Siemens SIRIUS System Manual

Specifications

Brand: Siemens
Category: Relays
Model: SIRIUS (System Manual)
File Type: PDF
File Size: —
Pages: 425

Read Online

Read the Siemens SIRIUS System Manual online using the built-in PDF viewer.

Text of the manual

This manual contains notices which you should observe to ensure your own personal safety, as well as to pro-

tect the product and connected equipment. These notices are highlighted in the manual by a warning triangle and are marked as follows according to the level of danger: Danger indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken. Warning indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken. Caution indicates that minor personal injury or property damage can result if proper precautions are not taken. Caution indicates that property damage can result if proper precautions are not taken. Attention draws your attention to particularly important information on the product, handling the product, or to a particu- lar part of the documentation. Qualified personnel Only qualified personnel should be allowed to install and work on this equipment. Qualified persons are defi- ned as persons who are authorized to commission, to ground, and to tag circuits, equipment, and systems in acc. with established safety practices and standards. Correct usage Note the following: Warning This device and its components may only be used for the applications described in the catalogue or the techni- cal descriptions, and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and operated and maintained as recommended. Brands SIMATIC®, SIMATIC HMI® and SIMATIC NET® are brands of SIEMENS AG. Some other designations used in these documents are also brands; the owner's rights may be violated if they are used by third parties for their own purposes. Siemens AG Bereich Automatisierungs- und Antriebstechnik Geschäftsgebiet Niederspannungs-Schalttechnik D-91050 Erlangen Siemens Aktiengesellschaft  Siemens AG 2001 Technical data subject to change without notice. Copyright Siemens AG 2001 All rights reserved The reproduction, transmission or use of this document or its con- tents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. Disclaimer of liability We have checked this manual to ensure that its contents are correct and applicable in relation to the hardware and software it describes. Despite all our endeavors, however, discrepancies cannot be wholly excluded and so we cannot guarantee complete correctness and applicability. However, the data in this manual are reviewed regularly and any necessary corrections included in subsequent editions. Sug- gestions for improvement are welcomed. Technical Assistance: Telephone: +49 (0) 9131-7-43833 (8°° - 17°° CET) Fax: +49 (0) 9131-7-42899 E-mail: [email protected] Internet: www.siemens.com/lowvoltage/technical-assistance Technical Support: Telephone: +49 (0) 180 50 50 222

SIRIUS System Manual

GWA 4NEB 430 0999-02b i Contents 1 System overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 1.2 Overview: Range of devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5 1.3 System features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10 1.4 Components and combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11 1.5 Mounting methods and terminal systems . . . . . . . . . . . . . . . . . . . . . . 1-15 1.5.1 Mounting the equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-15 1.5.2 Screw-type terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17 1.5.3 Cage Clamp terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-18 1.5.4 Connection cross-sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-20 1.6 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-22 1.6.1 Communication-capable low-voltage switching technology . . . . . . . . . . . . . . 1-22 1.6.2 Parameterization of PROFIBUS-DP and bus-capable low-voltage switching devices . 1-23 1.6.3 Actuator-sensor interface (AS-Interface) . . . . . . . . . . . . . . . . . . . . . . . 1-23 2 3RV1 circuit breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 2.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 2.2.1 General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6 2.2.2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7 2.2.3 Information on configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10 2.3 Field of application/variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13 2.3.1 Motor protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13 2.3.2 Transformer protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13 2.3.3 Starter protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13 2.3.4 Circuit breakers with overload relay function . . . . . . . . . . . . . . . . . . . . . 2-14 2.3.5 Fuse monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14 2.3.6 Switching direct current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16 2.3.7 Main and emergency stop switches . . . . . . . . . . . . . . . . . . . . . . . . . 2-17 2.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18 2.4.1 Attachable accessories: Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18 2.4.2 Auxiliary switch, alarm switch, and auxiliary release . . . . . . . . . . . . . . . . . 2-19 2.4.3 Motorized remote-control mechanism . . . . . . . . . . . . . . . . . . . . . . . . 2-23 2.4.4 Disconnecting module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26 2.4.5 Rotary switch extension for door . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-28 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508 . . . . . . 2-31 2.4.7 Housings and mounting accessories . . . . . . . . . . . . . . . . . . . . . . . . . 2-32 2.4.8 Busbar adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-37 2.4.9 Isolated 3-phase busbar system . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-41 2.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-45 2.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-45 2.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-46 2.5.3 Device circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-48 2.6 Dimensioned drawings (measurements in mm) . . . . . . . . . . . . . . . . . . . 2-49 2.7 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-58 2.7.1 General specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-58 2.7.2 Rated short-circuit breaking capacity Icn in acc. with IEC 60 947-2 . . . . . . . . . . 2-63 2.7.3 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-65

SIRIUS System Manual

ii GWA 4NEB 430 0999-02b 3 3RT1/3RH1 contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 3.1.1 Utilization categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 3.1.2 Positively driven operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7 3.1.3 Safe isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7 3.1.4 Explanation of terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9 3.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 3.2.1 Actuating systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12 3.2.2 Short-circuit protection of the SIRIUS contactors . . . . . . . . . . . . . . . . . . . 3-12 3.2.3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 3.2.3.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 3.2.3.2 Contact reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14 3.3 Application and areas of use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20 3.3.1 3RT10 contactors with 3 main contacts for switching motors . . . . . . . . . . . . . 3-20 3.3.2 3RT1446 contactors with 3 main contacts for switching resistive loads (AC-1) . . . . 3-21 3.3.3 3RT13 and 3RT15 contactors with 4 main contacts . . . . . . . . . . . . . . . . . . 3-22 3.3.4 3RT16 capacitor-switching contactors for switching capacitors . . . . . . . . . . . . 3-25 3.3.5 Contactors with an extended operating range . . . . . . . . . . . . . . . . . . . . . 3-26 3.3.5.1 Contactors with an extended operating range (3RH11...-0LA0/3RT10...-0LA0) . . . . . 3-27 3.3.5.2 Contactors with an extended operating range (3RH1122-2K.40, 3RT1017-2K.4., 3RT102.-3K.40) . . . . . . . . . . . . . . . . . . . . 3-29 3.3.6 3RH1 auxiliary contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-29 3.3.7 3RT10 contactor relays for switching motors (interface) and 3RH11 contactor relays for switching auxiliary circuits . . . . . . . . . . . . . . . . . . . . 3-30 3.3.8 Contactor combinations for reversing . . . . . . . . . . . . . . . . . . . . . . . . . 3-32 3.3.9 Star-delta combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-41 3.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-49 3.4.1 Attachable auxiliary switches for extending the auxiliary contacts . . . . . . . . . . . 3-52 3.4.1.1 Terminal markings of the contactors (frame sizes S00 to S3) . . . . . . . . . . . . . . . 3-57 3.4.1.2 Terminal markings of the contactors and auxiliary contactors combined with auxiliary switch blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-59 3.4.1.3 Auxiliary switches that can be attached to 3RH1 auxiliary contactors . . . . . . . . . . 3-61 3.4.2 Time-delay auxiliary switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-64 3.4.2.1 Frame size S00 (3RT1916-2E, -2F, -2G) . . . . . . . . . . . . . . . . . . . . . . . . . . 3-64 3.4.2.2 Frame sizes S0 to S3 (3RT1926-2E, -2F, -2G) . . . . . . . . . . . . . . . . . . . . . . . 3-66 3.4.3 Solid-state time relay blocks with semiconductor output . . . . . . . . . . . . . . . 3-67 3.4.3.1 Frame size S00 (3RT1916-2C, -2D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-68 3.4.3.2 Frame size S0 to S3 (3RT1926-2C, -2D) . . . . . . . . . . . . . . . . . . . . . . . . . . 3-69 3.4.4 Additional load module (3RT1916-1GA00) . . . . . . . . . . . . . . . . . . . . . . . 3-70 3.4.5 Coupling element for frame sizes S0 to S3 (3RH1924-1GP11) . . . . . . . . . . . . . 3-71 3.4.6 Surge suppression . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-73 3.4.7 Other accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-78 3.4.7.1 LED module for indicating contactor control (3RT1926-1QT00) . . . . . . . . . . . . . . 3-78 3.4.7.2 Auxiliary connecting lead terminal, 3-pole (for frame size S3) . . . . . . . . . . . . . . . 3-79 3.4.7.3 EMC module (3RT1916-1P..) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-79 3.4.7.4 Soldering pin connector for frame size S00 . . . . . . . . . . . . . . . . . . . . . . . . 3-81 3.4.7.5 Parallel connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-83 3.4.7.6 Covers for frame sizes S2 and S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-84 3.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-86 3.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-86 3.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-88 3.5.3 Changing the magnet coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-92 3.5.4 Changing the contact piece . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-97

SIRIUS System Manual

GWA 4NEB 430 0999-02b iii 3.6 Dimensioned drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . 3-99 3.7 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-110 4 3RU11, 3RB10, and 3RB12 overload relays . . . . . . . . . . . . . . . . . . . . . 4-1 4.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 4.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4 4.2.1 Overload relays in motor feeders . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5 4.2.2 General device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6 4.2.3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13 4.3 Application and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15 4.3.1 3RU11 thermal overload relay and 3RB10 electronic overload relay . . . . . . . . . . 4-15 4.3.2 3RB12 electronic overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19 4.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23 4.4.1 Electromechanical remote reset . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23 4.4.2 Mechanical remote reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24 4.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26 4.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26 4.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-29 4.5.3 Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-31 4.6 Dimensioned drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . 4-34 4.7 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-37 4.7.1 3RU11 thermal overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-37 4.7.2 3RB10 electronic overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-43 4.7.3 3RB12 electronic overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-47 5 3RA1 fuseless load feeders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 5.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . 5-2 5.2 Device descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3 5.2.1 Mounting systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4 5.2.2 Mounting kits for self-assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5 5.2.3 Complete devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5 5.3 Application and areas of use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7 5.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8 5.4.1 Accessories for the individual devices . . . . . . . . . . . . . . . . . . . . . . . . 5-8 5.4.2 Accessories specifically for the SIRIUS 3RA fuseless load feeder . . . . . . . . . . 5-8 5.4.3 Instructions for self-assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9 5.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18 5.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18 5.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21 5.5.3 Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23 5.6 Dimensioned drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . 5-24 5.7 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28 6 3RH, 3TX, LZX coupling links . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 6.1 Specifications/regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2 6.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3 6.2.1 Relay coupling modules versus semiconductor coupling modules . . . . . . . . . . 6-4 6.2.2 Coupling links in two-tier and box terminal format . . . . . . . . . . . . . . . . . . 6-5 6.2.3 Plug-in relay coupling links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6 6.2.4 Coupling links for direct attachment . . . . . . . . . . . . . . . . . . . . . . . . . 6-7 6.2.5 SIRIUS contactor relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7 6.2.6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7

SIRIUS System Manual

iv GWA 4NEB 430 0999-02b 6.2.7 Notes on configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8 6.2.8 Explanation of terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9 6.3 Application and areas of use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10 6.3.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10 6.3.2 Criteria for selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10 6.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12 6.4.1 Accessories for two-tier coupling links . . . . . . . . . . . . . . . . . . . . . . . . 6-12 6.4.2 Accessories for LZX plug-in relay coupling links . . . . . . . . . . . . . . . . . . . . 6-13 6.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14 6.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14 6.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14 6.5.3 Device circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16 6.6 Dimensioned drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . . 6-20 6.7 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-22 7 3RP10, 3RP15 solid-state time relays . . . . . . . . . . . . . . . . . . . . . . . . 7-1 7.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2 7.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3 7.2.1 Device types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3 7.2.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4 7.2.3 Special features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5 7.2.4 Notes on configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5 7.2.5 Explanation of terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7 7.3 Applications and uses (types of function) . . . . . . . . . . . . . . . . . . . . . . . 7-8 7.3.1 Multifunction (3RP10 00 solid-state time relay) . . . . . . . . . . . . . . . . . . . . 7-8 7.3.2 Multifunctional (3RP15 05 solid-state time relay) . . . . . . . . . . . . . . . . . . . 7-11 7.3.3 On-delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16 7.3.4 Off-delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17 7.3.5 Clock pulse generator (3RP15 55 solid-state time relay) . . . . . . . . . . . . . . . . 7-18 7.3.6 Star-delta function (3RP15 74/76 solid-state time relay) . . . . . . . . . . . . . . . . 7-19 7.3.7 Star-delta function with overtravel (3RP15 60 solid-state time relay) . . . . . . . . . . 7-19 7.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20 7.4.1 Accessories for 3RP10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20 7.4.2 Accessories for 3RP15 05 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20 7.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22 7.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22 7.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23 7.5.3 Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-24 7.6 Dimensioned drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . . 7-25 7.7 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-26 8 3RW3 semiconductor motor control unit . . . . . . . . . . . . . . . . . . . . . . 8-1 8.1 Specifications/regulations/approvals . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3 8.2 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5 8.2.1 Physical principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6 8.2.2 General device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10 8.2.3 Comparison of the 3RW3 semiconductor motor control unit (soft starter) with the SIKOSTART 3RW22 and SIKOSTART 3RW34 motor control units . . . . . . . . . . . 8-14 8.2.4 Comparison of the 3RW3 semiconductor motor control unit (soft starter) with the 3RA star-delta combination . . . . . . . . . . . . . . . . . . . . . . . . . 8-16 8.2.5 Notes on configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-16 8.3 Application and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-18

SIRIUS System Manual

GWA 4NEB 430 0999-02b v 8.3.1 Areas of application and criteria for selection . . . . . . . . . . . . . . . . . . . . . 8-18 8.3.2 Installation guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-18 8.3.3 Overview tables: correction factors . . . . . . . . . . . . . . . . . . . . . . . . . 8-21 8.3.3.1 3RW30/31 soft starters in a stand-alone installation . . . . . . . . . . . . . . . . . . . . 8-21 8.3.3.2 3RW30/31 soft starters in combination with the 3RV1 circuit breaker . . . . . . . . . . 8-22 8.3.3.3 Combining the 3RT contactor with the 3RU1 thermal overload relay and 3RW3 soft starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-24 8.3.3.4 Combining the 3RT contactor with the 3RB10 electronic overload relay and 3RW3 soft starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-26 8.3.4 Circuit example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-29 8.3.5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-30 8.3.6 Event messages and diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-32 8.3.7 Timing diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-33 8.4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-35 8.5 Mounting and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-37 8.5.1 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-37 8.5.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-37 8.5.3 Circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-38 8.6 Dimensioned drawings (dimensions in mm) . . . . . . . . . . . . . . . . . . . . . 8-41 8.7 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-42 8.7.1 Control electronics/power electronics . . . . . . . . . . . . . . . . . . . . . . . . 8-42 8.7.2 Short-circuit protection and fuse coordination . . . . . . . . . . . . . . . . . . . . 8-45 8.7.3 Site altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-50 8.7.4 Specifications in acc. with IEC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-51 8.7.5 Specifications in acc. with NEMA . . . . . . . . . . . . . . . . . . . . . . . . . . 8-52 Index Index-1

SIRIUS System Manual

GWA 4NEB 430 0999-02b vii Figures Figure 1-1: SIRIUS system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5 Figure 1-2: Circuit breaker, accessories (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6 Figure 1-3: Circuit breakers, accessories (frame sizes S0, S2, and S3) . . . . . . . . . . . . . . . . . . 1-6 Figure 1-4: Contactors, accessories (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7 Figure 1-5: Contactors, accessories (frame sizes S0 to S3). . . . . . . . . . . . . . . . . . . . . . . . . 1-8 Figure 1-6: Device combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13 Figure 1-7: Contactor combination for reversing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14 Figure 1-8: Cage Clamp terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-18 Figure 1-9: Conductor cross-sections £ 1 mm² . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-20 Figure 1-10: Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-22 Figure 2-1: 3RV1 circuit breakers (frame sizes S00 to S3). . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Figure 2-2: Setting the current setting Ie (example: frame size S00) . . . . . . . . . . . . . . . . . . . 2-7 Figure 2-3: Sealing the adjustment scale (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . 2-8 Figure 2-4: Tripped position, 3RV (frame size S0). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9 Figure 2-5: Locking the toggle switch (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9 Figure 2-6: Time-current characteristic, chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11 Figure 2-7: Frequency sensitivity of the n-short-circuit releases . . . . . . . . . . . . . . . . . . . . . . 2-12 Figure 2-8: Circuit breaker with overload relay function (frame sizes S0 to S3) . . . . . . . . . . . . 2-14 Figure 2-9: Circuit diagrams of circuit breakers for fuse monitoring. . . . . . . . . . . . . . . . . . . . 2-15 Figure 2-10: Mounting the transverse auxiliary switch (frame size S00) . . . . . . . . . . . . . . . . . . 2-19 Figure 2-11: Mounting/removing the lateral auxiliary switch/undervoltage release (frame size S00) 2-20 Figure 2-12: Mounting the disconnecting module (frame size S0) . . . . . . . . . . . . . . . . . . . . . 2-26 Figure 2-13: Locking the disconnecting module (frame size S0) . . . . . . . . . . . . . . . . . . . . . . 2-27 Figure 2-14: Locking the disconnecting module and mounting the cover (frame size S2) . . . . . . . 2-27 Figure 2-15: Mounting the rotary switch extension for the door (frame size S2) . . . . . . . . . . . . 2-28 Figure 2-16: Operating the rotary switch extension for the door . . . . . . . . . . . . . . . . . . . . . . 2-29 Figure 2-17: Locking the rotary switch extension for the door. . . . . . . . . . . . . . . . . . . . . . . . 2-30 Figure 2-18: Terminals for "Combination Motor Controller Type E" . . . . . . . . . . . . . . . . . . . . . 2-31 Figure 2-19: Molded-plastic surface casing (frame size S00). . . . . . . . . . . . . . . . . . . . . . . . . 2-32 Figure 2-20: Molded-plastic bay (frame size S00). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-33 Figure 2-21: Mounting the front plate (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-34 Figure 2-22: Mounting the front plate (frame size S0). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-34 Figure 2-23: Accessories for the housings and front plates (frame size S00). . . . . . . . . . . . . . . 2-35 Figure 2-24: Indicator light installation in a molded-plastic housing. . . . . . . . . . . . . . . . . . . . . 2-36 Figure 2-25: Mounting circuit breakers on busbar adapters (frame sizes S00 and S0) . . . . . . . . . 2-38 Figure 2-26: Mounting circuit breakers on busbar adapters (frame sizes S2 and S3) . . . . . . . . . . 2-39 Figure 2-27: Accessories for busbar adapters (frame sizes S00 to S2) . . . . . . . . . . . . . . . . . . 2-40 Figure 2-28: 3-phase busbar system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-41 Figure 2-29: Mounting the isolated 3-phase busbar system (frame sizes S00 to S0) . . . . . . . . . . 2-43 Figure 2-30: Mounting the isolated 3-phase busbar system (frame size S2) . . . . . . . . . . . . . . . 2-44 Figure 2-31: Mounting the circuit breakers onto the rail. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-45 Figure 2-32: Screw-on mounting of the 3RV1 (example: frame size S00). . . . . . . . . . . . . . . . . 2-45 Figure 2-33: Circuit breaker, soldering pin connector (frame size S00) . . . . . . . . . . . . . . . . . . 2-47 Figure 2-34: Device circuit diagram (frame size S00). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-48 Figure 2-35: Device circuit diagrams (frame sizes S0 to S3) . . . . . . . . . . . . . . . . . . . . . . . . . 2-48 Figure 2-36: Circuit breaker with relay function, device circuit diagrams (frame sizes S0 to S3) . . . 2-48 Figure 2-37: 3RV10 11, 3RV16 (frame size S00), 3RV10 21 (frame size S0) . . . . . . . . . . . . . . . 2-49 Figure 2-38: 3RV10 31 (frame size S2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-49 Figure 2-39: 3RV10 4 (frame size S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-49 Figure 2-40: 3RV11 21 (frame size S0), 3RV11 31 (frame size S2) . . . . . . . . . . . . . . . . . . . . . 2-50

SIRIUS System Manual

viii GWA 4NEB 430 0999-02b Figure 2-41: 3RV11 42 (frame size S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-50 Figure 2-42: 3RV19 28-1A (for frame size S0), 3RV19 38-1A (for frame size S2) . . . . . . . . . . . . 2-50 Figure 2-43: 3RV19 13-1. (for frame size S00). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-51 Figure 2-44: 3RV19 23-1. (for frame size S0), 3RV19 33-1. (for frame size S2). . . . . . . . . . . . . . 2-51 Figure 2-45: 3RV19 13-2DA00 (frame size S00), 3RV19 23-2DA00/-2GA00 (frame size S0). . . . . . 2-52 Figure 2-46: 3RV19 13-4C (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-52 Figure 2-47: 3RV19 23-4. (frame sizes S0, S2, S3). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-52 Figure 2-48: 3RV19 18-5A/-5B (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-53 Figure 2-49: 3RV19 26-0 (frame sizes S0, S2, S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-53 Figure 2-50: 3RV19 28-1H (frame size S0) and 3RT19 46-4GA07 (frame size S3) . . . . . . . . . . . . 2-53 Figure 2-51: 3RV19. 6-3AP0 for circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-54 Figure 2-52: 8US10.1-5DJ07, 8US1061-5FK08 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-55 Figure 2-53: 8US1251-5DM07, 8US1261-5FM08, 8US1923-2AA00 . . . . . . . . . . . . . . . . . . . . 2-55 Figure 2-54: 3RV19 15-1. (frame sizes S00, S0) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-55 Figure 2-55: 3RV19 35-1 (for circuit breakers in frame size S2) . . . . . . . . . . . . . . . . . . . . . . . 2-56 Figure 2-56: 3RV19 35-3 (for circuit breakers in frame size S2) . . . . . . . . . . . . . . . . . . . . . . . 2-56 Figure 2-57: 3RV19 15-5A, 3RV19 15-5B, 3RV19 25-5AB . . . . . . . . . . . . . . . . . . . . . . . . . . 2-56 Figure 2-58: 3RV19 35-5A, 3RV19 15-5D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-57 Figure 3-1: Frame sizes of the 3RT1 contactors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10 Figure 3-2: Contact areas. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 Figure 3-3: Characteristic curve of the electrical service life of the main contacts (frame size S00) 3-17 Figure 3-4: Characteristic curve of the electrical service life of the main contacts (frame size S0). 3-17 Figure 3-5: Characteristic curve of the electrical service life of the main contacts (frame size S2). 3-18 Figure 3-6: Characteristic curve of the electrical service life of the main contacts (frame size S3). 3-18 Figure 3-7: Characteristic curve of the electrical service life of the auxiliary contacts . . . . . . . . 3-19 Figure 3-8: Capacitor-switching contactors (frame sizes S0 and S2) . . . . . . . . . . . . . . . . . . . 3-25 Figure 3-9: Capacitor-switching contactors, circuit diagram . . . . . . . . . . . . . . . . . . . . . . . . 3-26 Figure 3-10: Contactors with an extended operating range, circuit diagrams . . . . . . . . . . . . . . 3-28 Figure 3-11: Contactors with an extended operating range, terminal markings . . . . . . . . . . . . . 3-28 Figure 3-12: Contactors with an extended operating range, circuit diagram . . . . . . . . . . . . . . . 3-28 Figure 3-13: Contactor relays: voltage ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-31 Figure 3-14: Fully assembled contactor combination for reversing (frame sizes S00 and S0) . . . . 3-32 Figure 3-15: Star-delta combination, locking device at the front (frame size S0). . . . . . . . . . . . . 3-34 Figure 3-16: Star-delta combination, locking devices at the front (frame sizes S2/S3) . . . . . . . . . 3-34 Figure 3-17: 4-pole contactor combination for reversing (frame size S0) . . . . . . . . . . . . . . . . . 3-38 Figure 3-18: 4-pole contactor combination for reversing (frame size S2) . . . . . . . . . . . . . . . . . 3-39 Figure 3-19: NC contact interlock (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-39 Figure 3-20: Contactor combination for reversing, main circuit (frame sizes S00 to S3) . . . . . . . . 3-40 Figure 3-21: Contactor combination for reversing, control circuit (frame size S00) . . . . . . . . . . . 3-40 Figure 3-22: Contactor combination for reversing, control circuit (frame sizes S0 to S3). . . . . . . . 3-41 Figure 3-23: Star-delta combinations (frame sizes S00, S0, S3). . . . . . . . . . . . . . . . . . . . . . . 3-42 Figure 3-24: Star-delta combination (frame size S2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-43 Figure 3-25: Star-delta combination, main circuit (frame sizes S00 to S3) . . . . . . . . . . . . . . . . 3-47 Figure 3-26: Star-delta combination, control circuit (frame size S00) . . . . . . . . . . . . . . . . . . . . 3-48 Figure 3-27: Star-delta combination, control circuit (frame sizes S0 to S3) . . . . . . . . . . . . . . . . 3-48 Figure 3-28: Accessories for contactors of frame size S00. . . . . . . . . . . . . . . . . . . . . . . . . . 3-49 Figure 3-29: Accessories for auxiliary contactors/contactor relays of frame size S00. . . . . . . . . . 3-50 Figure 3-30: Accessories for contactors of frame size S00. . . . . . . . . . . . . . . . . . . . . . . . . . 3-51 Figure 3-31: Auxiliary switch at front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-54 Figure 3-32: Auxiliary switch at side. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-55 Figure 3-33: Switching of the auxiliary contact elements. . . . . . . . . . . . . . . . . . . . . . . . . . . 3-56 Figure 3-34: Auxiliary contacts, contactors for switching motors (frame size S00) . . . . . . . . . . . 3-58

SIRIUS System Manual

GWA 4NEB 430 0999-02b ix Figure 3-35: Auxiliary contacts, contactors for switching motors (frame sizes S0 to S3). . . . . . . . 3-59 Figure 3-36: Graphical symbols for auxiliary contact elements in acc. with EN 50 012 (excerpt). . . 3-60 Figure 3-37: Device circuit diagrams of the auxiliary switch blocks (DIN EN 50 012) . . . . . . . . . . 3-60 Figure 3-38: Auxiliary contacts for auxiliary contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-61 Figure 3-39: Graphical symbols for auxiliary contactors in acc. with EN 50 011 (excerpt) . . . . . . . 3-62 Figure 3-40: Device circuit diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-63 Figure 3-41: Position diagrams of the auxiliary switches (frame sizes S0 to S3). . . . . . . . . . . . . 3-63 Figure 3-42: Time-delay auxiliary switch block (frame size S00). . . . . . . . . . . . . . . . . . . . . . . 3-65 Figure 3-43: Function diagrams of the time-delay auxiliary switches (frame size S00) . . . . . . . . . 3-65 Figure 3-44: Time-delay auxiliary switch block (frame sizes S0 to S3) . . . . . . . . . . . . . . . . . . . 3-66 Figure 3-45: Time-delay auxiliary switches, function diagrams (frame sizes S0 to S3) . . . . . . . . . 3-67 Figure 3-46: Control of loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-68 Figure 3-47: Solid-state time relay block with semiconductor output, installation (frame size S00) . 3-68 Figure 3-48: Solid-state time relay block with semiconductor output, function diagrams (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-69 Figure 3-49: Solid-state time relay with semiconductor output, circuit diagrams (frame size S00). . 3-69 Figure 3-50: Solid-state time relay with a semiconductor output, installation (frame size S00) . . . . 3-69 Figure 3-51: Solid-state time relay with semiconductor output, circuit diagrams . . . . . . . . . . . . 3-70 Figure 3-52: Solid-state time relay with semiconductor output, function diagrams . . . . . . . . . . . 3-70 Figure 3-53: Coupling link (frame sizes S0 to S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-71 Figure 3-54: Coupling link, circuit diagram (frame sizes S0 to S3). . . . . . . . . . . . . . . . . . . . . . 3-72 Figure 3-55: Disconnecting an unused contactor coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-73 Figure 3-56: Circuit with a varistor (AC/DC operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-74 Figure 3-57: Circuit with an RC element (AC/DC operation) . . . . . . . . . . . . . . . . . . . . . . . . . 3-74 Figure 3-58: Circuit with a diode (AC/DC operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-75 Figure 3-59: Surge suppressors, installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-77 Figure 3-60: RC element/varistor, circuit diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-78 Figure 3-61: LED module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-79 Figure 3-62: EMC suppression module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-80 Figure 3-63: Soldering pin connection, mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-81 Figure 3-64: Mounting the soldering pin connection on a 4-pole auxiliary switch block . . . . . . . . 3-81 Figure 3-65: Removing the spring from the soldering pin connection . . . . . . . . . . . . . . . . . . . 3-82 Figure 3-66: Terminal covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-85 Figure 3-67: 3RT: Screw-on attachment (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . 3-86 Figure 3-68: Snap-on attachment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-87 Figure 3-69: Installation positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-87 Figure 3-70: Cage Clamp terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-89 Figure 3-71: Insulation stop with Cage Clamp terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-89 Figure 3-72: Replacing the magnet coil (frame size S0/AC). . . . . . . . . . . . . . . . . . . . . . . . . . 3-92 Figure 3-73: Replacing the magnet coil (frame size S2/AC). . . . . . . . . . . . . . . . . . . . . . . . . . 3-93 Figure 3-74: Replacing the magnet coil (frame size S2/DC). . . . . . . . . . . . . . . . . . . . . . . . . . 3-94 Figure 3-75: Replacing the magnet coil (frame size S3/AC). . . . . . . . . . . . . . . . . . . . . . . . . . 3-95 Figure 3-76: Replacing the magnet coil (frame size S3/DC). . . . . . . . . . . . . . . . . . . . . . . . . . 3-96 Figure 3-77: Replacing the contact piece (frame size S2). . . . . . . . . . . . . . . . . . . . . . . . . . . 3-97 Figure 3-78: Replacing the contact piece (frame size S3). . . . . . . . . . . . . . . . . . . . . . . . . . . 3-98 Figure 3-79: Contact pieces (frame sizes S2/S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-98 Figure 3-80: 3RT1. 10 1/3RH11 contactors (frame size S00). . . . . . . . . . . . . . . . . . . . . . . . . 3-99 Figure 3-81: 3RT10 2 contactors, 3RT10 2 contactor relays (frame size S0) . . . . . . . . . . . . . . . 3-99 Figure 3-82: 3RT10 3 (frame size S2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-100 Figure 3-83: 3RT10 4, 3RT14 46 (frame size S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-100 Figure 3-84: 3RT10 1 (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-101 Figure 3-85: 3RT13 1, 3RT15 1 (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-101

SIRIUS System Manual

x GWA 4NEB 430 0999-02b Figure 3-86: 3RT13 2, 3RT15 2 (frame size S0). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-101 Figure 3-87: 3RT133, 3RT153 (frame size S2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-102 Figure 3-88: 3RT13 4 (frame size S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-102 Figure 3-89: 3RT1626 (frame size S0) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-103 Figure 3-90: 3RT1636 (frame size S2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-103 Figure 3-91: 3RT1646 (frame size S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-103 Figure 3-92: 3RT10 17, 3RH 11 (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-104 Figure 3-93: 3RT10 2, view from right (frame size S0) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-104 Figure 3-94: 3RT103, view from right (frame size S2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-104 Figure 3-95: 3RT104, view from right (frame size S3). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-104 Figure 3-96: 3RT1916-2E.., -2F.., -2G.. (frame size S00), 3RT19 26-2E.., -2F.., -2G.. (frame sizes S0 to S3) . . . . . . . . . . . . . . . . . . . . . . . 3-105 Figure 3-97: 3RT19 16-2 (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3RT19 26-2 (frame sizes S0 to S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-105 Figure 3-98: 3RH19 11-1AA.., 3RH19 11-1BA... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-105 Figure 3-99: Contactor combination for reversing (frame size S00) . . . . . . . . . . . . . . . . . . . . 3-107 Figure 3-100:Contactor combination for reversing (frame size S0) . . . . . . . . . . . . . . . . . . . . . 3-107 Figure 3-101:Contactor combination for reversing (frame size S2) . . . . . . . . . . . . . . . . . . . . . 3-107 Figure 3-102:Contactor combination for reversing (frame size S3) . . . . . . . . . . . . . . . . . . . . . 3-107 Figure 3-103:3RA1924-2B (frame sizes S0 to S3) 3RA1924-1A (frame sizes S0 to S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-108 Figure 3-104:Contactor combinations for star/delta (frame sizes S00 - S00 - S00) . . . . . . . . . . . . 3-108 Figure 3-105:Contactor combinations for star/delta (frame sizes S0 - S0 - S0) . . . . . . . . . . . . . . 3-108 Figure 3-106:Contactor combinations for star/delta (frame sizes S2 - S2 - S0) . . . . . . . . . . . . . . 3-108 Figure 3-107:Contactor combinations for star/delta (frame sizes S2 - S2 - S2) . . . . . . . . . . . . . . 3-109 Figure 3-108:Contactor combinations for star/delta (frame sizes S3 - S3 - S3) . . . . . . . . . . . . . . 3-109 Figure 4-1: 3RU11 overload relays (frame sizes S00 to S2). . . . . . . . . . . . . . . . . . . . . . . . . 4-6 Figure 4-2: 3RU11 overload relay (frame size S3). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6 Figure 4-3: 3RB12 electronic overload relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7 Figure 4-4: 3RU11 front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15 Figure 4-5: Setting the rated current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16 Figure 4-6: Sealing the adjustment scale (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . 4-16 Figure 4-7: Manual/automatic switchover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17 Figure 4-8: Time-current characteristic, chart for the 3RU11 . . . . . . . . . . . . . . . . . . . . . . . . 4-18 Figure 4-9: Time-current characteristics for class 10 and class 20, chart for the 3RB10 . . . . . . . 4-18 Figure 4-10: Front view of the 3RB12 electronic overload relays . . . . . . . . . . . . . . . . . . . . . . 4-19 Figure 4-11: Time-current characteristics, chart for the 3RB12 . . . . . . . . . . . . . . . . . . . . . . . 4-21 Figure 4-12: Electronic overload relay with analog output, front view . . . . . . . . . . . . . . . . . . . 4-21 Figure 4-13: Electrical remote reset, installation/removal. . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23 Figure 4-14: Mechanical remote reset: resetting plunger, installation . . . . . . . . . . . . . . . . . . . 4-24 Figure 4-15: Mechanical remote reset: resetting plunger, removal. . . . . . . . . . . . . . . . . . . . . 4-24 Figure 4-16: Mechanical remote reset: wire release, installation . . . . . . . . . . . . . . . . . . . . . . 4-25 Figure 4-17: Mechanical remote reset: wire release, removal . . . . . . . . . . . . . . . . . . . . . . . . 4-25 Figure 4-18: Mounting onto the 3RT contactor/3RW3 soft starter . . . . . . . . . . . . . . . . . . . . . 4-26 Figure 4-19: Stand-alone holder, example 3RU11 (frame size S00/S0) . . . . . . . . . . . . . . . . . . 4-27 Figure 4-20: Stand-alone holder, example 3RU11 (frame size S2/S3) . . . . . . . . . . . . . . . . . . . 4-27 Figure 4-21: Snap-on mounting and removal with the 3RT contactor . . . . . . . . . . . . . . . . . . . 4-27 Figure 4-22: Permissible installation positions for the 3RU11 . . . . . . . . . . . . . . . . . . . . . . . . 4-28 Figure 4-23: Loop-through system, 3RB1246 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-29 Figure 4-24: 3RU11: Cage Clamp terminal (frame size S2) . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30 Figure 4-25: 3RU11 circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-31 Figure 4-26: 3RU11 and 3RB10 device circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-31

SIRIUS System Manual

GWA 4NEB 430 0999-02b xi Figure 4-27: Connection example for the 3RU11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32 Figure 4-28: Connection example for the 3RU10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32 Figure 4-29: Connection plants for 3RB12 single-phase motors . . . . . . . . . . . . . . . . . . . . . . 4-33 Figure 4-30: 3RU11 16-..B0, (frame size S00) 3RU11 16, 3RB10 16, (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34 Figure 4-31: 3RU11 26-.B., 3RB10 26, (frame size S0) 3RU11 36-..B., 3RB10 36, (frame size S2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34 Figure 4-32: 3RU11 46-..B., 3RB10 46 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34 Figure 4-33: 3RB12 46, 3RB12 5. / 3RB12 62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-35 Figure 4-34: 3RU11 16-..C1 (frame size S00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-35 Figure 4-35: 3RU11 26-..D0 (frame size S0), 3RU11 36-..D0 (frame size S2). . . . . . . . . . . . . . . 4-35 Figure 4-36: 3RU11 46-..D0 (frame size S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-36 Figure 5-1: Rail adapter/busbar adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4 Figure 5-2: Self-assembly of a fuseless load feeder (frame size S00) . . . . . . . . . . . . . . . . . . 5-5 Figure 5-3: Self-assembly, rail, reversing operation (frame size S00) . . . . . . . . . . . . . . . . . . . 5-9 Figure 5-4: Self-assembly, rail, direct starter (frame sizes S00 to S3) . . . . . . . . . . . . . . . . . . 5-10 Figure 5-5: Self-assembly, rail, direct starter (frame size S00, Cage Clamp) . . . . . . . . . . . . . . 5-11 Figure 5-6: Self-assembly, rail, reversing operation (frame size S0) . . . . . . . . . . . . . . . . . . . . 5-12 Figure 5-7: Self-assembly, rail, reversing operation (frame sizes S2 and S3) . . . . . . . . . . . . . . 5-13 Figure 5-8: Self-assembly, busbars, direct starters (frame sizes S00 and S2). . . . . . . . . . . . . . 5-14 Figure 5-9: Self-assembly, busbars, direct starters (frame size S00/S0, Cage Clamp) . . . . . . . . 5-15 Figure 5-10: Self-assembly, busbars, reversing operation (frame sizes S00 and S0) . . . . . . . . . . 5-16 Figure 5-11: Self-assembly, busbars, reversing operation (frame size S2) . . . . . . . . . . . . . . . . 5-17 Figure 5-12: Screw-on attachment, fuseless load feeder (frame size S00) . . . . . . . . . . . . . . . . 5-19 Figure 5-13: Busbar system, mounting/removal (frame sizes S00 to S2) . . . . . . . . . . . . . . . . . 5-20 Figure 5-14: Circuit diagrams, direct starters (frame sizes S00 to S3) . . . . . . . . . . . . . . . . . . . 5-23 Figure 5-15: Circuit diagrams, reversing starters (frame sizes S00 to S3). . . . . . . . . . . . . . . . . 5-23 Figure 5-16: 3RA11 10-..A.. for direct-on-line starting 3RA12 10-..A.. for reversing operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24 Figure 5-17: 3RA11 10-..C.., 3RA11 10-..D.. for direct-on-line starting 3RA12 10-..C.., 3RA12 10-..D.. for reversing operation . . . . . . . . . . . . . . . . . . . . 5-24 Figure 5-18: 3RA11 20-..A.. for direct-on-line starting 3RA12 20-..B.. for reversing operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25 Figure 5-19: 3RA11 20-..C.., 3RA11 20-..D.. for direct-on-line starting 3RA1220-..C.., 3RA1120-..D.. for reversing operation. . . . . . . . . . . . . . . . . . . . . 5-25 Figure 5-20: 3RA1 direct-on-line starting (frame size S2) 3RA1 reversing operation (frame size S2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26 Figure 5-21: 3RA1 direct-on-line starting (frame size S0) 3RA1 reversing operation (frame size S0) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26 Figure 5-22: 3RA1 direct-on-line starting (frame size S3) 3RA1 reversing operation (frame size S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-27 Figure 6-1: Output coupler, Input coupler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5 Figure 6-2: Basic circuit diagram, line capacitance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8 Figure 6-3: Application example, coupling links in box terminal format. . . . . . . . . . . . . . . . . . 6-10 Figure 6-4: 24-pole connection lead for two-tier coupling links . . . . . . . . . . . . . . . . . . . . . . 6-12 Figure 6-5: 24-pole connection comb for two-tier coupling links. . . . . . . . . . . . . . . . . . . . . . 6-12 Figure 6-6: Cage Clamp terminals, coupling links. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14 Figure 7-1: 3RP1000 solid-state time relay, multifunctional . . . . . . . . . . . . . . . . . . . . . . . . 7-3 Figure 7-2: 3RP15 solid-state time relay, multifunctional with 2 changeover contacts . . . . . . . . 7-4 Figure 7-3: 3RP10 00 (multifunctional) operating time adjustment . . . . . . . . . . . . . . . . . . . . . 7-8 Figure 7-4: 3RP10 00 (multifunctional) function setting . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9 Figure 7-5: 3RP15 05 (multifunctional) operating time adjustment . . . . . . . . . . . . . . . . . . . . 7-11

SIRIUS System Manual

xii GWA 4NEB 430 0999-02b Figure 7-6: 3RP15 05 (multifunctional) function identification . . . . . . . . . . . . . . . . . . . . . . . 7-12 Figure 7-7: 3RP10 function diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16 Figure 7-8: 3RP15 1. function diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16 Figure 7-9: 3RP15 25 function diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17 Figure 7-10: 3RP15 27 function diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17 Figure 7-11: 3RP15 3. function diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17 Figure 7-12: 3RP15 40 function diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-18 Figure 7-13: 3RP15 55 function diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19 Figure 7-14: 3RP15 7. function diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-19 Figure 7-15:Coding plug set (3RP10 00). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20 Figure 7-16: Label set (3RP15) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20 Figure 7-17: Screw-on attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21 Figure 7-18: 3RP10: mounting on and removal from a 35 mm rail . . . . . . . . . . . . . . . . . . . . . 7-22 Figure 7-19: Rail mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22 Figure 7-20: Cage Clamp terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23 Figure 8-1: 3RW3 soft starter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5 Figure 8-1: Typical current and torque curve of a three-phase asynchronous motor . . . . . . . . . 8-6 Figure 8-2: Current and torque curves for star-delta starting . . . . . . . . . . . . . . . . . . . . . . . . 8-7 Figure 8-3: Method of operation of a frequency converter . . . . . . . . . . . . . . . . . . . . . . . . . 8-8 Figure 8-4: Phase firing of the supply voltage by semiconductor elements in the 3RW3 soft starter 8-9 Figure 8-5: Current and torque curves for a soft starter. . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10 Figure 8-6: Time ramp/timing diagram, 3RW30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12 Figure 8-7: Time ramp, 3RW31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12 Figure 8-8: Overview of soft starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-14 Figure 8-9: Load and motor torques and motor terminal voltage for operation with soft starter . . 8-17 Figure 8-10: 3RW3 soft starter + 3RV1 circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-22 Figure 8-11: 3RT+3RU1+3RW3 combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-24 Figure 8-12: 3RT+3RB10+3RW3 combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-26 Figure 8-13: 3RT+3RW3+3RB10 combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-27 Figure 8-14: Circuit example, 3RW3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-29 Figure 8-15: Settings, 3RW3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-30 Figure 8-16: Position of the terminals and the potentiometers for adjustment. . . . . . . . . . . . . . 8-32 Figure 8-17: Starting and coasting-down behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-33 Figure 8-18: Supply interruption in the bypassed state . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-34 Figure 8-19: Accessories: attachment of the fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-36 Figure 8-20: Connection example with an RC element . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-36 Figure 8-21: Circuit diagrams, 3RW3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-38 Figure 8-22: Circuit diagrams, 3RW30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-38 Figure 8-23: Circuit diagrams, 3RW31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-39 Figure 8-24: Motor control with an electromechanical brake . . . . . . . . . . . . . . . . . . . . . . . . 8-40 Figure 8-25: Reductions as a function of site altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-50

SIRIUS System Manual

GWA 4NEB 430 0999-02b xv Tables Table 1-1: Components and combinations with accessories . . . . . . . . . . . . . . . . . . . . . . 1-12 Table 1-2: Mounting methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-15 Table 1-3: Mounting the device on the rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-16 Table 1-4: Removing the device from the rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-16 Table 1-5: How to use a Cage Clamp terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-19 Table 1-6: Connection cross-section for frame size S00 . . . . . . . . . . . . . . . . . . . . . . . . 1-20 Table 1-7: Connection cross-section for frame size S0 . . . . . . . . . . . . . . . . . . . . . . . . . 1-20 Table 1-8: Connection cross-section for frame size S2 . . . . . . . . . . . . . . . . . . . . . . . . . 1-21 Table 1-9: Connection cross-section for frame size S3 . . . . . . . . . . . . . . . . . . . . . . . . . 1-21 Table 2-1: Circuit breakers, frame sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 Table 2-2: Contact position indicators of the circuit breakers . . . . . . . . . . . . . . . . . . . . . . 2-9 Table 2-3: Testing overload tripping (example: frame size S00) . . . . . . . . . . . . . . . . . . . . 2-10 Table 2-4: Suggestions for switching direct current . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16 Table 2-5: Attachable accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19 Table 2-6: Voltage ranges of the auxiliary releases . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20 Table 2-7: Testing overload tripping (example: frame size S0) . . . . . . . . . . . . . . . . . . . . . 2-21 Table 2-8: Alarm switch with tripped signal and short circuit signal . . . . . . . . . . . . . . . . . . 2-22 Table 2-9: Mounting the remote-control mechanism (frame size S2) . . . . . . . . . . . . . . . . 2-25 Table 2-10: Opening a cubicle door using the rotary switch extension . . . . . . . . . . . . . . . . 2-29 Table 2-11: Mounting the extension shaft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-30 Table 2-12: Housings for circuit breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-32 Table 2-13: Front plates for any housings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-33 Table 2-14: Busbar systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-37 Table 2-15: Dimensions of the busbar adapters and accessories . . . . . . . . . . . . . . . . . . . . 2-37 Table 2-16: Link modules for connecting circuit breakers to contactors . . . . . . . . . . . . . . . . 2-38 Table 2-17: Rated operational voltage/current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-41 Table 2-18: Types of 3-phase busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-41 Table 2-19: Conductor cross-section of the 3-phase feed-in terminals . . . . . . . . . . . . . . . . 2-42 Table 3-1: Utilization categories, test conditions for AC voltage . . . . . . . . . . . . . . . . . . . . 3-4 Table 3-2: Utilization categories, test conditions for DC voltages . . . . . . . . . . . . . . . . . . . 3-5 Table 3-3: Utilization categories, test conditions for AC voltage (auxiliary contact elements) . . 3-5 Table 3-4: Utilization categories, test conditions for DC voltage (auxiliary contact elements) . . 3-6 Table 3-5: Safe isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8 Table 3-6: Performance ranges of the 3RT10 contactors . . . . . . . . . . . . . . . . . . . . . . . . 3-10 Table 3-7: Types of 3RT/3RH contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11 Table 3-8: Actuating systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12 Table 3-9: Mechanical endurance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14 Table 3-10: Comparison between the 3RT1446 and 3RT1046 contactors . . . . . . . . . . . . . . 3-21 Table 3-11: Applications of 4-pole contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22 Table 3-12: 4-pole contactors and auxiliary contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22 Table 3-13: 4-pole reversing contactor combination with front interlock (frame size S0) . . . . . . 3-23

SIRIUS System Manual

xvi GWA 4NEB 430 0999-02b Table 3-14: 4-pole reversing contactor combination with lateral interlock (frame size S0) . . . . . 3-24 Table 3-15: 4-pole reversing contactor combination (frame sizes S2 and S3) . . . . . . . . . . . . 3-24 Table 3-16: Assembling the contactor combination for reversing (frame size S00) . . . . . . . . . 3-35 Table 3-17: Assembling the contactor combination for reversing (frame size S0) . . . . . . . . . . 3-36 Table 3-18: Assembling the contactor combination for reversing (frame sizes S2/S3) . . . . . . . 3-37 Table 3-19: Configuration of the star-delta combinations . . . . . . . . . . . . . . . . . . . . . . . . . 3-44 Table 3-20: Assembly of the star-delta combination in frame size S00 . . . . . . . . . . . . . . . . 3-45 Table 3-21: Assembly of the star-delta combinations in frame sizes S0 to S3 . . . . . . . . . . . . 3-46 Table 3-22: Auxiliary switch blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-53 Table 3-23: Expansion options for auxiliary switch blocks . . . . . . . . . . . . . . . . . . . . . . . . 3-54 Table 3-24: Possible auxiliary switch combinations (frame size S0/S2) . . . . . . . . . . . . . . . . 3-55 Table 3-25: Possible auxiliary switch combinations (frame size S3) . . . . . . . . . . . . . . . . . . 3-55 Table 3-26: Possible auxiliary switch combinations with 4-pole/capacitor-switching contactors . 3-56 Table 3-27: Auxiliary switches with make-before-break contacting . . . . . . . . . . . . . . . . . . 3-56 Table 3-28: Surge suppressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-75 Table 3-29: How surge suppressors work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-76 Table 3-30: Conductor cross-sections of 3-pole auxiliary connecting lead terminals (for frame size S3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-79 Table 3-31: Parallel links making and breaking capacity . . . . . . . . . . . . . . . . . . . . . . . . . . 3-83 Table 3-32: Parallel connections Variants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-84 Table 3-33: Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-84 Table 3-34: Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-86 Table 3-35: Vertical installation position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-88 Table 3-36: Conductor cross-sections (frame sizes S00 to S3) . . . . . . . . . . . . . . . . . . . . . 3-91 Table 4-1: Tripping classes/tripping times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 Table 4-2: Operating limits of time-delayed overload releases in the case of an all-pole load . . 4-2 Table 4-3: SIRIUS overload relays, configuration and functions . . . . . . . . . . . . . . . . . . . . 4-8 Table 4-4: Assignment of the overload relays to the contactors . . . . . . . . . . . . . . . . . . . . 4-9 Table 4-5: 3RU11/3RB10 auxiliary contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16 Table 4-6: Recovery time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17 Table 4-7: Failure of the control supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20 Table 5-1: Fuseless load feeder, accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8 Table 5-2: Self-assembly of the reversing starter for rail (frame size S00) . . . . . . . . . . . . . . 5-9 Table 5-3: Conductor cross-sections (frame size S00/S0) . . . . . . . . . . . . . . . . . . . . . . . . 5-21 Table 5-4: Conductor cross-sections (frame size S2) . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21 Table 5-5: Conductor cross-sections (frame size S3) . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22 Table 6-1: Regulations and specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2 Table 6-2: 3RH, 3TX, LZX coupling links - overview of the device groups with their distinguishing features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3 Table 6-3: Comparison: Relay coupling modules and semiconductor coupling modules . . . . . 6-4 Table 6-4: Selection criteria for the 3RH, 3TX, and LZX coupling links . . . . . . . . . . . . . . . . 6-11 Table 6-5: Conductor cross-sections for the 3RH, 3TX, and LZX coupling links . . . . . . . . . . 6-15 Table 6-6: Technical specifications, 3TX70 relay coupling links . . . . . . . . . . . . . . . . . . . . 6-22 Table 6-7: Technical specifications, 3TX7004/3TX7005 semiconductor coupling links . . . . . . 6-22

SIRIUS System Manual

GWA 4NEB 430 0999-02b xvii Table 6-8: Technical specifications, 3TX7002/3TX7003 semiconductor coupling links . . . . . . 6-22 Table 6-9: Technical specifications, LZX: RT/PT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-23 Table 6-10: Technical specifications, LZX: MT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-23 Table 6-11: Technical specifications, 3RH1924/3TX7090 . . . . . . . . . . . . . . . . . . . . . . . . . 6-24 Table 7-1: 3RP10 00 (multifunctional) operating time adjustment . . . . . . . . . . . . . . . . . . 7-8 Table 7-2: 3RP10 00 (multifunctional) circuit diagrams and function diagrams . . . . . . . . . . . 7-10 Table 7-3: 3RP15 05 (multifunctional) operating time adjustment . . . . . . . . . . . . . . . . . . 7-11 Table 7-4: 3RP15 05 (multifunctional) assignment of the identifying letters . . . . . . . . . . . . 7-13 Table 7-5: Function diagrams and circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-15 Table 7-6: Sealable cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-21 Table 7-7: Permissible conductor cross-sections for control and load current connections: . . . 7-23 Table 7-8: Technical specifications for the time relay . . . . . . . . . . . . . . . . . . . . . . . . . . 7-26 Table 8-1: Standards, certificates, and approvals, 3RW3 . . . . . . . . . . . . . . . . . . . . . . . . 8-3 Table 8-2: 3RW3, frame sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5 Table 8-3: Link modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-13 Table 8-4: Comparison of 3RW3/3RA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-16 Table 8-5: Stand-alone installation, minimum clearances at the side, 3RW3 . . . . . . . . . . . . 8-19 Table 8-6: Stand-alone installation, minimum clearances at the side, 3RW3 . . . . . . . . . . . . 8-19 Table 8-7: Correction factors, 3RW30/31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-22 Table 8-8: Correction factors: 3RV1 circuit breaker + 3RW3 soft starter . . . . . . . . . . . . . . 8-23 Table 8-9: 3RW3 installation guidelines, minimum clearances/lengths . . . . . . . . . . . . . . . . 8-24 Table 8-10: Correction factors, 3RT contactor + 3RU therm. overload relay + 3RW soft starter . 8-25 Table 8-11: 3RT + 3RB10 + 3RW3 installation guidelines, minimum clearances/minimum lengths 8-26 Table 8-12: 3RT1 + 3RW30/31 + 3RB10 installation guidelines, minimum clearances/minimum lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-27 Table 8-13: Correction factors, 3RT contactor + 3RB10 electronic overload relay + 3RW soft starter . . . . . . . . . . . . . . . . . . . . . . . . . 8-28 Table 8-14: 3RW30/31 event messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-32 Table 8-15: 3RW30/31 diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-33 Table 8-16: Accessories, 3RW30/31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-35 Table 8-17: Conductor cross-sections, 3RW30/31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-37 Table 8-18: Fuse configurations (SITOR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-46 Table 8-19: Fuse configurations (SITOR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-47 Table 8-20: Motor feeder: fuseless configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-48 Table 8-21: Motor feeder: fused configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-49 Table 8-22: 3RW3 motor ratings in acc. with IEC at 40° C . . . . . . . . . . . . . . . . . . . . . . . . 8-51 Table 8-23: 3RW3 motor ratings in acc. with IEC at 50° C . . . . . . . . . . . . . . . . . . . . . . . . 8-51 Table 8-24: 3RW3 motor ratings in acc. with IEC at 60° C . . . . . . . . . . . . . . . . . . . . . . . . 8-51 Table 8-25: 3RW3 motor ratings in acc. with NEMA at 40° C . . . . . . . . . . . . . . . . . . . . . . 8-52 Table 8-26: 3RW3 motor ratings in acc. with NEMA at 50° C . . . . . . . . . . . . . . . . . . . . . . 8-52 Table 8-27: 3RW3 motor ratings in acc. with NEMA at 60° C . . . . . . . . . . . . . . . . . . . . . . 8-52

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-1 1 System overview Section Subject Page 1.1 Specifications/regulations/approvals 1-3 1.2 Overview: Range of devices 1-5 1.3 System features 1-10 1.4 Components and combinations 1-11 1.5 Mounting methods and terminal systems 1-15 1.5.1 Mounting the equipment 1-15 1.5.2 Screw-type terminals 1-17 1.5.3 Cage Clamp terminals 1-18 1.5.4 Connection cross-sections 1-20 1.6 Communication 1-22 1.6.1 Communication-capable low-voltage switching technology 1-22 1.6.2 Parameterization of PROFIBUS-DP and bus-capable low-voltage switching devices 1-23 1.6.3 Actuator-sensor interface (AS-Interface) 1-23

SIRIUS System Manual

1-2 GWA 4NEB 430 0999-02b Introduction Siemens is one of the leading manufacturers of switchgear. The product range extends from devices that switch a few mA to circuit breakers used in power distribution. Throughout the continuing development of these products we have always striven to ensure that requirements in terms of fundamental performance features, electrical and mechanical service life, dimensions, and ease of installation and maintenance are met or exceeded. We have been able to meet the demands resulting from increased environ- mental awareness, particularly in the last ten years or so, by developing and using environment-friendly and recyclable materials. As a result, we have developed modern industrial switching devices, particularly in the field of low-voltage switchgear, that meet all the relevant demands in terms of envi- ronment-friendliness. Building on decades of experience, we have created a completely new gen- eration of circuit breakers, contactors, auxiliary contactors, overload relays, contactor relays, time relays, and 3RW3 semiconductor motor control devices (referred to below as soft starters) under the name SIRIUS for the large and continuously growing number of motor drives in the range up to 45 kW. These new SIRIUS devices fulfill all the demands placed on them in practice and can be used as stand-alone devices or modular components of com- plete load feeders, or integrated in low-voltage distribution cabinets or low- voltage switching stations.

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-3 1.1 Specifications/regulations/approvals Explosion protection Motor protection devices that protect a motor from overload in a hazardous area must meet certain requirements. These requirements are defined in the following standards: DIN VDE 0660, DIN VDE 0165, EN 60947-1:1991..+A11:1994, EN 60947-4-1, EN 50014:1994, EN 50019:1978+A1 to A5 Compliance with these standards has up until now been established by means of a test. Compliance could be documented in two ways: 1. By a test certificate from the manufacturer 2. By a test certificate from an independent test laboratory (e.g. PTB, DMT, KEMA, etc.). EU directive Testing of explosion protection has been defined more precisely as a result of the harmonization of the European Union. In addition to the above stan- dards, tests will also carried out in acc. with the EU directive 94/9/EC or ATEX 100a. Two procedures are in operation during the transition period up until 2003: Procedure 1 Test certificate from an independent test laboratory as usual (e.g. PTB, DMT, KEMA, etc.). Procedure 2 Special test certificate from certified test laboratories (in acc. with extended European rules). The statutory basis for this is the Official Journal of the European Union (no. 95/C2 15/02 of 19.08.1995). Siemens SIRIUS switching devices are tested and certified twice: Certificate 1 Test certificate from KEMA in the same way as before (valid until 2003) in acc. with: • DIN VDE 0660, DIN VDE 0165 • EN 60947-1:1991/A11 • EN 60947-4-1:1992, EN 50019:1978+A1 to A5 Certificate 2 Special test certificate from the DMT-BVS in acc. with: • DIN VDE 0660, DIN VDE 0165 • EN 60947-1:1991..+A11:1994, EN 60947-4-1 • EN 50014:1994, EN 50019:1978 + A1 to A5 • EU directive 94/9/EC (ATEX 100a - EU directive)

SIRIUS System Manual

1-4 GWA 4NEB 430 0999-02b DMT-BVS The DMT-BVS is, like the PTB, a certified German testing organization in compliance with the EU directive 76/117/EEC and EIExV. Like the PTB and other testing institutes in Europe, the DMT-BVS tests and awards certifi- cates in acc. with the explosion protection directive 94/9/EC and is accred- ited accordingly. Over 100 years ago, the DMT-BVS became the first testing station for explo- sion protection in Germany, and it has been a testing station for electrical equipment as well since 1912. DMT-BVS certificates are recognized through- out the world. For support in export matters, the DMT-BVS works with the chemical industry and is of course recognized by it. KEMA KEMA, which is a testing institute that enjoys worldwide recognition, is a certified European institute with many years of experience of testing for explosion protection. For support in export matters, KEMA also works with testing stations throughout the world.

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-5 1.2 Overview: Range of devices SIRIUS system The SIRIUS product range consists of 3RV circuit breakers, 3RT contactors, 3RH/3RT auxiliary contactors and contactor relays, 3RU thermal overload relays, 3RB10/3RB12 electronic overload relays, 3RP time relays, 3RW3 semiconductor motor control devices (referred to below as soft starters), and combinations of these devices, which form the 3RA load feeders. The individual devices are developed and built in such a way that it is very easy to put them together to make load feeders. This is possible because the devices are all built to work together on both an electrical and a mechan- ical level. Figure 1-1: SIRIUS system NSB00296

SIRIUS System Manual

1-6 GWA 4NEB 430 0999-02b Circuit breaker with a frame size of S00 and attachable accessories: Figure 1-2: Circuit breaker, accessories (frame size S00) Circuit breakers with frame sizes of S0, S2, and S3 and attachable accessories: Figure 1-3: Circuit breakers, accessories (frame sizes S0, S2, and S3) Attachable accessories for frame sizes S00, S0, S2, and S3: 1) Transverse auxiliary switch 2) Lateral auxiliary switch with 2 contacts 3) Lateral auxiliary switch with 4 contacts 4) Shunt release 5) Undervoltage release 6.1)Undervoltage release with leading auxiliary contacts (S00) 6.2)Undervoltage release with leading auxiliary contacts (S0 to S3) 7) Alarm switch (S0 to S3) 8) Disconnecting module (S0 and S2) NSB00005c 3 5 4 6.1 1 2 NSB00006c 3 5 4 8 1 2 7 6.2

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-7 Contactors with a frame size of S00 and accessories: Figure 1-4: Contactors, accessories (frame size S00) 1) Contactor 2) Contactor relay 3) Solid-state time relay block, on-delay 4) Solid-state time relay block, off-delay 5) Auxiliary switch block, time-delay (on-delay or off-delay or star-delta function) 6) 1-pole auxiliary switch block, infeed from above 7) 2-pole auxiliary switch block, infeed from above 8) 1-pole auxiliary switch block, infeed from below 9) 2-pole auxiliary switch block, infeed from below 10) 4-pole auxiliary switch block (terminal markings in acc. with DIN EN 50 012 or DIN EN 50 005) 11) 2-pole auxiliary switch block, standard or electronic type (terminal markings in acc. with DIN EN 50 005) 12) Soldering pin adapter for contactors with 4-pole auxiliary switch block 13) Soldering pin adapter for contactors and contactor relays 14) Additional load module to increase the permissible residual current 15) Surge suppressor with LED 16) Surge suppressor without LED 17) 3-phase feed-in terminal 18) Parallel link (neutral bridge), 3-pole, without terminal 19) Parallel link, 3-pole, with terminal 20) Parallel link, 4-pole, with terminal NSB00448 15 3 4 5 6 7 8 9 10 11 14 20 19 16 12 13 1 17 18 2

SIRIUS System Manual

1-8 GWA 4NEB 430 0999-02b Contactors with frame sizes of S0 to S3 with accessories: Figure 1-5: Contactors, accessories (frame sizes S0 to S3) 1) Contactor, frame size S0 2) Contactor, frame size S2 3) Contactor, frame size S3 For frame sizes S0 to S3: 4) Solid-state time relay block, on-delay 5) Solid-state time relay block, off-delay 6) Auxiliary switch block, time-delay (on- or off-delay or star-delta function) 7) 2-pole auxiliary switch block, infeed from above 8) 2-pole auxiliary switch block, infeed from below 9) 4-pole auxiliary switch block (terminal markings in acc. with DIN EN 50 012 or DIN EN 50 005) 10) Parallel link (neutral bridge), 3-pole, without terminal 11) Parallel link, 3-pole, with terminal NSB00449 4 10 5 18 17 16 11 1 12 9 6 15 14 1 8 7 13 16 19 21 20 2 21 22 23 20 3

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-9 12) 2-pole auxiliary switch block, attachable on the right or left side (terminal markings in acc. with DIN EN 50 012 or DIN EN 50 005) 13) 1-pole auxiliary switch block (a maximum of 4 can be snapped on) 14) Mechanical interlock, attachable at the side 15) Mechanical interlock, attachable at the front 16) Wiring blocks above and below (reversing mode) 17) Surge suppressor (varistor, RC element, diode combination), attachable above or below (varies for S0 and S2/S3) 18) Coupling link for direct connection to the contactor coil 19) LED block to display contactor function For frame sizes S2 and S3 only: 20) Terminal for contactor coil for setting up contactor combinations 21)Terminal cover for box terminals For frame size S3 only: 22)Terminal cover for terminal end and bar connection 23)Auxiliary connecting lead terminal, 3-pole

SIRIUS System Manual

1-10 GWA 4NEB 430 0999-02b 1.3 System features The entire SIRIUS range of devices is divided up into only four frame sizes (S00 up to 5.5 kW, S0 up to 11 kW, S2 up to 22 kW, and S3 up to 45 kW) with three different widths (45 mm for S00 and S0, 55 mm for S2, and 70 mm for S3) and has a uniform range of accessories for all frame sizes. Modular system The individual components of the SIRIUS range are building blocks in a mod- ular system that are harmonized in terms of both their frame size and their technical specifications. This ensures that individual requirements can be met quickly and cost-effectively. Uniformity The devices are harmonized with regard to their ratings and their technical specifications: • The same width ensures rapid installation. • The terminal systems are standardized, and devices with the same rated current have the same terminals. Performance capability All SIRIUS devices can be mounted side by side without derating in an ambi- ent air temperature of up to 60 °C. Accessories All accessories, such as the auxiliary switches and surge suppressors, can be mounted and removed without tools. You can use link modules that connect devices both mechanically and elec- trically to put together combinations of devices and build fuseless load feed- ers. Communication Direct communication with a higher-level controller is possible using: • The AS-Interface load feeder module • The ET 200X distributed I/O devices on the PROFIBUS-DP bus system • The ET 200S system

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-11 1.4 Components and combinations This section describes the components of the SIRIUS system and the device combinations that are possible with these components. Components of the SIRIUS system The following table contains a list of the components of the SIRIUS system together with the most important accessories: Components Brief description/features Accessories 3RV1 circuit breakers - Switch and protect motors and other loads up to 100 A - Auxiliary switches (transverse, lat- eral) - Undervoltage releases - Shunt releases - Alarm switches - Housing - 3-phase busbar system 3RT10 motor contac- tors - Switch motors up to 4 kW and currents up to 95 A - Types: 3-pole for switching - 4-pole, with 4 NO and 2 S + 2 NC contacts - Soldering pin adapter - Capacitor switching contactor - Reversing and star-delta combinations - Auxiliary switch blocks - Surge suppressors - Parallel links - Time relay blocks - Link modules - Wiring blocks 3RH11 contactor relays - Same type of construction as the 3RT - Basic version: 4-pole, expandable to 8 pins by means of auxiliary switch blocks - High contact stability (1 mA; 17 V) 3RT10/3RH11 contactor relays - Switch motors and auxiliary contactors with an extended operating range (17 V to 30 V) 3RU11 overload relays - CLASS 10 - Phase loss sensitivity - Series auxiliary contacts 1 NO + 1 NC contact - Frame size S00: repetition terminal for the auxiliary contact and coil connection for attachment to contactors - Integrated, transparent and sealable cover for the adjusting knob and test function - Remote RESET, electrical - Mechanical RESET - Terminal bracket for stand-alone installation 3RB10 overload relays - CLASS 10 and CLASS 20 - Rapid tripping operation in the event of phase loss (< 3 s) - Series auxiliary contacts 1 NO + 1 NC - Low power loss, energy-saving - Wide adjustment ranges for simple configura- tion, selection, and less storage - Extremely low energy requirements, approx. 50 mW - Remote RESET, electrical - Mechanical RESET - Terminal bracket for stand-alone installation

SIRIUS System Manual

1-12 GWA 4NEB 430 0999-02b Table 1-1: Components and combinations with accessories 3RB12 overload relays - CLASS 5 to CLASS 30 can be set - Phase loss sensitivity - 2 outputs per 1 NO + 1 NC contact - Integrated current transformers in all sizes - Motor protection due to the connection of a thermistor sensor circuit - Internal ground fault monitoring - Overload warning - Remote and automatic reset possible - High tripping accuracy - Wide adjustment ranges - Self-monitoring - Summation current transformer for external ground fault monitoring - DC adapter - Terminal cover 3RA1 load feeders - Fuseless load feeder consisting of a circuit breaker and contactor - Simple assembly with link modules and wir- ing blocks - Reversing combination (link modules) - Star-delta combination - Accessories for the basic devices (contactors and circuit breakers) - Special accessories: Auxiliary switches connectable from above or below 3RP10/15 solid-state time relays - 8 adjustable time ranges from 0.05 seconds to 10 hours - Constantly high repeatability - Type with combination voltage (24 VDC and 110 to 240 VAC) - 2 device types: on-delay and multifunctional (7 functions) - Long mechanical and electrical service life - Coding plug sets - Locking device 3RW30/31 soft starters - Reduction of the starting current for a smooth start - Soft coasting down function - Only 3 motor supply leads are required - System adaptation using setting options: starting time, starting voltage, coasting down time - Fans Load feeders with communication capa- bility Complete load feeders - At the AS-Interface with the AS-Interface IP65 compact starter AS-Interface IP20 load feeder module - On the Profibus-DP through the following sys- tems ET 200X with IP65 protection ET 200S with IP20 protection - Supply modules - Wiring Components Brief description/features Accessories

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-13 Device combinations The following diagrams show you the possible device combinations, using the S00 frame size as an example: Figure 1-6: Device combinations 3RV10 circuit breaker 3RA19 link module 3RT10 contactor 3RT10 contactor 3RU11 overload relay Fuseless load feeder Fused load feeder 3RA13 reversing combination 3RA14 star-delta combination

SIRIUS System Manual

1-14 GWA 4NEB 430 0999-02b Contactor combination for reversing the S00 frame size (with accessories): Figure 1-7: Contactor combination for reversing Individual parts: 1/2) Contactors 4/5/6)Kit The kit includes: 4) Mechanical interlock 5) 2 connection clips for 2 contactors 6) Wiring blocks above and below to connect the main conducting paths with electrical interlock (NC contact interlock - can be removed if required) Attachable accessories: 13) Soldering pin adapter 14) Auxiliary switch block, on the front (only an auxiliary switch blocks that complies with DIN EN 50 005 can be used) 16) Surge suppressor 2 6 1 6 4 5 NSB00459 13 14 14 14 14 14 16 13

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-15 1.5 Mounting methods and terminal systems 1.5.1 Mounting the equipment The method of mounting the equipment is uniform within each frame size. Table 1-2: Mounting methods Screw-on mounting The SIRIUS switching devices can be screwed on to a flat surface. Please note the following points with some of the devices: • 3RV1 circuit breaker, frame sizes S00/S0: Push-in lugs are required for screw-type mounting • 3RP15 time relay: Push-in lugs are required for screw-type mounting • Coupling links: No screw-type mounting • Soft starters: No screw-type mounting Snap-on mounting The SIRIUS switching devices are snapped onto 35 mm rails in acc. with DIN EN 50 022 without a tool. The devices with a frame size of S3 require a rail with an installation height of 15 mm. Alternatively, they can also be snapped onto 75 mm rails. Frame size Mounting Removal S00 to S3 Screwed on Removed with a screwdriver S00, S0 Snapped onto a 35 mm rail (in acc. with DIN EN 50 022) Removed without a tool S2 Snapped onto a 35 mm rail (in acc. with DIN EN 50 022) The snap-on spring can be opened with a screwdriver S3 Snapped onto a 35 mm rail (in acc. with DIN EN 50 022) Snapped onto a 75 mm rail The snap-on spring can be opened with a screwdriver

SIRIUS System Manual

1-16 GWA 4NEB 430 0999-02b The following table shows you how to mount the device onto the rail: Table 1-3: Mounting the device on the rail The following table shows you how to remove the device from the rail: Table 1-4: Removing the device from the rail You will find notes on mounting the different devices on the rail in the rele- vant parts of section n.5 on mounting methods and terminal systems. Frame size Procedure Illustration S00/S0 Place the device on the upper edge of the rail, and press it down- wards until it snaps onto the lower edge of the rail. S2/S3 Place the device on the upper edge of the rail, and tilt it towards the rail until it snaps onto the lower edge of the rail. Frame size Procedure Illustration S00/S0 Push the device downwards to release the tension of the mounting spring, and remove the device by tilting it. S2/S3 Using a screwdriver, push the clip on the lower rear side of the device downwards to release the tension of the mounting spring (1), and remove the device by tilting it (2). 2 1 1 1 2

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-17 1.5.2 Screw-type terminals The terminals used do not vary within a frame size. The current switched by the different devices of a single frame size does not vary either. This means you can use the same tool, torque, and conductor cross-section for the cir- cuit breakers, contactors, and overload relays of a single frame size. The stripped lengths are also the same. This is important in the case of prefabri- cated wiring. Screw-type terminals All the devices have screw-type terminals, either a terminal with a top washer or a box terminal, depending on the frame size. Devices with frame sizes S00 and S0 have terminals with captive screws and terminal washers that enable you to connect 2 conductors, even if they have different cross-sections. The box terminals of frame size S2 and S3 can also take 2 conductors with different cross-sections. Connection tools Use the following tools to make the connection: • Frame sizes S00 to S2: Screws are available for rated currents of up to 50 A for Pozidriv2 screwdrivers. • Frame size S3: To obtain the required torques for the frame size for up to 100 A, the screws have a 4 mm hexagon socket. The screwdriver guides allow screwdriving machines to be used. Lugs and connecting bars You can remove the box terminals from the devices with a frame size of S3 to connect conductors with lugs or connecting bars. A terminal cover is available as shock protection and to ensure that you comply with the required creepages and clearances when the box terminals are removed. You can find a detailed description in section n.4 on accessories.

SIRIUS System Manual

1-18 GWA 4NEB 430 0999-02b 1.5.3 Cage Clamp terminals The Cage Clamp terminal system is now available for circuit breakers, con- tactors, overload relays, and time relays. Cage-type clamping units, known as Cage Clamp terminals in the case of SIRIUS products, facilitate quick and maintenance-free wiring. Design The Cage Clamp terminal consists of two parts: • A power rail for conducting current • A sprung cage-type clamp for clamping strength Figure 1-8: Cage Clamp terminal Conductors The Cage Clamp terminal on the switching devices clamps all copper wires (single-core, stranded and finely stranded) from 0.25 mm2 to 2.5 mm2. The conductors can be clamped directly or with some protection for splicing. To this end, wire end ferrules or pin-end connectors can be placed on the con- ductor ends. The best solution is an ultrasonically condensed conductor. Clamp Power rail Single-core Stranded Finely stranded Finely stranded with wire end ferrule

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-19 Safety The devices are equipped with a two-wire connection. In other words, there are two independent connections for each conducting path. Only one conductor is connected to each clamping unit. The clamp presses the conductor against the power rail, which is curved at this point. The high specific compressive load thus achieved is gas-tight. The clamp presses its flat surface against the conductor, thus avoiding dam- age to it. The spring force of the clamp is designed so that it automatically adjusts to the radius of the conductor. This allows any deformation of the conductor to be dealt with. It is not possible for the clamping unit to loosen by itself. This connection is vibration- and shock-proof. These types of stress do not damage the conductor or cause any loss in contact. Machines and systems in which this type of stress occurs, such as vibrators and elevators, are particularly suitable applications for this connection. Transfer accuracy The contact pressure between the conductor and power rail is optimal, mak- ing this clamp terminal suitable for high-voltage installations and also for the transfer of voltages and currents in the mV and mA ranges in measuring technology and electronics. Tool Screwdrivers can be obtained from the NSK (low-voltage switchgear) cata- log for opening the Cage Clamp terminals. Procedure The following table shows you how to use the Cage Clamp: Table 1-5: How to use a Cage Clamp terminal Step Procedure 1 Insert the screwdriver into the rectangularopening until it stops. The screwdriver head auto- matically keeps the clamp open. 2 Insert the conductor into the oval terminal opening. 3 Remove the screwdriver. The terminal closes, and the conductor is thus secu- rely clamped. NSJ 00001 NSJ 00002 NSJ 00003

SIRIUS System Manual

1-20 GWA 4NEB 430 0999-02b Small conductor cross- sections With conductor cross-sections that are ≤ 1 mm2, you have to use an insula- ting stop to ensure the conductors remain securely clamped. The illustration below shows the procedure: Figure 1-9: Conductor cross-sections ≤ 1 mm² 1.5.4 Connection cross-sections Because SIRIUS is a modular system, the connection cross-sections are the same for all devices of a single frame size. The following tables specify the permissible conductor cross-sections for main and auxiliary conductor connections: Frame size S00 Table 1-6: Connection cross-section for frame size S00 Frame size S0 Table 1-7: Connection cross-section for frame size S0 ≤ 1 mm² 3RT1916-4JA02 Main and auxiliary conductors ∅ 5 to 6 mm/PZ2 0.8 to 1.2 Nm 7 to 10.3 lb.in Cage Clamp 2 x (0.5 to 1.5 mm²) 2 x (0.75 to 2.5 mm²) 2 x (0.25 to 2.5 mm²) 2 x (0.5 to 1.5 mm²) 2 x (0.75 to 2.5 mm²) 2 x (0.25 to 1.5 mm²) ---- 2 x (0.25 to 2.5 mm²) AWG 2 x (18 to 14) 2 x (24 to 14) 10 10 10 Control conductor: A1/A2 Auxiliary conductor: NO/NC Main conductor Screw-type terminal Cage Clamp terminal L1 L2 L3 T1 T2 T3 ∅ 5 to 6 mm/PZ2 0.8 1.2 Nm 7 to 10.3 lb.in ---- 2 to 2.5 Nm 18 to 22 lb.in 2 x (0.5 to 1.5 mm²) 2 x (0.75 to 2.5 mm²) 2 x (0.25 to 2.5 mm²) 2 x (1 to 2.5 mm²) 2 x (2.5 to 6 mm²) 2 x (0.5 to 1.5 mm²) 2 x (0.75 to 2.5 mm²) 2 x (0.25 to 1.5 mm²) 2 x (1 to 2.5 mm²) 2 x (2.5 to 6 mm²) ---- 2 x (0.25 to 2.5 mm²) ---- AWG 2 x (18 to 14) 2 x (24 to 14) 2 x (14 to 10) 10 10 10

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-21 Frame size S2 Table 1-8: Connection cross-section for frame size S2 Frame size S3 Table 1-9: Connection cross-section for frame size S3 Control conductor: A1/A2 Auxiliary conductor: NO/NC Main conductor Screw-type terminal Cage Clamp terminal L1 L2 L3 T1 T2 T3 ∅ 5 to 6 mm/PZ2 0.8 to 1.2 Nm 7 to 10.3 lb.in ---- ∅5 to 6 mm/PZ2 3 to 4.5 Nm 27 to 40 lb.in 2 x (0.5 to 1.5 mm²) 2 x (0.75 to 2.5 mm²) 2 x (0.25 to 2.5 mm²) 2 x (0.75 to 16 mm²) 2 x (0.5 to 2.5 mm²) 2 x (0.25 to 1.5 mm²) 2 x (0.75 to 16 mm²) 1 x (0.75 to 25 mm²) ---- ---- ---- 2 x (0.75 to 25 mm²) 1 x (0.75 to 35 mm²) AWG 2 x (18 to 14) 2 x (24 to 14) AWG 2 x (18 to 3) 1 x (18 to 2) 10 13 10 13 13 Control conductor: A1/A2 Auxiliary conductor: NO/NC Main conductor Screw-type terminal Cage Clamp terminal L1 L2 L3 T1 T2 T3 ∅5 to 6 mm/PZ2 0.8 to 1.2 Nm 7 to 10.3 lb.in ---- 4 to 6 Nm 35 to 53 lb.in 2 x (0.5 to 1.5 mm²) 2 x (0.75 to 2.5 mm²) 2 x (0.25 to 2.5 mm²) 2 x (2.5 to 16 mm²) 2 x (0.5 to 2.5 mm²) 2 x (0.25 to 1.5 mm²) 2 x (2.5 to 35 mm²) 1 x (2.5 to 50 mm²) ---- ---- 2 x (10 to 50 mm²) 1 x (10 to 70 mm²) AWG 2 x (18 to 14) 2 x (24 to 14) AWG 2 x (10 to 1/0) 1 x (10 to 2/0) min 22 4 10 17 10 17 10 17

SIRIUS System Manual

1-22 GWA 4NEB 430 0999-02b 1.6 Communication Figure 1-10: Communication 1.6.1 Communication-capable low-voltage switching technology This uniform range of communication-capable Siemens switching devices represents an innovative concept for effective cubicle automation. Commu- nication with the higher-level control system via open, PROFIBUS-DP, and AS-Interface connections. Actuator-sensor inter- face (AS-Interface) AS-Interface is a standardized, non-proprietary networking system (IEC 62026-2) for simple and usually binary actuators and sensors. It is pos- sible to connect it to SIMATIC programmable logic controllers via different master modules. A DP/AS-Interface link also ensures direct integration in a PROFIBUS-DP system or connection to other field buses via couplers. Up to 248 sensors and 186 actuators can be connected to an AS-Interface network over a maximum of 500 m. Safety-related signals can now also be net- worked with AS-Interface, thus dispensing with the wiring of emergency stop signals that was needed previously. PROFIBUS PROFIBUS is a standardized, non-proprietary field bus system (IEC 61158) to which most PLCs of leading manufacturers can be connected. Up to 125 nodes can be incorporated in one bus segment. Distances of up to 9.6 km can be bridged with copper cables and up to 100 km with fiber-optic cables. S7-300 M 3 M 3 M 3 NSA00001b AS-Interface M 3 LOGO! PROFIBUS-DP NT NT Safety monitor CP 343-2 Proximity switch BERO Command devices SIGNUM pneumatisch AS-Interface Motor starter Signal column DP/AS-Interface Link SIMOVERT MASTER DRIVES Distributed I/O device ET 200X Motor starter 3RA5 Motor protection and control device SIMOCODE-DP 3UF50 Interface DP/3WN6 and Circuit breaker 3WN6 HMI/Visualization COROS/WIN CC SIMATIC S7/M7/C7 Input/output modules in IP 20 analog digital Membrane keyboard 3SB4 Input/output modules in IP 67 secure digital input modules Distributed I/O device ET 200S

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-23 PROFIBUS-DP PROFIBUS-DP (DP being a German abbreviation for distributed I/O) is used for switching devices with higher communication requirements (e.g. the transmission of analog actual values with extremely fast response times). It is also used to link individual AS-Interface segments. 1.6.2 Parameterization of PROFIBUS-DP and bus-capable low-voltage switching devices Before commissioning, PROFIBUS-DP must be configured, and the individ- ual bus nodes must be parameterized. There are user-friendly tools available to the user for configuration and parameter assignment. Parameter assignment tools • For SIMATIC S7 masters, all the functions are integrated in the STEP 7 programming language. • For SIMATIC S5 masters and various non-Siemens masters, the COM PROFIBUS parameter assignment software is required. • Manufacturers of non-Siemens masters offer other configuration and parameter assignment programs. Applications The above program packages make it easy to carry out the following for PROFIBUS-DP and its nodes: • Configuration • Parameter assignment • Documentation • Commissioning • Testing • Diagnostics For additional information on communication-capable low-voltage switching devices, as well as system components and accessories, see the following catalogs: • ST 70 "S7, M7 and C7 Programmable Logic Controllers" • IK PI "Industrial Communication and Field Devices" 1.6.3 Actuator-sensor interface (AS-Interface) The actuator-sensor interface (AS-Interface) is a modular networking system for sensors and actuators in the lowest field range. It makes no difference to the program in the programmable controller whether parallel wiring with input/output modules or AS-Interface is used. It is therefore possible for existing systems to change to AS-Interface because you can continue to use the same programs. The entire system can be oper- ated without additional software. It is not necessary to be familiar with the internal workings of AS-Interface.

SIRIUS System Manual

1-24 GWA 4NEB 430 0999-02b Replacement for the cable harness Process signals that occur in situ, are normally transferred to the open loop control using extensive parallel wiring and input/output modules. This means that each sensor or actuator in the field is connected to the input/ output modules with its own cable. AS-Interface makes it possible to replace this cable harness with a simple two-wire cable for all sensors or actuators. Data and power on a two-wire cable The master communicates with the nodes via the AS-Interface cable. As well as data, this cable also transfers the supply voltage for the electronic components and sensors. The voltage is supplied to the AS-Interface cable from a special AS-Interface power supply unit with a data link. Setting up different structures The AS-Interface cable is laid in the same way as for an electrical installa- tion. A new feeder can be inserted at any point. This makes it possible to set up network structures (e.g. tree, star or line structures). No shielding or ter- minating resistors are required. The wiring can be adapted individually to the system or machine. Detailed configuration and installation guidelines can be found in the instal- lation guideline "Montage des Vernetzungssystems AS-Interface" (on mount- ing the AS-Interface networking system). Maximum system con- figuration Up to 62 nodes can be connected to the AS-Interface cable. A node is, for example, an AS-Interface module (digital or analog) or a BERO (proximity switch) with an integrated AS-Interface chip. A maximum of 4 binary stan- dard sensors and/or 4 actuators can be connected to an AS-Interface mod- ule. This produces a maximum configuration of 248 sensors and 186 actuators (62 nodes x 4 inputs and 3 outputs). IP 67 degree of protection AS-Interface is a networking system for direct use on the machine. The AS- Interface user compact modules have IP 67 protection. They can be used in situ without being enclosed. There are also AS-Interface modules for use with IP 20 protection in the cubicles or distributed switchboxes.

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-25 New installation system All compact modules are placed on a mounting plate. The mounting plate takes the AS-Interface cable and keeps it in place. Polarity reversal is not possible due to the profile of the cable. The compact modules are simply hooked on at the top of the mounting plate and secured with just one screw. When you secure the modules, contact is made with the AS-Interface cable. You do not have to strip or screw on the cable. Coding prevents errors All the modules are mechanically and electrically coded. The coding system prevents errors occurring in the event of replacement. At replacement, only one module of the same type can ever be mounted. This stops digital or analog modules (or even inputs or outputs) getting mixed up. Addressing To participate in data transfer with the master, each node must be assigned an address before commissioning of the AS-Interface network. Addressing devices are available for this. Addressing an installed module There is an additional feature which makes new Siemens modules even more user-friendly: the addressing socket. Using this socket you can address a module after it has been installed. It is not necessary to unscrew the module. Installation can be carried out in the system by personnel who are not familiar with the AS-Interface. The com- missioning engineer can address the modules easily when they are already installed. For the first time, this type of addressing is also possible with IP 67 protection. Diagnostics at a glance The new generation of AS-Interface modules (compact modules, analog modules, and SlimLine modules) has the new display system developed by Siemens. The status of a module is displayed by two LEDs lighting up continuously or flashing. This simple diagnostic feature directly on the module makes it possible for the user to find the error quickly and efficiently. This in turn reduces down- times. Certificates of the AS- Interface association All Siemens AS-Interface products are tested in acc. with the relevant testing regulations in an accredited test laboratory and certified by the AS- Interface association.

SIRIUS System Manual

1-26 GWA 4NEB 430 0999-02b Digital compact mod- ules with IP 67 protection The AS-Interface modules in the compact range are characterized by opti- mized operating features and improved user-friendliness. This can reduce mounting and commissioning times for AS-Interface by up to 40%. Additional LEDs provide information on the most important operat- ing modes of the module, resulting in a considerable increase in system availability. The modules of the compact range consist of two components: Mounting plate and compact module The mounting plate mechanically fixes the AS-Interface profile cables, takes the compact module, and serves as a template with drill holes. The compact module contains the electronic components for communica- tion and the M12 standard connections for inputs/outputs. Up to four sen- sors and four actuators can be easily and reliably connected to the compact module using the M12 standard connection. The mounting plate and compact module are only connected to each other by means of a single screw. Contact is established with the AS-Interface cable by means of the proven insulation displacement method. AS-Interface modules in the compact range that have an M12 connection can have a protective conductor (PE) connected to them. Using an addressing socket integrated in the compact module, you can also allocate addresses when the module is in place. Analog compact mod- ules with IP 67 protection The design of the analog modules has been adapted for the compact mod- ules. The analog input and output modules each have two channels. You can connect measuring sensors and analog actuators using standard M12 con- nectors. The following groups of analog modules exist: • Input module for two current sensors • Input module for two voltage sensors • Input module for two thermal resistors • Output module for two current actuators • Output module for two voltage actuators All the measured values - except for the thermal resistance value of Pt 100 (not linear) - are available in linear form. In other words, the non-linear trans- mission curve of the thermal resistor sensor is automatically linearized in the analog module, and measured values can be processed directly in the programmable controller. The input and output channels are isolated. Two-wire and four-wire sensors can be connected. Differential inputs produce considerable suppression of common-mode interference. The integrating sigma-delta converter ensures high measurement accuracy.

SIRIUS System Manual

GWA 4NEB 430 0999-02b 1-27 Pneumatic compact modules with IP 65 and IP 67 protection The pneumatic compact module is a highly integrated AS-Interface slave. As an input/output module that is entirely suitable for field deployment, it has four electrical inputs and two pneumatic outputs. The electrical inputs behave in the same way as the inputs of the digital input/output compact modules. Both integrated pneumatic outputs are implemented by means of two pre- set 4/2-way valves (2 to 8 bar; 550 Nl/min) with a shared compressed-air supply and separate exhaust air collection and can be operated manually using separate slide valves. Two cylinders that work in tandem, for example, can be connected to a module in this range. Connections to AS-Interface are made via the standard mounting plate. The AS-Interface cable is inserted into the corresponding cable guides, and the upper part is secured to the mounting plate by means of a screw. The mod- ule is ready for use. Safety first - emergency stop via AS-i AS-Interface is the first system on the market that can transmit both stan- dard signals and safety-related input signals (e.g. emergency stop) via the same cable. Only an additional safety monitor and safe modules are required to use AS- Interface as a safety bus. This enables category 4 in acc. with EN 954-1 to be achieved. A failsafe programmable controller or special master is not nec- essary. The concept and implementation of AS-Interface Safety at Work (AS-Inter- face SaW) have been tested and certified by TÜV (technical testing associa- tion). This means that the system can be converted to the considerably more flex- ible AS-Interface network, which is already available, thus obviating the need for the complex, separately implemented emergency stop wiring that has been necessary up to now.

SIRIUS System Manual

GWA 4NEB 430 0999-02b 2-1 2 3RV1 circuit breakers Section Subject Page 2.1 Specifications/regulations/approvals 2-3 2.2 Device description 2-5 2.2.1 General description 2-6 2.2.2 Operation 2-7 2.2.3 Information on configuration 2-10 2.3 Field of application/variants 2-13 2.3.1 Motor protection 2-13 2.3.2 Transformer protection 2-13 2.3.3 Starter protection 2-13 2.3.4 Circuit breaker with overload relay function 2-14 2.3.5 Fuse monitoring 2-14 2.3.6 Switching direct current 2-16 2.3.7 Main and emergency stop switches 2-17 2.4 Accessories 2-18 2.4.1 Attachable accessories: Overview 2-18 2.4.2 Auxiliary switch, alarm switch, and auxiliary release 2-19 2.4.3 Motorized remote-control mechanism 2-23 2.4.4 Disconnecting module 2-26 2.4.5 Rotary switch extension for door 2-28 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508 2-31 2.4.7 Housing and mounting accessories 2-32 2.4.8 Busbar adapter 2-37 2.4.9 Isolated 3-phase busbar system 2-41

3RV1 circuit breakers

SIRIUS System Manual 2-2 GWA 4NEB 430 0999-02b 2.5 Mounting and connection 2-45 2.5.1 Mounting 2-45 2.5.2 Connection 2-46 2.5.3 Device circuit diagrams 2-48 2.6 Dimensioned drawings 2-49 2.7 Technical specifications 2-58 2.7.1 General specifications 2-58 2.7.2 Rated short-circuit breaking capacity Icn in acc. with IEC 60 947-2 2-63 2.7.3 Limiter function with standard devices for 500 VAC and 690 VAC in acc. with IEC 60 947-2 2-65 Section Subject Page

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-3 2.1 Specifications/regulations/approvals Standards • The 3RV1 circuit breakers comply with the specifications for circuit break- ers in acc. with IEC 60947-2/DIN VDE 0660, Part 101. • The circuit breakers for motor protection comply with the specifications in acc. with IEC 60947-4-1/DIN VDE 0660, Part 102. • The auxiliary switches comply with IEC 60947-5-1/DIN VDE 0660 Part 200. Approvals/ test reports Confirmation of approvals, test certificates, and characteristics can be obtained on the Internet/intranet. Terminal markings The terminal markings comply with DIN EN 50 011. Utilization categories Circuit breaker in acc. with IEC 60947-2: A Motor starter in acc. with IEC 60947-4-1: AC-3 (main conducting paths) DC - 11 / AC - 15 (control and auxiliary conducting paths) Main and emergency stop switches The specifications for the main and emergency switches comply with IEC 60204/DIN VDE 0113 Part 1. Disconnector specifications Disconnector specifications comply with IEC 60947-3. Shock protection 3RV1 circuit breakers are shockproof in acc. with DIN VDE 0106 Part 100, even without accessories. You can find additional information on the subject of shock protection in the "Switching, Protection and Distribution in Low- Voltage Networks" manual, p. 37 ff. Degree of protection The degree of protection of the 3RV1 circuit breaker is IP 20. In the terminal area of frame sizes S2 and S3 the degree of protection is IP 00. Characteristics The time-current characteristics, the current limitation characteristics and the I2t characteristics have been determined in acc. with IEC 60947 and DIN VDE 0660.

3RV1 circuit breakers

SIRIUS System Manual 2-4 GWA 4NEB 430 0999-02b Conditions of application Explosion-proof motors KEMA test report no. EX-97.Y.3236 in acc. with EN 50 019:1977 +A1 to A5 and DIN VDE 0165 DMT certificate in acc. with directive 94/9 EC (ATEX) in preparation Nuclear power plants KTA certificate Railway vehicles DIN EN 50 155 Ships and docks Shipbuilding certificates of classes GL, LRS or DNV.

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-5 2.2 Device description 3RV1 circuit breakers are used to switch and protect three-phase induction motors of up to 45 kW at 400 VAC and for loads with rated currents of up to 100 A. The 3RV1 circuit breakers have 3 poles. To achieve the highest degree of flexibility, auxiliary switches, alarm switches, auxiliary releases, and other accessories can be easily attached to the circuit breakers without tools, as required. 3RV1 circuit breakers and 3RT1 contactors are built to work together on both an electrical level and physically. This enables them to be easily and quickly put together to make load feeders. Frame sizes 3RV1 circuit breakers are available in 4 frame sizes (S00 to S3). Figure 2-1: 3RV1 circuit breakers (frame sizes S00 to S3) The following table shows you the frame sizes and the corresponding maxi- mum rated operational current at a voltage of 400 VAC. The last column in the table tells you which three-phase induction motor is suitable for which particular size. Table 2-1: Circuit breakers, frame sizes S00 S0 S2 S3 Frame size Width Max. rated operational current Output power of the three-phase induction motor S00 45 mm 12 A 5.5 kW S0 45 mm 25 A 11 kW S2 55 mm 50 A 22 kW S3 70 mm 100 A 45 kW

3RV1 circuit breakers

SIRIUS System Manual 2-6 GWA 4NEB 430 0999-02b 2.2.1 General description Fields of application The 3RV1 circuit breakers are suitable for: • Motor and plant protection • Transformer protection • Starter protection (short-circuit protection) The 3RV16 11-0BD10 circuit breaker, frame size S00, is used for fuse moni- toring. Releases 3RV1 circuit breakers have: • Inverse-time delay, thermal overload releases • Instantaneous short-circuit releases The overload releases can be set to the load current. The short-circuit releases are set permanently to 12 times the rated current, which allows motors to start up without problems. Circuit breakers used for transformer protection are set to 19 times the rated current to avoid being tripped by the high inrush current. When the circuit breakers are tripped, in the case of frame size S00 the tog- gle switch goes into the tripped position, and in the case of frame sizes S0 to S3 the rotary switch switches to the tripped position. Before it is switched on again, the rotary switch must be put in the 0 position manually to avoid switching to the fault inadvertently. In the case of circuit breakers with a rotary switch, the tripping operation can also be reported electrically by means of an alarm switch. Tripping classes In acc. with IEC 947-4-1: • Frame sizes S00 to S3: class 10 • Frame sizes S2/S3: class 20 Auxiliary release The circuit breakers can also be equipped with one of the following auxiliary releases: • Shunt release • Undervoltage release • Undervoltage release with leading auxiliary contacts Auxiliary contact ele- ments The circuit breakers can be equipped with a transverse auxiliary switch, an electronically optimized transverse auxiliary switch or a lateral auxiliary switch (Section 2.4 Accessories). Shock protection Shock protection can be improved by covering the terminals and connec- tions. This can be achieved with the following accessories: • Frame size S00, S0: protective caps for transverse auxiliary switches • Frame size S2, S3: terminal covers for box terminals • Terminal covers for lug and bar connection

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-7 Other accessories Other accessories for circuit breakers: • Alarm switch • Disconnecting module • Isolated 3-phase busbar system • Busbar adapter • Rotary switches • Terminals for "Combination Motor Controller Type E" in acc. with UL 508 • Housing and front plates 2.2.2 Operation Setting the values Using a screwdriver, set the load rated current (current setting) Ie on the scale of the circuit breaker. Note the two possible markings: • Dash marking: marking for a circuit breaker in a stand-alone installation • Triangle marking: marking for a circuit breaker in a side-by-side installation Figure 2-2: Setting the current setting Ie (example: frame size S00) Warning The adjusting knob can be turned 360° clockwise. You can only turn it coun- terclockwise within the adjustment range. 360° o.k. RV-00222 Ie Max. + 60 °C Max. + 70 °C A

3RV1 circuit breakers

SIRIUS System Manual 2-8 GWA 4NEB 430 0999-02b Sealing the adjustment scale You can prevent unauthorized adjustment of the current setting by placing a transparent cover over it and sealing it. Figure 2-3: Sealing the adjustment scale (frame size S00) 3RV1908-0P

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-9 Switches The state of the circuit breakers can be determined by the position of the switches: Table 2-2: Contact position indicators of the circuit breakers Figure 2-4: Tripped position, 3RV (frame size S0) Locking the circuit breakers You can prevent the circuit breaker from being switched on by unauthorized persons by securing the switch drive (toggle switch or rotary switch) with a padlock (shackle diameter 3.5 to 4.5 mm). Figure 2-5: Locking the toggle switch (frame size S00) Reclosing after a tripping operation After the circuit breaker has been tripped, the switch goes into the tripped position to indicate this. You use the switch to close the circuit again. In the case of frame sizes S0 to S3, the rotary switch must be put in the OFF position manually before it is switched on again to avoid switching to the fault inadvertently. In the case of frame sizes S2 and S3, it is possible to switch on and off using a motorized remote-control mechanism (see Section 2.4, Accessories). Frame size Switch STOP ON Tripped S00 Toggle switch O I O S0, S2, S3 Rotary switch OFF ON Tripped Ø 3.5 to 4.5 mm

3RV1 circuit breakers

SIRIUS System Manual 2-10 GWA 4NEB 430 0999-02b Testing overload tripping The following table shows you how overload tripping of the circuit breaker is tested: Table 2-3: Testing overload tripping (example: frame size S00) 2.2.3 Information on configuration Short-circuit protection The short-circuit releases of the 3RV1 circuit breakers execute a three-phase isolation of the faulty load feeder from the network and prevent any further damage. With a short-circuit breaking capacity of 50 kA or 100 kA and a voltage of 400 VAC, the switches are considered to be short circuit-proof, since hig- her short-circuit currents are not to be expected where the switches are installed. Backup fuses are only required if the short-circuit current at the point of installation exceeds the rated short-circuit breaking capacity of the circuit breakers. You will find the short-circuit breaking capacity for other voltages and the size of any required fuse listed in Section 2.6, Technical specifications. Conditions of applica- tion 3RV1 circuit breakers are climate-proof. They are intended for use in closed areas where there are no harzardous operating conditions such as dust, cor- rosive fumes or destructive gases. Appropriate housings are available as an accessory for use in dusty and damp areas (see Section 2.4). Inrush current Because the operational currents, the starting currents and the current spikes vary on account of the inrush current, even in motors of the same power, the motor powers listed in the tables are only guide values. Most important when selecting the correct circuit breakers are the concrete start- ing data and rating of the motor to be protected. This also applies to circuit breakers used for transformer protection. Drawing Step Procedure 1 Switch the toggle switch/rotary switch from 0 to 1. 2, 3 Put a screwdriver in the test opening and push it to the left. Overload tripping is in working order when the toggle switch switches from 1 to 0 (frame size S00) or goes into the trip- ped position (frame sizes S0 to S3). 2 3 1

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-11 Phase loss sensitivity The phase loss sensitivity of the circuit breaker ensures that it is tripped in good time in the event of the loss of a phase and the resulting overcurrents in the other phases. During normal operation, the device should have a three-pole load. To pro- tect single-phase loads or direct current loads, all 3 main conducting paths should be switched in series. Explosion protection Note In the case of a three-pole load, at 5 to 8 times the set current, the release time deviates by a maximum of ± 20% and therefore complies with the requirement of DIN VDE 0165 and EN 50019: 1977 +A1 to A5 and DIN VDE 0165. Characteristics The tripping characteristic of the inverse-time delayed overload release (thermal overload release, a-release) is valid for direct current and alternat- ing current with frequencies of 0 to 400 Hz. The characteristics are valid for tripping operations from a cold state. From a warm state, the release times of the thermal releases are reduced to approximately 25 %. The tripping characteristics of the instantaneous electromagnetic overcur- rent releases (short-circuit release, n-release) is based on the rated current In, which in circuit breakers with adjustable overload releases is also the upper value of the adjustment range. The following is a chart of the time-current characteristic: Figure 2-6: Time-current characteristic, chart Time-current characteristics, current-limiting characteristics and I2t characte- ristics can be requested directly from your sales representative, if neces- sary. 10 5 2 1 10 000 5000 2000 1000 500 200 100 50 20 10 5 0,2 1 0,5 0,02 0,1 0,05 0,002 0,01 0,005 100 60 40 2 0,6 0,8 1 2 3 4 6 8 10 0,001 20 30 40 80 x n NSB00004 min s A 60 current opening time three-pole load class 20 three-pole load class 10 two-pole load class 10

3RV1 circuit breakers

SIRIUS System Manual 2-12 GWA 4NEB 430 0999-02b Frequency sensitivity of the short-circuit releases The characteristics of the short-circuit releases apply to frequencies of 50/ 60 Hz. For lower frequencies, such as 16 2/3 Hz, for higher frequencies up to 400 Hz, and for direct current, appropriate correction factors have to be taken into account. The following characteristic curve illustrates the frequency sensitivity of the short-circuit releases (calibrated to 12 times Iu +20%): Figure 2-7: Frequency sensitivity of the n-short-circuit releases The increase in tripping current is approximately 30% for DC voltage. Frequency converters The thermal switch disconnectors do not have to be corrected when you use frequency converters. 40 30 20 10 0 -10 -20 -30 0 50 100 200 250 300 350 400 Hz 150 Tripping current Change in %

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-13 2.3 Field of application/variants The tripping characteristics of the 3RV1 circuit breakers are designed prima- rily to protect three-phase induction motors. The circuit breakers are therefore also referred to as motor protecting switches. The 3RV1 circuit breakers for motor protection are limited to the protection of systems. 2.3.1 Motor protection Set current The current of the motor that is to be protected is set on the adjustment scale. The short-circuit release is set at the factory to 12 times the value of the rated current of the circuit breaker. This ensures problem-free startup and reliable protection of the motor. Phase loss sensitivity The phase loss sensitivity of the circuit breaker ensures that it is tripped in good time in the event of the loss of a phase and the resulting overcurrents in the other phases. CLASS10/CLASS20 Circuit breakers of frame sizes S00 to S3 with thermal overload releases comply with tripping class 10 (CLASS 10). Circuit breakers with the CLASS 20 tripping characteristic are available for frame sizes S2 and S3 in difficult startup conditions. 2.3.2 Transformer protection Inrush current In the case of primary protection of control transformers, the high inrush currents that occur when the transformers are switched on often result in the unwanted tripping of the protective devices. The 3RV1 circuit breakers with frame sizes S0 and S2 therefore have over- current releases for the protection of transformers that are set at the factory to approximately 19 times the rated current. This makes it possible to pro- tect transformers in which the inrush currents reach peak values of up to 30 times the rated current with circuit breakers in the primary circuit. In the case of 4AM control transformers with low inrush current (Siemens control transformers, for example), this is not required. 3RV1 circuit brea- kers can be used here for motor protection. 2.3.3 Starter protection The 3RV13 starter protection switches are circuit breakers without overload releases. They are used together with a contactor and overload relay if the circuit breaker is not to be triggered in the case of overload tripping.

3RV1 circuit breakers

SIRIUS System Manual 2-14 GWA 4NEB 430 0999-02b 2.3.4 Circuit breakers with overload relay function Circuit breakers with the 3RV11 overload relay function are available for frame sizes S0, S2, and S3. Description Circuit breakers with the overload relay function contain overload releases that do not affect the breaker mechanism of the circuit breakers. In the event of an overload, the circuit breaker remains switched on. To protect the following loads, 2 auxiliary contacts (1S + 1Ö) are attached on the right side. These are operated in the event of an overload. The auxiliary switch function can be evaluated or used to disconnect a downstream con- tactor. After the circuit breaker has cooled down, the auxiliary contacts are reset automatically. Caution In the overload range, the circuit breaker does not protect itself with the overload relay function. You must therefore ensure that the circuit breaker is safely disconnected by means of a downstream switching device (e.g. a contactor). Fixed link: auxiliary contacts with circuit breaker Note: The auxiliary contacts are connected to the circuit breaker on the right side and cannot be removed. Diagrams Figure 2-8: Circuit breaker with overload relay function (frame sizes S0 to S3) 2.3.5 Fuse monitoring The 3RV16 11-0BD10 circuit breaker is used with frame size S00 for fuse monitoring. A conducting path of the circuit breaker is switched in parallel for each fuse. If one fuse fails, the current flows via the parallel-switched conducting path of the circuit breaker and trips it. S0: 3RV1121-.... S2: 3RV1131-.... S3: 3RV1141-.... TEST TEST TEST

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-15 Warning Fuse monitoring using the 3RV16 11-0DB10 circuit breaker is not permissible in feeders with power control regulators where a DC feedback with higher values can occur in the event of a fault. Auxiliary switch func- tions The circuit breaker used for fuse monitoring can be equipped with a trans- verse or lateral auxiliary switch (Section 2.4, Accessories). The auxiliary switch reports the tripping of the circuit breaker and thus the failure of the fuse and initiates an all-pole disconnection of the problem circuit by a corre- sponding switching device. Safety sign Note When fuses used for isolation purposes are monitored, a warning sign must be put up next to them. Via the parallel-switched voltage circuit of the moni- toring facility, voltage may get into the area that is supposed to be isolated if the monitoring equipment has not bee disconnected. We suggest the following text for the warning: Voltages The 3RV16 11-0DB10 circuit breaker is suitable for fuse monitoring in the fol- lowing voltage ranges: • 24 to 690 VAC, 50/60 Hz • 24 to 250 VDC, 100 to 600 VDC Switching capacity ICN 100 kA Circuit diagrams Figure 2-9: Circuit diagrams of circuit breakers for fuse monitoring Attention To ensure isolation, also disconnect the fuse-monitoring device with the item designation ............ Ue AC 24 ... 690V DC 24 ... 250V DC 100 ... 600V I» I» I» I» I» I» I» I» I»

3RV1 circuit breakers

SIRIUS System Manual 2-16 GWA 4NEB 430 0999-02b Parallel cables/meshed networks Attention In the case of parallel cables and meshed networks, a tripping operation and report only occurs when the voltage difference at the circuit breaker is at least 24 V. 2.3.6 Switching direct current The 3RV1 circuit breakers for alternating current are suitable for switching direct current. However, you must note the maximum permissible DC volt- age per conducting path. In the case of higher voltages, series connection of 2 or 3 conducting paths is required. Response thresholds The response thresholds of the overload releases remain unchanged. The response thresholds of the short-circuit releases are increased with direct current by approximately 40%. The following table lists suggestions for switching direct current: Double ground fault Note In the case of the circuit with 2-pole switching and an ungrounded system, it is assumed that even in the event of a double ground fault that bridges two contacts, safe disconnection still occurs. Suggestion Circuit breaker Frame size Max. permissible direct voltage EI Meaning 3RV1. S00 to S3 150 VDC 2-pole switching Ungrounded system If a ground fault can be excluded, or if every ground fault is immediately corrected (ground-fault monitoring), the maximum per- missible DC voltage can be tripled. 3RV1. S00 to S3 300 VDC 2-pole switching Grounded system The grounded pole must always be assigned to the individual conducting path so that in the event of a ground fault there are always 2 conducting paths in series. 3RV1. S00 to S3 450 VDC 1-pole switching Grounded system 3 conducting paths in series. The grounded pole should be assigned to the unswitched conducting path. Table 2-4: Suggestions for switching direct current L- M L+ L- L M + L- L M +

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-17 2.3.7 Main and emergency stop switches Since the circuit breakers meet the requirements for disconnectors in acc. with IEC 60947-3 and the additional test requirements for circuit breakers with disconnector features in acc. with IEC 60947-2, they can be used with the appropriate accessories as main and emergency stop switches. They must also comply with DIN VDE 0113.

3RV1 circuit breakers

SIRIUS System Manual 2-18 GWA 4NEB 430 0999-02b 2.4 Accessories 2.4.1 Attachable accessories: Overview Auxiliary switches, alarm switches, auxiliary releases and other accessories can be easily attached to the circuit breakers without tools, as required. Accessories Function/use Width Attach to Transverse auxi- liary switch The contacts of the auxiliary switches close and open together with the main contacts of the circuit breaker. Variants: • 1 changeover contact • 1 NO + 1 NC contact • 2 NO contacts Width of the cir- cuit breaker remains the same Front Electronically optimized trans- verse auxiliary switch One transverse auxiliary switch can be attached for each circuit breaker: Variants: • 1 changeover contact Lateral auxiliary switch One lateral auxiliary switch can be attached for each circuit breaker: • 1 NO + 1 NC contact • 2 NO contacts • 2 NC contacts • 2 NO + 2 NC contacts 9 mm 18 mm Left side Alarm switch Frame sizes S0, S2 and S3 One alarm switch can be attached at the side of the circuit breakers with rotary switches. The alarm switch has two contact systems: • One contact system (1 NO + 1 NC) reports a general tripping operation, irrespective of whether it was caused by a short circuit, overload or auxiliary release. • The other contact system (1 NO + 1 NC) only switches in the event of a short circuit tripping operation. To reclose the circuit breaker after a short circuit, the alarm switch must be reset manually after the cause of the error has been elimi- nated. 18 mm Shunt release Remote release of the circuit breaker: • Via PLC: The coil of the release should be connected to the voltage only briefly • Especially suitable for emergency stop disconnection by means of appropriate emergency stop switches in acc. with DIN VDE 0113 18 mm Right side Accessories cannot be attached on the right of a circuit breaker with a relay func- tion. Undervoltage release Trips the circuit breaker in the event of a voltage interruption (e.g. when the power plug is removed) and prevents the motor starting up inadvertently when the voltage returns. Undervoltage release with lea- ding auxiliary con- tacts 2 NO Function and use, see undervoltage release. Additional function: The auxiliary contacts isolate the undervoltage release from the power system on both sides in the event of breaking or a tripping operation and thus prevent voltage distortion to the control circuit when the switch is in the off position. It is possible to reclose the circuit breaker because the contacts reclose.

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-19 Table 2-5: Attachable accessories 2.4.2 Auxiliary switch, alarm switch, and auxiliary release The maximum configuration for each 3RV1 circuit breaker is one transverse auxiliary switch, one lateral auxiliary switch, one alarm switch, and one aux- iliary release. Possible combinations The following combinations of auxiliary switches and alarm switches or of auxiliary switches are possible: • Auxiliary and alarm switches can be installed individually or together. The lateral auxiliary switch is installed on the left of the alarm switch. • Transverse and lateral auxiliary switches can be combined. • One auxiliary release can be attached on the right for each circuit breaker: Mounting the auxiliary switches The auxiliary switches, alarm switches, and auxiliary releases are mounted in the same way for all frame sizes: Transverse auxiliary switch (3RV1901-1D, -1E, -1F) Figure 2-10: Mounting the transverse auxiliary switch (frame size S00) Accessories Function/use Width Attach to Disconnecting module Frame sizes S0 and S2 The supply is fed to the circuit breaker via the disconnecting module. A connector which can only be removed when the circuit breaker is switched off isolates the circuit breaker from the power system on 3 poles. The shock-protected isolation position is easily visible and is secured by a padlock to ensure that the connector cannot be used during maintenance work, for example. Width of the cir- cuit breaker remains the same Upper side Motorized remote-control mechanism For frame sizes S2 and S3 The circuit breakers can be opened and closed via the remote-con- trolled mechanism by means of electrical commands. This enables a load or system to be disconnected from and then reconnected to the power system from an operator control panel. The circuit breaker can be disconnected from and reconnected to the remote-control mechanism in situ. Rotary switch extension for the door The rotary switch extension for the door consists of a knob, a drive coupling and an extension shaft. They comply with IP 65. The door interlock prevents the cubicle door being opened inadvertently when the switch is in the on position. The off position can be secured with a maximum of 3 padlocks. Emergency stop rotary switch extension Rotary switch extension with emergency stop function. 1 2 3RV 1901-1D, -1E

3RV1 circuit breakers

SIRIUS System Manual 2-20 GWA 4NEB 430 0999-02b Lateral auxiliary switch (3RV1901-....) Undervoltage release (3RV1901-....) Figure 2-11: Mounting/removing the lateral auxiliary switch/undervoltage release (frame size S00) Voltage ranges of the auxiliary releases One undervoltage release or shunt release can be installed for each circuit breaker. The following voltage ranges are possible: 1 2 1 2 3 3 3 1 1 3RV 1901-.... 3RV 19.2-.... Auxiliary release Frequency Undervoltage release AC 50 Hz AC 60 Hz 24 V 110 V 230 V 400 V 415 V 120 V 208 V 240 V 480 V Undervoltage release with leading auxiliary contacts 230 V 400 V 415 V 240 V 480 V Shunt release AC 50/60 Hz 100% duty cycle 1) 1) Transformer operational voltage of the lower mark of the voltage range at 0.85 (Tu = 60 °C) is valid for 100% (continuous) duty cycle only at AC 50/60 Hz AC 50/60 Hz; DC 5 sec. duty cycle 2) 2) Transformer operational voltage of the lower mark of the voltage range at 0.9 (Tu = 60 °C) is valid for 5 seconds duty cycle at AC 50/60 Hz and DC 20 V - 24 V 90 V - 110 V 210 V - 240 V 350 V - 415 V 500 V 20 V - 70 V 70 V - 190 V 190 V - 330 V 330 V - 500 V - Table 2-6: Voltage ranges of the auxiliary releases

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-21 23RV1 circuit breakers Mounting the alarm switch The following table explains how the 3RV19.2-.... alarm switch is mounted onto the circuit breaker: Drawing Step Procedure 1 Press and hold down the trans- port safety button on the inside of the alarm switch. 2 Then press the blue RESET but- ton on the front of the alarm switch. 3 Hook the alarm switch onto the circuit breaker. 4 Move the alarm switch towards the circuit breaker until you hear it click into place. Table 2-7: Testing overload tripping (example: frame size S0) 2 3 1 2 3RV 19.2-.... 3 4

3RV1 circuit breakers

SIRIUS System Manual 2-22 GWA 4NEB 430 0999-02b Alarm switch signals The alarm switch has two signals: • Tripped • Short circuit The following table lists the signals, the status of the alarm switch, and the procedure required: Drawing Status Procedure Tripped signal Tripped position LED: Red RESET button (blue): remains depressed Switch off (0 position) Switch on again (I position) Short circuit Tripped postion LED: red RESET button (blue): not depressed Switch off (0 position) Switch on again (I position) RESET button (blue): press Table 2-8: Alarm switch with tripped signal and short circuit signal 2 1

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-23 2.4.3 Motorized remote-control mechanism The motorized remote-control mechanism is available for 230 VAC, 50 Hz and 24 VDC • Frame size S2: Inmax = 50 A • Frame size S3: Inmax = 100 A Mounting and connec- tion The following table shows you how to mount and connect the motorized remote-control mechanism: Drawing Step Procedure 1 Remove the Allen key from the cover of the circuit breaker. 2 Use the Allen key to change the selector switch to "Manual". 3, 4 Undo the 2 screws and remove the cover. 5, 6 Undo the 4 screws on the remote- controlled mechanism, and remove it. (Pozidriv 2). 1 3 3 4 2 MANUAL AUTOMATIC 2 5(4 x) 6

3RV1 circuit breakers

SIRIUS System Manual 2-24 GWA 4NEB 430 0999-02b 7 Screw the frame onto the mount- ing surface using 4 screws (M5). 8, 9 Attach the circuit breaker using 2 screws. Attention: Use screws 14 mm in length. 10 Attach the ground wire. 11 Connect the main and control wires to the circuit breaker. 12 If desired, set MANUAL RESET: Remove the screw from the RESET lever. 13-15 Put the remote-control mecha- nism module into place, making sure that the driver covers the knob on the circuit breaker, and screw it on. Drawing Step Procedure 7 9 9 7 8 S2: M4/S3: M5 M5 (4 x) 3RV1921-1M 15 12 MANUAL RESET 14 13 (4 x) AUTOM. RESET 10 11

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-25 Table 2-9: Mounting the remote-control mechanism (frame size S2) Warning Do not set the "Automatic" position or operate the remote-control mecha- nism when open! There is a risk of injury! If used as an emergency stop, it is not permissible to switch on manually. Manual RESET Remove the screw from the RESET lever (step 12) 16-18 Screw the control wires for the remote-control mechanism onto the connector, and insert it. 19 Set the current. 20, 21 Put the cover on, and screw it tightly. 22 Use the Allen key to switch to AUTOMATIC and replace the Allen key in the cover. Drawing Step Procedure 16 17 21 21 22 (22) 20 18 19 UC

3RV1 circuit breakers

SIRIUS System Manual 2-26 GWA 4NEB 430 0999-02b 2.4.4 Disconnecting module The disconnecting module is suitable for creating a visible isolating dis- tance. The isolating connector can only be removed in a deenergized state. The isolating distance can be secured with padlocks when open. Disconnecting modules are available for the circuit breakers of frame sizes S0 and S2. Mounting sequence for the disconnecting mod- ule and lateral auxiliary switch Attention The disconnecting module covers the terminal screws of the transverse auxiliary switch. We therefore recommend that you use the lateral auxiliary switches or that you only install the disconnecting module once the trans- verse auxiliary switch has been wired. Locking Disconnecting modules can be mounted on the circuit breakers of every frame size. The modules are mounted in the same way for frame sizes S0 and S2. The following diagrams show you how to mount the disconnecting module for frame size S0 (3RV1928-1A): Figure 2-12: Mounting the disconnecting module (frame size S0) 1 3 2 4 5 7 6 8 8 3RV1928-1A 3RV1.2

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-27 Disconnecting and locking The disconnecting module can be locked and sealed or secured with two padlocks if the connector is removed during maintenance work, for example. The circuit breaker itself can also be secured with a third padlock. Figure 2-13: Locking the disconnecting module (frame size S0) Terminal cover (frame size S2) A terminal cover (3RT1936-4EA2) is available for the disconnecting module in frame size S2 (3RV1938-1A) that protects the contacts from dirt and pro- vides additional shock protection. Figure 2-14: Locking the disconnecting module and mounting the cover (frame size S2) 1 2 3 4 4 5 5 3RV1938-1A 4 2 1 3 3RT1936-4EA2 3RV1.3

3RV1 circuit breakers

SIRIUS System Manual 2-28 GWA 4NEB 430 0999-02b 2.4.5 Rotary switch extension for door Rotary switch extensions for doors are available for frame sizes S0, S2, and S3. They consist of a lockable rotary switch with a detachable door coupling, a 150 mm long extension shaft, and a connector for the switch drive. The door handle complies with IP 65. Installation Figure 2-15: Mounting the rotary switch extension for the door (frame size S2) 6 7 Min. 16 mm Max. 20 mm 3 1 2 4 5 3RV1926-0B, -0C, -0M: 130 mm 3RV1926-0K, -0L: 330 mm 0.7 to 0.9 Nm

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-29 Opening the door The following table shows you how the cubicle door can be opened using the rotary switch extension for the door: Table 2-10: Opening a cubicle door using the rotary switch extension Opening the door with great force Note: If the circuit breaker is in the ON position and the door is opened with a force >150 N to 200 N, the cap of the extension shaft is separated from the rotary switch of the circuit breaker to prevent the circuit breaker being destroyed. The circuit breaker remains in the ON position. Figure 2-16: Operating the rotary switch extension for the door Drawing Procedure To open the cubicle door, set the circuit breaker to O (OFF). This releases the extension shaft from the rotary switch and allows the door to be opened. If you want to open the cubicle door during operation, you can override the procedure by press- ing the button at the side of the rotary knob (step 1). To close it during operation, press the button again so that the exten- sion shaft snaps into place again. 2 1 1 2 Approx. 150 to 200 N

3RV1 circuit breakers

SIRIUS System Manual 2-30 GWA 4NEB 430 0999-02b The extension shaft must then be remounted on the circuit breaker and the rotary switch extension for the door as follows: Security When the rotary switch is in the OFF position, it can be secured with up to 3 padlocks (e.g. during maintenance work on the system). Figure 2-17: Locking the rotary switch extension for the door Drawing Procedure 1Switch the circuit breaker off, and turn the rotary switch on the door to OFF. 2Put the cap of the extension shaft on the rotary switch of the cir- cuit breaker, and put the extension shaft in the cap. 3Close the cubicle door. Table 2-11: Mounting the extension shaft 1 3 2 1 1 2 Max. ø 8 mm

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-31 2.4.6 Terminals for "Combination Motor Controller Type E" in acc. with UL 508 Since July 16, 2001, 1 inch air clearance and 2 inch creepage distance is required for "Combination Motor Controller Type E" on the input side in acc. with UL 508. Use terminal blocks 3RV1928-1H and 3RT1946-4GA07 for the 3RV10 circuit breakers in frame sizes S0 and S3. The 3RV10 circuit breaker in frame size S2 complies with the required air clearance and creepage dis- tance without a terminal block. Terminal blocks are not required for use in acc. with CSA. These terminal blocks cannot be used in the S0 frame size at the same time as the 3RV19.5 3-phase busbars or in the S3 frame size at the same time as a transverse auxiliary switch. Figure 2-18: Terminals for "Combination Motor Controller Type E" 3RV1928-1H Self-Protected Combination Controller Type E 3RT1946-4GA07 1 2 S3 S0

3RV1 circuit breakers

SIRIUS System Manual 2-32 GWA 4NEB 430 0999-02b 2.4.7 Housings and mounting accessories Molded-plastic housings (IP 55) are available if you want to install circuit breakers as single units. All the housings are equipped with neutral and ground terminals. Above and below are two openings that can be knocked out for cable glands. On the back of the housing there are 2 precut open- ings. All the cable bushings have metric dimensions. The surface casings can be sealed. There is space in the housing on the rail for additional modu- lar terminal blocks. Widths The widths of the housing depend on whether auxiliary releases are used: • 54 mm: circuit breaker + lateral auxiliary switch • 72, 82 mm: circuit breaker + lateral auxiliary switch + auxiliary release Mounting the surface casing Figure 2-19: Molded-plastic surface casing (frame size S00) Model Molded-plastic ... Width Frame size Housing with actuator membrane for toggle switch Surface casing 54 mm, 72 mm S00 Bay 72 mm S00 Lockable housing with rotary switch Surface casing 54 mm, 72 mm 82 mm S0 S2 Bay 72 mm S0 Lockable housing with emergency stop rotary switch (red/ yellow) Surface casing 54 mm, 72 mm 82 mm S0 S2 Bay 72 mm S0 Table 2-12: Housings for circuit breakers 3 4 1 2 Neutral/ground terminals

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-33 Mounting the bay Figure 2-20: Molded-plastic bay (frame size S00) Front plates Molded-plastic front plates that have IP 55 protection are suitable for any housing: 4 4 5 1 2 2 3 3 1 Front plates and accessories Model Frame size Front plates With actuator membrane and support for switch S00 With lockable with rotary switch S0, S2, S3 With lockable emergency-stop rotary switch (red/ yellow) S0, S2, S3 Accessories Support for front plate S0 Table 2-13: Front plates for any housings

3RV1 circuit breakers

SIRIUS System Manual 2-34 GWA 4NEB 430 0999-02b Mounting the front plates Frame size S00 Figure 2-21: Mounting the front plate (frame size S00) Frame size S0 Figure 2-22: Mounting the front plate (frame size S0) 3RV1913-4C 3RV1913-4B e.g. cubicle door 6 5 4 3 5 2 M6 M3 1 VU-01015 6 5 4 3 5 2 M6 M3 e.g. cubicle door M3 4 1 2 3 3RV1923-4G 3RV1923-4. M3 2 1 a 3RV1.2 86,5 3RV1.3 139,0 3RV1.4 164,5 3RV1923-4. + 3RV1923-4G

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-35 Accessories for the housings and front plates (S00) The following accessories are available for the housings and front plates of the circuit breakers in frame size S00: • Replacement actuator membrane • Locking device for 3 padlocks • Emergency-stop button (red/yellow) • Emergency-stop button (red/yellow) with safety lock Figure 2-23: Accessories for the housings and front plates (frame size S00) Locking device The locking device can be used on the inside of the housings or front plates. To do this, remove the frame of the actuator membrane. The locking device can be secured with up to 3 padlocks that can prevent the circuit breaker from being switched on during maintenance work, for example. Emergency-stop button The emergency-stop button is attached to the actuator membrane. When hit, the circuit breaker is switched off and the button locks into position. You can release the button by turning it or using a key. The circuit breaker can then be switched on again. Indicator lights Indicator lights are available for the housings and front plates of circuit breakers in frame sizes S00, S0, and S2. They contain a glow lamp and red, green, yellow, orange, and transparent lenses. Indicator lights are available for the following voltage ranges: 110-120 V, 220-240 V, 380-415 V and 480-500 V. 3RV1913-6B 3RV1913-7D 3RV1913-7E 1 2 3RV1913-7F

3RV1 circuit breakers

SIRIUS System Manual 2-36 GWA 4NEB 430 0999-02b Installation There is a precut opening on the front of the housing that can be knocked out to install an indicator light: Figure 2-24: Indicator light installation in a molded-plastic housing 2 1 16 mm For 3RV 1913-4 3RV 1903-5

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-37 2 3RV1 circuit breakers 2.4.8 Busbar adapter To enable the circuit breakers to be mounted without using up too much space, and to ensure that the infeed is economical in terms of both time and money, the switches are mounted directly onto busbar systems using bus- bar adapters. The circuit breakers are snapped onto the adapter and connected at the input side. This prepared unit is mounted directly onto the busbar systems, thus both attaching it mechanically and establishing electrical contact. Busbar systems The adapters are suitable for the following systems: Accessories The following accessories are available for busbar adapters: • Modules that can be mounted on either side to widen the adapters • Busbar holder for 3 rails • Molded-plastic covers for 3 terminals (40 mm system) • Molded-plastic cover profiles for shock protection Measurements The following table lists the dimensions of the busbar adapters and accesso- ries. Busbar systems with center-to-center spacing For copper busbars in acc. with DIN 46 433 Width Depth 40 mm systems 12 mm and 15 mm 5 mm and 10 mm 60 mm systems 12 mm to 30 mm 5 mm and 10 mm Table 2-14: Busbar systems System Busbar adapter and accessories Length Width For circuit breakers in frame size 40 mm Circuit breaker + lateral auxiliary switch 121 mm 45 mm 55 mm S00, S0 Circuit breaker 139 mm 55 mm S2 Circuit breaker 182 mm 70 mm 72 mm S3 (up to 400 V) S3 (up to 690 V) Side module 139 mm 182 mm 13.5 mm 13.5 mm S2 S3 60 mm Circuit breaker 182 mm 45 mm S00, S0 182 mm 55 mm S2 182 mm 70 mm 72 mm S3 (up to 400 V) S3 (up to 690 V) Side module 182 mm 13.5 mm S00 to S3 Table 2-15: Dimensions of the busbar adapters and accessories

3RV1 circuit breakers

SIRIUS System Manual 2-38 GWA 4NEB 430 0999-02b Link module for circuit breaker and contactor Link modules are needed to make electrical and mechanical connections between the circuit breaker and contactor to form a load feeder. Link mod- ules are available for the following combinations: You can find additional information about load feeders on busbar systems in Chapter 5, "Fuseless load feeders". Mounting circuit breakers on busbars The following illustrations show you how to mount circuit breakers in frame sizes S00 and S0 onto busbar adapters (8US1..1-5D) and how to remove them again, using frame size S00 as an example: Figure 2-25: Mounting circuit breakers on busbar adapters (frame sizes S00 and S0) Actuating voltage of contactor Frame size of contactor For circuit breakers of frame size AC and DC S00 S00 S00 S0 S0 S0 S2 S2 S3 S3 Table 2-16: Link modules for connecting circuit breakers to contactors 10 mm 8US1..1-5D Connection module

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-39 Mounting circuit breakers on a busbar system The following illustrations show you how to mount circuit breakers in frame sizes S2 and S3 onto a busbar adapter: Figure 2-26: Mounting circuit breakers on busbar adapters (frame sizes S2 and S3) S2 8US1.61-5FP08 1 8US1111-4SM00 6 to 9 Nm 2 3 4 8 5 7 6 S3 (3x)

3RV1 circuit breakers

SIRIUS System Manual 2-40 GWA 4NEB 430 0999-02b Mounting accessories The following illustration shows you how to mount accessories for busbar adapters for frame sizes S00 to S2: • Side module • Device holder • Extension piece • Outgoing terminal rail (for frame sizes S00 and S0 only) Figure 2-27: Accessories for busbar adapters (frame sizes S00 to S2) 40mm 1 2 1 2 Side module Outgoing terminal rail Extension piece Device holder

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-41 2.4.9 Isolated 3-phase busbar system 3-phase busbars are used to snap circuit breakers of frame sizes S00, S0, and S2 quickly and easily in a row onto a rail. There is only one power supply, via a feed-in terminal. The 3-phase busbar systems are safe from fingers and are shock protected. They are rated for the short-circuit stress that can occur on the output side of the connected circuit breakers. Figure 2-28: 3-phase busbar system Rated operational voltage/current Table 2-17: Rated operational voltage/current Models The 3-phase busbars take 2 to 5 circuit breakers, depending on the model. There are busbars with more generous spacing for circuit breakers with accessories attached on the side. Table 2-18: Types of 3-phase busbars 3-phase busbar 3RV1915-.AB Protective cap 3RV1915-6AB Feed-in terminal, connection from below (3RV1915-5B) Feed-in terminal, connection from above (3RV1915-5A) Spacer Rated operational voltage 690 V Rated current Frame sizes S00, S0: 63 A Frame size S2: 108 A Frame size of the circuit breaker Spacing Models S00, S0 45 mm For 2, 3, 4, or 5 circuit breakers 55 mm For 2, 3, 4, or 5 circuit breakers + accessories 63 mm For 2 or 4 circuit breakers + accessories S2 55 mm For 2, 3, or 4 circuit breakers 75 mm For 2, 3, or 4 circuit breakers + accessories

3RV1 circuit breakers

SIRIUS System Manual 2-42 GWA 4NEB 430 0999-02b Combination of frame sizes S00 and S0 Circuit breakers in frame sizes S00 and S0 vary in height and depth and therefore cannot be combined on one busbar. You can combine two busbars for circuit breakers in frame sizes S0 and S00 using an extension piece. Extending the bus It is possible to extend the busbars by clamping the connecting lugs of a fur- ther bus (turned 180°) under the terminals of the last circuit breaker (see the section on mounting). Attention Note the current-carrying capacity of the busbars when you extend them. Accessories The following accessories are available for the isolated 3-phase busbar sys- tem: • Feed-in terminal from above (3RV1915-5A for S00, 3RV1925-5AB for S0, 3RV1935-5A for S2) • Feed-in terminal from below (3RV1915-5B for S00, S0) • Connector A connector links two 3-phase busbars over a space of 45 mm for circuit breakers in frame sizes S00 and S0. • Protective cap for connecting lugs (3RV19 15-6AB) Protective caps provide shock protection for spare slots. To extend the bus, remove the protective caps. • Spacer Feed-in terminal 3-phase feed-in terminals make it possible to have greater conductor cross- sections than on the circuit breaker itself. Tightening torque: 2 to 4 Nm (17.6 to 35.2 LB.IN). Feed-in terminal - con- nection from below Attention The feed-in terminal with connection from below is clamped on instead of a circuit breaker. Make sure you check how much space you require when you order the 3-phase busbars. Frame size of the circuit breaker Connec- tion Conductors Conductor cross-section S00, S0 From above Single- or multi-core Finely stranded with wire end ferrule AWG 2.5 to 25 mm2 2.5 to 25 mm2 12 to 4 S00, S0 From below Single- or multi-core Finely stranded with wire end ferrule AWG 6 to 25 mm2 4 to 16 mm2 10 to 4 S2 From above Single- or multi-core Finely stranded with wire end ferrule AWG 2.5 to 50 mm2 1.5 to 35 mm2 14 to 0 Table 2-19: Conductor cross-section of the 3-phase feed-in terminals

3RV1 circuit breakers

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-43 Mounting the 3-phase busbars Figure 2-29: Mounting the isolated 3-phase busbar system (frame sizes S00 to S0) S0 S00: Cage Clamp S00 Turned 180° 3RV1915-5B 3RV1915-6AB 3RV1915-.AB 3b 3a 3c 3 1 1 2 3RV1925-5AB 3RV1915-5B 3RV1915-6AB 3RV1915-.AB 8WA2011-1DG30 Turned 180° 3RV1915-5A

3RV1 circuit breakers

SIRIUS System Manual 2-44 GWA 4NEB 430 0999-02b Figure 2-30: Mounting the isolated 3-phase busbar system (frame size S2) S2 3RV1935-5A 3RV1935-6A 3RV1935-1./3.

3RV1 circuit breaker

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-45 2 3RV1 circuit breaker 2.5 Mounting and connection 2.5.1 Mounting Mounting position You can install the 3RV1 circuit breakers anywhere. Snap-on mounting The circuit breakers are mounted by snapping them onto 35 mm rails that comply with DIN EN 50 022. The circuit breakers with a frame size of S3 require a rail with an installation height of 15 mm. Alternatively, they can also be snapped onto 75 mm rails. Figure 2-31: Mounting the circuit breakers onto the rail Screw-on mounting The circuit breakers are attached to a flat surface with 2 screws. For circuit breakers in frame sizes S00 and S0, two push-in lugs (3RB1900-0B) (pack of 10) are also required. Circuit breakers in frame sizes S2 and S3 can be screwed directly onto a base plate. Figure 2-32: Screw-on mounting of the 3RV1 (example: frame size S00) DIN EN 5022 S3 S00 RV-00298 1 2 1 1 2 DIN EN 5022 3RB1900-0B

3RV1 circuit breaker

SIRIUS System Manual 2-46 GWA 4NEB 430 0999-02b 2.5.2 Connection Tools You require the following to connect the circuit breakers: • Frame sizes S00 to S2: Pozidriv 2 screwdriver • Frame size S3: Allen key (4 mm) Conductor cross-sec- tions The typical SIRIUS conductor cross-sections apply (see Section 1.5.2 "Con- ductor cross-sections"). Screw-type terminals 3RV1 circuit breakers with frame sizes S00 and S0 have terminals with cap- tive screws and terminal washers that enable you to connect 2 conductors, even if they have different cross-sections. The box terminals of the circuit breakers of frame sizes S2 and S3 can also take 2 conductors with different cross-sections. With the exception of circuit breakers of frame size S3, which have terminal screws with a 4 mm Allen screw, all the terminal screws can be tightened using a standard screwdriver or a Pozidriv screwdriver (size 2). You can remove the box terminals from circuit breakers with a frame size of S3 to connect conductors with lugs or connecting bars. A terminal cover is available as shock protection and to ensure that you comply with the required creepages and clearances when the box terminals are removed. Soldering pin connec- tor Circuit breakers in frame size S00 can be soldered onto printed circuit boards by means of a soldering pin connector. A soldering pin connector is available for the main contacts and the transverse auxiliary switch.

3RV1 circuit breaker

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-47 Mounting the solder- ing pin adapters The soldering pin adapters are clamped above and below in the screw-type terminals of the circuit breakers. Alternatively, the power supply can be taken to the printed circuit boards via cables. Figure 2-33: Circuit breaker, soldering pin connector (frame size S00) 1 1 1 1 2 4 3 2

3RV1 circuit breaker

SIRIUS System Manual 2-48 GWA 4NEB 430 0999-02b 2.5.3 Device circuit diagrams Frame size S00 Figure 2-34: Device circuit diagram (frame size S00) Frame sizes S0 to S3 Figure 2-35: Device circuit diagrams (frame sizes S0 to S3) Circuit breaker with overload relay func- tion Frame sizes S0 to S3 Figure 2-36: Circuit breaker with relay function, device circuit diagrams (frame sizes S0 to S3) max. 10 A 3 1 L3 L2 L1 6 4 2 T3 T2 T1 5 11 14 12 3RV1901-1D U D2 D1 3RV1902-.A.. U D1 D2 08 07 3RV1912-.C.. 14 13 21 22 3RV1901-1E C2 C1 3RV1902-.D.. I >> I >> I >> 3RV1901-1G 33 41 34 42 3RV1901-.A 43 33 44 34 3RV1901-.B 42 32 41 31 3RV1901-.C 3RV1901-.J 13 21 31 43 14 22 32 44 23 13 24 14 3RV1901-1F 34 33 41 42 3RV1901-.A 43 33 44 34 3RV1901-.B 42 32 31 41 3RV1901-.C max. 10 A 3 1 L3 L2 L1 6 4 2 T3 T2 T1 5 11 14 12 3RV1901-1D U D2 D1 3RV1902-.A.. U D1 D2 08 07 3RV1922-.C.. 14 13 21 22 3RV1901-1E C2 C1 3RV1902-.D.. I >> I >> I >> 78 77 85 86 58 57 65 66 3RV1921-1M 3RV1901-1G 3RV1901-.J 13 21 31 43 14 22 32 44 3RV1901-1F 23 13 24 14 max. 10 A 3 1 L3 L2 L1 6 4 2 T3 T2 T1 5 I >> I >> I >> 98 97 95 96 34 33 41 42 3RV1901-.A 43 33 44 34 3RV1901-.B 42 32 31 41 3RV1901-.C 3RV1901-.J 13 21 31 43 14 22 32 44 11 14 12 3RV1901-1D 14 13 21 22 3RV1901-1E 3RV1901-1F 23 13 24 14 3RV1901-1G

3RV1 circuit breaker

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-49 2.6 Dimensioned drawings (measurements in mm) 3RV1 circuit breakers Figure 2-37: 3RV10 11, 3RV16 (frame size S00) 3RV10 21 (frame size S0) Figure 2-38: 3RV10 31 (frame size S2) Figure 2-39: 3RV10 4 (frame size S3) 1) Lateral auxiliary switch, 2-pole 7) Drilling pattern 2) Alarm switch (S0 to S3) or lateral auxiliary switch, 4-pole (S00 to S3) 8), 35 mm rail in acc. with EN 50022 3) Auxiliary release 9) Mounting onto 35 mm rail, 15 mm high, in acc. with EN 50 022 4) Transverse auxiliary switch or 75 mm rail in acc. with EN 50023 5) Push-in lugs for screw mounting 10) 4 mm Allen screw 6) Only with undervoltage release with leading auxiliary switch 11) Lockable in 0 position with shackle (5 mm in diameter) 1) 11) 3) 4) 5) 8) NSB 00026c 45 90 70 76 9 18 62 5 45 12 45 3,5 6) 2) 18 25 5 105 7) 2) 11) 5) 4) 8) 3) 1) NSB00027b 45 14 12 90 97 45 5 56 80 91 45 69 18 18 72 9 5 25 106 7) 20 55 18 18 45 85 109 121 127 5 8 132 144 140 89 125 1) 2) 3) 4) 8) NSB00028a 11) 9 5 30 130 7) 45 70 18 18 116 165 150 5 7 8 132 153 157 146 10) 11) 1) 2) 3) 4) 9) NSB00029b 169 9 5 30 155 7)

3RV1 circuit breaker

SIRIUS System Manual 2-50 GWA 4NEB 430 0999-02b 3RV11 circuit breaker with overload relay function Figure 2-40: 3RV11 21 (frame size S0) 3RV11 31 (frame size S2) Figure 2-41: 3RV11 42 (frame size S3) 1) Lateral auxiliary switch, 2-pole 2) Alarm switch or lateral auxiliary switch, 4-pole 3) Block for overload relay function 4) Transverse auxiliary switch 5) Push-in lugs for screw-type mounting 7) Drilling pattern 8) 35 mm rail in acc. with EN 50 022 9) Mounting onto 35 mm rails, 15 mm high, in acc. with EN 50 022 or 75 mm rails in acc. with EN 50 023 10) 4 mm Allen screw 11) Lockable in 0 position with shackle (5 mm in diameter) Disconnecting module Figure 2-42: 3RV19 28-1A (for frame size S0) 3RV19 38-1A (for frame size S2) 45 45 12 90 97 5 55 80 91 45 69 20 72 4) 8) 11) 5) 3) 2) 1) NSB00030b 18 9 5 25 106 7) 55 20 20 45 90 140 109 121 127 5 8 132 144 125 3) 4) 8) 11) NSB00031c 2) 1) 18 9 5 30 130 7) 70 90 20 45 116 150 5 7 8 146 132 153 157 165 10) 3) 4) 9) 11) NSB00032c 2) 1) 169 18 9 5 30 155 7) 51 94 45 NSB00033a 96 144 55 NSB00034a 149 57 121 190

3RV1 circuit breaker

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-51 Molded-plastic surface casing Figure 2-43: 3RV19 13-1. (for frame size S00) a) 3RV19 13-1CA00 85 mm 3) Knockout opening for M25 3RV19 13-1DA00 105 mm 4) Knockout opening for rear M20 cable routing b) With 3RV19 13-7D: 146.5 mm 5) With safety lock With 3RV19 13-7E: 166.5 mm 6) Max. shackle diameter for padlock is 8 mm The dimensions relate to the mounting surface 7) Indicator light 3RV19 03-5 c) With 3RV19 13-7D: 64 mm 8) Locking device 3RV19 13-6B With 3RV19 13-7E: 84 mm 9) Emergency-stop button 3RV19 13-7 d) The dimensions relate to the mounting surface Figure 2-44: 3RV19 23-1. (for frame size S0) 3RV19 33-1. (for frame size S2) a) 3RV19 23-1CA00 85 mm 1) Knockout opening for M32 (left) and M40 (right) 3RV1923-1DA00 105 mm 2) Knockout opening for rear M32 cable entry 1) Knockout opening for M25 3) Opening for padlock with a max. shackle diameter of 8 mm 2) Knockout opening for rear M20 cable entry 4) Indicator light 3RV19 03-5. 3) Opening for padlock with a max. shackle diameter of 8 mm 4) Indicator light 3RV19 03-5. NSB 00035c a) 77.5 45 19 145 - 148 4.5 88 9) b) 99 b) 100.5 b) 143 d) 190 b) c) 105 55 13 11 7) 3) 4) 6) 8) 5) 150 18 181 235 250 7 25 29 32 3) NSB 00037c 1) 2) 4) 19 45 2) 145 - 148 4.5 155 a) 126 18 NSB 00036c 3) 1) 4)

3RV1 circuit breaker

SIRIUS System Manual 2-52 GWA 4NEB 430 0999-02b Molded-plastic bay Figure 2-45: 3RV19 13-2DA00 (frame size S00) 3RV19 23-2DA00/-2GA00 (frame size S0) Molded-plastic front plate Figure 2-46: 3RV19 13-4C (frame size S00) Molded-plastic front plate + support Figure 2-47: 3RV19 23-4. (frame sizes S0, S2, S3) 105 95 max. 6 12 87 1) 2) 3) 1) Leuchtmelder 3RV19 03-5. 2) Ausbrechöffnungen für M25 3) Ausbrechöffnungen für M20 105 1) max. 7 12 87 2) 3) 95 1) Leuchtmelder 3RV19 03-5. 2) Ausbrechöffnungen für M25 3) Ausbrechöffnungen für M20 1) Indicator light 3RV19 03-5. 2) Knockout opening for M25 3) Knockout opening for M20 1) Indicator light 3RV19 03-5. 2) Knockout opening for M25 3) Knockout opening for M20 87.5 87.5 40 NSB 00039a 85 56,5 10 12 62 70 4,5 ø 7 1) 1) Leuchtmelder 3RV19 03-5. 1) Indicator light 3RV19 03-5. 56.5 4.5 40 NSB 00042a 85 56,5 10 18 12 62 70 7,4 ø 3,5 1) 1) Leuchtmelder 3RV19 03-5. 3.5 56.5 7.4 37.5 1) Indicator light 3RV19 03-5.

3RV1 circuit breaker

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-53 Soldering pin connector for main and auxiliary switches Figure 2-48: 3RV19 18-5A/-5B (frame size S00) Rotary switch extension for the door Figure 2-49: 3RV19 26-0 (frame sizes S0, S2, S3) 1) Lockable in 0 position with shackle (max. 8 mm in diameter) 2) Affixed with screw caps 5) Ground terminal 35 mm2 and support bracket for 330 mm shaft Terminals for "Combination Motor Controller Type E" in acc. with UL 508 Figure 2-50: 3RV19 28-1H (frame size S0) and 3RT19 46-4GA07 (frame size S3) 45 NSB00041 13.4 12 13.1 5 8.4 14.4 14.4 8.4 14.4 14.4 97.4 9 103 9 59 49 5 2 NSB 01090b 16 5) min. 55 2) 1) 5 45 66 19 15 1 ... 4 17 33 max. 327 34.5 27 72 121 74 45 NSB 01228 10 NSB 01229 168 70 84

3RV1 circuit breaker

SIRIUS System Manual 2-54 GWA 4NEB 430 0999-02b Motorized remote-control mechanism Figure 2-51: 3RV19. 6-3AP0 for circuit breaker a) 3RV19 36-3AP0, frame size S2, 211 mm b) 3RV19 46-3AP0, frame size S3, 236 mm NSB00044 RESET I> AUTOMATIC REVISION MANUAL I SI EMENS ∅5 87 182 224 148 112 a)

3RV1 circuit breaker

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-55 Busbar adapter Figure 2-52: 8US10.1-5DJ07 8US1061-5FK08 4) For busbars 1) For 40 mm busbar systems Width: 12 to 15 mm 2) Side module 8US1998-2KB00 Depth: 5 mm and 10 mm Figure 2-53: 8US1251-5DM07 8US1261-5FM08 8US1923-2AA00 1) For 60 mm busbar systems 1) For 60 mm busbar systems 3) For busbars 2) Side module 8US1998-2BM00 2) Side module 8US1998-2BM00 Width: 12 to 30 mm Depth: 5 and 10 mm 3-phase busbar systems Figure 2-54: 3RV19 15-1. (frame sizes S00, S0) 3RV19 15-1A for 2 circuit breakers (length 83 mm) 3RV19 15-3A for 2 circuit breakers with accessories (length 93 mm) 3RV19 15-1B for 3 circuit breakers (length 128 mm) 3RV19 15-3B for 3 circuit breakers with accessories (length 148 mm) 3RV19 15-1C for 4 circuit breakers (length 173 mm) 3RV19 15-3C for 4 circuit breakers with accessories (length 203 mm) 3RV19 15-1D for 5 circuit breakers (length 218 mm) 3RV19 15-3D for 5 circuit breakers with accessories (length 258 mm) �������� �� ��� �� � � ���� ��� 40 40 NSK-8187 32 50 �������� �� ���� ��� �� � � ��� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � NSK-8189 32 60 60 60 21 13 64 108 83 128 173 218 45 NSB 00055b 21 13 64 108 55 93 148 NSB 00056b 258 203

3RV1 circuit breaker

SIRIUS System Manual 2-56 GWA 4NEB 430 0999-02b Figure 2-55: 3RV19 35-1 (for circuit breakers in frame size S2) 3RV19 35-1A for 2 circuit breakers (length 111 mm) 3RV19 35-1B for 3 circuit breakers (length 166 mm) 3RV19 35-1C for 4 circuit breakers (length 221 mm) Figure 2-56: 3RV19 35-3 (for circuit breakers in frame size S2) 3RV19 35-3A for 2 circuit breakers with accessories (length 121 mm) 3RV19 35-3B for 3 circuit breakers with accessories (length 196 mm) 3RV19 35-3C for 4 circuit breakers with accessories (length 271 mm) 3-phase feed-in terminals Figure 2-57: 3RV19 15-5A 3RV19 15-5B 3RV19 25-5AB Connection from above (for frame size S00) Connection from below Connection from above (frame size S0) (frame size S00/S0) 31 55 111 221 NSB00057b 165 15 96 166 31 75 271 121 NSB00058b 196 96 166 15 NSB00059a 24 44 25 NSB00060b 31 a 92 14 14 44 73 a) 3RV1.1 19 mm a) 3RV1.2 23 mm 44 14 14 25 54 114 71 NSB01093a

3RV1 circuit breaker

SIRIUS System Manual GWA 4NEB 430 0999-02b 2-57 Connector Figure 2-58: 3RV19 35-5A 3RV19 15-5D (for frame size S2) (frame size S0 (left) and frame size S00 (right)) 34 NSB00061b 112 91 161 55 81 42,5 NSB 00062c 108 64 21 13