NVA100X - Getting started - 01 - 2018

— Packaging ProNext devices must be stored within the required temperature limits; the relative humidity should not cause condensation or formation of frost. It is recommended that the devices are stored in their packaging; in the case of long storage, especial- ly in extreme climatic conditions, it is recommended that the device is supplied with power for some hours before the commissioning, in order to bring the circuits to the rating conditions and to stabilize the operation of the components. — Contents • Getting started • Test report • Screws — Technical support Full documentation is available on the www.thytronic.it website; for information and purchase of licen- ses for oscillographic recording function please contact THYTRONIC. TABLE OF CONTENTS Packaging ...................................................................................................................................................................................................................1 Contents .....................................................................................................................................................................................................................1 Technical support ......................................................................................................................................................................................................1 INSTALLATION 2 Mounting .....................................................................................................................................................................................................................2 Flush mounting ...........................................................................................................................................................................................................2 I/O diagram .................................................................................................................................................................................................................4 Electrical connections ..............................................................................................................................................................................................5 Output relays ..............................................................................................................................................................................................................6 Binary Inputs ..............................................................................................................................................................................................................6 Ethernet Ports ............................................................................................................................................................................................................7 Local Port ....................................................................................................................................................................................................................7 RS485 port ...................................................................................................................................................................................................................8 PROGRAMMING AND SETTINGS 9 MMI Password management ..................................................................................................................................................................................9 MMI (Man Machine Interface) .............................................................................................................................................................................11 Reading variables (READ) ......................................................................................................................................................................................11 Setting modifying (SET) ..........................................................................................................................................................................................12 TEST ...........................................................................................................................................................................................................................13 COMMUNICATION ..................................................................................................................................................................................................13 Circuit breaker commands .....................................................................................................................................................................................13 MMI menu structure ...............................................................................................................................................................................................14 NVA100X#P2J00TE0 In 5A UAUX 110-230 Vac/dc 100V 100V IEn UEn Un 1A 1A 5A 1A 5A Flush mounting Inductive CTs-VTs ThySensor inputs versions Rack mounting with MAR support 20 kV UNP 630 A NVA100X#P2000TE2 Inp UAUX 110-230 Vac/dc IEn 1A 1A 5A GETTING STARTED NOTE This document does not replace the instruction manual. Some functions described may be not available in all NVA100X models. NVA100X THE COMPREHENSIVE SOLUTION FOR FEEDERS AND UTILITIES PROTECTION

NVA100X - Getting started - 01 - 2018

I N S T A L L A T I O N MOUNTING — Flush mounting The fixed case, fitted with special fastening brackets, is mounted on the front of electric control board, previously drilled as indicated in the drawing. In case of side-by-side mounting of several relays the minimum drilling distance is determined by the front dimensions indicated in the overall dimensions drawing, increased by 3 mm, to ensure an adequate tolerance and gasket space between adjacent relays. The depth dimension, as indicated in the drawing, must be increased by as much as needed to allow room for the wiring. DRILLING TEMPLATE SIDE VIEW RACK MOUNTING FRONT VIEW REAR VIEW 177 252 225 20 210 ±0.3 164.4 158.0 ±0.3 189 94.5 N.4 holes ø 4.2 N.4 holes ø 4.2 156 164.4 177 207 189 215 10 9 A B IN2D IN1C OC1E OC2F NVA100X#JA2MM00 In 5A UAUX 110-230 Vac/dc 100V 100V IEn UEn Un 1A 1A 5A 1A 5A 177 (4U) 101.6 482.6 465

NVA100X - Getting started - 01 - 2018

• Remove the two vertical frames for access the holes for the fi xing screws; the frames are snapped. • Insert the device into the slot. • Fit the device to the panel with four screws.. • Replace the vertical frames.

NVA100X - Getting started - 01 - 2018

I/O DIAGRAM Note [1] two redundant ports with hw-sw switching selectable from TX (RJ45) + FX (optical fiber), TX + TX or FX + FX. A version with two simultaneously active Ethernet FX ports with RSTP protocol is available. Note [2] A version with 10 indipendent input is available. UL1 UL2 UL3 UE VOLTAGE INPUTS 9 10 7 8 5 6 3 4 BLOCK IN 3 4 1 IL1 IL2 IL3 IE CURRENT INPUTS 2 3 4 5 6 7 8 Local Ethernet X 1 2 BLOCK OUT BLOUT- BLOUT+ RS485 5 6 A+ B- X UAUX 1 ≅ 2 B1 B A IN1C [2] 11 12 13 14 15 16 17 18 19 20 BINARY INPUTS 1 IN1-1 IN1-2 IN1-3 IN1-4 IN1-5 IN1-6 IN1-7 IN1-8 IN1-9 IN1-10 IN1-11 IN1-12 IN1-13 IN1-14 IN1-15 IN1-16 2 3 4 5 6 7 8 9 10 OUTPUT RELAYS 1 3 2 18 20 19 9 10 11 12 13 14 OC1E KC1-1 4 6 5 KC1-2 7 8 KC1-3 KC1-4 KC1-5 KC1-6 15 17 16 KC1-7 KC1-8 1 3 2 18 20 19 9 10 11 12 13 14 OC2F KC2-1 4 6 5 KC2-2 7 8 KC2-3 KC2-4 KC2-5 KC2-6 15 17 16 KC2-7 KC2-8 IN2D 11 12 13 14 15 16 17 18 19 20 BINARY INPUTS 1 IN2-1 IN2-2 IN2-3 IN2-4 IN2-5 IN2-6 IN2-7 IN2-8 IN2-9 IN2-10 IN2-11 IN2-12 IN2-13 IN2-14 IN2-15 IN2-16 2 3 4 5 6 7 8 9 10 NVA100X 4-20 mA Mis.1 + - 3 1 2 # / ∩ 4 Mis.2 + - 7 5 6 # / ∩ 8 Mis.3 + - 10 9 # / ∩ Mis.4 + - 13 11 12 # / ∩ 14 Mis.5 + - 17 15 16 # / ∩ 18 Mis.6 + - 19 20 # / ∩ OPTIONS TA-TV ThySensor TX [1] TX [1] FX [1] FX [1] ETHERNET Pt100 1 2 3 PT1 MPT1 T1 4 5 6 PT2 GND2 GND3 GND4 GND5 GND6 GND7 GND8 GND1 MPT2 T2 7 8 9 PT3 MPT3 T3 10 11 12 PT4 MPT4 T4 13 14 15 PT5 MPT5 T5 16 17 18 PT6 MPT6 T6 19 20 21 PT7 MPT7 T7 22 23 24 PT8 MPT8 T8 ThySensor INPUTS IL1-UL1 IL2-UL2 IL3-UL3 P1 P2 UE B5 B6 IE B9 B10 UAUX B1 ≅ B2 IRIG-B AM IRIG-B IN IRIG-B/1PPS IN 1PPS OUT IRIG-B OUT

NVA100X - Getting started - 01 - 2018

ELECTRICAL CONNECTIONS Electrical connections should be made by referring to the connection diagram; CT-VT input versions For the A1...A8 and B1...B10 , screw terminals with following characteristics are available: • Nominal cross section: 0.2 to 4 mm2 (AWG 24...10) for single conductor 0.2 to 1.5 mm2 for two conductors with same cross section • Tightening torque: 0.5-0.6 Nm • Stripping length: 7 mm For the IN1C-1...16, IN2D-1...16, OC1E-1...16 and OC2F-1...16 connections, screw terminals with following characteristics are available: • Nominal cross section: 0.14 to 2.5 mm2 (AWG 26...16) for single conductor da 0.14 to 0.75 mm2 for two conductors with same cross section • Tightening torque: 0.5-0.6 Nm • Stripping length: 8 mm For the X1...X6 (RS485 and blocks) connections, screw terminals with following characteristics are available: • Nominal cross section: 0.2 to 2.5 mm2 (AWG 24...12) for single conductor 0.2 to 1.5 mm2 for two conductors with same cross section • Tightening torque: 0.5-0.6 Nm • Stripping length: 10 mm A protective ground connection is required, which must be connected to the suitable screw with a separate lead of at least 4 mm2. Amperometric inputs In case of replacement of the relay or checks on the amperometric circuits is essential to provide appropriate support to achieve the secondary circuit shorting. For security reasons it is advisable to operate in the absence of line current. When making the current connections, attention must be paid to not exceeding the performance of the line current transformers. To be exact, the total load, constituted by the NA80 protective relay, any other protective relays or measuring instruments and the resistance of the connections, must not exceed the line CT performance. In particular, consumption of the relay input circuit must not exceed 0.2 VA while the load (expressed in VA) constituted by the conductors is given by: 0.018 × L × In 2 / S where: L the overall length, expressed in m, of the two conductors in relation to each phase; In nominal current of the line CT expressed in A; S cross sectional area of the current conductors expressed in mm2. Devices must be installed by qualified personnel only. No liability is accepted from Thytronic due to improper use. CAUTION If the secondary of a CT carrying primary current is open circuited, a high voltage can be developed across the CT terminals. CAUTION Voltage inputs Auxiliary power supply Amperometric inputs X1...X4 Block2 X5, X6 RS485 10 9 A B IN2D IN1C OC1E OC2F Ground connection screw Binary inputs Output relays NVA100X#JA2MM00 In 5A UAUX 110-230 Vac/dc 100V 100V IEn UEn Un 1A 1A 5A 1A 5A

NVA100X - Getting started - 01 - 2018

ThySensor inputs (NVA100X#P) The inputs current and voltage connections are made through pre-wired L1, L2 and L3 RJ45 plug. For the A1, A2 and U1, U2 screw terminals with following characteristics are available: • Nominal cross section: 0.2 to 4 mm2 (AWG 24...10) for single conductor 0.2 to 1.5 mm2 for two conductors with same cross section • Tightening torque: 0.5-0.6 Nm • Stripping length: 7 mm For the IN1C-1...16, IN2D-1...16, OC1E-1...16 and OC2F-1...16 connections, screw terminals with fol- lowing characteristics are available: • Nominal cross section: 0.14 to 2.5 mm2 (AWG 26...16) for single flexible conductor 0.14 to 0.75 mm2 for two conductors with same cross section • Tightening torque: 0.5-0.6 Nm • Stripping length: 8 mm For the X1...X6 (RS485 and blocks) connections, screw terminals with following characteristics are available: • Nominal cross section: 0.2 to 2.5 mm2 (AWG 24...12) for single flexible conductor 0.2 to 1.5 mm2 for two conductors with same cross section • Tightening torque: 0.5-0.6 Nm • Stripping length: 10 mm. — Output relays The device may be confi gured with: • Two boards with eight command relays KC1-1...KC1-8 and KC2-1...KC2-8 (SPDT, tipo C e SPST- NO,type A) • One board with eight command relays KC1-1...KC1-8 and one boardwith with sixteen signalling relay KS1-1...KS1-16 (SPST-NO, type A with four commons) It is advisable to verify that the technical characteristic of the contacts be suitable for the applied load (about current, nominal voltage, make and break current , etc..). All contacts are shown in de-energized state for standard reference. — Binary Inputs The input circuits are voltage-free; activation requires the application of a power source, preferably the same auxiliary voltage present in the switchboard. The inputs are dimensioned for a wide range of operation and does not require any hw and / or sw Voltage and amperometric inputs from ThySensor Residual voltage input Binary inputs Output relays L1 B L2 L3 IN2D IN1C OC1E OC2F Auxiliary power supply 1 2 5 6 Residual current input 9 10 X1...X4 Block2 X5, X6 RS485 Ground screw 10 9

NVA100X - Getting started - 01 - 2018

programming. AUX-IN external modules allow the thresholds setting for the binary inputs activation. The digital inputs switching threshold can be set during installation so that the command voltage is comparable to the supply voltage. The inputs are immune to transitory interferences, however the following recommendation must be considered in high disturbed environments: • Position input wiring away from high energy sources. • Set a debounce timer (tON and/or tOFF) to alloy the transient to decay. • Use shielded cables with ground connection on only one end (preferably at the relay side. — Ethernet Ports Pro_NX relays are supplied with two Ethernet ports with TX (RJ45) or FX (fi ber optic) connection, and ModBus / TCP or IEC 61850 protocol. The following options are available: A) TX + FX ports [1] B) TX + TX ports [1] C) FX + FX ports [1] D) FX + FX + RSTP [2] Connections to TX ports (RJ45) must be made with shielded cable FTP Cat.5e category or higher. The link must be enabled by means ThySetter sw and local connection: • Set the IP address (Host IP address and IP net mask) n order that the NVA100X and PC parame- ters are matched. • Set to OFF parameters Autonegotiation on relay. Parameters are inside the Communication \ Ethernet submenu. Dopo aver eseguito le modifiche, af- finché le nuove impostazioni relative alla comunicazione Ethernet siano attive, è necessario togliere l’alimentazione ausiliaria e successivamente rialimentare il relè. — Local Port A cross cable must be used for connection between computer and local port. Nota 1 The TX (RJ45) and FX (fi bra ottica) Ethernet port are multiplexed (single IP address). Under normal conditions, the primary port is active, while the secondary port is activated in the event of failure of the primary port or by means of hw-sw switching command. Note 2 Two simultaneously active Ethernet ports with RSTP protocol ethernet-wiring.ai 4 6 5 2 1 3 x NETWORK 3V3 TX TX LINK2 LINK1 4 6 5 2 1 3 x NETWORK 3V3 FX TX LINK2 LINK1 4 6 5 2 1 3 x NETWORK 3V3 FX LINK2 LINK1 Var. A) Var. B) Var. C)-D) Ingressi logici +UAUX -UAUX A B IN1C IN2D BINARY INPUTS 1 IN1-1 IN1-2 IN1-3 IN1-4 2 3 4 5 BINARY INPUTS 1 IN2-1 IN2-2 IN2-3 IN2-4 2 3 4 5

NVA100X - Getting started - 01 - 2018

When used the local port takes priority over the Ethernet port. — RS485 port RS485 communication circuit connections must be made using screened twisted pair cable observing the polarities; screening must only be connected to a single end. It is recommended to terminate the line at the extremities of the same; this must be performed on the RS485 line control unit and on the ProNext device placed at the furthest point serial1-sch.ai Connector RJ45 RS485 120 Ω 120 Ω SUPERVISION UNIT A+ B- X5 X6 NVA100X UAUX ≅ ETH-1 ETH-2 ETHERNET 1 - DTR 2 - GND 3 - RX 4 - TX RS232 RS485 A+ B- X5 X6 NVA100X UAUX ≅ ETH-1 ETH-2 ETHERNET 1 - DTR 2 - GND 3 - RX 4 - TX RS232 RS485 A+ B- 4 6 5 2 1 3 x NETWORK 3V3 FX TX LINK2 LINK1 RS485 B- A+

NVA100X - Getting started - 01 - 2018

P R O G R A M M I N G A N D S E T T I N G S All relay programming and adjustment operations may be performed through • MMI (keyboard and display) • a Personal Computer with the aid of the ThySetter software — MMI Password management Preamble For security purpose, is possible to password-protect modification to the settings of relays by mean of the MMI (keyboard and display). Is possible to select: • OFF - modification of the settings by means of MMI (keyboard and display) are permanently disabled, • ON - modification of the settings by means of MMI (keyboard and display) are permanently enabled, • By Password - modification of the settings by means of MMI (keyboard and display) are enabled only after typing of password. Default setting is ON (modification enabled). Setting can be changed using Thysetter only on level 1 ( menu (Preference / Session Level). ThySetter Setting Parameter Setting Enable is in menù Set / MMI. Note: to make any changes with Thysetter you need to start change settings, change the setting and end change settings. MMI If the By password mode is selected a new menu PASSWORD is inserted at the top of the display menu. Press the key ENTER PASSWORD message is displayed followed by Password not ok >>; press the key you can enter the personal password with the usual procedure (de- fault password is 0000): • Press the (Enter) button for a few seconds; the modification in progress status is highlighted by flashing of the START and TRIP LEDs and by appearance of the pointer on the bottom • Change the parameters by means the or moving to the next character with . • Press the (Enter) button; the cursor and the LED TRIP turn off (the LED START keeps flashing) • Press the (Enter) button for a few seconds; new message appears: Confirm settings? • Answer to the message ENTER: YES to confirm changes or RESET: NO to abort. • After entering the current password correctly, the message ENTER PASSWORD and PAS- SWORD OK >> appears on display. If password is correct, from this moment is possible to change settings. After some minutes of inactivity, reported by turning off the display backlight, Dopo alcuni minuti di inattività, segnalati dallo spegnimento della retroilluminazione del display, possibility of modification is disabled and therefore it is necessary to re-enter the password. If you continue navigating the menus without entering the password, you can view all settings, but it WARNING For safety reasons, a change of the rated values (Set \ Base menu) parameters become active only after an hw reset

NVA100X - Getting started - 01 - 2018

is impossible to make any modification (keeping pressed for some seconds the key (Enter) modi- fication procedure is disabled (LED START, TRIP and curson under the parameters to be modified). Changing password After correct insertion of password is displayed this message: ENTER PASSWORD and PASSWORD OK >>; pressing the key is shown the message CHANGE PASSWORD >> and pressing button you access the relative menu where you can enter the new password. Lost password To change password current one must be entered. If the password is lost, neither the password nor any parameter from MMI can be changed and the changes can only be made by ThySetter. To enable modification from MMI without password is needed to disable password lock connecting a PC with Thysetter setting ON parameter Parameters setting enable available in menu Set / MMI. If password is lost and password lock must be enabled, device database must be reset using the com- mand Set default setting available in the menu Command \ Default setting. (double click on Default Setting, click on Set default setting, right click --> Send Command). Note: The command Set default settings restores the factory settings, all user- defined adjustments are cleared. Be carefully to enter the correct parameter ! The device serial number should be set to avoid IP address conflicts for devices con- nected to the Ethernet network.

NVA100X - Getting started - 01 - 2018

MMI (MAN MACHINE INTERFACE) On the front panel there are eight buttons which allow the user to perform all the settings, reading and modification operations.[1] The adjustment of the settings and the operation mode of the output relays must be performed while the unit is electrically powered. All preset values are permanently stored in the nonvolatile memory. The buttons take the following operations: - (Up) move the cursor upwards to the preceding menu options - (Down) move the cursor downwards to the subsequent menu options - (Left) move the cursor upwards to the preceding menu options - (Right) move the cursor downwards to the subsequent menu options - (Enter) access to the selected menu with the option of modifying any given parameter - (Reset) abort the current changes and/or accessing the previous menu - Circuit breaker Open command - Circuit breaker Close command At power-up, the display shows the text: “THYTRONIC PRO-NVA100X-VM00-a date and time: (01/01/2000 00:00” The ON green Led points out the auxiliary power supply voltage (permanent lighted) and possible faults (blink lighted). The display backlight is automatically activated when any key switch is set. By means of the (Up) or (Down) buttons, it is possible to cyclically browse through the menu options: READ, SET, COMMUNICATION, TEST Having identifi ed the sub-menu of interest, it is possible to gain access by using the (Right) button and then analogously, run through the relevant options by using the (Up) or (Down) buttons. The full menu tree and some examples are showed in the following pages (numerical values and settings are pointed out as examples and does not agree with real situations). — Reading variables (READ) All data (measure, settings, parameters, etc...) can be displayed; they are arranged in functional group submenus:: “SELF TEST >>” “SERIAL NUMBER >>” “INFO >>” “MEASURES >>” “ACTIVE PROFILE >>” “PROTECTIONS >>” “PLC >>” “CIRCUIT BREAKER SUPERVISION >>” “DELAYED INPUTS IN1-1...IN1-16 >>” “INTERNAL STATES >>” “RELAYS KC1-1...KC1-8 >>” “PARTIAL COUNTERS >>” “TOTAL COUNTERS >>” “SELF-TEST >>” “PILOT WIRE DIAGNOSTIC >>” “SELECTIVE BLOCK BLOCK2 >>” “INTERNAL ELECTIVE BLOCK BLOCK4 >>” “FAULT RECORDING >>” “EVENTS RECORDING >>” Note 1 LSetting changes are enabled when the Enabling setting by MMI parameter is set OPEN CB CLOSE CB Label_LED LEDs Input 1 board LEDs L1-1...L1-8 user programmable Input 1 MMI board LEDs L1-1...L1-8 user programmable ON e Diagnostic Start Trip

NVA100X - Getting started - 01 - 2018

— Setting modifying (SET) For safety reason is sometime required that modification of settings using MMI (keyboard and display) is disabled; in this way only qualified personell can modify settings using software Thysetter. All changes in the setting parameters are carried out through MMI only if the Enable setting by MMI parameter is ON. (ENABLE SETTING BY MMI submenu inside the SET menu). To effect a change, having identified the parameter intended for change, the following procedure must be performed: • Select the parameter going through the menus by means the , and keys • Press the (Enter); button for a few seconds; the modification in progress status is highlighted by flashing of the START and TRIP LEDs and by appearance of the pointer on the bottom. • Move the cursor over the parameter intended for change using the (Enter) button,. • Change the parameters by means the (increment) or (decrement) buttons. • Press the (Enter) button to move the cursor over the last parameter in the display. • Press the (Enter) button once again; the cursor and the LED TRIP turn off (the LED START keeps flashing). • Press the (Enter) button for a few seconds; new message appears: “Confirm settings?” • Answer to the message ENTER: YES to confi rm changes or RESET: NO to abort. The end of the START LED blinking points out the end of procedure; the changes become right now active. The abort command may be used to abandon changes (prior to use of the ENTER: YES); the same effect is achieved by removing the auxiliary power supply to the relay. As example, to set the operating mode of the KC1-1 output relay as ENERGIZED, LATCHED, the following procedure must be issued: • Select menu Set “SET >>”by mean of the button (Down). • Press the (Right) button to enter; the following submenu title is displayed: “BASE >>” • Scroll menus by means (Down) button “INPUT SEQUENCE >>” “POLARITY >>” “LINE >>” “ENABLE VECTOR JUMP >>” “INPUTS IN1-1...IN1-16 >>” “RELAYS KC1-1...KC1-8 >>” “LEDs ON MMI >>” “LEDs LED1-1...LED1-8 >>” “SELF-TEST RELAY >>” “MMI >>” “AUTO-RECLOSE 79 >>” “PROFILE SELECTION >>” “PROFILE A >>” “PROFILE B >>” “PLC >>” “CIRCUIT BREAKER SUPERVISION 52 >>” “VT SUPERVISION 74VT >>” “CT SUPERVISION 74CT >>” “FAULT LOCATOR FL >>” “REMOTE TRIPPING >>” “PILOT WIRE DIAGNOSTIC >>” “DEMAND MEASURES >>” • Select the Set menu “RELAYS KC1-1...KC1-8 >>”, the “KC1-1 relay Setpoints >>” is displayed. • Press the (Right) button to enter; the following messages are displayed: “Logic DE-ENERGIZED Mode NO LATCHED” • Press the (Enter) button for a few seconds; the modification in progress status is highlighted by the both START and TRIP flashing. • Move the cursor over the parameter intended for change using the (Enter), button, (in our case on the message “Logic DE-ENERGIZED”, • Change the parameters by means the o “Logic ENERGIZED”, • Premere il pulsante (Enter) momentaneamente per posizionare il cursore in corrispondenza del- l’ultimo parametro visualizzato sul display, “Mode NO LATCHED”, • Modificare il parametro mediante i pulsanti (increment) or (decrement) buttons, “Mode LA- TCHED”, • Press the (Enter) button once again; the cursor and the LED TRIP turn off (the LED START keeps flashing), • Press the (Enter) button for a few seconds; new message appears: “Confirm settings?” • Answer to the message ENTER: YES to confirm changes or RESET: NO to abord The end of the LED START blinking points out the end of procedure.

NVA100X - Getting started - 01 - 2018

— TEST The operational tests with command of the selected output relays may be activated. By means of (Up) or (Down) buttons it is possible to browse the main menu till the “ “TEST” message; to enter you must press the (Right) button. [1] The display message “Test state: OFF” shows the test state (OFF or test in progress). By means of (Down) button is possible to browse menu to select: • Stop test • Start test • Test KC1-1 • Test KC1-2 • Test KC1-3 • Test K... As example, to start the test of KC1-1, the following procedure must be issued:: • Select the Start test menu “Start test? >>”. • Press the (Right) button to start; the test in progress status is highlighted by activation of all LEDs. • Come back by pressing the (Left) . • Select the relay to be tested KC1-1 by means or until the message “Test KC1-1? >> is displayed. • Press the (Right) button to start the test on KC1-1. • To terminate the test, it is necessary to select the “Stop test? >>” message and press the (Right). button to end the test. In any case the test will be automatically terminated after a delay of one minute. — COMMUNICATION Inside the COMMUNICATION menu it is possible to read/modify the setting data of the RS485 Protocol and Ethernet parameters. Since newer versions Ip Address can be modified only in Commands \ Set Params \ Set not resettable parameter. By means of (Up) or (Down) buttons it is possible to browse the main menu till the “RS485 Protocol >>”, “Ethernet Local Parameters >>” or“Ethernet Remote Parameters >>”; to enter you must press the (Right) button. As example, to select the address 12 for the ModBus protocol, the following procedure must be issued: • Select the Communication menu“COMMUNICATION >>”. • By means (Down) button select the “RS485 Protocol >>”. • Press the (Right) button to enter; the following message is displayed: “Protocol MODBUS” “Address 1” “9600 baud” • Start the procedure to effect a change explained in the Setting modifying (SET) paragraph • Press the (Enter); button for a few seconds; the modifi cation in progress status is highlighted by the both START and TRIP flashing. • Move the cursor over the parameter intended for change using the (Enter), button, (in the exam- ple on the 1 address), • Change the parameters by means the (increment) button (up to 12 address), • Press the (Enter) button to move the cursor over the last parameter in the display. • Press the (Enter) button once again; the cursor and the LED TRIP turn off (the LED START keeps flashing), • Press the (Enter) button for a few seconds; new message appears: “Confirm settings?” • Answer to the message ENTER: YES to confirm changes or RESET: NO to abort. The end of the LED blinking points out the end of procedure. — Circuit breaker commands By means of the (open) and (close) keys, the circuit breaker commands may be issued. The committed output relays must be enabled inside the Circuit Breaker supervision \ LEDs-relays allocation menu. Note 1 Instantly all the relays are switched in rest state, including relays programmed as “normally energized”

NVA100X - Getting started - 01 - 2018

MMI MENU STRUCTURE READ NVA100X_menuread1.ai Profile A ACTIVE PROFILE >> PROCEED READ MENU’ State N.Open OFF State SumI OFF State SumI^2t OFF State tbreak OFF SumIL1 0 In SumIL2 0 In SumIL3 0 In SumIL1^2t 0 In^2s SumIL2^2t 0 In^2s SumIL3^2t 0 In^2s CIRCUIT BREAKER SUPERVISION >> CB COMMANDS >> CB POSITION >> CB DIAGNOSTIC >> CB-OPEN Cmd OFF CB-CLOSE Cmd OFF CB state ? Binary IN1-1 OFF Binary IN1-2 OFF Binary IN1-3 OFF .................. Binary IN1-16 OFF DELAYED INPUTS IN1-1...IN1-16 >> VIN01 Status OFF VIN01 Timeout ON VIN02 Status OFF VIN02 Timeout ON .................. VIN032 Status OFF VIN032 Timeout ON VIN >> VOUT01: OFF VOUT02: OFF VOUT03: OFF .................. VOUT16: OFF VOUT >> INFO >> Code NVA100X-VM00-a Ver.sw 1.00 DSP fw Rel 1.00 SERIAL NUMBER >> Serial number 237 IEC61850 >> Code NVA100X-VM00-a Sw Release 1.30 SELF TEST >> Protection ON SERVICE Global self-test OK System OK Data-base: boot OK run-time OK DAta BUS: heavy OK minor OK DSP: .................. MODULES >> MMI board ON SING1 board ON SING2 board OFF SRC1 board ON ------------------ << No Yes >> Disable 27-27V1-37? DISABLE 27-37 FUNCTIONS BY OPERATOR >> PROTECTIONS >> SEE NEXT PAGES THYTRONIC PRO-NVA100X-VM00-a DATE: 19/06/2013 TIME: 17:29:59 PLC >> PLC State 1: 0 PLC State 2: 0 PLC State x: 0 .................. PLC State 32: 0 User SW name: xxx Ver.: DATE: 01/08/2007 PLC state: OFF PLC version: 01.40 Error: none Warning: none PLC States >> CLOCK ADJUST >> HOUR: 14 MINUTE: 25 SECONDS: 0 << Confirm >> DAY: 11 MONTH: 7 YEAR: 2013 << Confirm >> START SYNCHRO CHECK >> Start Synchro check? <> MEASURES >> IL1 0.000 In IL2 0.000 In IL3 0.000 In IE 0.000 IEn UL1 0.000 En UL2 0.000 En UL3 0.000 En UL4 0.000 Un4 UE 0.000 UEn U12 0.000 Un U23 0.000 Un U31 0.000 Un UEC 0.000 UECn ILmax 0.000 In ILmin 0.000 In IL 0.000 In ULmax 0.000 En UL 0.000 Un U 0.000 Un PhiL1 0 deg PhiL2 0 deg PhiL3 0 deg Alpha1 0 deg Alpha2 0 deg Alpha3 0 deg PhiE 0 deg PhiEC 0 deg DTheta 0 DThetaB I1 0.000 In I2 0.000 In I2/I1 0.000 In U1 0.000 En U2 0.000 En U/f 0.000 Un/fn P 0.000 Pn Q 0.000 Qn S 0.000 An CosPhi 1.000 PL1 0.000 Pn QL1 0.000 Qn CosPhiL1 1.000 PL2 0.000 Pn QL2 0.000 Qn CosPhiL2 1.000 PL3 0.000 Pn QL3 0.000 Qn CosPhiL3 1.000 IL1-2nd 0.000 In IL2-2nd 0.000 In IL3-2nd 0.000 In IL1-3rd 0.000 In IL2-3rd 0.000 In IL3-3rd 0.000 In IE-3rd 0.000 IEn UE-3rd 0.000 UEn IL1-4th 0.000 In IL2-4th 0.000 In IL3-4th 0.000 In IL1-5th 0.000 In IL2-5th 0.000 In IL3-5th 0.000 In f 0.000 Hz fUL1 0.000 Hz fUL4 0.000 Hz DV 0.000 Un4 DF 99.99 Hz PhiL14 0 deg df/dt 0.000 Hz/s IL1FIX 0.000 In IL2FIX 0.000 In IL3FIX 0.000 In PFIX 0.000 Pn QFIX 0.000 Qn IL1ROL 0.000 In IL1ROL 0.000 In IL2ROL 0.000 In IL3ROL 0.000 In PROL 0.000 Pn QROL 0.000 Qn IL1MAX 0.000 In IL2MAX 0.000 In IL3MAX 0.000 In PMAX 0.000 Pn QMAX 0.000 Qn IL1MIN 0.000 In IL2MIN 0.000 In IL3MIN 0.000 In PMIN 0.000 Pn QMIN 0.000 Qn EA+ 0 kWh EA- 0 kWh EQ+ 0 kvarh EQ- 0 kvarh EA 0 kWh EQ 0 kvarh INTERNAL STATES >> LEDs reset OFF Prof. switch OFF Block1: OFF Block2 Generic OFF Block2 50 OFF Block2 50N OFF TCS1 OFF TCS2 OFF Ext.trip BF OFF Remote trip OFF Fault trig OFF 52a OFF 52b OFF CB OPEN Cmd OFF CB CLOSE Cmd OFF CB Monitor OFF 79 Enable OFF 79 Block OFF 79 Ext. OFF Reset Demand OFF Reset Energy OFF Reset count. OFF Thermal image init OFF 74VT ext. OFF MCB VT OPEN OFF TCP >> MULTICAST >> SERVER >> RPC >> CLIENT01: OFF CLIENT02: OFF CLIENT03: OFF .................. CLIENT08: OFF CLIENT01: OFF CLIENT02: OFF CLIENT03: OFF .................. CLIENT08: OFF CON. TCP: 0 CON. MCAST: 0 NOTA I menù illustrano tutte le funzioni di protezione Le funzioni effettivamente presenti dipendono dalla versione di NVA100X-x (x = B, V, P, G o C)

NVA100X - Getting started - 01 - 2018

NVA100X_menuread1a.ai PROTECTIONS 27 >> Start U< OFF Trip U< OFF BLK1 U< OFF Start U<< OFF Trip U<< OFF BLK1 U<< OFF 27V1 >> Start U1< OFF Trip U1< OFF BLK1 U1< OFF 37 >> Start I< OFF Trip I< OFF BLK1 I< OFF 37P >> Start P1< OFF Trip P1< OFF BLK1 P1< OFF Start P2< OFF Trip P2< OFF BLK1 P1< OFF Start IE> OFF Trip IE> OFF CLP IE> OFF BLK1 IE> OFF BLK2IN IE> OFF BLK4IN IE> OFF Start IE>> OFF Trip IE>> OFF CLP IE>> OFF BLK1 IE>> OFF BLK2IN IE>> OFF BLK4IN IE>> OFF Start IE>>> OFF Trip IE>>> OFF CLP IE>>> OFF BLK1 IE>>> OFF BLK2IN IE>>> OFF BLK4IN IE>>> OFF 50N/51N-87NHIZ >> Start IEC> OFF Trip IEC> OFF CLP IEC> OFF BLK1 IEC> OFF BLK2IN IEC> OFF BLK4IN IEC> OFF Start IEC>> OFF Trip IEC>> OFF CLP IEC>> OFF BLK1 IEC>> OFF BLK2IN IEC>> OFF BLK4IN IEC>> OFF Start IEC>>> OFF Trip IEC>>> OFF CLP IEC>>> OFF BLK1 IEC>>> OFF BLK2IN IEC>>> OFF BLK4IN IEC>>> OFF 50N(C)/51N(C) >> 37Q >> Start P1< OFF Trip P1< OFF BLK1 P1< OFF Start P2< OFF Trip P2< OFF BLK1 P1< OFF 32P >> Start P1> OFF Trip P1> OFF BLK1 P1> OFF Start P2> OFF Trip P2> OFF BLK1 P2> OFF 32Q >> Start Q1> OFF Trip Q1> OFF BLK1 Q1> OFF Start Q2> OFF Trip Q2> OFF BLK1 Q2> OFF 49MG >> Alarm DThAL OFF BLK1 DThAL OFF BLK2IN DThAL OFF Trip DTh> OFF BLK1 DTh> OFF BLK2IN DTh> OFF Alarm DThAL1 OFF BLK1 DThAL1 OFF BLK2IN DThAL1 OFF BLK4IN DThAL1 OFF Alarm DThAL2 OFF BLK1 DThAL2 OFF BLK2IN DThAL2 OFF BLK2IN DThAL2 OFF BLK4IN DThAL2 OFF Trip DTh> OFF BLK1 DTh> OFF BLK2IN DTh> OFF BLK4IN DTh> OFF CLP DTh OFF 49LT >> 79 >> ActiveMode 79 OFF Run 79 OFF CycleState 79 Rest Residual-time 79 0 s LastEvent 79 No events EnableState 79 OFF Start(U/f)AL OFF Trip (U/f)AL OFF BLK1 (U/f)AL OFF Start(U/f)> OFF Trip (U/f)> OFF BLK1 (U/f)> OFF Start(U/f)>> OFF Trip (U/f)>> OFF BLK1 (U/f)>> OFF 24 >> Synchro Avv OFF Synchro ControlOFF Synchro Trip OFF Synchro diagnostic State V1-SYNC OFF State V4-SYNC OFF State f1-RANGE OFF State f4-RANGE OFF State V1>SYNC OFF State V4>SYNC OFF State V1> I2/I1 >> Start I21> OFF Trip I21> OFF BLK1 I21> OFF CLP I21> OFF 46M >> Start I2> OFF Trip I2> OFF CLP I2> OFF BLK1 I2> OFF BLK2IN I2> OFF Start I2>> OFF Trip I2>> OFF CLP I2>> OFF BLK1 I2>> OFF BLK2IN I2>> OFF Start I> OFF Trip I> OFF CLP I> OFF BLK1 I> OFF BLK2IN I> OFF BLK4IN I> OFF Start I>> OFF Trip I>> OFF CLP I>> OFF BLK1 I>> OFF BLK2IN I>> OFF BLK4IN I>> OFF Start I>>> OFF Trip I>>> OFF CLP I>>> OFF BLK1 I>>> OFF BLK2IN I>>> OFF BLK4IN I>>> OFF 50/51 >> PROCEED READ MENU’ Start I2AL> OFF Trip I2AL> OFF BLK1 I2AL> OFF Start I2>> OFF Trip I2>> OFF BLK1 I2>> OFF 46G >> 47 >> Start US1< OFF Start US> OFF Trip 47 OFF BLK1 47 OFF 55 >> Start CPhi1< OFF Trip CPhi1< OFF BLK1 CPhi1< OFF Start CPhi2< OFF Trip CPhi2< OFF BLK1 CPhi2< OFF 46LT >> Start I2> OFF Trip I2> OFF CLP I2> OFF BLK1 I2> OFF BLK2IN I2> OFF Start I2>> OFF Trip I2>> OFF CLP I2>> OFF BLK1 I2>> OFF BLK2IN I2>> OFF

NVA100X - Getting started - 01 - 2018

NVA100X_menuread1b.ai PROTECTIONS 74VT >> Block 74VT OFF Alarm 74VT OFF BLK1 74VT OFF 74CT >> Start I* OFF Trip S< OFF BLK1 S< OFF 59 >> Start IED> OFF Trip IED> OFF CLP IED> OFF BLK1 IED> OFF BLK2IN IED> OFF BLK4IN IED> OFF Start IED>> OFF Trip IED>> OFF CLP IED>> OFF BLK1 IED>> OFF BLK2IN IED>> OFF BLK4IN IED>> OFF Start IED>>> OFF Trip IED>>> OFF CLP IED>>> OFF BLK1 IED>>> OFF BLK2IN IED>>> OFF BLK4IN IED>>> OFF Start IED>>>> OFF Trip IED>>>> OFF CLP IED>>>> OFF BLK1 IED>>>> OFF BLK2IN IED>>>> OFF BLK4IN IED>>>> OFF 67N >> BF >> Trip Int/Ext OFF Start IBF> OFF Start IEBF> OFF Start BF OFF Trip BF OFF BLK1 BF OFF 74VTint67 State OFF 74VText67 State OFF Start IPD> OFF Trip IPD> OFF CLP IPD> OFF BLK1 IPD> OFF BLK2IN IPD> OFF BLK4IN IPD> OFF Start IPD>> OFF Trip IPD>> OFF CLP IPD>> OFF BLK1 IPD>> OFF BLK2IN IPD>> OFF BLK4IN IPD>> OFF Start IPD>>> OFF Trip IPD>>> OFF CLP IPD>>> OFF BLK1 IPD>>> OFF BLK2IN IPD>>> OFF BLK4IN IPD>>> OFF Start IPD>>>> OFF Trip IPD>>>> OFF CLP IPD>>>> OFF BLK1 IPD>>>> OFF BLK2IN IPD>>>> OFF BLK4IN IPD>>>> OFF 67 >> Start U> OFF Trip U> OFF BLK1 U> OFF Start U>> OFF Trip U>> OFF BLK1 U>> OFF 59N >> Start UE> OFF Trip UE> OFF BLK1 UE> OFF Start UE>> OFF Trip UE>> OFF BLK1 UE>> OFF VECTOR JUMP >> Start dphi> OFF Trip dphi> OFF BLK1 dphi> OFF Enphi state OFF Start 74TCS OFF Trip 74TCS OFF BLK1 74TCS OFF Start I2ndh> OFF 2ndh-REST >> 74TCS >> 59V2 >> Start U2> OFF Trip U2> OFF BLK1 U2> OFF 66 >> Trip 66 OFF BLK1 66 OFF ATST 0 s ANST 0 AtIN 0 s 81O >> Start f> OFF Trip f> OFF BLK1 f> OFF Start f>> OFF Trip f>> OFF BLK1 f>> OFF 81U >> Start f< OFF Trip f< OFF BLK1 f< OFF Start f<< OFF Trip f<< OFF BLK1 f<< OFF Start f<<< OFF Trip f<<< OFF BLK1 f<<< OFF Start f<<<< OFF Trip f<<<< OFF BLK1 f<<<< OFF 81R >> Start df> OFF Trip df> OFF BLK1 df> OFF Start df>> OFF Trip df>> OFF BLK1 df>> OFF Start df>>> OFF Trip df>>> OFF BLK1 df>>> OFF Start df>>>> OFF Trip df>>>> OFF BLK1 df>>>> OFF PROCEED READ MENU’ PREVIOUS READ MENU’

NVA100X - Getting started - 01 - 2018

READ PREVIOUS READ MENU’ PROCEED READ MENU’ PARTIAL COUNTERS SEE NEXT PAGES TOTAL COUNTERS SEE NEXT PAGES NVA100X_menuread2.ai NVA100X_menuread1.ai KC1-1 relay OFF KC1-1 coil OK KC1-2 relay OFF KC1-2 coil OK KC1-3 relay OFF KC1-3 coil OK KC1-4 relay OFF KC1-4 coil OK KC1-5 relay OFF KC1-5 coil OK KC1-6 relay OFF KC1-6 coil OK KC1-7 relay OFF KC1-7 coil OK KC1-8 relay OFF KC1-8 coil OK RELAYS KC1-1...KC1-8 Fault 0 (last) >> Fault 1 >> Fault ... >> Fault 10 >> FAULTS RECORDING >> PILOT WIRE DIAGNOSTIC >> BreakedBLIN1 OFF ShortedBLIN1 OFF BLOCK2IN-IPh OFF BLOCK2IN-IE OFF tb timeout OFF Fault 0 Cause: - Operating phase: - Date: Time: IL1r: 0.000 In IL2r: 0.000 In IL3r: 0.000 In UL1r: 0.000 Un UL2r: 0.000 Un UL3r: 0.000 Un U12r: 0.000 Un U23r: 0.000 Un U31r: 0.000 Un IEr: 0.000 IEn IECr: 0.000 IEn UEr: 0.000 UEn UECr: 0.000 UECn PhiL1r: 0 deg PhiL2r: 0 deg PhiL3r: 0 deg Alpha1r: 0 deg Alpha2r: 0 deg Alpha3r: 0 deg PhiEr: 0 deg PhiECr: 0 deg DTheta-r: : 0.000 DThetaB U1r: 0.000 En U2r: 0.000 En U/fr: 0.000 Un/fn Pr: 0.000 Pn Qr: 0.000 Qn CosPhir: 0.000 fr: 0.000 fn dfr: 0.000 Hz/s dphir: 0 deg Binary inputs IN1-16...IN1-1: 0000000000000000 IN2-16...IN2-1: 0000000000000000 Relay KC1-8...KC1-1: 00000000 KC2-8...KC2-1: 00000000 ST-IPh-BLK2 OFF ST-IE-BLK2 OFF BLK2OUT-IPh OFF BLK2OUT-IE OFF BLK2OUT-IPh/IE OFF SELECTIVE BLOCK BLOCK2 BLOCK2 INPUT >> BLOCK2 OUTPUT >> INTERNAL SELECTIVE BLOCK BLOCK4 >> ST-IPh-BLK4 OFF ST-IE-BLK4 OFF BLK4OUT OFF Event 0 (last) Power up 17/06/2013 06:48:27:254 Event 1 Settings 18/06/2013 06:48:27:254 Event 2 Power down 18/06/2013 08:00:27:137 Event ... Settings 18/06/2013 06:48:27:254 Event 299 Settings 18/06/2013 06:48:27:254 EVENTS RECORDING >>

NVA100X - Getting started - 01 - 2018

ParStUcnt 0 ParTrI>cnt 0 ParBk1I>cnt 0 ParBk2I>cnt 0 ParStI>>cnt 0 ParTrI>>cnt 0 ParBk1I>>cnt 0 ParBk2I>>cnt 0 ParStI>>>cnt 0 ParTrI>>>cnt 0 ParBk1I>>>cnt 0 ParBk2I>>>cnt 0 ParSt-P1>cnt 0 ParTr-P1>cnt 0 ParBk1-P1>cnt 0 ParSt-P2>cnt 0 ParRt-P2>cnt 0 ParBk1-P2>cnt 0 ParSt-P1cnt 0 ParTr-Q1>cnt 0 ParBk1-Q1>cnt 0 ParSt-Q2>cnt 0 ParRt-Q2>cnt 0 ParBk1-Q2>cnt 0 ParStU1cnt 0 ParTr(U/f)>cnt 0 ParBk1(U/f)>cnt 0 ParSt(U/f)>>cnt 0 ParTr(U/f)>>cnt 0 ParBk1(U/f)>>cnt 0 79 Counters >> 24 Counters >> ParRR79cnt 0 ParSR79cnt 0 ParDR79cnt 0 ParFR79Pcnt 0 ParFR79Ecnt 0 25 Counters >> 27 Counters >> 32P Counters >> 32Q Counters >> 27V1 Counters >> ParTr-47cnt 0 ParBk1-47cnt 0 47 Counters >> ParStI> 37P Counters >> 37Q Counters >> ParTr25cnt 0 ParStUE>cnt 0 ParTrUE>cnt 0 ParBk1UE>cnt 0 ParStUE>>cnt 0 ParRtUE>>cnt 0 ParBk1UE>>cnt 0 49MG Counters >> 55 Counters >> 67 Counters >> 67N Counters >> 81O Counters >> 81U Counters >> CB Counters >> 74TCS Counters >> 74VT Counters >> 74CT Counters >> BF Counters >> 50/51 Counters >> ParStU>cnt 0 ParTrU>cnt 0 ParBk1U>cnt 0 ParStU>>cnt 0 ParRtU>>cnt 0 ParBk1U>>cnt 0 59 Counters >> 59N Counters >> 50N/51N Counters >> 51V Counters >> 40 Counters >> 49LT Counters >> ParAlDthAL1cnt 0 ParBk1DthAL1cnt 0 ParBk2DthAL1cnt 0 ParAlDthAL2cnt 0 ParBk1DthAL2cnt 0 ParBk2DthAL2cnt 0 ParTrDth>cnt 0 ParBk1Dth>cnt 0 ParBk2Dth>cnt 0 46M Counters >> ParAlDthAL1cnt 0 ParBk1DthAL1cnt 0 ParBk2DthAL1cnt 0 ParAlDthAL2cnt 0 ParBk1DthAL2cnt 0 ParBk2DthAL2cnt 0 ParTrDth>cnt 0 ParBk1Dth>cnt 0 ParBk2Dth>cnt 0 50N(C)/51N(C Counters >> ParStIPD>cnt 0 ParTrIPD>cnt 0 ParBk1IPD>cnt 0 ParBk2IPD>cnt 0 ParStIPD>>cnt 0 ParTrIPD>>cnt 0 ParBk1IPD>>cnt 0 ParBk2IPD>>cnt 0 ParStIPD>>>cnt 0 ParTrIPD>>>cnt 0 ParBk1IPD>>>cnt 0 ParBk2IPD>>>cnt 0 ParStIPD>>>>cnt 0 ParTrIPD>>>>cnt 0 ParBk1IPD>>>>cnt 0 ParBk2IPD>>>>cnt 0 ParStIED>cnt 0 ParTrIED>cnt 0 ParBk1IED>cnt 0 ParBk2IED>cnt 0 ParStIED>>cnt 0 ParTrIED>>cnt 0 ParBk1IED>>cnt 0 ParBk2IED>>cnt 0 ParStIED>>>cnt 0 ParTrIED>>>cnt 0 ParBk1IED>>>cnt 0 ParBk2IED>>>cnt 0 ParStIED>>>>cnt 0 ParTrIED>>>>cnt 0 ParBk1IED>>>>cnt 0 ParBk2IED>>>>cnt 0 ParBk1-74CTcnt 0 ParTr74CTcnt 0 ParStBFcnt 0 ParTrTrcnt 0 ParBk1BFcnt 0 2ndh-REST Counters >> ParStI2ndh>cnt 0 N.OpenCBcnt 0 ParBk1-74VTcnt 0 ParTr74VTcnt 0 ParBk1-74TCScnt 0 ParTr74TCScnt 0 I2/I1 Counters >> ParStI21>cnt 0 ParTrI21>cnt 0 ParBk121>cnt 0 46LT Counters >> ParStI2>cnt 0 ParTrI2>cnt 0 ParBk1I2>cnt 0 ParBk2I2>cnt 0 ParStI2>>cnt 0 ParTrI2>>cnt 0 ParBk1I2>>cnt 0 ParBk2I2>>cnt 0 ParStIE>cnt 0 ParTrIE>cnt 0 ParBk1IE>cnt 0 ParBk2IE>cnt 0 ParStIE>>cnt 0 ParTrIE>>cnt 0 ParBk1IE>>cnt 0 ParBk2IE>>cnt 0 ParStIE>>>cnt 0 ParTrIE>>>cnt 0 ParBk1IE>>>cnt 0 ParBk2IE>>>cnt 0 ParStIEC>cnt 0 ParTrIEC>cnt 0 ParBk1IEC>cnt 0 ParBk2IEC>cnt 0 ParStIEC>>cnt 0 ParTrIEC>>cnt 0 ParBk1IEC>>cnt 0 ParBk2IEC>>cnt 0 ParStIEC>>>cnt 0 ParTrIEC>>>cnt 0 ParBk1IEC>>>cnt 0 ParBk2IEC>>>cnt 0 59V2 Counters >> ParStU2>cnt 0 ParTrU2>cnt 0 ParBk1U2>cnt 0 55 Counters >> ParStCPhi> ParTr66cnt 0 ParBk1-66cnt 0 ParSt-f>cnt 0 ParTr-f>cnt 0 ParBk1-f>cnt 0 ParSt-f>>cnt 0 ParTr-f>>cnt 0 ParBk1-f>>cnt 0 VECTOR JUMP Counters >> ParSt-dpi>cnt 0 ParTr-dpi>cnt 0 ParBk1-dpi>cnt 0 ParSt-f> ParSt-df>cnt 0 ParTr-df>cnt 0 ParBk1-df>cnt 0 ParSt-df>>cnt 0 ParTr-df>>cnt 0 ParBk1-df>>cnt 0 ParSt-df>>>cnt 0 ParTr-df>>>cnt 0 ParBk1-df>>>cnt 0 ParSt-df>>>>cnt 0 ParTr-df>>>>cnt 0 ParBk1-df>>>>cnt 0 PARTIAL COUNTERS NVA100X_menuread3.ai 46G Counters >> ParStI2AL>cnt 0 ParTrI2AL>cnt 0 ParBk1I2AL>cnt 0 ParStI2>>cnt 0 ParTrI2>>cnt 0 ParBk1I2>>cnt 0 TotStI-I/U>cnt 0 TotTrI-I/U>cnt 0 TotBk1I-I/U>cnt 0 TotBk2I-I/U>cnt 0 TotStI-I/U>>cnt 0 TotTrI-I/U>>cnt 0 TotBk1I-I/U>>cnt 0 TotBk2I-I/U>>cnt 0 ParSt40ALcnt 0 ParTr40ALcnt 0 ParBk140ALcnt 0 ParStXC1XD1cnt 0 ParTrXC1XD1cnt 0 ParBk1XC1XD1cnt 0 ParStXC2XD1cnt 0 ParTrXC2XD1cnt 0 ParBk1XC2XD2cnt 0 TotStI-I/U>cnt 0 TotTrI-I/U>cnt 0 TotBk1I-I/U>cnt 0 TotBk2I-I/U>cnt 0 TotStI-I/U>>cnt 0 TotTrI-I/U>>cnt 0 TotBk1I-I/U>>cnt 0 TotBk2I-I/U>>cnt 0

NVA100X - Getting started - 01 - 2018

TOTAL COUNTERS NVA100X_menuread4.ai TotStUcnt 0 TotTrI>cnt 0 TotBk1I>cnt 0 TotBk2I>cnt 0 TotStI>>cnt 0 TotTrI>>cnt 0 TotBk1I>>cnt 0 TotBk2I>>cnt 0 TotStI>>>cnt 0 TotTrI>>>cnt 0 TotBk1I>>>cnt 0 TotBk2I>>>cnt 0 TotSt-P1>cnt 0 TotTr-P1>cnt 0 TotBk1-P1>cnt 0 TotSt-P2>cnt 0 TotRt-P2>cnt 0 TotBk1-P2>cnt 0 TotSt-P1cnt 0 TotTr-Q1>cnt 0 TotBk1-Q1>cnt 0 TotSt-Q2>cnt 0 TotRt-Q2>cnt 0 TotBk1-Q2>cnt 0 TotStU1cnt 0 TotTr(U/f)>cnt 0 TotBk1(U/f)>cnt 0 TotSt(U/f)>>cnt 0 TotTr(U/f)>>cnt 0 TotBk1(U/f)>>cnt 0 79 Counters >> 24 Counters >> TotRR79cnt 0 TotSR79cnt 0 TotDR79cnt 0 TotFR79Pcnt 0 TotFR79Ecnt 0 25 Counters >> 27 Counters >> 32P Counters >> 32Q Counters >> 27V1 Counters >> TotTr-47cnt 0 TotBk1-47cnt 0 47 Counters >> TotStI> 37P Counters >> 37Q Counters >> TotTr25cnt 0 TotStUE>cnt 0 TotTrUE>cnt 0 TotBk1UE>cnt 0 TotStUE>>cnt 0 TotRtUE>>cnt 0 TotBk1UE>>cnt 0 49MG Counters >> 55 Counters >> 67 Counters >> 67N Counters >> 81O Counters >> 81U Counters >> CB Counters >> 74TCS Counters >> 74VT Counters >> 74CT Counters >> BF Counters >> 50/51 Counters >> TotStU>cnt 0 TotTrU>cnt 0 TotBk1U>cnt 0 TotStU>>cnt 0 TotRtU>>cnt 0 TotBk1U>>cnt 0 59 Counters >> 59N Counters >> 50N/51N Counters >> 51V Counters >> 40 Counters >> 49LT Counters >> TotAlDthAL1cnt 0 TotBk1DthAL1cnt 0 TotBk2DthAL1cnt 0 TotAlDthAL2cnt 0 TotBk1DthAL2cnt 0 TotBk2DthAL2cnt 0 TotTrDth>cnt 0 TotBk1Dth>cnt 0 TotBk2Dth>cnt 0 46M Counters >> TotAlDthAL1cnt 0 TotBk1DthAL1cnt 0 TotBk2DthAL1cnt 0 TotAlDthAL2cnt 0 TotBk1DthAL2cnt 0 TotBk2DthAL2cnt 0 TotTrDth>cnt 0 TotBk1Dth>cnt 0 TotBk2Dth>cnt 0 50N(C)/51N(C Counters >> TotStIPD>cnt 0 TotTrIPD>cnt 0 TotBk1IPD>cnt 0 TotBk2IPD>cnt 0 TotStIPD>>cnt 0 TotTrIPD>>cnt 0 TotBk1IPD>>cnt 0 TotBk2IPD>>cnt 0 TotStIPD>>>cnt 0 TotTrIPD>>>cnt 0 TotBk1IPD>>>cnt 0 TotBk2IPD>>>cnt 0 TotStIPD>>>>cnt 0 TotTrIPD>>>>cnt 0 TotBk1IPD>>>>cnt 0 TotBk2IPD>>>>cnt 0 TotStIED>cnt 0 TotTrIED>cnt 0 TotBk1IED>cnt 0 TotBk2IED>cnt 0 TotStIED>>cnt 0 TotTrIED>>cnt 0 TotBk1IED>>cnt 0 TotBk2IED>>cnt 0 TotStIED>>>cnt 0 TotTrIED>>>cnt 0 TotBk1IED>>>cnt 0 TotBk2IED>>>cnt 0 TotStIED>>>>cnt 0 TotTrIED>>>>cnt 0 TotBk1IED>>>>cnt 0 TotBk2IED>>>>cnt 0 TotBk1-74CTcnt 0 TotTr74CTcnt 0 TotStBFcnt 0 TotTrTrcnt 0 TotBk1BFcnt 0 2ndh-REST Counters >> TotStI2ndh>cnt 0 N.OpenCBcnt 0 TotBk1-74VTcnt 0 TotTr74VTcnt 0 TotBk1-74TCScnt 0 TotTr74TCScnt 0 I2/I1 Counters >> TotStI21>cnt 0 TotTrI21>cnt 0 TotBk121>cnt 0 46LT Counters >> TotStI2>cnt 0 TotTrI2>cnt 0 TotBk1I2>cnt 0 TotBk2I2>cnt 0 TotStI2>>cnt 0 TotTrI2>>cnt 0 TotBk1I2>>cnt 0 TotBk2I2>>cnt 0 TotStIE>cnt 0 TotTrIE>cnt 0 TotBk1IE>cnt 0 TotBk2IE>cnt 0 TotStIE>>cnt 0 TotTrIE>>cnt 0 TotBk1IE>>cnt 0 TotBk2IE>>cnt 0 TotStIE>>>cnt 0 TotTrIE>>>cnt 0 TotBk1IE>>>cnt 0 TotBk2IE>>>cnt 0 TotStIEC>cnt 0 TotTrIEC>cnt 0 TotBk1IEC>cnt 0 TotBk2IEC>cnt 0 TotStIEC>>cnt 0 TotTrIEC>>cnt 0 TotBk1IEC>>cnt 0 TotBk2IEC>>cnt 0 TotStIEC>>>cnt 0 TotTrIEC>>>cnt 0 TotBk1IEC>>>cnt 0 TotBk2IEC>>>cnt 0 59V2 Counters >> TotStU2>cnt 0 TotTrU2>cnt 0 TotBk1U2>cnt 0 55 Counters >> TotStCPhi> TotTr66cnt 0 TotBk1-66cnt 0 TotSt-f>cnt 0 TotTr-f>cnt 0 TotBk1-f>cnt 0 TotSt-f>>cnt 0 TotTr-f>>cnt 0 TotBk1-f>>cnt 0 VECTOR JUMP Counters >> TotSt-dpi>cnt 0 TotTr-dpi>cnt 0 TotBk1-dpi>cnt 0 TotSt-f> TotSt-df>cnt 0 TotTr-df>cnt 0 TotBk1-df>cnt 0 TotSt-df>>cnt 0 TotTr-df>>cnt 0 TotBk1-df>>cnt 0 TotSt-df>>>cnt 0 TotTr-df>>>cnt 0 TotBk1-df>>>cnt 0 TotSt-df>>>>cnt 0 TotTr-df>>>>cnt 0 TotBk1-df>>>>cnt 0 46G Counters >> TotStI2AL>cnt 0 TotTrI2AL>cnt 0 TotBk1I2AL>cnt 0 TotStI2>>cnt 0 TotTrI2>>cnt 0 TotBk1I2>>cnt 0 TotStI-I/U>cnt 0 TotTrI-I/U>cnt 0 TotBk1I-I/U>cnt 0 TotBk2I-I/U>cnt 0 TotStI-I/U>>cnt 0 TotTrI-I/U>>cnt 0 TotBk1I-I/U>>cnt 0 TotBk2I-I/U>>cnt 0 TotSt40ALcnt 0 TotTr40ALcnt 0 TotBk140ALcnt 0 TotStXC1XD1cnt 0 TotTrXC1XD1cnt 0 TotBk1XC1XD1cnt 0 TotStXC2XD1cnt 0 TotTrXC2XD1cnt 0 TotBk1XC2XD2cnt 0 TotStI-I/U>cnt 0 TotTrI-I/U>cnt 0 TotBk1I-I/U>cnt 0 TotBk2I-I/U>cnt 0 TotStI-I/U>>cnt 0 TotTrI-I/U>>cnt 0 TotBk1I-I/U>>cnt 0 TotBk2I-I/U>>cnt 0

NVA100X - Getting started - 01 - 2018

PILOT WIRE DIAGNOSTIC >> BreakedBLIN1 OFF ShortedBLIN1 OFF INTERNAL SELECTIVE BLOCK BLOCK4 >> ST-IPh-BLK4 OFF ST-IE-BLK4 OFF BLK4OUT OFF BLOCK2IN-IPh OFF BLOCK2IN-IE OFF tB timeout OFF ST-IPh-BLK2 OFF ST-IE-BLK2 OFF BLK2OUT-IPh OFF BLK2OUT-IE OFF BLK2OUT-IPh/IE OFF SELECTIVE BLOCK BLOCK2 >> BLOCK2 INPUT >> BLOCK2 OUTPUT >> Fault 0 Cause: No faults Operating phase: - Date: Time: IL1r: 0.000 In IL2r: 0.000 In IL3r: 0.000 In UL1r: 0.000 En UL2r: 0.000 En UL3r: 0.000 En U12r: 0.000 Un U23r: 0.000 Un U31r: 0.000 Un IEr: 0.000 IEn IECr: 0.000 In UEr: 0.000 UEn UECr: 0.000 UECn PhiL1r: 0 deg PhiL2r: 0 deg PhiL3r: 0 deg Alpha1r: 0 deg Alpha2r: 0 deg Alpha3r: 0 deg PhiEr: 0 deg PhiECr: 0 deg DTheta-r: DthetaB U1r: 0.000 En U2r: 0.000 En U/fr: 0.000 Un/fn Pr: 0.000 Pn Qr: 0.000 Qn CosPhir: 0.000 fr: 0.000 fn dfr: 0.000 Hz/s dphir: 0 deg Binary Inputs IN1-16...IN1-1 0000000000000000 Binary Inputs IN2-16...IN2-1 0000000000000000 Relays KC1-8...KC1-1 00000000 Relays KC2-8...KC2-1 00000000 Fault x Cause: No faults Operating phase: - Date: Time: IL1r: 0.000 In IL2r: 0.000 In IL3r: 0.000 In UL1r: 0.000 En UL2r: 0.000 En UL3r: 0.000 En U12r: 0.000 Un U23r: 0.000 Un U31r: 0.000 Un IEr: 0.000 IEn IECr: 0.000 In UEr: 0.000 UEn UECr: 0.000 UECn PhiL1r: 0 deg PhiL2r: 0 deg PhiL3r: 0 deg Alpha1r: 0 deg Alpha2r: 0 deg Alpha3r: 0 deg PhiEr: 0 deg PhiECr: 0 deg DTheta-r: DthetaB U1r: 0.000 En U2r: 0.000 En U/fr: 0.000 Un/fn Pr: 0.000 Pn Qr: 0.000 Qn CosPhir: 0.000 fr: 0.000 fn dfr: 0.000 Hz/s dphir: 0 deg Binary Inputs IN1-16...IN1-1 0000000000000000 Binary Inputs IN2-16...IN2-1 0000000000000000 Relays KC1-8...KC1-1 00000000 Relays KC2-8...KC2-1 00000000 FAULTS RECORDING >> Fault 0 (last) >> Fault 1 >> Fault .... >> Fault 299 >> EVENTS RECORDING >> Event 0 (last): Power up 21/06/2013 06:50:58:413 Event 1: Power down 20/06/2013 14:23:38:000 Event 2: Settings 19/06/2013 06:48:27:584 Event 3: KC1-2 off 19/06/2013 06:28:52:168 Event 4: KC1-2 on 19/06/2013 06:28:35:711 Event x: Power up xx/xx/xxx xx:xx:xx:xxx PROCEED SET MENU’ PREVIOUS READ MENU’ NVA100X_menuread5.ai

NVA100X - Getting started - 01 - 2018

SET NVA100X_menuset1.ai PROCEED SET MENU’ BASE >> PROCEED PROFILE A MENU’ (U/f)> Enable OFF Type Characteristic (U/f)>Curve DEFINITE t(U/f)>RES 0.1 s (U/f)>def OFF 1 Un/fn t(U/f)>def 1 s (U/f)>inv OFF 1 Un/fn t(U/f)>inv 5 s (U/f)>BLK1 OFF (U/f)>BF OFF (U/f)AL... disby(U/f)> OFF Relays (U/f)> (U/f)>ST-K - (U/f)>TR-K - LEDs (U/f)> (U/f)>ST-L - (U/f)>TR-L - (U/f)>> Enable OFF (U/f)>>def OFF 1 Un/fn t(U/f)>>def 1 s t(U/f)>inv 5 s (U/f)>>BLK1 OFF (U/f)>>BF OFF (U/f)AL... disby(U/f)>> OFF (U/f)>... disby(U/f)>> OFF Relays (U/f)>> (U/f)>>ST-K - (U/f)>>TR-K - LEDs (U/f)>> (U/f)>>ST-L - (U/f)>>TR-L - Plant .................. Reading RELATIVE IE Selected IE Measure UE or UL4 UE Phase correction UL1-UL4 0 deg In 5 A Inp 100 A IEn 1 A IEnp 100 A Un 100 V Unp 20000 V UEn 100 V UEnp 20000 V fn 50 Hz LANGUAGE English AUTO-RECLOSE 79 >> 79 Enable OFF 79 Mode Rapid+Slow N.DAR 3 trdt 0.3 s tsdt 30 s tr 180 s td1 5 s td2 5 s MC-td-EN OFF td 5 s MO-RES ON Phase trip 79-I> OFF 79-I>> OFF 79-I>>> OFF 79-IPD> OFF 79-IPD>> OFF 79-IPD>>> OFF 79-IPD>>>> OFF Earth trip 79-IE> OFF 79-IE>> OFF 79-IE>>> OFF 79-IED> OFF 79-IED>> OFF 79-IED>>> OFF 79-IED>>>> OFF External trip 79-Ext OFF Relays 79 79-Run-K - 79-AR-K - 79-Fail-K - 79-EnableState-K - LEDs 79 79-Run-L - 79-AR-L - 79-Fail-L - 79-EnableState-L - INPUT SEQUENCE >> I-Sequence IL1-IL2-IL3 Def. V-Sequence UL1-UL2-UL3 Def. SELF-TEST RELAY >> Minor failure alarm NO Self-test relay - PROFILE A >> PROFILE SELECTION >> Active Profile A MMI >> Param. setting enable ON Modules data visualization ASSIGNED MODULES POLARITY >> A1-A2 NORMAL A3-A4 NORMAL A5-A6 NORMAL A7-A8 NORMAL B3-B4 NORMAL B5-B6 NORMAL B7-B8 NORMAL B9-B10 NORMAL LINE >> R1L 0.05 mZNf/km X1L 0.05 mZNf/km R0L 0.05 mZNf/km X0L 0.05 mZNf/km L 10 km Logic Active-ON ON Delay IN1-1 tON 0 s OFF Delay IN1-1 tOFF 0 s IN1-1 matching None Logic Active-ON ON Delay IN1-x tON 0 s OFF Delay IN1-x tOFF 0 s IN1-2 matching None Logic Active-ON ON Delay IN1-2 tON 0 s OFF Delay IN1-2 tOFF 0 s IN1-2 matching None ENABLE VECTOR JUMP >> Endphi ON 0.2 En tEndphi 0.5 s INPUTS IN1-1...IN1-16 >> Binary input IN1-1 Setpoints >> Binary input IN1-2 Setpoints >> Binary input IN1-x Setpoints >> Logic ENERGIZED OPERATION MODE LATCHED Minimum pulse width KC1-1 tTR 150 ms Logic ENERGIZED OPERATION MODE LATCHED Minimum pulse width KC1-2 tTR 150 ms Logic ENERGIZED OPERATION MODE LATCHED Minimum pulse width KCx-x tTR 150 ms RELAYS KC1-1...KC1-8 >> IB >> IB 1 In 24 >> (U/f)> Element >> (U/f)AL Element >> (U/f)>> Element >> (U/f)AL Enable OFF (U/f)ALdef OFF 1 Un/fn t(U/f)ALdef 1 s (U/f)ALBLK1 OFF Relays(U/f)AL (U/f)ALST-K - (U/f)ALTR-K - LEDs(U/f)AL (U/f)ALST-L - (U/f)ALTR-L - 25 >> Common >> 25 Enable OFF 25 Logic 0-V1 and V4 Live tSTAB 0.1 s tCB_CLOSE 0.02 s timeout-SYNC 10 min tSYNC 0.1 s Vmax-SYNC 0.8 En Vmin-SYNC 0.3 En fRANGE 1 Hz Rof>SYNC 0 Hz U< Enable OFF Type Characteristic USYNC 0 Hz U<> 27 >> Common >> U< Element >> U<< Element >> df-NET 0.02 Hz df14-SYNC 0.05 Hz df41-SYNC 0.05 Hz dv14-SYNC 0.05 Un dv41-SYNC 0.05 Un dp14-SYNC 3 deg dp41-SYNC 3 deg V1>SYNC ON 0.5 En tV1>SYNC 1 s V4>SYNC ON 0.5 En tV4>SYNC 1 s V1> KC1-2 relay Setpoints >> KC1-x relay Setpoints >> LEDS ON MMI >> Start LED logic NO LATCHED Trip LED logic NO LATCHED LED 1 logic NO LATCHED LED 2 logic NO LATCHED LED 3 logic NO LATCHED LED 4 logic NO LATCHED LED 5 logic NO LATCHED LEDS LED1-1...LED1-8 >> LED1-1 logic NO LATCHED LED1-2 logic NO LATCHED LED1-3 logic NO LATCHED LED1-4 logic NO LATCHED LED1-x logic NO LATCHED LED1-8 logic NO LATCHED

NVA100X - Getting started - 01 - 2018

SET NVA100X_menuset2.ai PROCEED SET MENU’ PROFILE A PROCEED PROFILE A MENU’ FROM PROFILE A MENU’ 27V1 U1DIR P Forward P1>RES 0.00 s P1>def enable OFF P1>def 0.50 Pn tP1>def 1.00 s P1>BLK1 OFF P1>BF OFF Relays P1> P1>ST-K - P1>TR-K - LEDs P1> P1>ST-L - P1>TR-L - P2>DIR P Forward P2>RES 0.00 s P2>def enable OFF P2>def 0.50 Pn tP2>def 1.00 s P2>BLK1 OFF P2>BF OFF Relays P2> P2>ST-K - P2>TR-K - LEDs P2> P2>ST-L - P2>TR-L - 27V1 >> U1< Element >> 32P >> P1> Element >> P2> Element >> Q1>DIR Q Forward Q1>RES 0.00 s Q1>def enable OFF Q1>def 0.50 Qn tQ1>def 1.00 s Q1>BLK1 OFF Q1>BF OFF Relays Q1> Q1>ST-K - Q1>TR-K - LEDs Q1> Q1>ST-L - Q1>TR-L - Q2>DIR Q Forward Q2>RES 0.00 s Q2>def enable OFF Q2>def 0.50 Qn tQ2>def 1.00 s Q2>BLK1 OFF Q2>BF OFF Relays Q2> Q2>ST-K - Q2>TR-K - LEDs Q2> Q2>ST-L - Q2>TR-L - 32Q >> Q1> Element >> Q2> Element >> Logic37 OR I> I< Element >> P1> CB-37P Enable OFF tARM-P< 1.00 s Common >> P1< Element >> P2< Element >> Q1> Common >> Q1< Element >> Q2< Element >> 40AL Enable OFF Alpha40AL 45 gr. t40AL 1.00 s 40ALBLK1 OFF Relays 40AL 40ALST-K - 40ALTR-K - LEDs 40AL 40ALST-L - 40ALTR-L - XC1XD1 Enable OFF XC1 1.00 Znf XD1 1.00 Znf tXC1XD1 1.00 s tXC1XD1-RES 0.0 s XC1XD1-BLK1 OFF 40ALdisbyXC1XD1 OFF XC1XD1-BF OFF Relays XC1XD1 XC1XD1ST-K - XC1XD1TR-K - LEDs XC1XD1 XC1XD1ST-L - XC1XD1TR-L - XC1XD1 Enable OFF XC1 1.00 Znf XD1 1.00 Znf tXC1XD1 1.00 s tXC1XD1-RES 0.0 s XC1XD1-BLK1 OFF 40ALdisbyXC1XD1 OFF XC1XD1-BF OFF Relays XC1XD1 XC1XD1ST-K - XC1XD1TR-K - LEDs XC1XD1 XC1XD1ST-L - XC1XD1TR-L - Mode 40 Generator USUP< Enable OFF USUP< 0.50 Un 40 >> Common >> 40AL Element >> XC1XD1 Element >> XC2XD2 Element >> 46LT >> I2> Element >> Q2< Element >> 46M >> I2> Element >> I2> Element >> I2>> Enable OFF I2CLP> Mode OFF t2CLP>> 0.1 s t2>>RES 0 s I2>>def OFF 1 In I2CLP>>def 2 In t2>>def 1 s I2>>BLK1 OFF I2>>BLK2IN OFF I2>>BLK2OUT OFF I2>>2ndh-REST OFF I2>>BF OFF I2>disbyI2>> OFF Relays I2>> I2>>ST-K - I2>>TR-K - LEDs I2>> I2>>ST-L - I2>>TR-L - I2> Enable OFF Type Characteristic I2Curve DEFINITE I2CLP> Mode OFF t2CLP> 0.1 s t2>RES 0 s I2>def OFF 1 In t2>def 1 s I2>inv OFF 2 In t2>inv 10 s I2>BLK1 OFF I2>BLK2IN OFF I2>BLK2OUT OFF I2>2ndh-REST OFF I2>BF OFF Relays I2> I2>ST-K - I2>TR-K - LEDs I2> I2>ST-L - I2>TR-L - (the same as for 46LT)

NVA100X - Getting started - 01 - 2018

NVA100X_menuset3.ai PREVIOUS SET MENU’ PREVIOUS PROFILE A MENU’ PROCEED SET MENU’ I21CLP> Mode OFF t21CLP> 0.1 s I21>def OFF 0.5 I21CLP>def 1 t21>def 1 s I21>BLK1 OFF I21>2ndh-REST OFF Relays I21> I21>ST-K - I21>TR-K - LEDs I21> I21>ST-L - I21>TR-L - 46G >> I2AL> Element >> I2>> Element >> I2/I1 >> I21> Element >> 47 >> 47 Element >> I2>> Enable OFF I2>>inv 0.50 IB Kheat 1.0 s Kcool 1.0 s T2MIN 1.00 s T2MAX 500 s I2>>BLK1 OFF I2AL>disbyI2>> OFF I2>>BF OFF I2>disbyI2>> OFF Relays I2>> I2>>ST-K - I2>>TR-K - LEDs I2>> I2>>ST-L - I2>>TR-L - 47 Enable OFF Us1< Enable OFF Us1< 0.20 En Us> Enable ON Us> 0.80 En 47BLK1 OFF Relays 47 47TR-K - LEDs 47 47TR-L - I2AL> Enable OFF I2AL>def 0.10 IB tI2AL>def 1.00 s I2AL>BLK1 OFF Relays I2AL> I2AL>ST-K - I2Al>TR-K - LEDs I2AL> I2AL>ST-L - I2AL>TR-L - SET PROFILE A PROCEED PROFILE A MENU’ 49LT >> Common >> DthIN 0 DThetaB KINR 2 T 10 min Dth2ndh-REST OFF DthCLP Mode OFF tDthCLP 0.1 s DthAL1 Element >> DthAL1 Enable OFF DthAL1 0.5 DThetaB DthAL1BLK1 OFF DthAL1BLK2IN OFF DthAL1BLK2OUT OFF DthAL1BLK4 OFF Relays DthAL1 DthAL1-K - LEDs DthAL1 DthAL1-L - DthAL2 Enable OFF DthAL2 1 DThetaB DthAL2BLK1 OFF DthAL2BLK2IN OFF DthAL2BLK2OUT OFF DthAL2BLK4 OFF Relays DthAL2 DthAL2-K - LEDs DthAL2 DthAL2-L - DthAL2 Element >> Dth> Enable OFF Dth> 1.2 DThetaB Dth>BLK1 OFF Dth>BLK2IN OFF Dth>BLK2OUT OFF Dth>BLK4 OFF Dth>BF OFF Dth>disby50-51 OFF Relays Dth> Dth>-K - LEDs Dth> Dth>-L - Dth> Element >> 49MG >> Common >> DthIN 0.0 DThetaB KST 2.0 K2 0 T+ 10 min T- 1.0 T- DthCLP Mode OFF tDthCLP 0.10 s DthAL1 Element >> DthAL1 Enable OFF DthAL1 0.5 DThetaB DthAL1BLK1 OFF DthAL1BLK2IN OFF DthAL1BLK2OUT OFF Relays DthAL1 DthAL1-K - LEDs DthAL1 DthAL1-L - DthAL2 Enable OFF DthAL2 1.0 DThetaB DthAL2BLK1 OFF DthAL2BLK2IN OFF DthAL2BLK2OUT OFF Relays DthAL2 DthAL2-K - LEDs DthAL2 DthAL2-L - DthAL2 Element >> Dth> Enable OFF Dth> 1.2 DThetaB Dth>BLK1 OFF Dth>BLK2IN OFF Dth>BLK2OUT OFF Dth>BF OFF Dth>disby50-51 OFF Relays Dth> Dth>-K - LEDs Dth> Dth>-L - Dth> Element >> 50/51 >> I> Element >> I>> Enable OFF Type Characteristic: I>>Curve DEFINITE ICLP>> Mode OFF tCLP>> 0.1 s t>>RES 0 s I>>def OFF 1 In ICLP>>def 2 In t>>def 1 s I>>inv OFF 1 In ICLP>inv 2 In t>>inv 5 s I>>BLK1 OFF I>>BLK2IN OFF I>>BLK2OUT OFF I>>BLK4 OFF I>>2ndh-REST OFF I>>BF OFF I>disbyI>> OFF Relays I>> I>>ST-K - I>>TR-K - LEDs I>> I>>ST-L - I>>TR-L - I> Enable OFF Type Characteristic: I>Curve DEFINITE ICLP> Mode OFF tCLP> 0.1 s t>RES 0 s I>def OFF 1 In ICLP>def 2 In t>def 1 s I>inv OFF 1 In ICLP>inv 2 In t>inv 10 s I>BLK1 OFF I>BLK2IN OFF I>BLK2OUT OFF I>BLK4 OFF I>2ndh-REST OFF I>BF OFF Relays I> I>ST-K - I>TR-K - LEDs I> I>ST-L - I>TR-L - I>>> Enable OFF ST-I>>>&ST-U<< OFF ICLP>>> Mode OFF tCLP>>> 0.1 s t>>>RES 0 s I>>>def OFF 1 In ICLP>>>def 2 In t>>>def 1 s I>>>BLK1 OFF I>>>BLK2IN OFF I>>>BLK2OUT OFF I>>>BLK4 OFF I>>>2ndh-REST OFF I>>>BF OFF I>disbyI>>> OFF I>>disbyI>>> OFF Relays I>>> I>>>ST-K - I>>>TR-K - LEDs I>>> I>>>ST-L - I>>>TR-L - I>> Element >> I>>> Element >>

NVA100X - Getting started - 01 - 2018

NVA100X_menuset3a.ai PREVIOUS SET MENU’ PREVIOUS PROFILE A MENU’ PROCEED SET MENU’ SET PROFILE A PROCEED PROFILE A MENU’ 50N/51N-87NHIZ >> 50N(C)/51N(C) >> IE> Element >> IE>> Enable OFF Type IECLP>> Mode OFF tECLP>> 0.1 s tE>>RES 0 s IE>>def OFF 1 In IECLP>>def 2 In tE>>def 1 s IE>>BLK1 OFF IE>>BLK2IN OFF IE>>BLK2OUT OFF IE>>BLK4 OFF IE>>2ndh-REST OFF IE>>BF OFF IE>disbyIE>> OFF Relays IE>> IE>>ST-K - IE>>TR-K - LEDs IE>> IE>>ST-L - IE>>TR-L - IE> Enable OFF Type Characteristic: IE>Curve DEFINITE IECLP> Mode OFF tECLP> 0.1 s tE>RES 0 s IE>def OFF 1 IEn IECLP>def 2 IEn tE>def 1 s IE>inv OFF 1 In IECLP>inv 2 In tE>inv 10 s IE>BLK1 OFF IE>BLK2IN OFF IE>BLK2OUT OFF IE>BLK4 OFF IE>2ndh-REST OFF IE>BF OFF Relays IE> IE>ST-K - IE>TR-K - LEDs IE> IE>ST-L - IE>TR-L - IE>>> Enable OFF IECLP>>> Mode OFF tECLP>>> 0.1 s tE>>>RES 0 s IE>>>def OFF 1 In IECLP>>>def 2 In tE>>>def 1 s IE>>>BLK1 OFF IE>>>BLK2IN OFF IE>>>BLK2OUT OFF IE>>>BLK4 OFF IE>>>2ndh-REST OFF IE>>>BF OFF IE>disbyIE>>> OFF IE>>disbyIE>>> OFF Relays IE>>> IE>>>ST-K - IE>>>TR-K - LEDs IE>>> IE>>>ST-L - IE>>>TR-L - IE>> Element >> IE>>> Element >> IEC> Element >> IEC>> Enable OFF Type IECCLP>> Mode OFF tECCLP>> 0.1 s tEC>>RES 0 s IEC>>def OFF 1 In IECCLP>>def 2 In tEC>>def 1 s IEC>>BLK1 OFF IEC>>BLK2IN OFF IEC>>BLK2OUT OFF IEC>>BLK4 OFF IEC>>2ndh-REST OFF IEC>>BF OFF IEC>disbyIEC>> OFF Relays IEC>> IEC>>ST-K - IEC>>TR-K - LEDs IEC>> IEC>>ST-L - IEC>>TR-L - ILR> Enable OFF Mode51LR> No speed crt1 ILR>inv 0.8 IB I-MOT-ST 1 IB tLR>inv 10 s ILR>BLK1 OFF ILR>BLK2IN OFF ILR>BLK2OUT OFF ILR>BF OFF Relays ILR> ILR>ST-K - ILR>TR-K - LEDs ILR> ILR>ST-L - ILR>TR-L - ILR>> Enable OFF Mode51LR>> No speed crt1 tLRCLP>> 0.10 s ILR>>def 1.00 IB tLR>>def 1.00 s ILR>BLK1 OFF ILR>>BLK2IN OFF ILR>>BLK2OUT OFF ILR>>BF OFF Relays ILR>> ILR>>ST-K - ILR>>TR-K - LEDs ILR>> ILR>>ST-L - ILR>>TR-L - t-I/U>RES 0 s I-I/U>def enable OFF I-I/U>def 1.00 In t-I/U>def 1.00 s I-I/U>BLK1 OFF I-I/U>BLK2IN OFF I-I/U>BLK2OUT OFF I-I/U>BF OFF Relays I-I/U> I-I/U>ST-K - I-I/U>TR-K - LEDs I-I/U> I-I/U>ST-L - I-I/U>TR-L - t-I/U>>RES 0 s I-I/U>>def enable OFF I-I/U>>def 1.00 In t-I/U>>def 1.00 s I-I/U>>BLK1 OFF I-I/U>>BLK2IN OFF I-I/U>>BLK2OUT OFF I-I/U>BF OFF I-I/U>disbyI-I/U>> OFF Relays I-I/U>> I-I/U>>ST-K - I-I/U>>TR-K - LEDs I-I/U>> I-I/U>>ST-L - I-I/U>>TR-L - IEC> Enable OFF Type Characteristic: IEC>Curve DEFINITE IECCLP> Mode OFF tECCLP> 0.1 s tEC>RES 0 s IEC>def OFF 1 IEn IECCLP>def 2 IEn tEC>def 1 s IEC>inv OFF 1 In IECCLP>inv 2 In tEC>inv 10 s IEC>BLK1 OFF IEC>BLK2IN OFF IEC>BLK2OUT OFF IEC>BLK4 OFF IEC>2ndh-REST OFF IEC>BF OFF Relays IEC> IEC>ST-K - IEC>TR-K - LEDs IEC> IEC>ST-L - IEC>TR-L - IEC>>> Enable OFF IECCLP>>> Mode OFF tECCLP>>> 0.1 s tEC>>>RES 0 s IEC>>>def OFF 1 In IECCLP>>>def 2 In tEC>>>def 1 s IEC>>>BLK1 OFF IEC>>>BLK2IN OFF IEC>>>BLK2OUT OFF IEC>>>BLK4 OFF IEC>>>2ndh-REST OFF IEC>>>BF OFF IEC>disbyIE>>> OFF IEC>>disbyIE>>> OFF Relays IEC>>> IEC>>>ST-K - IEC>>>TR-K - LEDs IEC>>> IEC>>>ST-L - IEC>>>TR-L - IEC>> Element >> 51LR(48)/14 >> ILR> Element >> ILR>> Element >> IEC>>> Element >> Mode51V Voltage controlled U-I/U-1 0.8 Un U-I/U-2 0.5 Un K 1 51V >> Common >> I-I/U> Element >> I-I/U> Element >>

NVA100X - Getting started - 01 - 2018

NVA100X_menuset4.ai PREVIOUS SET MENU’ PREVIOUS PROFILE A MENU’ PROCEED SET MENU’ SET PROFILE A PROCEED PROFILE A MENU’ 55 >> Common >> CPhi1< DIR CosPhi Lag CPhi1> CPh2< Element >> 59N >> Common >> U> Enable OFF Type Characteristic UE>Curve DEFINITE tUE>RES 0 s UE>def OFF 0.1 UEn tUE>def 1 s UE>inv OFF 0.1 UEn tUE>inv 10 s UE>BLK1 OFF UE>BF OFF Relays UE> UE>ST-K - UE>TR-K - LEDs UE> UE>ST-L - UE>TR-L - tUE>>RES 0 s UE>>def OFF 0.1 UEn tUE>>def 1 s UE>>BLK1 OFF U>>BF OFF UE>disbyUE>> OFF Relays UE>> UE>>ST-K - UE>>TR-K - LEDs UE>> UE>>ST-L - UE>>TR-L - 3VoType59N UE 74VTint59N OFF 74VText59N OFF Common >> Mode67 I Logic67 1/3 74VTint67 OFF 74VText67 OFF UE> Element >> U>> Element >> 59V2 >> U2>def OFF 0.1 En tU2>def 1 s U2>BLK1 OFF U2>BF OFF Relays U2> U2>ST-K - U2>TR-K - LEDs U2> U2>ST-L - U2>TR-L - U2> Element >> 66 >> 66 Enable OFF Type66 NST tC 1 min NST 10 TST 30 s TIN 0 min 66BLK1 OFF Relays 66 66-TR-K - LEDs 66 66-TR-L - 59 >> Common >> U> Enable OFF Type Characteristic U>Curve DEFINITE U>def enable OFF U>def 1 Un tU>def 1 s U>inv enable OFF U>inv 1 Un tU>inv 10 s U>BLK1 OFF U>BF OFF Relays U> U>ST-K - U>TR-K - LEDs U> U>ST-L - U>TR-L - U>>def Enable OFF U>>def 1 Un tU>>def 1 s U>>BLK1 OFF U>disbyU>> OFF U>>BF OFF Relays U>> U>>ST-K - U>>TR-K - LEDs U>> U>>ST-L - U>>TR-L - Utype59 Uph-ph Logic59 OR U> Element >> U>> Element >> 67 >> IPD> Element >> IPD> Enable OFF Type Characteristic: IPD>Curve DEFINITE IPDCLP> Mode OFF tPDCLP> 0.1 s tPD>RES 0 s IPD>def OFF 1 In ThetaP>def 0 gr IPDCLP>def 1.5 In tPD>def 1 s IPD>inv OFF 1 In ThetaP>inv 0 gr IPDCLP>inv 1.5 In tPD>inv 10 s IPD>BLK1 OFF IPD>BLK2IN OFF IPD>BLK2OUT OFF IPD>BLK4 OFF IPD>2ndh-REST OFF IPD>BF OFF Relays IPD> IPD>ST-K - IPD>TR-K - LEDs IPD> IPD>ST-L - IPD>TR-L - IPD>>> Enable OFF IPDCLP>>> Mode OFF tPDCLP>>> 0.1 s tPD>>>RES 0 s IPD>>>def OFF 1 In ThetaP>>>def 0 gr IPDCLP>>>def 1.5 In tPD>>>def 1 s IPD>>>BLK1 OFF IPD>>>BLK2IN OFF IPD>>>BLK2OUT OFF IPD>>>BLK4 OFF IPD>>>2ndh-REST OFF IPD>>>BF OFF IPD>disbyIPD>>> OFF IPD>>disbyIPD>> OFF Relays IPD>>> IPD>>>ST-K - IPD>>>TR-K - LEDs IPD>>> IPD>>>ST-L - IPD>>>TR-L - IPD>>>> Enable OFF ST-IPD>>>>&STU<< OFF IPDCLP>>>> Mode OFF tPDCLP>>>> 0.1 s tPD>>>>RES 0 s IPD>>>>def OFF 1 In ThetaP>>>>def 0 gr IPDCLP>>>>def 1.5 In tPD>>>>def 1 s IPD>>>>BLK1 OFF IPD>>>>BLK2IN OFF IPD>>>>BLK2OUT OFF IPD>>>>BLK4 OFF IPD>>>>2ndh-REST OFF IPD>>>>BF OFF IPD>disbyIPD>>>> OFF IPD>>disbyIPD>>> OFF IPD>>>disbyIPD>>>> OFF Relays IPD>>>> IPD>>>>ST-K - IPD>>>>TR-K - LEDs IPD>>>> IPD>>>>ST-L - IPD>>>>TR-L - IPD>> Enable OFF Type Characteristic: IPD>>Curve DEFINITE IPDCLP>> Mode OFF tPDCLP>> 0.1 s tPD>>RES 0 s IPD>>def OFF 1 In ThetaP>>def 0 gr IPDCLP>>def 1.5 In tPD>>def 1 s IPD>>inv OFF 1 In ThetaP>>inv 0 gr IPDCLP>>inv 1.5 In tPD>>inv 5 s IPD>>BLK1 OFF IPD>>BLK2IN OFF IPD>>BLK2OUT OFF IPD>>BLK4 OFF IPD>>2ndh-REST OFF IPD>>BF OFF IPD>disbyIPD>> OFF Relays IPD>> IPD>>ST-K - IPD>>TR-K - LEDs IPD>> IPD>>ST-L - IPD>>TR-L - IPD>> Element >> IPD>>>> Element >> IPD>>> Element >>

NVA100X - Getting started - 01 - 2018

NVA100X_menuset5.ai PREVIOUS SET MENU’ PREVIOUS PROFILE A MENU’ PROCEED SET MENU’ SET PROFILE A PROCEED PROFILE A MENU’ Common >> 67N >> IED> Element >> IED> Enable OFF Type Characteristic: IED>Curve DEFINITE IEDCLP> Mode OFF tEDCLP> 0.1 s tED>RES 0 s IED>def OFF 1 IEn UED>def 0.1 UEn ThetaE>def 60 gr BetaE>def 45 gr IEDCLP>def 1.5 IEn tED>def 1 s IED>inv OFF 1 IEn UED>inv 0.1 UEn ThetaE>inv 60 gr BetaE>inv 45 gr IEDCLP>inv 1.5 IEn tED>inv 10 s IED>BLK1 OFF IED>BLK2IN OFF IED>BLK2OUT OFF IED>BLK4 OFF IED>BF OFF Relays IED> IED>ST-K - IED>TR-K - LEDs IED> IED>ST-L - IED>TR-L - IED>> Enable OFF Type Characteristic: IED>>Curve DEFINITE IEDCLP>> Mode OFF tEDCLP>> 0.1 s tED>>RES 0 s IED>>def OFF 1 IEn UED>>def 0.1 UEn ThetaE>>def 60 gr BetaE>>def 45 gr IEDCLP>>def 1.5 IEn tED>>def 1 s IED>>inv OFF 1 IEn UED>>inv 0.1 UEn ThetaE>>inv 60 gr BetaE>>inv 45 gr IEDCLP>>inv 1.5 IEn tED>>inv 10 s IED>>BLK1 OFF IED>>BLK2IN OFF IED>>BLK2OUT OFF IED>>BLK4 OFF IED>>BF OFF Relays IED>> IED>>ST-K - IED>>TR-K - LEDs IED>> IED>>ST-L - IED>>TR-L - IED>>>> Enable OFF IEDCLP>>>> Mode OFF tEDCLP>>>> 0.1 s tED>>>>RES 0 s IED>>>>def OFF 1 IEn ThetaE>>>>def 60 gr BetaE>>>>def 45 gr IEDCLP>>>>def 1 IEn tED>>>>def 1 s IED>>>>BLK1 OFF IED>>>>BLK2IN OFF IED>>>>BLK2OUT OFF IED>>>>BLK4 OFF IED>>>>BF OFF IED>disIED>>>> OFF IED>>disIED>>>> OFF IED>>>disIED>>>> OFF Relays IED>>>> IED>>>>ST-K - IED>>>>TR-K - LEDs IED>>>> IED>>>>ST-L - IED>>>>TR-L - IED>>> Enable OFF IEDCLP>>> Mode OFF tEDCLP>>> 0.1 s tED>>>RES 0 s IED>>>def OFF 1 IEn ThetaE>>>def 60 gr BetaE>>>def 45 gr IEDCLP>>>def 1 IEn tED>>>def 1 s IED>>>BLK1 OFF IED>>>BLK2IN OFF IED>>>BLK2OUT OFF IED>>>BLK4 OFF IED>>>BF OFF IED>disIED>>> OFF IED>>disIED>>> OFF Relays IED>>> IED>>>ST-K - IED>>>TR-K - LEDs IED>>> IED>>>ST-L - IED>>>TR-L - IED>> Element >> IED>> Element >> IED>>>> Element >> f>def OFF 1 fn tf>def 1 s f>BLK1 OFF f>BF OFF Relays f> f>ST-K - f>TR-K - LEDs f> f>ST-L - f>TR-L - IED>>> Element >> 81O >> f> Element >> f>>def OFF 1 fn tf>>def 1 s f>>BLK1 OFF f>>BF OFF f>disbyf>> OFF Relays f>> f>>ST-K - f>>TR-K - LEDs f>> f>>ST-L - f>>TR-L - f>> Element >> f> f< Element >> f<<< Element >> f<> f<<<< Element >> Mode67N I 3VoType67 UE Insens-Zone OFF M 1.5 74VTint67N OFF 74VText67N OFF

NVA100X - Getting started - 01 - 2018

NVA100X_menuset6.ai PREVIOUS SET MENU’ PREVIOUS PROFILE A MENU’ PROCEED SET MENU’ SET PROFILE A >> PROFILE B >> df>def OFF 1 Hz/s tdf>def 1 s Mode-df> Module df>BLK1 OFF df>BF OFF Relays df> df>ST-K - df>TR-K - LEDs df> df>ST-L - df>TR-L - df>>def OFF 1 Hz/s tdf>>def 1 s Mode-df>> Module df>>BLK1 OFF df>>BF OFF df>disbydf>> OFF Relays df>> df>>ST-K - df>>TR-K - LEDs df>> df>>ST-L - df>>TR-L - df>>>def OFF 1 Hz/s tdf>>>def 1 s Mode-df>>> Module df>>>BLK1 OFF df>>>BF OFF df>disbydf>>> OFF df>>disbydf>>> OFF Relays df>>> df>>>ST-K - df>>>TR-K - LEDs df>>> df>>>ST-L - df>>>TR-L - df>>>>def OFF 1 Hz/s tdf>>>>def 1 s Mode-df>>>> Module df>>>BLK1 OFF df>>>BF OFF df>disbydf>>>> OFF df>>disbydf>>>> OFF df>>>disbydf>>>> OFF Relays df>>>> df>>>>ST-K - df>>>>TR-K - LEDs df>>>> df>>>>ST-L - df>>>>TR-L - 81R >> df> Element >> df>>> Element >> df>> Element >> df>>>> Element >> dphi>def OFF 5 deg tdphi>RES 0 s Mode-dphi> Module dphi>BLK1 OFF dphi>BF OFF Relays dphi> dphi>ST-K - dphi>TR-K - LEDs dphi> dphi>ST-L - dphi>TR-L - VECTOR JUMP >> dphi> Element >> ModeBLIN1 OFF tB-IPh 2 s tB-IE 2 s Relays BLOCK2IN tB-K - LEDs BLOCK2IN tB-L - BLOCK2 INPUT >> ModeBLOUT1 OFF tF-IPh 1 s tF-IE 1 s tF-IPh/IE 1 s Relays BLOCK2OUT BLOCK2OUT-IPh-K - BLOCK2OUT-IE-K - BLOCK2OUT-IPh/IE-K - LEDs BLOCK2OUT BLOCK2OUT-IPh-L - BLOCK2OUT-IE-L - BLOCK2OUT-IPh/IE-L- BLOCK2 OUTPUT >> I2ndh> Enable OFF I2ndh> 10 % t2ndh>RES 0.1 s Relays I2ndh> I2ndh>ST-K - LEDs I2ndh> I2ndh>ST-L - 2ndh-REST >> 74TCS Enable OFF 74TCS-BLK1 OFF Relays 74TCS 74TCS-ST-K - 74TCS-TR-K - LEDs 74TCS 74TCS-ST-L - 74TCS-TR-L - 74TCS >> BF Enable OFF IBF> ON 0.1 In IEBF> ON 0.1 IEn tBF 1 s BF-BLK1 OFF CB Input ON Relays BF BF-ST-K - BF-TR-K - LEDs BF BF-ST-L - BF-TR-L - BF >> tFI-IPh 1 s tFI-IE 1 s BLOCK4 >> BLOCK2 >> ENABLE ON Relay K1 LEDs L1 Switch1: 0 Switch2: 0 Switch3: 0 Switch4: 0 Switchx: 0 Switch32: 0 PLC SWITCHES >> PLC Timer 1: 0 s PLC Timer 2: 0 s PLC Timer 3: 0 s PLC Timer 4: 0 s PLC Timer x: 0 s PLC Timer 24: 0 s PLC TIMERS >> PLC >> ModeN.Open OFF N.Open 10000 ModeSumI OFF SumI 5000 In ModeSumI^2t OFF tbreak 0.05 s SumI 5000 In^2s Mode-tOpen OFF Ktrig-break - tbreak> 1 s Relays N.Open-K - SumI-K - SumI^2t-K - tbreak-K - LEDs N.Open-L - SumI-L - SumI^2t-L - tbreak-L - CBopen-K - CBclose-K - CBclose-L - CBopen-L - CBdiag-K - CB Diagnostic >> LEDs-Relays allocation >> CIRCUIT BREAKER SUPERVISION >> SAME FOR PROFILE A

Sede: 20139 Milano - Piazza Mistral, 7 - Tel. +39 02 574 957 01 ra - Fax +39 02 574 037 63

Stabilimento: 35127 Padova - Z.I. Sud - Via dell’Artigianato, 48 - Tel. +39 049 894 770 1 ra - Fax +39 049 870 139 0 www.thytronic.it www.thytronic.com [email protected] NVA100X_menuset7.ai PREVIOUS SET MENU’ SET 74VT Enable OFF U2VT> ON 0.1 En I2VT> ON 0.1 In tbreak 0.05 s UVT< ON 0.1 En DIVT< ON 0.1 In IVT< ON 0.1 In 74VT-AR ON 74VT-BK-EN ON tVT-AL 1 s 74VT-BLK1 OFF Relays 74VT 74VT-BK-K - 74VT-AL-K - LEDs 74VT 74VT-BK-L - 74VT-AL-L - VT SUPERVISION 74VT >> 74CT Enable OFF S< 0.5 I* ON 0.1 I tS< 1 s S> RemTrBF OFF Relays RemTrip-K - LEDs RemTrip-L - Protocol MODBUS Address 1 9600 bauds REMOTE TRIPPING >> PulseBLOUT1 OFF PulseBLIN1 OFF Relays PulseBLIN1-K - LEDs PulseBLIN1-L - PILOTE WIRE DIAGNOSTIC >> Test state: OFF Stop test? Yes >> Start test? Yes >> Test KC1-1? Yes >> Test KC1-2? Yes >> Test KC1-3? Yes >> Test KC1-x? Yes >> Test KC1-8? Yes >> Test KC2-1? Yes >> Test KC2-2? Yes >> Test KC2-3? Yes >> Test KC2-x? Yes >> Test KC2-8? Yes >> TEST >> Periods tFIX 15 min tROL 5 min N.ROL 12 DEMAND MEASURES >> RS485 Protocol >> Ethernet Local Parameters >> Ethernet Remote Parameters >> COMMUNICATION >> FL Enable OFF FL-TRG-TR OFF FL-TRG-EXT OFF FAULT LOCATOR FL >> Local IP Address 200.1.2.206 Local Subnet Mask 255.255.255.0 Local IP Gateway 127.0.0.1 Local DHCP Enable OFF Local State RUN Remote IP Address 200.1.2.205 Remote Subnet Mask 255.255.255.0 Remote IP Gateway 200.1.2.9 Mode 1+2 Port 1 Muxed: 0 Automa START Link 1 TX: On Link 2 FX: Off Remote DHCP Enable OFF Startup Time: 5 s