socomec ISOM Digiware Instruction Manual
Text of the manual
measurement system for
electrical installations in an IT system
EN
INSTRUCTION
MANUAL
www.socomec.com/
operating-instructions
ISOM DIGIWARE - 546780C - SOCOMEC
1. DOCUMENTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2. HAZARDS AND WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2 .1 . Risk of electrocution, burns or explosion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2 .2 . Risk of damaging the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2 .3 . Responsibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3. BEFORE YOU START . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4. PRESENTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
4 .1 . About ISOM Digiware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
4.1.1. Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4.1.2. Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
4.1.3. Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
4.1.4. Electrical readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
4.1.5. Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
4 .2 . Presentation of associated current sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
4.2.1. Locating core balance transformers ΔIP, ΔIP-R, WR and TFR . . . .17
4.2.2. Adapter ISOM T-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
4.2.3. TE solid-core current sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
4.2.4. TR split-core current sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
4.2.5. TF flexible current sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
4.2.6. Adapters for 5A sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
5. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
5 .1 . Recommendations and safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
5 .2 . Installing ISOM Digiware units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
5.2.1. ISOM Digiware L-60, F-60, T-15 – mounted on DIN rail . . . . . . . . . .25
5.2.2. ISOM Digiware L-60, F-60 – board-mounted . . . . . . . . . . . . . . . . . . .26
5 .3 . Installing TE solid-core sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
5.3.1. Mounting accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
5.3.2. DIN rail mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
5.3.3. Plate mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
5.3.4. Installing on a cable with clamping collar . . . . . . . . . . . . . . . . . . . . . .29
5.3.5. Bar mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
5.3.6. Sensors assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
5.3.7. Sealing accessories for sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
5 .4 . Installing TR split-core sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
5.4.1. Cable mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
5 .5 . Stranded sensors TE mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
5.5.1. Cable or bus bar-mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
5 .6 . Installing the 5A adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
6. CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
6 .1 . Connecting ISOM Digiware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
6 .2 . Connecting the current sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
6.2.1. Connection concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
6.2.2. Details of the RJ12 connections for each current sensor . . . . . . . . .41
6 .3 . Connecting to the electrical network and circuits . . . . . . . . . . . . . . . . . . . . . . . .42
6.3.1. Configurable loads based on the network type . . . . . . . . . . . . . . . . .42
6.3.2. Description of the main network and circuit combinations . . . . . . . .43
6.3.3. Coupled networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
7. DIGIWARE BUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
7 .1 . Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
7.1.1. Digiware bus connection cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
7.1.2. Digiware Bus Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
7 .2 . Sizing of the power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
7.2.1. Equipment consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
7.2.2. Calculation rules for the max. number of products on the Digiware
bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
7.2.3. Digiware bus repeater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
EN CONTENTS
ISOM DIGIWARE - 546780C - SOCOMEC
8. STATUS LEDS, BUTTONS AND AUTO-ADDRESSING . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
8 .1 . Status LEDs and buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
8.1.1. L-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
8.1.2. F-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
8.1.3. T-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
8.1.4. Autotest . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
8 .2 . Auto-addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
9. COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
9 .1 . General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
9 .2 . RS485 and ISOM Digiware bus rule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
9.2.1. Connection with the D-55 or D-75 screen . . . . . . . . . . . . . . . . . . . . .54
9 .3 . Communication tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
10. CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
10 .1 . Configuration using Easy Config . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
10.1.1. Connection modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
10.1.2. Using Easy Config . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
10 .2 . Configuration from the ISOM Digiware D remote display . . . . . . . . . . . . . . .67
10.2.1. Connection mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
11. ALARMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
11 .1 . Alarms upon events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
11.1.1. Insulation and measurement alarm . . . . . . . . . . . . . . . . . . . . . . . . . .68
11.1.2. Digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
11.1.3. Combination of alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
11.1.4. System alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
11 .2 . Setting up alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
11.2.1. ALARM LED on front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
11.2.2. Activation of an output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
11.2.3. Acknowledging alarms by input . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
11.2.4. RS485 Modbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
11.2.5. Display and WEBVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
12. SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
12 .1 . Specifications ISOM Digiware L-60, F-60 and T-15 . . . . . . . . . . . . . . . . . . . . .72
12.1.1. Mechanical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
12.1.2. Electrical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
12.1.3. Measurement characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
12.1.4. Input/output specifications HMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
12.1.5. Communication specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
12.1.6. Environmental specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
12.1.7. Electromagnetic specifications (Directive 2014/30/EU) . . . . . . . . .76
12.1.8. Standards and safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
12.1.9. Longevity CEM directive 2014/30/EU . . . . . . . . . . . . . . . . . . . . . . . .76
12 .2 . Display characteristics – ISOM D-15h and ISOM Digiware D-55 / D-55h /
D-75 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
12.2.1. Mechanical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
12.2.2. Electrical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
12.2.3. ISOM D-55 / D-55h communication features . . . . . . . . . . . . . . . . .77
12.2.4. ISOM Digiware D-75 communication features . . . . . . . . . . . . . . . . .77
12.2.5. Environmental specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
12 .3 . ISOM Digiware L-60 response curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
12 .4 . ISOM Digiware F-60 response curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
13. PERFORMANCE CLASSES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
13 .1 . Specification of the characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
13 .2 . Evaluation of the power supply quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
ISOM DIGIWARE - 546780C - SOCOMEC
1. DOCUMENTATION
All documentation relating to ISOM Digiware and its sensors is
available on the SOCOMEC website at the following address:
www.socomec.fr
ISOM DIGIWARE - 546780C - SOCOMEC
2. HAZARDS AND WARNINGS
The term "unit" used in the following paragraphs encompasses ISOM and DIRIS Digiware and its associated current
sensors (ΔIP, TE, TR or TF).
The assembly, use, servicing (including cleaning) and maintenance of this equipment must only be carried out by
trained, qualified professionals (in case of failure, please contact our Customer Services).
SOCOMEC shall not be held responsible for failure to comply with the instructions in this manual.
2.1. Risk of electrocution, burns or explosion
Caution: risk of electric shock
Ref. ISO 7000-0434B (2004-01)
Caution: refer to the accompanying documentation each time this
symbol is shown
Ref. ISO 7010-W001 (2011-05)
• This device must only be installed and serviced (cleaning with a dry cloth) by qualified personnel who have in-
depth knowledge of installing, commissioning and operating the device and who have had appropriate training.
He or she should have read and understood the various safety measures and warnings stated in the instructions.
• Be aware of protection devices (insulation monitoring system), annual preventive maintenance should be carried
out to test the system's basic functions. (Manual activation of the test function)
• Use connection cables compatible with the voltage and connection terminals of the devices.
• If, for usage reasons, the device is connected by terminals L1, L2 to a powered IT network, terminals KE and FE
should not be separated from the protective conductor (PE).
• Prior to any work on or in the unit, disconnect all power sources (voltage inputs, the unit's auxiliary power supply
and dry contact supplies).
• The isolation options must be:
- within the electrical installation itself
- located somewhere convenient and easily accessible
- labelled as the unit's power switching device
• Always use an appropriate voltage detection device to confirm the absence of voltage.
• Replace all devices, doors and covers before turning on power to this equipment.
• Always power the device with the correct rated voltage.
• Install the unit following the recommended installation instructions and in a suitable electrical cabinet.
• These devices are designed to be integrated; they must be installed in an additional enclosure providing
protection against electric shocks and fire.
• Always connect ΔIP, TE, TR or TF current sensors using the recommended connection cables and observing the
maximum prescribed currents.
• For safety reasons, only use accessories that conform to the manufacturer's specifications.
• During installation, the safety of any system integrating the device is the responsibility of the system installer.
Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could
cause an electric shock, burn or arc flash.
Ref. IEC 61010-2-032
Failure to take these precautions could cause death or serious injuries.
If there is a problem, please contact
SOCOMEC,1 rue de Westhouse, 67235 BENFELD, FRANCE
Tel. +33 3 88 57 41 41
[email protected]
ISOM DIGIWARE - 546780C - SOCOMEC
2.2. Risk of damaging the unit
To ensure that the unit operates correctly, make sure that:
• The unit is correctly installed.
• The auxiliary power supply voltage indicated on the device: 24 VDC ± 10%.
• Use a 230 VAC / 24 VDC SOCOMEC power supply (4829 0120) or use a 1 A gG 24 VDC fuse.
• The 24VDC power supply should be a SELV (safety extra-low voltage).
• The network frequency indicated on the device: 50 to 460 Hz.
• There is a maximum voltage at the voltage input terminals of 480 VAC phase/phase or 480 VAC phase/neutral or
480 VDC.
• Always connect ΔIP, TE, TR or TF current sensors using the recommended connection cables and observing the
maximum prescribed currents.
• Only use RJ45 SOCOMEC cables to interconnect the modules via the Digiware bus.
• During specific checks, disconnect the devices from the network before attempting to insulate or carry out
dielectric testing.
• The devices are designed for indoor use.
• If the ambient temperature exceeds +50°C, the minimum temperature of the copper conductors to connect to
terminals should be +85°C.
Failure to respect these precautions could cause damage to the unit or cause an electrical shock.
2.3. Responsibility
• Assembly, connection and use must be carried out in accordance with the installation standards currently in force.
• The unit must be installed in accordance with the rules given in this manual.
• Failure to observe the rules for installing this unit may compromise the device's intrinsic safety.
• The unit must be positioned within an installation which complies with the standards currently in force.
• Any cable which needs to be replaced may only be replaced with a cable with the correct rating.
ISOM DIGIWARE - 546780C - SOCOMEC
3. BEFORE YOU START
To ensure the safety of personnel and the product, please carefully read the contents of these instructions before
installation.
Check the following points as soon as you receive the package containing the unit, one or several sensors:
• The packaging is in good condition
• The unit has not been damaged during transportation
• The device reference number conforms to your order
• The packaging includes the unit fitted with removable terminal blocks and a Quick Start guide.
ISOM DIGIWARE - 546780C - SOCOMEC
4. PRESENTATION
4.1. About ISOM Digiware
ISOM Digiware is an all-in-one insulating monitoring system incorporating IMD* and FLD** functions.
It can also carry out PMD*** measurements and monitoring.
ISOM Digiware essentially allows you to monitor the insulation of IT systems, by delivering alerts if the insulation level
drops below the thresholds set by the operator. It also combines the function of locating insulation faults under voltage,
simultaneously across multiple circuits.
ISOM Digiware offers a number of options including measuring the insulation, leakage capacity, voltage network,
current, frequency and temperature.
ISOM Digiware is an innovative concept based on a smart connection that sends the voltage data and other
synchronisation signals. Most importantly, this concept means you can view an insulation and leakage capacity reading
for each circuit monitored.
The insulation is monitored by an IMD* module and locating-signal booster for ISOM Digiware L-60 interrupted networks,
and insulation faults are located by FLD** ISOM Digiware F-60 modules. The voltage and current, as well as the ISOM
synchronisation signals are sent via the Digiware bus. On ISOM Digiware F-60 modules, six measuring channels (which
can both locate faults and measure load currents) manage one or mutiple circuits at once. Several modules can be
connected to the Digiware bus to ensure the full monitoring of an IT electrical system.
The ISOM Digiware system offers an innovative mapping function (OhmScanner technology); used mainly for predicting
insulation faults.
Wiring is made easier with "plug & play" RJ-type connections. The connection mode of the current sensors
(fault-locating core balance transformers with adapter ISOM T-15 or DIRIS Digiware current sensors) also helps with
quick and easy installation. Their automatic identification (type and size) significantly reduces the risk of errors during
installation. In addition, combining the current sensor with the ISOM Digiware means the overall accuracy of the ISOM
Digiware + Current sensor detection chain and overall measuring can be guaranteed for all values measured.
ISOM Digiware is configured from its ISOM Digiware D-x5 remote display or via the Easy Config software. You can view
the readings on the WEBVIEW web server embedded into the ISOM Digiware D-75 display (DGW: Data GateWay -
product standard IEC 62974-1), integrating the functions of monitoring electrical volumes and insulating the installation,
as well as managing energy data, and the surveillance, logging, monitoring of data.
Thanks to its architecture, ISOM Digiware can be easily integrated into a building automation system or energy
management system which requires the full monitoring of a large number of loads.
ISOM Digiware is available in models specific to medical IT systems for use on Group 2 premises (version "h").
ISOM Digiware comes in a heavy-duty model (version "t") compatible with extreme environments.
* IMD: Insulation monitoring device (product standard IEC 61557-8)
** FLD: Fault-locating device (product standard IEC 61557-9)
*** PMD: Power Metering and Monitoring Device in accordance with the product standard IEC 61557-12.
ISOM DIGIWARE - 546780C - SOCOMEC
4 .1 .1 . Range
Control and power supply interfaces (24VDC)
Multipoint display
ISOM Digiware D-55 Ref. 4729 0203
ISOM Digiware D-75 Ref. 4729 0205 (with web server)
ISOM Digiware D-75t Ref. 4729 0206 (with web server +
heavy-duty version)
Alert notifications for surgeries
Single-point self-powered reporting
ISOM Digiware D-15h Ref. 4729 0200
Multipoint reporting for medical premises (24VDC
power supply)
ISOM Digiware D-55h Ref. 4729 0204
Modules that are both an Insulation Monitoring
Device and locating current booster
Insulation monitoring device for disrupted IT
networks
ISOM Digiware L-60 Ref. 4729 0110
Insulation monitoring device for disrupted IT
networks – heavy-duty version
ISOM Digiware L-60t Ref. 4729 0111
Insulation monitoring device for medical IT
networks
ISOM Digiware L-60h Ref. 4729 0112
Insulation fault-locating modules (FLD)
Fault-locating devices, 6 circuits
for power networks or medical premises
ISOM Digiware F-60 Ref. 4729 0126
Fault-locating devices, 6 circuits – heavy-duty
version
ISOM Digiware F-60t Ref. 4729 0127
Adapter for locating core balance transformer
Adapter for locating core balance transformer ΔIP
ISOM T-15 Ref. 4729 0590
Adapter for locating core balance transformer ΔIP
– heavy-duty version
ISOM T-15t Ref. 4729 0591
ISOM DIGIWARE - 546780C - SOCOMEC
4 .1 .2 . Principle
ISOM Digiware
D-55 / D-55h / D-75 / D-75t (*)
(*) version h for medical buildings
ISOM Digiware
L-60 / L-60h (*)
DIRIS Digiware U
FE
KE
L1
L2
OPTIONAL
for PMD
measurement
INSULATION
MONITORING DEVICE
(IMD) AND
BOOSTER OF THE
LOCATING CURRENT (INJ)
ACCESS
POINT DISPLAY
ISOM Digiware D-55h
DISPLAY FOR
SURGERIES
(for L-60h only)
ISOM DIGIWARE - 546780C - SOCOMEC
ISOM Digiware F-60
Current sensor
TE, TR or TF
Locating core
balance transformer
ΔIP
Adapter
ISOM T-15
ISOM Digiware D-15h
Digiware bus
terminals
FAULT-LOCATING
DEVICE (FLD)
ISOM DIGIWARE - 546780C - SOCOMEC
4 .1 .3 . Functions
ISOM Digiware offers a number of options, including:
Insulation monitoring
• Measuring Rf, Ce, network frequency F
• Multi-load current measurement
• Insulation curve over 5 periods: hour, day, week, month, year
• "Mapping" mode (OhmScanner technology) to regularly track the insulation by circuit
General measurements (with DIRIS Digiware U module)
• Voltage measurement
• Operation across 4 quadrants
• Guarantees the overall accuracy of the DIRIS Digiware + Sensor measurement chain in terms of power and active
energy up to class 0.5, as per IEC standard 61557-12
Quality of the voltage (with module DIRIS Digiware U-30)
• Direct, inverse and zero-sequence voltages
• THD and harmonics up to order 63 for voltage
• Voltage imbalance
• EN50160 events (Uswl, Udip, Uint)
Data-logging
• Recording and timestamping of min/max electrical values
Metering
• Partial and total apparent, reactive and active power
• Multi-tariff (max. 8)
• Load curves
Alarm
• Timestamped alarms with boolean combination
Current and/or fault-locating inputs
• Measuring/monitoring 6 currents or 6 circuits.
• Current inputs with quick connection and automatic recognition of the current sensors
• Simultaneous management of several single-phase, two-phase and three-phase loads
• Connection of solid-core, split-core and flexible sensors
• Checking the connection, detecting the CT and auto-configuring the networks
• Guarantees the overall accuracy of ISOM/DIRIS Digiware + Sensor measurement chain at Class 0.5 in terms of
power and active energy as per IEC 61557-12
Communication
• Ethernet Modbus TCP output
• Embedded web server WEBVIEW-M available on the ISOM Digiware D-75 screen
• Time-synchronised with the ISOM Digiware D-x5 screen.
• Auto-detection and auto-addressing of devices connected from ISOM Digiware D-x5 displays
ISOM DIGIWARE - 546780C - SOCOMEC
4 .1 .4 . Electrical readings
ISOM Digiware
D-15h
D-55
D-55h
D-75
D-75t
Heavy-duty model for extreme environments
(humidity, impact, vibrations)
•
Function
Centralises single-device measurements
•
Centralises multi-device measurements
•
•
•
•
Clearer display with LED
•
High-resolution LCD display
(configuration, selection and visualisation display of circuits)
•
•
•
•
Power supply
Digiware
•
24 VAC
•
•
•
•
Communication
Master RS485 modbus
•
•
•
•
Digiware bus
•
•
•
•
•
Ethernet TCP Modbus
•
•
•
•
Ethernet Webserver
•
•
Format
Width / number of modules / installation
Mounted
on the
outside
of the
enclosure
D67mm
P40mm
Enclosed
mounting
DIN 96x96
Enclosed
mounting
DIN 96x96
Enclosed
mounting
DIN 96x96
Enclosed
mounting
DIN 96x96
Reference
4729 0200
4729 0203
4729 0204
4729 0205
4729 0206
ISOM Digiware
L-60
L-60t
L-60h
Heavy-duty model for extreme environments
(humidity, impact, vibrations)
•
Multi-measurement
Rf , Cf
•
•
•
U on AC or DC network, F
•
•
•
Alarms
At thresholds (Rf, U, T°C)
•
•
•
History of average values
Insulation curve over 5 periods (hour, day, week, month, year)
•
•
•
Format
Width/Number of modules
125 mm / 7
125 mm / 7
125 mm / 7
Reference
4729 0110
4729 0111
4729 0112
ISOM DIGIWARE - 546780C - SOCOMEC
ISOM Digiware
F-60
F-60t
Heavy-duty model for extreme environments
(humidity, impact, vibrations)
•
Application
Number of measurement channels
6
6
Fault-locating
Locating current by circuit IL
•
•
Insulation value Rf by circuit
•
•
History of average values
Insulation curve over 5 periods (hour, day, week, month, year)
•
•
Metering
+/- kWh, +/- kvarh, kVAh
•
•
Multi-tariff (max. 8)
•
•
Load curves
•
•
Multi-measurement
I1, I2, I3, ∑P, ∑Q, ∑S
•
•
Phi
•
•
Alarms
Thresholds
•
•
ON/OFF inputs / outputs
Numbers
0 / 1
0 / 1
Format
Width
36 mm
36 mm
Number of modules
2
2
Reference
4729 0126
4729 0127
ISOM DIGIWARE - 546780C - SOCOMEC
4 .1 .5 . Dimensions
ISOM Digiware L-60
125
Fix. 75
68
51
Fix. 6
6
89
45
Fix. 100
114
25
ISOM Digiware F-60
Fix. 6
66
51
45
6
Fix. 100
90
114
36
ISOM DIGIWARE - 546780C - SOCOMEC
4.2. Presentation of associated current sensors
Various types of current sensors can be connected to ISOM Digiware:
Fault-locating core balance transformers
• Solid-core (ΔIP)
• Split-core (ΔIP-R)
• Rectangular (WR, TFR)
Current sensors for measuring load currents
• Solid-core (TE)
• Split-core (TR) or flexible (TF).
The difference between these sensors means they can be adapted to any type of new, existing or high-current
existing installation. They all use a specific link with the fault-locating module ISOM Digiware F-60. This link provides a
quick connection, with no cabling errors. ISOM Digiware recognises the sensor size and type. In addition, combining
them means the overall accuracy of ISOM Digiware + current sensor measurement chain can be guaranteed over a
large measurement range.
ISOM Digiware F-60
6x TE/TR/TF sensors or
locating core balance
transformer ΔIP
STAGE 2
1
2
STAGE 1
Important:
To connect the current sensors, use only SOCOMEC cables, RJ12 straight cables, twisted pair, unshielded, 600 V,
-10°C / +70°C as per IEC 61010-1 version 3.0. We recommend that all the current sensors are installed in the same
direction.
Connection cables for current sensors:
* When laying cables, do not exceed a maximum length of 10 metres.
ISOM DIGIWARE - 546780C - SOCOMEC
4 .2 .1 . Locating core balance transformers ΔIP, ΔIP-R, WR and TFR
The locating core balance transformers house the active conductors and bring out the differential sum of the
vector currents, to highlight a fault in the current. These core balance transformers meet measurement sensitivity
requirements.
Solid-core (ΔIP, WR and TFR series) or split-core (ΔIP-R series), they are suitable for all cabling configurations.
Available in all shapes and sizes for use with any cable/bar size and configuration.
With a choice of multiple fasteners (ΔIP and ΔIP-R), they can be DIN rail-mounted, board-mounted or attached
directly to the cable.
A centring solution (for ΔIP and ΔIP-R) which uses a flexible clamping unit means you can centre the cable in the
core balance transformer to ensure accurate measuring and improve its immunity to disruptions in the mains power.
It also means you can mount the core balance transformer directly on a cable.
ΔIP-R split core balance transformers are quick and easy to install with their innovative "one-click" open/close
system. This system, designed without any parts, guarantees safe installation.
4.2.1.1. Range
Connection cables for current sensors:
RJ12
connection
cables
Cable length (m)
0.1
0.2
0.3
0.5
1
2
5
10
50 m reel
+ 100
connectors*
Number of
cables
Reference Reference Reference Reference Reference Reference Reference Reference
Reference
1
-
-
-
-
-
-
4829 0602 4829 0603
4829 0601
3
4829 0580 4829 0581 4829 0582 4829 0595 4829 0583 4829 0584
-
-
-
4
4829 0596 4829 0588 4829 0589
-
-
-
6
4829 0590 4829 0591 4829 0592 4829 0597 4829 0593 4829 0594
-
-
-
* When producing cables, do not exceed a maximum length of 10 metres.
ΔIP circular solid-core balance transformers
ΔIP15
ΔIP30
ΔIP50
ΔIP80
ΔIP120
ΔIP200
ΔIP300
Diameter
15 mm
30 mm
50 mm
80 mm
120 mm
200 mm
300 mm
I max
36 A
65 A
85 A
160 A
250 A
400 A
630 A
Reference
4750 6015
4750 6030
4750 6050
4750 6080
4750 6120
4750 6200
4750 6300
ΔIP circular split-core balance transformers
ΔIP-R50
ΔIP-R80
ΔIP-R120
Diameter
50 mm
80 mm
120 mm
I max
85 A
160 A
250 A
Reference
4750 6051
4750 6081
4750 6121
ISOM DIGIWARE - 546780C - SOCOMEC
WR/TFR rectangular solid-core balance transformers
WR70x175
WR115x305
WR150x350
TFR200x500
Diameter
70 x 175 mm
115 x 305 mm
150 x 350 mm
200 x 500 mm
I max
500 A
500 A
500 A
500 A
Reference
4795 0717
4795 1130
4795 1535
4795 2050
4.2.1.2. Dimensions
ΔIP circular solid-core balance transformers
A. Width
B. Diameter
C. Spacers
D. Rear bracket spacers
E. Depth
F. Height
G. Diameter of fixing screws
Type
A (mm)
B (mm)
C (mm)
D (mm)
E (mm)
F (mm)
G (mm)
Weight (kg)
ΔIP diameter 15
53
17.3
25
50
26
81
M4
0.10
ΔIP diameter 30
92
30
50
85
26
103.5
M4
0.15
ΔIP diameter 50
102.5
50
50
90
26
125
M5
0.27
ΔIP diameter 80
116
80
75
105
26
142.5
M5
0.38
ΔIP diameter 120
163
120
100
150
26
182.5
M6
0.72
ΔIP diameter 200
253
200
150
175x41.2
51
274
M6
1.74
ΔIP diameter 300
370
300
200
250x41.5
50
390
M6
3.60
A
Ø B
C
E
F
D
G
ΔIP-R circular split-core balance transformers
ΔIP
Ø 50 mm
Ø 80 mm
Ø 120 mm
A
160
204
252
B
49
79
119
C
30
30
30
D
77
108
149
T
200
260
328
F
116
156
204
Weight (g)
380
850
1500
100
61
80
50
25
25
25
Ø 6,4
40
28
8
10
21
55
25
D
E
F
C
A
B
62
ISOM DIGIWARE - 546780C - SOCOMEC
WR/TFR rectangular solid-core balance transformers
G
F
C
E
I
2.5
14
H
D
A
B
Type
A
(mm)
B
(mm)
C
(mm)
D
(mm)
E
(mm)
F
(mm)
G
(mm)
H
(mm)
I
(mm)
Weight
(kg)
WR 70x175
70
175
225
85
22
46
261
176
7.5
2.9
WR 115x305 115
305
360
116
25
55
402
240
8
6.3
WR 150x350 150
350
415
140
28
55
460
285
8
8.2
A. Gateway width
B. Gateway length
C. Spacers
D. Half-height
E. Depth of mounting spacer
F. Depth
G. Width
H. Height
I. Width of oblong fixing holes
F
1 Détail pour fixation du tore
Ø 2 .5
Ø 6 .1
D
B
G
H
A
1
Type
A
(mm)
B
(mm)
D
(mm)
F
(mm)
G
(mm)
H
(mm)
Weight
(kg)
TFR 200x500
200
500
140
62
585
285
7.2
A. Gateway width
B. Gateway length
D. Half-height
F. Depth
G. Width
H. Height
4 .2 .2 . Adapter ISOM T-15
Use the ISOM T-15 adapter to ensure the conversion and analysis of the signal between the output of the locating
core balance transformer and the fault-locating device ISOM Digiware F-60.
It can be mounted directly onto the core balance transformers ΔIP (diameter >30mm) or DIN rail.
It comes with all the connectivity required for any kind of application.
Do not install the adapter close to or touching any live parts, or close to breakers or other equipment
carrying dangerous voltage.
1
2
Attachments for core balance transformer
ISOM DIGIWARE - 546780C - SOCOMEC
STAGE 2
1
2
STAGE 1
4 .2 .3 . TE solid-core current sensors
The TE solid-core current sensors are used to set up measurement points in a new or existing installation. They are
easy to integrate as they are compact and respect the pitch of the circuit breakers. A wide range of accessories are
also available for direct fitting on all type of cabling (cable, flexible or rigid busbar) or on a DIN rail support or plate.
Thanks to the specific link, they are recognised by the ISOM Digiware and a high level of overall accuracy for the
measurement chain is guaranteed.
4.2.3.1. Range
TE-18
TE-18
TE-25
TE-35
TE-45
TE-55
Pitch
18 mm
18 mm
25 mm
35 mm
45 mm
55 mm
Nominal
current
range In
5 to 20 A
25 to 63 A
40 to 160 A
63 to 250 A
160 to 630 A
400 to 1000 A
I max
24 A
75.6 A
192 A
300 A
756 A
1200 A
Reference
4829 0500
4829 0501
4750 6052
4829 0503
4829 0504
4829 0505
TE-90
Pitch
90 mm
Nominal
current
range In
600 to 2000 A
I max
2400 A
Reference
4829 0506
ISOM DIGIWARE - 546780C - SOCOMEC
4.2.3.2. Dimensions
L
P
H
ØW
L
P
H
ØW
L
P
H
T
W
L
P
H
T
W
Dimensions in mm TE-18
TE-25
TE-35
TE-45
TE-55
Pitch
18
25
35
45
55
LxHxD
28 x 45 x 20
25 x 65 x 32.5
35 x 71 x 32.5
45 x 86 x 32.5
55 x 100 x 32.5
Ø W
ø 8.4
-
-
-
-
W
-
13.5 x 13.5
21 x 21
31 x 31
41 x 41
(T)
-
17.5
17.5
19.5
21.5
3.54
90
0.08
2.2
0.77
19.7
1.42
36
=
=
=
= 2.52 / 64
4.96
126
0.97
24.6
Dimensions in/mm TE-90
ISOM DIGIWARE - 546780C - SOCOMEC
4 .2 .4 . TR split-core current sensors
The TR split-core current sensors are used to set up measurement points in a new or existing installation without
interfering with its cabling. Thanks to the specific link, they are recognised by the DIRIS B and the overall accuracy of
the measurement chain is guaranteed.
4.2.4.1. Range
Four models are available from 25A to 600A to analyse several types of loads.
TR-10 / iTR-10
TR-14 / iTR-14
TR-21 / iTR-21
TR-32 / iTR-32
Cable passage
diameter
Ø 10 mm
Ø 14 mm
Ø 21 mm
Ø 32 mm
Nominal current
range In
25 - 63 A
40 - 160 A
63 - 250 A
160 - 600 A
Recommended
cable section
6 mm² (iTR-10)
10 mm² (iTR-14)
50 mm² (iTR-21)
50 mm² (iTR-32)
Maximum l
75.6 A
192 A
300 A
720 A
Part number
4829 0555 / 4829 0655
4829 0556 / 4829 0656
4829 0557 / 4829 0657
4829 0558 / 4829 0658
4.2.4.2. Dimensions
D
B
C
A
E
Dimensions in/mm
TR-10 / i TR-10
TR-14 / i TR-14
TR-21 / iTR-21
TR-32 / iTR-32
A
1.74
44
2.63
67
2.56
65
3.38
86
B
1.02
26
1.14
29
1.45
37
2.08
53
C
1.10
28
1.10
28
1.69
43
1.85
47
D
-
0.55
14
0.82
21
1.26
32
E
-
0.59
15
0.90
23
1.30
33
Diameter
0.39
10
0.55
14
0.82
21
1.26
32
ISOM DIGIWARE - 546780C - SOCOMEC
4 .2 .5 . TF flexible current sensors
The TF flexible current sensors use the Rogowski principle, covering a wide current range without saturation.
Their flexible design and easy opening system enables a quick installation inside electrical panels, making them
particularly well suited for adding measuring points in existing electrical installations, especially when space is limited.
The secure lock technology prevents non voluntary openings of the Rogowski rope.
4.2.5.1. Range
Six models are available, covering a large current range up to 6000 A with openings of different shapes and sizes.
They include a compact and self-supplied integrator, required to shape the current signal.
Due to the specific RJ12 connection, the TF current sensors can only be used with DIRIS Digiware
I, DIRIS B and DIRIS A-40. Used in conjunction with these PMD equipped with RJ12 connectors,
the overall accuracy of the measurement chain is guaranteed.
TF-40
TF-80
TF-120
TF-200
TF-300
TF-600
Ø (mm)
40
80
120
200
300
600
I nom. (a.c.)
100 … 400A
150 … 600A
400 … 2000A
600 … 4000A
1600 … 6000A
1600 … 6000A
Part number
4829 0573
4829 0574
4829 0575
4829 0576
4829 0577
4829 0578
4.2.5.2. Dimensions
Dimensions in/mm
TF-40
TF-80
TF-120
TF-200
TF-300
TF-600
Diameter D
1.57
40
3.15
80
4.72
120
7.87
200
11.81
300
23.62
600
Perimeter P
4.96
126
9.88
251
14.84
377
24.72
628
37.09
942
74.21
1885
Integrator
8.04 x 0.75 x 0.6
128 x 19 x 15
L
D
3.94
3.94
Ø 0.33
100
100
Ø 8 .3
ISOM DIGIWARE - 546780C - SOCOMEC
4 .2 .6 . Adapters for 5A sensors
The adapter lets you use a standard sensor supplying a 1A or 5A current to the secondary sensor. Using this kind
of sensor does not guarantee the overall accuracy of ISOM Digiware + sensor, as it depends on the accuracy of the
associated sensor (see standard "IEC 61557-12 annex D" for more information). The primary current is max. 10000 A
/ 5 A or 2000 A / 1 A.
4.2.6.1. Range
5A adapter
I name.
5 A
I max.
6 A
Reference
4829 0599
4.2.6.2. Dimensions
L
P
W
H
L
P
W
H
Dimensions in/mm
5A adapter
LxHxD
28 x 20 x 45
Aperture (W)
ø 8.4
ISOM DIGIWARE - 546780C - SOCOMEC
5. INSTALLATION
The following paragraphs describe the installation of ISOM Digiware and associated sensors.
5.1. Recommendations and safety
Refer to the safety instructions (section "2) Hazards and Warnings", page 5)
5.2. Installing ISOM Digiware units
5 .2 .1 . ISOM Digiware L-60, F-60, T-15 – mounted on DIN rail
L
1
2
1.38 in
35 mm
0.29 or 0.59 in
7.5 or 15 mm
PLEASE NOTE:
• When the ISOM T-15 adapter is mounted on DIN rail, do not fix the core balance transformer ΔIP to
the T-15
• Make sure the housing (e.g. enclosure) is large enough to take the ISOM Digiware L-60 (enough
thermal ventilation around the device)
• Make sure that the DIN rail is earthed
• Do not install the ISOM T-15 or ISOM Digiware F-60 close to or touching any live parts, or close to
breakers or other equipment carrying dangerous voltage (does not apply to ISOM Digiware L-60)
ISOM DIGIWARE - 546780C - SOCOMEC
5 .2 .2 . ISOM Digiware L-60, F-60 – board-mounted
0.19 in
5 mm
3.94 in
100 mm
Type of screw: M4
Tightening torque: 0.5 Nm
Washer diameter 0.47 in / 12 mm max.
If using a metal bracket, make sure it is earthed.
5.3. Installing TE solid-core sensors
5 .3 .1 . Mounting accessories
The mounting accessories supplied with the sensors are listed below:
Reference
Pitch
DIN rail and plate
mounting
DIN rail mounting
Plate mounting
Busbar mounting
4829 0500
4829 0501
TE-18
18 mm
x 1
4829 0502
TE-25
25 mm
x 2
x 4
4829 0503
TE-35
35 mm
x 2
x 4
x 2
4829 0504
TE-45
45 mm
x 2
x 4
x 2
4829 0505
TE-55
55 mm
x 2
x 4
x 2
4829 0506
TE-90
90 mm
x 2
x 6
ISOM DIGIWARE - 546780C - SOCOMEC
5 .3 .2 . DIN rail mounted
TE-18 -> TE-55
TE-90
2
1
Removing clamps
or
ISOM DIGIWARE - 546780C - SOCOMEC
Note: Fix sensor TE-90 to the DIN rail to make it easier to install. This is a temporary installation. Use the clamps to
install the TE-90 sensors on the DIN rail.
5 .3 .3 . Plate mounting
TE-18
1x
diameter 0.17 /
4.2 M4 max
1 Nm
0.81
20.5
1.05
26.8
1
1
2
2
2
2
3
3
TE-25 - > TE-55
4x
diameter 0.20
/ 5.2 M5 max
1 Nm
ISOM DIGIWARE - 546780C - SOCOMEC
TE-90
2
1
Removing clamps
x6
diameter 0.20
diameter 5 .2
Note: Use the clamps to install the TE-90 sensors on the board.
5 .3 .4 . Installing on a cable with clamping collar
TE-18
TE-25 - > TE-55
2
1
3
ISOM DIGIWARE - 546780C - SOCOMEC
TE-90
2
1
Removing clamps
I
NB: Use the clamps to install the TE-90 sensors on a cable with clamping collar.
Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could
cause an electric shock, burn or arc flash.
Ref. IEC 61010-2-032
5 .3 .5 . Bar mounting
TE-35 - > TE-55
A
A
A
C
B
Installation options:
A+B, A+C
0.4 Nm, 4mm
key
B
C
ISOM DIGIWARE - 546780C - SOCOMEC
TE-90
or
Tighten the jaws on both
sides of the cable by apply-
ing pressure .
The jaws must be per-
pendicular to the holding
notches .
60x10 mm
50x10 mm
I
I
2
1
Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could
cause an electric shock, burn or arc flash.
Ref. IEC 61010-2-032
ISOM DIGIWARE - 546780C - SOCOMEC
5 .3 .6 . Sensors assembly
TE-18
TE-25 - > TE-55
TE-35 - > TE-55
1.42
36
Staggered assembly
2x
Linear mounting
1x
Staggered assembly
Mounting accessories for combining sensors:
Reference
Linear assembly
Staggered assembly
4829 0598
x30
These accessories must be ordered separately.
5 .3 .7 . Sealing accessories for sensors
2
1
Reference
Sealing case for terminal
4829 0600
x20
These accessories must be ordered separately.
ISOM DIGIWARE - 546780C - SOCOMEC
5.4. Installing TR split-core sensors
5 .4 .1 . Cable mounting
2
Install on 300 V
insulated cables only!
1
K
L
I
3
Sharp edges
recommended
installation
Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could
cause an electric shock, burn or arc flash.
Ref. IEC 61010-2-032
Before closing the TR sensor, check that the air gap is clean (no contamination or corrosion)
ISOM DIGIWARE - 546780C - SOCOMEC
5.5. Stranded sensors TE mounting
5 .5 .1 . Cable or bus bar-mounting
!
1
2
3
4
I
DIRIS Digiware I
DIRIS B
DIRIS A-40
=
=
=
=
=
=
=
=
Centred position for the best measurement
Centred position for the best measurement
=
=
=
=
=
=
=
=
Do NOT clamp or pull out NON-
INSULATED conductors carrying
DANGEROUS VOLTAGE which
could cause an electric shock,
burn or arc flash.
Ref. IEC 61010-2-032
L1
L2
(1)
ISOM DIGIWARE - 546780C - SOCOMEC
5.6. Installing the 5A adapter
4
3
1
2
5A secondary
current
transformer
Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could
cause an electric shock, burn or arc flash.
Ref. IEC 61010-2-032
ISOM DIGIWARE - 546780C - SOCOMEC
6. CONNECTION
6.1. Connecting ISOM Digiware
DISPLAY
ISOM Digiware D-x5
DIRIS Digiware U
L-60, L-60h
VOLTAGE
MEASUREMENT
(OPTIONAL)
INSULATION
MONITORING
DEVICE (IMD)
1
2
3
4
7
7
8
5
6
ETHERNET
1
Power
supply
24VDC
2
COM
RS485
Modbus
3
U
300 Vac
ph/n
4
1x I/O
input
PTC
120°C
(ref: 4729
0560)
5
4x I/O
24 VDC
/ 40 mA
max
6
U/PE
inputs
L-60:
0-480
VAC/VDC
Ph/Ph
6
U/PE
inputs
L-60h:
0-250
VAC/VDC
Ph/Ph
7
2x alarm
outputs
250Vac
or 30Vdc,
3A max
8
FE input
9
1x digital
output
ON/OFF
24 VDC -
1A max
x }
0.2 - 2.5
mm2
x= 7 mm
0.14 - 1.5
mm2
x= 7 mm
0.2 - 2.5
mm2
x= 7 mm
0.2 - 1.5
mm2
x= 10 mm
0.2 - 1.5
mm2
x= 10 mm
0.2 - 2.5 mm2
x= 10 mm
0.2 - 2.5
mm2
x= 10 mm
0.2 - 2.5
mm2
x= 10 mm
0.14 - 1.5
mm2
x= 7 mm
(1) Earth must not be used in a neutral IT system
ISOM DIGIWARE - 546780C - SOCOMEC
Important:
• Only use Digiware bus RJ45 cables (UTP RJ45 straight, twisted pair, unshielded, AWG24, 600V CAT
5, -10 / +70°C in accordance with IEC 61010-1 version 3.0) between all the Digiware bus modules.
• The points in the table above are defined as SELV in accordance with IEC 61010: 1 to 5, 8, 9, as well
as the core balance transformer inputs/outputs of the F-60.
• • When connecting, make sure you separate the low voltage (LV) section and the very low voltage
(SELV) section to prevent any risk of electric shock.
• Conductors should be clamped to the closest terminals to avoid them detaching themselves and
reducing the insulation distances.
F-60
Alert notification D-15h
Digiware Bus
terminals
Locating core balance transformers ΔIP + adapter T-15
Current
sensors
Alert notification D-55h (without Digiware link)
INSULATION
FAULT-LOCATING
DEVICE
ALERT NOTIFICATION
DISPLAY FOR
SURGERIES (ONLY
AVAILABLE WITH
L-60h)
ETH
1
9
ISOM DIGIWARE - 546780C - SOCOMEC
Description of the terminals
ISOM Digiware D-15h
DIGIWARE
DIGIWARE
DIGIWARE
BUS
!
DIGIWARE
BUS
!
ISOM Digiware D-55 / D-55h / D-75
NC
RS485
LIYCY-CY
MASTER
Supply
24VDC
(20 W max)
Protection 1A gG
DIGIWARE
ETHERNET
ETHERNET
DIGIWARE
BUS
!
ISOM Digiware L-60
DIGIWARE BUS
14 11
Alarme 1
12
24 21
Alarme 2
22
FE
KE L1 L2
θ >
C in
4
3
2
1
C out
θ >
PTC (120ºC)
Exemple
de câblage
en sortie
Exemple
de câblage
en entrée
Digiware Bus: Digiware bus connection with other
equipment and the Digiware range
14 - 11 - 12: alarm relay output 1
24 - 21 - 22: alarm relay output 2.
It is not permitted for use on a 230V relay or a SELV
signal.
You can use different phases on the 2 output relays, but
they must be from the same three-phase network.
The relay's dry contacts should be protected with a 2A gG
fuse => use up to 2A with resistive load.
And T3AH250V => use up to 3A with resistive load.
EARTH FE: connection to the earth
Upper terminal
Lower terminal
KE - L1 - L2: network voltage Un + earth of booster
θ >: link to la temperature probe (PTC)
C out: shared output link
(Output: 12-24VDC Min 600Ω 40 mA max Input: Max
100Ω)
C in: shared input link
(Max 100Ω)
1 - 2 - 3 - 4: input or output connection (as per
configuration)
ISOM Digiware F-60
L-60 / L-60h connection
DIGIWARE BUS
RJ45
12
14
OUTPUT
24V (1A MAX)
11
I 04
I 05
I 06
I 01
I 02
I 03
!
Digiware bus: Digiware bus connection with other
Digiware devices
11 - 12 - 14: alarm relay output (fuse 1A gG)
I01 - I02 - I03 - I04 - I05 - I06: ISOM T-15 connection
(to core balance transformers) or current sensors TE/TR/
TF
FE
L1 L2
KE
FE
L1 L2
KE
Not allowed
Authorised
ISOM DIGIWARE - 546780C - SOCOMEC
IMPORTANT:
• Screw on the "network to be monitored" connector of the ISOM Digiware L-60 to ensure the
insulation is monitored.
• On all your ISOM Digiware devices, use RJ plugs at the RJ-45 connectors left free to prevent the
accumulation of conductive dust.
• A single ISOM Digiware L-60 insulation monitoring device should be connected or active on each
network or interconnected IT circuit.
• Always observe the auxiliary power supply voltage shown on the device: 24 VDC ± 10%.
• Use a P30 24 VDC power supply, available as 30 W (ref. 4729 0603), or protect the device with a 1
A gG 24 VDC fuse.
• Provide a 2A gG fuse on main voltage inputs.
ISOM DIGIWARE - 546780C - SOCOMEC
6.2. Connecting the current sensors
6 .2 .1 . Connection concept
ISOM Digiware F-60
Current sensors TE/TR/TF
or locating core balance
transformers ΔIP
STAGE 2
1
2
STAGE 1
Important:
• To connect the current sensors or locating core balance transformers, use SOCOMEC cables or equivalent only,
RJ12 straight cables, twisted pair, unshielded, 600 V -10 degC / +70degC in accordance with IEC 61010-1
version 3.0.
• We recommend that current sensors are installed in the same direction.
• Always connect input I01 first.
• In the same order as inputs I01 to I06, start by cabling the locating core balance transformers, followed by the
current sensors.
ISOM DIGIWARE - 546780C - SOCOMEC
6 .2 .2 . Details of the RJ12 connections for each current sensor
ΔIP/ ΔIP-R
TE
Mounting the ISOM T-15 on a locating core balance
transformer.
(T-15: do not mount on a busbar!)
RJ12
SOCOMEC
cable for
current sensors
ISOM Digiware F-60
TE-18 to TE-55
TE-90
TR
TF
SOCOMEC cable for
current sensors
Do not bring into contact
with dangerous voltages
ISOM Digiware F-60
SOCOMEC
cable for
current sensors
Cover
sealing
1
3
2
ISOM Digiware F-60
ISOM DIGIWARE - 546780C - SOCOMEC
6.3. Connecting to the electrical network and circuits
The insulation monitoring system ISOM Digiware is suitable for single-phase, two-phase, three-phase and continuous
networks.
The insulation monitoring module ISOM Digiware L-60 ensures the insulation of a complete powered IT system is
monitored. It automatically detects a DIRIS Digiware U module to ensure PMD measuring.
Each ISOM Digiware F-60 fault-locating module can monitor multiple live circuits at the same time. This approach
allows great flexibility in terms of where it is fitted in the installation.
The circuits are monitored (faults located on AC and DC and load currents measured on AC only) using several types
of current sensor (closed, open, flexible) selected depending on the new, existing or high-current installations.
The link between each ISOM Digiware F-60 fault-locating module and its associated sensors is made using specific
cables. With this connection you can quickly and easy install the units without any risk of cabling error and in
complete safety. The connected sensors are automatically detected.
In addition, ISOM Digiware can identify the majority of load types to be measured: single-phase, three-phase with or
without neutral using 1, 2, 3 or 4 sensors for balanced or unbalanced loads.
The overall accuracy of the ISOM Digiware + sensors measurement chain is guaranteed. To guarantee this accuracy,
SOCOMEC current sensor connection cables or equivalent must be used.
6 .3 .1 . Configurable loads based on the network type
The following table summarises the loads which can be configured based on the system's network type
Network type
Configurable load
1P+N
1P+N – 1CT
2P
2P – 1CT
2P+N
2P+N – 2CT / 2P – 1CT / 1P+N – 1CT
3P*
3P – 3CT / 3P – 2CT / 3P – 1CT
3P+N
3P+N – 4CT / 3P+N – 3CT / 3P+N – 1CT / 3P – 3CT / 3P – 2CT / 3P – 1CT / 1P+N – 1CT
(*) Note: Single-phase loads cannot exist on a 3P network.
ISOM DIGIWARE - 546780C - SOCOMEC
6 .3 .2 . Description of the main network and circuit combinations
Legend:
3AC / IMD + FLD + load current monitoring
3
3
M
M
1
AC motor
3
3
M
M
1
DC motor
3
3
M
M
1
Current
sensor
3
3
M
M
1
Balanced
load
3
3
M
M
1
Unbalanced
load
3
3
M
M
1
Fault-locating core
balance transformer
3
3
M
M
1
2 A gG
L-60
KE L1
FE
L2
L1
L2
L3
F-60
1
I04
I05
I06
I01
I02
I03
3
3
3
U
V1 V2 V3
VN
Three-phase network
without neutral with 3
locating core balance
transformers and 3
current sensors to fully
monitor 3 circuits
Voltage readings
+ earth (L-60)
Voltage terminals
(U-xx)
Terminals for sensors / core
balance transformers (F-60)
Three-phase
balanced
loads
Locating core balance
transformers
Current
sensors (CT)
Each current input is individual; see below for some connection examples:
6.3.2.1. ISOM Digiware F-60
Three-phase without neutral - 3 balanced loads
3P / IMD + FLD + current measurement
L-60
KE L1
FE
L2
L1
L2
L3
F-60
1
I04
I05
I06
I01
I02
I03
3
3
3
U
V1 V2 V3
VN
ISOM DIGIWARE - 546780C - SOCOMEC
Three-phase with neutral - 3 circuits
3P+N / IMD + FLD + input current measurement
U
V1 V2 V3
VN
L-60
KE L1
FE
L2
N
3
3
3
L1
L2
L3
1
F-60
I04
I05
I06
I01
I02
I03
Single-phase - 3 circuits
1P+N / IMD + FLD
F-60
I04
I05
I06
I01
I02
I03
M
M
M
L-60
KE L1
FE
L
N
1
U
V1 V2 V3
VN
L2
Single-phase - 6 circuits
1P+N / IMD + FLD
L-60
KE L1
FE
L2
L
N
1
F-60
I04
I05
I06
I01
I02
I03
M
M
M
M
M
M
ISOM DIGIWARE - 546780C - SOCOMEC
Continuous current - 6 circuits
DC / IMD + FLD
L-60
KE L1
FE
L2
L+
L-
1
F-60
I04
I05
I06
I01
I02
I03
M
M
M
M
M
M
Note relating to connections:
The Easy Config software can also be used to select numerous other configuration variants for the types of loads and
associated network voltages. (see section 10.1.2.2.)
6 .3 .3 . Coupled networks
6.3.3.1. Simple coupled networks without fault-locating options
In the case of coupled networks, you must ensure that only one IMD is active. You can do this by setting and using
I/O configurations for the ISOM Digiware L-60 (see section 10.1.2.4 on how to configure I/O in "disconnection"
mode).
Principle diagram:
Digiware
Digiware
Exclusion IMD
NOTE: Some applications may require you to manage the positions of general cut-off devices of the 2 transformers,
as part of excluding the IMD.
6.3.3.2. Simple coupled networks with fault-locating options
When using fault location on coupled networks, the operability of the IMD ISOM Digiware L-60 must be guaranteed
so it remains active with the whole set of ISOM Digiware F-60 locating devices.
This management is made possible by the 2 ISOM Digiware systems communicating with one another via an inter-
screen Ethernet communication D-X5.
ISOM DIGIWARE - 546780C - SOCOMEC
Principle diagram:
Digiware
MASTER DGW
Digiware
Ethernet
Exclusion IMD
+ exclusion DGW
NOTE: Some applications may require you to manage the positions of general cut-off devices of the 2 transformers,
as part of excluding the IMD.
6.3.3.3. Complex coupled networks
In the case of complex coupled networks (transformers > 2 and/or if using multiple general cut-off devices), it must
always be ensured that just one IMD is active on the interconnected network.
NOTE: For more details on the cabling and settings required for managing the network coupling, please see the
technical instructions, "Isom Digiware architecture".
ISOM DIGIWARE - 546780C - SOCOMEC
7. DIGIWARE BUS
7.1. Principle
Display
ISOM Digiware D
Option for PMD:
Measuring module U
DIRIS Digiware U-xx
Module IMD
ISOM Digiware L-60
Module FLD
ISOM Digiware F-60
Terminals DI-
RIS Digiware
ISOM Digiware is a system which must comprise the following elements:
• A remote display ISOM Digiware D-x5
• An ISOM Digiware L-60 IMD module
• A Digiware bus terminal resistor (ref. 4829 0180). This is supplied with the ISOM Digiware D display.
It can also be linked to:
• One or multiple ISOM Digiware F-60 FLD measuring modules for locating insulation faults when live.
• One or multiple adapter modules for ISOM T-15 locating core balance transformers.
• A U measuring module to make use of the PMD functionality.
When a DIRIS Digiware U-xx module is added to the system, always make sure you adjust the communication
baudrate of the Digiware bus to 115200 bauds in the Easy Config software from the DIRIS Digiware U-xx module.
7 .1 .1 . Digiware bus connection cable
Length (m)
Quantity
Reference
0.06
1
4829 0189
0.1
1
4829 0181
0.2
1
4829 0188
0.5
1
4829 0182
1
1
4829 0183
2
1
4829 0184
5
1
4829 0186
10
1
4829 0187
50 m reel + 100 connectors
4829 0185
Use the shortest possible length of cable to optimise the electromagnetic emissions.
The total max. width must not exceed 100 metres.
Use only SOCOMEC cables for the Digiware bus.
ISOM DIGIWARE - 546780C - SOCOMEC
7 .1 .2 . Digiware Bus Termination
Quantity
Reference
1
4829 0180
A DIRIS Digiware bus terminal resistor is supplied with every ISOM Digiware D display.
7.2. Sizing of the power supply
NC
RS485
LIYCY-CY
MASTER
Supply
24VDC
(20 W max)
Protection 1A gG
DIGIWARE
ETHERNET
ETHERNET
DIGIWARE
BUS
!
ISOM Digiware units are powered by a single 24 VDC port on the ISOM Digiware D screen.
2 power units are available:
• The P15 24 VDC power unit is available as a 15 W version (ref. 4829 0120):
• 230 VAC / 24 VDC – 0.63 A - 15 W
• Modular format
• Dimensions (H x W): 90 x 36 mm
The P30 24 VDC power unit is available as a 30 W version (ref. 4729 0603):
• 230 VAC / 24 VDC – 1.75 A - 30 W
• Modular format
• Dimensions (H x W): 90 x 54 mm
7 .2 .1 . Equipment consumption
Product
Power supplied (W)
Power consumed (W)
Power supply
P15 230V / 24V
15
P30 230V / 24V
30 (*)
Cables
25 metre package
0.75
System interface
ISOM Digiware D-x5
2.5
IMD / voltage module
ISOM Digiware L-60 / L-60h
2.3
DIRIS Digiware U-xx
0.72
ISOM DIGIWARE - 546780C - SOCOMEC
Module FLD
ISOM Digiware F-60
0.5
Single-point alert report
ISOM D-15h
0.5
Repeater
DIRIS Digiware C-32
1.5
Single-point display
ISOM T-15
0.05
(*) Max 20 W for use by the Digiware system
7 .2 .2 . Calculation rules for the max . number of products on the Digiware bus
The total power consumed by the equipment connected to the Digiware bus must not exceed the power from the
24 VDC power supply.
Size with P15 power supply (ref: (4829 0120) delivering 15 W
You can use the following, for example:
• 1 ISOM Digiware D-75 (2.5 W) display
• 1 IMD ISOM Digiware L-60 (2.3W) module
• 25 metres of cable (0.75 W)
and
• 2 FLD ISOM Digiware F-60 (1 x 0.5 = 5.5 W) modules
• 6 ISOM T-15 adapters (66 x 0.05 = 3.3 W)
g Total power = 14.35 W
Dimensioning with a P30 power supply (ref. 4729 0603) delivering a maximum usable power of 20 W by
the Digiware system
You can use the following, for example
• 1 ISOM Digiware D-75 (2.5 W) display
• 1 ISOM Digiware L-60 IMD module (2.3 W)
• 1 DIRIS Digiware voltage module U-xx (0.72 W)
• 25 metres of cable (0.75 W)
and
• 17 FLD ISOM Digiware F-60 (17 x 0.5 = 8.5 W) modules
• 102 ISOM T-15 adapters (102 x 0.05 = 5.1 W)
g Total power = 19.87 W
ISOM DIGIWARE - 546780C - SOCOMEC
7 .2 .3 . Digiware bus repeater
Whenever the power consumption is higher than 15 or 20 W (depending on the type of power supply used) or the
distance is greater than 100 m, a DIRIS Digiware C-32 repeater is required. In an ISOM Digiware system, a maximum
of 2 repeaters may be used.
DIRIS Digiware
C-32 repeater
Reference
4829 0103
Configuration example:
100 m max
or power consumption 20 W max
100 m max
or power consumption
20 W max
Digiware Bus Termination
ISOM Digiware D-x5
24 VDC power supply
24 VDC power supply
U-xx
L-60
C-32
F-60
The DIRIS Digiware U voltage module must be located upstream of the repeater.
The repeater requires a 24VDC power supply.
DIRIS Digiware C-32
Supply
24VDC
24VDC
DIGIWARE BUS
RJ45
IN
OUT
ISOM DIGIWARE - 546780C - SOCOMEC
8. STATUS LEDS, BUTTONS AND AUTO-ADDRESSING
8.1. Status LEDs and buttons
These LEDs can be used to find out the status of the product at any time. Use specific buttons to go straight to the
devices' main functions.
8 .1 .1 . L-60
ON
INJ
FAULT
ALARM 1
RESET
TEST
INJ
START/STOP
ALARM 2
COM
FE
14
11
12
1
C
Output
C
Input
2
3
4
22
24
21
Alarm2
Alarm1
L1
L2
DIGIWARE BUS
θ >
L-60t
ISOM
KE
Power supply (green)
Insulation alert ALARM1
Insulation alert ALARM2
Manual RESET button
Manual test button
(TEST)
Status LED for FLD booster (INJ)
Manual boost START/
STOP button: this button
is mainly used in the
portable locating phase.
It is prioritised in Settings
mode (see § 10.1.2)
System fault (red)
Communication (amber)
Addressing button
LED state
Fixed
Blinking
Pulse
ON
In operation
The screen communicates with
the device to retrieve the values/
data to display.
10 seconds – on request by
a Modbus control command
to identify the device (remote
screen…)
1 second to start-up
FAULT
An alarm (logical/analogue) is
active (does not take priority if
there is a setup alarm at the same
time)
At least one startup alarm is
active.
1 second to start-up
COM
Addressing problem.
Address OK
1 second to start-up and when a
frame received is processed
ALARM 1
Alarm sent when lowest threshold
is not met – ALARM1
ALARM 2
Alarm sent when lowest threshold
is not met – ALARM2
INJ
Injection in fault-locating mode
is ON
When the device is in manual test
mode
ISOM DIGIWARE - 546780C - SOCOMEC
8 .1 .2 . F-60
1
2
3
4
5
6
ON
FAULT
COM
TEST
RESET
ALARM
F-60
ISOM
Power supply (green)
Alarm channels 1 to 6
(amber)
System fault (red)
Communication (amber)
Addressing button in
config mode
Test (long press) / Reset
(short press) in operating
mode
LED state
Fixed
Blinking
Pulse
ON
In operation
The screen communicates with
the device to retrieve the values/
data to display.
10 seconds – on request via a
Modbus command to identify the
device (remote screen…)
1 second to start-up
FAULT
An alarm (logical/analogue) is
active (does not take priority if
there is a setup alarm at the same
time)
At least one setup alarm is active
(current sensor disconnected, V/I
not compatible)
1 second to start-up
COM
Addressing problem.
Address OK
1 second to start-up and when a
frame received is processed
/ALARM
At least one of the 6 channels is
showing an insulation fault (the
LED(s) for the faulty channels are
also constantly on)
Presence of a saturation current
(the LED(s) for the faulty channels
are flashing) or the measuring
system is blinded
Problem connecting the locating
core balance transformer or the
T-15
Manual test in progress
8 .1 .3 . T-15
ISOM T-15
Insulation alarm (amber)
LED state
Fixed
Blinking
Pulse
/ALARM
Presence of an insulation fault
on the remote device monitored
by the connected core balance
transformer
Problem with connecting to the
core balance transformer or the
measuring system is blinded
ISOM DIGIWARE - 546780C - SOCOMEC
8 .1 .4 . Autotest
In order to ensure a high degree of safety when measuring the insulation and in operation, ISOM Digiware offers
advanced autotesting functions.
After powering on the devices, all their internal measurement functions as well as the data memories and
connections to the network and the PE protection conductor are tested.
You can follow the progress of the autotest option on the D-x5 screen (Manual TEST message).
During operation, you can also run the auto-test at any time by pressing the TEST button (locally or remotely via the
input on the ISOM Digiware L-60).
The ALARM 1 and ALARM 2 signalling relay can be configured to switch if the auto-test fails (see section 11.1.4)
To ensure the smooth running of the system, Socomec recommends you regularly run the AUTOTEST.
8.2. Auto-addressing
In auto-addressing mode, you can automatically allocate addresses to ISOM and DIRIS Digiware devices, connected
to the remote ISOM Digiware D-x5 displays. The addresses are allocated manually on other devices (DIRIS A,
COUNTIS…)
Two modes are available:
• Mode 1 - Auto-detection and automatic addressing
• Mode 2 - Auto-detection and address selection
Mode 1 is done from the ISOM Digiware D-x5 display (see the relevant instructions on this)
Mode 2 is carried out from a PC with Easy Config installed.
The ISOM Digiware L-60 and ISOM Digiware F-60 modules have an auto-addressing option.
They are always connected to an ISOM Digiware D-x5 display
Note: During the auto-addressing process, the RS485 line is reserved for allocating addresses and no other
exchange of data is possible at this time.
ISOM DIGIWARE - 546780C - SOCOMEC
9. COMMUNICATION
9.1. General information
ISOM Digiware communicates via RS485 using the Modbus protocol. RS485 communication is available at a single
point on the ISOM Digiware D-55 or D-75 display.
It takes place via an RS485 serial link (2- or 3-wire) in accordance with the Modbus RTU protocol.
With the RS485 link, ISOM Digiware can be connected directly to a PC to retrieve the data.
The Modbus protocol requires a dialogue with a master/slave structure. The mode of communication is the RTU
(Remote Terminal Unit). In a standard setup, an RS485 link enables the interconnection of 32 RS485 devices (ISOM
Digiware D-55 or D-75 counting as one device), to a PC or a PLC etc. over a distance of 1,200 metres.
Example of the architecture of an ISOM Digiware D-55 or D-75 screen:
Supervision
MODBUS TCP
Web server
WEBVIEW (ISOM Digiware D-75)
ISOM Digiware D-55 / D-75
Digiware terminals
9.2. RS485 and ISOM Digiware bus rule
A certain number of rules must be respected when ISOM Digiware is connected using RS485. These rules are set
out in the paragraphs below.
9 .2 .1 . Connection with the D-55 or D-75 screen
The ISOM Digiware D-55 or D-75 screen is a master device of the RS485 bus and links to the DIRIS Digiware bus. It
is used like an Ethernet gateway.
They can be placed anywhere in the RS485 link.
The following rules must be observed:
• A 120 Ω resistor must be added at the start of the RS485 link
• A 120 Ω resistor must be added at the end of the RS485 link
• A terminal must be added at the end of the Digiware bus.
You can show 32 devices on an ISOM Digiware D-55/D-75 display.
ISOM DIGIWARE - 546780C - SOCOMEC
Apart from acting as an Ethernet gateway, the ISOM Digiware D-75 screen also features a WEBVIEW web server.
Other connections are possible with ISOM Digiware D remote display; refer to its manual for more details.
Web server
WEBVIEW (ISOM Digiware D-75)
ISOM Digiware D-55 / D-75
Digiware terminals
Supervision
MODBUS TCP
9.3. Communication tables
The communication tables and associated explanations can be found on the documentations page for ISOM
Digiware on the SOCOMEC website: www.socomec.com/en/isom-digiware
ISOM DIGIWARE - 546780C - SOCOMEC
10. CONFIGURATION
Configuration can be carried out using the Easy Config configuration software or directly from the remote display. The
Easy Config software is used to configure ISOM Digiware directly via RS485 or USB. Easy Config must be installed
before using the USB connection. To set the parameters from the remote display D-75 or D-55, refer to the manual
for the display.
10.1. Configuration using Easy Config
10 .1 .1 . Connection modes
Configuration using Easy Config (USB)
Easy Config
Supervision
MODBUS TCP
USB
ISOM F-60
Configuration using Easy Config via a display
Supervision
MODBUS TCP
Easy Config
ISOM Digiware D-55 / D-75
USB
ISOM DIGIWARE - 546780C - SOCOMEC
Configuration using Easy Config via an ISOM Digiware D-55 / D-75 display (Ethernet)
Supervision
MODBUS TCP
Web server
WEBVIEW (ISOM Digiware D-75)
ISOM Digiware D-55 / D-75
These products must be connected to the power supply before you configure them.
For the Digiware bus and 120-ohm termination resistors, see "Communication" on page “9.
COMMUNICATION”, page 54.
10 .1 .2 . Using Easy Config
Easy Config is configuration software used to set product parameters easily and quickly. Settings are made in
sequence:
Device —> Network —> Insulation —> Measurement method —> Values to be stored —> Alarms —> End of
configuration
Other steps may appear, depending on the version of your device (example: Loads or Inputs/Outputs)
ISOM DIGIWARE - 546780C - SOCOMEC
For each setting selected (1) a customised screen appears, depending on the connected device (2).
10.1.2.1. Configuring the device
ISOM L-60: Configuring L-60 output in positive safety
This screen shows all the key details about the device (read-only). You can also make communication settings
(address, baudrate, parity). Add a synchronisation time and date by pressing the relevant button.
ISOM F-60
This screen shows all the key details about the device (read-only). Only the address can be edited here (make
communication settings on the L-60)
ISOM DIGIWARE - 546780C - SOCOMEC
10.1.2.2. Network configuration
In the electrical network configuration menu, the user selects the type of network (three-phase, single-phase, etc.),
the nominal voltage, the network frequency, the direction of phase rotation and whether or not a voltage transformer
is used.
Configuration can only be done from the ISOM L-60
Example: three-phase network 400VAC:
On this screen you can configure the type of IMD connection:
Three-phase or two-phase g "2P"
Single-phase: 1P+N
Continuous g "DC"
The basic voltage, as well as the rated frequency of the network (50Hz, DC…)
On the F-60, you get one reminder of the initially set values from the L-60
Example of a 24 VDC continuous network:
ISOM DIGIWARE - 546780C - SOCOMEC
10.1.2.3. Configuration of the insulation
ISOM L-60
The "Common" screen defines the general settings of the device:
1) the network profile:
Choosing the profile is an easy way to support the measurement algorithm on the intended application, with
improved filtering/measurement times.
You can choose between 3 profiles:
• Custom
• Cabinet
• Control/command
2) The booster startup mode for finding the fault:
• Automatic: start the "LCI" booster when the "ALARM 2" threshold is reached
• Manual: start up the "LCI" booster only with the BP "INJ START/STOP"
3) Manual test input:
Defines which ON/OFF input (1 to 4) on the device is used to carry out a remote internal test of the device.
4) Operating mode of the relays:
Defines if these relays are active or stopped.
ISOM DIGIWARE - 546780C - SOCOMEC
The "IMD" screen defines the general settings of the device in IMD mode:
1) Measuring voltage:
This data can set the measurement voltage according to the type of network.
It either depends on the profile or you can select it in the "custom" profile.
2) Maximum permissible leakage capacity:
This data has a major impact on the integrity of the reading. Above all, it influences the measuring time of the device.
It either depends on the profile or you can select it in the "custom" profile.
3) Filter level:
Adjust the filter level of the device.
4) RHG network:
With this option you can monitoring the insulation on a high-resistance network (network earthed via a high-value
resistance).
5) RHG resistance:
Lets you adjust the ohm value of the earth resistance (only if RHG is active)
6) Boost command:
In manual boost mode, this defines how the IMD boost is controlled: via the logical input or via the communication
bus (Modbus or from the ISOM Digiware D-x5 display).
7) Output report:
Activate an output when the IMD is ON.
ISOM DIGIWARE - 546780C - SOCOMEC
The "INJ" screen defines the general settings in FLD mode:
1) Boost current:
This lets you set the maximum value of the locating current.
It depends on the selected profile.
2) Boost command:
In manual boost mode, this defines how the IMD boost is controlled: via the logical input or via the communication
bus (Modbus or from the ISOM Digiware D-x5 display)
3) Output report:
Activate an output when INJ mode is ON.
4) Activate "mapping" mode (OhmScanner technology)
With "mapping" mode you can track the flow over a selected period; the progress of the insulation by circuit. This
mode is very useful when you start to plan scheduled maintenance actions.
5) Mapping period
Adjust the time interval between 2 measurements generated in mapping mode.
6) Mapping duration
Adjust the boosting time in mapping mode.
ISOM DIGIWARE - 546780C - SOCOMEC
10.1.2.4. Configuration of inputs-outputs (I/O)
The ISOM L-60 has 4 I/Os which are fully configurable.
In this screen you can set each I/O separately:
1) Function of the I/O
Defines if it is used as an input or an output
2) Name:
Name the I/O
3) Mode:
Defines the I/O operating mode:
As an input, you can set the following 4 modes:
• Injection cutoff
• External TEST
• External RESET
• Measurement restart
4) Type:
Defines if it is active, either in an open or closed state.
ISOM DIGIWARE - 546780C - SOCOMEC
ISOM F-60:
The "Insulation" screen defines the following settings:
1) The operating mode:
Full mode: In this mode you can measure both the residual locating current and the insulation – by circuit. This is for
the high-performance locating of present or emerging insulation faults.
Required in mapping mode.
Degraded mode: in this mode you can only measure the residual locating current, to highlight ongoing insulation
faults.
You can also remotely connect locating units on a system where there is no Digiware bus connection.
2) The operating mode of the output relay
N/C (positive safety = relay stimulated during standby if there is no alarm)
N/O (negative safety = relay stimulated only if there is an alarm)
Note: a normally closed operation can be used to also generate an alarm in case the auxiliary power of the device is
lost.
3) Relay status
Can be enabled or disabled (enabled by default).
ISOM DIGIWARE - 546780C - SOCOMEC
10.1.2.5. Configuring loads (ISOM F-60 only)
The number and type of loads can be accessed in the load configuration menu. The user can also define its nominal
current, the name of the load, its usage and its location within the electrical installation.
The "Circuits" screen defines the following settings:
1) Type: insulation circuit
2) Activate the channel
3) Type of load
4) Name of load
5) The rated current
6) Usage
7) Related voltage
8) Size
9) Direction of the sensor
10) Current input
11) Number of turns
12) Internal resistance
13) Detecting configuration
2) Type: insulation circuit or measuring circuit
ISOM DIGIWARE - 546780C - SOCOMEC
10.1.2.6. Calculation method
The calculation methods for the various electrical parameters and the integration time are defined in this screen.
Alarms
The type of alarm and the configuration are set in Easy Config, see section "11. ALARMS", page 68 for more.
10.1.2.7. Synchronisation of products
Ensure that all connected devices are set to the same time, their time is controlled on an SNTP server (ISOM
Digiware D-55 / D-75) or manually (ISOM Digiware D-55 / D-75).
The screen below shows the configuration of the update from the ISOM Digiware D-75 screen. The update is done
either from an SNTP server or manually. The time may be displayed on connected products automatically based on a
configurable update schedule.
ISOM DIGIWARE - 546780C - SOCOMEC
10.2. Configuration from the ISOM Digiware D remote display
10 .2 .1 . Connection mode
ISOM F-60
ISOM Digiware D-55 / D-75
Digiware terminals
You can also configure the ISOM Digiware system from the ISOM Digiware D-x5 display itself. Refer to the manual for
the ISOM Digiware D display for more.
ISOM DIGIWARE - 546780C - SOCOMEC
11. ALARMS
Threshold alarms are available on the ISOM Digiware L-60 and F-60.
The alarms on digital inputs with change of output status are only available on ISOM Digiware L-60. These inputs are
mainly used for remotely reporting on the status of third-party devices.
11.1. Alarms upon events
Alarms can be generated when a threshold is exceeded for the electrical measurements (insulation) or if there is a
change in input status. Also, combinations can be made on the alarms created.
Up to 25 alarms detected are saved and timestamped; an alarm can have 3 distinct statuses: Alarm active, Alarm
completed, Alarm completed and acknowledged. Alarms can be acknowledged either automatically or by user
action, as required.
Up to 4 alarms are configured for an electrical measurement or insulation measurement per device and 4 for changes
in status of a digital input (digital inputs are available only on the ISOM Digiware L-60).
The alarms are configured via the Easy Config software.
11 .1 .1 . Insulation and measurement alarm
The alarms available will be based on electrical parameters measured in the products.
• Alarm if there is a variation in the realtime or average value of an electrical value:
L-60: insulation, voltage, frequency / F-60: current, insulation
• Selection of the hysteresis and high/low threshold
• Setting a time delay at the start and end of the alarm
F-60: Example of configuring an insulation alarm via Easy Config:
ISOM DIGIWARE - 546780C - SOCOMEC
F-60: Example of setting an alarm in Easy Config if the three-phase transformer is overloaded:
11 .1 .2 . Digital inputs
This option is available on the ISOM Digiware L-60
• Alarm upon change of status for a digital input
• Choice of a rising or falling edge
• Setting a time delay at the start and end of the alarm
ISOM DIGIWARE - 546780C - SOCOMEC
Example of configuring an alarm on a digital input via Easy Config:
11 .1 .3 . Combination of alarms
• 4 boolean combinations (OR, AND) on the defined alarms (electrical values, energy, inputs, etc.)
Example of configuring an alarm on a digital input via Easy Config:
11 .1 .4 . System alarms
If an installation error is detected during setup, an alarm will be automatically generated.
• No IMD measuring circuit connection (L-60)
Alarm if there is a connection problem with the measuring circuit of the IMD ISOM Digiware L-60 on the electrical
network you want to monitor:
- L1 and/or L2
- PE (2x)
ISOM DIGIWARE - 546780C - SOCOMEC
• Voltage network outside specified range (L-60)
The voltage network connected is outside the working range.
• Device temperature too high (L-60)
The device is overheating (automatically stop the LCI booster)
• Loss of communication (L-60)
The device is no longer connected to a master of the Digiware bus
• Level outside of the operating range (L-60)
IMD measurement is outside the tolerance range and cannot be shown, the L60 is blind
• Core balance transformer disconnected (F-60)
Alarm for detecting the absence of a current sensor
• VI link alarm (F-60)
Alarm for connection error between the current and the voltage
Requires a specific load level: 0.6 < PF < 1 and I> 2% In
• Alert for bad primary TC (F-60)
Configuration error in the primary circuit of the core balance transformer.
11.2. Setting up alarms
The installation alarms are automatically detected and alarms upon events are configured with the Easy Config
software.
There are several ways of identifying the presence of an alarm:
11 .2 .1 . ALARM LED on front
• Flashing: Setup alarm
• Constant: Alarm for an event (takes priority if there is a setup alarm at the same time)
11 .2 .2 . Activation of an output
• On ISOM Digiware L-60 and t F-60, one or more outputs can be activated when an alarm is detected
11 .2 .3 . Acknowledging alarms by input
• If an input is present, the alarm can be acknowledged from this input. Acknowledgement of an alarm can only be
taken into account if the alarm is complete
11 .2 .4 . RS485 Modbus
• Information on the alarms with timestamping available via the RS485 communication bus
• Sends alarm acknowledgement
11 .2 .5 . Display and WEBVIEW
• Information on alarms with timestamping
• Sends alarm acknowledgement
ISOM DIGIWARE - 546780C - SOCOMEC
12. SPECIFICATIONS
12.1. Specifications ISOM Digiware L-60, F-60 and T-15
12 .1 .1 . Mechanical specifications
Casing type
L-60, F-60:
DIN-rail mounting module and base
T-15:
Only is mounted directly on the core balance transformer, DIN rail or board
with Rilsan®
Casing protection index
IP20
Front panel protection index
IP40 on the nose in modular assembly
Material and flammability class of housing
Polycarbonate UL94-V0
Weights ISOM Digiware L-60 / F-60 / T-15
373 g / 103 g / 47 g
12 .1 .2 . Electrical characteristics
DIRIS Digiware C-31
P15 power supply
Specifications 230 VAC / 24 VDC – 0.63A – 15W
Modular format – Dimensions (H x W): 90 x 25 mm
Removable screw terminal block, 2 positions, stranded or solid 0.2 -
2.5 mm² cable
Monitored IT network ISOM Digiware L-60
AC or combined AC/DC
L-60: ≤ 480VAC L/L‘ or L/N
L-60h: ≤ 250 VAC
CAT III
AC frequency
50 - 460 Hz
DC
L-60: ≤ 480 VDC
Power consumption
L-60: 2.3 W
F-60: 0.8 W
12 .1 .3 . Measurement characteristics
Measurement accuracy
Accuracy
L-60 / L-60h:
in accordance with IEC 61557-8
F-60 / T-15:
In accordance with IEC 61557-9 with ΔIPR, WR and TFR
In accordance with IEC 61557-12 classification PMD DD with TE, TR, TF
with U-xx
ISOM Digiware L-60 performance
Specific response value Ran
L-60:
ALARM1: 500 Ω – 1MΩ
ALARM2: 500 Ω – 1MΩ
L-60h:
ALARM1: 50 kΩ – 500 kΩ
ALARM2: 50 kΩ – 500 kΩ
Max. leakage capacity Ce
300 µF, according to profile
Incertitude of specific response value
+/- 10% according to profile
Response time tan
For Ce=1µF: typical 4s
See curves § 12.3
Measurement voltage Um
L-60: 25, 75 or 120 V according to profile
L-60h: 25 V
Measurement current Im
Max 1 mA
Max. external DC voltage Ufg
552 V
ISOM DIGIWARE - 546780C - SOCOMEC
Internal impedance
Zi = 120 kOhms
Internal resistance with continuous current
Ri = 120 kOhms
Locating current
L-60:
1, 5, 10 or 25 mA according to profile
L-60h:
1 mA
Measurement range Ce
0-300µF (L-60)
ISOM Digiware F-60 performance (with DIRIS Digiware U-3x)
Number of sensor inputs
6
Associated current sensors
Locating core balance transformers ΔIP, closed sensors TE, open TR, flexible
TF
Accuracy of current measurement
0.2 DIRIS Digiware class only
Class 0.5 with TE or TF sensors
Class 1 with TR sensors
With module U and in accordance with IEC 61557-12
Connection
Specific Socomec cable with RJ12 connectors
Link to ISOM Digiware L-60
Link via Digiware bus
Link to ISOM Digiware F-60
Link via Digiware bus
Power factor measurement
Accuracy
Class 0.5 with TE or TF sensors
Class 1 with TR sensors
Voltage readings – ISOM L-60
Characteristics of the network measured
L-60: 24-480VAC/VDC (ph/ph or ph/n) - CAT.III
L-60h: 24-250VAC/VDC (ph/ph or ph/n) - CATIII
Operating range of the voltage network
+/-10%
Frequency range
50 to 460 Hz for L60
50 to 60 Hz for L60h
Network type
DC, 1P+N or 2P
Input consumption
≤ 0.1 VA
Rated impulse voltage
Rated impulse voltage 6kV (IEC60364-4-44)
Connection
Removable screw terminal block, 4 positions, stranded or solid 0.2 -
2.5 mm² cable
Frequency readings
Measurement range fn
In ISOM mode: 50 Hz to 460 Hz
Measurement voltage range fn
AC 24 to 480 V for L60
AC24 to 250 V for L60h
ISOM DIGIWARE - 546780C - SOCOMEC
12 .1 .4 . Input/output specifications HMI
Digital inputs/outputs – ISOM Digiware L-60
Number of inputs
4
Type / Power supply
Output: 12-24VDC min 600Ω 40 mA max
Input: Max 100 Ω
Insulated input, internal polarisation, dry contact (default impedance max
100 Ω) - SELV in accordance with IEC61010
Input functions
Logical status (state of the circuit breaker: position, trigger, drawer)
TEST, external RESET, stop measurement, start measurement
Output functions
Configurable alarm on breach of threshold 3A
Connection
Removable spring-cage terminal block, 6 positions - 4 dedicated to outputs,
1 input polarisation, 1 common output point, stranded or solid 0.2 - 1.5 mm²
cable
Relay outputs – ISOM Digiware L-60
Number of outputs
2
Type
Changeover switch
Rated voltage AC: 250 V
Rated voltage DC: 30 V
Sustained current: 3 A
Operating mode: standby/working
Default operating mode: standby
Output functions
Alarm
Connection
0.2 - 2.5 mm2
PTC inputs – ISOM Digiware L-60
Number of inputs
1
Type / Power supply
Logical status (temperature sensor)
Analogue input: PTC probe
Input functions
Alarm
Connection
0.2 - 2.5 mm2
12 .1 .5 . Communication specifications
Digiware BUS
Function
Connection between DIRIS Digiware modules
Cable type
Specific SOCOMEC cable with RJ45 connections
USB
Protocol
Modbus RTU on USB
Function
Configuration of ISOM Digiware modules L and F
Location
On each ISOM Digiware module L and F
Connection
Type B micro USB connector
ISOM DIGIWARE - 546780C - SOCOMEC
12 .1 .6 . Environmental specifications
Standard model
Ambient operating temperature
-10 to +55°C (IEC 60068-2-1 / IEC 60068-2-2)
Storage temperature
-40 to +70°C (IEC 60068-2-1 / IEC 60068-2-2)
Operating humidity
55°C / 90% RH (IEC 60068-2-30)
Operating altitude
< 2000 m
Vibration
2 Hz to 13.2 Hz – amplitude ± 1 mm (IEC 60068-2-6)
13.2 Hz to 100 Hz – acceleration ± 0.7g (IEC 60068-2-6)
Impact resistance
IK08 (5J) front panel
IK06 (1J) other panels
10 g / 11 ms, 3 pulses (IEC 60068-2-27)
PEP ecopassport - ISO 14025
ISOM Digiware: SOCO-00009-V01.01.
Reinforced model "t"
Operating temperature
-10°C to +70°C (IEC 60068-2-1 / IEC 60068-2-2)
Storage temperature
-40°C to +85°C (IEC 60068-2-1 / IEC 60068-2-2)
Operating humidity
55°C / 97% RH (IEC 60068-2-30)
Operating altitude
< 2000 m
Vibration
2.0 Hz to 25.0 Hz – amplitude ± 1.6 mm (IEC 60068-2-6)
25.0 Hz to 100 Hz – acceleration ± 4g (IEC 60068-2-6)
3Hz to 8.7Hz- amplitude ± 10 mm (IEC 60068-2-6)
8.7Hz to 150Hz – acceleration ± 3 g (IEC 60068-2-6)
Impact resistance
IK08 (5J) front panel
IK06 (1J) other panels
10 g / 11 ms, 3 pulses (IEC 60068-2-27)
30 g / 18 ms, 3 pulses (IEC 60068-2-27)
40 g / 6 ms, 3 pulses (IEC 60068-2-27)
PEP ecopassport – ISO 14025
ISOM Digiware: SOCO-00009-V01.01.
ISOM DIGIWARE - 546780C - SOCOMEC
12 .1 .7 . Electromagnetic specifications (Directive 2014/30/EU)
Immunity to electrostatic discharges
IEC 61000-4-2 - LEVEL III - CLASS A
Immunity to radiated radio-frequency fields
IEC 61000-4-3 - LEVEL III - CLASS A
Immunity to electrical fast transients/bursts
IEC 61000-4-4 - LEVEL IV - CLASS B
Immunity to impulse waves
IEC 61000-4-5 - LEVEL IV - CLASS B
Immunity to radio interference
IEC 61000-4-6 - LEVEL III
Immunity to power frequency magnetic fields
IEC 61000-4-8 - 400A/m LEVEL IV - CLASS A
Conducted emissions
CISPR11 Gr:1 - CLASS B
Radiated emissions
CISPR11 Gr:1 - CLASS B
12 .1 .8 . Standards and safety
Product
L-60:
Conformity with IEC 61557-8: IMD
Conformity with IEC 61557-9: LCI
F-60:
Conformity with IEC 61557-9: IFL
Conformity with PMD IEC 61557-12
T-15:
Conformity with IEC 61557-9: IFL
Safety
Conformity with Low Voltage Directive 2014/35/EU of 26 February
2014 (EN 61010-1:2010 and EN 61010-2-030)
Insulation coordination
Overvoltage category III – degree of pollution 2
12 .1 .9 . Longevity CEM directive 2014/30/EU
MTTF (mean time to failure)
> 100 years
12.2. Display characteristics – ISOM D-15h and ISOM Digiware D-55 / D-55h / D-75
12 .2 .1 . Mechanical specifications
HMI models
D-15h
3 LEDs - 2 keys
D-55 / D-55h / D-75
Capacitive touchscreen technology, 10 keys, 4 LEDs
Screen resolution
D-55 / D-55h / D-75: 350 x 160 pixels
Front panel protection index
D-15h: IP54 – marking conforms with IEC 60601-1 as on the
ISO105-X12
D-55 / D-55h / D-75: IP65
Material and flammability class of housing
Polycarbonate UL94-V0
Weight
D-15h: 100 g
D-55 / D-55h / D-75: 210 g
12 .2 .2 . Electrical specifications
Power supplies
Power supply
24 VDC ±10%
Power consumption
D-15h: 0.5 VA
D-55 / D-55h / D-75: 2.5 VA
ISOM DIGIWARE - 546780C - SOCOMEC
12 .2 .3 . ISOM D-55 / D-55h communication features
Type of screen
Multipoint remote screen
Ethernet RJ45 10/100 Mbs
Modbus TCP gateway function
RJ45 Digiware
Control and power supply interface function
RS485 2-3 wires
RS485 2-3 wire Master communication function Modbus RTU
USB
USB upgrade and configuration via type B micro USB connector
12 .2 .4 . ISOM Digiware D-75 communication features
Type of screen
Multipoint remote screen
Ethernet RJ45 10/100 Mbs
Gateway function:
- Modbus TCP
- Embedded web server WEBVIEW-M
SNTP protocol
Updates the screen from an NTP server.
The display updates the connected devices.
SMTPS protocol
Sends email notifications.
FTPS protocol
Automatically exports data via standard or secure FTP server
(consumption curves, load curves, measurement
logs)
RJ45 Digiware
Control and power supply interface function
RS485 2-3 wires
RS485 2-3 wire Master communication function Modbus RTU
USB
USB upgrade and configuration via type B micro USB connector
12 .2 .5 . Environmental specifications
Standard model
Operating temperature
-10°C to + 55°C
Storage temperature
-40°C to +70°C
Humidity
97%RH at +55°C (D-75t)
Installation category, Degree of pollution
Device powered by SELV, 2
ISOM DIGIWARE - 546780C - SOCOMEC
12.3. ISOM Digiware L-60 response curves
1.0
10.0
100.0
0.1
1
10
100
1000
Response Time Tan (s)
Response Value Ran (kOhms)
Response time (Tan) as a function of the response value (Ran)
and system leakage capacitance (Ce) according to EN/IEC 61557-8
(Un = 400 Vac, Fn = 50 Hz, Us = 24 Vdc, Um = 75 V, Injection Period = 1s, Low filtering, Distribution profile)
Ce = None
Ce ≤ 1µF
Ce ≤ 5 µF
Ce ≤ 25 µF
Ce ≤ 50 µF
Ce ≤ 150 µF
Ce ≤ 300 µF
1.0
10.0
100.0
1
10
100
1000
Response Time Tan (s)
Response Value Ran (kOhms)
Response time (Tan) as a function of the response value (Ran)
and system leakage capacitance (Ce) according to EN/IEC 61557-8
(Un = 230 Vac, Fn = 50 Hz, Us = 24 Vdc, Um = 25 V, Injection Period = 1s, Filtering Low, control/command profile)
Ce = None
Ce ≤ 1µF
Ce ≤ 5 µF
Ce ≤ 25 µF
Ce ≤ 50 µF
Ce ≤ 150 µF
Ce ≤ 300 µF
ISOM DIGIWARE - 546780C - SOCOMEC
13. PERFORMANCE CLASSES
Performance classes are drawn up in compliance with IEC 61557-12
DIRIS Digiware classification
DD in combination with dedicated sensors (TE, TR, TF)
Temperature
K55
Overall operating performance class for active power or
active energy
0.5 in combination with TE or TF solid-core sensors
1 in combination with TR split-core sensors
13.1. Specification of the characteristics
Symbol
Function
Overall operating
performance class of
DIRIS Digiware + dedicated
sensors * (TE, TR, TF) + one
module U compliant with IEC
61557-12
Measurement
range
Pa
Total active power
0.2 DIRIS Digiware only
0.5 with TE or TF sensors
1 with TR sensors
10% - 120% In
2% - 120% In
2% - 120% In
QA, QV
Total reactive power (arithmetic, vectorial)
1 with TE, TR or TF sensors
5% - 120% In
SA, SV
Total apparent power (arithmetic, vectorial)
0.5 with TE or TF sensors
1 with TR sensors
10% - 120% In
Ea
Total active energy
0.2 DIRIS Digiware only
0.5 with TE or TF sensors
1 with TR sensors
10% - 120% In
2% - 120% In
2% - 120% In
ErA, ErV
Total reactive energy (arithmetic, vectorial)
2 with TE, TR or TF sensors
5% - 120% In
EapA, EapV
Total apparent energy (arithmetic, vectorial)
0.5 with TE or TF sensors
1 with TR sensors
10% - 120% In
f
Frequency
0.02
45 - 65 Hz
I, IN
Phase current, measured neutral current
0.2 DIRIS Digiware only
0.5 with TE or TF sensors
1 with TR sensors
5% - 120% In
10% - 120% In
10% - 120% In
INc
Calculated neutral current
1 with TE or TF sensors
2 with TR sensors
10% - 120% In
U
Voltage (Lp-Lg or Lp-N)
0.2
50 - 300 VAC Ph/N
PFA, PFV
Power factor (arithmetic, vectorial)
0.5 with TE or TF sensors
1 with TR sensors
0.5 inductive to 0.8
capacitive
Pst, Plt
Flicker (short, long)
-
-
Udip
Voltage dip (Lp-Lg or Lp-N)
0.5
-
Uswl
Temporary overvoltages (Lp-Lg or Lp-N)
0.5
-
Uint
Voltage outage (Lp-Lg or Lp-N)
0.2
-
Unba
Voltage amplitude imbalance (Lp-N)
0.5
-
Unb
Voltage phase and amplitude imbalance (Lp-Lg or
Lp-N)
0.2
-
THDu,
THD-Ru
Total harmonic distortion rate of the voltage (relative
to the fundamental, relative to the efficient value)
1
Orders 1 to 63
Uh
Voltage harmonics
1
-
THDi,
THD-Ri
Total harmonic distortion rate of the current (relative
to the fundamental, relative to the efficient value)
1 with sensors TE, TR or TF
Orders 1 to 63
Ih
Current harmonics
1 with sensors TE, TR or TF
-
Msv
Centralised remote control signals
-
-
*With SOCOMEC connection cables.
ISOM DIGIWARE - 546780C - SOCOMEC
13.2. Evaluation of the power supply quality
Symbol
Function
Overall operating
performance class
DIRIS Digiware + dedicated
sensors (TE, TR, TF) in
compliance with IEC 61557-12
Measurement
range
f
Frequency
0.02
45 - 65 Hz
I, IN
Phase current, measured neutral current
0.2 DIRIS Digiware only
0.5 with TE or TF sensors
1 with TR sensors
5% - 120% In
10% - 120% In
10% - 120% In
INc
Calculated neutral current
1 with solid-core TE or TF sensors
2 with TR sensors
10% - 120% In
U
Voltage (Lp-Lg or Lp-N)
0.2
50 - 300 VAC Ph/N
Pst, Plt
Flicker (short, long)
-
-
Udip
Voltage dip (Lp-Lg or Lp-N)
0.5
-
Uswl
Temporary overvoltages (Lp-Lg or Lp-N)
0.5
-
Uint
Voltage outage (Lp-Lg or Lp-N)
0.2
-
Unba
Voltage amplitude imbalance (Lp-N)
0.5
-
Unb
Voltage phase and amplitude imbalance (Lp-Lg or
Lp-N)
0.2
-
Uh
Voltage harmonics
1
-
Ih
Current harmonics
1 with sensors TE, TR or TF
-
Msv
Centralised remote control signals
-
-
Non-contractual document. © 2019, Socomec SAS. All rights reserved.
MAIN OFFICE, CONTACT:
SOCOMEC SAS
1-4 RUE DE WESTHOUSE
67235 BENFELD, FRANCE
http://www.socomec.com
546780C