Record settings &

wiring details for future reference 6 Data Brochure Control settings and sequence of operation 4 5 D 161 08/07 tekmarNet®4 Setpoint Control 161 - Data Brochure 1 of 36 © 2007 D 161 - 08/07 The Setpoint Control 161 is a single stage heat setpoint control that can operate on an On / Off differential or can operate on Pulse Width Modulation. The control includes special modes for hot tub, domestic hot water tank and radiant floor applications. Introduction • • tN4 Compatible • • On / Off Differential • • Hot Tub Operation • • DHW Tank Operation • • Floor Operation • • Exercising • • Scenes • • Temperature Sensor Input Features

D 161 - 08/07

2 of 36 Display and DIP Switches Lock / Unlock (DIP Switch #1) Use the Lock / Unlock DIP switch to lock or unlock the Access Level of the 161. • • To unlock the Access Level, set the DIP switch to the unlocked (left) position. • • To lock the Access Level, set the DIP switch to the locked (right) position. Once locked, a padlock is displayed in the lower right corner of the display and the Access Level cannot be changed. Note: The tN4 System Control’s Lock / Unlock DIP switch overrides the Lock / Unlock DIP switch on the 161. Set the tN4 System Control’s Lock / Unlock DIP switch to the Unlock position before Access Levels can be changed on the setpoint control. tN4 System Control (DIP Switch #2) A tN4 System Control is a control, not a thermostat, that the Setpoint Control 161 connects to through the tN4 bus. All tN4 compatible Outdoor Reset Modules are tN4 System Controls. Table of Contents Table of Contents .............................. 2 Display and DIP Switches ................ 2 Dip Switches ................................. 2 Access Levels ............................... 3 Display .......................................... 3 Symbol Description ........................ 4 User Interface ............................... 4 Application Overview ........................ 5 On / Off Differential ......................... 5 Pulse Width Modulation ................ 6 Display Menus ................................. 7 VIEW Menu ................................... 7 ADJUST Menu ..............................10 SCENE Menu ...............................15 SCHEDULE Menu ........................16 MISCELLANEOUS Menu .............17 Sequence of Operation ...................19 Mode 1 - On / Off Setpoint ...........19 Mode 2 - Hot Tub ..........................19 Mode 3 - DHW Tank ................... 20 Mode 4 - Floor ............................ 21 Remote Enable / Disable ................ 22 Sensor Input ................................... 23 Setting the Schedule ...................... 23 Scenes ............................................ 24 Restore Factory Defaults ................ 25 Temperature Units .......................... 25 Backlight ........................................ 25 tN4 Features .................................. 25 Error Messages .............................. 28 Cleaning the Control ...................... 34 Warranty ......................................... 36 DIP Switches 24 V ±10% 50/60 Hz 1.7 VA 24 V (ac) 2 A Power: Relays: tN4 Setpoint Control 161 One Stage Heat Feb 2006 Lot 1948 Meets Class B: Canadian ICES FCC Part 15 Cut jumper to isolate relay For product instructions see brochure Use at least 194°F (90°C) conductors / 161 / • • If the setpoint control is connected to a tN4 System Control, set the tN4 System Control DIP switch to tN4 System Control (left position). • • If the setpoint control is not connected to a tN4 System Control, set the tN4 System Control DIP switch to None (right position).

3 of 32

© 2007 D 161 - 08/07 The Access Level restricts the number of Menus, Items and Adjustments that can be accessed by the user. The Access Level setting is found in the Miscellaneous (MISC) menu. Select the appropriate access level for the people who work with the setpoint control on a regular basis. The 161 has five Access Levels: • • Advanced (ADV): access to all settings • • Installer (InST): settings required for installation • • User (USEr): for property owners • • Limited (LTD): limited temperature adjustment • • Secure (SEC): for commercial and public installations In the Limited access level, the temperature can only be adjusted by +/-3°F (1.5°C) from the temperature setting entered prior to entering the Limited access level. In the Secure access level, all settings, including the temperature, cannot be changed. For more information, see the Miscellaneous (MISC) Menu section. In the following menu tables, the access level the item is visible in is shown in the access column. To adjust the Access Level: 1. Set the Unlock / Lock DIP switch to the unlock position. If a tN4 System Control is connected to the 161, the Unlock / Lock DIP switch on the tN4 System Control must be set to the unlock position. 2. Use the Menu button to select the MISC menu. 3. Use the Item button to select the Access item. 4. Use the Up and Down button to select the required Access Level. Item Field Displays an abbreviated name of the selected item Number Field Displays the current value of the selected item Status Field Displays the current status of the control’s inputs, outputs and operation Menu Field Displays the current menu Access Levels Display

D 161 - 08/07

4 of 36 Symbol Description MODE OF OPERATION Displays whether the device is in heating or off mode. LOCK The Access Levels are locked or a menu option is visible but not adjustable. RELAY 1 Displays when relay contact 1 is closed. OCCUPIED Displays when operating at the occupied temperature. WARNING An error is present. UNOCCUPIED Displays when operating at the unoccupied setback temperature. tN4 COMMUNICATION A tN4 network is detected. TIME OCCUPIED Displays when operating temporarily at the occupied temperature due to a remote enable or manual enable. Use the User Interface available on the Liquid Crystal Display (LCD) to setup and monitor the operation of the setpoint control. Use the four push buttons below the LCD (Menu, Item, Up, Down) to select settings. As the settings are entered, record the settings in the Job Record J 161. User Interface Menu The menus display in the Menu Field at the left of the LCD. Up to 5 menus are available: • • VIEW • • ADJUST • • SCENE • • SCHD (Schedule) • • MISC (Miscellaneous) To select a menu, press and release the Menu button. Item In each menu, a group of items can be selected. The abbreviated name of the selected item displays in the Item field of the LCD display. • • To view the next available item, press and release the Item button. • • To view the previous item, hold down the Item button and press and release the Up button. Adjusting a Setting To adjust a setting: 1. Use the Menu button to select the appropriate menu. 2. Use the Item button to select a menu item. 3. Use the Up or Down button to adjust the setting.

5 of 32

© 2007 D 161 - 08/07 Continue to next Item Continue to next Menu Continue to next Item Applications: On / Off Differential Mode 1 Setpoint (On / Off) Mode 2 Hot Tub Load Default Item To set the default item in the VIEW Menu, display item for more than five seconds. After navigating menus, the display reverts back to the default item after 60 seconds of button inactivity. Application Overview The Setpoint Control 161 is designed to support four different applications. The items shown in the VIEW and ADJUST Menu change depending on the Application Mode. Set the application mode as follows: 1) Setpoint 2) Hot Tub 3) DHW Tank 4) Floor The VIEW and ADJUST menus list which of the four application items are visible based upon the mode column. The TIME, SCENE, SCHD (Schedule) and MISC (Miscellaneous) menus are the same for the four application modes.

D 161 - 08/07

6 of 36 Mode 4 Floor Relay 1 Pulse Width Modulation (PWM) Operation PWM operates by centering the throttling range around the target setpoint temperature. PWM is best suited for large heating loads that do not change rapidly in temperature such as radiant floors. Heating Operation When the temperature is at the setpoint, Relay 1 is on for 50% of a cycle and off for 50% of a cycle. When the temperature is 1/2 of the throttling range below the setpoint, Relay 1 is on for 100% of a cycle. When the temperature is 1/2 of the throttling range above the setpoint, Relay 1 is off for 100% of a cycle. For ranges within the throttling range, Relay 1’s on time increases linearly as temperature falls. The throttling range is fixed at 3°F (1.5°C). The cycle length is either the same as the tN4 system control, or when a tN4 system control is not present, the cycle length is fixed at 15 minutes. Mode 3 DHW Tank Relay 1 On / Off Differential Operation The On / Off Differential operates by centering a differential range around the target setpoint temperature. On / Off differentials are best suited to heating loads that quickly change temperature. Heating Operation When heating, the setpoint control turns on Relay 1 when the temperature falls to 1/2 of the differential below the setpoint and turns off Relay 1 once the temperature reaches 1/2 of the differential above the setpoint. Target + ½ Differential Target – ½ Differential Target Differential Heating On / Off Differential Relay 1 On Relay 1 On Heating PWM Operation Warmer Set Heat Cycle Length Heat Relay 1 On Relay 1 On Relay 1 On Se tp oi nt Applications: Pulse Width Modulation

7 of 32

© 2007 D 161 - 08/07 VIEW MENU VIEW Menu (1 of 3) Mode Item Field Range Access Description 1 2 4 0:01 to 24:00 hr LTD USEr InST ADV OCCUPIED TIME SECTION B, D, E Displays the amount of time left on the manual override. The setpoint device operates at the Occupied temperature and then reverts back Scheduled temperature. Time counts down to 0:00 hours. Cancel the override by pressing the Up and Down buttons together at the same time or through the user switch or gateway. Note: This item is only available when a programmable setback schedule or normally unoccupied has been selected. 1 -31 to 266°F (-35.0 to 130.0°C) SEC LTD USEr InST ADV SETPOINT SECTION A Displays the measured setpoint sensor temperature. The VIEW menu items display the current operating temperatures and status information of the system. Continued on next page. Display Menus

D 161 - 08/07

8 of 36 Mode Item Field Range Access Description 2 -31 to 266°F (-35.0 to 130.0°C) SEC LTD USEr InST ADV HOT TUB SECTION B Displays the measured hot tub temperature. 3 -31 to 266°F (-35.0 to 130.0°C) SEC LTD USEr InST ADV DHW TANK SECTION C Displays the measured domestic hot water tank temperature. 4 -31 to 266°F (-35.0 to 130.0°C) SEC LTD USEr InST ADV FLOOR SECTION D Displays the measured floor temperature. 1 OFF, -4°F (-20.0°C) to Setpoint Maximum (variable) USEr InST ADV SET SETPOINT SECTION A Display the desired temperature. VIEW MENU VIEW Menu (2 of 3) Continued on next page.

9 of 32

© 2007 D 161 - 08/07 Mode Item Field Range Access Description 2 OFF, -4°F (-20.0°C) to Hot Tub Maximum (variable) USEr InST ADV SET HOT TUB SECTION B Display the desired temperature. 3 OFF, -4°F (-20.0°C) to DHW Maximum (variable) USEr InST ADV SET DHW SECTION C Display the desired temperature. 4 OFF, -4°F (-20.0°C) to Floor Maximum (variable) USEr InST ADV SET FLOOR SECTION D Display the desired temperature. 1 2 3 4 -31 to 266°F (-35.0 to 130.0°C) InST ADV SUPPLY TEMP OF tN4 BUS SECTION L Actual water temperature of the tN4 bus for heating. Note: This item is only available when the setpoint control is connected to a tN4 System Control, DIP switch 2 is set to tN4 System Control, and the Heat Source item in the ADJUST menu is set to hydronic (HYDr). VIEW MENU VIEW Menu (3 of 3) After the last item, the control returns to the first item in the menu.

D 161 - 08/07

10 of 36 ADJUST MENU ADJUST Menu (1 of 5) Mode Item Field Range Access Description 1 2 3 4 1, 2, 3, 4 Default = 1 InST ADV APPLICATION MODE SECTION A, B, C, D Select the application for the setpoint control. 1 = Setpoint 2 = Hot Tub 3 = DHW Tank 4 = Floor 2 HEAT, OFF Default = HEAT USEr InST ADV MODE OF OPERATION SECTION B Select to either heat or turn off the hot tub. 1 OFF, -4°F (-20°C) to Setpoint Maximum Default = 160°F (71.0°C) LTD USEr InST ADV SET SETPOINT OCCUPIED SECTION A Select the setpoint temperature for the occupied period. Note: In the Limited Access Level, the temperature can only be adjusted by +/-3°F (1.5°C) from the temperature setting entered prior to entering the Limited access level. The ADJUST Menu items are the programmable settings used to operate the mechanical equipment. Continued on next page.

11 of 32

© 2007 D 161 - 08/07 Mode Item Field Range Access Description 2 OFF, 40°F (4.5°C) to Hot Tub Maximum Default = 102°F (39.0°C) LTD USEr InST ADV SET HOT TUB OCCUPIED SECTION B Select the hot tub temperature for the occupied period. Note: In the Limited Access Level, the temperature can only be adjusted by +/-3°F (1.5°C) from the temperature setting entered prior to entering the Limited access level. 3 OFF, 40°F (4.5°C) to DHW Maximum Default = 130°F (54.5°C) LTD USEr InST ADV SET DHW TANK OCCUPIED SECTION C Select the domestic hot water tank temperature for the occupied period. Note: In the Limited Access Level, the temperature can only be adjusted by +/-3°F (1.5°C) from the temperature setting entered prior to entering the Limited access level. 4 OFF, 40°F (4.5°C) to Floor Maximum Default = 80°F (26.5°C) LTD USEr InST ADV SET FLOOR OCCUPIED SECTION D Select the floor temperature for the occupied period. Note: In the Limited Access Level, the temperature can only be adjusted by +/-3°F (1.5°C) from the temperature setting entered prior to entering the Limited access level. 1 50 to 239°F (10.0 to 115.0°C) Default = 200°F (93.5°C) ADV SETPOINT MAXIMUM SECTION A, Select the maximum setpoint temperature range adjustment. ADJUST MENU ADJUST Menu (2 of 5) Continued on next page.

D 161 - 08/07

12 of 36 Mode Item Field Range Access Description 2 50 to 104°F (10.0 to 40.0°C) Default = 104°F (40.0°C) ADV HOT TUB MAXIMUM SECTION B Select the maximum hot tub temperature range adjustment. 3 50 to 200°F (10 to 93.5°C) Default = 140°F (60.0°C) ADV DHW MAXIMUM SECTION C Select the maximum domestic hot water tank temperature range adjustment. 4 50 to 110°F (10.0 to 43.5°C) Default = 85°F (29.5°C) ADV FLOOR MAXIMUM SECTION D Select the maximum floor temperature range adjustment. 1 2 3 1 to 40°F (0.5 to 22.0°C) Default = 10°F (5.5°C) InST ADV DIFFERENTIAL Select the differential to cycle on and off around the setpoint temperature. ADJUST Menu (3 of 5) ADJUST MENU Continued on next page.

13 of 32

© 2007 D 161 - 08/07 Mode Item Field Range Access Description 1 2 3 4 HYDr, OTHr Default = HYDr InST ADV HEAT SOURCE SECTION L Select whether the heat source is hydronic (HYDr) or other (OTHr) when the setpoint control is connected to a tN4 System Control. Note: This item is only available when DIP switch 2 is set to tN4 System Control. 1 2 3 4 60 to 220°F (15.5 to 104.5°C) Default = 180°F (82.0°C) InST ADV EXCHANGE SUPPLY OCCUPIED SECTION L Select the desired supply water temperature required on the tN4 bus to heat the setpoint load during the occupied period. Note: This item is only available when DIP switch 2 is set to tN4 System Control, and the Heat Source item in the ADJUST menu is set to hydronic (HYDr). 1 2 3 4 On, OFF Default = OFF InST ADV PRIORITY SECTION L Select if the setpoint control has priority over the heating system. Note: This item is only available when DIP switch 2 is set to tN4 System Control, and the Heat Source item in the ADJUST menu is set to hydronic (HYDr). Note: Priority is not available when connected to a mix tN4 bus. ADJUST Menu (4 of 5) ADJUST MENU Continued on next page.

D 161 - 08/07

14 of 36 Mode Item Field Range Access Description 1 2 3 4 OFF, On Default = On InST ADV RELAY 1 PUMP SECTION L Select whether a system pump from a tN4 system control should operate whenever relay 1 is closed. Note: This item is only available when DIP switch 2 is set to tN4 System Control, and the Heat Source item in the ADJUST menu is set to hydronic (HYDr). 1 2 4 OFF, 1 to 12 Default = 1 ADV SETPOINT DEVICE ENABLE SECTION E Select the Setpoint Device Enable number to allow a remote device such as a User Switch to activate the Time Occupied override. The control then maintains the occupied temperature for a preset amount of time. Note: This item is only available when the setpoint control has tN4 communication. After the last item, the control returns to the first item in the menu. ADJUST Menu (5 of 5) ADJUST MENU

15 of 32

© 2007 D 161 - 08/07 SCENE MENU SCENE Menu (1 of 1) The SCENE Menu items set the current scene as well as the scene settings. Item Field Range Access Description OFF, 0:05 to 24:00 hr, On (in 5 min. increments) Default = 1:00 LTD USEr InST ADV RUN TIME OCCUPIED SECTION B, D, E Select the amount time for the setpoint control to operate at the occupied temperature when a Setpoint Device Enable is provided. Note: This item is only available in Application Mode 2 (Hot Tub) or 4 (Floor) if a programmable setback schedule is selected. Note: This item is only available in Application Mode 1 if a programmable setback schedule is selected and the Setpoint Device Enable setting in the ADJUST menu is set from 1 through 12. OFF, On Default = OFF InST ADV SCENE MENU SECTION H Select whether or not to use the scene feature on the setpoint control. After the last item, the control returns to the first item in the menu.

D 161 - 08/07

16 of 36 Item Field Range Access Description NONE, Mbr1, Mbr2, Mbr3, Mbr4, UnOc Default = NONE InST ADV HEAT SCHEDULE SECTION G Selects the schedule used by the setpoint control. If a schedule is not required, select NONE. If the schedule is set on another thermostat or setpoint control, select Mbr1 to Mbr4. UnOc is not available in Mode 3. Note: This item can be viewed in the USEr and InST (Installer) access levels but can only be adjusted in the ADV (Advanced) access level. SCHEDULE MENU SCHD (Schedule) Menu (1 of 1) The SCHEDULE menu allows the setpoint control to follow a schedule. After the last item, the control returns to the first item in the menu.

17 of 32

© 2007 D 161 - 08/07 MISC MENU MISC (Miscellaneous) Menu (1 of 2) The Miscellaneous menu items set display and control options such as access level and temperature units. Item Field Range Access Description SEC, LTD, USEr, InST, ADV Default = USEr SEC LTD USEr InST ADV ACCESS LEVEL The access level of the setpoint control. The access column shows which items are visible in each access level. Note: This item is only available when DIP switch 1 is set to the Unlock position and the tN4 system control DIP switch is set to the Unlock position. °F, °C Default = °F USEr InST ADV UNITS SECTION J Select Fahrenheit or Celsius as the temperature units. ON, TMPY, OFF Default = TMPY InST ADV BACKLIGHT SECTION K Select whether the backlight displays permanently, temporarily, or is off. The temporary backlight lasts for 30 seconds. Continued on next page.

D 161 - 08/07

18 of 36 MISC (Miscellaneous) Menu (2 of 2) Item Field Range Access Description – – –, 1 to 24 ADV NUMBER OF DEVICES SECTION L Number of tN4 devices connected to this tN4 bus. Note: This item is only available when the setpoint control has tN4 communication. bus#:01 to bus#:24, AUTO Default = AUTO SEC LTD USEr InST ADV ADDRESS SECTION L The tN4 bus address of this setpoint control. Auto allows the tN4 system to automatically assign an address to the setpoint control. To manually set the address, use the Up or Down buttons while in the ADV (Advanced) or InST (Installer) access level. Note: This item is only available when the setpoint control has tN4 communication. InST ADV RESTORE DEFAULTS Press the Up and Down buttons together to load the factory defaults. The SELECT icon appears and then the display shows DONE when the factory defaults have been completed. 161, Software Version SEC LTD USEr InST ADV TYPE Product number of this setpoint control. Hold the Up button to view the software version. After the last item, the control returns to the first item in the menu. MISC MENU

19 of 32

© 2007 D 161 - 08/07 Application Mode 1 is a generic setpoint control operation using an on/off differential for heating. The sensor is required to be located at the temperature control point. The setpoint control can have an occupied temperature setting. The setpoint load is not heated during the unoccupied or away periods. Application Mode 2 is designed specifically to heat hot tubs using an on/off differential. A sensor must be located in a temperature well on the recirculation pipe. The hot tub can have an occupied temperature setting. Sequence of Operation Application Mode 1 - On / Off Setpoint SECTION A Load Application Mode 2 - Hot Tub SECTION B Relay 1 Operation Relay 1 operates using an on/off differential to maintain the load at the Occupied temperature. During the Unoccupied period, Relay 1 is operated to maintain 10°F (5.5°C) less than the Occupied temperature setting. During the Away scene, Relay 1 is operated to maintain the Hot Tub at 50°F (10.0°C). Relay 1 Operation Relay 1 operates using an on/off differential to maintain the load at the Occupied temperature. Relay 1 does not operate during the Unoccupied or Away periods. Setting the Setpoint Off The setpoint temperature can be set to Off. When set to Off, Relay 1 will not turn on. If the heating area is outdoors, or the heating system has the potential to freeze, it is recommended that the setpoint always be set to a temperature and not set to Off. The setpoint can be set to Off if the heating system can be drained or the pump should remain off. The setpoint control power should never be shut off, otherwise an error message will appear on the rest of the tN4 system.