulation set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6
Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.1
Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.2
CAN bus installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.3
Circuit board EM-C4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8
Information on cold water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8.1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8.2
Calcification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8.3
Corrosion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8.4
Thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9
Descaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
10
ETAtouch controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.1 Up to software version X.35.X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.1.1 [Fresh water module] 2 pumps function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.1.2 Setting a time window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
10.2 Software version X.36.0 and later . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10.2.1 [Fresh water module] function block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
10.2.2 Setting a time window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10.3 Text menu - Adjustable parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
All contents of this document are property of ETA
Heiztechnik GmbH and are protected by copyright.
Any reproduction, transfer to third parties or use for
other purposes is prohibited without written permission
from the owner.
Subject to technical changes
We reserve the right to make technical modifications
without notice. Printing and typesetting errors or
changes of any kind made in the interim are not cause
for claims. Individual configurations depicted or
described here are only available optionally. In the
event of contradictions between individual documents
regarding delivery scope, the information in our current
price list applies.
Software Description
The software version described in this documentation
corresponds to the version valid at the time of publica-
tion. The software version installed on your product
may differ from that described in this documentation.
A software update to a more recent version can
always be performed. With the appropriate au-
thorisation, the required files can be found at
"www.eta.co.at".
Explanation of symbols
Instructions and information
Layout of safety instructions
SIGNAL WORD!
Type and source of danger
Possible effects
•
Measures for avoiding the danger
Types of safety instruction
CAUTION!
On non-compliance with this safety instruction, there is
a risk of material damage.
WARNING!
On non-compliance with this safety instruction, there is
a risk of physical injury.
DANGER!
On non-compliance with this safety instruction, there is
a risk of major physical injury.
1.2
Warranty, guarantee and liability
Installation in a dry, frost-proof room
A dry, frost-proof room is required for the installation.
Heed the drinking water ordinance
In terms of drinking water, the chemical, physical and
bacterial limits stated in the applicable national
drinking water ordinance must not be exceeded. See
chapter on 8 "Information on cold water".
Calcification
Potential calcification of the fresh water module is
excluded by the warranty. In the case of water with par-
ticularly high scale-forming properties, water softening
or regular descaling may be necessary. You can find
more information in the chapter on 8 "Information on
cold water".
Safety valve for the drinking water line
Before each closed drinking water heater (=TWE /
tank) a membrane safety valve is to be installed in
accordance with DIN 1988 and 4753, Part 1 and
TRD 721. This valves opens automatically when a set
operating pressure is exceeded (6, 8, 10 bar), and
after a pressure reduction it closes again automatical-
ly.
Except flow heaters with a nominal volume of less than
3 litres.
The ETA fresh water module falls under this
exception rule. That is why no additional safety
valve is required.
With the optional circulation set, however, a
safety valve is required on the drinking water side
(10 bar) and that is why it is already installed at the
factory. This must not be blocked nor removed.
pH value between 8 and 9
The pH value of water used to fill the heating system
must be between 8 and 9.
Warranty, guarantee and liability
5
Expanding the control system
Only components provided by us may be used for
expanding the control system, unless these are
generally available standard devices, such as thermo-
stats.
Proper installation
The installing contractor is liable for proper installation
according to the corresponding installation instructions
and the relevant rules and safety regulations. If you as
customer have installed the heating system partly or
entirely without relevant training and in particular
without up-to-date practical experience, without having
the installation checked by a trained and responsible
expert, we exclude defects in our delivery and conse-
quential damages resulting from this cause from our
warranty, guarantee and liability.
Repairs
Repairs are only permitted using spare parts provided
by us. The only exceptions are common standardised
parts such as electrical fuses or fastening materials, as
long as they possess the required features and do not
restrict the functionality of the system.
Repair of defects
For repairs of defects carried out by the customer or by
a third party, ETA shall only bear the costs or remain
obligated by warranty if this work was approved in
writing in advance by the customer service of ETA
Heiztechnik GmbH.
ETA Heiztechnik GmbH
A-4716 Hofkirchen an der Trattnach, Gewerbepark 1
www.eta.co.at
Declaration of conformity
Product:
Fresh water module with energy-saving pumps
Types:
ETA FWM-E
EU Directives:
2004/108/EC
Directive relating to electromagnetic compatibility (EMC Directive)
2006/95/EC
Directive relating to electrical equipment designed for use within certain voltage limits
(low-voltage Directive)
2011/65/EU
Directive on the restriction of the use of certain hazardous substances in electrical and
electronic equipment (RoHS 2 Directive)
Applied Standards:
EN 60335-1:2012
Household and similar electrical appliances - Safety
Part 1: General requirements
IEC 61000-6 1/2:2005
Electromagnetic compatibility (EMC):
Generic standards - Immunity for residential, commercial and light-industrial environ-
ments (1) and industrial environments (2)
IEC 61000-6 3/4:2007
+ A1:2011
Electromagnetic compatibility (EMC):
Generic standards - Emission standard for residential, commercial and light-industrial
environments (3) and industrial environments (4)
We hereby declare that the product in its standard design as stated here corresponds to the above provisions.
Hofkirchen, 16/05/2014
Ing. Johann Eibelhuber
Quality Assurance
DI Ferdinand Tischler
Management
Technical data "Fresh water module 33"
7
3
Description
3.1
Technical data "Fresh water
module 33"
Fig. 3-1: Components
1
Bleed screw
2
Return temperature sensor for hot water circuit
3
3/4" flow connector from buffer
4
Admixing pump as calcification protection
5
Flow temperature sensor for hot water circuit
6
Buffer pump for hot water circuit
7
Flow sensor with temperature sensor for hot water
8
3/4" return connection to buffer
9
3/4" cold water connection
10 3/4" hot water connection
11 Optional circulation pump with safety valve
(10 bar) and drain cock to empty the hot water
circulation line
12 Circuit board [EM-C]
Fig. 3-2: Dimensions
Technical data
Tap output
33 litres/minute with 45 °C hot water at a buffer
temperature of 60 °C.
Pressure loss (drinking water side)
15 litres/minute = 150 mbar (1,5 mws)
33 litres/minute = 580 mbar (5,8 mws)
Connections (drinking water side)
DN20 (3/4") internal thread; according to DIN
DVGW or ÖNORM B5014-4
Connections (hot water side)
DN20 (3/4") internal thread
Purging connections
DN15 (1/2")
Pumps
Two speed-regulated highly efficient pumps for
hot water preparation and calcification
protection (admixing pump)
Standards
Corresponds to DIN DVGW or ÖNORM B5014-
4
Technical data "Fresh water module 44"
Description
3.2
Technical data "Fresh water module 44
"
Fig. 3-3: Components
1
Bleed screw
2
Return temperature sensor for hot water circuit
3
1" flow connector from buffer
4
Admixing pump as calcification protection
5
Flow temperature sensor for hot water circuit
6
Buffer pump for hot water circuit
7
Flow sensor with temperature sensor for hot water
8
1" return connection to buffer
9
1" cold water connection
10 1" hot water connection
11 Optional circulation pump with safety valve
(10 bar) and drain cock to empty the hot water
circulation line
12 Circuit board [EM-C]
Fig. 3-4: Dimensions
Technical data
Tap output
44 litres/minute with 45°C hot water at a buffer
temperature of 60°C
Pressure loss (drinking water side)
20 litres/minute = 160 mbar (1,6 mws)
44 litres/minute = 560 mbar (5,6 mws)
Connections (drinking water side)
DN25 (1") internal thread; according to DIN
DVGW or ÖNORM B5014-4
Connections (hot water side)
DN25 (1") internal thread
Purging connections
DN15 (1/2")
Pumps
Two speed-regulated highly efficient pumps for
hot water preparation and calcification
protection (admixing pump)
Standards
Corresponds to DIN DVGW or ÖNORM B5014-
4
Potentiometer and operating display
The temperature of the hot water can be set with the
potentiometer on the under side, from 40°C to 60°C.
The LED that is attached next to it shows the current
operating condition as well as any faults regardless of
the light colour and the flashing frequency.
The potentiometer is only active if the fresh water
module is operated without the ETAtouch
controller.
1
LED for operating display
2
Potentiometer to set the hot water temperature
Operating displays of the LEDs
•
Flashing GREEN (1x per second):
The fresh water module is in preparation.
•
GREEN lights:
The fresh water module is in operation and delivers
hot water.
•
Flashing YELLOW (1x per second):
The fresh water module is ready, but in emergency
mode without admixing pump.
•
YELLOW lights:
The fresh water module is in emergency mode and
delivers hot water.
Fault displays of the LEDs
•
Flashing RED (1x every 4 seconds):
The temperature sensor for the hot water is
defective.
•
Flashing RED (2x every 4 seconds):
The temperature sensor for the hot water flow is
defective.
•
Flashing RED (3x every 4 seconds):
The temperature sensor for the hot water return is
defective.
•
Flashing RED (4x every 4 seconds):
The potentiometer for manual setting of the hot
water temperature is defective.
•
Flashing RED (5x every 4 seconds):
Automatic venting by the admixing pump does not
work. There may be air in the primary circuit of the
fresh water module. Or the admixing pump,
cabling or the outlet on the circuit board is
defective.
If emergency mode is activated, it still attempts to
produce hot water.
To remedy, vent the fresh water module or activate
the function [Automatic venting].
•
Flashing RED (6x every 4 seconds):
The hot water is not heated. The buffer may be
cold or the lines are blocked. Also check the func-
tionality of the buffer pump. If it is defective, you
can try to produce hot water by replacing the
admixing pump and activating emergency mode.
The fresh water module works autonomously.
The basic functions of the fresh water module are
already configured at the factory, also without CAN-
Bus connection to boiler. In this way, the fresh water
module can be put into operation immediately as soon
as the buffer delivers heat. Power is supplied via a
230 V earthed socket.
The temperature of the hot water can be set with the
potentiometer on the under side, from 40 °C to 60 °C.
The LED that is attached next to it shows the current
operating condition as well as any faults.
Even if the fresh water module works autono-
mously, a CAN-Bus connection to the ETAtouch
controller is recommended. This enables multiple
settings for the hot water and any faults are reported
back.
How the fresh water module works
If hot water is drawn off, the flow sensor starts up the
buffer pump of the fresh water module. The hot heating
water is directed through the primary side of the plate
heat exchanger, heating it up.
Fig. 3-5: Function of the fresh water module
1
Connections for the boiler water circuit (primary
side)
2
Connections for cold water (secondary side)
The cold water that simultaneously flows through the
plate heat exchanger on the secondary side absorbs
this heat and exits the fresh water module as hot water.
The design of the fresh water module protects it
against calcification
In principle, all parts that bear hot water are at risk of
calcification, particularly in the context of hard,
calcareous water and temperatures above 60°C.
However, the decisive advantage of the fresh water
module compared with a hot water tank is its very fast
flow, which leaves almost no time for the lime to build
up in the plate heat exchanger. In the same way, the
lime build up has little opportunity to form as it is
purged from the plate heat exchanger as a result of the
high flow speeds.
In order to protect the plate heat exchanger
against calcification, a second pump called an
admixing pump is also installed. Whilst the hot water is
being drawn off, the admixing pump reverse pumps a
proportion of the heating water that has cooled down in
the plate heat exchanger and mixes this with the hot
heating water from the buffer. As a result of this, the
critical calcification temperature of 60°C is not reached
and lime buildup is prevented.
Fig. 3-6: Admixing of heating water
If a hot water temperature above 55 °C is set, it is
no longer assured that the heating water can be
mixed to a temperature below 60 °C. This can result in
individual ducts of the plate heat exchanger no longer
having any protection against calcification.
The hot side of the plate heat exchanger is arranged at
the bottom. As hot water rises and cool water sinks, the
water is mixed in the plate heat exchanger at the end
of each hot water draw-off. This ensures that the plate
heat exchanger will cool down to below the critical
temperature of 60°C during the standby phases.
Information for installation
11
Hydraulic connection of the fresh water module
The schematic representation also contains the
optionally available circulation set. A bleed valve with
sufficient dimensions must be installed at the highest
point of the flow line from the buffer to the fresh water
module.
Fig. 3-7: Hydraulic connection
Required software version
The configuration of the fresh water module "33"
requires the software version X.35.7 or X.41.0 or
higher. An update must be performed first if a lower
version is installed.
The fresh water module "44" requires the
software version X.46.0 or higher. A configuration
with the previous software interface (up to X.35.X) is
therefore not possible. But the fresh water module
works independently, even without a CAN-bus
connection to the ETAtouch control.
3.4
Information for installation
Hydraulically uncoupling the fresh water module,
only installing a solenoid valve in exceptional
cases
Ideally, separate piping must run between the fresh
water module and the buffer and this should not be
integrated in the flow between the heat producer and
the buffer.
However, if this is not possible, then a solenoid
valve (230 V, Kv value > 7) must be installed in
the boiler water return line of the fresh water module.
This opens only if hot water is required and prevents
the plate heat exchanger from being heated up unin-
tentionally by the boiler pump (the pump from the heat
producer to the buffer).
The solenoid valve is connected to the circuit board
[EM-C] at the terminal [S102 LZ]. The ouput of the
buffer pump from the fresh water module must then be
duplicated, i.e. additionally assigned to the terminal
[S102 LZ]
on
the
circuit
board
[EM-C]. This
assignment is only possible for systems with an
ETAtouch control panel.
Take the line resistance of the hot water installa-
tion into account.
The "WILO - Yonos Para-Z" pump installed in the
optional circulation set is dimensioned so that in con-
ventional installations a sufficient flow rate is achieved
(see pump curve).
The flow sensor of the fresh water module is
dimensioned for a flow rate of 2 - 40 l/min. But if
less than 1 l/min hot water is used, it could be that the
flow sensor is not responding and thus the circulation
is not starting. For this reason, the line resistance of
the hot water installation must be checked during in-
stallation. If required, the operating mode of the
circulation pump can be adjusted (see Fig. 7-2:
"Factory pump settings").
Practical example:
At 0.24 m³/h feed capacity (4 l/min), an installation with
a new aluminium interconnector (16 x 2.2 mm, 20 m
length, 6 fittings) has a line resistance of approx.
1.60 mWs. This roughly corresponds to the pump
characteristic of the circulation pump at the "constant
speed" setting, just below Stage II (see characteristic
curve Fig. 7-3: ""Constant speed" characteristic
curve"). In this setting, the pump needs approximately
18 W of power.
If the circulation does not work, check the following
points:
•
Were the pipelines purged?
•
Is circulation even possible? (blocked lines,
crushing, pressed in protective cap ...)
Information for installation
Description
•
Check the pipe dimensions, lengths and number of
fittings and calculate the line resistance.
The technical illustrations show the assembly of the
"fresh water module 33". These graphics apply equally
to other available fresh water modules from ETA.
Assembly and installation only by qualified
specialist personnel
The assembly and installation may be performed
by specialist personnel with the corresponding
qualifications only.
4.1
Preparation
Select installation site of the fresh water module
The fresh water module can be attached to a wall or
directly on the buffer storage tank. If installing on a
wall, the fresh water module should be mounted in the
vicinity of the buffer (maximum 5 m simple line length)
to limit pressure losses.
The length of the CAN-Bus line supplied for
connection
to
the
boiler
is
10 m.
The
3 temperature sensors for the buffer can be connected
to the circuit board [EM-C] of the fresh water module.
Removing the plastic cover
Prior to starting installation, remove the plastic cover
by loosening the screw on the bottom side.
Hydraulic connection on the buffer
Ideally, the fresh water module is laterally connected to
the buffer. Since this ensures optimal ventilation of the
buffer on its buffer cap.
Fig. 4-1: preferred connection variant
If a lateral connection is not possible, the fresh water
module can be connected to the buffer cap. But then
the flow line must have an incline to the fresh water
module. The T-piece for the bleed valve must be the
same size as the connection on the buffer, so that no
air pocket may form.
Fig. 4-2: alternative connection variant
Select installation site
Installation
4.2
Select installation site
Mounting the fresh water module on the wall
The position for two screws on the top and bottom side
each must be transferred to the wall. Mount the
four screws in the wall, hang the fresh water module
on these and fasten in place.
Fig. 4-3: Mounting holes for wall installation
The fresh water module weighs approximately
20 kg.
Mounting the fresh water module on the buffer
For mounting the fresh water module on the buffer, a
bracket with clamping jaws for 6/4" nipples is optionally
available.
Fig. 4-4: optional bracket with clamping jaws
Reseal the 6/4" nipple and mount in a buffer
connection that is not in use. Mount the clamping jaws
at the required height in the bracket. Push the bracket
with the clamping jaws onto the nipple and fasten
using the two screws.
Fig. 4-5: Bracket with clamping jaws
Hang the fresh water module on the 4 screws present
on the bracket and fasten.
Fig. 4-6: Fastening the fresh water module in place
4.3
Connecting piping
Leave the joint at the fresh water module "44"
For the fresh water module "44", the joint is
already included in the delivery scope of the fresh
water module. Keep this in fresh water module so that
it is available if later a circulation set is retrofitted.
Fig. 4-7: Joint
Mounting the screw joints
At the top, mount the ball valve on the flow connection
using the supplied flat seal.
Fig. 4-8: Ball valve on flow connection
Mount the check valve and the ball valve on the return
connection to the buffer. Use flat seals with all screw
joints.
Fig. 4-9: Check valve on return connection
Note the flow direction of the check valve. This
must flow from the fresh water module to the
buffer.
For cold water, mount both ball valves with purging
connections using the supplied flat seals.
Fig. 4-10: Cold water connections
Produce piping for the fresh water module
The preferred lateral connection of the fresh water
module to the buffer is shown in the following.
Establish the flow line from the buffer to the fresh water
module.
Fig. 4-11: Flow line to the fresh water module
If a lateral connection is not possible, the fresh
water module can also be connected to the buffer
cap. But then the flow line must have an incline to the
fresh water module. See the following graphic.
Fig. 4-12: alternative connection
Mount the return line from the fresh water module to
the buffer.
Fig. 4-13: Return line to the buffer
Install bleed valve
A bleed valve with sufficient dimensions must be
installed at the highest point.
Fig. 4-14: Bleed valve
If the fresh water module was connected to the buffer
cap, the T-piece for the bleed valve must be the same
size as the connection on the buffer, so that no air
pockets may form.
Fig. 4-15: Bleed valve
Installing the dirt filter upstream of the fresh water
module
At least one dirt filter must be installed upstream
of the fresh water module in the cold water
system.
Connecting the cold water pipe
Connect the cold water pipe to the fresh water module.
Fig. 4-16: Cold water connections
If the water installation is designed with rigid
pipes and narrow diameters (such as 15 mm CU
or 1/2" galvanised, for example), then pressure shocks
are to be expected. In order to protect all components
against pressure shocks, we recommend fitting a small
diaphragm pressure expansion vessel (for example,
8 litre version suitable for drinking water) in order to
absorb the pressure shocks in the hot water pipe. The
respective national hygiene standards must be
observed in the process.
Establish a CAN-Bus connection to the boiler
Establish a CAN-Bus connection between the boiler
and the fresh water module with the CAN-Bus line
supplied.
The fresh water module can also be put into
operation without a CAN-Bus connection. The
temperature of the hot water can be set with the poten-
tiometer on the under side, from 40 °C to 60 °C. Nev-
ertheless, a CAN-Bus connection to the ETATouch
controller is recommended, as this enables multiple
settings for the hot water and any faults are reported
back.
Optional circulation set for the hot water
A circulation set for the hot water can optionally be
installed on the fresh water module.
Fig. 4-17: Optional circulation set
1
18 mm joint (DN15)
2
Safety valve (10 bar)
3
Circulation pump
4
Drain cock to bleed the hot water circulation line
5
Joint with 1" outer thread
For the fresh water module "44", the joint is
already included in the delivery scope of the fresh
water module. Keep this in fresh water module so that
it is available if later a circulation set is retrofitted.
Fig. 4-18: Joint
Mounting the circulation set
Insert the circulation set at the fresh water module and
mount the joint at the connection using the supplied flat
seal.
Fig. 4-19: Mounting the joint
To attach the joint, push the bracket into the recess on
the housing.
Fig. 4-20: Attaching the joint
Running piping to the safety valve
A safety valve with 10 bar opening pressure has
already been installed on the circulation set at the
factory.
Fig. 4-21: Safety valve
Position the outlet of the safety valve so that no
leaking water can drip onto the pump. Therefore,
guide the outlet with a pipe to the ground or drainage
system (e.g. sewer). A freely visible, open flow path
(e.g. siphon funnel) during the procedure allows a
visual check to determine whether the safety valve is
dripping.
Dripping safety valve due to pressure surges and
thermal expansion
When running a hot water circulation, the water is
heated in a closed system and expands. The check
valve in the cold water inlet prevents water expansion
in the cold water pipe. The safety valve prevents
excessive pressure in the system and thus protects the
fresh water module or installation. This is why it is
possible that the safety valve opens a little and begins
to drip. Similar to a pressure-free under-counter
storage tank or a hot water tank.
If the water installation is designed with rigid pipes and
narrow diameters (such as 15 mm CU or 1/
2" galvanised, for example), then pressure surges are
to be expected.
In order to protect all components against
pressure shocks, we recommend fitting a small
diaphragm pressure expansion vessel (for example,
8 litre version suitable for drinking water) in order to
absorb the pressure shocks in the hot water pipe. This
expansion tank also avoids a leaking safety valve.
The pressure expansion vessel for the hot water
pipe must comply with the country-specific
hygiene standards.
Connecting the hot water pipe
Connect the hot water pipe for the circulation.
Fig. 4-22: Connecting the hot water pipe
Do not use thermally regulated pumps for hot
water circulation
If the ETA circulation set is not used but instead
an external circulation set is installed, you may
not use thermally regulated pumps. Because this will
switch off when the return gets too warm, then the
"self-learning" function (often called "Auto Loop") will
not work properly for the fresh water module.
Content of this configuration
Only the steps required for the configuration of this
product are described below. The configuration of the
complete heating system is described in the "Configu-
ration" manual supplied with the boiler.
Required software version
The configuration of the fresh water module "33"
requires the software version X.35.7 or X.41.0 or
higher. An update must be performed first if a lower
version is installed.
The fresh water module "44" requires the
software version X.46.0 or higher. A configuration
with the previous software interface (up to X.35.X) is
therefore not possible. But the fresh water module
works independently, even without a CAN-bus
connection to the ETAtouch control.
Starting the configuration assistant
The process of starting the configuration assistant
differs depending on the installed software version.
Software version X.35.X and earlier
•
Increase the authorisation to [Service]. Then open
the [Toolbox] menu by pressing the
button and
the [Configure system] button.
Software version X.36.0 and later
•
In the system settings
, increase the authori-
zation to [Service] and open the system configura-
tion menu with the [Systems configuration] button.
Start the configuration assistant with the
[Starting the assistant] button.
Description for software version X.36.0 and later
The following description and screen shots represent
the software interface of version X.36.0 and later.
Function block [FWM 2pumps] is already installed
To control the fresh water module using energy-saving
pumps, the circuit board [EM-C] features the separate
[FWM 2pumps] function block; this is already installed
at the factory.
For monitoring purposes, check whether this is
shown in the [Selected function blocks] column
for the circuit board [EM-C 0] in the function blocks
overview.
Adjusting options in function block [FWM 2pumps]
The circulation pump is already configured at the
factory (=option [Circulation pump]) as well as the hot
water temperature settings via the potentiometer only
(=option [Target value can be set with rotary knob]).
If, however, no circulation pump is installed or the
hot water temperature should be set with the
ETATouch controller, these options must be deactivat-
ed.
This is done by selecting the fresh water module
function block from the [Selected function blocks]
column:
Open options. Deactivate the respective option in the
window that opens:
Press the [Accept] button to save.
Adding fresh water module as consumer
The fresh water module is connected to the buffer
as an additional consumer (together with the
heating circuits, for example). A separate connection is
not required.
If there is not yet any connection between the buffer
and the heating circuit, a new connection must be set
up. For this purpose, press the [New connection]
button and select the [Heating water] connection type.
Connect the fresh water module (as a consumer) to
the buffer (as a producer). See below for an example
with a heating circuit and the fresh water module:
Tab. 5-1: Example with heating circuit and fresh water
module
If there is already a connection between the
buffer and the heating circuits, the fresh water
module must only be added to this connection as an
additional consumer.
Selected function blocks
EM-C 0
FWM 2pumps
Circulation pump
Target value can be set with rotary knob
Connections
Heating water
Producers
GM-C 0: Buffer: HC/HWT
Consumers
EM-C 0: FWM: .
GM-C 0: HC: .
Assigning a terminal for the optional solenoid
valve
This step is only necessary if the fresh water
module is installed in the flow between the heat
producer and the buffer, meaning that a solenoid valve
is required. The solenoid valve is connected to the
circuit board [EM-C] at the terminal [S102 LZ] and
must be assigned manually.
Assigning terminal
1.
In the [Selected function blocks] field, first select
the function block of the fresh water module [FWM
(FWM 2pumps)].
2.
Double tap at the buffer pump [Buffer pump]. A
window opens.
3.
Select in the lower window the terminal [S102 LZ]
at the board [EM-C] and add it with [Connect].
4.
Close the window using the [Close] button.
Installing a configuration
Finish by pressing [Apply] to install the configuration.
The configuration will then be adopted and the
software restarted.
Electrical connection must only be made by
qualified specialist personnel
The electrical installation must only be performed
by specialist personnel with the corresponding
qualifications.
Power supply of the module
Power is supplied to the module via the power
plug that has already been mounted; this is
performed independent of the boiler. However, the
power supply can also be securely wired to the
electronic distributor.
DANGER!
Electric shock
There are live parts on the circuit boards. If
touched, they can cause injury and
property damage.
Before beginning any work, isolate the system
completely from all power sources, ensure that it
cannot be switched back on, and verify that it is
safely isolated from supply.
CAUTION!
Flexible stranded conductors
If flexible stranded conductors are not used for the
wiring, the contacts in the plug connections will be
subjected to excessive mechanical strain. In this case,
the warranty for the electronics would become null and
void.
Only flexible stranded conductors may be used for
the wiring.
6.2
CAN bus installation
Establishing a CAN bus connection
To establish the CAN-Bus connection to the boiler,
there a two terminals and the associated cable in the
delivery scope.
Fig. 6-1: CAN-bus cable
Only clamp the "Sch" shield on one side. Do not
connect the "+" and "Gnd" wires.
Example: connection to circuit board [GM-C]
A terminal resistor (yellow jumper) must be set at
the end of the CAN-Bus. If both CAN-Bus
terminals are allocated, the terminal resistor must be
removed on this circuit board.
In the example listed above, the terminal resistor must
be removed from the circuit board [GM-C] at [X4] and
set on circuit board [EM-C] at [X1].
CAN bus installation
23
Check the node numbers if the circuit boards are
the same design
If multiple circuit boards of the same design (e.g.: two
[EM-C]) are connected to one another via CAN-bus,
those circuit boards must have different and
consecutive node numbers. In this way they are
recognized in CAN-bus and can be configured.
Therefore, compare the node numbers of the
individual circuit boards of the same design and
set them as needed using the node switch.
Circuit board EM-C4
Electrical connections
6.3
Circuit board EM-C4
Terminals marked with the
symbol are not factory pre-wired.
Terminal
Function
Default assignment
CAN Node
CAN-Bus node switch
Position "7" for fresh water module "33"
Position "9" for fresh water module "44"
F1
Fuse T 3,15 A (Mains power input)
S100
Supply 230 V
Mains power input
S101
230 V output
Buffer pump and admixing pump
S102 LA
230 V output
Circulation pump (optional)
S102 LZ
230 V output
Motor ball valve for cascade systems (if there are
several fresh water modules)
From factory, this output is intended for motor ball
valves of cascade systems in order to activate
the subsequent fresh water module (also referred to
as "Slave" module).
This output can also be used for a solenoid valve in
order to turn off the heater side of the fresh water
module in case this is not connected hydraulically
decoupled. See chapter 3.4 "Information for installa-
tion".
S103
230 V input
On the factory side, the contacts "NC" and
"COM" are connected (bridged), because
otherwise all 230 V outputs are locked.
S600 T1
Temperature input
Primary flow
S600 T2
Temperature input
Primary return
S600 T3
Temperature input
Free (can be used for buffer)
S600 T4
Temperature input
Free (can be used for buffer)
S600 T5
Temperature input
Potentiometer for the hot water temperature
S600 T6
Temperature input
Hot water
Circuit board EM-C4
25
S601
RS-485 bus
S602
PWM output
Speed control for buffer pump
S603
PWM output
Speed control for admixing pump
S604
24 V input
Flow sensor with temperature sensor
S605A
CAN bus
From boiler
S605B
CAN bus
Free
X1
CAN-Bus terminal resistor
X2
RS-485 terminal resistor
X3
Boot jumper
Terminal
Function
Default assignment
Monitoring the screw joints
Due to vibration and thermal expansion, all screw
joints must be inspected and tightened prior to
commissioning.
Bleeding before commissioning
The fresh water module must be ventilated before
commissioning. For ventilation, there is a ventilation
screw on the top of the fresh water module.
Fig. 7-1: Bleed screw
The option [Automatic venting] has been enabled
at the factory. In this way, the controller
recognises the introduction of air into the heat
exchanger and tries to remove it with the help of both
pumps. This can also take place multiple times one
after the other.
If, however, the water is still not sufficiently warm, there
is still air in the plate heat exchanger and manual
venting is needed. To do this, carry out the following
steps.
Venting the fresh water module
1.
Open the hot water tap in the drinking water
network so that the fresh water module pumps
start.
2.
After about 15 seconds, close the hot water tap
again.
3.
Open the vent screw in the fresh water module and
allow the air to escape.
4.
Then open the hot water tap once more and carry
out the steps again. Carry on doing this until no
more air escapes from the fresh water module.
Mounting the plastic cover
Reattach the plastic cover following commissioning.
Pull off the protective film and affix the ETA logo in the
corresponding recess.
Adjusting the speed of the circulation pump
By default, the circulation pump is set to "Constant
Speed" in the "III" position. If required, the operating
mode "differential pressure variable (Δp-v)" (left scale
on the rotary knob) can also be set.
Fig. 7-2: Factory pump settings
Using the current flow rate (readable in the text menu
of the ETAtouch control) and the pump curve (see
pump characteristics), the speed of the circulation
pump can be adapted to the customer's requirements.
We recommend adjusting the pump so that a flow
rate of approximately 4 l/min is achieved. A
minimum flow of 2 l/min must be guaranteed for the
flow sensor to trigger.
Thermal valves for the circulation line are actually
not required, because the circulation pump shuts
down in time by means of the return sensor. If there are
several strands available for the circulation line and
thermal valves are installed in these, at least one
strand must always remain open (the longest strand, if
possible) so that circulation can occur.
Fig. 7-3: "Constant speed" characteristic curve
Fig. 7-4: "Differential pressure variable (Δp-v)" characteristic
curve
Adjusting the runtime of the circulation pump
After installation, and after all lines have been
connected and vented, the runtime of the circulation
pump must be adjusted. Thus unnecessarily long run
times of the circulation pump can be prevented and the
risk of calcification of the heat exchanger in the fresh
water module is minimized.
You can determine the required running time of
the circulation pump in the following way. Start
the circulation pump in the control system by means of
manual operation in the inputs and outputs menu. After
starting, measure the time until the fresh water module
warms up the return line for the circulation. This time
(e.g. 3 minutes) is required to heat the hot water pipe.
Then enter this time in parameter [Circulation runtime].
During this time measurement, no hot water may be
tapped (e.g. by sink, shower ...), because otherwise an
incorrect time is measured.
Circulation
Circulation runtime
Information on cold water
8
Information on cold water
8.1
General
Different variants of fresh water modules and heat
exchangers
In general, there are two major points to consider for
drinking water heating via plate heat exchangers:
•
Calcification:
This depends on the water hardness specified in
degrees of German hardness (°dH).
•
Corrosion of the plate heat exchanger:
This depends on the water quality, especially the
conductance.
This is why ETA offers two versions of fresh water
modules or replacement heat exchangers. The
inexpensive standard solution with stainless steel
plates connected by copper solder, as well as the
somewhat more expensive special solution with
stainless steel plates connected by stainless steel
brazing solder ("INOX" heat exchanger).
If you have the fresh water module with the
"standard heat exchanger" but are not sure
whether this can keep up with the demands of your
drinking water, then you can operate the fresh water
module normally, of course. If the heat exchanger
actually develops leaks due to copper corrosion, you
can exchange it at any time for the special solution with
stainless steel brazing solder. This heat exchanger is
also offered individually by ETA.
Ask your heating technician
We recommend that you take advantage of the heating
technician's experience. He or she will know whether
you must pre-treat your drinking water and which
procedure is best suited to the drinking water in your
region.
8.2
Calcification
Increasing water hardness increases the risk of
calcification
Irrespective of the type of drinking water heater, we
recommend installing a water softener from a water
hardness of 14°dH and above. With our fresh water
module, damage caused by calcification is not of great
concern since an inexpensive replacement heat
exchanger from ETA can be replaced by the heating
engineer in a few easy steps. For machines like coffee
makers, washing machines, dishwashers ... the
damage from calcification is often associated with high
costs, or the devices may even become irreparable.
Due to the fact that 1 litre of water contains about
18 mg of calcium for each °dH, the risk of calcifi-
cation increases with increasing water hardness. One
litre of water with 10° dH therefore contains around
180 mg calcium, at 20° dH about 360 mg.
The calcification risk also increases when the hot
water temperature is set above 55 °C or when
circulation pumps are operated for 24 hours (in other
words practically all the time). In these cases, the
provided protective measures against excessive calci-
fication, such as reducing the primary temperature
(see functionality of the fresh water module),
circulation breaks or its deactivation and optimised
connection arrangement of the ETA fresh water
module, are unable to cope.
The heat exchangers offered by ETA do not
exhibit any differences in terms of calcification.
They only differ in terms of corrosion resistance.
8.3
Corrosion
The electrical conductance is crucial for possible
copper corrosion
What is important for potential copper corrosion of the
solder connections of the individual plates is the
electrical conductance. How well water conducts
current is determined with the conductance meter. This
can only measure how well all conductive minerals in
the water conduct together. The conductance of
individual materials cannot be determined. So this
overall hardness determines the conductance.
Basically, water with a lower conductance has a lower
overall hardness. Water with higher conductance is
correspondingly harder. However, it is not possible to
calculate the hardness from the conductance with a
precise formula, or vice versa.
A rule of thumb is: per °dH the conductance of tap
water increases by at least 35 μS/cm.
Due to the content of sodium, chloride and sulphate in
different tap waters differing widely, the conductance
can be pushed up sharply. For example: tap water with
an overall hardness of: 17° dH and a conductance of
over 700 μS/cm exists. So the rule of thumb can only
be applied to a limited extent for tap water. However, it
is helpful in making a rough estimation without precise
water tests.
In general, copper soldered heat exchangers with
a conductance of less than 500 μS/cm are very
corrosion-resistant. At 500-1000 μS/cm, corrosion
Information on cold water
Thresholds
29
cannot be ruled out depending on other water
properties. At a conductance of over 1000 μS/cm
corrosion is likely.
Therefore, the rule of thumb results in the following
thresholds for copper-soldered heat exchangers in
regard to water hardness:
If the water hardness is minimised by a
softening system, the electrical conductivity
of the drinking water still remains unchanged.
8.4
Thresholds
Thresholds for the water quality on the drinking water side
Tab. 8-1: Thresholds for drinking water
Conductance
Water hardness
Resistance
< 500 μS/cm
at approx.
<14.3° dH
corrosion-
resistant
500-1000 μS/cm at approx. 14.3 -
28.6° dH
Corrosion is no
excluded
> 1000 μS/cm
approx. >28.6°
dH
Corrosion is
likely
Conductance
Water hardness
Resistance
Substance
Standard heat exchanger
(soldered with copper solder)
"INOX" heat exchanger (soldered
with stainless steel brazing
solder)
Appearance
clear
clear
Odour
odourless
odourless
Impurities
free from deposits and/or particles
free from deposits and/or particles
pH value
between 7.5 and 8.5
between 6 and 10
electrical conductivity
< 500 µS/cm
no restriction
Chloride (Cl-)
< 100 mg/l
< 100 mg/l
Sulphate (SO4
2-)
< 100 mg/l
no restriction
Nitrate (NO3)
< 100 mg/l
no restriction
Nitrite (NO2)
not permitted
not permitted
Ammonia (NH3, NH4
+)
< 2.0 mg/l
no restriction
Free chlorine (Cl)
< 1.0 mg/l
< 1.0 mg/l
Iron (Fe)
< 0.2 mg/l
no restriction
Aluminium (Al)
< 0.2 mg/l
no restriction
Manganese (Mn)
< 0.1 mg/l
no restriction
Free carbon dioxide (CO2)
< 5 mg/l
no restriction
Hydrogen sulphide (H2S)
< 0.05 mg/l
no restriction
Hydrogen carbonate (HCO3)
< 300 mg/l
no restriction
Descaling the fresh water module
If the heat exchanger of the fresh water module is
calcified, it can be descaled via the two purging
connections with the use of acetic acid or formic acid.
Fig. 9-1: Purging connections
When descaling using acid, the flow sensor must
be removed and replaced with an adapter as it is
not acid-proof.
Fig. 9-2: Flow sensor
Once a plate heat exchanger has been calcified,
it will never again provide the same level of
performance as a model that is 'as new'. In the event
of heavy calcification, we recommend replacing the
plate heat exchanger. The fair spare part price offered
by ETA means that replacement is often even cheaper
than purging or descaling, both of which are labour-
intensive.
Using acetic acid or formic acid
5 to 12 per cent acetic acid or 10 to 20 per cent formic
acid is suitable for descaling purposes. Both acids are
available from drugstores. Pay attention to the concen-
tration.
CAUTION!
Always pour the acid into the water; never pour the
water into the acid (this leads to spraying that can
cause burns). Use protective gloves and safety
goggles.
In standard cases, use the medium specified dilution.
Dilution using less water poses a risk to the seals.
Mixing ratios:
•
Dilute vinegar essence (25%) with 1 to 4 parts
water
•
Dilute acetic acid concentrate (60%) with 4 to 12
parts water
•
Dilute formic acid (85%) with 4 to 8 parts water
Professional mixtures including phosphoric acid
are available for treating particularly stubborn cal-
cification.
Purge the fresh water module for 1 hour
Mix 10 litres of dilution and use a purging pump to
purge the solution via a pellet bin for approximately
1 hour.
After purging
Having purged the heat exchanger, seal the
connections once more and reattach the cover.
Up to software version X.35.X
31
10 ETAtouch controller
10.1
Up to software version X.35.X
10.1.1
[Fresh water module] 2 pumps
function block
10.1.1.1
Overview
Overview of the fresh water module (2 pumps)
You can return to the overview by pressing
and
[FWM].
1
Operating condition
2
Temperature [Buffer top]
3
Temperature [Primary return]
4
Display of hot water uptake
5
Temperature [Hot water]
6
Timer [Stand-by times]
This only appears if the hot water temperature is
not set via the potentiometer (option [Target value
can be set with rotary knob] is deactivated).
7
Timer [Circulation times]
This only appears if a circulation pump is installed
and the [Self-learning] function is deactivated.
Function of the fresh water module
The desired hot water temperature is set with the po-
tentiometer on the fresh water module. If in the config-
uration the [Target value can be set with rotary knob]
option is deactivated, the timer [Stand-by times]
appears in the overview. With this you can set different
time windows and hot water temperatures for every
day of the week.
Inside these time windows, the upper part of the buffer
is maintained at no lower than the configured hot water
temperature. Outside the set time windows, the hot
water is maintained at the lowest set temperature of
the 3 time windows, provided that the accumulator
tank is sufficiently hot.
If an additional circulation pump for hot water is
installed, the different operating modes for this
pump are set in the same way. See the following
description for this.
Operating modes for the circulation pump
There are two ways to operate the circulation pump.
Either through automatic detection of the operating
times ("self-learning" function, often referred to as
"auto loop") or manual specification of the operating
times (set time window).
•
"Self-learning" function:
This is already set at the factory (= parameter [Self-
learning] to [Yes]). The hot water tappings of the
past 2 weeks are stored for automatic determina-
tion of the daily operating times. On the basis of
this, the operating times of the current day are
calculated and the circulation pump is started in a
timely manner.
In this operating mode, the circulation pump starts
as soon as hot water is drawn (detected by the flow
sensor in the fresh water module). The pump will
then run for a while and subsequently pause.
These runtimes and pauses are configurable
(=parameter [Circulation runtime] and [Circulation
pause]).
After commissioning, no more data is
available for the "self-learning" circulation.
That is why an operating period of about 4 weeks
is required in the beginning, so that the control
system can save sufficient data.
•
Setting a time window:
To do this, the "self-learning" function must be
switched off (= parameter [Self-learning] to [No]).
The operating times of the circulation pump are
now set manually, for example from 10:00 am to
2:00 pm . Within these time windows, the
circulation pump alternately starts and pauses,
based on the set runtimes and pauses, regardless
of whether hot water is currently being drawn or
not.
Example:
Time window = 10:00 am to 2:00 pm
[Circulation runtime] = 5 minutes
[Circulation pause] = 10 minutes
=> The pump runs from 10:00 am to 10:05 am ,
Up to software version X.35.X
ETAtouch controller
then pauses until 10:15 am , restarts at 10:15 am,
pauses from 10:20 am to 10:30 am , and so on ...
until the end of the time window at 2:00 pm .
In this operating mode, the circulation pump
can also start outside of the time window
when hot water is being tapped. This is useful if, for
example, the time window ends at 8:00 pm and
you shower at 9:30 pm . When you then turn on the
hot water briefly, the circulation pump starts, and
you will have hot water for showering shortly
afterwards.
This runtime (outside the time window) is set in the
text menu (parameter [Circulation pump delay]).
Enter the same value as parameter [Circulation
runtime].
Heat exchanger
The tap symbol next to the heat
exchanger is only displayed if the fresh
water module is feeding hot water into the
water mains. The temperature shown
next to this is the temperature of the hot
water currently being supplied.
If no hot water is being supplied, the heat exchanger is
shown blue all the way through.
Circulation pump in operation
Optional: for [Circulation pump]
The pump symbol next to the heat
exchanger appears when the circulation
pump for hot water is in operation.
Timer [Stand-by times]
This is only displayed if option [Target value can
be set with rotary knob] is deactivated
This timer displays the set charging times of the
current day for charging the hot water tank. These time
windows are displayed as a black bar in the timer.
Timer [Circulation times]
This only appears if a circulation pump is installed
and the [Self-learning] function is deactivated.
This timer displays the set times of the current day to
operate the circulation pump. These time windows are
displayed as a black bar in the timer.
10.1.1.2
Operating modes
Ready
No hot water is currently being taken.
Working
Hot water is currently being supplied.
Buffer cold
Hot water is being supplied, but the buffer is not hot
enough to reach the configured hot water temperature.
Primary return too warm
Hot water is being supplied, but the selected hot water
temperature is being reduced because the [Primary
return] temperature in the heat exchanger of the fresh
water module is too high.
Malfunction
A temperature sensor in the fresh water module has a
defect.
Circulation
The circulation pump is in operation.
Venting
The controller has found air in the fresh water module
and automatic venting is in operation. For this, both
pumps are operated at full speed for a short period of
time to remove the air from the fresh water module.
This can also take place multiple times sequentially.
Emergency operation
The fresh water module is in emergency mode
because the admixing pump is defective. Currently, hot
water is being delivered but it is only being produced
with the buffer pump.
Without
the
admixing
pump,
calcification
protection of the heat exchangers it not
guaranteed.
Protracted
emergency
mode
can
therefore calcify the heat exchanger.
Ready (Emergency operation)
The fresh water module is in emergency mode
because the admixing pump is defective.
Without
the
admixing
pump,
calcification
protection of the heat exchangers it not
guaranteed.
Protracted
emergency
mode
can
therefore calcify the heat exchanger.
Circulation
Circulation pump delay
Up to software version X.35.X
33
10.1.1.3
Operation
Setting charging times and temperatures of the
fresh water module
With the [Stand-by times] timer, you can set different
time windows and hot water temperatures for the fresh
water module for each day of the week.
Within these time windows, the upper part of the
accumulator tank is maintained at no less than
the set hot water temperature.
Outside the set time windows, the hot water is
maintained at the lowest set temperature of the 3 time
windows, provided that the accumulator tank is suffi-
ciently hot.
To set the charging times and temperatures, tap the
overview
screen
on
the
[Stand-by
times]
timer. A screen
opens.
Fig. 10-1: Overview of hot water charging times
Set the hot water temperature as low as possible
to prevent limescale build-up.
You can find further details about setting the time
window in chapter 10.1.2 "Setting a time
window".
Setting circulation times for the circulation pump
With the [Circulation times] timer, you can set 3
different time windows for the circulation times of the
circulation pump for each day of the week.
To set the circulation times, tap the [Circulation times]
timer
in
the
overview screen. A screen opens.
Fig. 10-2: Overview of circulation times
Set the circulation times to be as short as
possible to ensure good buffer stratification and
prevent limescale build-up.
You can find further details about setting the time
window in chapter 10.1.2 "Setting a time
window".
Up to software version X.35.X
ETAtouch controller
10.1.2
Setting a time window
Setting time window and temperatures
The time window is set with the timer for charging the
tank (for example for accumulator tank and hot water
tank), or the operating times (for example for the
heating circuit).
1
Timer to set a time window
Setting a time window and the hot water
temperature for the hot water tank will be
described in the following. This example applies
accordingly for all other function blocks with timers.
To
set
the
charging
times,
tap
the
timer
in
the
overview. An overview opens.
Fig. 10-3: Overview
Set the individual time windows and temperatures by
tapping the lines [Time slot 1:], [Time slot 2:], [Time slot
3:] and [Set-back temperature between time slots:]. A
settings window appears after tapping.
Fig. 10-4: Settings window
Enter the time window and desired temperature and
press [Accept] to save. Set the further time windows
the same way.
Press the [Delete] button to delete a set time
window and restore the factory settings.
Copying time windows
After you have set the time windows, you can copy
them for other days of the week. To do this, tap the
[Copy] button in the overview screen.
Fig. 10-5: Overview
Up to software version X.35.X
35
A screen opens showing the individual days of the
week.
Fig. 10-6: Copying time windows
Make your selection and press the [Accept] button to
save.
Software version X.36.0 and later
ETAtouch controller
10.2
Software version X.36.0 and later
10.2.1
[Fresh water module] function block
Fresh water module overview screen
1
Operating condition and information.
A description of the operating conditions can be
found in the integrated Help menu by pressing the
button.
2
Producer for the fresh water module.
Currently, the fresh water module is charged by the
buffer at a flow temperature of 58 °C.
3
Primary side return temperature
4
Circulation pump (only displayed if it has been
installed and is in operation)
5
Hot water temperature (the tap is displayed only
when hot water is currently being drawn)
6
[Settings] button.
In this menu, the time window can be set, for
example.
Function of the fresh water module
The desired hot water temperature is set with the po-
tentiometer on the fresh water module. If in the config-
uration the [Target value can be set with rotary knob]
option has been disabled, different time windows and
hot water temperatures can be set. See chapter on
10.2.1.1 "Setting the hot water charging times".
Inside these time windows, the upper part of the buffer
is maintained at no lower than the configured hot water
temperature. Outside the set time windows, the hot
water is maintained at the lowest set temperature of
the time windows, provided that the accumulator tank
is sufficiently hot.
If an additional circulation pump for hot water is
installed, the different operating modes for this
pump are set in the same way. See the following
description for this.
Operating modes for the circulation pump
There are two ways to operate the circulation pump.
Either through automatic detection of the operating
times ("self-learning" function, often referred to as
"auto loop") or manual specification of the operating
times (set time window).
•
"Self-learning" function:
This is already set at the factory (= parameter [Self-
learning] to [Yes]). The hot water tappings of the
past 2 weeks are stored for automatic determina-
tion of the daily operating times. On the basis of
this, the operating times of the current day are
calculated and the circulation pump is started in a
timely manner.
In this operating mode, the circulation pump starts
as soon as hot water is drawn (detected by the flow
sensor in the fresh water module). The pump will
then run for a while and subsequently pause.
These runtimes and pauses are configurable
(=parameter [Circulation runtime] and [Circulation
pause]).
After commissioning, no more data is
available for the "self-learning" circulation.
That is why an operating period of about 4 weeks
is required in the beginning, so that the control
system can save sufficient data.
•
Setting a time window:
To do this, the "self-learning" function must be
switched off (= parameter [Self-learning] to [No]).
The operating times of the circulation pump are
now set manually, for example from 10:00 am to
2:00 pm . Within these time windows, the
circulation pump alternately starts and pauses,
based on the set runtimes and pauses, regardless
of whether hot water is currently being drawn or
not.
Example:
Time window = 10:00 am to 2:00 pm
[Circulation runtime] = 5 minutes
[Circulation pause] = 10 minutes
=> The pump runs from 10:00 am to 10:05 am ,
then pauses until 10:15 am , restarts at 10:15 am,
pauses from 10:20 am to 10:30 am , and so on ...
until the end of the time window at 2:00 pm .
In this operating mode, the circulation pump
can also start outside of the time window
when hot water is being tapped. This is useful if, for
example, the time window ends at 8:00 pm and
you shower at 9:30 pm . When you then turn on the
hot water briefly, the circulation pump starts, and
Software version X.36.0 and later
37
you will have hot water for showering shortly
afterwards.
This runtime (outside the time window) is set in the
text menu (parameter [Circulation pump delay]).
Enter the same value as parameter [Circulation
runtime].
10.2.1.1
Setting the hot water charging times
Open the overview screen of the set charging
times and temperatures
The standby times for the hot water and the set tem-
peratures can be adjusted in the settings (
button).
To adjust, open the settings and then open the standby
times of any given day with the
[Stand-by times
Daily plan] button. An overview screen opens.
Fig. 10-7: Overview
1
Set time windows (standby times)
2
Select day of the week
3
Add another time window
4
Graphical representation of the time window
setting
5
Overview of all time windows for the entire week
6
Delete time window
7
Adjustable hot water temperature within the time
window
8
Period of the time window
9
Set-back temperature of the hot water outside the
time window
Setting the time window and copying to other
days of the week is described in chapter 10.2.2
"Setting a time window".
If a circulation pump is also installed (and the
function [Self-learning] is switched off), these
operating times are set in the same way (button
[Circulation times Daily plan]).
Circulation
Circulation pump delay
Software version X.36.0 and later
ETAtouch controller
10.2.2
Setting a time window
Setting the charging and operation times
In some function blocks, the time window for charging
the tank (for example the buffer and hot water tank), or
the operating times (for example for the heating circuit)
are set. This time window must be created in the
settings of the respective function block.
Subsequently, the setting of the charging times
and temperatures will be described in relation to
the hot water tank. This example applies accordingly to
other function blocks.
Open the overview of the time window settings
1.
Open the settings for the function block with the
[Settings] button.
Fig. 10-8: Open the settings
2.
Access the charge times of a particular day with
the
[Charging times Daily plan] button.
Fig. 10-9: Access charging times
3.
An overview screen opens.
Fig. 10-10: Overview
1
Selected time window (charging times or operating
times)
2
Select day of the week
3
Add another time window
4
Graphical representation of the time window
setting
5
Overview of all time windows for the entire week
6
Delete time window
7
Adjustable target temperature.
This is dependent on the function block, and, in this
example, corresponds to a hot water temperature
of 55 °C.
8
Period of the time window.
In this example, the hot water is charged between
08:00 a.m. and 8:00 p.m. to 55 °C.
9
Set-back temperature.
Outside the time window, the hot water is charged
to this set temperature.
Setting the time window is described below.
Software version X.36.0 and later
39
Setting the charging times
1.
In the overview, select the charge time. In each
field, use the arrow keys (
,
) to set the
time and temperature.
Fig. 10-11: Setting time slot and temperature
In this example, the hot water is charged between
08:00 a.m. and 8:00 p.m. to 55 °C
2.
If an additional time window is necessary, add it
using the
button. Adjust as described above.
A maximum of 3 time windows can be set. To
delete an unnecessary time window, press
the
button in the selected time window.
3.
For the period outside of the set charging times, a
reduced temperature can be set. To adjust the
settings, select the [Set-back temperature outside
the time window] field and use the arrow keys to
select the desired temperature.
Fig. 10-12: Reduced operation temperature settings
In this example, the desired hot water temperature
outside the charging times is 30 °C.
When loading times and temperatures of a day of the
week have been set, they can be copied to other days
of the week.
Copying time windows
In the following example, the time windows from
Wednesday are copied to Saturday and Sunday.
Time
windows
from Wednesday copied
to
Saturday and Sunday.
1.
In the overview, press the
[Weekly plan] button
to switch to view all days of the week.
Fig. 10-13: Copying time windows to days of the week
2.
This opens an overview of time windows for all
days of the week. First, choose the day of the week
to copy (this is framed) and then press the [Copy
selected day] button.
Fig. 10-14: Overview
3.
Now, select the days of the week for which the time
window is to be copied. In this example Saturday
and Sunday.
Fig. 10-15: Select days of the week
Pressing the [Mark all days] button marks all days.
Text menu - Adjustable parameters
ETAtouch controller
4.
Press the [Save] button to save. The overview will
be updated accordingly. Close the window using
the arrow on the left side.
You can also access the week overview via the
function block settings (
button). For this,
press the
[Charging times Weekly plan] button in
the settings.
10.3
Text menu - Adjustable
parameters
Adjustable parameters
Detailed descriptions of the parameters are provided
below.
Explanation of [Automatic venting]
This function attempts to remove introduced air from
the fresh water module automatically.
If the function is activated and the controller detects air
intake, both pumps are operated at full speed for a
short period of time to remove the air from the fresh
water module. This can also take place multiple times
sequentially.
This function is activated by default. During
venting, the hot water can briefly be hotter than
the target temperature set.
Explanation of the [Emergency operation only with
buffer pump] function
Emergency operation of the fresh water module can be
activated with this function if the admixing pump is
defective.
If it is activated, water heating is only provided by the
buffer pump. Without the admixing pump, calcification
protection of the heat exchangers is not guaranteed
Protracted emergency mode can therefore calcify the
heat exchanger.
Explanation of the function [Self-learning]
With this function, the operating times of the circulation
pump of the last 2 weeks are saved. The operating
times of the current day are calculated based on this
and the circulation pump will be put into operation ac-
cordingly. This function is also called the "Auto Loop"
function.
This function is set to [Yes] by default. If [No] is
set, the operating times for the circulation pump
can be set manually.
Hot water
Automatic venting
Emergency operation only with buffer pump
Circulation
Self-learning
Circulation runtime
Circulation pause
Circulation pump delay
Text menu - Adjustable parameters
41
Explanation [Circulation runtime]
Optional: only for circulation pump
This parameter specifies the duration for operating the
circulation pump after it has been started by the control
system. Once this time has expired, the circulation
pump is switched off for the set duration [Circulation
pause].
Example:
[Circulation runtime] = 3 minutes
[Circulation pause] = 10 minutes
If the circulation pump has been started, it is in
operation for 3 minutes and then disabled for
10 minutes. This means that it can only be requested
again by the control system after 13 minutes.
You can determine the required running time of
the circulation pump in the following way. Start
the circulation pump in the control system by means of
manual operation in the inputs and outputs menu. After
starting, measure the time until the fresh water module
warms up the return line for the circulation. This time
(e.g. 3 minutes) is required to heat the hot water pipe.
Then enter this time in parameter [Circulation runtime].
During this time measurement, no hot water may be
tapped (e.g. by sink, shower ...), because otherwise an
incorrect time is measured.
Explanation [Circulation pause]
Optional: only for circulation pump
This parameter sets the pause after a circulation pump
operation. The control system can only restart the
circulation pump after this pause/break has expired.
Example:
[Circulation runtime] = 3 minutes
[Circulation pause] = 10 minutes
If the circulation pump has been started, it is in
operation for 3 minutes and then disabled for
10 minutes. This means that it can only be requested
again by the control system after 13 minutes.
Explanation [Circulation pump delay]
Optional: only for circulation pump
If a time is set for this parameter, then the circulation
pump also starts outside the time window set. This is
useful if, for example, the time window ends at 8:00 pm
and you shower at 9:30 pm. When you then turn on the
hot water briefly, the circulation pump starts, and you
will have hot water for showering shortly afterwards.
Enter the same value for this parameter as for
parameter [Circulation runtime].
Simplified electrical connection (overview)
11 Simplified electrical connection (overview)
Simplified electrical connection (overview)
43
Frischwassermodul
93994-1
Frischwassermodul
EM-C
S101
S103
S100
S602
S603
S604
S600
N
L
L
N