MR ETOS TD Operating Instructions Manual

Text of the manual

© All rights reserved by Maschinenfabrik Reinhausen

Dissemination and reproduction of this document and use and disclosure of its content are strictly prohibited unless expressly permitted. Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents, utility models or designs. The product may have been altered since this document was published. We reserve the right to change the technical data, design and scope of supply. Generally the information provided and agreements made when processing the individual quotations and orders are binding. The original operating instructions were written in German.

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 3 4453918/14 EN ETOS® TD Table of contents 1 Introduction....................................................................................................................... 10 1.1 Manufacturer.....................................................................................................................................  10 1.2 Completeness...................................................................................................................................  10 1.3 Safekeeping......................................................................................................................................  10 1.4 Notation conventions ........................................................................................................................  11 1.4.1 Symbols .............................................................................................................................................................. 11 1.4.2 Hazard communication system........................................................................................................................... 12 1.4.3 Information system.............................................................................................................................................. 13 1.4.4 Instruction system ............................................................................................................................................... 14 1.4.5 Typographic conventions .................................................................................................................................... 14 2 Safety................................................................................................................................. 15 2.1 Appropriate use ................................................................................................................................  15 2.2 Inappropriate use..............................................................................................................................  15 2.3 Fundamental safety instructions.......................................................................................................  16 2.4 Personnel qualification......................................................................................................................  18 2.5 Personal protective equipment .........................................................................................................  19 2.6 Drying transformer............................................................................................................................  20 2.6.1 Drying transformer in autoclave .......................................................................................................................... 20 2.6.2 Drying transformer in its own tank....................................................................................................................... 20 3 IT security.......................................................................................................................... 21 4 Product description.......................................................................................................... 24 4.1 Scope of delivery ..............................................................................................................................  24 4.2 Function description..........................................................................................................................  24 4.3 Performance features .......................................................................................................................  25 4.4 Operating modes ..............................................................................................................................  26 4.5 Design...............................................................................................................................................  27 4.5.1 Name plate.......................................................................................................................................................... 28 4.5.2 Gear motor.......................................................................................................................................................... 28 4.5.3 Control cabinet.................................................................................................................................................... 29 4.5.4 ISM® assemblies ................................................................................................................................................ 31 4.6 Visualization......................................................................................................................................  38 4.6.1 Main screen......................................................................................................................................................... 38

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 4 4453918/14 EN ETOS® TD 4.6.2 Additional operating controls and display elements when using the MControl touch panel (optional)................ 42 4.6.3 Operating concept............................................................................................................................................... 42 5 Packaging, transport and storage .................................................................................. 46 5.1 Packaging.........................................................................................................................................  46 5.1.1 Suitability............................................................................................................................................................. 46 5.1.2 Markings.............................................................................................................................................................. 47 5.2 Transportation, receipt and handling of shipments...........................................................................  47 5.3 Storage of shipments........................................................................................................................  48 5.4 Unpacking shipments and checking for transportation damages .....................................................  49 6 Mounting ........................................................................................................................... 52 6.1 Fitting the control cabinet to the transformer ....................................................................................  52 6.2 Cable recommendation.....................................................................................................................  55 6.3 Information about connecting serial interfaces RS232 and RS485 ..................................................  55 6.4 Notes on connecting to the MR sensor bus......................................................................................  57 6.4.1 MSENSE® DGA.................................................................................................................................................. 59 6.4.2 MESSKO® MTeC® EPT303 FO......................................................................................................................... 60 6.4.3 MESSKO® MTRAB® 2.5.................................................................................................................................... 61 6.4.4 MSENSE®-FO ECU-I/S...................................................................................................................................... 62 6.5 Information about connecting analog sensors..................................................................................  62 6.6 Information about screening the cables for analog signals...............................................................  65 6.7 Information about laying fiber-optic cable.........................................................................................  65 6.8 Connecting motor-drive unit..............................................................................................................  66 7 Commissioning................................................................................................................. 69 7.1 Performing tests................................................................................................................................  69 7.1.1 Function test of the motor-drive unit.................................................................................................................... 69 7.1.2 High-voltage tests on the transformer................................................................................................................. 69 7.1.3 Dielectric tests on transformer wiring.................................................................................................................. 70 7.2 Transporting transformer to the operating site..................................................................................  70 7.3 Commissioning the transformer at the operating site .......................................................................  71 8 Operation........................................................................................................................... 72 8.1 Actuating motor-drive unit locally......................................................................................................  72 8.2 Selecting the operating mode...........................................................................................................  72 8.3 Monitoring motor-drive unit...............................................................................................................  72

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 5 4453918/14 EN ETOS® TD 9 Visualization...................................................................................................................... 73 9.1 Establishing connection to visualization ...........................................................................................  73 9.2 General.............................................................................................................................................  75 9.2.1 Setting general device functions ......................................................................................................................... 76 9.2.2 Set up automatic logout ...................................................................................................................................... 77 9.2.3 Activating/deactivating service user access........................................................................................................ 78 9.3 Configuring the network....................................................................................................................  79 9.4 MQTT................................................................................................................................................  81 9.5 Setting the device time .....................................................................................................................  83 9.5.1 Time synchronization via PTP............................................................................................................................. 84 9.6 Configuring syslog ............................................................................................................................  85 9.7 SCADA .............................................................................................................................................  87 9.7.1 Configuring IEC 61850 (optional)........................................................................................................................ 87 9.7.2 Configuring IEC 60870-5-101 (optional) ............................................................................................................. 89 9.7.3 Configuring IEC 60870-5-103 (optional) ............................................................................................................. 92 9.7.4 Configuring IEC 60870-5-104 (optional) ............................................................................................................. 94 9.7.5 Configuring Modbus (optional)............................................................................................................................ 96 9.7.6 Configuring DNP3 (optional) ............................................................................................................................... 98 9.7.7 Configuring GOOSE (optional).......................................................................................................................... 100 9.7.8 Configure data points (optional)........................................................................................................................ 105 9.7.9 Display status of the SCADA connection.......................................................................................................... 112 9.8 Name plate .....................................................................................................................................  113 9.8.1 Enter the name plate data................................................................................................................................. 113 9.8.2 Displaying the name plate................................................................................................................................. 114 9.9 Linking signals and events..............................................................................................................  114 9.9.1 Linking functions ............................................................................................................................................... 115 9.9.2 Linking digital outputs........................................................................................................................................ 117 9.9.3 Linking control system messages ..................................................................................................................... 118 9.10 Cooling system control (optional) ...................................................................................................  119 9.10.1 Configuring cooling stages................................................................................................................................ 119 9.10.2 Set the operating mode..................................................................................................................................... 121 9.10.3 Deactivating cooling system control.................................................................................................................. 121 9.10.4 Configuring load-dependent mode.................................................................................................................... 121 9.10.5 Configuring periodic mode ................................................................................................................................ 123 9.10.6 Configuring alternating mode............................................................................................................................ 124 9.10.7 Configuring the frequency-based cooling system control ................................................................................. 125

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 6 4453918/14 EN ETOS® TD 9.10.8 Displaying status of cooling stages................................................................................................................... 128 9.11 Cooling system monitoring (optional) .............................................................................................  129 9.11.1 Setting the cooling system monitoring function................................................................................................. 129 9.11.2 Cooling efficiency monitoring (optional) ............................................................................................................ 130 9.11.3 Cooling system flow monitoring (optional) ........................................................................................................ 131 9.12 Drive overview ................................................................................................................................  135 9.13 Displaying power characteristics ....................................................................................................  136 9.14 Regulation.......................................................................................................................................  137 9.14.1 Response to control system disconnection (optional)....................................................................................... 137 9.14.2 Setting control variable (optional)...................................................................................................................... 139 9.15 Voltage regulation...........................................................................................................................  140 9.15.1 Setting the desired value................................................................................................................................... 140 9.16 Reactive power regulation (optional) ..............................................................................................  157 9.17 Transformer data ............................................................................................................................  160 9.17.1 Setting transformer data.................................................................................................................................... 161 9.17.2 Circuit examples for voltage transformers and current transformers ................................................................ 163 9.18 Measurement..................................................................................................................................  176 9.18.1 UI measuring channels ..................................................................................................................................... 176 9.18.2 Control variable................................................................................................................................................. 177 9.18.3 Regulation mode............................................................................................................................................... 177 9.18.4 Display power factor negative........................................................................................................................... 177 9.19 Synchronizing the motor-drive unit .................................................................................................  178 9.19.1 Single-column on-load tap-changer model ....................................................................................................... 178 9.19.2 Multi-column on-load tap-changer model.......................................................................................................... 179 9.20 Line drop compensation .................................................................................................................  180 9.20.1 R&X compensation ........................................................................................................................................... 180 9.20.2 Z compensation................................................................................................................................................. 182 9.21 Parallel operation (optional)............................................................................................................  183 9.21.1 Parallel operation methods ............................................................................................................................... 184 9.21.2 Configuring parallel operation ........................................................................................................................... 188 9.21.3 TAPCON® 2xx retrofit....................................................................................................................................... 192 9.21.4 Detecting parallel operation via group inputs (optional).................................................................................... 193 9.22 Monitoring functions........................................................................................................................  194 9.22.1 Voltage monitoring ............................................................................................................................................ 194 9.22.2 Current monitoring ............................................................................................................................................ 196 9.22.3 Power monitoring .............................................................................................................................................. 199

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 7 4453918/14 EN ETOS® TD 9.22.4 Power flow monitoring....................................................................................................................................... 201 9.22.5 Tap position monitoring (optional)..................................................................................................................... 203 9.22.6 U bandwidth monitoring .................................................................................................................................... 204 9.22.7 Q bandwidth monitoring (optional) .................................................................................................................... 206 9.22.8 Phase symmetry monitoring.............................................................................................................................. 208 9.22.9 Temperature monitoring.................................................................................................................................... 209 9.22.10 Monitoring the gas volume of the Buchholz relay (OLTC) ................................................................................ 210 9.22.11 Monitoring the gas volume of the Buchholz relay (transformer)........................................................................ 211 9.22.12 Monitoring the oil pressure (transformer).......................................................................................................... 211 9.22.13 Monitoring the oil pressure (on-load tap-changer) ............................................................................................ 212 9.23 Target-tap-position operation..........................................................................................................  213 9.24 Measured values ............................................................................................................................  213 9.24.1 Displaying current measured values................................................................................................................. 213 9.24.2 Displaying measured value recorder (optional)................................................................................................. 214 9.24.3 Setting the measured value recorder................................................................................................................ 218 9.24.4 Displaying temperature curve (optional) ........................................................................................................... 220 9.24.5 Displaying winding temperatures (optional) ...................................................................................................... 221 9.24.6 Displaying the measured values of the Buchholz relay (optional)..................................................................... 221 9.24.7 Displaying the measured values of the pressure relief device (optional).......................................................... 222 9.24.8 Displaying the measured value trend of the oil level and dehydrating breather (optional)................................ 222 9.25 On-load tap-changer monitoring.....................................................................................................  223 9.25.1 Changing tap position designation (optional).................................................................................................... 223 9.25.2 Setting the TCR calculation factor (optional)..................................................................................................... 223 9.25.3 Displaying tap-change operation statistics (optional)........................................................................................ 224 9.25.4 Motor Current Index (MCI) ................................................................................................................................ 225 9.25.5 Displaying information about contact wear (only OILTAP®)............................................................................. 229 9.25.6 Configuring OLTC PreCheck ............................................................................................................................ 230 9.25.7 Information about the on-load tap-changer....................................................................................................... 231 9.26 Transformer monitoring (optional) ..................................................................................................  232 9.26.1 Hot-spot calculation (optional)........................................................................................................................... 232 9.26.2 Hot-spot forecast (optional)............................................................................................................................... 235 9.26.3 Setting calculation of transformer's loss of life (optional) .................................................................................. 236 9.26.4 Displaying protective device status (optional)................................................................................................... 237 9.27 Dissolved gas analysis (optional) ...................................................................................................  237 9.27.1 Configuring DGA monitoring ............................................................................................................................. 238 9.27.2 Displaying measured values ............................................................................................................................. 241

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 8 4453918/14 EN ETOS® TD 9.28 MR sensor bus................................................................................................................................  246 9.28.1 Configuring MR sensor bus............................................................................................................................... 247 9.28.2 Managing sensors............................................................................................................................................. 248 9.28.3 Function assignment......................................................................................................................................... 250 9.28.4 Defining the sensors ......................................................................................................................................... 251 9.28.5 Displaying information on the connected sensors............................................................................................. 255 9.29 Configuring analog inputs and outputs (optional) ...........................................................................  257 9.30 Configuring digital inputs and outputs.............................................................................................  259 9.31 Maintenance (optional) ...................................................................................................................  261 9.31.1 Setting operator interval for OLTC maintenance............................................................................................... 262 9.31.2 Setting operator interval for transformer maintenance...................................................................................... 263 9.31.3 Undertaking and confirming maintenance......................................................................................................... 264 9.31.4 Displaying maintenance overview..................................................................................................................... 267 9.31.5 Displaying the maintenance logbook ................................................................................................................ 267 9.31.6 Suppressing a maintenance event.................................................................................................................... 269 9.32 Dynamic Transformer Rating (optional)..........................................................................................  270 9.32.1 Configuring the Dynamic Transformer Rating................................................................................................... 271 9.32.2 Displaying the Dynamic Transformer Rating..................................................................................................... 272 9.33 Event management.........................................................................................................................  274 9.33.1 Displaying and acknowledging events .............................................................................................................. 274 9.33.2 Configuring events ............................................................................................................................................ 275 9.33.3 Displaying event memory.................................................................................................................................. 277 9.34 User administration.........................................................................................................................  278 9.34.1 User roles.......................................................................................................................................................... 278 9.34.2 Changing the password .................................................................................................................................... 280 9.34.3 Creating, editing and deleting users.................................................................................................................. 281 9.34.4 Setting access rights to parameters and events ............................................................................................... 282 9.34.5 User authentication via RADIUS (optional)....................................................................................................... 283 9.35 Information about device ................................................................................................................  285 9.35.1 Hardware........................................................................................................................................................... 285 9.35.2 Software............................................................................................................................................................ 286 9.35.3 Parallel operation .............................................................................................................................................. 286 9.36 Import/export manager ...................................................................................................................  287 9.36.1 Exporting data................................................................................................................................................... 287 9.36.2 Importing data (software version 3.44 and later)............................................................................................... 288

Table of contents

Maschinenfabrik Reinhausen GmbH 2020 9 4453918/14 EN ETOS® TD 9.37 Configuring media converter with managed switch ........................................................................  289 9.37.1 Commissioning.................................................................................................................................................. 290 9.37.2 Configuration..................................................................................................................................................... 291 9.38 TAPCON® Personal Logic Editor (TPLE).......................................................................................  292 9.38.1 Function ............................................................................................................................................................ 292 9.38.2 Configuring TPLE.............................................................................................................................................. 306 10 Fault elimination............................................................................................................. 310 10.1 Motor-drive unit...............................................................................................................................  310 10.2 Human-machine interface...............................................................................................................  311 10.3 Other faults .....................................................................................................................................  311 11 Inspection and maintenance ......................................................................................... 312 11.1 Maintaining motor-drive unit ...........................................................................................................  312 11.2 Cleaning motor-drive unit................................................................................................................  312 12 Event messages ............................................................................................................. 313 13 Disassembly.................................................................................................................... 324 14 Disposal........................................................................................................................... 326 15 Technical data................................................................................................................. 327 15.1 Gear motor......................................................................................................................................  327 15.2 Control cabinet................................................................................................................................  327 15.2.1 Connection terminals ........................................................................................................................................ 328 15.2.2 Drawings ........................................................................................................................................................... 329 15.3 ISM® assemblies............................................................................................................................  335 15.3.1 Voltage measurement and current measurement............................................................................................. 335 15.3.2 UI 5-4 voltage measurement and current measurement................................................................................... 336 15.3.3 Digital inputs and outputs.................................................................................................................................. 338 15.3.4 Analog inputs and outputs................................................................................................................................. 340 15.3.5 CPU (central processing unit) I ......................................................................................................................... 341 15.3.6 CPU (central processing unit) II ........................................................................................................................ 343 15.3.7 System networking............................................................................................................................................ 345 15.4 Tests...............................................................................................................................................  347 Glossary .......................................................................................................................... 348 List of key words ............................................................................................................ 350

Maschinenfabrik Reinhausen GmbH 2020

10 4453918/14 EN ETOS® TD 1 Introduction This technical file contains detailed descriptions on the safe and proper in- stallation, connection, commissioning and monitoring of the product. It also includes safety instructions and general information about the prod- uct. This technical file is intended solely for specially trained and authorized per- sonnel. 1.1 Manufacturer The product is manufactured by: Maschinenfabrik Reinhausen GmbH Falkensteinstraße 8 93059 Regensburg Tel.: (+49) 9 41/40 90-0 E-mail: [email protected] Further information on the product and copies of this technical file are avail- able from this address if required. 1.2 Completeness This technical file is incomplete without the supporting documents. The following documents also apply in addition to this technical file: ▪ Connection diagrams ▪ Routine test report ▪ Supplement Also observe generally valid legislation, standards, and guidelines as well as specifications on accident prevention and environmental protection in the re- spective country of use. 1.3 Safekeeping Keep this technical file and all supporting documents ready at hand and ac- cessible for future use at all times.

Maschinenfabrik Reinhausen GmbH 2020

11 4453918/14 EN ETOS® TD 1.4 Notation conventions 1.4.1 Symbols Symbol Meaning Wrench size Tightening torque Number and type of fastening material used Fill with oil Cut open, cut through Clean Visual inspection Use your hand Adapter ring Apply a coat of paint Use a file Grease Coupling bolt Use a ruler

Maschinenfabrik Reinhausen GmbH 2020

12 4453918/14 EN ETOS® TD Symbol Meaning Use a saw Hose clip Wire eyelet, safety wire Use a screwdriver Apply adhesive Lock tab Table 1: Symbols 1.4.2 Hazard communication system Warnings in this technical file are displayed as follows. 1.4.2.1 Warning relating to section Warnings relating to sections refer to entire chapters or sections, sub-sec- tions or several paragraphs within this technical file. Warnings relating to sections use the following format: WARNING Type of danger! Source of the danger and outcome. ►Action ►Action 1.4.2.2 Embedded warning information Embedded warnings refer to a particular part within a section. These warn- ings apply to smaller units of information than the warnings relating to sec- tions. Embedded warnings use the following format:  DANGER! Instruction for avoiding a dangerous situation.

Maschinenfabrik Reinhausen GmbH 2020

13 4453918/14 EN ETOS® TD 1.4.2.3 Signal words and pictograms The following signal words are used: Signal word Definition DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE Indicates measures to be taken to prevent damage to property. Table 2: Signal words in warning notices Pictograms warn of dangers: Pictogram Definition Warning of a danger point Warning of dangerous electrical voltage Warning of combustible substances Warning of danger of tipping Warning of danger of crushing Table 3: Pictograms used in warning notices 1.4.3 Information system Information is designed to simplify and improve understanding of particular procedures. In this technical file it is laid out as follows:

Maschinenfabrik Reinhausen GmbH 2020

14 4453918/14 EN ETOS® TD Important information. 1.4.4 Instruction system This technical file contains single-step and multi-step instructions. Single-step instructions Instructions which consist of only a single process step are structured as fol- lows: Aim of action ü Requirements (optional). ►Step 1 of 1. ð Result of step (optional). ð Result of action (optional). Multi-step instructions Instructions which consist of several process steps are structured as follows: Aim of action ü Requirements (optional). 1. Step 1. ð Result of step (optional). 2. Step 2. ð Result of step (optional). ð Result of action (optional). 1.4.5 Typographic conventions Typographic convention Purpose Example UPPERCASE Operating controls, switches ON/OFF [Brackets] PC keyboard [Ctrl] + [Alt] Bold Software operating controls Press Continue button …>…>… Menu paths Parameter > Control parameter Italics System messages, error messages, signals Function monitoring alarm triggered [► Number of pages] Cross reference [► Page 41]. Dotted underscore ............................................. Glossary entry, abbreviations, defini- tions, etc. Glossary entry ........................ Table 4: Typographic conventions used in this technical file

Maschinenfabrik Reinhausen GmbH 2020

15 4453918/14 EN ETOS® TD 2 Safety ▪ Read this technical file through to familiarize yourself with the product. ▪ This technical file is a part of the product. ▪ Read and observe the safety instructions provided in this chapter. ▪ Read and observe the warnings in this technical file in order to avoid func- tion-related dangers. ▪ The product is manufactured on the basis of state-of-the-art technology. Nevertheless, risks to life and limb for the user or impairment of the prod- uct and other material assets due to the function may arise in the event of improper use. 2.1 Appropriate use If used as intended and in compliance with the requirements and conditions specified in this technical document as well as with the warnings in this tech- nical document and attached to the product, then the product does not present any danger to people, property or the environment. This applies throughout the product's entire life, from delivery through installation and op- eration to disassembly and disposal. The operational quality-assurance system ensures a consistently high qual- ity standard, particularly in regard to the observance of health and safety re- quirements. The following is considered appropriate use: ▪ Only operate the product in accordance with this technical file and the agreed delivery conditions and technical data ▪ Use the equipment and special tools supplied solely for the intended pur- pose and in accordance with the specifications of this technical file ▪ Use the product only with the transformer specified in the order ▪ You will find the standard valid for the product and the year of issue on the nameplate ▪ The serial numbers of on-load tap-changers and on-load tap-changer ac- cessories (drive, drive shaft, bevel gear, protective relay etc.) must match if the on-load tap-changers and on-load tap-changer accessories are sup- plied as a set for one order 2.2 Inappropriate use Use is considered to be inappropriate if the product is used other than as de- scribed in the Appropriate use section. Please also note the following: ▪ Risk of explosion and fire from highly flammable or explosive gases, va- pors, or dusts. Do not operate product in areas at risk of explosion. ▪ Unauthorized or inappropriate changes to the product may lead to per- sonal injury, material damage, and operational faults. Only modify product following discussion with Maschinenfabrik Reinhausen GmbH.

Maschinenfabrik Reinhausen GmbH 2020

16 4453918/14 EN ETOS® TD 2.3 Fundamental safety instructions To prevent accidents, malfunctions and damage as well as unacceptable ad- verse effects on the environment, those responsible for transport, installa- tion, operation, maintenance and disposal of the product or parts of the prod- uct must ensure the following: Personal protective equipment Loosely worn or unsuitable clothing increases the danger of becoming trapped or caught up in rotating parts and the danger of getting caught on protruding parts. This poses a danger to life and limb. ▪ Wear appropriate personal protective equipment such as a helmet, work gloves, etc. for the respective activity. ▪ Never wear damaged personal protective equipment. ▪ Never wear rings, necklaces, or other jewelry. ▪ If you have long hair, wear a hairnet. Work area Untidy and poorly lit work areas can lead to accidents. ▪ Keep the work area clean and tidy. ▪ Make sure that the work area is well lit. ▪ Observe the applicable laws for accident prevention in the relevant coun- try. Drying the transformer Drying the motor-drive unit will cause damage to property as well as motor- drive unit malfunctions. ▪ Never dry the motor-drive unit. Working during operation The product may only be operated in a sound, operational condition. Other- wise it poses a danger to life and limb. ▪ Regularly check the operational reliability of safety equipment. ▪ Comply with the inspection work, maintenance work and maintenance in- tervals described in this technical file.

Maschinenfabrik Reinhausen GmbH 2020

17 4453918/14 EN ETOS® TD Invisible laser radiation Looking directly into the beam or the reflected beam can cause eye damage. The beam is emitted at the optical connections or at the end of the fiber-optic cables connected to them on the assemblies. Read the chapter "Technical Data" [►Section 15, Page 327] for further information. ▪ Never look directly into the beam or the reflected beam. ▪ Never look into the beam with the aid of optical instruments such as a magnifying glass or a microscope. ▪ In the event that the laser beam strikes your eyes, close your eyes imme- diately and move your head out of the path of the beam. Working with current transformers Dangerous high voltages may occur when a current transformer is operated with an open secondary circuit. This can lead to injuries and property dam- age. ▪ Never operate a current transformer with an open secondary circuit; short- circuit the current transformer to prevent this. ▪ Observe the information in the current transformer operating instructions. Handling electrical components Electrical components can be damaged by electrostatic discharges. ▪ Never touch electrical components during commissioning, operation or maintenance work. ▪ Take suitable measures (e.g. covers) to ensure that personnel cannot touch components. ▪ Wear suitable personal protective equipment (e.g. grounded strap). Explosion protection Highly flammable or explosive gases, vapors and dusts can cause serious explosions and fire. This increases the danger to life and limb. ▪ Do not install, operate or perform maintenance work on the product in ar- eas where a risk of explosion is present. Safety markings Warning signs and safety information plates are safety markings on the product. They are an important aspect of the safety concept. ▪ Observe all safety markings on the product. ▪ Make sure all safety markings on the product remain intact and legible. ▪ Replace safety markings that are damaged or missing.

Maschinenfabrik Reinhausen GmbH 2020

18 4453918/14 EN ETOS® TD Ambient conditions To ensure reliable and safe operation, the product must only be operated under the ambient conditions specified in the technical data. ▪ Observe the specified operating conditions and requirements for the in- stallation location. Auxiliary materials and operating materials Auxiliary materials and operating materials not approved by the manufac- turer can lead to personal injury, damage to property and malfunctions of the product. ▪ Only use conductive and grounded hoses, pipes, and pump equipment that are approved for flammable liquids. ▪ Only use lubricants and auxiliary materials approved by the manufacturer. ▪ Contact the manufacturer. Modifications and conversions Unauthorized or inappropriate changes to the product may lead to personal injury, material damage and operational faults. ▪ Only modify the product after consultation with Maschinenfabrik Rein- hausen GmbH. Spare parts Spare parts not approved by Maschinenfabrik Reinhausen GmbH may lead to physical injury, damage to the product and malfunctions. ▪ Only use spare parts that have been approved by Maschinenfabrik Rein- hausen GmbH. ▪ Contact Maschinenfabrik Reinhausen GmbH. 2.4 Personnel qualification The person responsible for assembly, commissioning, operation, mainte- nance and inspection must ensure that the personnel are sufficiently quali- fied. Electrically skilled person The electrically skilled person has a technical qualification and therefore has the required knowledge and experience, and is also conversant with the ap- plicable standards and regulations. The electrically skilled person is also pro- ficient in the following: ▪ Can identify potential dangers independently and is able to avoid them. ▪ Is able to perform work on electrical systems. ▪ Is specially trained for the working environment in which (s)he works. ▪ Must satisfy the requirements of the applicable statutory regulations for accident prevention.

Maschinenfabrik Reinhausen GmbH 2020

19 4453918/14 EN ETOS® TD Electrically trained persons An electrically trained person receives instruction and guidance from an electrically skilled person in relation to the tasks undertaken and the poten- tial dangers in the event of inappropriate handling as well as the protective devices and safety measures. The electrically trained person works exclu- sively under the guidance and supervision of an electrically skilled person. Operator The operator uses and operates the product in line with this technical file. The operating company provides the operator with instruction and training on the specific tasks and the associated potential dangers arising from im- proper handling. Technical Service We strongly recommend having maintenance, repairs and retrofitting carried out by our Technical Service department. This ensures that all work is per- formed correctly. If maintenance is not carried out by our Technical Service department, please ensure that the personnel who carry out the mainte- nance are trained and authorized by Maschinenfabrik Reinhausen GmbH to carry out the work. Authorized personnel Authorized personnel are trained by Maschinenfabrik Reinhausen GmbH to carry out special maintenance. 2.5 Personal protective equipment Personal protective equipment must be worn during work to minimize risks to health. ▪ Always wear the personal protective equipment required for the job at hand. ▪ Never wear damaged personal protective equipment. ▪ Observe information about personal protective equipment provided in the work area. Protective clothing Close-fitting work clothing with a low tearing strength, with tight sleeves and with no protruding parts. It mainly serves to protect the wearer against being caught by moving machine parts. Safety shoes To protect against falling heavy objects and slipping on slippery surfaces. Safety glasses To protect the eyes from flying parts and splashing liq- uids. Visor To protect the face from flying parts and splashing liq- uids or other dangerous substances. Hard hat To protect against falling and flying parts and materials.

Maschinenfabrik Reinhausen GmbH 2020

20 4453918/14 EN ETOS® TD Hearing protection To protect against hearing damage. Protective gloves To protect against mechanical, thermal, and electrical hazards. Table 5: Personal protective equipment 2.6 Drying transformer 2.6.1 Drying transformer in autoclave Observe the following information when drying the transformer in an auto- clave. NOTICE Damage to drive and on-load tap-changer/de-energized tap- changer! If the drive is dried in an autoclave, the drive and on-load tap-changer/de- energized tap-changer may be damaged. ►Do not dry drive in an autoclave. ►Remove on-load tap-changer head cover with gear motor before drying. To do so, follow the operating instructions of the on-load tap-changer. Do not remove gear motor from the on-load tap-changer head cover. 2.6.2 Drying transformer in its own tank If you dry the transformer in its own tank, the drive can remain attached to the transformer during drying.

3 IT security

Maschinenfabrik Reinhausen GmbH 2020 21 4453918/14 EN ETOS® TD 3 IT security Observe the following recommendations for secure operation of the product. General ▪ Ensure that only authorized personnel have access to the device. ▪ Only use the device within an ESP (electronic security perimeter). Do not connect the device to the Internet in an unprotected state. Use mecha- nisms for vertical and horizontal network segmenting and security gate- ways (firewalls) at the transition points. ▪ Ensure that the device is only operated by trained personnel who are fa- miliar with IT security. Commissioning Observe the following recommendations for device commissioning: ▪ User IDs must be unique and assignable. Do not use a "Group account" function or the "Auto login" function. ▪ Activate the "Auto logout [►Section 9.2.2, Page 77]" function. ▪ Restrict the rights of the individual user groups as much as is feasible; this helps avoid errors during operations. A user with the "Operator" role, for example, should only perform operations and should not be able to change any device settings. ▪ Delete or disable the default "admin" user ID. This requires first creating a new user account with the "Administrator" role. You can then use it to delete or disable the default "admin" account. ▪ Deactivate service user access [►Section 9.2.3, Page 78]. ▪ Enable SSL/TLS encryption [►Section 9.2, Page 75]; access to the de- vice is then only possible using the SSL/TLS protocol. In addition to en- crypting communication, this protocol also checks the authenticity of the server. ▪ Use TLS version 1.2 or higher wherever possible. ▪ Integrate the device into a public key infrastructure. Create your own SSL certificates for this if necessary and then import them. ▪ Connect the device to a central log server by using the syslog interface [►Section 9.6, Page 85]. ▪ Only use the SNMP function if you can ensure that the communication is protected by external security equipment. Operation Observe the following recommendations during device operation: ▪ Change the password at regular intervals. ▪ Export the security log [►Section 9.36.1, Page 287] at regular intervals. ▪ Check the log files regularly for unauthorized system access and other se- curity-related events.

3 IT security

Maschinenfabrik Reinhausen GmbH 2020 22 4453918/14 EN ETOS® TD Interfaces The device uses the following interfaces for communication: CPU CAN 1 1 9 CAN 2 1 9 COM 1 1 9 COM 2 1 9 - + 24V DC RUN INIT ERR USB2.0 4 6 2 A 8 C H TEST PROG RUN 4 6 2 A E 0 8 C L ETH 1 ETH 2.1 ETH 2.2 Figure 1: CPU assembly interfaces Interface Protocol Port Description CAN 1 - - DIO assembly connection CAN 2 - - Communication with other ISM® devices (e.g. parallel operation) COM 1 - - Internal system interface COM 2 - - Serial interface (SCADA) USB - - Import or export of data ETH 1 TCP 80 HTTP for web-based visualization1), 2) ETH 1 TCP 443 HTTPS for web-based visualization1), 2) ETH 1 TCP 102 IEC 61850 ETH 1 TCP 502 Modbus3) ETH 1 TCP 20000 DNP33) ETH 1 UDP 161 SNMP4) ETH 2.x TCP 21 FTP1) (only for MR service) ETH 2.x TCP 80 HTTP for web-based visualization1) ETH 2.x TCP 443 HTTPS for web-based visualization1) ETH 2.x TCP 990 FTPS (only for MR service) ETH 2.x TCP 8080 HTTP for web-based visualization1) ETH 2.x TCP 8081 HTTPS for web-based visualization1) ETH 2.x UDP 161 SNMP4) Table 6: Interfaces and open ports of the CPU assembly 1) Port is closed if you activate the device's SSL encryption. 2) Depending on the setting of the parameter Visualization release [►Page 80].

3 IT security

Maschinenfabrik Reinhausen GmbH 2020 23 4453918/14 EN ETOS® TD 3) Default setting; if you have modified the port for the control system proto- col, only the set port is open. 4) Depending on the setting of the SNMP agent parameter. Encryption standards The device supports the following TLS versions: ▪ TLS 1.0 ▪ TLS 1.1 ▪ TLS 1.2 The device uses the following cipher suites for a TLS-secured connection: Key exchange Authentication Encryption Key length Operating mode Hash func- tion TLS ECDHE RSA WITH AES 128 CBC SHA1) DHE SHA265 ECDHE ECDSA GCM SHA256 ECDH 256 CBC SHA1) RSA1) SHA256 GCM SHA384 Table 7: Cipher suite 1) Not available with TLS version >= 1.2 The device uses the SHA256 hash function to save passwords.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 24 4453918/14 EN ETOS® TD 4 Product description 4.1 Scope of delivery The motor-drive unit is packaged with protection against moisture and is de- livered as follows: ▪ Gear motor (pre-installed on the on-load tap-changer) ▪ Control cabinet ▪ Connection cable ▪ Product documentation Please note the following: 1. Check the shipment for completeness using the shipping documents. 2. Store the parts in a dry place until installation. 3. The product must remain in its airtight, protective wrapping and may only be removed immediately before installation. 4.2 Function description The motor-drive unit adjusts the operating position of on-load tap-changers in regulating transformers to the individual operating requirements. To do so, the on-load tap-changer is delivered with a pre-installed gear mo- tor that is controlled by an electronic control unit. The electronic control unit is located in a control cabinet and connected to the gear motor via a connec- tion cable. A complex installation of drive shafts and bevel gears and the associated coupling and centering of the individual modules is not required for the ETOS® TD.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 25 4453918/14 EN ETOS® TD The motor-drive unit control unit can be configured and the measured values and results can be displayed using the web-based visualization. Here, the functional scope is based on the ordered product version. Figure 2: ETOS® TD and on-load tap-changer on one power transformer 4.3 Performance features The motor-drive unit is characterized by the following features in particular: ▪ On-load tap-changer driven using the gear motor directly on top of the on- load tap-changer head. ▪ Electronic control of the gear motor ▪ In multi-column on-load tap-changer model: Control of 3 gear motors with one single control cabinet. ▪ Easy connection of the gear motor and control cabinet via integrated ca- ble plug connection ▪ Automatic adjustment during commissioning ▪ OLTC pre-check: Check for compliance with the permissible operating conditions (load current, oil level, oil temperature) prior to each on-load tap-change operation ▪ Web-based visualization for configuring the motor-drive unit and display- ing important data ▪ On-load tap-changer monitoring ▪ Transformer monitoring ▪ Integrated voltage regulation (optional) ▪ SCADA – IEC 60870-5-101 – IEC 60870-5-103 – IEC 60870-5-104

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 26 4453918/14 EN ETOS® TD – IEC 61850 (edition 1 and edition 2) – Modbus (RTU, TCP, ASCII) – DNP3 ▪ Free digital inputs and outputs, depending on the device configuration ▪ Free analog inputs and outputs, depending on the device configuration 4.4 Operating modes You can select the operating mode of the motor-drive unit with the control switch in the control cabinet [►Section 4.5.3, Page 29]. Depending on the version of the motor-drive unit, the control switch is designated with S32 (without voltage regulation) or S132 (with voltage regulation). You can oper- ate the motor-drive unit in the following operating modes: LOCAL (S32/S132 in position LOC) In the Local operating mode, you can operate the motor-drive unit via control switch S3 only. Commands via SCADA are not possible. There is no auto- matic voltage regulation. REMOTE (S32/S132 in position REM) In the Remote operating mode, you can operate the motor-drive unit via ex- ternal keys or SCADA commands only depending on the setting of the Re- mote behavior [►Page 76] parameter. Automatic voltage regulation is pos- sible (optional). AUTO (S132 in position AUTO, only with option "Automatic voltage regulation") In the Auto operating mode you can activate automatic voltage regulation. You cannot actuate the motor-drive unit manually in this mode. Commands via SCADA are possible depending on the setting of the Remote behavior [►Page 76] parameter. LOCAL REMOTE AUTO Control using S3 control switch Yes No No Control using digital inputs No Yes No Control using SCADA1) No Yes Yes Automatic voltage regulation3) No Yes Yes Table 8: Overview of operating modes 1) Optional when connecting the motor-drive unit to a control system (SCADA) 2) You can use the Remote behavior [►Page 76] parameter to set the be- havior 3) Only with "Voltage regulation" option, function can be activated/deactivated using digital inputs or SCADA

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 27 4453918/14 EN ETOS® TD 4.5 Design This chapter contains an overview of the design of the motor-drive unit. The entire system consisting of the on-load tap-changer and motor-drive unit in- cludes the following subassemblies: Figure 3: Design 1 On-load tap-changer 3 Connecting cable 2 Gear motor 4 Control cabinet

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 28 4453918/14 EN ETOS® TD 4.5.1 Name plate The name plate is in the control cabinet of the motor-drive unit. Figure 4: Name plate 1 Name plate 4.5.2 Gear motor The gear motor is on the head of the on-load tap-changer. It is connected di- rectly to the drive shaft of the on-load tap-changer and carries out the on- load tap change operation. The gear motor is delivered pre-installed with the on-load tap-changer and does not normally have to be uninstalled. Figure 5: Gear motor

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 29 4453918/14 EN ETOS® TD 4.5.3 Control cabinet The control cabinet contains the following components: Figure 6: Control cabinet 1 Tap position display 2 Control switch 3 Ethernet interface ETH1.1 (RJ45) 4 Plug socket X19, max. 10 A 5 Motor protective switch Q1 6 Fuses F14 and F25

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 30 4453918/14 EN ETOS® TD Operating controls The control cabinet contains the following operating controls: Figure 7: Operating controls 1 Control switch S32 LOC/REM or S132 LOC/AUTO/REM 2 Control switch S3 RAISE/LOWER Display elements The control cabinet contains the following display elements: Figure 8: Display elements 1 Motor running LED 2 Event yellow/red LED 3 Tap position display 4 Operation counter

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 31 4453918/14 EN ETOS® TD Cable duct for digital inputs and outputs If you would like to connect digital inputs and outputs of the DIO assembly, a cable duct is available in the control cabinet to route the cable harness. Figure 9: Cable duct for digital inputs and outputs (example of control cabinet structure) 1 Cable duct in the control cabinet 4.5.4 ISM® assemblies 4.5.4.1 CPU (central processing unit) I The CPU I assembly is the central processing unit for the device. It contains the following interfaces: ▪ Internal system interface RS232 (COM1) ▪ Serial interface RS232/485 (COM2)

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 32 4453918/14 EN ETOS® TD ▪ 3x Ethernet (ETH1, ETH 2.1, ETH 2.2) ▪ USB (USB 2.0) ▪ 2x CAN bus (CAN 1, CAN 2) CPU CAN 1 1 9 CAN 2 1 9 COM 1 1 9 COM 2 1 9 - + 24V DC RUN INIT ERR USB2.0 4 6 2 A 8 C H TEST PROG RUN 4 6 2 A E 0 8 C L ETH 1 ETH 2.1 ETH 2.2 Figure 10: CPU I assembly 4.5.4.2 CPU (central processing unit) II The CPU II assembly is the central computing unit for the device. It contains the following interfaces: ▪ Internal system interface RS232 (COM1) ▪ Serial interface RS232/485 (COM2) ▪ 3x Ethernet (ETH 1, ETH 2.1, ETH 2.2) ▪ USB (USB 2.0) ▪ 2x CAN bus (CAN 1, CAN 2) CPU CAN 1 1 9 CAN 2 1 9 COM 1 1 9 COM 2 1 9 - + 24V DC RUN INIT ERR USB2.0 4 6 2 A 8 C H TEST PROG RUN 4 6 2 A E 0 8 C L ETH 1 ETH 2.1 ETH 2.2 Figure 11: CPU assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 33 4453918/14 EN ETOS® TD 4.5.4.3 Voltage measurement and current measurement The UI 1 assembly is used for measuring 1-phase voltage and current. Figure 12: UI 1 assembly The UI 3 assembly is used for measuring 3-phase voltage and current. Figure 13: UI 3 assembly Warning of a danger point. Read the information given in the product oper- ating instructions. Warning of dangerous electrical voltage. This assembly is protected via double insulation or reinforced insulation. Table 9: Safety-relevant symbols on the assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 34 4453918/14 EN ETOS® TD 4.5.4.4 UI 5-4 voltage measurement and current measurement The UI 5-4 assembly is used for measuring 3-phase voltage and current. Figure 14: UI 5-4 assembly Warning of a danger point. Read the information given in the product oper- ating instructions. Warning of dangerous electrical voltage. This assembly is protected via double insulation or reinforced insulation. Table 10: Safety-relevant symbols on the assembly 4.5.4.5 Digital inputs and outputs The assemblies DIO 28-15 and DIO 42-20 (HL) provide you with a number of digital inputs and outputs that differs based on the version: ▪ DIO 28-15: 28 inputs, 15 outputs (6 N/O contacts, 9 change-over con- tacts) ▪ DIO 42-20 (HL): 42 inputs, 20 outputs (8 N/O contacts, 12 change-over contacts)

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 35 4453918/14 EN ETOS® TD Figure 15: DIO 42-20 assembly Warning of a danger point. Read the information given in the product oper- ating instructions. Warning of dangerous electrical voltage. Table 11: Safety-relevant symbols on the assembly 4.5.4.6 Analog inputs and outputs The AIO 2 and AIO 4 assemblies provide analog inputs and outputs: ▪ AIO 2: 2 channels ▪ AIO 4: 4 channels In accordance with the device configuration, the AIO assembly supports one of the following signal types: Input Output Voltage Current Voltage Current 0...10 V 0...20 mA 4...20 mA 0...10 V 0...20 mA 4...20 mA Resistance measurement (such as PT100, resistor contact series) Table 12: Signal types supported by the AIO assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 36 4453918/14 EN ETOS® TD Figure 16: AIO 4 assembly 4.5.4.7 Media converter The MC 2-2 assembly is a media converter, which converts 2 electrical con- nections (RJ45) to one fiber-optic cable connection each. Each is converted independently of the other. The following interfaces are available: ▪ 2x RJ45 (ETH12, ETH22) ▪ 2x Duplex-LC (SFP module) (ETH11, ETH21) The media converter is designed to be transparent for the network and does not have its own IP address. Figure 17: MC 2-2 assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 37 4453918/14 EN ETOS® TD 4.5.4.8 Media converter with managed switch The assembly SW 3-3 is a media converter with managed switch. It com- bines two independent functions and provides you with the following inter- faces: ▪ A media converter converts an electric connection (RJ45) into a fiber-optic cable connection – RJ45 (ETH12) – Duplex-LC (SFP module) (ETH11) ▪ Managed switch with redundancy function (PRP or RSTP) – 2x RJ45 (ETH23, ETH24), device-internal connection – 2x Duplex-LC (SFP module) (ETH21, ETH22), redundancy connection The following redundancy functions are available to you according to your order: ▪ PRP (standard setting) ▪ RSTP Figure 18: SW 3-3 assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 38 4453918/14 EN ETOS® TD 4.6 Visualization 4.6.1 Main screen The web-based visualization is split into various areas. Figure 19: Main screen 1 Display area 2 Secondary navigation 3 Primary navigation 4 Status bar The most important measured values of the transformer are displayed on the main screen. The individual status displays of the transformer shown can be selected directly when accessing them via the web browser. They act as links to the corresponding menu items. If you are operating the device via the front panel, you are only able to call up the elements via the Information menu. If the device does not have one of the optional functions, this will be indi- cated in the main screen via a small padlock . Depending on the device configuration, the main screen displays the schematic representation of a transformer for network applications or a transformer for industrial applications.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 39 4453918/14 EN ETOS® TD 4.6.1.1 Transformer for network applications Figure 20: Transformer data 1 DGA (status) 2 Top-oil temperature 3 Hot-spot temperature 4 Cooling system (status) 5 Load current and load voltage of phases L1, L2, L3 6 Transformer name Figure 21: Apparent power, oil level, and ambient temperature 1 Asset intelligence 2 Total apparent power 3 Ambient temperature 4 Oil level (transformer on left, on- load tap-changer on right)

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 40 4453918/14 EN ETOS® TD Figure 22: On-load tap-changer and motor-drive unit 1 OLTC oil temperature 2 Current tap position 3 Voltage regulator 4 Tap-change operation statistics 5 OLTC status message (collective message) 4.6.1.2 Transformer for industrial applications Figure 23: Transformer data 1 DGA (status) 2 Top-oil temperature 3 Hot-spot temperature 4 Cooling system (status) 5 Load current an load voltage of the phases L1, L2, L3 (high-voltage side) 6 Transformer name

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 41 4453918/14 EN ETOS® TD Figure 24: Apparent power, oil level, and ambient temperature 1 Asset intelligence 2 Total apparent power 3 Ambient temperature 4 Oil level (transformer on left, on- load tap-changer on right) Figure 25: On-load tap-changer and motor-drive unit 1 OLTC oil temperature 2 Current tap position 3 Voltage regulator 4 Tap-change operation statistics 5 OLTC status message (collective message)

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 42 4453918/14 EN ETOS® TD 4.6.2 Additional operating controls and display elements when using the MControl touch panel (optional) If you are using the device with the optionally available MControl touch panel, additional operating controls and display elements are displayed on the left edge of the screen. Depending on the device configuration, a variety of keys are available: Figure 26: Additional display elements and operating controls Status LED status Status display 1) REMOTE key Select the operating mode: ▪ On: REMOTE ▪ Off: LOCAL 2) AVR AUTO key Activate auto mode. 2) RAISE key Send a control command to the motor-drive unit to increase the voltage. Only possible in manual mode. 2) AVR Manual key Activate manual mode. 2) LOWER key Send a control command to the motor-drive unit to reduce the voltage. Only possible in manual mode. 1) Not available if local/remote is toggled using a digital input. 2) Only available in the "Automatic voltage regulation" function package. 4.6.3 Operating concept You can operate the device using the web-based ISM™ Intuitive Control In- terface visualization via a PC.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 43 4453918/14 EN ETOS® TD User rights and user roles The device is equipped with a rights system and a roles system. The display and access rights to device settings or events can therefore be controlled at user level. You can configure the rights system and roles system to meet your require- ments. You will find more information on user rights and user roles in the User administration [►Section 9.34, Page 278] section. You can only modify the device settings or parameters if you have the nec- essary user rights. Logging on, logging off and changing users The control of access rights to device settings and parameters is user- based. Various users can log in at the same time (e.g. via the visualization) and access the device. To log in as a user, proceed as follows: 1. Select the LOGIN or CHANGE button in the status line. 2. Enter your user name and password and select the OK button. ð The name of the logged-in user appears in the status line. To log out as a user, proceed as follows: ►Press the LOGOUT button in the status line. Navigation If you are operating the device using the web-based visualization, you can navigate by clicking on the appropriate buttons. Example To navigate to the "Date" parameter, proceed as follows: 1. Go to Settings. 2. Go to Parameters. 3. Go to Time synchronization. 4. Select Time. In these operating instructions, the path for navigating to a parameter is al- ways shown in an abridged form: Go to Settings > Parameters > Time syn- chronization.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 44 4453918/14 EN ETOS® TD Parameter search You can use the quick search function in the parameter menu to search for a parameter. Enter the name of the desired parameter in the Search entry field. Figure 27: Quick search Expert mode The device has an expert mode for entering the parameters. You can enter the parameters directly into the overview screen of the respective menu in this mode. Figure 28: Expert mode To activate the expert mode, proceed as follows: 1. Go to Settings > Parameters. 2. Select the Expert mode checkbox. ð Expert mode is active.

4 Product description

Maschinenfabrik Reinhausen GmbH 2020 45 4453918/14 EN ETOS® TD Hiding/showing parameters Depending on how you set the parameters, the device will hide or show ad- ditional parameters related to this function.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2020 46 4453918/14 EN ETOS® TD 5 Packaging, transport and storage 5.1 Packaging The products are sometimes supplied with sealed packaging and sometimes in a dry state, depending on requirements. Sealed packaging surrounds the packaged goods with plastic foil on all sides. Products that have also been dried are identified by a yellow label on the sealed packaging. In the dry state, delivery is also possible in a transport container. The information in the following sections should be applied as appropriate. 5.1.1 Suitability NOTICE Property damage due to incorrectly stacked crates! Stacking the crates incorrectly can lead to damage to the packaged goods. ►The outer marking on the packaging states if, for example, the on-load tap-changer or selector has been packed upright. Never stack these crates. ►General rule: Do not stack crates above a height of 1.5 m. ►For other crates: Only stack up to 2 equally sized crates on top of one an- other. The packaging is suitable to ensure undamaged and fully functional means of transportation in compliance with local transportation laws and regula- tions. The packaged goods are packed in a sturdy crate. This crate ensures that, when in the intended transportation position, the packaged goods are stabi- lized to prevent impermissible changes in position, and that none of the parts touch the loading surface of the means of transport or touch the ground after unloading. Sealed packaging surrounds the packaged goods with plastic foil on all sides. The packaged goods are protected from humidity using a desiccant. The plastic foil was bonded after the desiccant is added.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2020 47 4453918/14 EN ETOS® TD 5.1.2 Markings The packaging bears a signature with instructions for safe transport and cor- rect storage. The following symbols apply to the shipment of non-hazardous goods. Adherence to these symbols is mandatory. Protect against moisture Top Fragile Attach lifting gear here Center of mass Table 13: Shipping pictograms 5.2 Transportation, receipt and handling of shipments WARNING Danger of death or severe injury! Danger of death or serious injuries due to tipping or falling load. ►Only transport the crate when closed. ►Do not remove the securing material used in the crate during transport. ►If the product is delivered on a pallet, secure it sufficiently. ►Only trained and authorized persons may select the sling gear and se- cure the load. ►Do not walk under the suspended load. ►Use means of transport and lifting gear with a sufficient carrying capacity in accordance with the weight stated on the delivery slip. In addition to oscillation stress, jolts must also be expected during trans- portation. In order to prevent possible damage, avoid dropping, tipping, knocking over and colliding with the product. If a crate tips over, falls from a certain height (e.g. when slings tear) or is subject to an unbroken fall, damage must be expected regardless of the weight. Every delivered shipment must be checked for the following by the recipient before acceptance (acknowledgment of receipt): ▪ Completeness based on the delivery slip ▪ External damage of any type The checks must take place after unloading when the crate or transport con- tainer can be accessed from all sides.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2020 48 4453918/14 EN ETOS® TD Visible damage If external transport damage is found upon receipt of the shipment, proceed as follows: ▪ Immediately record the identified transport damage in the shipping docu- ments and have this countersigned by the carrier. ▪ In the event of severe damage, total loss or high damage costs, immedi- ately notify the manufacturer and the relevant insurance company. ▪ After identifying damage, do not modify the condition of the shipment fur- ther and retain the packaging material until an inspection decision has been made by the transport company or the insurance company. ▪ Record the details of the damage immediately on site together with the carrier involved. This is essential for any claim for damages. ▪ Photograph damage to packaging and packaged goods. This also applies to signs of corrosion on the packaged goods due to moisture inside the packaging (rain, snow, condensation). ▪ NOTICE! Damage to packaged goods due to damaged sealed packag- ing. If the product is delivered in sealed packaging, check the sealed packaging immediately. If the sealed packaging is damaged, do not under any circumstances install or commission the packaged goods. Either re- dry the dried packaged goods as per the operating instructions, or contact the manufacturer to agree on how to proceed. ▪ Identify the damaged parts. Hidden damage When damages are not determined until unpacking after receipt of the ship- ment (hidden damage), proceed as follows: ▪ Make the party responsible for the damage liable as soon as possible by telephone and in writing, and prepare a damage report. ▪ Observe the time periods applicable to such actions in the respective country. Inquire about these in good time. With hidden damage, it is very hard to make the transportation company (or other responsible party) liable. Any insurance claims for such damages can only be successful if relevant provisions are expressly included in the insur- ance terms and conditions. 5.3 Storage of shipments Packaged goods dried by Maschinenfabrik Reinhausen Upon receipt of the shipment, immediately remove the packaged goods dried by Maschinenfabrik Reinhausen from the sealed packaging and store air-tight in dry insulating fluid until used if the packaged goods were not sup- plied in insulating fluid. Non-dried packaged goods Non-dried packaged goods but with a functional sealed packaging can be stored outdoors when the following conditions are complied with.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2020 49 4453918/14 EN ETOS® TD When selecting and setting up the storage location, ensure the following: ▪ Protect stored goods against moisture (flooding, water from melting snow and ice), dirt, pests such as rats, mice, termites and so on, and against unauthorized access. ▪ Store the crates on timber beams and planks as a protection against ris- ing damp and for better ventilation. ▪ Ensure sufficient carrying capacity of the ground. ▪ Keep entrance paths free. ▪ Check stored goods at regular intervals. Also take appropriate action after storms, heavy rain or snow and so on. Protect the packaging foil from direct sunlight so that it does not disintegrate under the influence of UV rays, which would cause the packaging to lose its sealing function. If the product is installed more than 6 months after delivery, suitable mea- sures must be taken without delay. The following measures can be used: ▪ Correctly regenerate the drying agent and restore the sealed packaging. ▪ Unpack the packed goods and store in a suitable storage space (well ven- tilated, as dust-free as possible, humidity < 50% where possible). 5.4 Unpacking shipments and checking for transportation damages ▪ NOTICE! Transport the packaged crate to the place where installation will take place. Do not open the sealed packaging until just before installation. If this is not done, damage to the packaged goods may occur due to inef- fectively sealed packaging. ▪  WARNING! When unpacking, check the condition of the packaged goods. Secure packaged goods in an upright crate from tipping out. If this is not done, the packaged goods may be damaged and serious injuries may result. ▪ Check completeness based on the delivery slip. Attachment points for lifting gears WARNING Danger of death and damage to property! Danger of death and damage to property due to tipping or falling load! ►Only trained and appointed persons may select the sling gear and secure the load. ►Do not walk under the hanging load. ►Use means of transport and lifting gear with a sufficient carrying capacity in accordance with the weight stated in the Technical data [►Section 15, Page 327] section. ▪ Control cabinet: – Retractable brackets on top left and right, opening size 25 x 25 mm.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2020 50 4453918/14 EN ETOS® TD Figure 29: Control cabinet lifting gear limit stop –  WARNING! The cable angle of the lifting gear must always be less than 45° in relation to the vertical. Otherwise, the control cabinet may be damaged and serious injuries may result. Figure 30: Maximum permissible cable angle for the control cabinet lifting gear limit stop ▪ Gear motor: – Lifting using the slip around the gear motor –  WARNING! Only suitable for lifting the gear motor. Use the on-load tap-changer attachment points to lift the entire on-load tap-changer. Otherwise, the gear motor and on-load tap-changer may be damaged and serious injuries may result.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2020 51 4453918/14 EN ETOS® TD Figure 31: Slip for lifting the gear motor

Maschinenfabrik Reinhausen GmbH 2020

52 4453918/14 EN ETOS® TD 6 Mounting This chapter describes how to correctly install and connect the device. WARNING Danger of death or severe injury! An energized transformer and energized on-load tap-changer components can cause death or serious injuries during installation of the drive! ►Ensure the de-energized state of the transformer and on-load tap- changer components during installation of the drive. 6.1 Fitting the control cabinet to the transformer Alternatively, you can secure the control cabinet to another point away from the transformer. The supplied connection cable between the control cabinet and the gear motor is 6.5 m long. If required, you can contact Maschinenfab- rik Reinhausen GmbH for other lengths. The control cabinet has four fixing attachments on the rear to secure it. 1. Attach four stud bolts (not supplied by MR) to the transformer tank. Figure 32: Fastening the stud bolts Type A ± 15 mm B ± 2 mm S (850 mm) 575 mm 500 mm L (1350 mm) 575 mm 500 mm XL (1800 mm) 790 mm 1290 mm

Maschinenfabrik Reinhausen GmbH 2020

53 4453918/14 EN ETOS® TD 2. For control cabinets with vibration damper: Attach the vibration damper to the control cabinet. Figure 33: Vibration damper 3. Use the fixing attachments to attach the control cabinet to the stud bolts and align it vertically on the transformer tank. Figure 34: Attaching the control cabinet

Maschinenfabrik Reinhausen GmbH 2020

54 4453918/14 EN ETOS® TD 4. NOTICE! Damage to the control cabinet due to mechanical tension. Se- cure the control cabinet without subjecting it to mechanical tension. Figure 35: Securing the drive 5. Connect the grounding cable to the control cabinet and transformer tank, holding it against the control cabinet using a wrench (wrench size 36). Figure 36: Connecting the grounding cable to the control cabinet

Maschinenfabrik Reinhausen GmbH 2020

55 4453918/14 EN ETOS® TD 6.2 Cable recommendation Please note the following Maschinenfabrik Reinhausen GmbH recommenda- tion when wiring the device. ▪ Excessive line capacitance can prevent the relay contacts from interrupt- ing the contact current. In control circuits operated with alternating current, take into account the effect of the line capacitance of long control cables on the function of the relay contacts. ▪ If you want to route Ethernet connections from a control cabinet or build- ing, we recommend using fiber-optic cables (in accordance with the IEC 61850-90-4 recommendation). ▪ Ensure that the copper cables used have a temperature resistance of 70°C. Cable Assembly Type Cross section Material Max. length Power supply X1 Unshielded 2.5 mm² Copper - Voltage measurement X10 (UI1/3) Shielded 2.5 mm² Copper - Current measurement X10 (UI1/3) Unshielded 4 mm² Copper - Digital signal inputs DIO 28-15, DIO 42-20 Shielded 1.5 mm2 Copper 400 m (<25 Ω/km) Digital signal outputs* DIO 28-15, DIO 42-20 Shielded 1.5 mm2 Copper - Analog signal inputs X6 (AIO 2/4) Shielded 1 mm2 Copper 400 m (<25 Ω/km) Analog signal outputs X6 (AIO 2/4) Shielded 1 mm2 Copper - RS232, SUB-D CPU I Shielded 0.25 mm2 - 25 m RS485, SUB-D CPU I Shielded 0.25 mm2 - 140 m CAN bus CPU I Shielded 0.75 mm² - 2000 m (entire CAN bus) Ethernet RJ45 CPU I Min. CAT5, shielded S/FTP - - 100 m Ethernet FO MC 2-2, SW 3-3 Duplex LC, 1310 nm - 2000 m Grounding connection Housing Unshielded 16 mm² Copper - Table 14: Recommendation for connection cables *) Observe line capacitance, see note above. 6.3 Information about connecting serial interfaces RS232 and RS485 NOTICE Damage to the device! Using the wrong data cable may damage the device. ►Only use data cables which comply with the description below.

Maschinenfabrik Reinhausen GmbH 2020

56 4453918/14 EN ETOS® TD RS232 (D-SUB 9-pole) To connect the device via the RS232 interface (COM2), use a data cable with the following structure: Figure 37: RS232 data cable (9-pole) RS485 (D-SUB 9-pole) To connect the device via the RS485 interface (COM2), use a data cable with the following structure: Figure 38: RS485 data cable

Maschinenfabrik Reinhausen GmbH 2020

57 4453918/14 EN ETOS® TD D-SUB 9-pole plug connection Only use 9-pole D-SUB plugs with the following characteristics: ▪ Plug housing is metallic or metal-plated ▪ Cable shielding is connected with the plug using one of the two following variants: – Shielding is screwed down with traction relief. – Shielding is soldered with plug housing. Figure 39: Example of a soldered shielding on a plug housing 6.4 Notes on connecting to the MR sensor bus The optionally available MR sensor bus function lets you connect digital and analog sensors to the device over Modbus RTU. The MR sensor bus sup- ports the connection of up to 31 sensors (Modbus slaves). The ISM® device operates as the Modbus master. Ensure that no other Modbus master is connected over the MR sensor bus. Assign a unique Modbus address to each sensor you are connecting over MR sensor bus. The MR sensor bus may experience errors if multiple sen- sors are using the same Modbus address. Observe the following notes for connecting the sensors: ▪ NOTICE! Damage to the device or sensor. Connect all of the sensors to the potential equalization rail to avoid circulating currents over the MR sensor bus. ▪ The MR sensor bus uses Modbus in a 2-wire configuration (2W). The 4- wire configuration (4W) is not supported. ▪ You must connect the sensors via a shielded line with 3 conductors (D0, D1, Common). The data lines (D0, D1) must be in twisted pairs. Note the cable recommendation. ▪ Stub lines from the bus node to the respective device must be shorter than 20 m.

Maschinenfabrik Reinhausen GmbH 2020

58 4453918/14 EN ETOS® TD ▪ The CPU assembly contains a terminating resistor (120 Ω) at the COM2 interface. Install another terminating resistor (120 Ω, 0.5 W) at the other end of the bus. ▪ The CPU assembly contains a pull-up resistor and a pull-down resistor (each of 680 Ω in accordance with the Modbus specification). No addi- tional pull-up/pull-down resistors are needed. CPU-COM2 Sensor 1 Sensor x D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 D0 (A) D1 (B) Com. (C) D0 (A) D1 (B) Com. (C) 120 Ω Figure 40: MR sensor bus

Maschinenfabrik Reinhausen GmbH 2020

59 4453918/14 EN ETOS® TD 6.4.1 MSENSE® DGA If you would like to use an MSENSE® DGA sensor, you must connect the sensor to the MR sensor bus in accordance with the following connection ex- amples. If the MSENSE® DGA sensor is the only bus device or the last bus device, you must use a terminating resistor (120 Ω, 0.5 W). CPU-COM2 MSENSE DGA 2/3 D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 D0 (A) D1 (B) Com. (C) 1 4 2 3 5 1 2 3 4 5 D1 (B) D0 (A) Figure 41: Connection example MSENSE® DGA 2/3 (connector M12, type A, 5-pole in accor- dance with IEC 61076-2-101) CPU-COM2 MSENSE DGA 5 D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 (PhoneB) (GND) X302:5 X302:4 X302:3 X302:2 X302:1 (OUTA) (OUTB) (PhoneA) Figure 42: Connection example MSENSE® DGA 5 (terminal X302)

Maschinenfabrik Reinhausen GmbH 2020

60 4453918/14 EN ETOS® TD CPU-COM2 MSENSE DGA 9 D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 (PhoneB) (GND) X304:5a X304:4b X304:3 X304:1a X304:1b (OUTA) (OUTB) (PhoneA) Figure 43: Connection example MSENSE® DGA 9 (terminal X304) 6.4.2 MESSKO® MTeC® EPT303 FO If you would like to use a MESSKO® MTeC® EPT303 FO sensor, you must connect the sensor to the RS485 plug terminals on the sensor bus. Use a shielding clamp to apply the shield to the cable. You can directly connect ad- ditional MESSKO® MTeC® EPT303 FO sensors to the plug terminal. The EPT303 FO sensor module contains a terminating resistor. If you would like to use the EPT303 FO sensor together with other sensor types on an MR sensor bus, then we recommend connecting the EPT303 FO sensor to the end of the bus. CPU-COM2 EPT303 FO D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 D+ (B) GND D- (A) D+ (B) GND D- (A) 1 2 3 4 5 6 1 6 Figure 44: Connection example MESSKO® MTeC® EPT303 FO (terminal RS485)

Maschinenfabrik Reinhausen GmbH 2020

61 4453918/14 EN ETOS® TD 6.4.3 MESSKO® MTRAB® 2.5 If you would like to use a MESSKO® MTRAB® 2.5 sensor, you must con- nect the sensor to the RS485 plug terminals on the sensor bus. CPU-COM2 MTRAB 2.5 D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 D+ | Rx+ D- | Rx- Comm Tx- Tx+ Shield Figure 45: Connection example MESSKO® MTRAB® 2.5 (terminal RS485) You must enable the half-duplex operating mode on the sensor by switching the "Duplex mode" switch to the "HALF" setting. If the MESSKO® MTRAB® 2.5 sensor is the only bus device or the last bus device, you must activate the sensor terminating resistor by switching the "BUS termination 120 ohms" switch to the position "1 = ON" and "2 = OFF". Figure 46: MESSKO® MTRAB® 2.5 Modbus configuration 1 Terminating resistor: in half duplex mode: 1 = ON, 2 = OFF; in full du- plex mode: 1 = ON, 2 = ON 2 Operating mode: HALF = half du- plex, FULL = full duplex 3 Modbus address

Maschinenfabrik Reinhausen GmbH 2020

62 4453918/14 EN ETOS® TD 6.4.4 MSENSE®-FO ECU-I/S If you would like to use an MSENSE®-FO ECU-I or ECU-S sensor, you must connect the sensor to the RS485 plug terminals on the sensor bus. Use a shielding clamp to apply the shield to the cable. If the MSENSE®-FO sensor is the only bus device or the last bus device, you must use a terminating re- sistor (120 Ω, 0.5 W). You must activate the half-duplex, 2-conductor operat- ing mode on the sensor via the MSET-FO configuration software. CPU-COM2 MSENSE®-FO D0 (A) D1 (B) Com. (C) 1 2 3 4 5 6 7 8 9 Tx+ 1 2 3 4 5 Tx- Rx+ Rx- GND Figure 47: Connection example MSENSE®-FO ECU-I and ECU-S (terminal RS485) 6.5 Information about connecting analog sensors NOTICE Damage to the device and sensors! Incorrectly connected and configured analog inputs/outputs may result in damage to the device and sensor. ►Follow information about connecting analog sensors [►Section 6.5, Page 62]. ►Configure analog inputs and outputs according to the connected sensors.

Maschinenfabrik Reinhausen GmbH 2020

63 4453918/14 EN ETOS® TD The AIO assembly has a separate plug connector for each channel (input or output). The plugs are assigned as follows: 1 3 2 4 5 11 13 12 14 15 6 8 7 9 10 16 18 17 19 20 RDY AIO + - 24V DC 1 3 2 4 5 1 2 3 4 5 Figure 48: Plug assignment of the AIO module (illustration using module AIO 4 as an example) Interface Pin Description 1 6 11 16 I OUT (+): Current output + 2 7 12 17 I/U IN (+) U OUT (+): Voltage input +, current input +, voltage output + 3 8 13 18 I/U IN (-): Voltage input -, current in- put - 4 9 14 19 I/U OUT (-): Voltage output -, current output - 5 10 15 20 Not used Table 15: Analog inputs and outputs You can connect the following types of analog sensors: ▪ 4...20 mA ▪ PT100/PT1000 (2-wire, 3-wire, 4-wire)

Maschinenfabrik Reinhausen GmbH 2020

64 4453918/14 EN ETOS® TD 4...20 mA sensor You must connect a 4...20 mA sensor to the pins and . You must also connect the supplied bridge to the pins , , and . I OUT (+) I/U IN (+) U OUT (+) I/U IN (-) I/U OUT (+) 1 2 3 4 5 --- 4...20 mA signal source Figure 49: Connection example for a 4...20 mA sensor PT100/PT1000 sensor Depending on type, you must connect a PT100 sensor or PT1000 sensor as follows: ▪ 2-wire: pin and ▪ 3-wire: pin , and ▪ 4-wire: pin , , , and I OUT (+) I/U IN (+) U OUT (+) I/U IN (-) I/U OUT (+) 1 2 3 4 5 --- 2-wire I OUT (+) I/U IN (+) U OUT (+) I/U IN (-) I/U OUT (+) 1 2 3 4 5 --- 3-wire I OUT (+) I/U IN (+) U OUT (+) I/U IN (-) I/U OUT (+) 1 2 3 4 5 --- 4-wire PT100/PT1000 Figure 50: Connection example for a PT100/PT1000 sensor

Maschinenfabrik Reinhausen GmbH 2020

65 4453918/14 EN ETOS® TD 6.6 Information about screening the cables for analog signals In order to correctly record the analog signals, you must place the cable screening in the motor-drive unit on the grounding bar. The cable shielding should be removed as late as possible before connecting to keep the section with unshielded cables as short as possible. The shielding must be con- nected with shielding clips. 1 3 2 4 5 11 13 12 14 15 6 8 7 9 10 16 18 17 19 20 RDY AIO 4 + - 24V DC 11 12 13 14 15 16 17 18 20 19 1 2 3 4 5 6 7 8 9 10 Figure 51: Examples of supporting screening on ground bar (on left: Direct connection to AIO assembly, on right: Connection using line-up terminal) 6.7 Information about laying fiber-optic cable To ensure the smooth transfer of data via the fiber-optic cable, you must en- sure that mechanical loads are avoided when laying the fiber-optic cable and later on during operation. Also observe the information from the manufac- turer of the fiber-optic cable and the following instructions: ▪ Radii must not fall below the minimum permissible bend radii (do not bend fiber-optic cable). ▪ The fiber-optic cables must not be over-stretched or crushed. Observe the permissible load values. ▪ The fiber-optic cables must not be twisted. ▪ Be aware of sharp edges because they can damage the fiber-optic cable's coating during laying or can place mechanical loads on the coating later on. ▪ Provide a sufficient cable reserve near distributor cabinets. Lay the re- serve such that the fiber-optic cable is neither bent nor twisted when tight- ened.

Maschinenfabrik Reinhausen GmbH 2020

66 4453918/14 EN ETOS® TD 6.8 Connecting motor-drive unit NOTICE Damage to the connecting cable! Damage to the connecting cable due to impermissibly small bend radiuses and kinks. ►When routing the connection cable, observe the minimum bend radiuses: min. 51 mm for fixed routing, min. 170 mm if moved occasionally. ►When routing the connection cable, make sure that the maximum permit- ted cable jacket temperature of 80 °C is not exceeded during operation. You may only connect the control cabinet to circuits with an external over- current protection device and an isolating device with all poles disconnected so the equipment can be fully de-energized if required (service, maintenance etc.). Suitable equipment includes isolating devices in accordance with IEC 60947-1 and IEC 60947-3 (e.g. circuit breakers). Observe the properties of the relevant circuits (voltage, maximum currents) when selecting the cir- cuit breaker type. In addition, observe the following: ▪ It must be easy for the operator to access the isolating device ▪ The isolating device must be labeled for the device and circuits to be iso- lated ▪ The isolating device may not be a part of the power line ▪ The isolating device may not interrupt the main protective conductor You must connect the power supply circuit with a conductor cross-section of at least 2.5 mm2 (AWG 13) and protect it with a miniature circuit breaker. Se- lect the miniature circuit breaker based on the product's electrical power data (voltage and current, see nameplate) and the internal wiring's conductor cross-sections (see connection diagram). ▪ Max. 10 A at 0.75 mm² ▪ Max. 16 A at 1.5...2.5 mm² You have to connect the motor-drive unit to an uninterruptible power supply to be able to switch the on-load tap-changer if the power supply fails. To connect the motor-drive unit proceed as follows: ü The control cabinet is installed at the desired location. ü Use only the specified cables for wiring. Note cable recommendation [►Section 6.2, Page 55]. 1. Remove and dispose of the transport protective cap for the plug connector of the gear motor.

Maschinenfabrik Reinhausen GmbH 2020

67 4453918/14 EN ETOS® TD 2. Connect the connection cable provided to the plug connector of gear mo- tor. Connect the other end of the connection cable to the terminal in the control cabinet in accordance with the connection diagram provided. Figure 52: Connecting the connection cable to the gear motor 3. Connect the grounding cable to the ground connection of the gear motor and connect it to the ground connection on the on-load tap-changer head or transformer. Figure 53: Connection of the grounding cable on the grounding bar of the gear motor 1 Grounding bar

Maschinenfabrik Reinhausen GmbH 2020

68 4453918/14 EN ETOS® TD 4. Connect the shield of the connection cable provided (electrical connection between control cabinet and gear motor) using shielded clamps on the grounding bar in the control cabinet. Figure 54: Connection of the shielded clamps on the grounding bar of the control cabinet 1 Grounding bar Tighten cable screw connections on control cabinet to the following tighten- ing torques: M20: 8 Nm, M32: 20 Nm. 5. Optional: Connect digital inputs and outputs, analog sensors, voltage measurement and current measurement of the transformer in accordance with the connection diagram. For shielded cables, place the cable shield on the grounding bar in the control cabinet. 6. Connect the power supply of the control cabinet in accordance with the connection diagram provided. 7. Engage the motor protective switch Q1 in the control cabinet.

Maschinenfabrik Reinhausen GmbH 2020

69 4453918/14 EN ETOS® TD 7 Commissioning 7.1 Performing tests Please contact Maschinenfabrik Reinhausen GmbH (MR) if any aspect of the tests is not clear. 7.1.1 Function test of the motor-drive unit WARNING Risk of death or severe injury! Danger of death or severe injury due to electrical voltage and incorrect as- sembly! ►Ensure that the motor-drive unit is connected in accordance with the con- nection diagrams provided. ►Ensure protection against contact; the cover plates must be closed. ►Ensure that the gear motor and on-load tap-changer head cover are fas- tened properly. NOTICE Damage to the on-load tap-changer! Damage to the on-load tap-changer by actuating the on-load tap-changer without oil. ►Make sure that the selector is fully immersed in transformer oil and that the oil compartment of the on-load tap-changer is completely filled with oil. To check that the motor-drive unit is functioning, proceed as follows: 1. Synchronize motor-drive unit [►Section 9.19, Page 178]. 2. Move motor-drive unit into the lowest operating position. 3. Lower tap position of motor-drive unit once more. ð Motor-drive unit tap position may not change since it is in the end posi- tion. 4. Move motor-drive unit into the highest operating position. 5. Raise tap position of motor-drive unit once more. ð Motor-drive unit tap position may not change since it is in the end posi- tion. ð The motor-drive unit function test is completed. Contact Maschinenfabrik Reinhausen if faults occurred during the function test. 7.1.2 High-voltage tests on the transformer Note the following points before performing high-voltage tests on the trans- former:

Maschinenfabrik Reinhausen GmbH 2020

70 4453918/14 EN ETOS® TD ▪ Ensure that the oil compartment of the on-load tap-changer is completely filled with insulating fluid. ▪ Ensure that all protective devices for the on-load tap-changer are function- ing correctly and are ready for use. ▪ Ensure that the ground connections on the motor-drive protective housing and protective housing fastening are free of paint. ▪ Only perform high voltage test if motor-drive unit door is closed. ▪ Disconnect external connections to electronic components in the motor- drive unit to prevent damage from overvoltage. ▪ When connecting the motor-drive unit's supply voltage, only use the cable bushings in the protective housing base intended for lead insertion. ▪ Guide all ground connecting leads to one central connection point (estab- lishment of suitable reference earth). ▪ Disconnect all electronic components before the high voltage test. Before a dielectric test of the wiring, remove all devices with a withstand voltage of < 1000 V. ▪ Remove leads used for testing before the high voltage test as these func- tion as antennas. ▪ Wherever possible, route the measurement leads and data leads sepa- rately to the energy cables. Contact the manufacturer if you have any questions about possible sources of danger. 7.1.3 Dielectric tests on transformer wiring Note the following points for dielectric tests on the transformer wiring: The motor-drive unit is put through dielectric tests before delivery. ►Before the dielectric test for the transformer wiring, disconnect drive from the section to be tested to rule out increased component loading for those components fitted in the motor-drive unit. 7.2 Transporting transformer to the operating site You can leave the motor-drive unit completely on the transformer if you would like to transport the transformer to the installation location. If you have to remove the gear motor for transporting the transformer, proceed as fol- lows: 1. Remove the connecting cable plug. 2. Remove gear motor screw connection on the on-load tap-changer head cover (3x M12). 3. Use lifting gear to remove gear motor from the on-load tap-changer head cover. 4. Cover exposed shafts and seals to protect them from dirt and damage. 5. Set the gear motor on the installation location of the transformer from above onto the on-load tap-changer head cover using the lifting gear.

Maschinenfabrik Reinhausen GmbH 2020

71 4453918/14 EN ETOS® TD 6. Tighten fixing screws (3x M12) using a tightening torque of 62 ± 6 Nm. 7. Connect gear motor [►Section 6.8, Page 66]. 7.3 Commissioning the transformer at the operating site Before commissioning the transformer, repeat the function tests. WARNING Danger of death or severe injury! Danger of death or severe injury due to incorrect operation. ►Only commission the transformer once the functions have been checked in accordance with section "Tests on the motor-drive unit". NOTICE Damage to motor-drive unit! Damage to the motor-drive unit due to condensate in the control cabinet. ►Always keep the control cabinet of the motor-drive unit tightly closed. ►In the event of operation interruptions of more than 8 weeks prior to initial use, connect and operate the anti-condensation heater in the control cab- inet. If this is not possible, place a sufficient amount of desiccant in the control cabinet.

Maschinenfabrik Reinhausen GmbH 2020

72 4453918/14 EN ETOS® TD 8 Operation 8.1 Actuating motor-drive unit locally To actuate the motor-drive unit locally, proceed as follows: ü Operating mode switch S32 or S132 is in the LOC position. ►Turn control switch S3 in the raise or lower direction. ð The motor-drive unit performs the tap-change operation. 8.2 Selecting the operating mode You can select the following operating modes: ▪ LOC (Local) ▪ REM (Remote) ▪ AUTO (only with option "Automatic voltage regulation") To select the operating mode, proceed as follows: ►Turn control switch S32 or S132 to the desired position. 8.3 Monitoring motor-drive unit WARNING Danger of death or severe injury! Danger of death or severe injury due to failure to observe the safety instruc- tions! ►Make sure that only trained technicians perform work on the motor-drive unit. ►Note relevant safety instructions. Monitoring of the motor-drive unit is limited to occasional visual inspections. For efficiency reasons these visual checks can be combined with the usual checks on the transformer. Pay particular attention to the following: ▪ Control cabinet seals ▪ Correct functioning of installed electrical heater in control cabinet of mo- tor-drive unit ▪ Seal integrity of the control cabinet's cable bushings

Maschinenfabrik Reinhausen GmbH 2020

73 4453918/14 EN ETOS® TD 9 Visualization The ETOS® TD motor-drive unit is equipped with web-based visualization . This allows you to configure the device with a computer and to display mea- sured values. System requirements To access the web-based visualization, you need a PC with an HTML5-ca- pable browser. The display is optimized for the following browsers: ▪ Microsoft® Internet Explorer 10 or higher ▪ Google Chrome™ 9.1 Establishing connection to visualization You can use the ETH1.1 interface or the optional ETH2.2 interface of the CPU assembly to establish the connection to the visualization. The inter- faces do not use a DHCP server. Therefore, you must assign a static IP ad- dress to your PC. To do this, observe the following configuration example: Interface Configuration Standard ETH1.1 IP address: 192.168.165.1 (not adjustable) PC IP address: 192.168.165.100 Subnet mask: 255.255.255.0 Optional ETH2.2 IP address: 192.0.1.230 (factory setting) [►Section 9.3, Page 79] Subnet mask: 255.255.255.0 PC IP address: 192.0.1.100 Subnet mask: 255.255.255.0 Table 16: Interface configuration example

Maschinenfabrik Reinhausen GmbH 2020

74 4453918/14 EN ETOS® TD Establishing a connection via the ETH1.1 interface To establish a connection via the ETH1.1 interface, proceed as follows: 1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the ETH1.1 interface. Figure 55: Establishing a connection via the front interface 2. Assign a unique IP address to the PC in the same subnet as the device (e.g. 192.168.165.100). 3. Enter the visualization's IP address http://192.168.165.1, or if SSL encryption is active enter https://192.168.165.1, in the browser on the PC. ð The visualization is accessed. Establishing a connection via the ETH2.2 interface on the CPU module (optional) The device is supplied with the IP address 192.0.1.230 at the factory. If you have changed the IP address, you can view the IP address in the Com- munication menu.

Maschinenfabrik Reinhausen GmbH 2020

75 4453918/14 EN ETOS® TD To connect via the ETH2.2 interface, proceed as follows: 1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the ETH2.2 interface. Figure 56: Establishing a connection via the ETH2.2 interface on the back 2. Assign a unique IP address to the PC in the same subnet as the device (e.g. 192.0.1.100). 3. Enter the visualization's IP address (e.g. http://192.0.1.230, if SSL encryption is active enter https://192.0.1.230) in the browser on the PC. ð The visualization is accessed. 9.2 General You can set general parameters in this menu item.

Maschinenfabrik Reinhausen GmbH 2020

76 4453918/14 EN ETOS® TD 9.2.1 Setting general device functions You can set general device functions with the following parameters. Settings Parameters General Name Value Language English Commissioning wizard Yes Auto-logout Off Time until auto-logout 15.0 min Measured value display Primary values Transformer name Transformer Remote behavior Hardware and SCADA USB interface Off Service user access activation Activated SNMP Agent Off Home Events Information Recorder Settings EN CHANGE REBOOTadmin 14.04.2020 14:22 Figure 57: General 1. Go to Settings > Parameters > System > General. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. Commissioning wizard You can use this parameter to set whether the commissioning wizard is to launch automatically when the device is restarted. Measured value display You can use this parameter to set whether the displayed measured values and control parameters are to refer to the primary side or secondary side of the measuring transducers. Transformer name You can use this parameter to enter a transformer name for identification purposes. The transformer name will be displayed on the main screen in the visualization. Remote behavior You can use this parameter to select the behavior of the device in remote operating mode. Depending on the device configuration, you can set the re- mote behavior as follows: ▪ Through the visualization (optional) ▪ By setting the digital inputs (optional)

Maschinenfabrik Reinhausen GmbH 2020

77 4453918/14 EN ETOS® TD You can select the following settings: Setting Description Hardware only The device accepts commands through digital inputs. SCADA only The device accepts commands via SCADA. Hardware and SCADA The device accepts commands via digital inputs and SCADA. Table 17: Selecting remote behavior USB interface You can use this parameter to deactivate the USB interface. You can select the following options: ▪ On: USB interface is activated ▪ Off: USB interface is deactivated 9.2.2 Set up automatic logout You can change the settings so that the device of a logged-in user automati- cally logs the user out after a certain period of inactivity. These settings apply to all users. If you have activated the Auto login [►Section 9.34.3, Page 281] function for a user, then this user will not be automatically logged out. Settings Parameters General Name Value Language English Commissioning wizard Yes Auto-logout Off Time until auto-logout 15.0 min Measured value display Primary values Transformer name Transformer Remote behavior Hardware and SCADA USB interface Off Service user access activation Activated SNMP Agent Off Home Events Information Recorder Settings EN CHANGE REBOOTadmin 14.04.2020 14:22 Figure 58: General 1. Go to Settings > Parameters > System > General. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter.

Maschinenfabrik Reinhausen GmbH 2020

78 4453918/14 EN ETOS® TD Auto logout You can use this parameter to activate th automatic logout function. Time until auto logout You can use this parameter to set the time period of inactivity after which a user is automatically logged out. 9.2.3 Activating/deactivating service user access The device is equipped with user access for the Maschinenfabrik Rein- hausen GmbH Technical Service department. This access is for error diag- nostics and troubleshooting in the event of device faults. Only activate ser- vice user access for a limited time period for remedying faults in order to safeguard IT security. If you deactivate the service user access and lose your password for the ad- ministrator role, it is not possible to reset the administrator password. If the administrator password is lost, the device must be reset to the default set- tings. When doing so, all information stored on the device (parameters, measured values, etc.) will be lost. Settings Parameters General Name Value Language English Commissioning wizard Yes Auto-logout Off Time until auto-logout 15.0 min Measured value display Primary values Transformer name Transformer Remote behavior Hardware and SCADA USB interface Off Service user access activation Activated SNMP Agent Off Home Events Information Recorder Settings EN CHANGE REBOOTadmin 14.04.2020 14:22 Figure 59: General You must be assigned the administrator role to set parameters. When in delivery status, you can log in as the administrator as follows: ▪ User name: admin ▪ Password: admin 1. Go to Settings > Parameters > System > General. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter.

Maschinenfabrik Reinhausen GmbH 2020

79 4453918/14 EN ETOS® TD 5. Restart the device to apply the change. Service user access activation You can use this parameter to activate or deactivate service user access. 9.3 Configuring the network You can configure the ETH 1 and ETH 2.2 network interfaces of the CPU as- sembly in this menu item. You can only set the parameters for ETH 1 if the device is equipped with the optional control system connection via Ethernet (TCP/IP): ▪ IEC 61850 ▪ IEC 60870-5-104 ▪ Modbus (Modbus type TCP active) ▪ DNP3 (DNP3 transmission type TCP active) ▪ MQTT You can only set the parameters for ETH 2.2 if the device is equipped with the optional interface for visualization. Settings Parameters Network ...ngs Name Value IP address Eth 1 192.168.10.254 Subnet mask Eth 1 255.255.255.0 Gateway address Eth 1 0.0.0.0 IP address Eth 2.2 192.0.1.230 Subnet mask Eth 2.2 255.255.255.0 Gateway address Eth 2.2 0.0.0.0 Visualization release Only ETH 2.x SSL/TLS encryption Off TLS version >= 1.0 Home Events Information Recorder Settings EN CHANGE REBOOTadmin 04.02.2020 11:14 Figure 60: Network settings 1. Go to Settings > Parameters > System > Network settings. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. IP address ETH 1/ETH 2.2 You can use this parameter to assign an IP address to the device.

Maschinenfabrik Reinhausen GmbH 2020

80 4453918/14 EN ETOS® TD Assign IP addresses to both web-based visualization and SCADA (optional) in different subnets. Otherwise you will not be able to establish a connec- tion. Subnet mask ETH 1/ETH 2.2 You can use this parameter to set the subnet mask. Be sure to enter a valid network mask that is not 0.0.0.0, otherwise it will not be possible to connect to the device. Gateway address ETH 1/ETH 2.2 You can use this parameter to set the gateway's IP address. If you set the value to 0.0.0.0, no gateway is used. Visualization release You can use this parameter to set the interfaces via which you can access the visualization: ▪ Only ETH 2.x ▪ ETH 1 and ETH 2.x You can only set this parameter if the device is equipped with the optional control system connection via Ethernet (TCP/IP) and the optional interface for visualization. SSL/TLS encryption You can use this parameter to set whether the process for accessing the vi- sualization should be carried out over an SSL/TLS-encrypted connection.

Maschinenfabrik Reinhausen GmbH 2020

81 4453918/14 EN ETOS® TD TLS version You can use this parameter to set the accepted TLS versions. If you would like to establish an encrypted connection to the visualization, you must use an accepted TLS version. You can select the following options: Option Accepted TLS versions >= 1.0 ▪ 1.0 ▪ 1.1 ▪ 1.2 >= 1.1 ▪ 1.1 ▪ 1.2 >= 1.21) ▪ 1.2 Table 18: TLS version 1) This option can be selected only if the TLS version is supported by the connected peripheral equipment. Activate DNS (optional) You can use this parameter to activate DNS for name resolution. If you would like to use the MQTT protocol, you can establish the connection to the MQTT via a DNS server as an option. Also set the parameters necessary for the MQTT [►Section 9.4, Page 81] protocol. DNS server (optional) You can use this parameter to set the IP address of the DNS server. 9.4 MQTT You can activate and configure the MQTT message protocol in this menu point. To do so, you must connect the device to an MQTT server (Broker) via Ethernet via the ETH 1 or ETH2.x interface on the CPU assembly. Note that the device will only send messages (publish). The receive message function is not active. There are 2 options available for configuring the protocol: ▪ Via the IP address of the MQTT server: – Enter the IP address as the broker address. – It is not necessary to configure a DNS server. ▪ Via DNS server: – Configure the DNS server in "Network settings". – Enter the URL as the broker address.

Maschinenfabrik Reinhausen GmbH 2020

82 4453918/14 EN ETOS® TD Settings Parameters MQTT Name Value Activate MQTT Off Broker address Broker port 8883 Client username Password SSL/TLS encryption Off Home Events Information Recorder Settings EN CHANGE REBOOTadmin 23.09.2020 09:23 Figure 61: MQTT ü When using a URL on the broker, it may be necessary to enter and acti- vate [►Page 81] the IP address [►Page 81] of the DNS server. ü If a DNS server is not available, enter the IP address [►Page 79] of the MQTT server. 1. Go to Settings > Parameters > System > MQTT. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. Activate MQTT You can use this parameter to activate the transmission of messages to the MQTT server (broker). Broker address If you use a URL address, you can use this parameter to enter the domain name of the MQTT server (broker). Otherwise, you can enter the IP address of the MQTT server. Broker port You can use this parameter to set the port of the MQTT server (broker). The following ports are used as standard: ▪ 8883 (SSL/TLS) ▪ 1883 Client username (optional) You can use this parameter to set the client user name for authentication at the broker. When using authentication, you must configure the broker ac- cordingly.

Maschinenfabrik Reinhausen GmbH 2020

83 4453918/14 EN ETOS® TD Password (optional) You can use this parameter to set the password for authentication at the bro- ker. When using authentication, you must configure the broker accordingly. SSL/TLS encryption You can use this parameter to set whether the data should be transmitted over an SSL/TLS-encrypted connection. Note that an encrypted data transmission does not work if you are using an SSL proxy. 9.5 Setting the device time You can set the the device time manually or automatically via an SNTP time server. The device must be connected to a time server via Ethernet for this purpose. You can operate SNTP and PTP at the same time. In this case, the PTP time is queried in slave operation. Settings Parameters Time synch...ion Name Value Time synchronization via SNTP Off Time synchronization via SNTP Off SNTP time server 0.0.0.0 Synchronization interval 60 s PTP hops 1 PTP version IEEE 1588-2008 PTP interface ETH 2.x Automatic Daylight Savings Time Off Time zone UTC +01:00 Time zone (UTC+01:00) Amsterdam, Berlin, Activate second time server Off SNTP time server 2 0.0.0.0 Home Events Information Recorder Settings EN CHANGE REBOOTadmin 23.09.2020 09:23 Figure 62: Time synchronization 1. Go to Settings > Parameters > System > Time synchronization. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. Time You can use this parameter to set the date and time manually. Time synchronization via SNTP You can use this parameter to activate time synchronization using an SNTP time server.

Maschinenfabrik Reinhausen GmbH 2020

84 4453918/14 EN ETOS® TD SNTP time server You can use this parameter to enter the IP address of a SNTP time server. If you are using a time server, the device uses the time of the time server as the system time. Be sure to enter a valid time server address that is not 0.0.0.0, otherwise it will not be possible to connect to the device. Synchronization interval You can use this parameter to set the interval at which the device is to call up the time from the time server. Automatic daylight saving / standard time You can use this parameter to activate the automatic switchover between daylight saving time and standard time. Depending on the time zone (region) set, the device switches automatically between daylight saving time and standard time on the specified days. Time zone If the time information is transmitted to the device by a network service (SNTP or SCADA), this time is transferred depending on the set reference time. To adjust the device time to your local time, you can use the time shift parameter to set the time shift to UTC. Example: Region Time shift to UTC Mumbai, India UTC +5:30 h Beijing, China UTC +8:00 h Brasilia, Brazil UTC -3:00 h Table 19: Time shift to UTC (Coordinated Universal Time) SNTP time server 2 (optional) You can use this parameter to enter the IP address of the second time server (optional). 9.5.1 Time synchronization via PTP You can use this parameter to activate time synchronization via a PTP time server. PTP hops You can use this parameter to enter the number of network sections be- tween master and slave. You can set up to 16 hops.

Maschinenfabrik Reinhausen GmbH 2020

85 4453918/14 EN ETOS® TD PTP version You can use this parameter to select the PTP version. ▪ PTP version 1 (IEEE 1588-2002) ▪ PTP version 2 (IEEE 1588-2008) PTP interface You can use this parameter to select the interface that the device is to use for PTP. 9.6 Configuring syslog The device supports the transmission of log messages via the syslog proto- col in accordance with the standards RFC 5424 and RFC 3164. Settings Parameters Syslog Name Value Activate syslog Off Syslog standard RFC 5425 Syslog server 0.0.0.0 Syslog server port 6514 Reconnect delay time 10 s Device designation m200 Emergency severity level Off Alert severity level Off Critical severity level Off Error severity level Off Warning severity level Off Notice severity level Off Info severity level Off Home Events Information Recorder Settings EN CHANGE REBOOTadmin 31.01.2020 08:56 Figure 63: Syslog 1. Go to Settings > Parameters > System > Syslog. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. Activate syslog You can use this parameter to activate transmission of syslog messages via the device.

Maschinenfabrik Reinhausen GmbH 2020

86 4453918/14 EN ETOS® TD Syslog standard You can use this parameter to adjust the transmission process and the for- mat for the syslog messages. You can select the following options: Standard Transport Message format RFC 5425 (recom- mended) TLS RFC 5424 RFC 5426 UDP RFC 6587 TCP RFC 3164 UDP RFC 3164 Table 20: Syslog standard If you use the standard RFC 5245 (TLS), you have to import the root certifi- cate and the client certificate with the corresponding key to the syslog server. For more information, refer to the section titled Importing data [►Section 9.36.2, Page 288]. Syslog server You can use this parameter to set the IP address of the syslog server. Syslog server port You can use this parameter to set the port of the syslog server. Reconnect delay time You can use this parameter to determine how long the device will wait be- fore it attempts to reconnect after the connection has been interrupted earlier or a syslog message could not be transmitted (only for TCP or TLS). Device designation You can use this parameter to set the device designation that the device will be identified with on the syslog server. Severity level You can set which syslog messages the device will send. You can also acti- vate or deactivate messages for each severity level. Severity level Description Emergency The system is unusable. Alert Immediate intervention required. Critical Critical state Error Error state Warning Warning state

Maschinenfabrik Reinhausen GmbH 2020

87 4453918/14 EN ETOS® TD Severity level Description Notice Notice state Info Information state Debug Debug state Table 21: Severity levels 9.7 SCADA The following section describes how you can configure the device to connect to a control system (SCADA). You can download the data points with the help of the export manager [►Section 9.36, Page 287]. 9.7.1 Configuring IEC 61850 (optional) If you want to use the IEC 61850 control system protocol, you must set the following parameters. Also refer to the section Configuring the network [►Section 9.3, Page 79]. Settings Parameters IEC 61850 Name Value IED name TAPCON Device ID TAPCON Access point MRTCAP Edition Edition 1 Home Events Information Recorder Settings EN CHANGE REBOOTadmin 04.02.2020 11:14 Figure 64: IEC 61850 1. Go to Settings > Parameters > System > IEC 61850. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. IED name You can use this parameter to assign the device an IED name in order for it to be identified in the IEC 61850 network. The IED name must start with a letter and may contain no more than 11 characters.

Maschinenfabrik Reinhausen GmbH 2020

88 4453918/14 EN ETOS® TD Device ID You can use this parameter to assign a device ID to the device in order that it can be identified in the IEC 61850 network. Access point You can use this parameter to assign a name to the access point in the IEC 61850 network. Edition You can use this parameter to switch between edition 1 and edition 2 of the IEC 61850 control system protocol. 9.7.1.1 Downloading an ICD file You can download the ICD file from the device via the Import/Export Man- ager [►Section 9.36, Page 287]. To do this, you have to establish an Ether- net connection between the device and your PC. 9.7.1.2 Importing CID/SCD file (optional) Note the following definitions for importing a CID file or SCD file. Only the following elements may differ between the imported IED and the exported IED from the TEMPLATE.icd. ▪ DataSet elements can be created in each LN ▪ ReportControl elements can be created in the LN containing the associ- ated DataSet ▪ IP address (if this is not present, the preset one is used) ▪ Subnet mask (if this is not present, the preset one is used) ▪ Gateway IP address (if this is not present, the preset one is used) ▪ Name of IED (IED name) ▪ Name of AccessPoint (AccessPoint attribute name) ▪ Name of logical device (LDevice attribute inst) OSI-PSEL, OSI-SSEL, and OSI-TSEL cannot be adjusted. The SCD file may contain no more than 45 IEDs. It may take several min- utes to import a complete SCD file. The SCD file should only contain the IEDs needed. You can import the CID/SCD file via the Import/Export Manager. To do so, proceed as follows: 1. Go to Settings > Import. 2. Select and import the desired CID/SCD file.

Maschinenfabrik Reinhausen GmbH 2020

89 4453918/14 EN ETOS® TD 9.7.2 Configuring IEC 60870-5-101 (optional) If you want to use the IEC 60870-5-101 control system protocol, you must set the following parameters. Settings Parameters IEC 60870-5-101 Name Value Serial interface RS232 Baud rate 9600 Transmission procedure Unbalanced Number of link address octets 1 Link address 1 Number of ASDU address octets 1 ASDU address 1 No. of information object address... 1 Number of cause of transmission o... 1 Number of databits 8 Parity Even Number of stop bits 1 ASDU single character confirmatio... Off Home Events Information Recorder Settings EN CHANGE REBOOTadmin 31.01.2020 13:05 Figure 65: IEC 60870-5-101 1. Go to Settings > Parameters > System > IEC 60870-5-101. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. Serial interface You can use this parameter to select the serial interface for data transmis- sion. You can select the following options: ▪ RS232 ▪ RS485 Baud rate You can use this parameter to set the serial interface's baud rate. You can select the following options: ▪ 9600 baud ▪ 19200 baud ▪ 38400 baud ▪ 57600 baud ▪ 115200 baud

Maschinenfabrik Reinhausen GmbH 2020

90 4453918/14 EN ETOS® TD Transmission procedure You can use this parameter to set the transmission procedure. You can se- lect the following options: ▪ Unbalanced transmission ▪ Balanced transmission Number of link address octets You can use this parameter to set how many octets are provided for the link address. Link address You can use this parameter to set the link address. Number of ASDU address octets You can use this parameter to set how many octets are provided for the ASDU address. ASDU address You can use this parameter to set the address of the ASDU. No. of information object address octets You can use this parameter to set how many octets are provided for the in- formation object address. Number of cause of transmission octets You can use this parameter to set how many octets are provided for the cause of transmission. Number of data bits You can use this parameter to set the number of databits. Parity You can use this parameter to set the parity. You can select the following options: ▪ None ▪ Even ▪ Odd Number of stop bits You can use this parameter to set the number of stop bits.

Maschinenfabrik Reinhausen GmbH 2020

91 4453918/14 EN ETOS® TD ASDU single character confirmation You can use this parameter to set whether a confirmation is to be sent as single characters instead of as a complete message. Single character confir- mation is only possible for requesting data of class 2 (Class 2 Request). RES bit test You can use this parameter to set whether the device is to check the RES bit (Reserved Bit) in the control field. You can select the following options: Option Description On Messages from the master with RES bit = 1 are declined by the device. Off Messages from the master with RES bit = 1 are accepted by the device. Table 22: RES bit test ASDU sequence optimization With this parameter, you can set which method is to be used for optimizing the ASDU types. The standard enables optimization in order to be able to transfer multiple value changes in a telegram in a sequence of ascending in- formation object addresses. This is displayed by the sequence bit. The se- lection of ASDU types for which this optimization is allowed is based on the edition of the standard. You can select the following options: Option Description None The device does not optimize the ASDU types. Ed. 1 Optimization in accordance with IEC 60870 Edition 1 (Type 1, 3, 9, 11, 21, 126). Ed. 1 Amendment2 Optimization in accordance with IEC 60870 Edition 1, Amendment 2 (Type 1, 3, 9, 11, 13, 15 21, 126). Ed. 2 Optimization in accordance with IEC 60870 Edition 2 (Type 1, 3, 5, 7, 9, 11, 13, 15, 20, 21, 126). Table 23: ASDU sequence optimization

Maschinenfabrik Reinhausen GmbH 2020

92 4453918/14 EN ETOS® TD Reference time You can use this parameter to set which time is to be transmitted by the con- trol system. The device uses this information for time synchronization [►Section 9.5, Page 83]. You can select the following options: Option Description Local The control system transmits the local time. Note: If you use this option, you must deactivate the au- tomatic changeover between daylight saving time and standard time [►Page 84]. Otherwise the device will use an incorrect time. UTC The control system transmits the time as UTC. The de- vice calculates the local time from UTC and the set time zone [►Page 84]. Table 24: Reference time 9.7.3 Configuring IEC 60870-5-103 (optional) If you want to use the IEC 60870-5-103 control system protocol, you must set the following parameters. Settings Parameters IEC 60870-5-103 Name Value Serial interface RS232 Baud rate 9600 ASDU address 1 Number of databits 8 Parity Even Number of stop bits 1 DFC compatibility Standard Reference time UTC Home Events Information Recorder Settings EN CHANGE REBOOTadmin 31.01.2020 13:05 Figure 66: IEC 60870-5-103 1. Go to Settings > Parameters > System > IEC 60870-5-103. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. Serial interface You can use this parameter to select the serial interface for data transmis- sion. You can select the following options: ▪ RS232 ▪ RS485

Maschinenfabrik Reinhausen GmbH 2020

93 4453918/14 EN ETOS® TD Baud rate You can use this parameter to set the serial interface's baud rate. You can select the following options: ▪ 9600 baud ▪ 19200 baud ▪ 38400 baud ▪ 57600 baud ▪ 115200 baud ASDU address You can use this parameter to set the address of the ASDU. Number of data bits You can use this parameter to set the number of databits. Parity You can use this parameter to set the parity. You can select the following options: ▪ None ▪ Even ▪ Odd Number of stop bits You can use this parameter to set the number of stop bits. DFC compatibility You can use this parameter to set how the device is to use the DFC bit (Data Flow Control) in the control field. You can select the following options: Option Description Standard The device sets the DFC bit in each response to a com- mand. The device thus indicates that the master may not send any further commands. The master must react to the ACD bit (Access Demand) and retrieve the response to the command e.g. via a request for data of class 1 from the slave queue. Alternative The device sets the DFC bit in a response if a second command is received without the master having previ- ously sent a request for data of class 1. Table 25: DFC compatibility

Maschinenfabrik Reinhausen GmbH 2020

94 4453918/14 EN ETOS® TD Reference time You can use this parameter to set which time is to be transmitted by the con- trol system. The device uses this information for time synchronization [►Section 9.5, Page 83]. You can select the following options: Option Description Local The control system transmits the local time. Note: If you use this option, you must deactivate the au- tomatic changeover between daylight saving time and standard time [►Page 84]. Otherwise the device will use an incorrect time. UTC The control system transmits the time as UTC. The de- vice calculates the local time from UTC and the set time zone [►Page 84]. Table 26: Reference time 9.7.4 Configuring IEC 60870-5-104 (optional) If you want to use the IEC 60870-5-104 control system protocol, you must set the following parameters. Also refer to the section Configuring the net- work [►Section 9.3, Page 79]. Settings Parameters IEC 60870-5-104 Name Value TCP port 2404 ASDU address 1 ASDU sequence optimization None Reference time UTC Home Events Information Recorder Settings EN CHANGE REBOOTadmin 31.01.2020 13:05 Figure 67: IEC 60870-5-104 1. Go to Settings > Parameters > System > IEC 60870-5-104. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. TCP port You can use this parameter to set the TCP port.

Maschinenfabrik Reinhausen GmbH 2020

95 4453918/14 EN ETOS® TD ASDU address You can use this parameter to set the address of the ASDU. ASDU sequence optimization With this parameter, you can set which method is to be used for optimizing the ASDU types. The standard enables optimization in order to be able to transfer multiple value changes in a telegram in a sequence of ascending in- formation object addresses. This is displayed by the sequence bit. The se- lection of ASDU types for which this optimization is allowed is based on the edition of the standard. You can select the following options: Option Description None The device does not optimize the ASDU types. Ed. 1 Optimization in accordance with IEC 60870 Edition 1 (Type 1, 3, 9, 11, 21, 126). Ed. 1 Amendment2 Optimization in accordance with IEC 60870 Edition 1, Amendment 2 (Type 1, 3, 9, 11, 13, 15 21, 126). Ed. 2 Optimization in accordance with IEC 60870 Edition 2 (Type 1, 3, 5, 7, 9, 11, 13, 15, 20, 21, 126). Table 27: ASDU sequence optimization Reference time You can use this parameter to set which time is to be transmitted by the con- trol system. The device uses this information for time synchronization [►Section 9.5, Page 83]. You can select the following options: Option Description Local The control system transmits the local time. Note: If you use this option, you must deactivate the au- tomatic changeover between daylight saving time and standard time [►Page 84]. Otherwise the device will use an incorrect time. UTC The control system transmits the time as UTC. The de- vice calculates the local time from UTC and the set time zone [►Page 84]. Table 28: Reference time IP address Client 1/2/3 (optional) If you use the optional "Multi-client" function, you can use these parameters to set the IP addresses of the SCADA clients. The device only accepts com- mands through the control system from end devices that have their IP ad- dresses set here.

Maschinenfabrik Reinhausen GmbH 2020

96 4453918/14 EN ETOS® TD Note that all SCADA clients communicate with the device on an equal basis, because the device does not prioritize commands. If you transmit com- mands from several SCADA clients to the device at the same time, the de- vice will execute the last transmitted command. 9.7.5 Configuring Modbus (optional) If you want to use the Modbus control system protocol, you must set the cor- responding parameters depending on the Modbus type selected. Also refer to the section Configuring the network [►Section 9.3, Page 79] if you want to use Modbus TCP. Settings Parameters Modbus Name Value Modbus type RTU Modbus address 1 TCP port 502 Maximum TCP connections 10 TCP Keepalive Off Serial interface RS232 Baud rate 9600 Number of databits 8 Parity Even Number of stop bits 1 Home Events Information Recorder Settings EN CHANGE REBOOTadmin 31.01.2020 13:05 Figure 68: Modbus 1. Go to Settings > Parameters > System > Modbus. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. Modbus type You can use this parameter to set the Modbus type. You can select the fol- lowing options: ▪ RTU ▪ TCP ▪ ASCII Modbus address You can use this parameter to set the Modbus address. TCP port You can use this parameter to set the TCP port.

Maschinenfabrik Reinhausen GmbH 2020

97 4453918/14 EN ETOS® TD Maximum TCP connections You can use this parameter to set the maximum number of TCP connec- tions. TCP Keepalive You can use this parameter to activate/deactivate the "TCP Keepalive" func- tion. Serial interface You can use this parameter to select the serial interface for data transmis- sion. You can select the following options: ▪ RS232 ▪ RS485 Baud rate You can use this parameter to set the serial interface's baud rate. You can select the following options: ▪ 9600 baud ▪ 19200 baud ▪ 38400 baud ▪ 57600 baud ▪ 115200 baud Number of data bits You can use this parameter to set the number of databits. Parity You can use this parameter to set the parity. You can select the following options: ▪ None ▪ Even ▪ Odd Number of stop bits You can use this parameter to set the number of stop bits.

Maschinenfabrik Reinhausen GmbH 2020

98 4453918/14 EN ETOS® TD 9.7.6 Configuring DNP3 (optional) If you would like to use the DNP3 control system protocol, you must set the parameters listed below. Also refer to the section Configuring the network [►Section 9.3, Page 79] if you want to use the DNP3 via TCP. Settings Parameters DNP3 Name Value DNP3 transmission type TCP TCP port 20000 Device address 1 Timeout for response confirmation 5 s Unsolicited messages Off Destination address 10000 Timeout confirmation 5 s Indefinite unsolicited retries Off Number of unsolicited retries 3 User ID code ISM Reference time UTC Home Events Information Recorder Settings EN CHANGE REBOOTadmin 31.01.2020 13:05 Figure 69: DNP3 1. Go to Settings > Parameters > System > DNP3. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. 9.7.6.1 DNP3 transmission type You can use this parameter to set the transmission type. You can select the following options: ▪ TCP ▪ Serial TCP port You can use this parameter to set the TCP port. Serial interface You can use this parameter to select the serial interface for data transmis- sion. You can select the following options: ▪ RS232 ▪ RS485

Maschinenfabrik Reinhausen GmbH 2020

99 4453918/14 EN ETOS® TD Baud rate You can use this parameter to set the serial interface's baud rate. You can select the following options: ▪ 9600 baud ▪ 19200 baud ▪ 38400 baud ▪ 57600 baud ▪ 115200 baud 9.7.6.2 Device address You can use this parameter to set the device link address. 9.7.6.3 Destination address You can use this parameter to set the destination master link address. 9.7.6.4 Unsolicited messages You can use this parameter to set whether the device is to support unso- licited messages. If you activate unsolicited messages, the device sends a message via the control system every time a value is changed. 9.7.6.5 Repetition of unsolicited messages You can use this parameter to set how often the device is to send an unso- licited message until it receives a response from the DNP3 master. 9.7.6.6 Repeat unsolicited messages indefinitely You can use this parameter to set the device to send an indefinite number of unsolicited messages until it receives a response from the DNP3 master. 9.7.6.7 Timeout You can use this parameter to set the timeout for unsolicited messages. 9.7.6.8 Timeout for response confirmation You can use this parameter to set the timeout for response confirmation for unsolicited messages. 9.7.6.9 User ID code You can use this parameter to set the user ID code.

Maschinenfabrik Reinhausen GmbH 2020

100 4453918/14 EN ETOS® TD Reference time You can use this parameter to set which time is to be transmitted by the con- trol system. The device uses this information for time synchronization [►Section 9.5, Page 83]. You can select the following options: Option Description Local The control system transmits the local time. Note: If you use this option, you must deactivate the au- tomatic changeover between daylight saving time and standard time [►Page 84]. Otherwise the device will use an incorrect time. UTC The control system transmits the time as UTC. The de- vice calculates the local time from UTC and the set time zone [►Page 84]. Table 29: Reference time 9.7.7 Configuring GOOSE (optional) You can use the optional GOOSE function to send GOOSE messages (GOOSE publisher) or receive GOOSE messages (GOOSE subscriber) via the IEC 61850 control system protocol with the device. The configuration of GOOSE is described in the following sections. 9.7.7.1 Configuring GOOSE publisher If you configure the device as a GOOSE publisher, you can send all data points which the device provides via MMS as GOOSE messages. To do this, you have to configure the data points using DataSets in an SCD/CID file. SCD/CID file requirements ▪ The GOOSE control block (GSEControl) and the associated DataSet can only be created in LLN0. ▪ GSE elements for the configuration of the GOOSE message can be cre- ated under ConnectedAP. ▪ The maximum number of data points per GOOSE message is defined in Private Element type="MR-MAX-GOOSE-PUBLISH-FCDA". You cannot adjust this value. ▪ The maximum number of usable GSEControl elements is defined in TEM- PLATE.icd under Services GOOSE. You cannot adjust this value. ▪ The shortest repeat time is defined in Private Element type="MR- MINTIME-GOOSE". You cannot adjust this value.