Siemens SIMATIC NET Installation Manual
Text of the manual
Rugged Ethernet Switches
RUGGEDCOM RS8000T
https://www.siemens.com
Rugged Ethernet Switches
RUGGEDCOM RS8000T
Installation Manual
Preface
Introduction
1
Installing the Device
2
Device Management
3
Communication Ports
4
Technical Specifications
5
Certification
6
01/2021
C79000-G8976-1023-05
Warning Notice System
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety
alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown
below are graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger
will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning
relating to property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the
specific task in accordance with the relevant documentation, in particular its warning notices and safety
instructions. Qualified personnel are those who, based on their training and experience, are capable of
identifying risks and avoiding potential hazards when working with these products/systems.
Proper Use of Siemens Products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant
technical documentation. If products and components from other manufacturers are used, these must be
recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning,
operation and maintenance are required to ensure that the products operate safely and without any
problems. The permissible ambient conditions must be complied with. The information in the relevant
documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of
the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Siemens AG
Digital Industry
Process Automation
Postfach 48 48
90026 NÜRNBERG
GERMANY
© 01/2021 Subject to Change
Copyright © Siemens 2021
All rights reserved
Table of Contents
Preface ............................................................................................................................................ v
Related Documents ................................................................................................................. v
Accessing Documentation ....................................................................................................... v
Registered Trademarks ............................................................................................................ v
Warranty ................................................................................................................................. v
Training .................................................................................................................................. vi
Customer Support .................................................................................................................. vi
Contacting Siemens ............................................................................................................... vii
1
Introduction ........................................................................................................................... 1
1.1
Feature Highlights ................................................................................................. 1
1.2
Description ............................................................................................................ 2
1.3
Required Tools and Materials ................................................................................. 4
1.4
Decommissioning and Disposal ............................................................................. 4
1.5
Cabling Recommendations .................................................................................... 4
1.5.1
Supported Fiber Optic Cables ................................................................................ 5
2
Installing the Device ............................................................................................................. 7
2.1
Mounting the Device ............................................................................................. 7
2.1.1
Mounting the Device on a DIN Rail ........................................................................ 8
2.1.2
Mounting the Device to a Rack .............................................................................. 9
2.1.3
Mounting the Device to a Panel .......................................................................... 11
2.2
Connecting the Failsafe Alarm Relay .................................................................... 11
2.3
Connecting Power ............................................................................................... 12
2.3.1
Connecting AC Power .......................................................................................... 13
2.3.2
Connecting DC Power ......................................................................................... 14
3
Device Management ........................................................................................................... 17
3.1
Connecting to the Device .................................................................................... 17
3.2
Configuring the Device ........................................................................................ 18
3.3
Resetting the Device ........................................................................................... 18
4
Communication Ports .......................................................................................................... 19
4.1
Copper Ethernet Ports ......................................................................................... 19
4.2
Fiber Optic Ethernet Ports ................................................................................... 20
5
Technical Specifications ...................................................................................................... 21
5.1
Power Supply Specifications ................................................................................ 21
5.2
Failsafe Relay Specifications ................................................................................ 21
5.3
Copper Ethernet Port Specifications ..................................................................... 21
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
iii
Table of Contents
5.4
Fiber Optic Ethernet Port Specifications ............................................................... 22
5.5
Operating Environment ....................................................................................... 22
5.6
Mechanical Specifications .................................................................................... 22
5.7
Dimension Drawings ........................................................................................... 22
6
Certification ......................................................................................................................... 25
6.1
Approvals ............................................................................................................ 25
6.1.1
CSA ..................................................................................................................... 25
6.1.2
European Union (EU) .......................................................................................... 25
6.1.3
FCC ..................................................................................................................... 26
6.1.4
ISO ...................................................................................................................... 26
6.1.5
ACMA .................................................................................................................. 26
6.1.6
RoHS ................................................................................................................... 27
6.2
EMC and Environmental Type Tests ..................................................................... 27
iv
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
This guide describes the RUGGEDCOM RUGGEDCOM RS8000T. It describes the
major features of the device, installation, commissioning and important technical
specifications.
It is intended for use by network technical support personnel who are responsible
for the installation, commissioning and maintenance of the device. It is also
recommended for use by network and system planners, system programmers, and
line technicians.
Related Documents
Other documents that may be of interest include:
Document Title
Link
RUGGEDCOM ROS Configuration Manual
https://support.industry.siemens.com/cs/ww/en/
view/109737246
Accessing Documentation
The latest user documentation for RUGGEDCOM RS8000T is available online at
https://support.industry.siemens.com . To request or inquire about a user document,
contact Siemens Customer Support.
Registered Trademarks
RUGGEDCOM ™ and ROS™ are trademarks of Siemens AG.
Other designations in this manual might be trademarks whose use by third parties
for their own purposes would infringe the rights of the owner.
Warranty
Siemens warrants this product for a period of five (5) years from the date of
purchase, conditional upon the return to factory for maintenance during the
warranty term. This product contains no user-serviceable parts. Attempted service by
unauthorized personnel shall render all warranties null and void. The warranties set
forth in this article are exclusive and are in lieu of all other warranties, performance
guarantees and conditions whether written or oral, statutory, express or implied
(including all warranties and conditions of merchantability and fitness for a particular
purpose, and all warranties and conditions arising from course of dealing or usage
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
v
or trade). Correction of nonconformities in the manner and for the period of time
provided above shall constitute the Seller’s sole liability and the Customer’s exclusive
remedy for defective or nonconforming goods or services whether claims of the
Customer are based in contract (including fundamental breach), in tort (including
negligence and strict liability) or otherwise.
For warranty details, visit https://www.siemens.com or contact a Siemens customer
service representative.
Training
Siemens offers a wide range of educational services ranging from in-house training
of standard courses on networking, Ethernet switches and routers, to on-site
customized courses tailored to the customer's needs, experience and application.
Siemens' Educational Services team thrives on providing our customers with the
essential practical skills to make sure users have the right knowledge and expertise
to understand the various technologies associated with critical communications
network infrastructure technologies.
Siemens ' unique mix of IT/Telecommunications expertise combined with domain
knowledge in the utility, transportation and industrial markets, allows Siemens to
provide training specific to the customer's application.
For more information about training services and course availability, visit https://
www.siemens.com or contact a Siemens Sales representative.
Customer Support
Customer support is available 24 hours, 7 days a week for all Siemens customers.
For technical support or general information, contact Siemens Customer Support
through any of the following methods:
Online
Visit http://www.siemens.com/automation/support-request to submit a
Support Request (SR) or check on the status of an existing SR.
Telephone
Call a local hotline center to submit a Support Request (SR). To locate a
local hotline center, visit https://w3.siemens.com/aspa_app/?lang=en.
Mobile App
Install the Industry Online Support app by Siemens AG on any Android,
Apple iOS or Windows mobile device and be able to:
•
Access Siemens' extensive library of support documentation,
including FAQs and manuals
•
Submit SRs or check on the status of an existing SR
vi
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
Contact a local Siemens representative from Sales, Technical Support,
Training, etc.
•
Ask questions or share knowledge with fellow Siemens customers
and the support community
Contacting Siemens
Address
Siemens AG
Industry Sector
300 Applewood Crescent
Concord, Ontario
Canada, L4K 5C7
Telephone
Toll-free: 1 888 264 0006
Tel: +1 905 856 5288
Fax: +1 905 856 1995
E-Mail
[email protected]
Web
https://www.siemens.com
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
vii
Installation Manual, 01/2021, C79000-G8976-1023-05
The RUGGEDCOM RUGGEDCOM RS8000T provides substation hardened, fully
managed, Ethernet switches specifically designed to operate reliably in electrically
and environmentally harsh environments.
The RUGGEDCOM RS8000T model provides IEEE 1613 Class 2 error-free
communications performance under EMI stress. An operating temperature range of
-40 to 85 °C (-40 to 185 °F) allows the RUGGEDCOM RS8000T to be placed in almost
any location.
The RUGGEDCOM RS8000T provides a wide range of power supply options suitable
for multiple industries and for worldwide operability. Options include 24 VDC, 48
VDC, and HI (88-300 VDC or 85-264 VAC)
The RUGGEDCOM RS8000T offers advanced Layer 2 and 3 networking features and
network management via the Rugged Operating System (ROS). A unique feature of
ROS is the performance of its IEEE 802.1w Rapid Spanning Tree Protocol (RSTP) used
for implementing fault tolerant ring and mesh network architectures. The protocol
has been optimized to support ring sizes of up to 160 switches and fault recovery
times in the order of less than 5 ms per switch.
The RUGGEDCOM RS8000T’s superior ruggedized design coupled with the Rugged
Operating System (ROS) provides improved system reliability and advanced
networking features making it ideally suited for creating Ethernet networks for
mission-critical, real-time control applications.
1.1
Feature Highlights
Ethernet Ports
•
Six 10/100Base-TX and two 100Base-FX ports
•
Multi-mode and single-mode optical transceivers
•
Industry standard fiber optical connectors: MTRJ, LC
Rated for Reliability in Harsh Environments
•
Immunity to EMI and heavy electrical surges
•
Meets IEEE 1613 Class 2 (electric utility substations)
•
Exceeds IEC 61850-3 (electric utility substations)
•
Exceeds IEC 61800-3 (variable speed drive systems)
•
Exceeds IEC 61000-6-2 (generic industrial)
•
Exceeds NEMA TS-2 (traffic control equipment)
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
1
-40 to 85 °C (-40 to 185 °F) operating temperature (no fans)
•
Failsafe Output Relay: For critical failure or error alarming
•
Conformal coated printed circuit boards (optional)
Cyber Security Features
•
Multi-level user passwords
•
SSH/SSL (128-bit encryption)
•
Enable/disable ports, MAC based port security
•
Port based network access control (802.1x)
•
VLAN (802.1Q) to segregate and secure network traffic
•
RADIUS centralized password management
•
SNMPv3 authentication and 56-bit encryption
Management Tools
•
Web-based, Telnet, CLI management interfaces
•
SNMP v1/v2/v3 (56-bit encryption)
•
Remote Monitoring (RMON)
•
Rich set of diagnostics with logging and alarms
Universal Power Supply Options
•
Universal high-voltage range: 88-300 VDC or 85-264 VAC
•
Popular low voltage ranges: 24 VDC (10-36 VDC), 48 VDC (36-59 VDC)
•
Terminal blocks for reliable maintenance free connections
•
CSA/UL 60950 safety approved to 85 °C (185 °F)
1.2
Description
The RUGGEDCOM RS8000T features various ports, controls and indicator LEDs on the
front and rear panels for configuring and troubleshooting the device.
2
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
Port Status Indicator LEDS
5
RS232 Serial Console Port (DB9)
Figure 1.1
Front and Rear Panels
POWER LED
Illuminates when power is being supplied to the device.
Color
Description
Green
Device ready
Off
No power
RESET Button
Shuts down and restarts the device. For more information, refer to
"Resetting the Device (Page 18)".
Port Status Indicator LEDs
These LEDs indicate when serial ports are active.
LED
State
Meaning
Solid
Link detected
Link
Off
No link detected
Blinking
Link activity
(receiving)
RX
Off
No link activity
Blinking
Link activity
(transmitting)
TX
Off
No link activity
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
3
1.3 Required Tools and Materials
RS232 Serial Console Port
The serial console port is for interfacing directly with the device
and accessing initial management functions. For information
about connecting to the device via the serial console port, refer to
"Connecting to the Device (Page 17)".
Communication Ports
Receive and transmit data. For more information about the
various ports available for the RUGGEDCOM RS8000T, refer to
"Communication Ports (Page 19)".
1.3
Required Tools and Materials
The following tools and materials are required to install the RUGGEDCOM RS8000T:
Tools/Materials
Purpose
AC or DC power cord (16 AWG)
For connecting power to the device.
CAT-5 Ethernet cables
For connecting the device to the network.
Flathead screwdriver
For mounting the device to a DIN rail.
Phillips screwdriver
For mounting the device to a panel.
4 x #8-32 screws
For mounting the device to a panel.
1.4
Decommissioning and Disposal
Proper decommissioning and disposal of this device is important to prevent malicious
users from obtaining proprietary information and to protect the environment.
Decommissioning
This device may include sensitive, proprietary data. Before taking the device out of
service, either permanently or for maintenance by a third-party, make sure it has
been fully decommissioned.
For more information, refer to the associated Configuration Manual.
Recycling and Disposal
For environmentally friendly recycling and disposal of this device and related
accessories, contact a facility certified to dispose of waste electrical and electronic
equipment. Recycling and disposal must be done in accordance with local
regulations.
1.5
Cabling Recommendations
All copper Ethernet ports on RUGGEDCOM products include transient suppression
circuitry to protect against damage from electrical transients and conform with
IEC 61850-3 and IEEE 1613 Class 1 standards. This means that during a transient
4
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
1.5.1 Supported Fiber Optic Cables
electrical event, communications errors or interruptions may occur, but recovery is
automatic.
Siemens also does not recommend using copper Ethernet ports to interface with
devices in the field across distances that could produce high levels of ground
potential rise (i.e. greater than 2500 V), during line-to-ground fault conditions.
1.5.1
Supported Fiber Optic Cables
The following fiber optic cable types are supported under the stated conditions.
Distance (m)
Cable Type
Wavelength (nm)
Modal Bandwidth
(MHz·km)
100Base-FX
1000Base-SX
10GBase-SR
850
200
—
275
33
OM1 (62.5/125)
1300
500
2000
—
—
850
500
—
550
82
OM2 (50/125)
1300
500
2000
—
—
850
1500
—
550
300
OM3 (50/125)a
1300
500
2000
—
—
850
3500
—
550
400
OM4 (50/125)a
1300
500
2000
—
—
a Laser optimized.
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
5
1.5.1 Supported Fiber Optic Cables
6
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
Installing the Device
2
This chapter describes how to install the device, including mounting the device,
connecting power, and connecting the device to the network.
DANGER
Electrocution hazard – risk of serious personal injury and/or damage to
equipment
Before performing any maintenance tasks, make sure all power to the device has
been disconnected and wait approximately two minutes for any remaining energy
to dissipate.
IMPORTANT
This product contains no user-serviceable parts. Attempted service by unauthorized
personnel shall render all warranties null and void.
Changes or modifications not expressly approved by Siemens AG could invalidate
specifications, test results, and agency approvals, and void the user's authority to
operate the equipment.
IMPORTANT
This product should be installed in a restricted access location where access can only
be gained by authorized personnel who have been informed of the restrictions and
any precautions that must be taken. Access must only be possible through the use
of a tool, lock and key, or other means of security, and controlled by the authority
responsible for the location.
2.1
Mounting the Device
The RUGGEDCOM RS8000T is designed for maximum mounting and display
flexibility. It can be equipped with connectors that allow it to be installed in a 48 cm
(19 in) rack, 35 mm (1.4 in) DIN rail, or directly on a panel.
IMPORTANT
Heat generated by the device is channeled outwards from the enclosure. As such, it
is recommended that 2.5 cm (1 in) of space be maintained on all open sides of the
device to allow for some convectional airflow.
Forced airflow is not required. However, any increase in airflow will result in a
reduction of ambient temperature and improve the long-term reliability of all
equipment mounted in the rack space.
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
7
Installing the Device
2.1.1 Mounting the Device on a DIN Rail
Note
For detailed dimensions of the device with either rack, DIN rail or panel hardware
installed, refer to "Dimension Drawings (Page 22)".
2.1.1
Mounting the Device on a DIN Rail
The RUGGEDCOM RS8000T can be ordered with a panel/DIN rail adapter preinstalled
on the back of the chassis. Use the adapter to mount the device to a standard 35 mm
(1.4 in)IEC/EN 60715 or TS35 DIN rail.
Mounting the Device
To mount the device to a DIN rail, do the following:
1.
Hook the top teeth of the adapter onto the DIN rail.
Note
The adapter features a sliding release with a slot at the bottom for a flathead
screwdriver.
1
2
3
1
1
2
1
DIN Rail
2
Panel/DIN Rail Adaptor
Figure 2.1
Mounting the Device to a DIN Rail
2.
Insert a flathead screwdriver into the slot of the sliding release and move it
down.
3.
Push the device against the bottom of the DIN rail, then let go of the sliding
release to latch the device.
8
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
Installing the Device
2.1.2 Mounting the Device to a Rack
Removing the Device
To remove the device from a DIN rail, do the following:
1.
Insert a flathead screwdriver into the slot of the sliding release and move it
down.
1
3
2
1
2
1
1
DIN Rail
2
DIN Rail Adapter
Figure 2.2
Removing the Device from a DIN Rail
2.
Swing the bottom of the device away from the DIN rail.
3.
Lift the device off the DIN rail.
2.1.2
Mounting the Device to a Rack
To secure the device to a standard 48 cm (19 in) rack, do the following:
1.
Remove the four screws from the side of the device.
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
9
Installing the Device
2.1.2 Mounting the Device to a Rack
2.
Insert the device into rack mount adapter and use the screws to secure it.
Note
The device can be installed with the communication ports facing the front or
rear of the rack, depending on the desired orientation.
2
1
1
Rack Mount Adapter
2
Screw
Figure 2.3
Rack Mounting
3.
Insert the rack mount adapter and device assembly into the rack.
Note
Since heat within the device is channelled to the enclosure, it is recommended
that 1 rack-unit of space, or 44 mm (1.75 in), be kept empty above the device.
This allows a small amount of convectional airflow.
Forced airflow is not required. However, any increase in airflow will result in a
reduction of ambient temperature and improve the long-term reliability of all
equipment mounted in the rack space.
4.
Secure the adapter to the rack using the supplied hardware.
10
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
Installing the Device
2.1.3 Mounting the Device to a Panel
2.1.3
Mounting the Device to a Panel
To mount the device to a panel, do the following:
1.
Place the device against the panel and align the adapters with the mounting
holes.
2
1
1
1
1
2
1
Screw
2
Panel/DIN Rail Adaptor
Figure 2.4
Panel Mounting
2.
Install the supplied screws to secure the adapters to the panel.
2.2
Connecting the Failsafe Alarm Relay
The failsafe relay can be configured to latch based on alarm conditions. The NO
(Normally Open) contact is closed when the unit is powered and there are no active
alarms. If the device is not powered or if an active alarm is configured, the relay
opens the NO contact and closes the NC (Normally Closed) contact.
Note
Control of the failsafe relay output is configurable through RUGGEDCOM ROS . One
common application for this relay is to signal an alarm if a power failure occurs. For
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
11
Installing the Device
2.3 Connecting Power
more information, refer to the RUGGEDCOM RS8000T Configuration Manual for the
RUGGEDCOM RS8000T.
The following shows the proper relay connections.
1
2
3
1
Normally Closed
2
Common
3
Normally Open
Figure 2.5
Failsafe Alarm Relay Wiring
2.3
Connecting Power
The RUGGEDCOM RS8000T supports a single integrated high AC/DC or low DC power
supply
IMPORTANT
•
For 88-300 VDC rated equipment, an appropriately rated circuit breaker must be
installed.
•
For 100-240 VAC rated equipment, an appropriately rated circuit breaker must
be installed.
•
Use minimum #16 gage wiring when connecting terminal blocks.
•
A circuit breaker is not required for 12, 24 or 48 VDC rated equipment.
•
Power input terminals have reverse polarity protection for 12, 24 and 48 VDC
rated equipment.
•
Equipment must be installed according to applicable local wiring codes and
standards.
12
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
Installing the Device
2.3.1 Connecting AC Power
2.3.1
Connecting AC Power
To connect a high AC power supply to the device, do the following:
NOTICE
Electrical hazard – risk of damage to equipment
Before testing the dielectric strength (HIPOT) in the field, remove the braided
ground cable connected to the surge ground terminal and chassis ground. This cable
connects transient suppression circuitry to chassis ground and must be removed in
order to avoid damage to transient suppression circuitry during testing.
1.
Connect the positive wire from the power source to the positive/hot (+/H)
terminal on the terminal block.
4
1
2
3
1
Positive/Hot (+/H) Terminal
2
Negative/Neutral (-/N) Terminal
3
Surge Ground Terminal
4
Braided Ground Cable
Figure 2.6
Terminal Block Wiring
2.
Connect the negative wire from the power source to the negative/neutral (-/N)
terminal on the terminal block.
3.
Using a braided wire or other appropriate grounding wire, connect the surge
ground terminal to the chassis ground connection. The surge ground terminal
is used as the ground conductor for all surge and transient suppression circuitry
internal to the unit.
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
13
Installing the Device
2.3.2 Connecting DC Power
4.
Using a #6 ring lug and #6-32 screw, secure the ground terminal on the power
source to the chassis ground terminal on the device. Make sure the lug is
tightened to 1.7 N·m (15 lbf·in).
2
1
3
1
Stainless Steel Stud
2
#6-32 Screw
3
#6 Ring Lug
Figure 2.7
Chassis Ground Connection
2.3.2
Connecting DC Power
To connect a high or low DC power supply to the device, do the following:
NOTICE
Electrical hazard – risk of damage to equipment
Before testing the dielectric strength (HIPOT) in the field, remove the braided
ground cable connected to the surge ground terminal and chassis ground. This cable
connects transient suppression circuitry to chassis ground and must be removed in
order to avoid damage to transient suppression circuitry during testing.
14
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
Installing the Device
2.3.2 Connecting DC Power
1.
Connect the positive wire from the power source to the positive/hot (+/L)
terminal on the terminal block.
4
1
2
3
1
Positive/Hot (+/L) Terminal
2
Negative/Neutral (-/N) Terminal
3
Surge Ground Terminal
4
Braided Ground Cable
Figure 2.8
Terminal Block Wiring
2.
Connect the negative wire from the power source to the negative/neutral (-/N)
on the terminal block.
3.
Using a braided wire or other appropriate grounding wire, connect the surge
ground terminal to the chassis ground connection. The surge ground terminal
is used as the ground conductor for all surge and transient suppression circuitry
internal to the unit.
4.
Using a #6 ring lug and #6-32 screw, secure the ground terminal on the power
source to the chassis ground terminal on the device. Make sure the lug is
tightened to 1.7 N·m (15 lbf·in).
2
1
3
1
Stainless Steel Stud
2
#6-32 Screw
3
#6 Ring Lug
Figure 2.9
Chassis Ground Connection
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
15
Installing the Device
2.3.2 Connecting DC Power
16
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
This section describes how to connect to and manage the device.
3.1
Connecting to the Device
The following describes the various methods for accessing the RUGGEDCOM ROS
console and Web interfaces on the device. For more detailed instructions, refer to the
RUGGEDCOM RS8000T Configuration Manual for the RUGGEDCOM RS8000T.
Serial Console Port
Connect a PC or terminal directly to the serial console port to access the boot-time
control and RUGGEDCOM ROS console interface.
IMPORTANT
The serial console port is intended to be used only as temporary connections during
initial configuration or troubleshooting.
The serial console port implements RS232 DCE (Data Communication Equipment) on
a DB9 connector. The following is the pin-out for the port:
5
9
6
1
Figure 3.1
Serial DB9 Console Port
Pin
Name
Description
1
NC
No Connection
2
TX
Transmit Data
3
RX
Receive Data
4
NC
No Connection
5
GND
Signal Ground
6
NC
No Connection
7
NC
No Connection
8
NC
No Connection
9
NC
No Connection
Communication Ports
Connect any of the available Ethernet ports on the device to a management switch
and access the RUGGEDCOM RS8000T console and Web interfaces via the device's IP
address. For more information about available ports, refer to "Communication Ports
(Page 19)".
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
17
3.2 Configuring the Device
3.2
Configuring the Device
Once the device is installed and connected to the network, it must be configured.
All configuration management is done via the RUGGEDCOM ROS interface. For more
information about configuring the device, refer to the RUGGEDCOM RUGGEDCOM
RS8000T Configuration Manual associated with the installed software release.
3.3
Resetting the Device
The RUGGEDCOM RS8000T can be reset (rebooted) using the RESET button. The
RESET button is recessed and can only be reached using a pin or small screwdriver.
To reset the device, quickly press and release the RESET button with a pin.
18
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
The RUGGEDCOM RS8000T can be equipped with various types of communication
ports to enhance its abilities and performance. To determine which ports are
equipped on the device, refer to the factory data file available through RUGGEDCOM
ROS . For more information on how to access the factory data file, refer to the
RUGGEDCOM RS8000T Configuration Manual for the RUGGEDCOM RS8000T.
Each communication port type has a specific place in the RUGGEDCOM RS8000T
chassis.
1
2
1
Ports 1 to 6
2
Ports 7 to 8
Figure 4.1
Port Assignment
Port
Type
1 to 6
10/100Base-TX
7 to 8
100Base-FX
4.1
Copper Ethernet Ports
The RUGGEDCOM RS8000T supports several 10/100Base-TX Ethernet ports that allow
connection to standard Category 5 (CAT-5) unshielded twisted-pair (UTP) cables with
RJ45 male connectors. The RJ45 connectors are directly connected to the chassis
ground on the device and can accept CAT-5 shielded twisted-pair (STP) cables.
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
19
4.2 Fiber Optic Ethernet Ports
The following is the pin-out for the RJ45 male connector:
1
8
Figure 4.2
RJ45 Ethernet Port Pin
Configuration
Pin
Name
Description
1
RX+
Receive Data+
2
RX-
Receive Data-
3
TX+
Transmit Data+
4
Reserved (Do Not Connect)
5
Reserved (Do Not Connect)
6
TX-
Transmit Data-
7
Reserved (Do Not Connect)
8
Reserved (Do Not Connect)
Case
Shield (Chassis Ground)
For specifications on the available copper Ethernet ports, refer to "Copper Ethernet
Port Specifications (Page 21)".
4.2
Fiber Optic Ethernet Ports
Fiber optic Ethernet ports are available with either MTRJ (Mechanical Transfer
Registered Jack) or LC (Lucent Connector) connectors. Make sure the Transmit (Tx)
and Receive (Rx) connections of each port are properly connected and matched to
establish a proper link.
2
1
1
Tx Connector
2
Rx Connector
Figure 4.3
MTRJ Port
2
1
1
Tx Connector
2
Rx Connector
Figure 4.4
LC Port
For specifications on the available fiber optic Ethernet ports, refer to "Fiber Optic
Ethernet Port Specifications (Page 22)".
20
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
This chapter provides important technical specifications related to the device.
5.1
Power Supply Specifications
Input Range
Power
Supply Type
Minimum
Maximum
Internal Fuse
Ratinga b
Maximum Power
Consumptionc
12-24 VDC
10 VDC
36 VDC
6.3 A(F)
24 VDC
18 VDC
36 VDC
5 A(F)
48 VDC
36 VDC
59 VDC
3.15 A(T)
HI (125/250 VDC)d
88 VDC
300 VDC
3.15 A(T)
HI (110/230 VAC)d
85 VAC
265 VAC
3.15 A(T)
15 W
a (F) denotes fast-acting fuse
b (T) denotes time-delay fuse.
c Power consumption varies based on configuration. 10/100Base-TX ports consume roughly 1 W less than
fiber optic ports.
d This is the same power supply for both AC and DC.
5.2
Failsafe Relay Specifications
Voltage
Current
30 VAC
0.3 A
30 VDC
1 A
80 VDC
0.3 A
5.3
Copper Ethernet Port Specifications
The following details the specifications for copper Ethernet ports that can be ordered
with the RUGGEDCOM RS8000T.
Speeda
10/100Base-TX
Connector
RJ45
Duplexa
FDX/HDX
Cable Typeb
> CAT-5
Wiring Standardc
TIA/EIA T568A/B
Maximum Distanced
100 m (328 ft)
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
21
5.4 Fiber Optic Ethernet Port Specifications
Isolatione
1.5 kV
a Auto-negotiating.
b Shielded or unshielded.
c Auto-crossover and auto-polarity.
d Typical distance. Dependent on the number of connectors and splices.
e RMS 1 minute.
5.4
Fiber Optic Ethernet Port Specifications
The following details the specifications for fiber optic Ethernet ports that can be
ordered with the RUGGEDCOM RS8000T.
5.5
Operating Environment
The RUGGEDCOM RS8000T is rated to operate under the following environmental
conditions.
Ambient Operating
Temperaturea
-40 to 85°C (-40 to 185 °F)
Ambient Storage
Temperature
-40 to 85°C (-40 to 185 °F)
Ambient Relative
Humidityb
5% to 95%
Maximum Altitude
2000 m (6562 ft)
a Ambient Temperature as measured from a 30 cm radius surrounding the center of the enclosure.
b Non-condensing
5.6
Mechanical Specifications
Weight
2.25 kg (5 lbs)
Ingress Protection
IP30
Enclosure
18 AWG Galvanized Steel
5.7
Dimension Drawings
Note
All dimensions are in millimeters, unless otherwise stated.
22
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
Rack Mount Dimensions
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
23
Panel and Din Rail Mount Dimensions
24
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
The RUGGEDCOM RS8000T device has been thoroughly tested to guarantee its
conformance with recognized standards and has received approval from recognized
regulatory agencies.
6.1
Approvals
This section details the standards to which the RUGGEDCOM RS8000T complies.
6.1.1
CSA
This device is certified by the CSA Group to meet the requirements of the following
standards:
•
CSA-C22.2 NO. 62368-1
Information Technology Equipment – Safety – Part 1: General Requirements (Bi-
National standard, with UL 62368-1)
•
UL 62368-1
Information Technology Equipment – Safety – Part 1: General Requirements)
6.1.2
European Union (EU)
This device is declared by Siemens AG to comply with essential requirements and
other relevant provisions of the following EU directives:
•
EN 62368-1
Information Technology Equipment – Safety – Part 1: General Requirements
•
EN 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
•
EN 50581
Technical Documentation for the Assessment of Electrical and Electronic
Products with Respect to the Restriction of Hazardous Substances
•
EN 60825-1
Safety of Laser Products – Equipment Classification and Requirements
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
25
Information Technology Equipment – Radio disturbance characteristics – Limits
and methods of measurement
The device is marked with CE and European Explosive Atmosphere symbols and can
be used throughout the European community.
A copy of the CE Declaration of Conformity is available from Siemens AG. For contact
information, refer to "Contacting Siemens (Page vii)".
6.1.3
FCC
This device has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated
in a commercial environment.
This device generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential
area is likely to cause harmful interference in which case users will be required to
correct the interference at their own expense.
IMPORTANT
Changes or modifications not expressly approved by the party responsible for
compliance could void the user's authority to operate this device.
6.1.4
ISO
This device was designed and manufactured using a certified ISO (International
Organization for Standardization) quality program that adheres to the following
standard:
•
ISO 9001:2015
Quality management systems – Requirements
6.1.5
ACMA
This device meets the requirements of the following Australian Communications and
Media Authority (ACMA) standards under certificate ABN 98 004 347 880:
•
Radiocommunications (Compliance Labelling – Devices) Notice 2014 made
under Section 182 of the Radiocommunications Act 1992
26
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
Radiocommunications Labelling (Electromagnetic Compatibility) Notice 2008
made under Section 182 of the Radiocommunications Act 1992
•
Radiocommunications (Compliance Labelling – Electromagnetic Radiation)
Notice 2003 made under Section 182 of the Radiocommunications Act 1992
•
Telecommunications Labelling (Customer Equipment and Customer Cabling)
Notice 2001 made under Section 407 of the Telecommunication Act 1997
The device is marked with an RCM symbol to indicate compliance when sold in the
Australian region.
A copy of the Declaration of Conformity is available via Siemens Industry Online
Support at https://support.industry.siemens.com/cs/ww/en/view/89855782.
6.1.6
RoHS
This device is declared by Siemens AG to meet the requirements of the following
RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain
hazardous substances in electrical and electronic equipment:
•
China RoHS 2
Administrative Measure on the Control of Pollution Caused by Electronic
Information Products
A copy of the Material Declaration is available online at https://
support.industry.siemens.com/cs/ww/en/view/109738831.
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RS8000T has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
Description
Test Levels
Severity
Levels
Enclosure
Contact
±8 kV
4
IEC
61000-4-2
ESD
Enclosure Air
±15 kV
4
IEC
61000-4-3
Radiated RFI
Enclosure
ports
20 V/m
x
Signal ports
±4 kV @ 2.5 kHz
x
IEC
61000-4-4
Burst (Fast Transient)
DC Power
ports
±4 kV
4
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
27
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
AC Power
ports
±4 kV
4
Earth
ground ports
±4 kV
4
Signal ports
±4 kV line-to-earth,
±2 kV line-to-line
4
DC Power
ports
±2 kV line-to-earth,
±1 kV line-to-line
3
IEC
61000-4-5
Surge
AC Power
ports
±4 kV line-to-earth,
±2 kV line-to-line
4
Signal ports
10 V
3
DC Power
ports
10 V
3
AC Power
ports
10 V
3
IEC
61000-4-6
Induced (Conducted) RFI
Earth
ground ports
10 V
3
IEC
61000-4-8
Magnetic Field
Enclosure
ports
40 A/m continuous,
1000 A/m for 1 s
DC Power
ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
IEC
61000-4-29
30% for 1 period,
60% for 50 periods
IEC
61000-4-11
Voltage Dips and Interrupts
AC Power
ports
100% for 5 periods,
100% for 50 periods
Signal ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
DC Power
ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
IEC
61000-4-12
Damped Oscillatory
AC Power
ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
Signal ports
30 V Continuous,
300 V for 1 s
4
IEC
61000-4-16
Mains Frequency Voltage
DC Power
ports
30 V Continuous,
300 V for 1 s
4
IEC
61000-4-17
Ripple on DC Power Supply
DC Power
ports
10%
3
Signal ports
2 kVAC (Fail-
Safe Relay output)
DC Power
ports
1.5 kVDC
Dielectric Strength
AC Power
ports
2 kVDC
Signal ports
5 kV (Fail-Safe
Relay Output)
IEC 60255-5
HV Impulse
DC Power
ports
5 kV
28
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
AC Power
ports
5 kV
IEEE 1613 (C37.90.x) EMC Immunity Type Tests
Note
The RUGGEDCOM RS8000T meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports.
IEEE Test
IEEE 1613
Clause
Description
Test Levels
Enclosure Contact
±8 kV
C37.90.3
9
ESD
Enclosure Air
±15 kV
C37.90.2
8
Radiated RFI
Enclosure ports
35 V/m
Signal ports
±4 kV @ 2.5 kHz
DC Power ports
±4 kV
AC Power ports
±4 kV
Fast
Transient
Earth ground ports
±4 kV
Signal ports
2.5 kV common
mode @ 1MHz
DC Power ports
2.5 kV common and
differential mode @ 1MHz
C37.90.1
7
Oscillatory
AC Power ports
2.5 kV common and
differential mode @ 1MHz
Signal ports
5 kV (Failsafe Relay)
DC Power ports
5 kV
HV Impulse
AC Power ports
5 kV
Signal ports
2 kVAC (Failsafe Relay)
DC Power ports
1.5 kVDC
C37.90
6
Dielectric
Strength
AC Power ports
2 kVAC
Environmental Type Tests
Test
Description
Test Levels
Severity Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40
°F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185
°F), 16 Hours
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Db
95% (non-
condensing), 55 °C
(131 °F), 6 cycles
IEC 60255-21-1
Vibration
2 g @ 10-150 Hz
Class 2
IEC 60255-21-2
Shock
30 g @ 11 ms
Class 2
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05
29
6.2 EMC and Environmental Type Tests
30
RUGGEDCOM RS8000T
Installation Manual, 01/2021, C79000-G8976-1023-05