MR MSENSE VAM Operating Instructions Manual

Text of the manual

© All rights reserved by Maschinenfabrik Reinhausen

Dissemination and reproduction of this document and use and disclosure of its content are strictly prohibited unless expressly permitted. Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents, utility models or designs. The product may have been altered since this document was published. We reserve the right to change the technical data, design and scope of supply. Generally the information provided and agreements made when processing the individual quotations and orders are binding. The original operating instructions were written in German.

Table of contents

Maschinenfabrik Reinhausen GmbH 2021 3 6796573/02 EN MSENSE® VAM Table of contents 1 Introduction......................................................................................................................... 7 1.1 Manufacturer.......................................................................................................................................  7 1.2 Completeness.....................................................................................................................................  7 1.3 Safekeeping........................................................................................................................................  7 1.4 Notation conventions ..........................................................................................................................  7 1.4.1 Hazard communication system............................................................................................................................. 7 1.4.2 Information system................................................................................................................................................ 9 1.4.3 Instruction system ................................................................................................................................................. 9 1.4.4 Typographic conventions .................................................................................................................................... 10 2 Safety................................................................................................................................. 11 2.1 Appropriate use ................................................................................................................................  11 2.2 Inappropriate use..............................................................................................................................  12 2.3 Fundamental safety instructions.......................................................................................................  12 2.4 Personnel qualification......................................................................................................................  13 2.5 Personal protective equipment .........................................................................................................  14 3 IT security.......................................................................................................................... 16 4 Product description.......................................................................................................... 20 4.1 MSENSE® VAM monitoring system versions...................................................................................  20 4.2 Scope of delivery ..............................................................................................................................  20 4.3 Function description..........................................................................................................................  21 4.4 Performance features .......................................................................................................................  22 4.5 Design...............................................................................................................................................  23 4.5.1 VS 1 sensor assembly ........................................................................................................................................ 24 4.5.2 Control cabinet.................................................................................................................................................... 24 4.6 Main screen ......................................................................................................................................  32 4.6.1 MSENSE® VAM as an integration solution......................................................................................................... 32 4.6.2 MSENSE® VAM as a standalone version........................................................................................................... 33 4.7 Operating concept ............................................................................................................................  33 5 Packaging, transport and storage .................................................................................. 38 5.1 Packaging.........................................................................................................................................  38 5.1.1 Suitability............................................................................................................................................................. 38 5.1.2 Markings.............................................................................................................................................................. 39

Table of contents

Maschinenfabrik Reinhausen GmbH 2021 4 6796573/02 EN MSENSE® VAM 5.2 Transportation, receipt and handling of shipments...........................................................................  39 5.3 Storage of shipments........................................................................................................................  40 5.4 Unpacking shipments and checking for transportation damages .....................................................  41 6 Mounting ........................................................................................................................... 43 6.1 Installing the Cap rail modules / control cabinet ...............................................................................  43 6.1.1 Installing the cap rail modules............................................................................................................................. 43 6.1.2 Integration solution in the ETOS® ED motor-drive unit....................................................................................... 47 6.1.3 Fitting the control cabinet to the transformer....................................................................................................... 47 6.2 Mounting the vibration sensor...........................................................................................................  50 6.3 Connecting the assemblies...............................................................................................................  51 6.3.1 Cable recommendation....................................................................................................................................... 51 6.3.2 Information about connecting serial interfaces RS232 and RS485..................................................................... 52 6.3.3 Information about connecting analog sensors .................................................................................................... 55 6.3.4 Electromagnetic compatibility.............................................................................................................................. 57 6.3.5 Information about laying fiber-optic cable ........................................................................................................... 60 6.3.6 Connecting the vibration sensor to the control cabinet ....................................................................................... 61 6.3.7 Connecting the motor-drive unit controller to the monitoring system.................................................................. 64 6.3.8 Connecting the temperature sensor.................................................................................................................... 64 6.3.9 Connecting additional leads (optional)................................................................................................................ 65 6.3.10 Connecting the power supply.............................................................................................................................. 65 6.4 Checking functional reliability ...........................................................................................................  66 7 Commissioning................................................................................................................. 67 7.1 Visualization......................................................................................................................................  67 7.2 Commissioning wizard......................................................................................................................  69 7.3 Setting the language.........................................................................................................................  70 7.4 Setting date and time........................................................................................................................  71 7.5 Name plate .......................................................................................................................................  71 7.5.1 Enter the name plate data................................................................................................................................... 71 7.5.2 Displaying the name plate................................................................................................................................... 72 7.6 Setting the control system protocol (optional)...................................................................................  72 7.7 Performing tests................................................................................................................................  72 7.7.1 Checking measured values and status of digital inputs and outputs .................................................................. 73 7.7.2 Performing function tests .................................................................................................................................... 73 7.7.3 Electrical high-voltage tests on the transformer.................................................................................................. 73 7.7.4 Ground test ......................................................................................................................................................... 74

Table of contents

Maschinenfabrik Reinhausen GmbH 2021 5 6796573/02 EN MSENSE® VAM 7.7.5 Dielectric tests on transformer wiring.................................................................................................................. 75 8 Operation........................................................................................................................... 76 8.1 Visualization......................................................................................................................................  76 8.2 User administration...........................................................................................................................  78 8.2.1 User roles............................................................................................................................................................ 78 8.2.2 Changing the password ...................................................................................................................................... 80 8.2.3 Creating, editing and deleting users.................................................................................................................... 80 8.2.4 Setting access rights to parameters and events ................................................................................................. 82 8.3 Events menu.....................................................................................................................................  83 8.4 Information menu..............................................................................................................................  87 8.5 Recorder menu.................................................................................................................................  91 8.6 Settings menu...................................................................................................................................  94 8.7 Menu Settings > Parameters ............................................................................................................  94 8.7.1 Menu Settings > Parameters > General.............................................................................................................. 95 8.7.2 Configuring the network ...................................................................................................................................... 97 8.7.3 Time synchronization .......................................................................................................................................... 97 8.7.4 Configuring syslog............................................................................................................................................. 100 8.7.5 Setting the screensaver .................................................................................................................................... 101 8.7.6 Linking digital outputs and control system messages....................................................................................... 101 8.7.7 Linking functions ............................................................................................................................................... 103 8.7.8 Temperature monitoring.................................................................................................................................... 104 8.7.9 On-load tap-changer > OLTC data.................................................................................................................... 105 8.7.10 Power grid > Tap position monitoring................................................................................................................ 105 8.7.11 SCADA.............................................................................................................................................................. 106 8.8 Menu Settings > Events..................................................................................................................  127 8.9 Menu Settings > DIO configuration (optional).................................................................................  128 8.10 Menu Settings > AIO configuration (optional).................................................................................  130 8.11 Tap position table ...........................................................................................................................  132 8.12 Menu Settings > Reset VAM ..........................................................................................................  132 8.13 Menu settings > VAM update rules.................................................................................................  133 8.14 Menu Settings > Commissioning wizard.........................................................................................  134 8.15 Menu Settings > TPLE....................................................................................................................  134 8.15.1 Function ............................................................................................................................................................ 134 8.15.2 Configuring TPLE.............................................................................................................................................. 147 8.16 Menu Settings > Import ..................................................................................................................  150

Table of contents

Maschinenfabrik Reinhausen GmbH 2021 6 6796573/02 EN MSENSE® VAM 8.17 Menu Settings > Export ..................................................................................................................  152 8.17.1 VAM export ....................................................................................................................................................... 153 8.18 Menu Settings > Administration......................................................................................................  155 9 Inspection and maintenance ......................................................................................... 156 9.1 Care................................................................................................................................................  156 9.2 Inspection .......................................................................................................................................  156 9.3 Maintenance ...................................................................................................................................  156 10 Fault elimination............................................................................................................. 157 10.1 General faults .................................................................................................................................  157 10.2 Event messages .............................................................................................................................  157 10.3 Human-machine interface...............................................................................................................  158 10.4 Other faults .....................................................................................................................................  158 11 Disassembly.................................................................................................................... 159 12 Disposal........................................................................................................................... 160 13 Technical data................................................................................................................. 161 13.1 Control cabinet standalone version ................................................................................................  161 13.1.1 Connection terminals ........................................................................................................................................ 162 13.2 Voltage supply ................................................................................................................................  162 13.3 CPU (central processing unit) II......................................................................................................  162 13.4 DIO 28-15 digital inputs and outputs ..............................................................................................  164 13.5 AIO 2 analog inputs and outputs ....................................................................................................  166 13.6 VI 4 vibration sensor input module .................................................................................................  167 13.7 VS 1 vibration sensor......................................................................................................................  167 13.8 Sensor cable...................................................................................................................................  168 Glossary .......................................................................................................................... 169 List of key words ............................................................................................................ 170

Maschinenfabrik Reinhausen GmbH 2021

7 6796573/02 EN MSENSE® VAM 1 Introduction This technical file contains detailed descriptions on the safe and proper in- stallation, connection, commissioning and monitoring of the product. It also includes safety instructions and general information about the prod- uct. This technical file is intended solely for specially trained and authorized per- sonnel. 1.1 Manufacturer The product is manufactured by: Maschinenfabrik Reinhausen GmbH Falkensteinstraße 8 93059 Regensburg Tel.: (+49) 9 41/40 90-0 E-mail: [email protected] Further information on the product and copies of this technical file are avail- able from this address if required. 1.2 Completeness This technical file is incomplete without the supporting documents. The following documents are considered supporting documents: ▪ Operating instructions ▪ Connection diagrams 1.3 Safekeeping Keep this technical file and all supporting documents ready at hand and ac- cessible for future use at all times. 1.4 Notation conventions This section contains an overview of the symbols and textual emphasis used. 1.4.1 Hazard communication system Warnings in this technical file are displayed as follows.

Maschinenfabrik Reinhausen GmbH 2021

8 6796573/02 EN MSENSE® VAM 1.4.1.1 Warning relating to section Warnings relating to sections refer to entire chapters or sections, sub-sec- tions or several paragraphs within this technical file. Warnings relating to sections use the following format: WARNING Type of danger! Source of the danger and outcome. ►Action ►Action 1.4.1.2 Embedded warning information Embedded warnings refer to a particular part within a section. These warn- ings apply to smaller units of information than the warnings relating to sec- tions. Embedded warnings use the following format:  DANGER! Instruction for avoiding a dangerous situation. 1.4.1.3 Signal words and pictograms The following signal words are used: Signal word Definition DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE Indicates measures to be taken to prevent damage to property. Table 1: Signal words in warning notices

Maschinenfabrik Reinhausen GmbH 2021

9 6796573/02 EN MSENSE® VAM Pictograms warn of dangers: Pictogram Definition Warning of a danger point Warning of dangerous electrical voltage Warning of combustible substances Warning of danger of tipping Warning of danger of crushing Table 2: Pictograms used in warning notices 1.4.2 Information system Information is designed to simplify and improve understanding of particular procedures. In this technical file it is laid out as follows: Important information. 1.4.3 Instruction system This technical file contains single-step and multi-step instructions. Single-step instructions Instructions which consist of only a single process step are structured as fol- lows:

Maschinenfabrik Reinhausen GmbH 2021

10 6796573/02 EN MSENSE® VAM Aim of action ü Requirements (optional). ►Step 1 of 1. ð Result of step (optional). ð Result of action (optional). Multi-step instructions Instructions which consist of several process steps are structured as follows: Aim of action ü Requirements (optional). 1. Step 1. ð Result of step (optional). 2. Step 2. ð Result of step (optional). ð Result of action (optional). 1.4.4 Typographic conventions Typographic convention Purpose Example UPPERCASE Operating controls, switches ON/OFF [Brackets] PC keyboard [Ctrl] + [Alt] Bold Software operating controls Press Continue button …>…>… Menu paths Parameter > Control parameter Italics System messages, error messages, signals Function monitoring alarm triggered [► Number of pages] Cross reference [► Page 41]. Dotted underscore ............................................. Glossary entry, abbreviations, defini- tions, etc. Glossary entry ........................ Table 3: Typographic conventions used in this technical file

Maschinenfabrik Reinhausen GmbH 2021

11 6796573/02 EN MSENSE® VAM 2 Safety ▪ Read this technical file through to familiarize yourself with the product. ▪ This technical file is a part of the product. ▪ Read and observe the safety instructions provided in this chapter. ▪ Read and observe the warnings in this technical file in order to avoid func- tion-related dangers. ▪ The product is manufactured on the basis of state-of-the-art technology. Nevertheless, risks to life and limb for the user or impairment of the prod- uct and other material assets due to the function may arise in the event of improper use. 2.1 Appropriate use The product is a monitoring system for monitoring on-load tap-changers on power transformers/reactors. You can use the product to detect time and amplitude anomalies in the progression of the vibro-acoustic signal sent by the on-load tap-changer and receive event messages when anomalies are detected. The product is designed solely for use in electrical energy systems and facili- ties. It may only be used in compliance with the requirements and conditions listed in this technical file as well as the warnings in this technical file and the warnings posted on the product. This applies throughout the service life of the product, from delivery, installation and operation to removal and dis- posal. The following is considered appropriate use: ▪ Only use the product with the on-load tap-changer and the motor-drive unit specified in the order. ▪ Only use the product for on-load tap-changers that have not already been damaged. ▪ Operate the product in accordance with this technical file, the agreed- upon delivery conditions and the technical data. ▪ Ensure that all necessary work is performed by qualified personnel only. ▪ Only use the equipment and special tools included in the scope of delivery for the intended purpose and in accordance with the specifications of this technical file. ▪ Only use the product on transformers with insulated add-on parts after ap- proval by Maschinenfabrik Reinhausen GmbH (special version required). ▪ Only operate the product in industrial areas. Observe the notices in this technical file regarding electromagnetic compatibility and the technical data.

Maschinenfabrik Reinhausen GmbH 2021

12 6796573/02 EN MSENSE® VAM 2.2 Inappropriate use ▪ The product is not suitable for extending the permitted service life of the on-load tap-changer specified by the on-load tap-changer manufacturer. ▪ The product is not a protective device. Do not use it to handle safety-re- lated functions. ▪ Risk of explosion and fire from highly flammable or explosive gases, va- pors, or dusts. Do not operate the product in areas at risk of explosion. ▪ The product is not intended for use in environments subject to strong cor- rosion effects. ▪ Unauthorized or inappropriate changes to the product may lead to per- sonal injury, material damage and operational faults. Only modify the product after consultation with Maschinenfabrik Reinhausen GmbH. 2.3 Fundamental safety instructions To prevent accidents, malfunctions and damage as well as unacceptable ad- verse effects on the environment, those responsible for transport, installa- tion, operation, maintenance and disposal of the product or parts of the prod- uct must ensure the following: Personal protective equipment Loosely worn or unsuitable clothing increases the danger of becoming trapped or caught up in rotating parts and the danger of getting caught on protruding parts. This poses a danger to life and limb. ▪ Wear appropriate personal protective equipment such as a helmet, work gloves, etc. for the respective activity. ▪ Never wear damaged personal protective equipment. ▪ Never wear rings, necklaces, or other jewelry. ▪ If you have long hair, wear a hairnet. Work area Untidy and poorly lit work areas can lead to accidents. ▪ Keep the work area clean and tidy. ▪ Make sure that the work area is well lit. ▪ Observe the applicable laws for accident prevention in the relevant coun- try. Working during operation The product may only be operated in a sound, operational condition. Other- wise it poses a danger to life and limb. ▪ Regularly check the operational reliability of safety equipment. ▪ Comply with the inspection work, maintenance work and maintenance in- tervals described in this technical file.

Maschinenfabrik Reinhausen GmbH 2021

13 6796573/02 EN MSENSE® VAM Securing the motor-drive unit If you open the motor-drive unit during operation, there is a danger of electric shock due to live components behind the swing frame. ▪ Secure the motor-drive unit against unauthorized opening during opera- tion by using a padlock. ▪ The motor-drive unit may only be opened by an electrically skilled person. Safety markings Warning signs and safety information plates are safety markings on the product. They are an important aspect of the safety concept. ▪ Observe all safety markings on the product. ▪ Make sure all safety markings on the product remain intact and legible. ▪ Replace safety markings that are damaged or missing. Ambient conditions To ensure reliable and safe operation, the product must only be operated under the ambient conditions specified in the technical data. ▪ Observe the specified operating conditions and requirements for the in- stallation location. Modifications and conversions Unauthorized or inappropriate changes to the product may lead to personal injury, material damage and operational faults. ▪ Only modify the product after consultation with Maschinenfabrik Rein- hausen GmbH. Spare parts Spare parts not approved by Maschinenfabrik Reinhausen GmbH may lead to physical injury, damage to the product and malfunctions. ▪ Only use spare parts that have been approved by Maschinenfabrik Rein- hausen GmbH. ▪ Contact Maschinenfabrik Reinhausen GmbH. 2.4 Personnel qualification The person responsible for assembly, commissioning, operation, mainte- nance and inspection must ensure that the personnel are sufficiently quali- fied.

Maschinenfabrik Reinhausen GmbH 2021

14 6796573/02 EN MSENSE® VAM Electrically skilled person The electrically skilled person has a technical qualification and therefore has the required knowledge and experience, and is also conversant with the ap- plicable standards and regulations. The electrically skilled person is also pro- ficient in the following: ▪ Can identify potential dangers independently and is able to avoid them. ▪ Is able to perform work on electrical systems. ▪ Is specially trained for the working environment in which (s)he works. ▪ Must satisfy the requirements of the applicable statutory regulations for accident prevention. Electrically trained persons An electrically trained person receives instruction and guidance from an electrically skilled person in relation to the tasks undertaken and the poten- tial dangers in the event of inappropriate handling as well as the protective devices and safety measures. The electrically trained person works exclu- sively under the guidance and supervision of an electrically skilled person. Operator The operator uses and operates the product in line with this technical file. The operating company provides the operator with instruction and training on the specific tasks and the associated potential dangers arising from im- proper handling. Technical Service We strongly recommend having maintenance, repairs and retrofitting carried out by our Technical Service department. This ensures that all work is per- formed correctly. If maintenance is not carried out by our Technical Service department, please ensure that the personnel who carry out the mainte- nance are trained and authorized by Maschinenfabrik Reinhausen GmbH to carry out the work. Authorized personnel Authorized personnel are trained by Maschinenfabrik Reinhausen GmbH to carry out special maintenance. 2.5 Personal protective equipment Personal protective equipment must be worn during work to minimize risks to health. ▪ Always wear the personal protective equipment required for the job at hand. ▪ Never wear damaged personal protective equipment. ▪ Observe information about personal protective equipment provided in the work area.

Maschinenfabrik Reinhausen GmbH 2021

15 6796573/02 EN MSENSE® VAM Protective clothing Close-fitting work clothing with a low tearing strength, with tight sleeves and with no protruding parts. It mainly serves to protect the wearer against being caught by moving machine parts. Safety shoes To protect against falling heavy objects and slipping on slippery surfaces. Safety glasses To protect the eyes from flying parts and splashing liq- uids. Visor To protect the face from flying parts and splashing liq- uids or other dangerous substances. Hard hat To protect against falling and flying parts and materials. Hearing protection To protect against hearing damage. Protective gloves To protect against mechanical, thermal, and electrical hazards. Table 4: Personal protective equipment

3 IT security

Maschinenfabrik Reinhausen GmbH 2021 16 6796573/02 EN MSENSE® VAM 3 IT security Observe the following recommendations for secure operation of the product. General ▪ Ensure that only authorized personnel have access to the device. ▪ Only use the device within an ESP (electronic security perimeter). Do not connect the device to the Internet in an unprotected state. Use mecha- nisms for vertical and horizontal network segmenting and security gate- ways (firewalls) at the transition points. ▪ Ensure that the device is only operated by trained personnel who are fa- miliar with IT security. Commissioning Observe the following recommendations for device commissioning: ▪ User IDs must be unique and assignable. Do not use a "Group account" function or the "Auto login" function. ▪ Activate the "Auto logout" function. ▪ Restrict the rights of the individual user groups as much as is feasible; this helps avoid errors during operations. A user with the "Operator" role, for example, should only perform operations and should not be able to change any device settings. ▪ Delete or disable the default "admin" user ID. This requires first creating a new user account with the "Administrator" role. You can then use it to delete or disable the default "admin" account. ▪ Deactivate service user access. ▪ Enable SSL/TLS encryption; access to the device is then only possible us- ing the SSL/TLS protocol. In addition to encrypting communication, this protocol also checks the authenticity of the server. ▪ Use TLS version 1.2 or higher wherever possible. ▪ Integrate the device into a public key infrastructure. Create your own SSL certificates for this if necessary and then import them. ▪ Connect the device to a central log server by using the syslog interface [►Section 8.7.4, Page 100]. Operation Observe the following recommendations during device operation: ▪ Change the password at regular intervals. ▪ Export the security log at regular intervals. ▪ Check the log files regularly for unauthorized system access and other se- curity-related events. Interfaces The device uses the following interfaces for communication:

3 IT security

Maschinenfabrik Reinhausen GmbH 2021 17 6796573/02 EN MSENSE® VAM Figure 1: ETH1.1 interface on the OT1205 assembly Interface Protocol Port Description ETH1.1 TCP 21 FTP service access 1) ETH1.1 TCP 80 Web visualization 1) ETH1.1 TCP 443 SSL-protected web visualization ETH1.1 TCP 990 SSL-protected FTP service access ETH1.1 TCP 8080 Web visualization (alternative port) 1) ETH1.1 TCP 8081 SSL-protected web visualization (alternative port) Table 5: Interfaces and open ports of the OT1205 assembly 1) Port is closed if you activate the device's SSL encryption. Figure 2: Interfaces of the CPU assembly

3 IT security

Maschinenfabrik Reinhausen GmbH 2021 18 6796573/02 EN MSENSE® VAM Interface Protocol Port Description CAN 1 - - Connection of the DIO assembly CAN 2 - - Communication with other ISM® devices (e.g. parallel operation) COM 1 - - Internal system interface COM 2 - - Serial interface (SCADA) USB - - Import or export of data ETH 1 TCP 80 HTTP for web-based visualization1), 2) ETH 1 TCP 443 HTTPS for web-based visualization1), 2) ETH 1 TCP 102 IEC 61850 ETH 1 TCP 502 Modbus3) ETH 1 TCP 20000 DNP33) ETH 2.x TCP 21 FTP1) (only for MR service) ETH 2.x TCP 80 HTTP for web-based visualization1) ETH 2.x TCP 443 HTTPS for web-based visualization1) ETH 2.x TCP 990 FTPS (only for MR service) ETH 2.x TCP 8080 HTTP for web-based visualization1) ETH 2.x TCP 8081 HTTPS for web-based visualization1) Table 6: Interfaces and open ports of the CPU assembly 1) Port is closed if you activate the device's SSL encryption. 2) Depending on the setting of the parameter Visualization release. 3) Default setting; if you have modified the port for the control system proto- col, only the set port is opened. Encryption standards The device supports the following TLS versions: ▪ TLS 1.0 ▪ TLS 1.1 ▪ TLS 1.2

3 IT security

Maschinenfabrik Reinhausen GmbH 2021 19 6796573/02 EN MSENSE® VAM The device uses the following cipher suites for a TLS-secured connection: Key exchange Authentication Encryption Key length Operating mode Hash func- tion TLS ECDHE RSA WITH AES 128 CBC SHA1) DHE SHA265 ECDHE ECDSA GCM SHA256 ECDH 256 CBC SHA1) RSA1) SHA256 GCM SHA384 Table 7: Cipher suite 1) Not available with TLS version >= 1.2 The device uses the SHA256 hash function to save passwords.

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 20 6796573/02 EN MSENSE® VAM 4 Product description 4.1 MSENSE® VAM monitoring system versions The device is available in the following versions: ▪ MSENSE® VAM: – Standalone version in the control cabinet ▪ ETOS® ED/TD with MSENSE® VAM function: – Integration solution in the motor-drive unit ▪ ETOS® IM with MSENSE® VAM function: – Integration solution in the customer control cabinet (pluggable modules) ▪ MSENSE® BM with MSENSE® VAM function 4.2 Scope of delivery Please note the following: ▪ Check the shipment for completeness using the shipping documents. ▪ Store the parts in a dry place until installation. Depending on the product version, the following MSENSE® VAM monitoring system assemblies are included in the scope of supply. Depending on the order, additional ETOS® modules that are not listed in these instructions may also be used. Also observe the corresponding operating instructions. MSENSE® VAM: Standalone version in the control cabinet ▪ VI 4 vibration sensor input module ▪ VAM sensor assembly (including VS 1 vibration sensor, adapter screw and kick guard) ▪ Sensor cable for VS 1 vibration sensor ▪ Analog AIO 2 or AIO 4 inputs/outputs ▪ G1 PULS DIMENSION QS3.241 power supply ▪ Digital DIO 28-15 or DIO 42-20 inputs/outputs ▪ CPU II (central processing unit) ▪ Control cabinet ▪ Optional: MC 2-2 media converter ▪ Optional: SW 3-3 media converter with managed switch ▪ Optional: Display ▪ Optional: PT100 for OLTC oil temperature (temperature pocket must be available in the on-load tap-changer head cover)1)

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 21 6796573/02 EN MSENSE® VAM ETOS® ED/TD with MSENSE® VAM option: Integration solution in the motor-drive unit ▪ VI 4 vibration sensor input module ▪ VAM sensor assembly (including VS 1 vibration sensor, adapter screw and kick guard) ▪ Sensor cable for VS 1 vibration sensor ▪ Optional: MC 2-2 media converter ▪ Optional: SW 3-3 media converter with managed switch ▪ Optional: Display ▪ Optional: PT100 for OLTC oil temperature (temperature pocket must be available in the on-load tap-changer head cover)1) ETOS® IM with MSENSE® VAM option: Integration solution in the customer control cabinet (pluggable modules) ▪ VI 4 vibration sensor input module ▪ VAM sensor assembly (including VS 1 vibration sensor, adapter screw and kick guard) ▪ Sensor cable for VS 1 vibration sensor ▪ Analog AIO 2 or AIO 4 inputs/outputs ▪ G1 PULS DIMENSION QS3.241 power supply ▪ Digital DIO 28-15 or DIO 42-20 inputs/outputs ▪ CPU II (central processing unit) ▪ Optional: MC 2-2 media converter ▪ Optional: SW 3-3 media converter with managed switch ▪ Optional: Display ▪ Optional: PT100 for OLTC oil temperature (temperature pocket must be available in the on-load tap-changer head cover)1) 1) Oil temperature recording is a prerequisite for the self-learning of the yel- low limit value curve. As an alternative to recording the OLTC oil tempera- ture, the top-oil temperature can be used. 4.3 Function description The product is a monitoring system for monitoring vibro-acoustic signals from on-load tap-changers. You can use the product to detect time and am- plitude anomalies in the vibro-acoustic signal progression and receive event messages when anomalies are detected. The on-load tap-changer is equipped with measuring equipment that records the vibro-acoustic signal in the system throughout the entire tap change se- quence and analyses it immediately upon completion. In addition, the sys- tem determines the changed tap position and the oil temperature in the on- load tap-changer.

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 22 6796573/02 EN MSENSE® VAM Using the implemented algorithms, the monitoring system can reliably detect any potential anomalies that occur in the vibro-acoustic signal progression, taking the temperature variations of the on-load tap-changer oil into account. Status message The MSENSE® VAM monitoring system produces a 3-stage status mes- sage: Status Device/visualization dis- play SCADA/digital output re- mote signaling Normal OK message through blue status message No remote signaling Warning The first and the second anomalies in an evaluation cluster are indicated via a yellow status message in the VAM analysis (Infor- mation menu). No remote signaling Alarm A third anomaly arising in an evaluation cluster or the third successive anom- aly triggers an additional event message (Events menu). This event message is transmitted to a connected SCADA system. In addition, it can also be sent to a digital output. 4.4 Performance features The MSENSE® VAM monitoring system monitors the vibro-acoustic signals from on-load tap-changers and has the following : ▪ Monitoring on-load tap-changers/reactors in accordance with the technical specification in the order confirmation ▪ Suitable for on-load tap-changers with oil-switch and vacuum-switch tech- nology ▪ Recording of the vibro-acoustic signals during on-load tap-changer opera- tion via automatic triggering ▪ Evaluation of the vibro-acoustic signal progression with regard to time and amplitude anomalies ▪ Self-learning limit value at an oil temperature above 15 °C, which moves towards the signal progression with increasing tap-change frequency Ap- proximately 5 tap-change operations per evaluation cluster (e.g. 5x from step 1 to step 2 in reverse tap-change operation) are necessary before the first limit value curve is displayed. The signals are also evaluated below 15 °C, but the limit value is not ad- justed. ▪ Display and recording of the measured and calculated values ▪ Status messages via digital outputs ▪ Web-based visualization

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 23 6796573/02 EN MSENSE® VAM ▪ SCADA – IEC 60870-5-101 – IEC 60870-5-103 – IEC 60870-5-104 – IEC 61850 (edition 1 and edition 2) – Modbus (RTU, TCP, ASCII) – DNP3 4.5 Design This chapter contains an overview of the design of the monitoring system: Figure 3: Design, example of single-column application 1 On-load tap-changer head cover 2 Vibration sensor with kick guard 3 Control cabinet 4 Sensor cable 5 Transformer

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 24 6796573/02 EN MSENSE® VAM 4.5.1 VS 1 sensor assembly Figure 4: VAM sensor assembly 1 Sensor cable 2 Kick guard 3 Vibration sensor 4 Adapter 4.5.2 Control cabinet Depending on the order, the electronic assemblies are either already in- stalled in a control cabinet or are supplied as individual components for mounting on a cap rail. The following two figures show a design example for the standalone version.

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 25 6796573/02 EN MSENSE® VAM 4.5.2.1 Display elements and operating controls The control cabinet contains the following display elements and operating controls: Figure 5: Display elements and operating controls (example) 1 Indicator lamp H1: yellow = "Anomaly detected" 2 Indicator lamp H2: green = "No anomalies" 3 Service interface

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 26 6796573/02 EN MSENSE® VAM 4.5.2.2 Control cabinet layout The following figure shows an example layout in the control cabinet with the most important electronic assemblies for the MSENSE® VAM. The order- specific details can be found in the connection diagram provided. Figure 6: Control cabinet layout (example) A10 CPU II (central processing unit) A22 VI 4 vibration sensor input module A18 Analog AIO 2 or AIO 4 inputs/out- puts G1 Voltage supply X19 Plug socket F13 Miniature circuit breaker for heat- ing F14 Miniature circuit breaker for control system F25 Residual current circuit breaker plug A19 Digital inputs/outputs DIO 28-15 The functions of the device's individual assemblies are described in the fol- lowing section. You can find more information about these assemblies in the Technical data [►Section 13, Page 161] section.

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 27 6796573/02 EN MSENSE® VAM 4.5.2.2.1 Power supply The G1 PULS DIMENSION QS3.241 assembly supplies power to the de- vice. Figure 7: G1 PULS DIMENSION QS3.241 assembly 4.5.2.2.2 CPU (central processing unit) II The CPU II assembly is the central computing unit for the device. It contains the following interfaces: ▪ Internal system interface RS232 (COM1) ▪ Serial interface RS232/485 (COM2) ▪ 3x Ethernet (ETH 1, ETH 2.1, ETH 2.2) ▪ USB (USB 2.0) ▪ 2x CAN bus (CAN 1, CAN 2) Figure 8: CPU assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 28 6796573/02 EN MSENSE® VAM 4.5.2.2.3 DIO 28-15 digital inputs and outputs The DIO 28-15 assembly makes 28 inputs and 15 outputs (6 N/O contacts, 9 change-over contacts) available. Figure 9: DIO 28-15 assembly Warning of a danger point. Read the information given in the product oper- ating instructions. Warning of dangerous electrical voltage. Table 8: Safety-relevant symbols on the assembly 4.5.2.2.4 Analog inputs and outputs (AIO 2) The AIO 2 assembly provides 2 channels for analog inputs and outputs. In accordance with the device configuration, the AIO assembly supports one of the following signal types: Input Output Voltage Current Voltage Current 0 to 10 V 0...20 mA 4...20 mA 0 to 10 V 0...20 mA 4...20 mA Resistance measurement (e.g. PT100, resistor contact series) Table 9: Signal types supported by the AIO assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 29 6796573/02 EN MSENSE® VAM Figure 10: AIO 2 assembly 4.5.2.2.5 VI 4 vibration sensor input module The VI 4 assembly records the vibration sensor signals via an IEPE inter- face. The abbreviation IEPE refers to an industry standard for piezo-electri- cal sensors (IEPE = Integrated Electronics Piezo Electric). Figure 11: Assembly VI 4 The measured signals are processed with evaluation algorithms.

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 30 6796573/02 EN MSENSE® VAM 4.5.2.2.6 Media converter The MC 2-2 assembly is a media converter, which converts 2 electrical con- nections (RJ45) to one fiber-optic cable connection each. Each is converted independently of the other. The following interfaces are available: ▪ 2x RJ45 (ETH12, ETH22) ▪ 2x Duplex-LC (SFP module) (ETH11, ETH21) The media converter is designed to be transparent for the network and does not have its own IP address. Figure 12: MC 2-2 assembly 4.5.2.2.7 Media converter with managed switch The assembly SW 3-3 is a media converter with managed switch. It com- bines two independent functions and provides you with the following inter- faces: ▪ A media converter converts an electric connection (RJ45) into a fiber-optic cable connection – RJ45 (ETH12) – Duplex-LC (SFP module) (ETH11) ▪ Managed switch with redundancy function (PRP or RSTP) – 2x RJ45 (ETH23, ETH24), device-internal connection – 2x Duplex-LC (SFP module) (ETH21, ETH22), redundancy connection The following redundancy functions are available to you according to your order: ▪ PRP (standard setting) ▪ RSTP

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 31 6796573/02 EN MSENSE® VAM Figure 13: SW 3-3 assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 32 6796573/02 EN MSENSE® VAM 4.6 Main screen The visualization start screen of the MSENSE® VAM monitoring system varies depending on the product version. Their is a difference between the following product versions: ▪ MSENSE® VAM as an integration solution ▪ MSENSE® VAM as a standalone product 4.6.1 MSENSE® VAM as an integration solution Figure 14: Main screen 1 Display area 2 Secondary navigation 3 Primary navigation 4 Status bar Click on the on-load tap-changer in the graphic to enter the overview screen for the vibro-acoustically measured tap-change operations of the on-load tap-changer (OLTC).

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 33 6796573/02 EN MSENSE® VAM 4.6.2 MSENSE® VAM as a standalone version In the standalone version, the last recorded tap-change operation of the on- load tap-changer (OLTC tap-change operation) is displayed directly in the start screen (Home). Figure 15: Start screen Further information on the start screen can be found in the "Visualiza- tion" [►Section 8.1, Page 76] section. 4.7 Operating concept You can operate the device using the controls on the front panel or using the web-based ISM™ Intuitive Control Interface visualization on a PC. The scope of function and structure of both options is virtually identical. User rights and user roles The device is equipped with a rights system and a roles system. The display and access rights to device settings or events can therefore be controlled at the user level. You can configure the rights system and roles system to meet your require- ments. You will find more information on user rights in the User administra- tion section. You can only modify the device settings or parameters if you have the nec- essary user rights. Logging on, logging off and changing users The control of access rights to device settings and parameters is user- based. Various users can log in at the same time (e.g. via the visualization) and access the device.

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 34 6796573/02 EN MSENSE® VAM If you want to operate the device via the controls and visualization at the same time, you have to log in on the device and via the visualization. 1. Select the LOGIN or CHANGE button in the status line. 2. Enter your user name and password and select the OK button. ð The name of the logged-in user appears in the status line. To log out as a user, proceed as follows: ►Press the LOGOUT button in the status line. Navigation If you are operating the device using the controls on the front panel, you can use the rotary knob to navigate through the entire menu. The menu currently selected has a blue border. To open the highlighted menu, you have to press the key. Pressing the key returns you to the previous menu level. If you are operating the device using the web-based visualization, you can navigate by clicking on the appropriate buttons. Example 1. Go to Settings. 2. Go to Parameters. 3. Go to System. 4. Go to Time synchronization. 5. Select Time. In these operating instructions, the path for navigating to a parameter is al- ways shown in an abridged form: Go to Settings > Parameters > System > Time synchronization. Setting parameters There are various ways to configure the settings, depending on the parame- ter.

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 35 6796573/02 EN MSENSE® VAM Selecting from a list To select a list entry, proceed as follows: 1. Use the rotary knob to navigate to the list and press the key. Figure 16: Select an entry from a list 2. Use the rotary knob to highlight the list entry and press the key. 3. Press the Accept button to save the modified parameter. Entering a value To enter a value, proceed as follows: 1. Use the rotary knob to select the value field and press the key. ð If operating via the front panel, the numerical keypad appears. Figure 17: Entering a value 2. Enter the desired value and confirm with . 3. Press the Accept button to save the modified parameter.

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 36 6796573/02 EN MSENSE® VAM Entering text 1. Use the rotary knob to select the text box and press the key. ð If operating via the front panel, the keyboard appears. Figure 18: Entering text 2. Enter the desired text and confirm with . 3. Press the Accept button to save the modified parameter. Parameter search You can use the quick search function in the parameter menu to search for a parameter. Enter the name of the desired parameter in the Search entry field. Figure 19: Quick search

4 Product description

Maschinenfabrik Reinhausen GmbH 2021 37 6796573/02 EN MSENSE® VAM Expert mode The device has an expert mode for entering the parameters. You can enter the parameters directly on the overview screen of the respective menu in this mode. Figure 20: Expert mode 1. Go to Settings > Parameters. 2. Select the Expert mode checkbox. ð Expert mode is active. Hiding/showing parameters Depending on how you set the parameters, the device will hide or show ad- ditional parameters related to this function.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2021 38 6796573/02 EN MSENSE® VAM 5 Packaging, transport and storage 5.1 Packaging The products are sometimes supplied with sealed packaging and sometimes in a dry state, depending on requirements. Sealed packaging surrounds the packaged goods with plastic foil on all sides. Products that have also been dried are identified by a yellow label on the sealed packaging. In the dry state, delivery is also possible in a transport container. The information in the following sections should be applied as appropriate. 5.1.1 Suitability NOTICE Property damage due to incorrectly stacked crates! Stacking the crates incorrectly can lead to damage to the packaged goods. ►The outer marking on the packaging states if, for example, the on-load tap-changer or selector has been packed upright. Never stack these crates. ►General rule: Do not stack crates above a height of 1.5 m. ►For other crates: Only stack up to 2 equally sized crates on top of one an- other. The packaging is suitable to ensure undamaged and fully functional means of transportation in compliance with local transportation laws and regula- tions. The packaged goods are packed in a sturdy crate. This crate ensures that, when in the intended transportation position, the packaged goods are stabi- lized to prevent impermissible changes in position, and that none of the parts touch the loading surface of the means of transport or touch the ground after unloading. Sealed packaging surrounds the packaged goods with plastic foil on all sides. The packaged goods are protected from humidity using a desiccant. The plastic foil was bonded after the desiccant is added.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2021 39 6796573/02 EN MSENSE® VAM 5.1.2 Markings The packaging bears a signature with instructions for safe transport and cor- rect storage. The following symbols apply to the shipment of non-hazardous goods. Adherence to these symbols is mandatory. Protect against moisture Top Fragile Attach lifting gear here Center of mass Table 10: Shipping pictograms 5.2 Transportation, receipt and handling of shipments WARNING Danger of death or severe injury! Danger of death or serious injuries due to tipping or falling load. ►Only transport the crate when closed. ►Do not remove the securing material used in the crate during transport. ►If the product is delivered on a pallet, secure it sufficiently. ►Only trained and authorized persons may select the sling gear and se- cure the load. ►Do not walk under the suspended load. ►Use means of transport and lifting gear with a sufficient carrying capacity in accordance with the weight stated on the delivery slip. In addition to oscillation stress, jolts must also be expected during trans- portation. In order to prevent possible damage, avoid dropping, tipping, knocking over and colliding with the product. If a crate tips over, falls from a certain height (e.g. when slings tear) or is subject to an unbroken fall, damage must be expected regardless of the weight. Every delivered shipment must be checked for the following by the recipient before acceptance (acknowledgment of receipt): ▪ Completeness based on the delivery slip ▪ External damage of any type The checks must take place after unloading when the crate or transport con- tainer can be accessed from all sides.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2021 40 6796573/02 EN MSENSE® VAM Visible damage If external transport damage is found upon receipt of the shipment, proceed as follows: ▪ Immediately record the identified transport damage in the shipping docu- ments and have this countersigned by the carrier. ▪ In the event of severe damage, total loss or high damage costs, immedi- ately notify the manufacturer and the relevant insurance company. ▪ After identifying damage, do not modify the condition of the shipment fur- ther and retain the packaging material until an inspection decision has been made by the transport company or the insurance company. ▪ Record the details of the damage immediately on site together with the carrier involved. This is essential for any claim for damages. ▪ Photograph damage to packaging and packaged goods. This also applies to signs of corrosion on the packaged goods due to moisture inside the packaging (rain, snow, condensation). ▪ NOTICE! Damage to packaged goods due to damaged sealed packag- ing. If the product is delivered in sealed packaging, check the sealed packaging immediately. If the sealed packaging is damaged, do not under any circumstances install or commission the packaged goods. Either re- dry the dried packaged goods as per the operating instructions, or contact the manufacturer to agree on how to proceed. ▪ Identify the damaged parts. Hidden damage When damages are not determined until unpacking after receipt of the ship- ment (hidden damage), proceed as follows: ▪ Make the party responsible for the damage liable as soon as possible by telephone and in writing, and prepare a damage report. ▪ Observe the time periods applicable to such actions in the respective country. Inquire about these in good time. With hidden damage, it is very hard to make the transportation company (or other responsible party) liable. Any insurance claims for such damages can only be successful if relevant provisions are expressly included in the insur- ance terms and conditions. 5.3 Storage of shipments Packaged goods dried by Maschinenfabrik Reinhausen Upon receipt of the shipment, immediately remove the packaged goods dried by Maschinenfabrik Reinhausen from the sealed packaging and store air-tight in dry insulating fluid until used if the packaged goods were not sup- plied in insulating fluid. Non-dried packaged goods Non-dried packaged goods but with a functional sealed packaging can be stored outdoors when the following conditions are complied with.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2021 41 6796573/02 EN MSENSE® VAM When selecting and setting up the storage location, ensure the following: ▪ Protect stored goods against moisture (flooding, water from melting snow and ice), dirt, pests such as rats, mice, termites and so on, and against unauthorized access. ▪ Store the crates on timber beams and planks as a protection against ris- ing damp and for better ventilation. ▪ Ensure sufficient carrying capacity of the ground. ▪ Keep entrance paths free. ▪ Check stored goods at regular intervals. Also take appropriate action after storms, heavy rain or snow and so on. Protect the packaging foil from direct sunlight so that it does not disintegrate under the influence of UV rays, which would cause the packaging to lose its sealing function. If the product is installed more than 6 months after delivery, suitable mea- sures must be taken without delay. The following measures can be used: ▪ Correctly regenerate the drying agent and restore the sealed packaging. ▪ Unpack the packed goods and store in a suitable storage space (well ven- tilated, as dust-free as possible, humidity < 50% where possible). 5.4 Unpacking shipments and checking for transportation damages ▪ NOTICE! Transport the packaged crate to the place where the packaged goods are to be installed. Do not open the sealed packaging until just be- fore installation. Otherwise, damage to the packaged goods may occur due to ineffectively sealed packaging. ▪  WARNING! When unpacking, check the condition of the packaged goods. Place the packaged goods in an upright crate and protect it from tipping out. Otherwise, the packaged goods may become damaged and serious injuries may result. ▪ Check the completeness of the accessories kit using the delivery slip. Attachment points for lifting gear WARNING Danger of death and damage to property! Danger of death and damage to property due to tipping or falling load! ►Only trained and authorized persons may select the sling gear and se- cure the load. ►Do not walk under the suspended load. ►Use means of transport and lifting gear with a sufficient carrying capacity in accordance with the weight stated in the Technical data [►Section 13, Page 161] section.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2021 42 6796573/02 EN MSENSE® VAM ▪  WARNING! Serious injuries and damage to the control cabinet due to falling load. Attach the lifting gear such that the cable angle is always less than 45° in relation to the vertical. Figure 21: Maximum permissible cable angle for the lifting-gear limit stop of the control cabinet ▪  WARNING! Serious injuries due to the control cabinet tipping and damage to the cable gland if the control cabinet is set down, transported or stored upright. Only set down, transport and store the control cabinet on its back. ▪ Only remove the control cabinet from the crane once it has been fully con- nected to the transformer.

Maschinenfabrik Reinhausen GmbH 2021

43 6796573/02 EN MSENSE® VAM 6 Mounting This chapter describes how to correctly mount and connect the device. Note the connection diagrams provided. DANGER Electric shock! Risk of fatal injury due to electrical voltage. Always observe the following safety regulations when working in or on electrical equipment. ►Disconnect the equipment. ►Lock the equipment to prevent an unintentional restart. ►Make sure all poles are de-energized. ►Ground and short-circuit. ►Cover or cordon off adjacent energized parts. NOTICE Damage to the device! Electrostatic discharge may cause damage to the device. ►Take precautionary measures to prevent the build-up of electrostatic charges on work surfaces and personnel. Installing the MSENSE® VAM monitoring system includes the following steps, which are described in the following sections: 1. Depending on the product version selected, install the cap rail modules in the customer control cabinet or in the control cabinet on the transformer. You will find the appropriate description in the "Cap rail module assembly/ control cabinet" [►Section 6.1, Page 43] section. 2. Mounting the vibration sensor [►Section 6.2, Page 50] 3. Connecting the assemblies [►Section 6.3, Page 51] – Connecting the vibration sensor to the control cabinet – Connecting the motor-drive unit controller to the monitoring system – Connecting the temperature sensor – Connecting additional leads – Connecting the power supply After completing the installation, check the functionality [►Section 6.4, Page 66]. 6.1 Installing the Cap rail modules / control cabinet 6.1.1 Installing the cap rail modules With the MSENSE® VAM product version as an integration solution in the customer control cabinet, the cap rail modules must be installed in a suitable control cabinet, taking the EMC standards into consideration. This section does not apply for other product versions.

Maschinenfabrik Reinhausen GmbH 2021

44 6796573/02 EN MSENSE® VAM 6.1.1.1 Minimum distances NOTICE Damage to the device! Insufficient circulation of ambient air can result in damage to the device due to overheating. ►Keep the ventilation slots clear. ►Ensure sufficient distance to neighboring components. ►Only mount device in horizontal position (ventilation slots are at the top and bottom). Reliable operation of the device in the permitted temperature range requires that you maintain the following minimum distances to the control cabinet and to neighboring components: Minimum distance To the floor of the control cabinet 88.9 mm (3.5 in) Corresponds to 2 RU To the roof of the control cabinet Between assemblies on the bus bar and assem- blies on the remote cap rail Table 11: Minimum distances in the control cabinet Figure 22: Example depiction of the minimum distances in a control cabinet For other installation types, contact Maschinenfabrik Reinhausen GmbH. 6.1.1.2 Fastening the cap rail The cap rail is required to mount a bus bar or a device's remote assemblies in a control cabinet. Only use the following types of cap rails in accordance with EN 60715: ▪ TH 35-7.5 ▪ TH 35-15 The cap rail may not be painted or lacquered.

Maschinenfabrik Reinhausen GmbH 2021

45 6796573/02 EN MSENSE® VAM WARNING Electric shock! Risk of fatal injury due to electrical voltage if the cap rail is not connected to the protective ground. ►Connect the cap rail to the protective ground securely (e.g. with a protec- tive conductor line-up terminal). ►Ensure that the cap rail is connected securely to the protective ground via a ground test after installation. ►Fasten the cap rail to the rear panel of the switch cabinet using screws and contact washers or lock washers. The distance between the screws may be no more than 10 cm (3.94 in). Figure 23: Fastening the cap rail 6.1.1.3 Installing the bus rail on the cap rail The bus rail connects assemblies, such as the CPU, DIO and AIO, to each other mechanically and electrically. The bus bar can contain different assem- blies according to your order. ►  WARNING! Mount the bus rail on the cap rail, ensuring that the bus rail engages correctly. Otherwise, it can result in electric shock due to a faulty connection to the protective ground.

Maschinenfabrik Reinhausen GmbH 2021

46 6796573/02 EN MSENSE® VAM Figure 24: Hooking the bus rail into position 6.1.1.4 Installing the assembly at a distance on the cap rail The assemblies VI 4, CPU II and AIO 2/AIO 4 are delivered pre-mounted on the bus rail. The following optional assemblies must be mounted with an off- set on a cap rail: ▪ DIO 28-15 or DIO 42-20 ▪ MC 2-2 ▪ SW 3-3 ▪ G1 (PULS) ü Cap rail fastened to the rear panel of the cabinet [►Section 6.1.1.2, Page 44]. ►  WARNING! A faulty connection to the protective ground can lead to an electric shock in the event of faults. Hook the assembly onto the cap rail at the specified location, ensuring that the assembly engages cor- rectly.

Maschinenfabrik Reinhausen GmbH 2021

47 6796573/02 EN MSENSE® VAM Figure 25: Example: Hooking on DIO and SW assemblies 6.1.2 Integration solution in the ETOS® ED motor-drive unit With this product version, proceed in accordance with the ETOS® ED oper- ating instructions and follow the safety information and warnings they con- tain when mounting the control cabinet on the transformer. Once mounted, continue in accordance with the section "Mounting the vibration sen- sor" [►Section 6.2, Page 50] in these instructions. 6.1.3 Fitting the control cabinet to the transformer This section describes how to mount the control cabinet of the stand-alone version to the transformer. The special design with vibration dampers must be used on transformers where the control cabinet is subject to vibration.

Maschinenfabrik Reinhausen GmbH 2021

48 6796573/02 EN MSENSE® VAM The control cabinet has four fixing attachments on the rear to secure it. To mount the control cabinet on the transformer, proceed as follows: 1. Attach four stud bolts (not supplied by MR) to the transformer tank. Figure 26: Fastening the stud bolts 2. Use the fixing attachments to attach the control cabinet to the stud bolts and align it vertically on the transformer tank. Figure 27: Attaching the control cabinet

Maschinenfabrik Reinhausen GmbH 2021

49 6796573/02 EN MSENSE® VAM 3. NOTICE! Secure the control cabinet without subjecting it to mechanical tension. Otherwise, the control cabinet may be damaged. Figure 28: Fastening the control cabinet 4. Connect the grounding cable to the control cabinet and transformer tank, holding it against the control cabinet using a wrench of size 36. Figure 29: Connecting the grounding cable to the control cabinet

Maschinenfabrik Reinhausen GmbH 2021

50 6796573/02 EN MSENSE® VAM 6.2 Mounting the vibration sensor When selecting the mounting position, ensure that there is the greatest pos- sible clearance to the drive motor, drive shafts and pipelines to reduce the disruptive effect on the vibro-acoustic recording to a minimum. To mount the VAM sensor, proceed as follows: 1. Remove one bolt from the on-load tap-changer cover. Reuse the washer that is present. Figure 30: Removing bolt 2. NOTICE! Incorrect mounting can destroy the vibration sensor. Only apply a tool with wrench size 17 to the lower hexagon of the adapter to attach the sensor assembly. Place the washer over the open tapped hole and screw in the sensor assembly (vibration sensor with adapter and kick guard) with a torque of 34 Nm.

Maschinenfabrik Reinhausen GmbH 2021

51 6796573/02 EN MSENSE® VAM Figure 31: Mounting the vibration sensor 6.3 Connecting the assemblies The following section describes how to establish the electrical connection to the device. WARNING Electric shock! Risk of fatal injury due to connection errors. ►Ground the device using the grounding screw on the housing. 6.3.1 Cable recommendation Please note the following Maschinenfabrik Reinhausen recommendation when wiring the device. Excessive line capacitance can prevent the relay contacts from interrupting the contact current. In control circuits operated with alternating current, take into account the effect of the line capacitance of long control cables on the function of the relay contacts. If you want to route Ethernet connections from a control cabinet or building, we recommend the use of fiber-optic cables (in accordance with the IEC 61850-90-4 recommendation). The sensor cable is included in the scope of delivery and is oil-resistant and UV-resistant.

Maschinenfabrik Reinhausen GmbH 2021

52 6796573/02 EN MSENSE® VAM Use oil-resistant versions for all connection cables outside of control cabi- nets and versions also with additional UV resistance for those outside of buildings. Cable Assembly Cable type Conductor cross-sec- tion Max. length Signal inputs DIO 28-15, DIO 42-20 Shielded 1.5 mm2 400 m (<25 Ω/km) Signal outputs* DIO 28-15, DIO 42-20 Shielded 1.5 mm2 - Signal inputs AIO 2, AIO 4, AIO 8 Shielded 1 mm2 400 m (<25 Ω/km) Signal outputs AIO 2, AIO 4, AIO 8 Shielded 1 mm2 - RS232, SUB-D CPU I, CPU II Shielded 0.25 mm2 25 m RS485; SUB-D CPU I, CPU II Shielded 0.25 mm2 140 m Ethernet RJ45 CPU I Min. CAT5, shielded S/FTP - 100 m Ethernet FO MC 2-2, SW 3-3 Duplex LC Multimode, OM3, 1310 nm - 2000 m Table 12: Recommendation for connection cables *) Observe line capacitance, see note above. 6.3.2 Information about connecting serial interfaces RS232 and RS485 NOTICE Damage to the device! Using the wrong data cable may damage the device. ►Only use data cables which comply with the description below.

Maschinenfabrik Reinhausen GmbH 2021

53 6796573/02 EN MSENSE® VAM RS232 (D-SUB 9-pole) To connect the device via the RS232 interface (COM2), use a data cable with the following structure: Figure 32: RS232 data cable (9-pole)

Maschinenfabrik Reinhausen GmbH 2021

54 6796573/02 EN MSENSE® VAM RS485 (D-SUB 9-pole) To connect the device via the RS485 interface (COM2), use a data cable with the following structure: Figure 33: RS485 data cable D-SUB 9-pole plug connection Only use 9-pole D-SUB plugs with the following characteristics: ▪ Plug housing is metallic or metal-plated ▪ Cable shielding is connected with the plug using one of the two following variants: – Shielding is screwed down with traction relief. – Shielding is soldered with plug housing.

Maschinenfabrik Reinhausen GmbH 2021

55 6796573/02 EN MSENSE® VAM Figure 34: Example of a soldered shielding on a plug housing 6.3.3 Information about connecting analog sensors NOTICE Damage to the device and sensors! Incorrectly connected and configured analog inputs/outputs may result in damage to the device and sensor. ►Follow information about connecting analog sensors [►Section 6.3.3, Page 55]. ►Configure analog inputs and outputs according to the connected sensors. The AIO assembly has a separate plug connector for each channel (input or output). The plugs are assigned as follows: Figure 35: Plug assignment of the AIO module (illustration using module AIO 4 as an example)

Maschinenfabrik Reinhausen GmbH 2021

56 6796573/02 EN MSENSE® VAM Interface Pin Description 1 6 11 16 I OUT (+): Current output + 2 7 12 17 I/U IN (+) U OUT (+): Voltage input +, current input +, voltage output + 3 8 13 18 I/U IN (-): Voltage input -, current in- put - 4 9 14 19 I/U OUT (-): Voltage output -, current output - 5 10 15 20 Not used Table 13: Analog inputs and outputs You can connect the following types of analog sensors: ▪ 4...20 mA ▪ PT100/PT1000 (2-wire, 3-wire, 4-wire) 4...20 mA sensor You must connect a 4...20 mA sensor to the pins and . You must also connect the supplied bridge to the pins , , and . I OUT (+) I/U IN (+) U OUT (+) I/U IN (-) I/U OUT (+) 1 2 3 4 5 --- 4...20 mA signal source Figure 36: Connection example for a 4...20 mA sensor PT100/PT1000 sensor Depending on type, you must connect a PT100 sensor or PT1000 sensor as follows: ▪ 2-wire: pin and ▪ 3-wire: pin , and ▪ 4-wire: pin , , , and

Maschinenfabrik Reinhausen GmbH 2021

57 6796573/02 EN MSENSE® VAM I OUT (+) I/U IN (+) U OUT (+) I/U IN (-) I/U OUT (+) 1 2 3 4 5 --- 2-wire I OUT (+) I/U IN (+) U OUT (+) I/U IN (-) I/U OUT (+) 1 2 3 4 5 --- 3-wire I OUT (+) I/U IN (+) U OUT (+) I/U IN (-) I/U OUT (+) 1 2 3 4 5 --- 4-wire PT100/PT1000 Figure 37: Connection example for a PT100/PT1000 sensor 6.3.4 Electromagnetic compatibility The device has been developed in accordance with applicable EMC stan- dards. The following points must be noted in order to maintain the EMC standards. 6.3.4.1 Wiring requirement of installation site Note the following when selecting the installation site: ▪ The system's overvoltage protection must be effective. ▪ The system's ground connection must comply with all technical regula- tions. ▪ Separate system parts must be joined by a potential equalization. ▪ The device and its wiring must be at least 10 m away from circuit-break- ers, load disconnectors and busbars. 6.3.4.2 Wiring requirement of operating site Note the following when wiring the operating site: ▪ Route the connecting leads in grounded metal cable ducts. ▪ Do not route lines which cause interference (e.g. power lines) and lines susceptible to interference (e.g. signal lines) in the same cable duct. ▪ Maintain a distance of more than 100 mm between lines which cause in- terference and those which are susceptible to interference.

Maschinenfabrik Reinhausen GmbH 2021

58 6796573/02 EN MSENSE® VAM Figure 38: Recommended wiring 1 Cable duct for lines causing inter- ference 3 Cable duct for lines susceptible to interference 2 Line causing interference (e.g. power line) 4 Line susceptible to interference (e.g. signal line) ▪ Short-circuit and ground reserve lines. ▪ Never connect the device with a multi-wire collective pipe. ▪ For signal transmission, use shielded lines with individual conductors (out- going conductor / return conductor) twisted in pairs. ▪ Connect full surface of shielding (360º) to device or to a nearby grounding bar. Using single conductors may limit the effectiveness of the shielding. Con- nect close-fitting shielding to cover all areas.

Maschinenfabrik Reinhausen GmbH 2021

59 6796573/02 EN MSENSE® VAM Figure 39: Recommended connection of the shielding 1 Connection of the shielding via a single conductor 2 Full-surface connection of the shielding 6.3.4.3 Wiring requirement in control cabinet Note the following when wiring the control cabinet: ▪ The control cabinet where the device will be installed must be prepared in accordance with EMC requirements: – Functional division of control cabinet (physical separation) – Constant potential equalization (all metal parts are joined) – Line routing in accordance with EMC requirements (separation of lines which cause interference and those susceptible to interference) – Optimum shielding (metal housing) – Overvoltage protection (lightning protection) – Collective grounding (main grounding rail) – Cable bushings in accordance with EMC requirements – Any contactor coils present must be interconnected ▪ The device's connection cables must be laid in close contact with the grounded metal housing or in metallic cable ducts with a ground connec- tion. ▪ Signal lines and power lines/switching lines must be laid in separate cable ducts.

Maschinenfabrik Reinhausen GmbH 2021

60 6796573/02 EN MSENSE® VAM 6.3.4.4 Information about screening the cables for analog signals In order to correctly record the analog signals, you must place the cable screening in the motor-drive unit on the grounding bar. The cable shielding should be removed as late as possible before connecting to keep the section with unshielded cables as short as possible. The shielding must be con- nected with shielding clips. Figure 40: Examples of supporting screening on ground bar (on left: Direct connection to AIO assembly, on right: Connection using line-up terminal) 6.3.5 Information about laying fiber-optic cable To ensure the smooth transfer of data via the fiber-optic cable, you must en- sure that mechanical loads are avoided when laying the fiber-optic cable and later on during operation. Also observe the information from the manufac- turer of the fiber-optic cable and the following instructions: ▪ Radii must not fall below the minimum permissible bend radii (do not bend fiber-optic cable). ▪ The fiber-optic cables must not be over-stretched or crushed. Observe the permissible load values. ▪ The fiber-optic cables must not be twisted. ▪ Be aware of sharp edges because they can damage the fiber-optic cable's coating during laying or can place mechanical loads on the coating later on. ▪ Provide a sufficient cable reserve near distributor cabinets. Lay the re- serve such that the fiber-optic cable is neither bent nor twisted when tight- ened.

Maschinenfabrik Reinhausen GmbH 2021

61 6796573/02 EN MSENSE® VAM 6.3.6 Connecting the vibration sensor to the control cabinet Depending on the application, one or more vibration sensors are included in the scope of delivery. Repeat the following steps for a multi-column applica- tion. You must connect the vibration sensor to the control cabinet using the sen- sor cable provided. Note the following information when routing the sensor cable: ▪ Route the sensor cable with as much shielding as possible on the trans- former (e.g. in the tube or cable duct) and along a conductive grounded surface that runs without interruption. ▪ Route sensor cables separately from supply lines and do not create any unnecessary loops. ▪ The vibration sensor cable can also be routed together with the tempera- ture sensor cable in a protective tube. ▪ On the control cabinet, it is advantageous to have routing parallel to the earthing cable that connects the transformer and the control cabinet to- gether. To route the sensor cable, proceed as follows: 1. Remove the vibration sensor cover cap. Figure 41: Vibration sensor cover cap 2. Ensure that the sensor cable plug and the socket on the sensor are dry and free of dirt. If this is not the case, clean and dry them with a cloth.

Maschinenfabrik Reinhausen GmbH 2021

62 6796573/02 EN MSENSE® VAM 3. Plug in the sensor cable plug and screw it in by hand. Figure 42: Plugging in the sensor cable 4. Route the sensor cable on the transformer to the control cabinet with shielding to prevent mechanical damage and interference.

Maschinenfabrik Reinhausen GmbH 2021

63 6796573/02 EN MSENSE® VAM 5. Shorten the sensor cable to the desired length. Loops or coil windings of an excessive length are not permitted when routing the cable. Figure 43: Sensor cable routing 1 Temperature sensor cable 2 Control cabinet 3 Vibration sensor cable 4 Transformer 5 On-load tap-changer head cover If the control cabinet is farther away, extend the sensor cable with a shielded cable in the motor drive cabinet or in a metal intermediate terminal box. Follow the information in the Cable recommendation [►Section 6.3.1, Page 51] section and implement continuous shielding.

Maschinenfabrik Reinhausen GmbH 2021

64 6796573/02 EN MSENSE® VAM For the control cabinet connection, proceed as follows: 1. Connect the sensor cable shield to the grounding bar in the control cabi- net using a shielded clamp. When doing so, only expose the cable shield as much as is necessary for the shielded clamp. Figure 44: Sensor cable shield connection Tighten the cable screw connections on the control cabinet with the follow- ing tightening torques: M20: 8 Nm, M32: 20 Nm. 2. Connect the sensor cable in accordance with the connection diagram pro- vided (blue = signal, brown = signal ground, black = ground in control cab- inet). 6.3.7 Connecting the motor-drive unit controller to the monitoring system To synchronize the vibro-acoustic signals with the tap position change, it is necessary to measure the diverter switch operation in the motor-drive con- troller. With the integration solution in the motor-drive unit, this connection is already made at the factory. With the "standalone" and "integration solution in the customer control cabi- net" versions, you must make this connection yourself. To do so, connect the position transmitter module of the motor-drive unit to the DIO assembly of the vibro-acoustic monitoring system in accordance with the connection dia- gram provided. 6.3.8 Connecting the temperature sensor Depending on the application, one or more temperature sensors are in- cluded in the scope of delivery. When making the connection, follow the con- nection diagram on the associated dimensional drawing. Make the connec- tion to the control cabinet in accordance with the connection diagram pro- vided for the monitoring system.

Maschinenfabrik Reinhausen GmbH 2021

65 6796573/02 EN MSENSE® VAM 6.3.9 Connecting additional leads (optional) Connect additional leads as necessary in accordance with the connection di- agram: ▪ Digital inputs and outputs ▪ Control system ▪ Visualization Routing information for connecting the control system or visualization When connecting the device to a control system or to your network for ac- cessing the visualization, observe the following recommendation on the ca- ble routing in the control cabinet: Figure 45: Recommendation on the cable routing in the control cabinet for the connection of the control system or visualization 6.3.10 Connecting the power supply You may only connect the control cabinet to circuits with an external over- current protection device and an isolating device with all poles disconnected so the equipment can be fully de-energized if required (service, maintenance etc.).

Maschinenfabrik Reinhausen GmbH 2021

66 6796573/02 EN MSENSE® VAM Suitable equipment includes isolating devices in accordance with IEC 60947-1 and IEC 60947-3 (e.g. circuit breaker). Note the properties of the relevant circuits (voltage, maximum currents) when selecting the circuit breaker type. In addition, observe the following: ▪ It must be easy for the operator to access the isolating device ▪ The isolating device must be labeled for the device and circuits to be iso- lated ▪ The isolating device may not be a part of the power line ▪ The isolating device may not interrupt the main protective conductor You must connect the power supply circuit with a conductor cross-section of at least 2.5 mm2 (AWG 13) and protect it with a C6A or B6A type miniature circuit breaker. To connect the voltage supply, proceed as follows: ►Connect the power supply of the control cabinet to terminal X1 in accor- dance with the connection diagram provided. 6.4 Checking functional reliability To ensure that the device is wired correctly, check its functionality. NOTICE Damage to device and system periphery! An incorrectly connected device can lead to damage to the device and sys- tem periphery. ►Check the entire configuration before commissioning. To check the functionality, proceed as follows: ►Apply voltage to the control cabinet. ð The device's control system boots up; after a brief period, the relay switches the operating contact STATUS OK (DIO 28-15:1B). The device is fully mounted and can be configured. The actions required for this are described in the following chapter.

Maschinenfabrik Reinhausen GmbH 2021

67 6796573/02 EN MSENSE® VAM 7 Commissioning 7.1 Visualization The MSENSE® VAM monitoring system is equipped with web-based visual- ization. This enables you to configure the device with a computer and to dis- play measured values. Overview of Ethernet interfaces: MSENSE® VAM product version ETH 1.1 ETH 2.1 ETH 2.2 Standalone version in the control cabinet Yes No Optional Integration solution in the ETOS® TD motor- drive unit Yes No Optional Integration solution in the ETOS® ED motor- drive unit without display No Yes Optional Integration solution in the ETOS® ED motor- drive unit with display Yes No Optional Integration solution in the customer control cabinet (ETOS® IM, pluggable modules) No Yes Optional Establishing a connection for visualization via the ETH 1.1 front interface 1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the ETH 1.1 interface. This interface is directly accessible after opening the control cabinet door. Depending on the product version, there are two op- tions: Figure 46: MSENSE® VAM standalone front interface

Maschinenfabrik Reinhausen GmbH 2021

68 6796573/02 EN MSENSE® VAM Figure 47: ETOS® ED front interface 2. Assign a unique IP address to the PC in the same subnet as the device (e.g. 192.168.165.100). 3. Enter the visualization's IP address http://192.168.165.1, or if SSL encryption is active enter https://192.168.165.1, in the browser on the PC. ð The visualization is accessed. Establishing a connection for visualization via the ETH 2.1 or ETH 2.2 interface You can use the ETH 2.1 interface or the optional ETH 2.2 interface of the CPU assembly to establish the connection to the visualization. The inter- faces do not use a DHCP server. Therefore, you must assign a static IP ad- dress to your PC. To do this, observe the following configuration example: Interface Configuration Standard ETH 2.1 IP address: 192.168.165.1 (not adjustable) PC IP address: 192.168.165.100 Subnet mask: 255.255.255.0 Optional ETH 2.2 IP address: 192.0.1.230 (factory setting) [►Section 8.7.2, Page 97] Subnet mask: 255.255.255.0 PC IP address: 192.0.1.100 Subnet mask: 255.255.255.0 Table 14: Interface configuration example

Maschinenfabrik Reinhausen GmbH 2021

69 6796573/02 EN MSENSE® VAM 1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the ETH 2.1 or ETH 2.2 interface. Figure 48: CPU interface ETH 2.1 or ETH 2.2 2. Assign a unique IP address to the PC in the same subnet as the device (e.g. ETH 2.1: 192.168.165.100). 3. Enter the IP address of the visualization (e.g. ETH 2.1: http://192.168.165.1; if SSL encryption is active, enter https://192.168.165.1) in the browser on the PC. ð The visualization is accessed. 7.2 Commissioning wizard If you want the device to help when setting the relevant parameters, you can use the commissioning wizard. The commissioning wizard provides a selec- tion of parameters that you can configure in order. A detailed description of each of the parameters can be found in the Opera- tion [►Section 8, Page 76] chapter. To call up the commissioning wizard, you will need the necessary access rights. When in delivery status, you can log in as the administrator as follows: ▪ User name: admin ▪ Password: admin

Maschinenfabrik Reinhausen GmbH 2021

70 6796573/02 EN MSENSE® VAM To set the parameters with the help of the commissioning wizard, proceed as follows: 1. Log in as a user with the necessary access rights. 2. Go to Settings > Commissioning wizard. Figure 49: Calling up the commissioning wizard 3. Press the Next button to launch the commissioning wizard. 4. Follow the on-screen instructions. Once you have entered all of the parameters relevant to commissioning, continue with the function test. 7.3 Setting the language You can use this parameter to set the display language for the device. The device comes with a maximum of four languages. The following languages are available: English Italian* German Portuguese* French* Russian* Spanish* Chinese* Korean* Polish* *) Language is available as an option (upon request) To set the language, proceed as follows: 1. Select the Language button in the status bar, or as an alternative go to Settings > General > Language. Figure 50: Setting the language 2. Select the desired language from the list box.

Maschinenfabrik Reinhausen GmbH 2021

71 6796573/02 EN MSENSE® VAM 3. Press the Accept button to save the modified parameter. ð The "Restart device" dialog appears. 4. Restart the device to apply the changed language setting. 7.4 Setting date and time You can set the date and time in the following ways: ▪ Manually ▪ Time synchronization via control system (SCADA) ▪ Time synchronization via SNTP time server If you are using a control system, the device automatically synchronizes the date and time with the control system. If you would like to use an SNTP time server, you must set the required parameters. For more information, refer to the information in the section Setting the de- vice time [►Section 8.7.3, Page 97]. 7.5 Name plate You can enter the data of the nameplates from the transformer, on-load tap- changer and motor-drive unit and display it later. When operating ETOS® with the MSENSE® VAM option, you must enter the correct serial number for every on-load tap-changer. This entry is neces- sary to ensure the correct assignment of the vibro-acoustic records in the external database. 7.5.1 Enter the name plate data You can enter the name plate data for the transformer, the on-load tap- changer and the motor-drive unit. Figure 51: Nameplate

Maschinenfabrik Reinhausen GmbH 2021

72 6796573/02 EN MSENSE® VAM 1. Go to Settings > Parameters > System > Nameplate. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. 7.5.2 Displaying the name plate You can display the nameplate data for the transformer, on-load tap- changer, and motor-drive unit. Figure 52: Transformer nameplate ►Go to Information > System > Nameplate > Transformer/On-load tap- changer/Motor-drive unit. 7.6 Setting the control system protocol (optional) If you need a control system protocol, you must set the parameters required for this. More information on this (e.g. data points) is to be found in the pro- vided supplement for the control system protocol. You do not need to set additional parameters for commissioning. 7.7 Performing tests Please contact Maschinenfabrik Reinhausen GmbH (MR) if any aspect of the tests is not clear.

Maschinenfabrik Reinhausen GmbH 2021

73 6796573/02 EN MSENSE® VAM 7.7.1 Checking measured values and status of digital inputs and outputs Upon commissioning the device, check whether the measured values and status of digital inputs and outputs are plausible. To do so, use an additional measuring device if necessary in order to check the individual measured val- ues. To display the status of the digital inputs and outputs, proceed as follows: 1. Go to Information > Hardware. 2. Select the individual assemblies one after another and check the individ- ual measured values or the status of digital inputs and outputs. 3. If errors arise, check the measurement path and the wiring. 7.7.2 Performing function tests To ensure that the monitoring system functions seamlessly, you have to check the communication with the sensor and the automatic triggering func- tion after each installation or maintenance action as follows: 1. Check that the wiring of the sensor and the signal feedback is in accor- dance with the supplied circuit diagram. 2. Perform a few on-load tap-changes for all positions and in both directions and check the plausibility of the signal progression including the envelope curve in the monitoring system. 3. Check that the signals are being recorded and saved correctly. 4. Optional: Check the control system. ð The monitoring system is ready to function. 7.7.3 Electrical high-voltage tests on the transformer It is essential that you ensure only trained, instructed expert personnel who are familiar with and comply with the pertinent safety and technical regula- tions, who are aware of the potential risks, and who consistently use the oc- cupational safety equipment provided to prevent injury and property damage are assigned to perform such a transformer test. Note the following points before performing high voltage tests on the trans- former: ▪ Check that the ground connections on the control cabinet and the control cabinet fixings are free of paint. ▪ Only perform a high voltage test with the control cabinet door closed. ▪ Disconnect the sensor cable and other external connections to electronic components in the control cabinet to prevent damage through overvolt- age. ▪ When connecting the control cabinet's supply voltage, only use the bush- ings in the protective housing base intended for lead insertion. ▪ Guide all ground connecting leads to one central connection point (estab- lishment of suitable reference earth).

Maschinenfabrik Reinhausen GmbH 2021

74 6796573/02 EN MSENSE® VAM ▪ Disconnect all electronic components before the high voltage test. Before a dielectric test of the wiring, remove all devices with a withstand voltage of < 1000 V. ▪ Remove leads used for testing before the high voltage test, because these function as antennas. ▪ Wherever possible, route the measurement leads and data leads sepa- rately to the energy cables. 7.7.4 Ground test For commissioning, carry out a ground test (check of the impedance of the protective bonding) in accordance with IEC 61010-1. Note the following in- formation: ▪ Test current: 2 times the measurement current of the overcurrent protec- tion device of the supply line. ▪ Test duration: 1 minute for each measurement point. ▪ The measured voltage between the measurement point and the protective conductor must be smaller than 10 V. Proceed as follows to carry out the ground test: 1. Feed the test current at the fixing screw of assembly DIO 28-15 or DIO 42-20 using a constant current source and measure the voltage between the measurement point and the protective conductor. ð The measured voltage must remain less than 10 V over a duration of 1 minute. Figure 53: Perform a ground test on the DIO assembly (sample representation of the DIO 28-15 assembly).

Maschinenfabrik Reinhausen GmbH 2021

75 6796573/02 EN MSENSE® VAM 2. Feed the test current at the grounding terminal of the G1 PULS DIMEN- SION QS3.241 assembly using a constant current source and measure the voltage between the measurement point and the protective conductor. ð The measured voltage must remain less than 10 V over a duration of 1 minute. Figure 54: Perform a ground test on the G1 PULS DIMENSION QS3.241 assembly 7.7.5 Dielectric tests on transformer wiring Note the following points for dielectric testson the transformer wiring: The monitoring system has been put through dielectric tests before delivery. ►Before the dielectric test for the transformer wiring, disconnect the moni- toring system from the section to be tested to rule out increased compo- nent loading for those components fitted in the control cabinet.

Maschinenfabrik Reinhausen GmbH 2021

76 6796573/02 EN MSENSE® VAM 8 Operation This chapter describes all the functions and setting options for the device. 8.1 Visualization The integration solution and the standalone version have different start screens. The figure shows the start screen of the integration solution. Figure 55: Start screen of the integration solution 1 Display area 2 Secondary navigation 3 Primary navigation 4 Status bar Primary navigation The primary navigation on the right edge of the screen is always structured the same way, regardless of the product version. The buttons of the primary navigation have the following functions: Button Function Home Switch to the start screen Events Switch to the display of events detected Information Switch to the display of information on: ▪ Installed hardware ▪ OLTC ▪ Tap-change operation statistics ▪ OLTC oil temperature curve ▪ VAM analysis

Maschinenfabrik Reinhausen GmbH 2021

77 6796573/02 EN MSENSE® VAM Button Function Recorder Switch to the display of statistics for tap position and oil temperature Settings Switch to the settings menu With the integration solution, clicking on the on-load tap-changer on the start screen accesses the overview screen for the vibro-acoustically recorded tap- change operations of the on-load tap-changer (OLTC tap-change opera- tions). Standalone version start screen On the start screen of the standalone version, the vibro-acoustic signal pro- gression of the last recorded and evaluated on-load tap-changer operation is shown in blue. Clicking on the Home button always returns you to this screen. Once the recording of a tap-change operation is complete, the calculation and evaluation is performed. With complex switching sequences and a high switching frequency, it may take a few minutes before the latest tap-change operation is displayed. Figure 56: Standalone version start screen The upper curve in yellow indicates the self-learned limit value. In addition, the corresponding properties of the tap-change operation are shown: ▪ Type of OLTC tap-change operation (e.g. reverse tap-change operation) ▪ Start and end position of the tap-change ▪ Date and time of the tap-change operation ▪ Oil temperature of the on-load tap-changer ▪ Number of OLTC tap-change operations registered until now ▪ Status display with the following color code:

Maschinenfabrik Reinhausen GmbH 2021

78 6796573/02 EN MSENSE® VAM Color code Definition Blue No anomalies: Plausibility criteria met and limit values not exceeded Yellow Limit value was exceeded Gray The evaluation could not be carried out Remark: With the integration solution, you will go to the same view if you display the most recent recorded tap-change operations in the Information menu. 8.2 User administration User administration is based on a system of roles. You must assign a role to every user. You can define access rights to parameters and events for each role. The access rights depend on the product version [►Section 4.1, Page 20] and the associated scope of supply. 8.2.1 User roles The access rights to device functions and settings are controlled using a hi- erarchical system of roles. The system has 5 different roles with different ac- cess rights. Some of these access rights are fixed, but you can configure the access rights to particular parameters and events. Note the Setting access rights to parameters and events [►Section 8.2.4, Page 82] section. If you are not logged in on the device, you will assume the "Data display" user role. Upon delivery, the following roles are provided: Role Description Data display User who can only view data of relevance to operation. ▪ Display all parameters ▪ Display all events Diagnostics User who can view data and log data of relevance to oper- ation. ▪ Display all parameters ▪ Display all events ▪ Export log data Operator User who can view data of relevance to operation and ac- knowledge events. The user can perform manual tap- change operations using the device's controls. ▪ Display all parameters ▪ Display and acknowledge all events

Maschinenfabrik Reinhausen GmbH 2021

79 6796573/02 EN MSENSE® VAM Role Description Parameter configura- tor User who can view and modify data of relevance to opera- tion. ▪ Display and modify all parameters ▪ Import and export parameters ▪ Display, modify, and acknowledge all events Administrator User who can view and modify all data. ▪ Read all parameters ▪ Display, modify, and acknowledge all events Table 15: Roles in delivery status Access to the following areas of the device is linked to the roles: Function Data display Diagnostics Operator Parameter configurator Administrator Administration - - - - + Restart device - - + + + Import - - - + + Export - + - + + Set date and time - - + + + Calling up the commissioning wizard - - - + + Calibrate resistor contact se- ries - - - + + Actuation of the RAISE, LOWER, REMOTE, AVR AUTO, and AVR MANUAL keys - - + + + Setting topology - - - + + Configuring analog inputs and outputs - - - + + Configuring digital inputs and outputs - - - + + Setting TPLE - - - + + Configuring data points - - - + + Calling up the maintenance wizard - - - + + Changing tap position table - - - + + Enabling ECOTAP Modbus - - - + + Adding sensors to the MR sensor bus - - - + + Table 16: Access rights permanently linked to the roles

Maschinenfabrik Reinhausen GmbH 2021

80 6796573/02 EN MSENSE® VAM 8.2.2 Changing the password All users can change their passwords provided that the user account is not set up as a group account. You can only change a group account's pass- word if you are logged in as the administrator. Note that the password must satisfy the following requirements: ▪ At least eight characters ▪ At least three of the four following character types – Upper case letters – Lower case letters – Numbers – Special characters To change the password, proceed as follows: 1. Select the user name in the status line. Figure 57: Changing the password 2. Enter the new password twice. 3. Press the Accept button to save the changed password. 8.2.3 Creating, editing and deleting users You can set the following options for all users: ▪ Username and password ▪ Role: You can assign a role to every user. The access rights to parame- ters and events are linked to the roles. ▪ Group account: With this option, you can declare a user account to be a group account (e.g. for access by different people). Users with a group ac- count cannot change their own password. The password can only be changed by the administrator.

Maschinenfabrik Reinhausen GmbH 2021

81 6796573/02 EN MSENSE® VAM ▪ Active: You can activate or deactivate the user. Deactivated users cannot log in. The user data is still stored in the device. ▪ Auto login: You can activate the Auto-login function for a user. This user is automatically logged in when the system is restarted or another user logs out. Figure 58: Overview of users created You can only create, edit, and delete users if you are assigned an adminis- trator role. When in delivery status, you can log in as the administrator as follows: ▪ User name: admin ▪ Password: admin Creating users To create a new user, proceed as follows: 1. Go to Settings > Administration > User. 2. Press the Create user button. 3. Enter the user name once and the password twice. 4. Select the role you want. 5. If necessary activate the Group account, Active or Auto login options. 6. Press the Accept button to save the user. Editing users To edit an existing user, proceed as follows: 1. Go to Settings > Administration > User. 2. Select the desired user in the list. 3. Make the amendments desired.

Maschinenfabrik Reinhausen GmbH 2021

82 6796573/02 EN MSENSE® VAM 4. Press the Accept button to save the user. Deleting user To delete an existing user, proceed as follows: 1. Go to Settings > Administration > User. 2. Select the desired user in the list. 3. Press the Delete user button. 4. Press the Accept button to delete the user. 8.2.4 Setting access rights to parameters and events You can configure access rights to parameters and events for the available roles. The following options are available for this purpose: ▪ Read: Parameter/event may be displayed. ▪ Write: Parameter/event may be modified. ▪ Acknowledge: Event may be acknowledged. Figure 59: Setting access rights for an event You can only change access rights if you are assigned an administrator role. When in delivery status, you can log in as the administrator as follows: ▪ User name: admin ▪ Password: admin To set the access rights to parameters and events, proceed as follows: 1. Go to Settings > Administration > Parameters/events. ð A list of all parameters or events appears. 2. Select the desired entry in the list.

Maschinenfabrik Reinhausen GmbH 2021

83 6796573/02 EN MSENSE® VAM 3. Select the options you want. 4. Press the Accept button to save the change. 8.3 Events menu The device is equipped with event management, which allows you to detect various device operating statuses and to adapt the behavior of the device. With the MSENSE® VAM monitoring system, only yellow and gray events occur. A list of the events with explanations and handling recommendations can be found in the "Event messages" [►Section 10.2, Page 157] section. To display the events currently active, proceed as follows: ►Go to Events. ð A list of currently pending events appears. Figure 60: Events menu The events are numbered consecutively. A short description and a time stamp for each one follows. Acknowledging events Acknowledgeable events must be acknowledged in the event overview so that they are no longer displayed. All other events are automatically removed once the cause is remedied (e.g. limit value no longer exceeded). To acknowledge the events, proceed as follows: ►To acknowledge the events, highlight the desired events in the  col- umn, then press the Acknowledge button. ð The events have been acknowledged.

Maschinenfabrik Reinhausen GmbH 2021

84 6796573/02 EN MSENSE® VAM Displaying event memory Past events are stored in the event memory. The following information is dis- played: Column Description # Consecutive number of events No. Event number for clear identification Event category: ▪ Warning (yellow) ▪ Info (gray) Event Event text Time Date and time of event (DD-MM-YYYY, HH:MM:SS/ms) Event coming/going: Event coming Event going Table 17: Event memory To call up the event memory, proceed as follows: 1. Go to Events. 2. Press the Log button. Figure 61: Event history

Maschinenfabrik Reinhausen GmbH 2021

85 6796573/02 EN MSENSE® VAM Detailed description of the events By double-clicking on an event, you can call up the detailed description and find a handling recommendation to fix the problem. Figure 62: Event description You will find the details on the properties of the events and a description of how you can configure this in the chapter "Menu settings > Events" [►Sec- tion 8.8, Page 127]. Filtering events To adjust the display, you can define a filter. To do so, proceed as follows: 1. Press the Filter button. 2. Enter the desired time period. 3. Select the checkbox and enter the desired event number. ð The event text is displayed. 4. Select the desired event categories and the desired event status. ð Press the Search button to display the desired events.

Maschinenfabrik Reinhausen GmbH 2021

86 6796573/02 EN MSENSE® VAM Figure 63: Events list filter function Exporting events You can export the event memory entries currently displayed as a csv file. If you first create a filter, only the filtered entries are exported. To export the events, proceed as follows: ü First connect using Connect PC or connect a storage medium to the USB port on the CPU I module. 1. Press the Export button. 2. Select the desired option for data transmission (PC or USB). ð The data is exported. Figure 64: Export events list

Maschinenfabrik Reinhausen GmbH 2021

87 6796573/02 EN MSENSE® VAM 8.4 Information menu The Information menu has the following selection options: Figure 65: Information menu ▪ Hardware: Overview of the available hardware modules and the signals present. ▪ Software: Serial number and versions of the software used. ▪ OLTC: Information on the on-load tap-changer. ▪ Tap-change operation statistics: Information on the frequency of the on- load tap-changer operations. ▪ Temperatures: Temperature of the transformer. ▪ VAM analysis: Analyzed vibro-acoustic measurements of the on-load tap- changer. Menu Information > VAM analysis: For every tap-change operation listed, you will receive the following informa- tion: ▪ Tap-change operation type ▪ Start position and end position of the tap-change operation. ▪ Time of the tap-change operation ▪ Status

Maschinenfabrik Reinhausen GmbH 2021

88 6796573/02 EN MSENSE® VAM Figure 66: VAM analysis Tap-change operation type The monitoring system distinguishes between the following types of tap- change operations: ▪ Change-over selector operation: The change-over selector also changes in this tap-change operation. ▪ Small tap change: Tap selector operation in which the distance between the stationary selector contacts used for this tap-change operation is small. ▪ Moderate tap change: Tap selector operation in which the distance be- tween the attached selector contacts used for this tap-change operation is moderate. ▪ Large tap change: Tap selector operation in which the distance between the attached selector contacts used for this tap-change operation is large. ▪ Reverse tap-change operation: Tap-change operation in which the tap changes in the opposite direction to the most recent tap-change operation and does not involve actuation of the selector. Status information Color code Definition Blue No anomalies: Plausibility criteria met and limit values not exceeded Yellow Limit value was exceeded Gray The evaluation could not be carried out

Maschinenfabrik Reinhausen GmbH 2021

89 6796573/02 EN MSENSE® VAM Filter options Using the drop-down menu, you can limit the selection of tap-change opera- tions to those of a specific tap-change operation type or to those involving a specific property. ▪ Selection according to tap-change operation type: – Change-over selector operation – Small, medium or large tap change – Reverse tap-change operation ▪ Selection according to property: – All – Marked – Evaluation ok – Anomalies – Without evaluation Display of selected tap-change operations To display individual tap-change operations with the associated VAM signal and the stored limit value as a curve, proceed as follows: 1. Place a check mark in the first column in front of the tap-change op- eration that is to be displayed as a curve. Up to 100 tap-change opera- tions can be shown in the visualization via web browser. A maximum of 10 tap-change operations can be shown on the device display. 2. Confirm via the Display button. ð They will be displayed differently depending on the number of selected tap-change operations. If more than one tap-change operation is selected, then the limit value curve display will be omitted for clarity purposes: Number of selected tap-change operations 1 2-100 >100 Display of VAM signal Yes Yes No Display of limit value curve Yes No No

Maschinenfabrik Reinhausen GmbH 2021

90 6796573/02 EN MSENSE® VAM The following figure shows an example of the visualization of an individual tap-change operation: Figure 67: Display of a tap-change operation The following figure shows an example of how multiple selected tap-change operations are shown at the same time: Figure 68: Display of multiple tap-change operations If multiple tap-change operations are selected for the visualization, it is pos- sible to hide or show individual tap-change operations by clicking on them in the key. Using the web-based ISM™ Intuitive Control visualization allows you to zoom into an area of the signal. To do this, hold down the left mouse button and draw a frame around the desired area. To return to the original repre- sentation, click on the symbol.

Maschinenfabrik Reinhausen GmbH 2021

91 6796573/02 EN MSENSE® VAM 8.5 Recorder menu Use the "Information" [►Section 8.4, Page 87] menu to compare the vibro- acoustic signals of several tap-change operations, enabling you to see the changes. With the standalone version, you can use the measured value recorder func- tion to display the temporal progression of the oil temperature, and with the integration solution, you can use this function to display the temporal pro- gression of additional measured values and signals. If you call up the measured value recorder directly on the device display, you can select a maximum of 3 measured values. If you access it via the web visualization, you can select a maximum of 10 measured values. To display the measured value recorder on the device display, proceed as follows: 1. Go to Recorder. Figure 69: Recorder 2. Select the signals to be displayed in the list. 3. If necessary, set the desired axis for each signal. 4. Enter the start time and the end time for the measured value display.

Maschinenfabrik Reinhausen GmbH 2021

92 6796573/02 EN MSENSE® VAM 5. Press Display to call up the measured value display (data log). Figure 70: Measured value display The operation described below is only possible if you access the visualiza- tion using a computer. 6. Move the mouse indicator to a measurement point for more information. 7. Use the mouse to produce a selection window or turn the mouse wheel to zoom into or out of the diagram. If necessary, you can move an enlarged diagram with the right mouse button. 8. Select the button to save the displayed measured values as a csv file.

Maschinenfabrik Reinhausen GmbH 2021

93 6796573/02 EN MSENSE® VAM Trend curves If you call up the measured value recorder using a PC, you can display a trend curve instead of the measured values. The trend curve can, for exam- ple, be a moving average over a configurable time period. Figure 71: Setting trend curves 1. Call up the measurement recorder and the desired measured value se- ries. 2. Press the Trend button. 3. Select the desired measured values. 4. Select the desired trend function. 5. Entire the desired time period for the calculation of the trend curve. 6. Press the Accept button to display the trend curves. ð The trend curve is displayed. Measured values that are displayed as trend curves are marked with the symbol. Figure 72: Trend curve display

Maschinenfabrik Reinhausen GmbH 2021

94 6796573/02 EN MSENSE® VAM 8.6 Settings menu You have the following selection options in this menu: ▪ Parameters: Functions and settings of the device. ▪ Events: Overview of all available events for the device. ▪ Configure DIO: Configuration of the digital inputs and outputs (DIOs). ▪ Configure AIO: Configuration of the analog inputs and outputs (AIOs). ▪ Tap-change operation table: Reference of the tap-change operation designations. ▪ Reset VAM: Reset the self-learned statistics of the vibro-acoustic signals. ▪ Commissioning wizard: Support when setting up the relevant parame- ters. These are separated into three groups: general, time synchroniza- tion, IEC 61850. ▪ TPLE: With the TPLE (TAPCON® Personal Logical Editor) function, you can link inputs and outputs with one another via function modules. ▪ Import: Import data via a USB or a PC. ▪ Export: Export data via a USB or a PC. ▪ Administration: You can use this menu to change user administration settings. As an administrator, you can view and adjust the rights of se- lected users. 8.7 Menu Settings > Parameters The parameters are divided into four groups. You will find more information directly via the link: 1. System – General [►Section 8.7.1, Page 95] – Configuring the network [►Section 8.7.2, Page 97] – Time synchronization [►Section 8.7.3, Page 97] – Syslog [►Section 8.7.4, Page 100] – Screensaver [►Section 8.7.5, Page 101] – Configuring IEC 61850 (optional) [►Section 8.7.11.1, Page 106] – Configuring IEC 60870-5-101 (optional) [►Section 8.7.11.2, Page 108] – Configuring IEC 60870-5-103 (optional) [►Section 8.7.11.3, Page 111] – Configuring IEC 60870-5-104 (optional) [►Section 8.7.11.4, Page 114] – Configuring Modbus (optional) [►Section 8.7.11.5, Page 116] – Configuring DNP3 (optional) [►Section 8.7.11.6, Page 118] – Configuring data points (optional) [►Section 8.7.11.7, Page 120] – Linking digital outputs [►Section 8.7.6, Page 101] – Linking messages [►Section 8.7.6, Page 101] – Linking functions [►Section 8.7.7, Page 103]

Maschinenfabrik Reinhausen GmbH 2021

95 6796573/02 EN MSENSE® VAM 2. Active part – Temperature monitoring [►Section 8.7.8, Page 104] 3. On-load tap-changer – OLTC data [►Section 8.7.9, Page 105] 4. Power grid – Tap position monitoring [►Section 8.7.10, Page 105] 8.7.1 Menu Settings > Parameters > General In this menu, you can make general settings and prepare the settings for web-based visualization: Settings Parameters General Name Value Language English Commissioning wizard Yes Auto-logout Off Time until auto-logout 15.0 min Measured value display Primary values Transformer name Transformer Remote behavior Hardware and SCADA USB interface Off Service user access activation Activated SNMP Agent Off Home Events Information Recorder Settings EN CHANGE REBOOT admin 14.04.2020 14:22 Figure 73: General General settings ▪ Language – With this setting, you can specify the device display language. – The display language can also be set via the status bar [►Section 7.3, Page 70] ▪ Commissioning wizard – Information on how to set whether the commissioning wizard starts up once the device is restarted is available here [►Page 96]. ▪ Auto-logout – You can use this to set whether a user is to be logged out automatically in the event of a long period of inactivity. ▪ Transformer name – Enter the transformer name for identification. ▪ Remote behavior – Information on how to set the remote behavior is available here [►Sec- tion 8.7.1.1, Page 96].

Maschinenfabrik Reinhausen GmbH 2021

96 6796573/02 EN MSENSE® VAM ▪ USB interface – Here, you can activate/deactivate the USB interface [►Section 8.7.1.2, Page 96]. Settings for web-based visualization ▪ IP address ▪ Subnet mask ▪ Gateway address ▪ SSL encryption ▪ TLS version Commissioning wizard You can use this parameter to set whether the commissioning wizard is to launch automatically when the device is restarted. 8.7.1.1 Remote behavior You can use this parameter to select the behavior of the device in remote operating mode. You can select the following options: Option Description Hardware only The device accepts commands via digital inputs. SCADA only The device accepts commands via SCADA. Hardware and SCADA The device accepts commands via digital inputs and SCADA. Table 18: Selecting remote behavior To set the remote behavior, proceed as follows: 1. Go to Settings > Parameters > General > Remote behavior. 2. Select the desired option. 3. Press the Accept button to save the modified parameter. 8.7.1.2 Activating/deactivating the USB interface You can use this parameter to deactivate the USB interface. You can select the following options: ▪ On: USB interface is activated ▪ Off: USB interface is deactivated Proceed as follows to activate/deactivate the USB interface: 1. Go to Settings > Parameters > General > USB interface. 2. Select the desired option. 3. Press the Accept button to save the modified parameter.

Maschinenfabrik Reinhausen GmbH 2021

97 6796573/02 EN MSENSE® VAM 8.7.2 Configuring the network You can configure the ETH 1 and ETH 2.2 network interfaces of the CPU as- sembly in this menu item. You can only set the parameters for ETH 1 if the device is equipped with the optional control system connection via Ethernet (TCP/IP): ▪ IEC 61850 ▪ IEC 60870-5-104 ▪ Modbus (Modbus type TCP active) ▪ DNP3 (DNP3 transmission type TCP active) You can only set the parameters for ETH 2.2 if the device is equipped with the optional interface for visualization. Figure 74: Network settings 1. Go to Settings > Parameters > System > Network settings. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. 8.7.3 Time synchronization You can set the the device time manually or automatically via an SNTP time server. The device must be connected to an SNTP time server via Ethernet for this purpose. You can set the following parameters: ▪ Time synchronization via SNTP ▪ Activate second time server (optional) ▪ SNTP time server (for the first and second SNTP time servers) ▪ Synchronization interval ▪ Time zone

Maschinenfabrik Reinhausen GmbH 2021

98 6796573/02 EN MSENSE® VAM ▪ Automatic daylight saving / standard time ▪ Time (manual setting) Figure 75: Setting time synchronization The following sections describe how you can set these parameters. 8.7.3.1 Activating time synchronization using SNTP You can use this parameter to activate time synchronization using an SNTP time server. To activate time synchronization using SNTP, proceed as follows: 1. Go to Settings > Parameters > Time synchronization > Time synchro- nization via SNTP. 2. Select the option you want. 3. Press the Accept button to save the modified parameter. Second time server (optional) As an option, you can use a second time server, e.g. should the first one fail. When you activate the second time server, the device synchronizes the time with the second time server if a connection cannot be established with the first time server. If the device is able to re-establish the connection to the first time server, it automatically synchronizes the time with the first time server again. You can only use the second time server if you have activated the Time synchronization via SNTP parameter and entered an IP address for the first time server. To activate the second time server, proceed as follows: 1. Go to Settings > Parameters > Time synchronization > Activate sec- ond time server. 2. Select the option you want.

Maschinenfabrik Reinhausen GmbH 2021

99 6796573/02 EN MSENSE® VAM 3. Press the Accept button to save the modified parameter. 8.7.3.2 Entering the time server address This parameter lets you enter the IP address of a SNTP time server. If you are using a time server, the device uses the time of the time server as the system time. Be sure to enter a valid time server address that is not 0.0.0.0, otherwise it will not be possible to connect to the device. To enter the time server address of the SNTP server, proceed as follows: 1. Go to Settings > Parameters > Time synchronization > SNTP time server. 2. Enter time server address. 3. Press the Accept button to save the modified parameter. Entering time server address of second time server (optional) You can use this parameter to enter the IP address of the second time server as an option. To enter the time server address of the second SNTP server, proceed as fol- lows: 1. Go to Settings > Parameters > Time synchronization > SNTP time server 2. 2. Enter time server address. 3. Press the Accept button to save the modified parameter. 8.7.3.3 Setting the time zone If the time information is conveyed to the device by a network service (SNTP or SCADA), this time is transferred depending on the set reference time. To adjust the device time to your local time, you can use the time shift parame- ter to set the time shift to UTC. Example: Region Time shift to UTC Mumbai, India UTC +5:30 h Beijing, China UTC +8:00 h Brasilia, Brazil UTC -3:00 h Table 19: Time shift to UTC (Coordinated Universal Time) To set the time zone, proceed as follows: 1. Go to Settings > Parameters > Time synchronization > Time zone. 2. Select the option you want.

Maschinenfabrik Reinhausen GmbH 2021

100 6796573/02 EN MSENSE® VAM 3. Press the Accept button to save the modified parameter. 8.7.3.4 Setting synchronization interval You can use this parameter to set the interval at which the device is to call up the time from the time server. To set the synchronization interval, proceed as follows: 1. Go to Settings > Parameters > Time synchronization > Synchroniza- tion interval. 2. Enter synchronization interval. 3. Press the Accept button to save the modified parameter. 8.7.3.5 Setting the date and time manually You can use the Time parameter to set the date and time. To do so, proceed as follows: 1. Go to Settings > Parameters > Time synchronization > Time. 2. Enter the date and time. 3. Press the Accept button to save the modified parameter. 8.7.4 Configuring syslog The device supports the transmission of log messages via the syslog proto- col in accordance with the standards RFC 5424 and RFC 3164. Figure 76: Syslog 1. Go to Settings > Parameters > System > Syslog. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter.

Other Control Systems Manuals