Extinguishing Control Panel
Installation and Commissioning
The operation and functions described in this manual are available from Software Version Ex-3000-V2.05C onwards.
Steel IP30, RAL 7035
Dimensions H x W x D mm
330 x 400 x 90
Environmental Class
Class A – Indoor IP30 0°C to 40°C
Humidity
95 % Max
Weight (excluding batteries)
5.1Kg
Cable Entries (20mm knockouts)
17x top and 13x top rear
Mains Supply
200V-240V (+10%, -15%), 50/60Hz AC, 1.0A max
Power Supply
Imax
24V DC, 3A High Efficiency Switched Mode [2A load, 1A battery charging]
Ripple: 200mV max. (Note: 1V p-p including switching frequency noise)
Imax(a) = 1.2A 1, Imax(b) = 3.0A 2
Battery Capacity and Battery
Internal Resistance
24V 4Ah Internal (min), 24V 7Ah Internal (max)
1.6Ω
Charging Current
1.0A Temperature Compensated (27.4V DC nominal at 20°C)
Number of Fire Zones
3
Number of Flooding Zones
1
Actuator Output
24V DC, 1.0A suitable for either Metron or Solenoid
Sounder Outputs
3x rated at 1A each programmable
Relay Outputs
4x rated at 1A 30VAC/DC (max) 10mA 5V (min) [2x Fixed – Fire / Fault, 2x Programmable]
Relay Outputs (Optional)
8x rated at 1A 30VAC/DC (max) 10mA 5V (min) programmable (requires EXP-008)
Key-Switches (Optional)
2x Programmable
External Inputs (Monitored)
7x Fixed (Mode, Manual Trigger, Hold, Abort, Flow Monitor, Valve Monitor, Pressure Monitor)
4x Programmable
AUX Supply Output
24V DC, 0.5A
Communications
RS485 to Remote Status Indicators
Display
Graphic LCD 124x64 dots
LED Indicators
26
Event log
100 Fire / Trigger Events, 500 General Log Events
Standards
EN12094-1:2003, EN12094-3 :2003,
EN54-2:1997 +A1:2006, EN54-4:1997 +A1:2002 +A2:2006, EN54-13 :2005
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice
1 The overall capability of the power supply is restricted to panel loading and maximum power available from the AUX outputs. Refer to the
relevant sections of this manual for the minimum and maximum output voltages of each circuit.
2 The charger is turned off in alarm.
Table of Contents
Page
1
INTRODUCTION
5
1.1
STANDARDS
5
1.2
CAUTIONS AND WARNINGS
5
1.3
DESCRIPTION
5
1.1
EN54 FUNCTIONS
6
1.1.1
EN54 Optional Features with Requirements
6
1.2
EN12094 FUNCTIONS
7
1.2.1
EN12094-1 Optional Features with Requirements
7
1.3
INSTALLATION APPROVALS
9
1.3.1
Fire System Installations
9
1.3.2
Wiring Regulations
9
2
INSTALLATION
10
2.1
IDENTIFICATION OF PARTS
10
2.2
INSTALLING THE BACK BOX
11
2.3
WIRING INSTALLATION
12
2.3.1
AC Mains Wiring
12
2.3.1.1
Cable Gland
12
2.3.2
Battery Wiring
12
2.3.3
24VDC Power Supply Wiring
13
2.3.4
PSE Configuration
13
2.3.5
External Wiring
13
2.3.5.1
Relay Outputs
14
2.3.5.2
RS485 Communications
14
2.3.5.3
AUX DC Supply Output
15
2.3.5.4
Detection Zone Inputs
15
2.3.5.5
Sounder / Monitored Output Circuits
16
2.3.5.6
Input Circuits
18
2.3.5.7
Actuator Output Circuit
18
2.3.5.8
USB
19
2.3.5.9
Recommended Cable Routing
20
2.4
KEY-SWITCH INSTALLATION
21
2.5
ADJUSTING THE LCD CONTRAST
21
2.6
LOADING CALCULATIONS
22
2.6.1
Panel Loading
22
2.6.2
Battery Standby Calculation
22
3
PROGRAMMING
23
3.1
INTRODUCTION
23
3.1.1
Access Levels
23
3.1.2
Front Panel Controls and Indications
23
3.1.3
Enable Controls
24
3.1.4
Navigating through menus
24
3.1.5
Numeric data entry
25
3.2
RECOMMENDED PROGRAMMING PROCEDURE
25
3.3
LEVEL 3 MENU FUNCTIONS
25
3.3.1
Detection Zones
26
3.3.2
Alarms
26
3.3.2.1
Sounder Configuration
27
3.3.2.2
Pulse Pattern Configuration
28
3.3.3
Extinguishing
29
3.3.3.1
Output Set-Up
29
3.3.3.2
Cause and Effects Programming
29
3.3.3.3
Extract Set-Up
30
3.3.3.4
Release Signal Termination (Test Function)
30
3.3.4
Inputs
31
3.3.5
Outputs
32
3.3.5.1
Switched AUX Output
33
3.3.6
Passwords
33
3.3.6.1
Default Passwords
33
3.3.7
General Options
34
3.3.7.1
Daylight Saving Options
34
Enable PC LINK
36
3.3.10
Exit
36
4
SERVICE AND MAINTENANCE
37
4.1
MAINTENANCE SCHEDULE
37
4.1.1
Daily Actions
37
4.1.2
Monthly Actions
37
4.1.3
Quarterly Actions
37
4.1.4
Annual Actions
37
4.2
REPLACEMENT OF COMPONENTS
38
4.2.1
Batteries
38
4.2.2
Liquid Crystal Display
38
5
APPENDICES
39
5.1
APPENDIX 1 – FORGOTTEN LEVEL 3 PASSWORD
39
5.2
APPENDIX 2 – COMPATIBLE DEVICES
40
5.2.1
Detectors
40
5.3
APPENDIX 3 – RECOMMENDED CABLES
42
5.3.1
Fire Rated Cables
42
5.3.2
Non-Fire rated cables
42
5.4
APPENDIX 4 – TROUBLESHOOTING
43
Advanced Electronics Ltd declare that the ExGo Gas Extinguishing Control Panel conforms to the essential
requirements specified in the Construction Products Directive 89/106/EEC: Refer to the full CPD schedule on
the back page.
EN12094-1:2003
EN54-2:1997 +A1:2006
EN54-4:1997 +A1:2002 +A2:2006
EN54-13:2005
In addition, the ExGo complies with the following:
Low Voltage Directive 2006/95/EC
EN60950-1: 2006
Safety of information technology equipment
Electromagnetic Compatibility Directive 2004/108/EC
EN55022: 1998
Emissions, Class B
EN50130-4: 1996 +A2: 2003
Immunity, Product Family Standard
1.2 Cautions and Warnings
STOP
BEFORE INSTALLATION – Refer To the Ratings shown on the label inside
the product and to the ‘Specifications Chart’ in this document.
Please read this manual carefully. If you are unclear on any point DO NOT
proceed. Contact the manufacturer or supplier for clarification and guidance.
Only Trained service personnel should undertake the Installation,
Programming and Maintenance of this equipment.
This product has been designed to comply with the requirements of the Low
Voltage Safety, EMC and the CPD Directives. Failure to follow the installation
instructions may compromise its adherence to these standards.
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE DEVICES
This equipment is constructed with static sensitive components. Observe anti-
static precautions at all times when handling printed circuit boards. Wear an
anti-static earth strap connected to panel enclosure earth point. Before installing
or removing any printed circuit boards remove all sources of power (mains and
battery).
1.3 Description
This manual covers the installation, programming and commissioning of the ExGo Extinguishing Control Panel.
Refer to the User Manual (Document No. 680-148) for details of how to operate the panel.
The ExGo is a Single Flooding Zone Control Panel with up to three detection zone circuits.
The detection zones are compatible with conventional detectors and call points. Refer to the compatibility
section for full details of the compatible devices tested.
Install the panel, detection circuits, sounder circuits, etc. in accordance with the instructions in Section
2 and then program the operation in accordance with the instructions detailed in Section 3.
1.1 EN54 Functions
This Control Panel is compliant with the requirements of EN54-2: 1997 +A1: 2006
and EN54-4: 1997 +A1: 2002 +A2: 2006.
In addition to the basic requirements, the following optional functions are provided
and these comply with the requirements of EN54.
CIE Optional Functions
EN54-2 Clause
Outputs to Fire Alarm Devices
Delays to outputs
Alarm Counter
Total Loss of Power
Test Condition
7.8
7.11
7.13
8.4
10
P.S.E Functions
EN54-4 Clause
Operation from a main power supply
Operation from a standby battery
Monitor and Charge the Standby Battery
Recognise and Notify Supply Faults
5.1
5.2
5.3
5.4
This Fire Alarm Control Panel also supports additional functions that are not covered
by EN54. These are as follows:
Additional Function
Refer to
Paragraphs
Auxiliary Power Supply Output
Auxiliary Relay Outputs
2.3.5.3
2.3.5.1
1.1.1
EN54 Optional Features with Requirements
In addition to the mandatory requirements of EN54-2, the Control and Indicating Equipment (CIE) supports the
following optional features with requirements: -
Section 7.8
Outputs to Fire Alarm Devices.
The CIE has provision for connection to Fire Alarm Devices. It is possible to Silence
and Re-sound the alarms at Level 2. Refer to the User Manual for further
information.
Refer to Sections 2.3.5.5 and 3.3.5 for information on installation and output
programming.
Section 7.11
Delays to Outputs.
The CIE has provision for delaying the activation of outputs in response to zone fire
conditions. These delays are programmable on a zone–by–zone basis.
Refer to Section 3.3.1 for information on delay programming.
Section 7.13
Alarm Counter.
The CIE has provision record the number of times that the fire alarm condition is
entered. Refer to the User Manual for further information.
Total Loss of Power.
The CIE has provision to annunciate a total loss of power for one hour. Refer to
Section 3.3.7 for information on configuring this option.
Conditions:
- Requires installation of 7Ah batteries
- The minimum battery operating voltage is 20.4V
- Output Power AUX2 must not be used for external equipment.
- Output Power AUX1 will be switched off when battery voltage is <20.4V
Section 10
Test Condition.
The CIE has provision for testing the installation on a per zone basis. Refer to the
User Manual for further information.
1.2 EN12094 Functions
This Control Panel is compliant with the requirements of EN12094-1: 2003 and
complies with the following mandatory functions:
Reception and processing of input trigger signals (zone inputs and manual trigger)
Transmission of the extinguishing signal (actuator output)
Output to alarm devices
Indication
Transmission of the fault warning and component status conditions
Transmission of the released condition
This control panel incorporates a manual triggering device in accordance with the
requirements of EN12094-3: 2003.
1.2.1
EN12094-1 Optional Features with Requirements
In addition to the mandatory requirements of EN12094-1, the Extinguishing Control Device (ECD) supports the
following optional features with requirements: -
Section 4.17
Delay of Extinguishing Signal.
The ECD has provision to delay the transmission of the extinguishing signal. This can
be programmed in 1-second intervals up to a maximum of 60-seconds. Refer to
Section 3.3.3.1 for programming.
Section 4.18
Monitor Flow of Extinguishing Agent.
The ECD has provision to monitor the flow of the extinguishing agent once released.
One fixed input is provided. Programmable inputs can also be configured as flow
inputs. Refer to Sections 2.3.5.6, 3.3.4 and 3.3.3.1.
Section 4.19
Monitor of Status of Extinguishing Components.
The ECD has the provision to monitor the status of extinguishing components such as
loss of agent, temperature, etc. Refer to Sections 2.3.5.6, 3.3.4 and 3.3.3.1.
Means shall be provided to transmit the information concerning the blocked position
of a manual control device. Refer to sections 2.3.5.1 and 3.3.5 for further information.
Emergency Hold Device.
The ECD has provision for an emergency hold device. Refer to Sections 2.3.5.6, 3.3.4
and 3.3.3.1.
Means shall be provided to transmit the information concerning the activation of an
emergency hold device. Refer to sections 2.3.5.1 and 3.3.5 for further information.
Section 4.21
Control of Flooding Time.
The ECD has provision to control the duration of the flooding time. Refer to Section
3.3.3.1 for programming.
Section 4.23
Manual Only Mode.
The ECD has provision to switch from Auto/Manual to Manual Only means of
establishing the extinguishing signal. This can be by Level 2 User Menu Option, fixed
input, programmable input or by Key-Switch Option. Refer to Sections 2.3.5.6, 3.3.4
and 3.3.3.1.
Section 4.24
Triggering Signals to Equipment within the System.
The ECD has provision to transmit triggering signals to extinguishing system
equipment such as pilot cylinders, warning devices, etc. Refer to Sections 2.3.5.5 and
3.3.5.
These circuits are required to be monitored for fault conditions by the ECD.
Section 4.26
Triggering Signals to Equipment outside the System.
The ECD has provision to transmit triggering signals to other equipment such as
doors, ventilation shut down, etc. Refer to Sections 2.3.5.1 and 3.3.5.
These circuits are to be monitored for fault conditions by the receiving device.
Section 4.27
Emergency Abort Device.
The ECD has provision for an emergency abort device. This can be by fixed input or
programmable input option. Refer to Sections 2.3.5.6, 3.3.4 and 3.3.3.1.
Means shall be provided to transmit the information concerning the activation of an
emergency abort device. Refer to sections 2.3.5.1 and 3.3.5 for further information.
Section 4.30
Activation of Alarm Devices with Different Signals.
The ECD has provision to activate sounding devices with different signals to indicate
the pre-discharge warning condition (pulsing, 1s/1s), the release condition
(continuous) and the hold condition (pulsing, 1s/4s). Refer to Sections 3.3.2.1 and
3.3.2.2. Three pulsing patterns can be defined.
1.3 Installation Approvals
1.3.1
Fire System Installations
The panel must be installed and configured for operation in accordance with these instructions and the
applicable code of practice or national standard regulations for fire systems / extinguishing system installation
(for example BS5839-1: 2002, BS7273-1: 2006) appropriate to the country and location of the installation.
1.3.2
Wiring Regulations
The panel and system must be installed in accordance with these instructions and the applicable wiring codes
and regulations (for example BS7671) appropriate to the country and location of the installation.
2.1 Identification of Parts
The following diagram shows the major parts of the panel.
LIVE
EARTH
NEUTRAL
U
S
B
S
U
P
P L
Y
P
S
U
C
o
m
m
s
P
R
O
G
R
U
N
u
P
M
O
D
E
R
E
B
O
O
T
R
e
l
a
y
-
1
F
I
R
E
R
e
l
a
y
R
e
l
a
y
-
2
F
A
U
L
T
R
e
l
a
y
R
S
4
8
5
A
U
X
S
u
p
p
l
y
Z
O
N
E
-
1
-
Z
O
N
E
-
2
-
Z
O
N
E
-
3
-
S
N
D
R
-
1
-
S
N
D
R
-
2
-
S
N
D
R
-
3
-
M
O
D
E
S
e
l
e
c
t
M
a
n
u
a
l
T
r
i
g
g
e
r
H
O
L
D A
B
O
R
T P
r
e
s
s
u
r
e
M
o
n
i
t
o
r
V
A
L
V
E
M
o
n
i
t
o
r
F
L
O
W
M
o
n
i
t
o
r
A
c
t
u
a
t
o
r
O
u
t
p
u
t
P
R
O
G
I
n
p
u
t
-
1
P
R
O
G
I
n
p
u
t
-
2
P
R
O
G
I
n
p
u
t
-
3
P
R
O
G
I
n
p
u
t
-
4
M
A
N
U
A L
O
N L
Y
A
U T
O
+
M
A N
U
A L
L
O
W
P R
E
S
S
U
R
E
M
A N
U
A
L
D
I S
A
B L
E
D
D
I S
A
B L
E
D
F
A
U L
T
T
I M
E
R
H
E
L
D
A
B
O
R
T
E
D
R
E
L
E
A
S
E
I M
M
I
N E
N T
R
E
L
E
A
S
E
D
E X T I N G U I S H A N T
P
O
W
E
R
S
Y
S
T
E
M
F
A
U L
T
T
E
S
T
S
O
U N
D E
R
D
E
L
A
Y
E
D
D
I S
A B
L
E
S
O
U
N D
E
R
D
I S
A
B L
E
D
F
A
U
L
T
S
O
U N
D
E
R
F
A
U L
T
F I R E
S
I L E
N
C
E
D
G E N E R A L
-
1
-
D E T E C T I O N
Z O N E S
F I R E
F A U L T /
T E S T /
D I S A B L E
-
2
-
-
3
-
E
S
C
M
E
N
U
W
X
Y
Z
T
U
V
P
Q
R
S
G
H
I
J
K
L
M
N
O
D
E
F
A
B
C
R E S E T
S I L E N C E /
R E S O U N D
M U T E
!
S O U N D
A L A R M S
(
H
O
L D
2 s
)
B S
E
N
5
4
- 2 :
1
9 9
8
B
S
E
N
5 4
- 4
:
1 9
9 8
B S
E
N
1
2
0 9
4 - 1
:
2 0
0
3
C
L
A S
S
-
A
E X T I N G U I S H A N T
R E L E A S E
P
U
L L
D
O
W
N
A
N
D
P R
E
S
S
B
U
T
T
O
N
DOOR
BACK BOX
CHASSIS
ASSEMBLY
AC INPUT
PSU MODULE
MANUAL RELEASE
COVER
RELAY MODULE
(OPTIONAL)
SLIDE-IN LABEL
The panel comprises a back box, door, chassis assembly and PSE module.
The chassis is mounted onto the back box via two screws and keyhole mounting holes. The screws do not have
to be removed to remove the chassis.
The chassis contains the main printed circuit card with terminal block connections for field wiring. A fascia label
is affixed to the front of the chassis providing the user controls and indications (LCD and LED indicators). A
hinged yellow plastic cover is fitted to the front face and provides access to the manual release button.
The PSE module converts the in-coming AC Supply to 24V DC (nominal) and provides battery charging. The
PSE is connected to the chassis via a DC Cable and a serial communications cable. The PSE design is to BS
EN54-4: 1998 +A2 and provides monitoring for AC failure, battery missing, battery low, charger failure and
battery high internal resistance.
Standoff pillars are provided in the back box to fit a standard Exp-008 8-Way Relay Module. This is connected
to the main printed circuit card via ribbon cable.
Up to two (programmable function) key-switch assemblies (Exp-001 & Exp-002) can be fitted to the chassis
plate below the manual release cover. The cables plug onto the main printed circuit card. Slide-in labels with
pre-printed text are available.
2.2 Installing the back box
Enclosure dimensions and fixing points are shown in the diagram below. Remove the chassis before installing
the enclosure (retain in a safe place).
LIVE
EARTH
NEUTRAL
400
160
160
26
275
330
90
When batteries are installed, the ExGo can weigh in excess of 10Kg. Use appropriate fixing hardware to secure
the panel to the wall.
For example, drill the required holes in the supporting wall using a drill bit diameter 7.0 mm and plug with a
suitable 40mm long expansion plug. Affix the panel to the wall with M5 screws (length 40mm) or No.10 screws
(length 1½”).
Ensure that there is sufficient space to allow the cover to be removed / opened when the panel is finally
mounted.
2.3 Wiring Installation
2.3.1
AC Mains Wiring
The power supply is classified as Class1
equipment construction and must be earthed in
accordance to EN60950 recommendations.
Route the high voltage mains AC wiring into the
enclosure using a suitable knockout and keeping
the AC wiring away from any circuit boards and all
other wiring.
The panel must be connected to the
supply earth through the power
cable.
The mains input connector is shown
in the diagram opposite. Note the
positions of the earth, neutral and
live terminal connections.
These are clearly marked on the label next to the
connector. The connector block contains an
integral fuse holder for a 20mm fuse.
Secure the mains input wiring using a tie wrap as
close to the terminal block as possible.
The fuse is rated as follows:
T 3.15A H 250V
Replace with correct rating and specification only.
FUSE
Brown
Grn/Yel
LIVE
EARTH
NEUTRAL
PSU Internal Mains
Wiring
Blue
Field Connections
AC Mains terminations
Connect the ExGo to the mains supply via a
readily accessible, disconnect device
(Isolation Switch) and suitable earth fault
protection incorporated in the building
installation wiring.
The Mains cable should be a minimum cable
size of 0.75mm² rated at 250V and fused via
a 5A anti-surge fuse. Maximum cable size is
limited to 4mm².
Keep all mains wiring separate from the
Extra Low Voltage (ELV) battery cables and
power supply output cables.
2.3.1.1 Cable Gland
The cable gland and any cord clamp bushings used in routing the Mains cable through
the 20mm knockout must have a minimum flame-retardant rating of 94HB.
Suggested glands and bushings are: -
Type
Gland IP65 – Brass M20, EExd / Eexe
Gland IP68 – Nylon 66 M20 Black, UL94V2
Bushing – Nylon 66 M20 Black, UL94V2
Manufacturer
Lappcable
Multicomp
Multipcomp
2.3.2
Battery Wiring
The system is designed to charge 24V
batteries or two 12V batteries connected in
series. Refer to diagram opposite.
Use the short black connection link to
connect the batteries.
Use the Red & Black leads provided to
connect the batteries to the BAT+ & BAT–
terminals on the PSE module.
Mount the batteries on the bottom of the
enclosure.
+V DC POWER
0V DC POWER
BATTERY +
BATTERY –
OBSERVE POLARITY OF CONNECTIONS!
Must be
earthed
24VDC Power Supply Wiring
The main printed circuit card on the chassis
is supplied with 24V DC from the power
supply.
In addition, the operating status of the power
supply is communicated to the main
electronics via a serial link.
The two cables are fitted as standard and
plug onto the main printed circuit card.
Refer to diagrams opposite.
+V DC POWER
0V DC POWER
BATTERY +
BATTERY –
COMMS LEAD
DC POWER LEAD
To remove the chassis assembly, disconnect
the two cable plugs from the chassis card
itself. There is no need to remove the wiring
from the power supply.
Note: If wired correctly, the DC Supply plug is
reversible without presenting a danger of
polarity reversal.
S
U
P
P
L
Y
P
S
U
C
o
m
m
s
a
y
-
1
F
I
R
E
R
e
l
a
y
R
e
l
a
y
-
2
F
A
U
L
T
R
e
l
a
y
R
S
4
8
5
A
U
X
S
u
p
p
l
y
Z
O
N
E
-
1
-
Z
O
N
E
-
2
-
Z
O
N
E
-
3
-
S
N
D
R
-
1
-
S
N
D
R
-
2
-
S
N
D
R
-
3
-
M
O
D
E
S
e
l
e
c
t
M
a
n
u
a
l
T
r
i
g
g
e
r
H
O
L
D
M
A
N
U
A L
O
N L
Y
L
O
W
M
A N
U
A
L
D
I S
A
B L
E
D
D
I
S
A
B
L
E
D
T
I
M
E
R
H
E
L
D
R
E
L
E
A
S
E
I M
M
I
N
E
N
T
E X T I N G U I S H
P
O
W
E
R
S
Y
S
T
E
M
F
A
U
L
T
T
E
S
T
S
O
U N
D E
R
D
E
L
A
Y
E
D
D
I S
A B
L
E
S
O
U
N D
E
R
D
I S
A
B L
E
D
F
A
U
L
T
S
O
U N
D
E
R
F
A
U
L
T
F I R E
S
I L E
N
C
E
D
G E N E R A L
-
1
-
D E T E C T I O N
Z
F I R E
-
2
-
-
3
-
E
S
C
M
E
N
U
W
X
Y
Z
T
U
V
P
Q
R
S
G
H
I
J
K
L
M
N
O
D
E
F
A
B
C
R E S E T
S I L E N C E /
R E S O U N D
M U T E
!
S O U N D
A L A R M S
(
H
O
L D
2 s
)
SERIAL COMMS
DC POWER
OBSERVE POLARITY OF CONNECTIONS!
2.3.4
PSE Configuration
The PSE module can be configured for
operation as a PSE + CHARGER or PSE
ONLY 3 (if battery standby is not required).
A pin header, J1, provides a means for
selecting this operation.
The panel is supplied with the PSE
configured for PSE + CHARGER mode of
operation.
Remote LED
Connections
NOT FITTED ON
1.5A PSE
PSE ONLY
PSE + CHARGER
Fit Jumper in required
location. The unit is
supplied as default set for
PSE + Charger Mode of
operation as shown.
2.3.5
External Wiring
General Notes
Install cables suitable for the application and
degree of fire protection required.
All input and output circuits are SELV type.
To maintain electrical integrity of the SELV
wiring on the output lines all SELV wiring
should be segregated from the LV mains
wiring and be wired using cable with
insulation suitable for the application.
NB: Minimum / Maximum cable size for all
connections is limited to 0.35mm² / 2.5mm²
(22-14AWG).
Any specific recommendations are detailed
below for each type of circuit.
Refer to the Recommended Wiring Routing
section for details of cable routing within the
enclosure.
All electrical wiring installation work should be
carried out in accordance with the code of
practice applicable in the country of installation.
To minimise the effects of EMC interference all
data wiring circuits should be wired with a twisted
pair of conductors with a cross sectional area
suitable for the loading conditions.
In areas where cabling may come into contact
with high frequency interference, such as
portable radio transceivers etc. the output wiring
cable should be of a twisted pair construction
within an overall screen. The screen should be
terminated to one of the dedicated earth studs /
bus bar available in the panel.
3 This configuration is not in accordance with the requirements of EN54-4. If configured for PSE ONLY, the panel will not report fault
conditions for battery missing, charger failure or battery high resistance.
2.3.5.1 Relay Outputs
Section 8.8
Fault Output.
The Fault Relay is arranged for failsafe operation as standard.
The panel is equipped with four relay outputs. See
diagram opposite for terminal block positions.
Each output is unsupervised with volt-free
changeover contacts rated at 30V AC/DC, 1A,
resistive.
The Fault and Fire Relays are fixed to indicate
their respective conditions.
The Fault relay is normally activated. It will de-
energise on any fault condition including total loss
of power.
Relay outputs 1&2 are programmable.
R
e
l
a
y
-
1
F
I
R
E
R
e
l
a
y
R
e
l
a
y
-
2
F
A
U
L
T
R
e
l
a
y
R
S
4
8
5
A
U
X
S
u
p
p
l
y
Z
O
N
E
-
1
-
Z
O
-
P
O
W
E
R
S
Y
S
T
E
M
F
A
U
L
T
T
E
S
T
S
O
U N
D E
R
D
E
L
A
Y
E
D
D
I S
A B
L
E
S
O
U
N D
E
R
D
I S
A
B L
E
D
F
A
U
L
T
S
O
U N
D
E
R
F
A
U
L
T
F I R E
S
I L E
N
C
E
D
G E N E R A L
R E
S I L
R E S
M U
!
S O
A L A
(
H
O
Additional Relays
If additional relays are required, then install the
Exp-008 8-Way Relay card in the rear of the
enclosure.
Mounting pillars are provided. Affix the card with
the supplied M3 fixing screws.
Connect the 10-Way ribbon cable between the
relay card and the main chassis card – the
connectors are polarised to prevent incorrect
connection.
Two changeover and six normally open volt-free
relay outputs are provided. Each is rated at 30V
AC/DC, 1A, resistive.
All Relay outputs are programmable.
RELAY
1
RELAY
2
RELAY
3
RELAY
4
RELAY
5
RELAY
6
RELAY
7
RELAY
8
COM NC NO COM NC NO
COM NO COM NO COM NO
COM NO COM NO COM NO
2.3.5.2 RS485 Communications
One RS485 bus circuit is provided for connection
of local peripheral devices such as Remote Status
Indicator panels.
SUPERVISED. POWER LIMITED.
CCITT RS485 – Style 4
Wiring to be twisted pair and screened.
Maximum distance 1000m. Maximum line
impedance 50Ω.
Connect the cable from 'A' to 'A' and from 'B' to 'B'.
Equipment is connected via a daisy chain. A 150Ω
End-of-Line resistor to be fitted at last unit.
Connect the screen to one of the earth studs / bus
bar in the back of the panel enclosure and to the
designated point in the remote status indicator
panels. Ensure the screen is continuous.
S
U
P
P
L
Y
P
S
U
C
o
m
m
s
R
e
l
a
y
-
1
F
I
R
E
R
e
l
a
y
R
e
l
a
y
-
2
F
A
U
L
T
R
e
l
a
y
R
S
4
8
5
A
U
X
S
u
p
p
l
y
Z
O
N
E
-
1
-
Z
O
N
E
-
2
-
Z
O
N
E
-
3
-
F I R E
S
I L E
N
C
E
D
G E N E R A L
R E S E T
A B
SCR B A
SCR B A
SCR B A
B A
SCR
150Ω
IN
OUT
IN
OUT
Remote
Status
Indicator
Remote
Status
Indicator
Extinguishing
Panel
RS485
AUX Supply
2.3.5.3 AUX DC Supply Output
Two Auxiliary Power Outputs are provided.
18.0 – 28.0 V DC, 0.5A 4 SUPERVISED. POWER
LIMITED.
AUX #1 : 4-Wire Smoke Detector Power or other
similar application. Power turns off for
4-5 seconds on reset and when EN54-
2 Clause 8.4 limit is reached.
AUX #2 : 24V DC (nominal) power output for
external equipment (remote status
indicators) 5.
Use appropriately sized cable for the current load
to ensure device compatibility.
S
U
P
P L
Y
P
S
U
C
o
m
m
s
R
e
l
a
y
-
1
F
I
R
E
R
e
l
a
y
R
e
l
a
y
-
2
F
A
U
L
T
R
e
l
a
y
R
S
4
8
5
A
U
X
S
u
p
p
l
y
Z
O
N
E
-
1
-
Z
O
N
E
-
2
-
Z
O
N
E
-
3
-
P
O
W
E
R
S
Y
S
T
E
M
F
A
U L
T
T
E
S
T
S
O
U N
D E
R
D
E
L
A
Y
E
D
D
I S
A B
L
E
S
O
U
N D
E
R
D
I S
A
B L
E
D
F
A
U
L
T
S
O
U N
D
E
R
F
A
U L
T
F I R E
S
I L E
N
C
E
D
G E N E R A L
E
S
C
T
U
V
P
Q
R
S
G
H
I
J
K
L
A
B
C
R E S E T
S I L E N C E /
R E S O U N D
M U T E
!
S O U N D
A L A R M S
(
H
O
L D
2 s
)
AUX-2 AUX-1
2.3.5.4 Detection Zone Inputs
Section 12.5.2
In accordance with EN54-2, a maximum of 32 detectors per zone only.
Three conventional detection zone inputs are
provided. These are nominally 20V DC circuits
and are current limited.
The circuits are monitored for open and short
circuits. For normal monitoring, a 6800Ω End-of-
Line resistor is required. Maximum line
impedance 32Ω.
The circuit is designed to be compliant with
conventional detectors and call points with an
equivalent series resistance of 470Ω or 270Ω.
S
U
P
P
L
Y
P
S
U
C
o
m
m
s
R
e
l
a
y
-
1
F
I
R
E
R
e
l
a
y
R
e
l
a
y
-
2
F
A
U
L
T
R
e
l
a
y
R
S
4
8
5
A
U
X
S
u
p
p
l
y
Z
O
N
E
-
1
-
Z
O
N
E
-
2
-
Z
O
N
E
-
3
-
P
O
W
E
R
S
Y
S
T
E
M
F
A
U
L
T
T
E
S
T
S
O
U N
D E
R
D
E
L
A
Y
E
D
D
I S
A B
L
E
S
O
U
N D
E
R
D
I S
A
B L
E
D
F
A
U
L
T
S
O
U N
D
E
R
F
A
U
L
T
F I R E
S
I L E
N
C
E
D
G E N E R A L
E
S
C
T
U
V
P
Q
R
S
G
H
I
J
K
L
A
B
C
R E S E T
S I L E N C E /
R E S O U N D
M U T E
!
S O U N D
A L A R M S
(
H
O
L D
2 s
)
If using devices that apply a short across the zone circuit, refer to Section 3.3.1 for how to configure this
use.
2.3.5.4.1 Standard Arrangement 6
Connect the detectors and manual call points (if
required) in series with no spurs.
Connect the end-of-line resistor across the
terminals of the last device.
OBSERVE POLARITY OF CONNECTIONS!
6800Ω
Zone-1 Zone-2 Zone-3
Detector
Detector
Call Point
2.3.5.4.2 Diode Base Arrangement 6
If the installation requires conformance to
BS5839-1: 2002 Code of Practice regarding the
supervision of removal of detectors and / or
operation of call points when detectors are
removed, then install the detectors using diode
bases.
An Active-End-of-Line device is required instead
of the 6800Ω resistor (Item Exp-006).
AEL
Zone-1 Zone-2 Zone-3
Detector
Detector
Call Point
4 TOTAL OUTPUT LOAD must not exceed panel supply rating – maximum 2A.
5 AUX-2 also provides power for the Exp-008 8-Way Relay card. This current must be subtracted from the total available AUX-2 power to
give the available output power. If EN54-2 Clause 8.4 function is enabled then, to ensure that the minimum buzzer alert time of 1 hour is
maintained, AUX2 should not be used to power external equipment.
6 The system has been tested for compliance with the circuit impedance monitoring requirements of EN54-13 using the standard EOL
resistor. No EN54-13 compliance is declared for the use of an Active End-of-Line (EXP-006).
2.3.5.4.3 Intrinsic Safe Arrangement 7
The Zone Circuit can be configured for use with
Intrinsic Safety detectors and barriers – see
programming section.
The recommended isolation barrier is a
PEPPERL+FUCHS Model: KFDO-CS-Ex1.51P or
MTL Model: 5061
Only use intrinsic safe detectors and call points.
The number of devices permitted and cables will
depend on the IS classification – refer to the
detector manufacturers’ information for further
details.
6800Ω
Zone-1 Zone-2 Zone-3
IS Detector
IS Detector
IS Call Point
SAFE AREA
HAZARDOUS AREA
11
12
1
2
Isolation
Barrier
+
–
The End-of-line resistor used must be rated for the
appropriate IS zone classification.
2.3.5.5 Sounder / Monitored Output Circuits
Three conventional 24V DC sounder style output
circuits are provided. 8
18.0 – 28.0 V DC, 1.0A 9 max
SUPERVISED. POWER LIMITED.
The sounder outputs can be configured to turn on
continuously or to pulse (1s ON / 1s OFF).
The sounder outputs are monitored for open and
short circuit conditions using reverse polarity
signals.
The outputs can be configured to be non-
silencing for use with pilot valves, etc. (refer to
section 0 for programming).
S
U
P
P
L
Y
P
S
U
C
o
m
m
s
F
A
U
L
T
R
e
l
a
y
R
S
4
8
5
A
U
X
S
u
p
p
l
y
Z
O
N
E
-
1
-
Z
O
N
E
-
2
-
Z
O
N
E
-
3
-
S
N
D
R
-
1
-
S
N
D
R
-
2
-
S
N
D
R
-
3
-
M
O
D
E
S
e
l
e
c
t
M
a
n
u
a
l
T
r
i
g
g
e
r
H
O
L
D A
B
O
R
T P
r
e
s
s
u
r
e
M
o
n
i
t
o
r
V
A
L
V
E
M
o
n
i
t
o
r
F
M
M
A
N
U
A L
O
N L
Y
A
U
T
O
+
M
A N
U
A
L
L
O
W
P
R
E
S
S
U
R
E
M
A N
U
A
L
D
I S
A
B L
E
D
D
I
S
A
B
L
E
D
F
A
U L
T
T
I
M
E
R
H
E
L
D
A
B
O
R
T
E
D
R
E
L
E
A
S
E
I M
M
I
N
E
N
T
R
E
L
E
A
S
E
D
E X T I N G U I S H A N T
S
Y
S
T
E
M
F
A
U
L
T
S
O
U N
D E
R
D
E
L
A
Y
E
D
S
O
U
N D
E
R
D
I S
A
B L
E
D
S
O
U N
D
E
R
F
A
U
L
T
S
I L E
N
C
E
D
E N E R A L
-
1
-
D E T E C T I O N
Z O N E S
F I R E
F A U L T /
T E S T /
D I S A B L E
-
2
-
-
3
-
E
S
C
M
E
N
U
W
X
Y
Z
T
U
V
P
Q
R
S
G
H
I
J
K
L
M
N
O
D
E
F
A
B
C
R E S E T
S I L E N C E /
R E S O U N D
M U T E
!
S O U N D
A L A R M S
(
H
O
L D
2 s
)
Sounders must be equipped with an in-built
blocking diode that prevents the sounder from
taking power when the output is in the
supervising condition.
An End-of-Line Resistor (EOLR) of value
10,000Ω ½ Watt must be fitted to the last
sounder / bell.
Ensure that cable of appropriate conductor size is
used to maintain the required sounder operating
voltage under the minimum battery voltage
condition – see below for calculation.
EOL
10k ohm
EOL
10k ohm
EOL
10k ohm
SDR-1 SRD-2 SDR-3
GENERAL FIRE ALARM
FLOODING ZONE ALARM
TYPICAL
2.3.5.5.1 Intrinsic Safe Arrangement
The Sounder Circuit can be configured for use
with Intrinsic Safety sounders and barriers.
The recommended isolation barrier is a MTL
Model: 778ac
Only use intrinsic safe sounders. The number of
devices permitted and cables will depend on the
IS classification – refer to the sounder
manufacturers’ information for further details.
EOL
10k ohm
SDR-1 SRD-2 SDR-3
+
–
Isolation
Barrier
+
–
IS Sounders - Polarised
SAFE AREA
HAZARDOUS AREA
7 Due to the isolation barrier internal resistance, intrinsic safe circuits are not monitored in accordance with the circuit impedance monitoring
requirements of EN54-13.
8 By default, SNDR1 & SNDR2 are for configured for general fire alarms. SND3 is dedicated to the extinguishant alarm (flooding zone)
output in accordance with EN12094-1.
9 TOTAL OUTPUT LOAD (continuous) must not exceed panel supply rating – maximum 2A.
2.3.5.5.2 EN54-13 Monitoring
The sounder outputs support monitoring with an Active EOL device to ensure circuit
integrity in accordance with the requirements of EN54-13.
The sounder circuits can be configured for
compliance with EN54-13 by programming
and the use of an Active EOL device. All
panel sounder outputs must be fitted with the
Active EOL device (Mxp-505)
The panel uses techniques to ensure that a
fault warning condition is reported if the circuit
resistance increases to a condition where the
voltage at the last device may fall below its
minimum operating voltage level. This is
compatible for load currents from minimum up
to maximum (1 ampere).
Install the Active EOL device at the end of the
sounder circuit instead of the normal EOL
resistor – this device is polarity sensitive.
Connect the Red lead to the sounder + signal
line.
+
-
Typical
Arrangement
Active
EOL
Typical Sounder Arrangement.
OBSERVE POLARITY
The Active EOL device is polarity
sensitive.
The Active EOL is fuse protected –
however, if connected incorrectly
and the sounder circuit is activated,
the fuse will open and is not user
replaceable.
2.3.5.5.3 Sounder Circuit Lengths
The voltage drop on each alarm circuit should be calculated to ensure that the minimum voltage at the end of
the circuit exceeds the minimum required by each sounding device at the minimum alarm circuit output voltage.
The voltage at the end of the circuit is given by:
Minimum Alarm Voltage = VOUT(MIN) – (IALARM x RCABLE)
Minimum Output Voltage (VOUT(MIN)) is VBAT(MIN) – 1.0V = 20.0V
Alarm Current (IALARM) is the sum of the loads presented by the sounding devices in alarm.
Cable Resistance (RCABLE) is the sum of the cable resistance in both cores x cable length.
Cable Resistance (RCABLE) for 1.0mm2 is 0.036Ω / metre
Cable Resistance (RCABLE) for 1.5mm2 is 0.024Ω / metre
Cable Resistance (RCABLE) for 2.5mm2 is 0.015Ω / metre
Insulation Resistance (Core-Core and Core-Screen)
2M Ω
2.3.5.6 Input Circuits
Seven Fixed function Input circuits are provided for
the following functions:
MODE SELECT [Auto / Manual], MANUAL TRIGGER, HOLD,
ABORT, PRESSURE MONITOR, VALVE MONITOR and FLOW
MONITOR.
Four Programmable Function Input Circuits are
provided. Each input circuit is monitored for open
and short circuit conditions – see typical
arrangement below.
EOL = 6800Ω. Maximum line impedance 50Ω.
Connect to volt-free switches / relay contacts only.
S
U
P
P L
Y
P
S
U
C
o
m
m
s
8
5
A
U
X
S
u
p
p
l
y
Z
O
N
E
-
1
-
Z
O
N
E
-
2
-
Z
O
N
E
-
3
-
S
N
D
R
-
1
-
S
N
D
R
-
2
-
S
N
D
R
-
3
-
M
O
D
E
S
e
l
e
c
t
M
a
n
u
a
l
T
r
i
g
g
e
r
H
O
L
D A
B
O
R
T P
r
e
s
s
u
r
e
M
o
n
i
t
o
r
V
A
L
V
E
M
o
n
i
t
o
r
F
L
O
W
M
o
n
i
t
o
r
A
c
t
u
a
t
o
r
O
u
t
p
u
t
P
R
O
G
I
n
p
u
t
-
1
P
R
O
G
I
n
p
u
t
-
2
P
R
O
G
I
n
p
u
t
-
3
P
R
O
G
I
n
p
u
t
-
4
M
A
N
U
A L
O
N L
Y
A
U T
O
+
M
A N
U
A L
L
O
W
P R
E
S
S
U
R
E
M
A N
U
A
L
D
I S
A
B L
E
D
D
I S
A
B L
E
D
F
A
U L
T
T
I M
E
R
H
E
L
D
A
B
O
R
T
E
D
R
E
L
E
A
S
E
I M
M
I
N E
N T
R
E
L
E
A
S
E
D
E X T I N G U I S H A N T
A
U L
T
A
Y
E
D
B L
E
D
A
U L
T
N
C
E
D
-
1
-
D E T E C T I O N
Z O N E S
F I R E
F A U L T /
T E S T /
D I S A B L E
-
2
-
-
3
-
E
S
C
M
E
N
U
W
X
Y
Z
T
U
V
P
Q
R
S
G
H
I
J
K
L
M
N
O
D
E
F
A
B
C
R E S E T
S I L E N C E /
R E S O U N D
M U T E
!
S O U N D
A L A R M S
(
H
O
L D
2 s
)
B S
E
N
5
4
- 2 :
1
9 9
8
B
S
E
N
5 4
- 4
:
1 9
B S
E
N
1
2
0 9
4 - 1
:
2 0
0
3
C
L
A S
S
E X T I N G U I S H A N T
R E L E A S E
P
U
L L
D
O
W
N
A
N
D
P R
E
S
S
B
U
T
T
O
6K8
470R
TYPICAL SWITCH
ARRANGEMENT
U
S
B
S
U
P
P L
Y
P
R
O
G
R
U
N
u
P
M
O
D
E
R
E
B
O
O
T
S
N
D
R
-
1
-
S
N
D
R
-
2
-
S
N
D
R
-
3
-
M
O
D
E
S
e
l
e
c
t
M
a
n
u
a
l
T
r
i
g
g
e
r
H
O
L
D A
B
O
R
T P
r
e
s
s
u
r
e
M
o
n
i
t
o
r
V
A
L
V
E
M
o
n
i
t
o
r
F
L
O
W
M
o
n
i
t
o
r
A
c
t
u
a
t
o
r
O
u
t
p
u
t
P
R
O
G
I
n
p
u
t
-
1
P
R
O
G
I
n
p
u
t
-
2
P
R
O
G
I
n
p
u
t
-
3
P
R
O
G
I
n
p
u
t
-
4
M
A
N
U
A L
O
N L
Y
A
U T
O
+
M
A N
U
A L
L
O
W
P R
E
S
S
U
R
E
M
A N
U
A
L
D
I S
A
B L
E
D
D
I S
A
B L
E
D
F
A
U L
T
T
I M
E
R
H
E
L
D
A
B
O
R
T
E
D
R
E
L
E
A
S
E
I M
M
I
N E
N T
R
E
L
E
A
S
E
D
E X T I N G U I S H A N T
-
1
-
D E T E C T I O N
Z O N E S
F I R E
F A U L T /
T E S T /
D I S A B L E
-
2
-
-
3
-
S
C
M
E
N
U
W
X
Y
Z
T
U
V
R
S
H
I
J
K
L
M
N
O
D
E
F
A
B
C
B S
E
N
5
4
- 2 :
1
9 9
8
B
S
E
N
5 4
- 4
:
1 9
9 8
B S
E
N
1
2
0 9
4 - 1
:
2 0
0
3
C
L
A S
S
-
A
E X T I N G U I S H A N T
R E L E A S E
P
U
L L
D
O
W
N
A
N
D
P R
E
S
S
B
U
T
T
O
N
6K8
6K8
470R
VALVE FULLY OPEN (NORMAL)
VALVE FULLY CLOSED
VALVE MONITOR SWITCH
ARRANGEMENT
The VALVE MONITOR input is used to monitor
the open / closed state of a mechanical valve
control device.
If the valve is in an indeterminate state (neither
fully open nor fully closed) for more than 30
seconds, the panel will indicate a fault
condition.
If unused, connect a 3300Ω (or 2x 6800Ω in
parallel) EOL across the terminals.
An end-of-line module (Exp-005) is
available to simplify the wiring. This
incorporates the end-of-line resistor and
the activation resistors – see opposite.
470 ohm
Not used
Common
Break off TAB to remove 6800 ohm
end-of-line resistor
Exp-005
470 ohm
6800 ohm
Common
Break off TAB to remove 6800 ohm
end-of-line resistor
Exp-005
2.3.5.7 Actuator Output Circuit
The actuator output can be used to drive both
igniting (metron) style and solenoid style
actuators.
18.0 – 28.0 V DC, 1.0A10
SUPERVISED. POWER LIMITED.
The circuit is monitored for both open and short
circuit conditions.
The output can supply a continuous 1A current for
solenoid style actuators or can provide a 3A
(15mS) pulse for igniting style actuators.
Output type is configurable - refer to Programming
section.
U
S
B
S
U
P
P L
Y
P
S
U
C
o
m
m
s
N
E
-
Z
O
N
E
-
3
-
S
N
D
R
-
1
-
S
N
D
R
-
2
-
S
N
D
R
-
3
-
M
O
D
E
S
e
l
e
c
t
M
a
n
u
a
l
T
r
i
g
g
e
r
H
O
L
D A
B
O
R
T P
r
e
s
s
u
r
e
M
o
n
i
t
o
r
V
A
L
V
E
M
o
n
i
t
o
r
F
L
O
W
M
o
n
i
t
o
r
A
c
t
u
a
t
o
r
O
u
t
p
u
t
P
R
O
G
I
n
p
u
t
-
1
P
R
O
G
I
n
p
u
t
-
2
P
R
O
G
I
n
p
u
t
-
3
P
R
O
G
I
n
p
u
t
-
4
-
1
-
D E T E C T I O N
Z O N E S
F I R E
F A U L T /
T E S T /
D I S A B L E
-
2
-
-
3
-
E X T I N G U I S H A N T
R E L E A S E
P
U
L L
D
O
W
N
A
N
D
P R
E
S
S
B
U
T
T
O
N
10 TOTAL OUTPUT LOAD (continuous) must not exceed panel supply rating – maximum 2A.
2.3.5.7.1 Igniting Actuators
The circuit is current limited and one to four
igniting actuators can be wired in series without
special requirements.
No additional resistance is required in the circuit
Maximum line impedance 7Ω including the internal
resistance of the actuators.
Up to 4 igniting
actuators in series
M
M
M
M
2.3.5.7.2 Solenoid Actuators
A Back-EMF diode must be fitted across the
solenoid coil. Observe polarity – see diagram
opposite.
Coil resistance 25Ω-200Ω.
Maximum line impedance 1.5Ω -5.0Ω depending
on coil impedance – see calculation below.
Two solenoids can be connected in parallel. The
panel will learn the combined circuit impedance
and will indicate an open circuit condition if one of
the actuators becomes disconnected.
SOLENOID
MIN 30Ω
DIODE 1N4004 or
equivalent
2.3.5.7.3 Solenoid Actuator Circuit Lengths
The voltage drop on the actuator circuit should be calculated to ensure that the minimum voltage at the end of
the circuit exceeds the minimum required by the solenoid (typically 18V) at the minimum actuator circuit output
voltage.
The voltage at the end of the circuit is given by:
Minimum Actuator Voltage = VOUT(MIN) – (IACTUATOR x RCABLE)
Minimum Output Voltage (VOUT(MIN)) is VBAT(MIN) – 1.5V = 19.5V
Actuator Current (IACTUATOR) is the sum of the loads presented by the actuator devices.
Cable Resistance (RCABLE) is the sum of the cable resistance in both cores x cable length.
Cable Resistance (RCABLE) for 1.0mm2 is 0.036Ω / metre
Cable Resistance (RCABLE) for 1.5mm2 is 0.024Ω / metre
Cable Resistance (RCABLE) for 2.5mm2 is 0.015Ω / metre
Insulation Resistance
(Core-Core and Core-
Screen)
2M Ω
2.3.5.8 USB
The USB socket is for connection to a Laptop or
PC.
This can be used for upload of a new logo or
download of the configuration and log files.
Refer to section 3.3.9 for further information.
U
S
B
S
U
P
P L
Y
P
R
O
G
R
U
N
u
P
M
O
D
E
R
E
B
O
O
T
S
N
D
R
-
1
-
S
N
D
R
-
2
-
S
N
D
R
-
3
-
M
O
D
E
S
e
l
e
c
t
M
a
n
u
a
l
T
r
i
g
g
e
r
H
O
L
D A
B
O
R
T P
r
e
s
s
u
r
e
M
o
n
i
t
o
r
V
A
L
V
E
M
o
n
i
t
o
r
F
L
O
W
M
o
n
i
t
o
r
A
c
t
u
a
t
o
r
O
u
t
p
u
t
P
R
O
G
I
n
p
u
t
-
1
P
R
O
G
I
n
p
u
t
-
2
P
R
O
G
I
n
p
u
t
-
3
P
R
O
G
I
n
p
u
t
-
4
-
1
-
D E T E C T I O N
Z O N E S
-
2
-
2.3.5.9 Recommended Cable Routing
The following diagram shows the recommended cable routing within the enclosure.
LIVE
EARTH
NEUTRAL
U
S
B
S
U
P
P L
Y
P
S
U
C
o
m
m
s
P
R
O
G
R
U
N
u
P
M
O
D
E
R
E
B
O
O
T
R
e
l
a
y
-
1
F
I
R
E
R
e
l
a
y
R
e
l
a
y
-
2
F
A
U
L
T
R
e
l
a
y
R
S
4
8
5
A
U
X
S
u
p
p
l
y
Z
O
N
E
-
1
-
Z
O
N
E
-
2
-
Z
O
N
E
-
3
-
S
N
D
R
-
1
-
S
N
D
R
-
2
-
S
N
D
R
-
3
-
M
O
D
E
S
e
l
e
c
t
M
a
n
u
a
l
T
r
i
g
g
e
r
H
O
L
D A
B
O
R
T P
r
e
s
s
u
r
e
M
o
n
i
t
o
r
V
A
L
V
E
M
o
n
i
t
o
r
F
L
O
W
M
o
n
i
t
o
r
A
c
t
u
a
t
o
r
O
u
t
p
u
t
P
R
O
G
I
n
p
u
t
-
1
P
R
O
G
I
n
p
u
t
-
2
P
R
O
G
I
n
p
u
t
-
3
P
R
O
G
I
n
p
u
t
-
4
M
A
N
U
A
L
O
N
L
Y
A
U T
O
+
M
A
N
U
A L
L
O
W
P R
E
S
S
U
R
E
M
A
N
U
A
L
D
I
S
A
B
L
E
D
D
I S
A
B L
E
D
F
A
U
L
T
T
I M
E
R
H
E
L
D
A
B
O
R
T
E
D
R
E
L
E
A
S
E
I
M
M
I
N E
N T
R
E
L
E
A
S
E
D
E X T I N G U I S H A N T
P
O
W
E
R
S
Y
S
T
E
M
F
A
U L
T
T
E
S
T
S
O
U
N
D
E
R
D
E
L
A
Y
E
D
D
I S
A
B
L
E
S
O
U
N
D
E
R
D
I
S
A
B
L
E
D
F
A
U
L
T
S
O
U N
D
E
R
F
A
U L
T
F I R E
S
I
L E
N
C
E
D
G E N E R A L
-
1
-
D E T E C T I O N
Z O N E S
F I R E
F A U L T /
T E S T /
D I S A B L E
-
2
-
-
3
-
E
S
C
M
E
N
U
W
X
Y
Z
T
U
V
P
Q
R
S
G
H
I
J
K
L
M
N
O
D
E
F
A
B
C
R E S E T
S I L E N C E /
R E S O U N D
M U T E
!
S O U N D
A L A R M S
(
H
O
L
D
2 s
)
B S
E
N
5
4
-
2
:
1
9
9
8
B
S
E
N
5 4
-
4
:
1
9
9
8
B S
E
N
1
2
0
9
4 - 1
:
2 0
0
3
C
L
A
S
S
-
A
E X T I N G U I S H A N T
R E L E A S E
P
U
L L
D
O
W
N
A
N
D
P R
E
S
S
B
U
T
T
O
N
AC INPUT
Cable Tie
AC IN
Relays
485 / AUX
Zone Inputs
Sounder Outputs
Inputs
Actuator
Output
2.4 Key-Switch Installation
Key-Switch Assembly
Nut
PL4: KEY-SW #1
PL3: KEY-SW #2
O
D
E
R
E
B
O
O
T
R
e
l
a
y
-
1
F
I
R
E
R
e
l
a
y
R
e
l
a
y
-
2
F
A
U
L
T
R
e
l
a
y R
S
4
8
5
A
U
X
S
u
p
p
l
y
Z
O
N
E
-
1
- Z
O
U S B
P
R
O
G
R
U
N
u P
M
H
O
L
D
A
B
O
R
T
P
r
e
s
s
u
r
e
M
o
n
i
t
o
r
V
A
L
V
E
M
o
n
i
t
o
r
F
L
O
W
M
o
n
i
t
o
r
A
c
t
u
a
t
o
r
O
u
t
p
u
t
P
R
O
G
I
n
p
u
t
-
1 P
R
O
G
I
n
p
u
t
-
2 P
R
O
G
I
n
p
u
t
-
3 P
R
O
G
I
n
p
u
t
-
4
B
S
E
N
5
4
-
2
:
1
9
9
8
B
S
E
N
5
4
-
4
:
1
9
9
8
B
S
E
N
1
2
0
9
4
-
1
:
2
0
0
3
C
L
A
S
S
-
A
S
U
P
P
L
Y
P S U
C o m m s
N
E
-
2
- Z
O
N
E
-
3
-
S
N
D
R
-
1
- S
N
D
R
-
2
- S
N
D
R
-
3
- M
O
D
E
S
e
l
e
c
t
M
a
n
u
a
l
T
r
i
g
g
e
r
M A N U A L O N L Y
A U T O +
M A N U A L
VALVE CLOSED
M
A
N
U
A
L
D
I
S
A
B
L
E
D
D
I
S
A
B
L
E
D
F
A
U
L
T
T
I
M
E
R
H
E
L
D
A
B
O
R
T
E
D
R
E
L
E
A
S
E
I
M
M
I
N
E
N
T
R
E
L
E
A
S
E
D
E
X
T
I
N
G
U
I
S
H
A
N
T
P
O
W
E
R
S
Y
S
T
E
M
F
A
U
L
T
T
E
S
T
S
O
U
N
D
E
R
D
E
L
A
Y
E
D
D
I
S
A
B
L
E S
O
U
N
D
E
R
D
I
S
A
B
L
E
D
F
A
U
L
T
S
O
U
N
D
E
R
F
A
U
L
T
F
I
R
E
S
I
L
E
N
C
E
D
G
E
N
E
R
A
L
-
1
-
D
E
T
E
C
T
I
O
N
Z
O
N
E
S
F
I
R
E
F
A
U
L
T
/
T
E
S
T
/
D
I
S
A
B
L
E
-
2
-
-
3
-
E
S
C
M
E
N
U
W
X
Y
Z
T
U
V
P
Q
R
S
G
H
I
J
K
L
M
N
O
D
E
F
A
B
C
R E S E T
S I L E N C E
M U T E
!
SILENCE /
SOUND
ALARMS
E
X
T
I
N
G
U
I
S
H
A
N
T
R
E
L
E
A
S
E
P
U
L
L
D
O
W
N
A
N
D
P
R
E
S
S
B
U
T
T
O
N
PL3
PL4
SLIDE-IN LABEL
Using a sharp knife, cut through the fascia label using the key-switch mounting hole as a template.
Insert the key-switch assembly through the hole and secure with the fixing nut. Before fully tightening, insert the
slide-in label with the required function description into the pocket in the fascia label.
Plug the connector into the respective connector on the card.
Key-Switch assemblies are available in both trapped (Exp-001) and non-trapped (Exp-002) versions.
Refer to the Programming section to define the action of the key-switch.
2.5 Adjusting the LCD Contrast
Press the CONTRAST ADJUST button. This display will show the contrast adjust option.
Use the buttons to adjust the contrast (viewing angle) darker
or lighter as required. The bar graph adjusts to show the contrast
setting.
Press the button to confirm the setting.
The display will then revert to the normal operating display.
2.6 Loading Calculations
2.6.1 Panel Loading
The Total Panel Load must not exceed the rating of the power supply. The power supply can deliver a 2A total
load maximum.
The panel loading includes the panel itself (70/125mA), any power required for additional option modules and all
external power required for the Input, Output and AUX circuits.
The backlight is turned off during AC supply failure (after 60 seconds). It turns on in Alarm or if the panel keys
are pressed.
2.6.2 Battery Standby Calculation
Quiescent Load
Fire Alarm Load
Equipment
I (A)
x
Total
I (A)
x
Total
EX-3001 Panel
0.07011
1.0
= 0.070
0.12512
1.0
= 0.125
Exp-008
0.000
1.0
=
0.06513
1.0
=
AUX #1 Supply Output14
1.0
=
1.0
=
AUX #2 Supply Output14
1.0
=
1.0
=
Sounder Output 115
1.0
=
Sounder Output 215
1.0
=
Sounder Output 315
1.0
=
Actuator Output
1.0
=
Total
Quiescent Load
=
Alarm Load
=
x 24 hr =
Ahr
x 72 hr =
Ahr
216 x 0.5 hr =
Ahr
(carry forward) +
Ahr
Total Load (Quiescent + Alarm) =
Ahr
x 1.2516 (Battery De-rating factor) =
Ahr
11 Figure quoted is for mains fail condition (backlight off) – add 15mA for first hour of fault when the backlight is on.
12 Figure quoted is for fire in mains fail condition – with Relay1, Relay 2 & Fire relay energised (backlight on).
13 Figure quoted is for all relays on. 8mA per relay output on.
14 Maximum 0.5A load per AUX. Calculate the required load for each auxiliary output in both the quiescent and alarm conditions. Refer to
the technical information for each device that is to be powered from the panel AUX Output to determine the overall AUX loading currents.
The sum of all these additional currents should be entered in these fields.
15 Maximum 1.0A load per Sounder.
16 The alarm load should be doubled to allow for changes in battery efficiency for loads in excess of the recommended C/20 discharge rate.
The total load calculated should be multiplied by a de-rating factor of 1.25 to allow for changes in battery efficiency over time. The above
calculation is in accordance with the recommendations in BS5839-1: 2002.
These instructions cover the configuration and programming of the panels.
NOTE: The panel is delivered in a non-configured condition. In this mode (or if the panel is
returned to factory default settings) the panel defaults to MANUAL ONLY mode of operation.
After configuring the panel, use the Level 2 EXTINGUISH MODES menu option (or the
configured key-switch / inputs) to set the panel into the AUTO+MANUAL mode.
3.1.1 Access Levels
The panel operation is protected from inadvertent and erroneous misuse by means of four access levels. These
levels are as follows:
Level 1 Untrained user
Level 2 Authorised User
Level 3 Commissioning, Service and Maintenance
Level 4 Commissioning, Service and Maintenance – Special Tools Required
This document covers the Level 3 functions. For details on the operation and use of the panel at Levels 1 & 2,
refer to User Manual 680-148. Full details are supplied with any special tools.
A level-3 password is required to enter the commissioning menus. For details of Passwords, refer to Section
3.3.6.
Level-3 Passwords.
If this number is lost, it is not possible to enter commission mode functions.
Refer to 5.1 for further information.
3.1.2 Front Panel Controls and Indications
Key-Switch Assembly
(Optional)
U
S
B
S
U
P
P
L
Y
P
S
U
C
o
m
m
s
P
R
O
G
R
U
N
u
P
M
O
D
E
R
E
B
O
O
T
R
e
l
a
y
-
1
F
I
R
E
R
e
l
a
y
R
e
l
a
y
-
2
F
A
U
L
T
R
e
l
a
y R
S
4
8
5
A
U
X
S
u
p
p
l
y
Z
O
N
E
-
1
- Z
O
N
E
-
2
- Z
O
N
E
-
3
-
S
N
D
R
-
1
- S
N
D
R
-
2
- S
N
D
R
-
3
- M
O
D
E
S
e
l
e
c
t
M
a
n
u
a
l
T
r
i
g
g
e
r
H
O
L
D
A
B
O
R
T
P
r
e
s
s
u
r
e
M
o
n
i
t
o
r
V
A
L
V
E
M
o
n
i
t
o
r
F
L
O
W
M
o
n
i
t
o
r
A
c
t
u
a
t
o
r
O
u
t
p
u
t
P
R
O
G
I
n
p
u
t
-
1 P
R
O
G
I
n
p
u
t
-
2 P
R
O
G
I
n
p
u
t
-
3 P
R
O
G
I
n
p
u
t
-
4
M
A
N
U
A
L
O
N
L
Y
A
U
T O
+
M
A
N U
A
L
V A LV E
C L O S E D
M
A
N
U
A
L
D
I
S
A
B
L
E
D
D
I
S
A
B
L
E
D
F
A
U
L
T
T
I
M
E
R
H
E
L
D
A
B
O
R
T
E
D
R
E
L
E
A
S
E
I
M
M
I
N
E
N
T
R
E
L
E
A
S
E
D
E
X
T
I
N
G
U
I
S
H
A
N
T
P
O
W
E
R
S
Y
S
T
E
M
F
A
U
L
T
T
E
S
T
S
O
U
N
D
E
R
D
E
L
A
Y
E
D
D
I
S
A
B
L
E S
O
U
N
D
E
R
D
I
S
A
B
L
E
D
F
A
U
L
T
S
O
U
N
D
E
R
F
A
U
L
T
F
I
R
E
S
I
L
E
N
C
E
D
G
E
N
E
R
A
L
-
1
-
D E T E C T
I O N
Z O N E S
F I R E
F
A
U
L
T
/
T
E
S
T
/
D
I
S
A
B
L
E
-
2
-
-
3
-
E
S
C
M
E
N
U
W
X
Y
Z
T
U
V
P
Q
R
S
G
H
I
J
K
L
M
N
O
D
E
F
A
B
C
R E S E T
S I L E N C E
M U T E
!
RESOUND /
SOUND
ALARMS
B
S
E
N
5
4
-
2
:
1
9
9
8
B
S
E
N
5
4
-
4
:
1
9
9
8
B
S
E
N
1
2
0
9
4
-
1
:
2
0
0
3
C
L
A
S
S
-
A
E
X
T
I
N
G
U
I
S
H
A
N
T
R
E
L
E
A
S
E
P
U
L
L
D
O
W
N
A
N
D
P
R
E
S
S
B
U
T
T
O
N
Extinguishant Status
Number Buttons
Control Buttons
General Status
LCD
Navigation Buttons
Detection Zone Status
Manual Release Button
The LCD along with the LED Indicators shows the operating status of the system. Examples of the information
presented are shown below:
Typical Menu Display
SYSTEM NORMAL
22 AUG 2007 16:39:00
[System status]
1 of 1 conditions:
DETECTION ZONE3
OPEN CIRCUIT
[Level 2 Menu]
VIEW .
TEST
EXTINGUISH MODES
DISABLE/ENABLE
EXIT LEVEL 2
[Release status]
UNAFFECTED
Release Imminent
Release Activated
Release Complete
[Release status]
RELEASE IMMINENT..
-15
RELEASE ACTIVATED
5 Seconds Elapsed
RELEASE ACTIVATED
24 Seconds Elapsed
DISCHARGE COMPLETE
(No Flow Detected)
RESET ALLOWED
The display shows a countdown
timer with the amount of time
remaining before the extinguishant
is released.
3.1.3 Enable Controls
Controls are normally disabled. To access the menus, press the Menu button. The display shows the following:
[CONTROLS DISABLED]
ENABLE CONTROLS
VIEW
LED TEST
Enter Your Password
Enter Your Password
**
Press the button to select the
‘Enable Controls’ option.
The display prompts for entry of
the password.
Enter the password. As each
number is pressed, an * character
is displayed. Finally, press the
button to confirm.
[Level 2 Menu]
VIEW .
TEST
EXTINGHUISH MODES
DISABLE/ENABLE
EXIT LEVEL 2
Enter Your Password
Not Recognized!
[Level 2 Menu]
EXTINGHUISH MODES
DISABLE/ENABLE
EXIT LEVEL 2
DATE/ TIME
COMMISSION .
The display then shows the Level 2
Menu options.
If the password is incorrect (or if
not entered in time) the above
message is shown.
Scroll down to the Commission
Menu
3.1.4 Navigating through menus
When a menu is displayed, use the buttons to highlight the required menu option and then press the
button to select it.
Press the ‘Esc’ button from within a menu option to return to the previous menu.
The display will revert to the status mode display after 60 seconds on no activity (15 seconds in a fire alarm
condition). Press the Menu button again to return to the menu option. A programmable timer can be configured
to automatically cancel Level 2 access.
3.1.5 Numeric data entry
Numbers are entered by moving to the required field, and then typing in the required number, followed by the
button. The display returns to the previous menu.
If the number is entered incorrectly, press the button to clear the entry and then re-enter the required
number. Alternatively, press the ‘Esc’ button to cancel the number entry and return to the previous menu.
3.2 Recommended Programming Procedure
It is recommended that the configurable options be programmed in the following sequence:
Configure General Options and Passwords
Configure the Extinguishing Output Type and Cause & Effect Rule
Configure the Detection Zone Input Circuits
Configure the Alarm Outputs and Cause & Effect Rule
Configure any other Input / Output Circuits
3.3 Level 3 Menu Functions
The following table gives a list of the Level 3 Menu Functions and a brief description for each function.
Menu Option
Sub Menu
Comments / Description
3
DETECTION
ZONE 1
ZONE 2
ZONE 3
Configuration of the Detection Zone Input Circuits
4
ALARM OUTPUTS
SOUNDER 1
SOUNDER 2
SOUNDER 3
PULSE PATTERN
Configuration of the Alarm Sounder Output Circuits and
pulsing operation
2
EXTINGUISHING
OUTPUT SET-UP
Configuration of the Actuator Output Circuit
CAUSE & EFFECT
Configuration of the release cause and effects rule
EXTRACT SET-UP
Configuration of the Extract Output
5
INPUTS
Configuration of the Programmable Input Circuits
5
OUTPUTS
Configuration of the Programmable Output (Relay) Circuits
1
PASSWORDS
Configuration of the Engineer and User Passwords
1
GENERAL
Configuration of General parameters
5
STATUS INDICATORS
Configuration of any Remote Status Indicator Panels
ENABLE P.C. LINK
Permits the connection of a PC for upload of a logo or
download of the configuration and log files.
EXIT
Leave the Commission Menu
To enter the Commissioning / Programming Menu, select the COMMISSION option in the Level 2 Menu and
press the button. The display prompts for the Level 3 password.
To exit from the Commissioning / Programming Menu, select the EXIT option and press the button. The
display prompts for the Level 3 password.
3.3.1 Detection Zones
This menu configures each of the three detection zone input circuits. Highlight the DETECTION option and
press the button. The following Zone Select Menu will be shown.
[Zone Select]
ZONE 1 .
ZONE 2
ZONE 3
LEARN ZONE LOADS
(loads learned)
Use the buttons to highlight the required zone and
then press the button to select it.
A menu of parameters is then presented for the selected
zone.
Select the Learn Zone Load option and follow instructions
to maximise zone sensitivity to open-circuit conditions.
Note that the Learn Zone Load process must only be performed when all detection zones are in their normal
operating state. The process should be repeated whenever any changes to the zone configuration are made.
The presence of the “(loads learned)” text indicates that the process has been compled successfully.
The Learn Zone Load process must be completed to ensure that the system complies fully
with the requirements of EN54-13.
[Zone 1 Settings]
SNDR DELAY : 0 .
VERIFY TIME : 0
I.S. ZONE : NO
SHORT=ALARM : NO
NON-LATCH : NO
Use the buttons to highlight the required parameter
and then press the button to select / change it.
The table below details the parameters can be adjusted:
Parameter
Comments / Description
Options
Default
Setting
SNDR DELAY
Determines if the sounders are to be delayed before operating
when the panel detects a fire alarm from this zone.
0 – 600 seconds
0
VERIFY TIME
Determines the minimum time that the circuit must be in the
alarm condition before an alarm condition is registered.
0 – 30 Seconds 17
0
I.S. ZONE?
Determines whether the circuit is for use with Intrinsic Safety
Barriers.
NO / YES
NO
SHORT=ALARM?
Determines if a short circuit is to be treated as an alarm
condition. If selected, the short circuit supervision on this circuit
is disabled. Normally, AFD or MCP devices will switch the circuit
into the alarm state via a 270Ω-470Ω resistor / equivalent load.
NO / YES18
NO
NON-LATCH?
Determines if the panel should automatically reset from the
alarm condition if the alarm is cleared.
NO / YES19
NO
3.3.2 Alarms
SNDR3 is dedicated to the flooding zone (protected area) sounders and is part of the ECD. SNDR1 & SNDR2
are general fire alarm sounders.
17 Settings in excess of 9 seconds are not in accordance with BS EN 54-2: 1998.
18 This Setting is not in accordance with BS EN 54-2:1998.
19 This setting is not in accordance with BS EN 54-2: 1998.
This menu configures each of the three alarm output circuits. Highlight the ALARM OUTPUTS option and press
the button. The following Sounder Select Menu will be shown.
[Sounder Select]
Sounder-1 (Fire) .
Sounder-2 (Fire)
Sounder-3 (Gas)
PULSE PATTERN
Use the buttons to highlight the required sounder (or
the pulse pattern option) and then press the button to
select it.
A menu of parameters is presented for the selected
sounder.
3.3.2.1 Sounder Configuration
[Zone 1 Settings]
ZONE1 FIRE: ON .
ZONE2 FIRE: ON
ZONE3 FIRE: ON
STAGE-1 : ON
COUNTDOWN : ON
Use the buttons to highlight the required parameter
and then press the button to select / change it.
The table below details the parameters can be adjusted:
Parameter
Comments / Description
Options
Default Setting
SNDR1
SNDR2
SNDR320
ZONE 1 FIRE
Determines the response of the output to a fire
alarm condition from this zone.
OFF, PULSED, ON
ON
ON
OFF
ZONE 2 FIRE
Determines the response of the output to a fire
alarm condition from this zone.
OFF, PULSED, ON
ON
ON
OFF
ZONE 3 FIRE
Determines the response of the output to a fire
alarm condition from this zone.
OFF, PULSED, ON
ON
ON
OFF
STAGE-1
Determines the response of the output when at
least one of the qualifying conditions for release
has been established.
OFF, PULSED, ON
ON
ON
OFF
COUNTDOWN
Determines the response of the output when the
activated condition has been established and
the ECD is in the Imminent Release phase. This
setting overrides any pre-existing state during
the countdown period.
OFF, PULSED, ON
ON
ON
PULSE2
STAGE-2
Determines the response of the output when the
actuator output activated condition has been
established.
OFF, PULSED, ON
ON
ON
ON
SOUND ALARMS
Determines the response of the output when the
front panel EVACUATE button is pressed.
OFF, PULSED, ON
ON
ON
ON
PULSE ON HOLD
Determines the response of the output when the
hold button / input is active. This setting
overrides any pre-existing state during the hold
condition. If ‘YES’ the hold pulse pattern is
enforced, if ‘NO’ the programmed ‘countdown’
mode is enforced.
NO / YES
NO
NO
YES
MAY SILENCE
Determines the response of the output when the
front panel SILENCE button is pressed. If set to
NO, the output will not be turned off when the
sounders are silenced.
NO / YES
YES
YES
YES
SOUND IN TEST
Determines the response of the output to a zone
test fire (with sounders). Set to yes, the output
will activate momentarily on any test fire.
NO / YES
YES
YES
YES
EN54-13
Determines whether extended transmission path
monitoring is in use and defines the maximum
alarm load current.21
NONE, 100mA,
250mA, 500mA,
1000mA
NONE
NONE
NONE
20 SNDR3 is dedicated to the Gas ECD for the flooding zone alarm. For compliance with EN12094-1, this alarm circuit will turn ON during
the released state regardless of any configuration settings.
21 If enabled, the panel monitors the circuits to ensure that at the specified load current, the circuit can deliver the load current whilst still
maintaining circuit device voltage compatibility levels via the transmission path resistance. If enabled, the sounder circuit must be fitted with
an Mxp-505 EOL Device.
Triggering Signals to Equipment within the System. 22
The general fire alarm outputs can be used / configured to transmit triggering signals
to extinguishing system equipment such as pilot cylinders, warning devices, etc.
If required, the outputs can be non-silencing. These outputs can be individually
disabled (sounder-1 / sounder-2).
3.3.2.2 Pulse Pattern Configuration23
Section 4.30
Activation of Alarm Devices with Different Signals.
Signals during the pre-discharge warning period should be intermittent and signals
during the activated / released condition should be continuous.
In addition to turning the sounders ON, the sounders can be pulsed as an alert tone. Three separate pulse
patterns can be configured.
[Pulse Pattern]
PULSE-1 ON 1s.
PULSE-1 OFF 4s
PULSE-2 ON 1s
PULSE-2 OFF 1s
HOLD PULSE ON 1s
Use the buttons to highlight the required pulse period
and then press the button to select it.
A menu of parameters is presented for the selected
sounder.
[Number Entry]
Value: 1
Enter New Value:-
0
Maximum: 7
The current on/off period is shown.
Enter a new on/off period as required.
Parameter
Comments / Description
Options
Default
Setting
PULSE-1 ON
Specifies the Sounder ON period during an ALERT
condition.
1 – 7 Seconds
1
PULSE-1 OFF
Specifies the Sounder OFF period during an ALERT
condition.
1 – 7 Seconds
4
PULSE-2 ON
Specifies the Sounder ON period during an ALERT
condition.
1 – 7 Seconds
1
PULSE-2 OFF
Specifies the Sounder OFF period during an ALERT
condition.
1 – 7 Seconds
1
HOLD PULSE ON 24
Specifies the Sounder ON period during the HOLD
condition.
1 – 7 Seconds
1
HOLD PULSE OFF 24
Specifies the Sounder OFF period during the HOLD
condition.
1 – 7 Seconds
2
From Software Version 2.02 :
A second ALERT pulse type (PULSE-1) is provided. The original ALERT pulse type is now renamed as PULSE-
2 and this is the default pulse pattern for the COUNTDOWN condition.
22 Do not use SNDR3 for these functions.
23 ON normally takes precedence over PULSE patterns. Exceptions: during the pre-discharge countdown or during a hold condition.
24 The mark to space ratio of the HOLD PULSE signal should be configured to create a different and unique pattern to the standard Alert
PULSE-1 or PULSE-2 patterns.
The Extinguishing Menu comprises three separate sub-menus. These cover the operating parameters of the
actuator output (Output Set-Up), the fire alarm and manual conditions required to activate the output (Cause &
Effect) and operating parameters for any Extract output (Extract Set-Up).
[Extinguish Select]
Output Set-Up .
Cause & Effect
Extract Set-Up
Use the buttons to highlight the required menu option
and then press the button to select it.
3.3.3.1 Output Set-Up
The display presents a menu of parameter options along with their current settings.
[Release Settings]
ACTUATOR: SOLENOID .
COUNTDOWN AUTO: 0
COUNTDOWN MAN : 0
RELEASE PERIOD: 0
MINS TO RESET : 0
Use the buttons to highlight the required option and
then press the button to select it.
The table below details each available option.
Parameter
Comments / Description
Options
Default
Setting
ACTUATOR
Specifies the type of actuating devices connected to the
output.
METRON
SOLENOID
NOT
LEARNT
COUNTDOWN AUTO
Specifies the delay timer before activating the actuator
output when the condition originates from AFD Zone
inputs.
0 – 60 Seconds
30
COUNTDOWN MAN
Specifies the delay timer before activating the actuator
output when the condition originates from any manual
trigger input.
0 – 60 Seconds
30
RELEASE PERIOD
Specifies the duration of the actuating output signal.
0 – 1800 Seconds
300
MINS TO RESET
Specifies the minimum time that must elapse before a
reset can be performed after the activated condition has
been established.
0 – 30 Minutes
10
HELD COUNTDOWN
Specifies whether the countdown time will restart or will
freeze or will continue for the remaining duration when
the hold activation is removed.
RESTART COUNT
SUSPEND COUNT25
CONTINUE COUNT
RESTART
IN COUNTDOWN
Specifies whether a RESET can be performed during the
countdown period.
ALLOW RESET 26
PREVENT RESET
PREVENT
FLOW DETECTION
Specifies whether Flow Detection is in use. When set to
YES, the “Released” condition will not be established if
flow is not detected during the release period. The
display will also show “No flow Detected”.
YES/NO27
YES
[Actuator Detection]
Fault-Free Wiring?
Press √ to learn
The actuator output type must be learnt.
Press the button to proceed and the panel will analyse
the circuit to determine the type of actuating device(s).
It will also analyse the circuit impedance. No other
adjustments are necessary.
3.3.3.2 Cause and Effects Programming
The display presents a menu of parameter options along with their current settings.
25 This setting is not in accordance with BS EN 12094-1: 2003.
26 This setting is not in accordance with BS EN 12094-1: 2003.
27 When set to NO, the RELEASED condition is established at the instance the actuator output is turned on.
NOTE: Irrespective of the setting for this parameter, if a valid signal is received on the flow input circuit then a RELEASED condition will be
established.
Release Active When:-
TWO Z1&Z2 : √ .
TWO Z1&Z3 : X
TWO Z2&Z3 : X
ALL Z1&Z2&Z3 : --
Some options are mutually exclusive. Depending on the
options selected, some options are inhibited and cannot be
adjusted – the current setting is shown as ‘- -‘.
The settings only apply to the AFD inputs. A Manual
Trigger input will immediately generate the activated
condition.
If all three ‘Two Zone’ parameters are enabled then the
activated condition is established when any two of the
three zones are in the fire condition.
IMMEDIATE Z1 : --
IMMEDIATE Z2 : --
IMMEDIATE Z3 : --
Use the buttons to highlight the required option and then press the button to select it. The table below
details each available option.
Parameter
Comments / Description
Options
Default
Setting
TWO Z1&Z2
Determines if the activated condition is established by a
fire condition in two zones – Zones 1 and 2.
, X, --
TWO Z1&Z3
Determines if the activated condition is established by a
fire condition in two zones – Zones 1 and 3.
, X, --
X
TWO Z2&Z3
Determines if the activated condition is established by a
fire condition in two zones – Zones 2 and 3.
, X, --
X
ALL Z1&Z2&Z3
Determines if the activated condition is established only
when all three zone detection circuits are in a fire
condition.
28, X, --
--
IMMEDIATE Z1
Determines if the activated condition is established when a
fire occurs on Zone 1
, X, --
--
IMMEDIATE Z2
Determines if the activated condition is established when a
fire occurs on Zone 2
, X, --
--
IMMEDIATE Z2
Determines if the activated condition is established when a
fire occurs on Zone 3
, X, --
--
3.3.3.3 Extract Set-Up
The display presents a menu of parameter options along with their current settings.
[Extract Settings]
EXTRACT MINS: 0 .
EXTRACT MODE:
MANUAL PROMPT
Use the buttons to highlight the required option and
then press the button to select it.
The table below details each available option.
Parameter
Comments / Description
Options
Default
Setting
EXTRACT MINS
Specifies the duration of the extract signal following
release of the extinguishant.
0 – 120 Minutes
0
EXTRACT MODE
Specifies whether the panel should prompt to start the
extract phase or whether the extract output should turn on
immediately following discharge.
MANUAL PROMPT
AUTOMATIC
MANUAL
PROMPT
3.3.3.4 Release Signal Termination (Test Function)
Section 4.21.5
A special Engineer function is provided to terminate an extended active extinguishing
control signal for the purposes of testing the system. This is provided at Level 2 using
the EXTINGUISHING menu option. When prompted, enter the Level 3 password
and a further option (STOP RELEASE: YES) is provided in the menu. Highlight this
option and press the button to turn off the extinguishing control signal output.
28 This setting is not in accordance with BS EN 12094-1: 2003.
The display presents a list of the programmable inputs along with their current settings.
[Input Settings]
PROG INPUT 1: .
NOT IN USE .
PROG INPUT 2:
NOT IN USE
PROG INPUT 3:
Use the buttons to highlight the required input and
then press the button to select / change it.
The table below details each available input and the
programmable settings.
The default setting for all inputs is NOT IN USE except:
KEY-SWITCH 1 = LEVEL 2 ACCESS
KEY-SWITCH 2 = MODE SELECT
Inputs 29
Setting Options
Comments
PROG INPUT 1
NOT IN USE
The Input is not used.
PROG INPUT 2
*
SOUND ALARMS
Activating an input with this setting will cause all sounder outputs to operate as
programmed.
PROG INPUT 3
*
SILENCE ALARMS
Activating an input with this setting will cause all sounder outputs to be Silenced
(where permitted).
PROG INPUT 4
*
RESET
Activating an input with this setting will cause the panel to be reset (if permitted).
KEY-SWITCH 1
EXT. FAULT
Activating an input with this setting will register a fault condition on the panel.
KEY-SWITCH 2
MANUAL TRIGGER
Activating an input with this setting will initiate the manual release activated
condition.
PRESSURE
Activating an input with this setting will register a pressure warning condition.
VALVE MON
Activating an input with this setting will register a Valve Monitor warning
condition.
MODE SELECT
Activating an input with this setting will select MANUAL ONLY mode. Note: When
multiple inputs are defined as mode select, then any switch in the active state will
set the system into MANUAL ONLY mode.
HOLD
Activating an input with this setting will stop the activated condition countdown
timer preventing the release of the extinguishant.
ABORT
Activating an input with this setting will abort the activated condition.
*
LEVEL-2 ACCESS
Activating an input with this setting will enable Level-2 Control Keys and Menu
functions. A password is not required.
START EXTRACT
Activating an input with this setting will turn on any output configured as an
Extract output. The output will remain on for the programmed time.
KEEP EXTRACT ON
Activating an input with this setting will turn on any output configured as an
Extract output. The output will remain on irrespective of any programmed
operation or times.
DISABLE GAS
Activating one or more inputs with this setting will disable extinguishing (in the
same manner as the level-2 Disable/Enable menu option). Manual and automatic
triggering of gas release will be inhibited.
*
DISABLE ZONES
Activating one or more inputs with this setting will disable all detection zones.
DISABLE AUTO ZN
Activating one or more inputs with this setting will disable all detection zones
which can affect an automatic release of gas (zones included in the cause &
effect logic).
29 For compliance with EN54-13 monitoring requirements, Inputs 1-4 shall only be used for EN12094-1 functions. Functions marked with a ‘*’
should not be used.
The display presents a list of the programmable outputs along with their current settings.
[Prog. Outputs]
RELAY 1 .
> NOT IN USE .
RELAY 2
* GENERAL FAULT
AUX RELAY 1
Use the buttons to highlight the required output and then
press the button to select / change it.
The table below details each available output and the
programmable settings available. The output can also be
configured as an INVERTED output (indicated by an *
character). In this mode, it is normally turned on and will turn off
when the applicable cause & effect occurs.
[Output Settings]
MODE: .
NOT IN USE .
INVERTED: NO
Use the buttons to highlight the required option and then
press the button to select / change it.
The default settings are as follows:
RELAY 1:
STAGE-1
[INVERTED = NO]
RELAY 2:
RELEASED
[INVERTED = NO]
AUX RELAY 1 – 8:
NOT IN USE
[INVERTED = NO]
SWITCHED AUX:
RESET
[INVERTED = YES]
Outputs
Setting Options
Comments
RELAY 1
NOT IN USE
The Output is not used and will not activate.
RELAY 2
FOLLOW SOUNDER 1
The output is activated when Sounder 1 is activated.
AUX RELAY 1
FOLLOW SOUNDER 2
The output is activated when Sounder 2 is activated.
AUX RELAY 2
FOLLOW SOUNDER 3
The output is activated when Sounder 3 is activated.
AUX RELAY 3
GENERAL FIRE
The output is activated if any fire condition event occurs.
AUX RELAY 4
GENERAL FAULT
The output is activated if any fault condition event occurs.
AUX RELAY 5
STAGE-1
The output is activated when a first stage alarm is recognized.30
AUX RELAY 6
STAGE-2
The output is activated when a second stage release is recognized and the
actuator output is due to be operated.
AUX RELAY 7
RELEASED
The output is activated when the release of extinguishant has been completed.
AUX RELAY 8
ON HOLD
The output is activated when the release of extinguishant has been held.
SWITCHED AUX
ABORTED
The output is activated when the release is aborted. It remains in this state until
the panel is reset.
MANUAL MODE
The output is activated when the manual only mode is selected. (In the off
position the output indicates auto+manual).
VALVE CLOSED
The output is activated when the valve monitor is active.
RESET
The output is activated for approximately 10-15 seconds when the panel is
reset.
ZONE1 or STAGE-2
The output is activated when a second stage release is recognized OR the fire
alarm is from Zone 1.
ZONE2 or STAGE-2
The output is activated when a second stage release is recognized OR the fire
alarm is from Zone 2.
ZONE3 or STAGE-2
The output is activated when a second stage release is recognized OR the fire
alarm is from Zone 3.
EXTRACT
The output is activated when the extract phase is in process.
TEST MODE
The output is activated when any of the zones are in a test state.
SUPERVISORY
The output is activated during a ‘Pressure Low’ or ‘Valve Stuck’ condition.
DISABLEMENT
The output is activated whenever any disablement condition is present except
for the disablement of programmable releays.
WARNING
The output is activated whenever a “Valve Closed”, “Aborted”, “Hold” or
“Manual Only” condition is present.
FIRE + MAN. TRIG
The output is activated whenever a Fire condition exists or a manual trigger
has been used to initiate the release of gas. Remains active until a successful
Gas Reset (for Manual trigger condition) or while ever the Fire state persists.
30 NOTE: Stage-1 will also be activated as soon as an immediate Stage-2 condition (i.e. manual release or single zone fire alarm activation)
occurs.
The output is activated whenever a manual trigger has been used to initiate the
release of gas. Remains active until a successful Gas Reset.
3.3.5.1 Switched AUX Output
The Switched AUX Output is normally turned on and will turn off for about 5 seconds when the panel is reset.
This is useful for resetting conventional beam detectors, etc.
SWITCHED AUX:
RESET
[INVERTED = YES]
The output can alternatively be programmed to turn on when specific conditions occur to power external
equipment. For example, turn on when Stage 1 is active.
SWITCHED AUX:
STAGE-1
[INVERTED = NO]
3.3.6 Passwords
The display presents a menu of user password options.
[Select User]
USER 1 1234
USER 1 1234
USER 2 1234
USER 3 1234
ENGINEER 7654
Use the buttons to highlight the required password
and then press the button to select / change it.
[Number Entry]
Value: 1234
Enter New Value:-
0
Maximum: 99999999
The current password is shown.
Enter a new password as required for the specific user.
Passwords can be up to Eight Digits long.
A time-out for Level 2 access can be configured – See Section 3.3.7 – if no buttons are pressed, the panel will
then automatically cancel Level 2 access and return to Level 1 access when the time-out has elapsed.
3.3.6.1 Default Passwords
USER 1
1234
USER 2
1234
USER 3
1234
USER 4
1234
ENGINEERS CODE
7654
3.3.7 General Options
The display presents a menu of user general options.
Parameter
Comments / Description
Options
Default
Setting
Level 2 Time Out
The Level 2 Time Out can be configured in the range 0 – 5
minutes (0 = No time out – stay in Level 2)
After the timeout, the menu functions and user controls are
inhibited. Password entry is required to re-enable these.
0 – 5 Minutes
5 Minutes
Earth Detection
Determines if the panel shall report earth detection faults.
YES/NO
YES
Pressure Inputs
Determines the normal, quiescent state of the contacts
associated with the equipment used to sense loss of
extinguishant pressure (applies to all system inputs used
for pressure loss detection).
Normally Open /
Normally Closed
Normally
Open
Config
Shows the checksum of the configuration memory.
Option to erase the configuration (press the button).
> Erase
Configuration
N/A
Program
Shows the current program version
Press the button to show the program checksum.
> Show Checksum
N/A
Log
Determines the information that is recorded in the log.
Standard+ Mode also records the return to normal
transitions.
Standard,
Standard+
Standard
Service Number
Determines the telephone contact number that is shown
on the normal display when there is an acknowledged fault
condition.
---
Service Due Date
Determines the date/time at which a fault warning
messages will be displayed to indicate service is overdue.
dd-mmm-yyyy
hh:mm
06-01-2020
10:00
Mute
Determines if the panel permits the buzzer to be muted at
Level 1 or if it can only be muted at Level 2.
LEVEL-1
LEVEL-2
LEVEL-1
Reset Mode
Determines if the user is presented with the choice of
resetting ‘gas only’ or ‘fire & gas’ on a reset , alternativley
no menu is presented and ‘fire & gas’ are always reset.
PROMPT
ALL
PROMPT
Daylight Saving
Used to turn on/ off daylight saving mode – which
automatically shifts the current time forward/ backwards by
1 hour on programmed days of the year.
YES
NO
YES
EN54-2 [8.4]
Determines if the panel shall annunciate a total loss of
power.
YES
NO
NO
Section 7.6
Reset from the fire alarm condition.
For full compliance with both EN54-2 and EN12094-1 the ‘PROMPT’ option
must be selected for Reset Mode. For compliance with only 12094-1 select the
‘ALL’ option. This option provides a single reset button action to reset the
system (note reset is inhibited during the activation condition).
3.3.7.1 Daylight Saving Options
The display presents a menu of the daylight saving configuration.
Parameter
Comments / Description
Options
Default
Setting
Enabled
Determines whether the daylight saving function is on or
off. On means that the time will be shifted forwards &
backwards by 1 hour, two times a year on the dates
determined below.
YES
NO
YES
Forward Order
Specifies which occurance of the day specified (below) in
the month specified (below) the time will be shifted
forwards by 1 hour (at 2AM the time will change to 3AM).
1ST
2ND
3RD
4TH
LAST
LAST
Forward Day
Specifies on which day of the week the time will be shifted
forwards by 1 hour.
MON – SUN
SUN
Comments / Description
Options
Default
Setting
Forward Month
Specifies in which month the time will be shifted forwards
by 1 hour .
JAN – DEC
MAR
Back Order
Specifies which occurance of the day specified (below) in
the month specified (below) the time will be shifted back by
1 hour (at 2AM the time will change to 1AM).
1ST
2ND
3RD
4TH
LAST
LAST
Back Day
Specifies on which day of the week the time will be shifted
back by 1 hour.
MON – SUN
SUN
Back Month
Specifies in which month the time will be shifted back by 1
hour.
JAN – DEC
OCT
3.3.8 Status Indicators
The display presents a list of the available remote status indicator addresses.
[Status Indicators]
RSI-1 UNUSED
RSI-2 UNUSED
RSI-3 UNUSED
RSI-4 UNUSED
RSI-5 UNUSED
Up to seven (7) RSI panels can be connected to the
extinguishing panel.
Use the buttons to highlight the required RSI and
then press the button to select / change it.
[RSI-1 Settings]
ACTIVE: NO .
INPUT-1:
NOT IN USE
INPUT-2:
NOT IN USE
A list of the RSI programmable functions is presented.
Use the buttons to highlight the required RSI function
and then press the button to select / change it.
Parameter
Comments / Description
Options
Default
Setting
ACTIVE
Determines if an RSI at this address is connected.
NO / YES
NO
INPUT-1
Determines the action if this input
See Section 0
NOT IN USE
INPUT-2
Determines the action if this input
See Section 0
NOT IN USE
KEYSWITCH
Determines the action if this input
See Section 0
MODE
SELECT
OUTPUT-1 31
Determines the action if this output
See Section 0
NOT IN USE
OUT-1 INVERT
Determines whether the output is inverted (normally on)
NO / YES
NO
OUTPUT-2 31
Determines the action if this output
See Section 0
NOT IN USE
OUT-2 INVERT
Determines whether the output is inverted (normally on)
NO / YES
NO
BUZZER
Determines if the buzzer is in use or not at this RSI
NO / YES
YES
TICK=MUTE
Detemined if the buzzers in the panel and all other RSI
can be muted from this RSI.
NO / YES
YES
31 The optional 2-Way Relay card (Exp-007) must be installed in the RSI for these outputs.
3.3.9 Enable PC LINK
The ENABLE PC LINK menu option allows a PC to be connected to the panel for upload / download.
[USB Port Enabled]
CURRENT STATUS:
IDLE
The display shows the current status of the link. Possible
status messages are:
LOGO UPDATE
(< PC)
EVENT DATA TRANSFER
(> PC)
CONFIG DATA TRANSGER
(> PC)
NOTE: When this function is enabled and in use, any fault reporting of power supply (PSE)
fault conditions is temporarily suspended.
3.3.10 Exit
To exit from the Commissioning / Programming Menu, select the EXIT option and press the button. The
display prompts for the Level 3 password.
4 Service and Maintenance
4.1 Maintenance Schedule
This equipment should be maintained in accordance with the regulations and codes appropriate to the country
and location of installation. The following is recommended if no other regulations apply.
4.1.1 Daily Actions
The site operator / user should perform the following checks and actions:
a) The panel indicates normal operation. If any faults exist, these should be recorded in a logbook.
b) Any recorded faults have received attention and have been signed off.
4.1.2 Monthly Actions
The site operator / user should perform the following checks and actions:
a) Any stand-by generators should be started and fuel levels checked.
b) Operate at least one call point or detector (from different zones each month) and check that the panel
enters a fire alarm condition and that the appropriate / programmed alarm or warning devices are sounded /
operated. Where permissible, this should include any links to the fire brigade or remote centre.
c) Check that all outstanding faults have been recorded and have received attention.
4.1.3 Quarterly Actions
The service / maintenance contractor should perform the following checks and actions:
a) Check that all entries in the logbook have been addressed, check the event log in the panel and take the
necessary remedial actions.
b) Visually inspect the panel for any moisture ingress or other deterioration, check all battery connections and
test / check the alarm, fault and other functions of the panel operation.
c) Ascertain if any building or structural alterations have been carried out that would affect the placement /
location of call points or detectors. If so, perform a visual inspection.
d) Record in the logbook any defects or remedial actions that must be undertaken and arrange for these to be
carried out as soon as possible.
4.1.4 Annual Actions
The service / maintenance contractor should perform the following checks and actions:
a) Perform the checks as recommended above in the daily, monthly and quarterly schedules.
b) Perform a complete “Walk Test” of the system to check that each call point and detector is operating to its
manufacturers’ specification.
c) Visually inspect all cable fittings. Check that the equipment is undamaged and that the conditions of
installation have not changed such that they fall outside of the equipment specifications.
d) Inspect and test all batteries and replace as required – refer to Section 4.2 for recommended replacement
schedule.
e) Record in the logbook any defects or remedial actions that must be undertaken and arrange for these to be
carried out as soon as possible.
4.2 Replacement of Components
In general, all of the components parts used in the construction of the panel have been selected for long life and
reliability.
However, certain components may require to be changed on a regular service basis. The details of these are as
follows:
4.2.1 Batteries
For battery installation, see section 2.3.2
Respect the Environment.
Batteries must be disposed of responsibly and in accordance with any local
regulations.
Expected Life:
-
3-5 years at an ambient temperature of 20°C
Replacement Schedule:
-
As above. However, note that the expected battery life is shortened by
increase in ambient temperature. The life reduces by 50% for every
10°C rise above ambient. Refer to battery manufacturer for further
information.
Manufacturer / Part Numbers: -
YUASA
POWERSONIC
4AH
NP4-12
5AH
PS-1250-F1
7AH
NP7-12
7AH
PS-1270
STOP
For optimum performance and charge retention, Yuasa recommend that
batteries are ‘top-charged’ prior to installation.
For batteries up to 6 months old from date of manufacture, charge at 2.4V per
cell (i.e. 14.4V per battery) for 20 hours prior to installing the batteries.
It is not recommended to use batteries that are more than 6 months old, from
their date of manufacture, on a new installation.
It is quite normal for lead-acid batteries to vent hydrogen when
being charged.
The panel is adequately ventilated to dissipate this hydrogen.
DO NOT seal the enclosure or install in a sealed enclosure or
cavity.
4.2.2 Liquid Crystal Display
Expected Life:
-
> 10 years
Replacement Schedule:
-
When the display becomes difficult to read. The display contrast will
gradually fade with time.
-
Replace the complete circuit card assembly.
5.1 Appendix 1 – Forgotten Level 3 Password
Should the Level-3 password be forgotten, contact Customer Support to obtain a temporary permit number to
regain access to the panel programming functions.
Customer Support will require a decryption key displayed by the panel. To obtain this number, attempt to gain
access to the Level-3 Programming Functions entering “1” when prompted for the password. As soon as the
“Password Invalid” message is shown, press the “0” button and the display will show a decryption key. Make a
note of this number.
For example:
Enter Your Password
214728378
Customer Support will provide a temporary permit number that you can enter when prompted for the Level-3
password. As soon as access has been regained to the Level-3 Programming Functions, select the Passwords
Menu Option and check / change the Level-3 password. (Refer to Section 3.3.6 for further information).
5.2 Appendix 2 – Compatible Devices
5.2.1 Detectors
Manufacturer
Part Number
Description
№ /
Zone
№ / Zone
(Schottky
bases)32
Apollo
55000-215
Series-65 Ion smoke
32
26
55000-216
Series-65 Ion smoke
32
26
55000-217
Series-65 Ion smoke
32
26
55000-218
Series-65 Ion smoke (Integrating)
32
26
55000-219
Series-65 Ion smoke (Integrating)
32
26
55000-220
Series-65 Ion smoke (Integrating)
32
26
55000-315
Series-65 Photo-smoke
32
26
55000-316
Series-65 Photo-smoke
32
26
55000-317
Series-65 Photo-smoke
32
26
55000-120
Series-65 Heat A1R
30
26
55000-121
Series-65 Heat A1R
30
26
55000-122
Series-65 Heat A1R
32
26
55000-125
Series-65 Heat BR
30
26
55000-126
Series-65 Heat BR
30
26
55000-127
Series-65 Heat BR
32
26
55000-130
Series-65 Heat CR
30
26
55000-131
Series-65 Heat CR
30
26
55000-132
Series-65 Heat CR
32
26
55000-135
Series-65 Heat CS
30
26
55000-136
Series-65 Heat CS
30
26
55000-137
Series-65 Heat CS
32
26
Apollo
ORB-OP-12001-APO
ORBIS Photo-smoke
16
16
ORB-OH-13001-APO
ORBIS Multi-sensor
16
16
ORB-HT-11001-APO
ORBIS A1R Heat
16
16
ORB-HT-11002-APO
ORBIS A2S Heat
16
16
ORB-HT-11003-APO
ORBIS BR Heat
16
16
ORB-HT-11004-APO
ORBIS BS Heat
16
16
ORB-HT-11005-APO
ORBIS CR Heat
16
16
ORB-HT-11006-APO
ORBIS CS Heat
16
16
ARGUS
Aurora-DN / S100 (using
330R base)
Photo smoke
18
16
Aurora-TN / S400
(using 330R base)
Heat (RoR)
22
16
Aurora-DTN / S200
(using 330R base)
Multi
19
16
Argo (using 330R base)
Heat (58deg Fixed)
24
16
S300 (using 330R base)
Heat (75deg Fixed)
24
16
Hochiki
SLR-E3
CDX Photo-smoke
32
24
DCD-AE3
CDX Heat
32
24
32 The number of devices that can be fitted to a zone when using schottky diode bases. The figure stated ensures that all detector fires/
faults are registered under various worst case scenarios e.g. Fire detection with devices removed from bases:- all but the last device
removed from it’s base; 32 Ohms cable impedance; no E.O.L device fitted (open circuit).
Also note that calculations assume an Active end of line device exhibiting a ‘fault current’ of no more than 40uA.
№ / Zone
(Schottky
bases)32
DCD-CE3
CDX Heat
32
24
DFG-60E
CDX Heat
32
16
DFJ-AE3
CDX Heat
32
24
DFJ-CE3
CDX Heat
32
24
HF-24
UV Flame
8
8
SPC-ET
CDX Beam
6
6
SPB-ET
CDX Beam
7
6
SRA-ET
CDX Beam
4
4
Nittan
EVC-P
Evolution Photo-smoke
32
15
EVC-H-A2S
Evolution Heat
32
15
EVC-H-CS
Evolution Heat
32
15
Nittan
2SC-LS (using 330R base)
Sensortec Heat R-O-R
32
13
NFD-68P (using 330R base)
Sensortec U.V. Flame
14
13
2RA-P (using 330R base)
Sensortec Dual I.R flame
32
13
NHD-G1, G2, GH1
(using 330R base)
Sensortec Heat Detectors
32
13
ST-I (using 330R base)
Sensortec Ion smoke
32
13
ST-P (using 330R base)
Sensortec Photo-smoke
32
13
STA-D5 (using 330R base)
Sensortec Duct smoke
32
13
System Sensor
ECO1002
(standard base – no resistor)
ECO1000 Heat / Photo
28
25
ECO1003 (standard base –
no resistor)
ECO1000 Photo-smoke
32
25
ECO1004T (standard base –
no resistor)
ECO1000 Heat (78deg Fixed)
28
25
ECO1005 (standard base –
no resistor)
ECO1000 Heat (RoR)
30
25
ECO1005T (standard base –
no resistor)
ECO1000 Heat (58deg Fixed)
30
25
System Sensor
2351TEM (standard base –
no resistor)
Series-300 Multi
26
25
2351E (standard base – no
resistor)
Series-300 Photo-smoke
32
25
5351TE (standard base – no
resistor)
Series-300 Heat
26
25
4351E (standard base – no
resistor)
Series-300 Heat
26
25
5351E (standard base – no
resistor)
Series-300 Heat
28
25
5.3 Appendix 3 – Recommended Cables
5.3.1 Fire Rated Cables
For best performance, the prefered cables are 2-core twisted with overall shield.
Manufacturer
(In alphabetical order)
Cable Type
Core Sizes (mm)
5839-1 Rated
RS
485
1.0
1.5
2.5
S (30)
E (120)
AEI
Firetec Multicore Standard. FS2C
-
33
AEI
Firetec Multicore Enhanced Ref. FE2C
-
33
AEI
Firetec Armoured Ref. F2C
-
33
Calflex
Calflam CWZ
- (2.5mm2)
-
Cavicel SpA
Firecel SR/114H 34
34
Cavicel SpA
Firecel SR/114E 34
34
Draka
Firetuf (OHLS) FTZ
Draka
Firetuf PLUS
Draka
Firetuf Power (Armoured)
-
Draka
Firetuf Data 1-Pair 0.63mm
-
-
-
Huber & Suhner
Radox FRBS/M1x2
-
Irish Driver-Harris Co Ltd
Kilflam 2000
Irish Driver-Harris Co Ltd
Kilflam 3000
Prysmian (Pirelli)
FP200 Flex
(1.0mm2)
-
-
Prysmian (Pirelli)
FP200 Gold
(1.0mm2)
Prysmian (Pirelli)
FP PLUS
Prysmian (Pirelli)
FP400 (Steel wire armoured)
-
Tratos Cavi SpA
FIRE-safe TW950
Tyco Thermal Controls
Mineral Insulated Twin Twisted PYRO-E CCM2T
Tyco Thermal Controls
Pyrotenax Served Mineral Insulated Cable (light
and heavy duty)
Tyco Thermal Control
Pyro-S
Wrexham
Mineral Insulated Cable (light and heavy duty)
5.3.2 Non-Fire rated cables
Suitable for the RSI RS485 Link. For best performance, the prefered cables are 2-core twisted with overall shield.
Manufacturer
Model
Cable Type
Alpha & BICC
Alpha 2421, BICC
H8093
Screened Twisted Pair 18 AWG Type 2
Alpha & BICC
Alpha 2411, BICC
H8091
Screened Twisted Pair 20 AWG Type 2:
Belden
8205
Unscreened Twisted Pair 20 AWG (0.5 mm²) Belden
Belden
8461
Unscreened Twisted Pair 18 AWG (0.8mm²) Belden
Belden
8760
Screened Twisted Pair 18 AWG (0.79mm²) Belden
Belden
8762
Screened Twisted Pair 20 AWG (0.56mm²) Belden
Belden
9802
Screened Twisted Pair 20 AWG Type E buried distribution wire **35
33 1.5mm2 only.
34 Also available in steel wire armoured (SWA) and steel wire braid (SWB) formats. 1.0mm2 preferred for network.
35 Twisted pair cable suitable for use underground (NB NOT SINGLE WIRE ARMOURED)
5.4 Appendix 4 – Troubleshooting
Symptom
Cause/ Solution
The display shows the condition
“ACTUATOR CIRCUIT”
“ NOT READY”
This indicates that the actuator type has not been ‘learnt’ – or that a
wiring fault caused the learn process to be aborted.
The control panel must determine the exact characteristics of the actuator
and wiring connected to the Actuator terminals. This is carried out from
the commissioning menu:- COMMISSIONING->EXTINGUISHING-
>OUTPUT SET_UP. Refer to section 3.3.3.1.
The display shows the condition
“ACTUATOR CIRCUIT”
“SHORT CIRCUIT” or “OPEN CIRCUIT”
1. Wiring fault on the actuator circuit – check wiring.
2. The wiring or actuator used has been changed/ modified. Re-learn the
new actuator characteristics – see section 3.3.3.1.
After commissioning, the control panel
appears to be stuck in Manual Only Mode.
I have no key-switches fitted/ activated.
The factory settings of the control panel mean that the level-2 menu
mode select function defaults to Manual Only Mode – to avoid inadvertant
triggering during installation.
Change the level-2 menu mode from the following menu:-
Level 2 Menu->EXTINGUISHIN MODES->TRIGGER (select
‘AUTO+MANUAL’).
Note that if factory settings are restored, from the commissioniong menu,
the Manual Only Mode will automatically be re-instated.
I can’t reset the control panel during the
pre-discharge countdown.
As default, resetting the gas release during the countdown is prevented
(to comply with EN12094-1). A configuration setting can be changed to
allow reset during this time – see section 3.3.3.1 (IN COUNTDOWN
setting).
When testing the system, during the
discharge period, I have to wait until the
reset allowed time has elapsed.
By entering the engineers code to select the EXTINGUISH MODES
menu from the Level-2 Menu, an option ‘STOP RELEASE’ is presented –
select this option to cancel the current activation sequence (allow a
reset).
The display shows the condition
“VALVE MONITOR INPUT”
“VALVE STUCK”
Note that the Valve monitor Input requires a different End Of Line resistor
value for the ‘normal’ condition. If no valve is being monitored fit two 6.8K
Ohms resistors in parallel across the terminals (or a single 3.3K Ohms
resistor).
The pressure switch I am using has
normally open contacts – when I connect it
to the system I continually get a ‘low
pressure’ condition reported.
Various types of pressure monitoring equipment are available. To use
normally open contacts, modify the ‘Pressure Inputs’ configuration setting
in the Level-3->General Menu, see section 3.3.7.
The control panel does not detect battery
missing.
Ensure that the jumper link on the power supply module is in the correct
position. See section 2.3.4
EN 12094-1: 2003
Electrical automatic control and delay device
Environmental class: A
1 Flooding Zone
CO2 Low pressure
CO2 High pressure
Inert gas systems
Provided options:
-
Delay of extinguishing signal
-
Monitor Flow of Extinguishing Agent
-
Monitoring of status of components
-
Emergency Hold Device
-
Control of flooding time: 0 – 1800s
-
Manual Only Mode
-
Triggering Signals to Equipment within the System
-
Triggering Signals to Equipment outside the System
-
Emergency Abort Device
-
Activation of Alarm Devices with Different Signals
Response delay activated condition
maximum 3s
Response delay triggering of outputs
maximum 1s
EN54-2: 1997 +A1
Control and indicating equipment for fire detection and fire
alarm systems for buildings
Provided options:
-
Outputs to Fire Alarm Devices
-
Delays to outputs
-
Alarm Counter
-
Test Condition
EN54-4: 1997 +A2
Power supply equipment for fire detection and fire alarm
systems for buildings
Ex-3001
Advanced Electronics Ltd
Moorland Way, Cramlington, Northumberland, NE23 1WE UK
Tel: +44 (0)1670 707 111
Fax: +44 (0)1670 707 222
Email: [email protected]
Web: www.advancedco.com
Doc Number:
680-147
Revision: 06