Longo programmable controller
LPC-2.C06
Communication terminal
Version 1
SMARTEH d.o.o. / Poljubinj 114 / 5220 Tolmin / Slovenia / Tel.: +386(0)5 388 44 00 / e-mail: [email protected] / www.smarteh.si
Longo programmable controller LPC-2.C06
Written by SMARTEH d.o.o.
Copyright © 2020, SMARTEH d.o.o.
User Manual
Document Version: 1
June, 2020
i
Longo programmable controller LPC-2.C06
STANDARDS AND PROVISIONS: Standards, recommendations,
regulations and provisions of the country in which the devices will
operate, must be considered while planning and setting up electrical
devices. Work on 100 .. 240 V AC network is allowed for authorized
personnel only.
DANGER WARNINGS: Devices or modules must be protected from
moisture, dirt and damage during transport, storing and operation.
WARRANTY CONDITIONS: For all modules LONGO LPC-2 – if no
modifications are performed upon and are correctly connected by
authorized personnel – in consideration of maximum allowed
connecting power, warranty of 24 months is valid from the date of
sale to the end buyer, but not more than 36 months after delivery
from Smarteh. In case of claims within warranty time, which are based
on material malfunctions the producer offers free replacement. The
method of return of malfunctioned module, together with description,
can be arranged with our authorized representative. Warranty does
not include damage due to transport or because of unconsidered
corresponding regulations of the country, where the module is
installed.
This device must be connected properly by the provided connection
scheme in this manual. Misconnections may result in device damage,
fire or personal injury.
Hazardous voltage in the device can cause electric shock and may
result in personal injury or death.
NEVER SERVICE THIS PRODUCT YOURSELF!
This device must not be installed in the systems critical for life (e.g.
medical devices, aircrafts, etc.).
If the device is used in a manner not specified by the manufacturer,
the degree of protection provided by the equipment may be impaired.
Waste electrical and electronic equipment (WEEE) must be collected
separately!
LONGO LPC-2 complies to the following standards:
•
EMC: EN 61000-6-3:2007 + A1:2011, EN 61000-6-1:2007, EN 61000-
3-2:2006 + A1:2009 + A2: 2009, EN 61000-3-3:2013
•
LVD: IEC 61010-1:2010 (3rd Ed.), IEC 61010-2-201:2013 (1st Ed.)
Smarteh d.o.o. operates a policy of continuous development.
Therefore we reserve the right to make changes and improvements to
any of the products described in this manual without any prior notice.
MANUFACTURER:
SMARTEH d.o.o.
Poljubinj 114
5220 Tolmin
Slovenia
ii
Longo programmable controller LPC-2.C06
Longo programmable controller LPC-2.C06
1 ABBREVIATIONS................................................................................1
2 DESCRIPTION...................................................................................2
3 FEATURES.......................................................................................3
4 OPERATION.....................................................................................4
4.1 Parameters..............................................................................4
5 INSTALLATION..................................................................................7
5.1 Connection scheme....................................................................7
5.2 Mounting instructions.................................................................9
5.3 Module labeling.......................................................................11
6 TECHNICAL SPECIFICATIONS................................................................12
7 CHANGES .....................................................................................13
8 NOTES..........................................................................................14
iii
Longo programmable controller LPC-2.C06
1 ABBREVIATIONS
DC
Direct Current
TTL
Transistor-Transistor Logic
RX
Receive
TX
Transmit
UART
Universal Asynchronous Receiver-Transmitter
1
Longo programmable controller LPC-2.C06
2 DESCRIPTION
LPC-2.C06 is a communication module for RS-232, TTL or RS-485 serial UART communication. It's
main feature is being a gateway for UART protocols, exchanging UART data with the main module,
where all of data is being interpreted. That way, different communication protocols, which are
based on the RS-232, TTL or RS-485 UART protocols, can be implemented, e.g. DMX, proprietary
protocols.
LPC-2.C06 is controlled and powered from the main module (e.g. LPC-2.MC9) via Right internal bus.
2
Longo programmable controller LPC-2.C06
3 FEATURES
Figure 1: LPC-2.C06 module
Table 1: Technical data
RS-232 port with possibility to use TTL voltage levels (select-able with jumper)
RS-485 port
Signal LEDs
Supplied from main module
Small dimensions and standard DIN EN50022-35 rail mounting
3
Longo programmable controller LPC-2.C06
4 OPERATION
Module parameters can be read or written via Smarteh IDE software.
4.1 Parameters
Input
Protocol type [Protocol_Type]: Protocol type feedback. Intended for future use.
Type: USINT
Raw to engineering data:
0 .. 255
→ 0 .. 255
I2C session counter [I2C_Session_Cnt]: It changes after each session when data in module
updates. It updates every cca.100 ms.
Type: USINT
Raw to engineering data:
0 .. 255
→ 0 .. 255
Receive counter [Rx_Counter]: It changes if new data in Rx_Buffer is available.
Type: USINT
Raw to engineering data:
0 .. 255
→ 0 .. 255
Received data length [Rx_Data_Len]: Number of data in Rx Buffer.
Type: UINT
Raw to engineering data:
0 . 65535
0 .. 65535
→
Received telegram status [Rx_TLG_Status]: Status of received telegram.
Type: USINT
Raw to engineering data:
xxxxxxx0
No telegram timeout
→
xxxxxxx1
Telegram timeout
→
Xxxxxx0x
No data (byte) timeout
→
xxxxxx1x
Data (byte) timeout
→
xxxxx0xx
No parity error
→
xxxxx1xx
Parity error
→
xxxx0xxx
No framing error
→
xxxx1xxx
Framing error
→
xxx0xxxx
No data overflow
→
xxx1xxxx
Data overflow
→
Receive reception status [Rx_Reception_Status]: Status of reception.
Type: USINT
Raw to engineering data:
0
No reception
→
1
Reception in progress
→
2
Reception ended (timeout)
→
3
Reception ended (data received)
→
4
Longo programmable controller LPC-2.C06
11
Error in reception
→
Maximum receive timeout [Rx_Timeout_Max]: Maximal timeout between received data
bytes in received telegram.
Type: UINT
Raw to engineering data:
0 .. 65535
0 .. 65535 us
→
Output
Protocol type [Protocol_Type]: Selector of protocol type. Intended for future use.
Type: USINT
Raw to engineering data:
0
Universal
→
2 .. 255
Custom protocols. If custom protocol is
→
not implemented universal protocol is used.
Protocol option [Protocol_Option]: Protocol options.
Type: USINT
Raw to engineering data:
xxxxxxx0
RS485
→
xxxxxxx1
RS232
→
Xxxxxx0x
Normal TTL Tx signal
→
xxxxxx1x
Inverted TTL Tx signal
→
xxxxx0xx
Normal RS232 and inverted TTL Rx signal
→
xxxxx1xx
Inverted RS232 and normal TTL Rx signal
→
UART speed [UART_Speed]: Selector of baudrate.
Type: USINT
Raw to engineering data:
0
300
→
1
600
→
2
1200
→
3
2400
→
4
4800
→
5
9600
→
6
19200 (default)
→
7
38400
→
8
57600
→
9
115200
→
other
19200
→
UART parity [UART_Parity]: Selector of parity.
Type: USINT
Raw to engineering data:
0
No parity bit
→
1
Odd
→
2
Even
→
other
No parity bit
→
UART databits [UART_Databits]: Number of data bits.
5
Longo programmable controller LPC-2.C06
Type: USINT
Raw to engineering data:
5
5 bits
→
6
6 bits
→
7
7 bits
→
8
8 bits (default)
→
other
8 bits
→
UART stopbits [UART_Stopbits]: Number of stop bits.
Type: USINT
Raw to engineering data:
0
1 bit
→
1
1 bit
→
2
2 bits (default)
→
other
2 bits
→
Received telegram timeout [Rx_TLG_Timeout]: Telegram timeout for receiving data.
Type: UINT
Raw to engineering data:
0
No timeout
→
other
Timeout value (in ms)
→
Received data timeout [Rx_Data_Timeout]: Data timeout for receiving data.
Type: UINT
Raw to engineering data:
0
No timeout
→
other
Timeout value (in us)
→
Received data length [Rx_Data_Len]: Length of received data.
Type: UINT
Raw to engineering data:
0 .. 1000
Number of expected data.
→
1001
AUTO (receive data until timeout or buffer is
→
full)
other
AUTO
→
Transmitted data length [Tx_Data_Len]: Number of bytes to transmit.
Type: UINT
Raw to engineering data:
0 .. 270
0 .. 270 bytes
→
Transmit counter [Tx_Counter]: Transmit data only when counter changes.
Type: USINT
Raw to engineering data:
0 .. 255
0 .. 255
→
Transmit buffer [Tx_Buffer_{1..270}]: Transmit buffer with content to send over UART. It
contains 270 variables, e.g. Tx_Buffer_1, Tx_Buffer_2...
Type: USINT
Raw to engineering data:
0 .. 255
0 .. 255
→
6
Longo programmable controller LPC-2.C06
5 INSTALLATION
5.1 Connection scheme
Figure 2: Connection scheme
Table 2: RS4851
RS485.4
GND
RS485.5
RS-485 (A)
RS-485 standard voltage levels
RS485.6
RS-485 (B)
Table 3: RS2321
RS232.1
GND
RS232.2
RS-232 (Tx)
S1 Position 1-2 (RS232)
RS-232 standard
→
voltage levels
S1 Position 2-3 (TTL)
→ 0 .. 5 V
RS232.3
RS-232 (Rx)
Table 4: K1
Internal BUS
Data & DC power supply
Connection to I/O module
1
Wires connected to the module must have cross sectional area at least 0.75 mm 2. Minimum temperature rating of wire
insulation must be 85 °C.
7
Longo programmable controller LPC-2.C06
Table 5: K2
Internal BUS
Data & DC power supply
Connection to I/O module
Table 6: S1 – Voltage levels for RS232 port
S1
Position 1-2, RS-232
S1
Position 2-3, TTL
8
Longo programmable controller LPC-2.C06
5.2 Mounting instructions
Figure 3: Housing dimensions
•
Dimensions in millimeters.
All connections, module attachments and assembling must be done
while module is not connected to the main power supply.
Mounting instructions:
1.
Switch OFF main power supply.
2.
Mount LPC-2.C06 module to the provided place inside an electrical panel (DIN EN50022-35
rail mounting).
3.
Mount other LPC-2 modules (if required). Mount each module to the DIN rail first, then
attach modules together through K1 and K2 connectors.
4.
Connect input and output wires according to the connection scheme in Figure 2.
5.
Switch ON main power supply.
Dismount in reverse order. For mounting/dismounting modules to/from DIN rail a free space of at
least one module must be left on the DIN rail.
NOTE: LPC-2 main module should be powered separately from other electrical appliance connected
to LPC-2 system. Signal wires must be installed separately from power and high voltage wires in
accordance with general industry electrical installation standard.
9
18
90
95
36
60
Longo programmable controller LPC-2.C06
Figure 4: Minimum clearances
The clearances above must be considered before module mounting.
10
Longo programmable controller LPC-2.C06
5.3 Module labeling
Figure 5: Label
Label (sample):
Label description:
1.
XXX-N.ZZZ - full product name.
◦
XXX-N - Product family
◦
ZZZ - product
2.
P/N: AAABBBCCDDDEEE - part number.
▪
AAA - general code for product family,
▪
BBB - short product name,
▪
CCDDD - sequence code,
•
CC - year of code opening,
•
DDD - derivation code,
▪
EEE – version code (reserved for future HW and/or SW firmware upgrades).
3.
S/N: SSS-RR-YYXXXXXXXXX - serial number.
◦
SSS – short product name,
◦
RR – user code (test procedure, e.g. Smarteh person xxx),
◦
YY – year,
◦
XXXXXXXXX – current stack number.
4.
D/C: WW/YY - date code.
•
WW – week and
•
YY – year of production.
Optional
1.
MAC
2.
Symbols
3.
WAMP
4.
Other
11
XXX-N.ZZZ
P/N: AAABBBCCDDDEEE
S/N: SSS-RR-YYXXXXXXXXX
D/C: WW/YY
Longo programmable controller LPC-2.C06
6 TECHNICAL SPECIFICATIONS
Table 8: Technical specifications
Power supply
from main module via internal bus
Max. power consumption
1 W
Connection type
screw type connector for stranded wire 0.75 to 1.5 mm2
Dimensions (L x W x H)
90 x 18 x 60 mm
Weight
60 g
Ambient temperature
0 to 50 °C
Ambient humidity
max. 95 %, no condensation
Maximum altitude
2000 m
Mounting position
vertical
Transport and storage temperature
-20 to 60 °C
Pollution degree
2
Overvoltage category
II
Electrical equipment
Class II (double insulation)
Protection class
IP 30
12
Longo programmable controller LPC-2.C06
7 CHANGES
The following table describes all the changes to the document.
Date
V.
Description
12.06.2020
1
The initial version, issued as LPC-2.C06 module UserManual.
13