SuperWISE II a

Instructions for Use 20200921 Art. 1545229 The document was originally written in Swedish. Symbol key Symbols on the machine. This product complies with applicable EU directives Symbols in this user manual Warning/Caution! Electrical voltage Content Symbol key ................................................................. 1 Application area .................................................. 2 General....................................................................... 2 Electrical safety ........................................................... 2 Handling ..................................................................... 2 Installation .................................................................. 2 Installation dimensions and weights ................ 3 SuperWISE II / SuperWISE II SC .................................... 5 SuperWISE II 2K / SuperWISE II 2K SC ......................... 6 LED - Explanation ........................................................ 7 Use ............................................................................. 8 Maintenance ............................................................... 8 Service/maintenance ................................................... 8 Materials and surface treatment .................................. 8 Disposal ...................................................................... 8 Product warranty ........................................................ 8 SuperWISE II / SuperWISE II SC .................................... 9 Control unit replacement .......................................... 9 Retro-fitting Swegon Connect ................................ 9 SuperWISE II 2K / SuperWISE II 2K SC ....................... 10 Control unit replacement ........................................ 10 Retro-fitting Swegon Connect.......................................10 Technical data ............................................................11 Electrical data ............................................................11 References .................................................................11

Swegon reserves the right to alter specifications. 20200921

The packaging contains the following items: 1 SuperWISE II / 1 SuperWISE II 2K / 1 SuperWISE II SC (Swegon Connect) / 1 SuperWISE II 2K SC (Swegon Connect) 1 x Instructions for use Electrical safety Permitted voltage, see “Electrical data”. It is not permissible to insert foreign objects into the product’s contactor connections or the electronics's ventilation openings; as this entails a risk for short circuiting. Ensure that the product is disconnected from the power supply when working on products that are not required to run. Always follow local/national regulations regarding who may carry out this type of electrical installation. Handling • The product must be handled with care. Installation • Moist, cold and aggressive environments must be avoided. • Avoid installing the product near a heat source. • Assemble the product according to applicable industry regulations. • Install the product so that it cannot be accessed by unauthorized persons. • Install the product for easy access during service and maintenance. • Install the product so that the cabinet door can open unobstructed. • Check to make sure that the product does not have any visible defects. • Check that the product is properly secured after it has been installed. • Check that all cables are properly secured in place after they have been installed. • Avoid installing the product on metal walls or by steel beams. Application area The product is a control unit designed for comfort ven- tilation within Swegon’s system for demand-controlled ventilation WISE. The product is used to collect ventilation and climate data and to optimise the operation of the air handling unit. SuperWISE also provides data that is available via the web interface. SuperWISE SC offers a flexible cloud based service that permits communications between products, systems and users. By using Swegon Connect the system can be moni- tored and controlled remotely. General Read through the entire instructions for use before you install/use the product and save the instructions for future reference. It is not permissible to make changes or modify this product other than what is specified in this document. Place the cabinet so that it is not accessible to unauthorised persons.

20200921 Swegon reserves the right to alter specifications.

SuperWISE II Installation dimensions and weights Figure 1. SuperWISE II, SuperWISE II SC, measurement figure (mm). *Minimum free clearance to nearby installations. Figure 3. SuperWISE II, SuperWISE II SC underside, measurement figure (mm). 150 M25 (x1) 40 35 35 35 35 M16 (x2) Ø22,5 (x6) 360 260 Figure 2. Holes for installation (mm), SuperWISE //, SuperWISE II SC. 4x installation screws (clearance hole Ø = 8 mm), screw selection based on the substrate. Weight (kg) SuperWISE II 5,8 SuperWISE II SC 6,3 400 40 300 100* 50* 50* 300* Antenna, only included in SuperWISE II SC Figure 4. SuperWISE II 2K, SuperWISE II 2K SC, measurement figure (mm). *Minimum free clearance to nearby installations. 400 40 300 100* 50* 50* 300* Antenna, only included in SuperWISE II 2K SC SuperWISE II, SuperWISE II SC SuperWISE II 2K, SuperWISE II 2K SC Weight (kg) SuperWISE II 2K 7,1 SuperWISE II 2K SC 7,6 260 360 Figure 5. Holes for installation (mm), SuperWISE // 2K, SuperWISE II 2K SC. 4x installation screws (clearance hole Ø = 8 mm), screw selection based on the substrate. Figure 6. SuperWISE II 2K, SuperWISE II 2K SC underside, measurement figure (mm). 210 M25 (x1) 40 35 35 35 35 M16 (x2) Ø22,5 (x6)

Swegon reserves the right to alter specifications. 20200921

Connections Connect the cables in the following order: A. Communication cables (see item 3 below) B. Power supply 230 V AC (see items 4 and 7 below) Figure 7. SuperWISE II, SuperWISE II SC. NOTE! Swegon Connect (2) and antenna (6) only included in SuperWISE II SC. 2 6 1 3 4 5 7 1. SuperWISE control unit - Main communication unit 2. Swegon Connect – Router (is only included in SuperWISE II SC/SuperWISE II 2K SC). Communicates on the mobile network and ideally on the 4G network. If the cabinet contains Swegon Connect, the cabinet must be placed so that it can receive mobile signals. The cabinet can be supplemented with an extra antenna for increased signal strength (see Accessories) for improved mobile coverage. See the separate docu- mentation for Swegon Connect on www.swegon.com 3. Switch - 8 ports (if more ports are required, install a supplementary switch outside of the cabinet) • Port 1: SuperWISE control unit • Port 2: Swegon Connect • Port 3-8: Free for e.g. WISE DIR/AHU/BMS 4. Main switch - Connection of the power supply 5. Transformer 6. Antenna, only included in SuperWISE II SC/SuperWISE II 2K SC 7. Earth connection Figure 8. SuperWISE II 2K, SuperWISE II 2K SC. NOTE! Swegon Connect (2) and antenna (6) only included in SuperWISE II 2K SC. 2 6 1 3 4 5 7

20200921 Swegon reserves the right to alter specifications.

SuperWISE II DIV GPS ANT PWR USB ETH0 ETH1 IN0 IN1 OUT IN0 IN1 OUT SIM WAN DAT PWR USR POE 1 2 3 4 5 1 3 5 7 2 4 6 8 + - Output DC 24V 30W DC OK UNI POWER Input AC 100V-240V L V 20A L.ON O.OFF Figure 10. SuperWISE II control unit, top, connection. COM COM USB 3.0 USB 3.0 USB 2.0 USB 2.0 SIM Card SIM Card USB external memory (Mounted USB memory supplied) 1 3 5 7 2 4 6 8 HDD HDD SYS SYS LAN LAN LAN LAN VGA VGA DIO DIO DC 12-24V DC 12-24V FG FG V- V- V+ V+ DIV GPS ANT PWR USB ETH0 ETH1 IN0 IN1 OUT IN0 IN1 OUT SIM WAN DAT PWR USR POE + - Antenna L N L N + - Output DC 24V 30W DC OK UNI POWER Input AC 100V-240V L N Service port Figure 9. SuperWISE //, SuperWISE // SC, connection. RJ45 RJ45 RJ45 RJ45 Port 3-8 AHU (for example GOLD, WISE DIR, property network) 230 V AC L N SuperWISE II / SuperWISE II SC

Swegon reserves the right to alter specifications. 20200921

SuperWISE II 2K / SuperWISE II 2K SC DIV GPS ANT PWR USB ETH0 ETH1 IN0 IN1 OUT IN0 IN1 OUT SIM WAN DAT PWR USR POE 1 2 3 4 5 1 3 5 7 2 4 6 8 + - Output DC 24V 30W DC OK UNI POWER Input AC 100V-240V L V 20A L.ON O.OFF USB external memory (Mounted USB memory supplied) 1 3 5 7 2 4 6 8 DIV GPS ANT PWR USB ETH0 ETH1 IN0 IN1 OUT IN0 IN1 OUT SIM WAN DAT PWR USR POE + - Antenna L N L N + + – – 2.1 2.2 2.3 2.4 Output DC 24V 60W DC OK Input AC 100-240V L N 1.1 1.2 Service port Figure 11. SuperWISE // 2K, SuperWISE // 2K SC, connection. RJ45 RJ45 RJ45 RJ45 Port 3-8 AHU (for example GOLD, WISE DIR, property network) 230 V AC L N

20200921 Swegon reserves the right to alter specifications.

SuperWISE II LED - Explanation DIV GPS ANT PWR USB ETH0 ETH1 IN0 IN1 OUT IN0 IN1 OUT SIM WAN DAT PWR USR POE + - Not used. SIM: Steady green light with the SIM card is inserted WAN: Flashes orange if there is contact with the mobile network (2G, 3G or 4G) DAT: Flashes red when data is ready to send over the mobile network PWR: (Power) Flashes green - power to the unit USR: “Spare” POE: Power over Ethernet, “Spare” Swegon Connect SuperWISE II control unit HDD HDD SYS SYS LAN LAN LAN LAN VGA VGA DIO DIO DC 12-24V DC 12-24V FG FG V- V- V+ V+ DC power supply + - Output DC 24V 30W DC OK UNI POWER Input AC 100V-240V L N Green light when the voltage is on, goes out when the output voltage drops below 21.5V DC Switch 1 3 5 7 2 4 6 8 Green light - data being sent Orange diode denotes which communication rate is active Lit: 100 Mbps Not lit: 10 Mbps Green light - power to the unit Figure 12. LED key SuperWISE II control unit. Figure 14. LED key Swegon Connect control unit. Figure 13. LED key DC power supply. Figure 15. LED key switch. HDD: Flashes red - Storage on the memory unit SYS: Green light - Power to the unit

Swegon reserves the right to alter specifications. 20200921

Use Commissioning Commissioning must be performed by qualified and trained WISE service engineers. Trouble shooting • Check that the cables are connected correctly. • Make sure that the product is energized, the supply LED should be lit/flash green. • Check the LED indications, see “LED key”. • Check the status on the SuperWISE user interface (web pages). • Check that Swegon Connect is connected correctly and that the SIM card is inserted correctly. Maintenance Cleaning of electrical components • If needed, use a dry cloth to clean the components. • Never use water, detergent and cleaning solvent or a vacuum cleaner. External cleaning • If necessary use tepid water and a well-wrung cloth. • Never use solvents. Service/maintenance • The product does not require any maintenance, except for any cleaning when necessary. • It is not permissible to open or repair electrical compo- nents. • If you suspect that the product or a component is defective, please contact Swegon. • A defective product or component must be replaced by an original spare part from Swegon. Materials and surface treatment The cabinet is made of polycarbonate (PC), colour code: RAL 7035 (Industrial grey). Disposal Waste must be handled according to local regulations. Product warranty The product warranty or service agreement will not be in effect/will not be extended if: (1) the product is repaired, modified or changed, unless such repair, modification or change has been approved by Swegon AB; or (2) the serial number on the product has been made illegible or is missing.

20200921 Swegon reserves the right to alter specifications.

SuperWISE II Control unit replacement Turn off the power using the main switch before any work is started. Disconnect all the cables to the control unit, loosen the four screws and lift out the control unit. Place the control unit on the 4 spacer bolts and screw back the screws. Reconnect the cables and switch on the power using the main power switch. Figure 16. Control unit replacement. Retro-fitting Swegon Connect ON ON OFF OFF Turn off the power using the main switch before any work is started. Disconnect all the cables to the control unit, loosen the four screws and lift out the control unit. Fit the antenna in the top of the enclosure and tighten the lock nut on the inside. Antenna Fit a DIN rail-mount on Swegon Connect and mount on the DIN rail in the bottom of the cabinet. Connect the antenna and cables, see “Connection”. Refit the control unit and connect the cables. Switch on the power using the main power switch. Figure 17. Retro-fitting Swegon Connect. ON ON OFF OFF Main Switch Main Switch SuperWISE II / SuperWISE II SC

Swegon reserves the right to alter specifications. 20200921

SuperWISE II 2K / SuperWISE II 2K SC Control unit replacement Retro-fitting Swegon Connect Turn off the power using the main switch before any work is started. ON ON OFF OFF Main switch Turn off the power using the main switch before any work is started. ON ON OFF OFF Main switch Disconnect all the cables to the control unit, loosen the two screws and lift out the control unit. Place the control unit on the bottom of the cabinet and screw back the screws. Reconnect the cables and switch on the power using the main power switch. Figure 18. Control unit replacement. Fit the antenna in the top of the enclosure and tighten the lock nut on the inside. Mount the Swegon Connect on the bottom of the cabinet. Antenna Connect the cables and the antenna. Switch on the power using the main power switch. Figure 19. Retro-fitting Swegon Connect.

20200921 Swegon reserves the right to alter specifications.

SuperWISE II References www.swegon.com Building Materials Declaration WISE System Guide SuperWISE II product sheet SuperWISE II / SuperWISE II SC User Manual Technical data Output power (ERP) SuperWISE II SC/SuperWISE II 2K SC External mobile network: Max. 2W (GSM mode) Frequency band SuperWISE II SC/SuperWISE II 2K SC External mobile network: 900/2100... MHz USB: Type A Switch/ Ethernet: Switch supports 3 (Gold/AHU) + 3 outputs (WISE DIR) IP class: IP44 Ambient temperature Operation: -20 – +50°C Storage: -40 – +80°C RH: 10-95% non-condensing CE marking: 2014/53/EU (RED) 2011/65/EU (RoHS2) Electrical data Power supply: 230V 10 A Connections pipe dim. Power terminals: Max. 2.5 mm2 Suitable cable diameter through the chassis (screw terminals): 5-10 mm Max. power consumption SuperWISE II: 34W SuperWISE II SC: 34W SuperWISE II 2K: 60W SuperWISE II 2K SC: 60W Declaration of Conformity Swegon AB hereby declares that the radio equipment SuperWISE II / SuperWISE II SC / SuperWISE II 2K / SuperWISE II 2K SC conforms with the Directive 2014/53/EU and Directive 2011/65/EU. The complete EU Declaration of Conformity is available at Swegon’s website: www.swegon.com. This declaration is applicable only if the product has been installed according to the instructions in this document and if no changes have been made on this product.